Propped Beam PB07
TIMBER PROPPED BEAM V5.02 Demo User

Beam: (Propped Beam PB07) 240mm x 45mm F17 KD HW


Bending: M(dl)* = 3.36kNm < øM(dl) = 8.79kNm, M* = 6.45kNm < øM = 12.34kNm OK (0.38,0.52)
Shear: V(dl)* = 3.62kN < øV(dl) = 12.56kN, V* = 7.04kN < øV = 17.63kN OK (0.29,0.40)
Deflection: δdl = L/489 (7mm), δll = L/573 (6mm) OK
Tip: δdl = Lc/163 (-6mm), δll = Lc/215 (-5mm) OK
Reactions: Left Rdl = 0.8kN, Rll = 3.5kN, R* = 6.2kN, Right Rdl = 1.4kN, Rll = 5.5kN, R* = 10.0kN

Geometry (For a primary building member)

Category = 2 (1) House, (2) Primary building elements, (3) Important

Span (L) = 3600 mm Cantilever (Lc) = 1000 mm


Centres (cts) = 450 mm Edge restrained = C (T)ension, (C)omp.
Lay = 600 mm (Downward)
Loadings

Live Load type = Floor AS/NZS 1170.0 - Table 4.1


Long term LL (Ψl) = 0.20
Uniform dead loads
Floor dead load (wdl) = 0.40 kPa * 450 mm + kN/m = 0.18 kN/m
Wall dead load (wdl) = 0.50 kPa * 450 mm + kN/m = 0.23 kN/m
Other dead load (wdl) = kPa * mm + kN/m = 0.00 kN/m
Include S.Wt = Y (Y)es,(N)o S.Wt = 0.07 kN/m
Σwdl = 0.48 kN/m
Uniform live loads
Floor live load (wdl) = 3.00 kPa * 450 mm + kN/m = 1.35 kN/m
Partitions (wll) = 0.50 kPa * 450 mm + kN/m = 0.23 kN/m
Σwll = 1.58 kN/m
Point loads
Dead load (pdl) = kN Position = 1800 mm from LHS, (T)ip of cantilever
Live load (pll) = 1.80 kN (Load in span L)

Long term LL factor (Ψl) = 0.40 (Ψlp) = 0.60


w(dl+Ψl.ll)* = 1.35*(wdl+Ψl*wll) = 1.49 kN/m M(dl+Ψl.ll)+* = 3.36 kNm at 1800mm
w* = 1.2*wdl+1.5*wll = 2.93 kN/m M(dl+Ψl.ll)-* = 0.75 kNm
p(dl+Ψl.ll)* = 1.35*(pdl+Ψlp*pll) = 1.46 kN M+* = 6.45 kNm at 1800mm
p* = 1.2*pdl+1.5*pll = 2.70 kN M-* = 1.47 kNm
V(dl+Ψl.ll)*= 3.62 kN
V* = 7.04 kN
Bending and Shear Capacity - Cl 3.2.1 & Cl 3.2.5

Member = 240mm x 45mm F17 KD HW Area (A) = 10800 mm²


Description = F17k seasoned hardwood Section modulus (Zx) = 432 x10³ mm³
Design depth (dD) = 240 mm Stiffness (Ix) = 51.8 x10⁶ mm⁴
Design width (dW) = 45 mm Modulus of elasticity (E) = 14000 MPa - Table H2.1

S1=1.25*dD/dW*(Lay/dD)⁰·⁵ = 10.54 For comp. edge restrained - Cl 3.2.3.2


k12 = 1.000 for ρb*S < 10 - Cl 3.2.4 f'b = 42.0 MPa
Strength reduction factor (ø) = 0.85 Table 2.1 f's = 3.6 MPa
øM(dl) = ø*(k1=0.57)*k4*k6*k9*k12*f'b*Zx = 8.79 kNm Material constant (ρb) = 0.92 (rb=0.81)
øM = ø*k1*k4*k6*k9*k12*f'b*Zx = 12.34 kNm Duration factor (k1) = 0.80
Moisture factor (k4) = 1.00
øV(dl) = ø*(k1=0.57)*k4*k6*f's*(2/3*A) = 12.56 kN Temp. factor (k6) = 1.00
øV = ø*k1*k4*k6*f's*(2/3*A) = 17.63 kN Sharing factor (k9) = 1.00
Size modifer (mod.b) = 1.00
Deflections Size modifer (mod.s) = 1.00

Ireq'd DL (span/300) = 31.8 x10⁶ mm⁴ < Critical j2 = 2.0


Ireq'd LL (12mm max) = 27.1 x10⁶ mm⁴

Between supports at 1800mm from LHS (approx. max) Tip of cantilever


δDL = 7.4 mm (down) Span / 489 δDL = -6.1 mm (up) Span / 163
δLL = 6.3 mm (down) Span / 573 δLL = -4.7 mm (up) Span / 215

Deflection Limits

Service class = N (1),(2),(3),(S)evere/Adverse,(N)ot applicable

δDL lim. = Span/ 300 = 12mm or 16 mm DL lim. = 12 mm


δLL lim. = Span/ 300 = 12mm or 12 mm LL lim. = 12 mm

Tip of cantilever
δDL lim. = Cant./ 150 = 7mm or 16 mm DL lim. = 7 mm
δLL lim. = Cant./ 150 = 7mm or 12 mm LL lim. = 7 mm
Notes:
Double members:
Double members are not considered laminated.
Refer to AS1684.2 Cl 2.3 for requirements of
vertical lamination.
Laminated = Y (Y)es,(N)o

Max. deflection between supports must


be manually determined - refer below.

Importance:
Category 1 House failure affecting < 25m², secondary building element
Category 2 Building, house failure affecting > 25m²
Category 3 Important

Double spans:
Moment taken critical at internal support.
Dead load descriptions:
Title =
Title =
Title =

Live load description:


Title =
Title = Partitions

Point load description:


Title =

Alternative Point Live Loads:


Alternative point live load is to be manually assessed.

Duration:
Storage and passage durations used
are based on intermediate durations from Table 2.3
and used with engineering judgement.
k4 factor:
Partial seasoning factor
Refer Cl 2.4.2.2 & 2.4.2.3 for more information.

k6 factor:
Refer Cl 2.4.3 if designing structures near coastal
regions of Queensland north of 25°S and all other
regions north of 16°S

Material constant:
Refer to Appendix E2
Load ratio = 0.81

Dead load deflection:


Dead Load in calculations includes the
portion of permanent live load (Ψl) as noted
in clause 2.4.1.2 Note 1 and AS1170.2 Table 4.1

Maximum deflection between supports:


Approx. pos = 1.800 m from LHS
Position = 1.800 m from LHS

Service class:
Service class defined in AS/NZS 1328.1 1998 Glued Laminated Structural Timber
1 - Domestic houses, Commerical Offices
2 - Open sheds, exposed beams under soffits, porches, laundries
3 - Marine structures, Bridges
S - Severe/Adverse requires specialist advice