Motor starter for USA and Canada

Special considerations governing the


application of Manual Motor Controllers
and Motor Starters in North America

Technical Paper
Dipl.-Ing. Wolfgang Esser,
Dipl.-Ing. Dirk Meyer
Fourth, supplemented edition 2016
4th, supplemented edition 2016
Wolfgang Esser, Dipl.-Ing.

Dipl.-Ing. Dirk Meyer


Manager Special Applications
Eaton Experience Center EMEA
Electrical Sector
Eaton Industries GmbH, Bonn

With grateful acknowledgement


of the support from:

Mr. Andre R. Fortin, BA Phys

and

Mr. Dieter Reiß, Dipl.-Ing.


Manager- Product Certifications
Institute for International Product Safety GmbH, Bonn

2
Overview of contents and Foreword

Special considerations governing the application of Manual Motor Controllers and


Motor Starters in North America

 Page
Recommendations on navigating through this comprehensive technical paper 4
Quick overview and summary of contents 4
Special considerations governing the application of manual motor controllers and motor starters in North America 5
Product certification requirements in North America 5
Influence of specifiers and users of certified electrical equipment 6
Requirements of various sales channels for certified electrical equipment 7
Electrical equipment groupings in North America 8
Manual Motor Controller or Circuit Breaker? 8
North American electrical ratings for Industrial Control Equipment 9
Equipment approvals conducted by electrical inspectors 9
Group installations per NEC, Article 430-53 and CEC Part 1, Rule 28-206 („Group Protection“)11
• Consequences of group installation requirements on motor branch circuit conductor sizing 12
Examples of popular components and combinations in Motor Branch Circuits 14
Additional items worthy of consideration with respect to enclosed equipment. 14
Basic concepts related to electrical products on the North American market 14
• Motor contactors for the North American market 14
– Combination „Contactor + Overload Relay“ (Non-combination Motor starter)14
• Manual motor controllers for the North American market 15
– Manual Motor Controller (Starter) PKZ15
– “Motor protective switch” NZM…-ME…-NA, “Motor protective circuit breaker”. 15
• Molded Case Circuit Breakers for the North American market 15
– NZM...-S(E)-CNA Instantaneous Trip circuit breakers  18
– NZM…-A(V)(E)(F)…-NA Inverse Time molded case circuit breakers  19
– Advantages of circuit breakers over fuses in North American motor branch circuits 19
• Manually operated disconnect switches in motor circuits 20
Motor Starters in accordance with North American specifications 21
• Combination Motor Starters 21
Various constructive solutions for „Combination Motor Starters“22
UL 508 Type E Self-protected Combination Motor Controller
• 22
Self-Protected Combination Starter MSC-...-...-M...-SP
• 23
• PKZM0-..+BK25/3-PKZ0-E Manual Type E Self-Protected Combination Controller 23
+ For applications in the US
+ For applications in Canada
• UL 508 Type F Combination Starter24
Tap Conductor Protector 25
Summary of Figure 12 (next page) 25
Validity25
References25
Figure 12, North American motor starter constructions  26
Useful Tables 28

3
Recommendations on navigating through this
comprehensive technical paper

Readers who are pressed for time and segments can vary significantly with for industrial machinery, i.e. one for
wish to take a quicker road at finding respect to their proper application. North America and the other for the
possible answers to their questions are The basis for much of the IEC, since the general structural layout
encouraged to skip ahead to the misunderstanding is rooted in the of both panels afforded by these
section entitled “Various constructive North American practice of requiring components can now become more or
solutions for Combination Motor separate upstream branch circuit less the same, if not totally identical.
Starters”, indicated in bold in the protective devices to be installed ahead The use of fuseless equipment can be
Index of Contents. of motor starter equipment (such as especially advantageous for export
manual motor controllers per IEC/EN assemblies since the procurement of
Readers who would like to seek a standards) normally certified under the North American fuses locally in Europe
better understanding of why they need UL 508 and CSA-C22.2 No.14-05 can sometimes be problematic, and
to adopt these solutions for export to industrial control standards. As a rule, certain fuse classes can mean an
North America are encouraged to North American product standards for increase in overall panel size
consult the segments under the protective devices, such as UL 489 and requirements.
introductory sections (not in bold in the CSA-C22.2 No. 5-09, require
Index of Contents) primarily dealing significantly larger air and creepage The paper clearly highlights that the
with: clearances on incoming terminations general topic of product certification
than standard industrial control and regulatory approval is rather
• the main features of the North equipment. complex. It is in a constant state of flux
American electrical safety system and changes must be monitored
• the differing characteristics of Machine manufacturers and panel closely and diligently. There are many
„Energy Distribution“ and „Industrial builders who export and wish to details of critical importance to a user
Control“ electrical equipment. standardize on one solution for which only the manufacturer would be
• general knowledge on North machinery and its associated electrical in a position to know. Eaton Electric
American electrical equipment and equipment may well consider the has the specialists in place who can
assemblies following list of fuseless „Combination keep you abreast of developments and
• the differing requirements of motor Motor Controllers Starters“ as the provide you with the necessary
starter constructions most viable option, and one which engineering and design help, as well as
finds equal acceptance in the IEC localized support and start-up
This technical paper is directed towards world: assistance directly in North America.
planners, project engineers, panel You can put your trust in the
builders and users who are involved • UL 508 Type E Self-Protected experience we have accumulated over
with the application of electrical Combination Motor Controller decades of involvement in the North
equipment in North America, primarily – Self-Protected Combination American market place; certification of
from an export perspective. A detailed Controllers (Starters) electrical equipment and assemblies
description of the equipment – Manual Self-Protected Combination has always been an Eaton specialty.
certification process and a discussion Motor Controllers (Starters)
of specific component design details Eaton Industries GmbH, Bonn
were purposely omitted. In spite of its • UL 508 Type F Combination Motor
breadth, the paper deals mostly with Controllers (Starters)
specific component related aspects of
manual motor controllers and motor In such cases, however, it is necessary
starters commonly encountered in the to keep in mind that North American
North American market. engineering requirements related to
Comprehensive project design of North the equipment, including the use of
American engineered assemblies will North American wiring materials and
require additional and specific conductor color specifications, would
knowledge to that effect. have to be followed. Figure 12 at the
end of the paper details the
Quick overview and summary of constructional composition of various
contents: motor starter design solutions and their
suitability to meet application
The paper sheds light into differing requirements.
construction and application aspects of
motor starter equipment which exist The fuseless based solutions
between market places in North mentioned above should make it much
America and the IEC world. Identical or easier to reduce the need for two
similar terms used in both market distinct versions of electrical equipment

4
Special considerations governing the application
of manual motor controllers and motor starters in
North America
Differing product standards and market and marketed by various control gear standards are still not yet fully
customs in both Europe (IEC- manufacturers, generally share a similar harmonized.
Guidelines)1 and North America (NEC2 / construction and have been
CEC)3 can often lead to frustrating successfully applied by the millions Product certification requirements in
delays and/or costly and extensive world-wide. It’s interesting to note in North America
alterations of European engineered this respect that there is a very
assemblies exported to North America established market for IEC based In the US, equipment approvals and
(e.g. control panels for industrial products in North America, particularly listings are mandated by the
machinery). Conversely, there are only in the machine tool industrial sector governmental agency OSHA4 and the
minor differences within North America and the export of engineered NEC, which require third party
between relevant US and Canadian assemblies back to the European certification5 or “listing” of electrical
based standards which cover such continent. European products and products and engineered assemblies
installations. These slight deviations control panel design engineering by independent and nationally
will be discussed further in later philosophies have thus become well recognized testing laboratories (NRTL)5,
sections. This paper will attempt to established throughout North America. e.g. UL6. In Canada, all electrical
point out differing viewpoints between Still, there is a feeling that many equipment must comply with the CEC,
both major markets, and hopefully technical innovations originating out of and CSA certification7 is a legally
assist in preventing misunderstandings, Europe remain generally unknown in binding requirement for all electrical
irritating delays and costly reparations North America, and that this perception products and assemblies.
which may otherwise occur in projects is not necessarily rooted in the lack of
involving the export of electrical certification for these newer product Equipment listings in North America are
equipment. We remain in constant designs. Rather, it may have more to closely associated to third party
touch with the activities of key do with the absence of a suitable North certification marks which must appear
certification agencies and with our American product standard which on products to validate this claim.
Eaton colleagues in North America, would allow recently introduced Components which have been
who always keep us abreast of the innovations and technological successfully tested to applicable product
latest developments in this regard. breakthroughs to take full advantage of standards will therefore be affixed with
their application possibilities, as is the an appropriate laboratory stamp or mark.
The term „Motor Starter“, commonly case in the EU. However, conformity (Table 1). In the US and Canada,
used in North America for many years, with internationally based standards, as cataloging of certified products used to
has also now been adopted in Germany well as knowledge derived from years be published solely in book form. Today,
to a large extent, albeit with a of positive field experiences, simply this type of information is made largely
somewhat differing interpretation. The don’t add up to much in terms of available through the internet8 through
introduction of the IEC / EN 60947-4-1 verifying compliance with local North the use of on-line directories from the
[1] standard years ago was mostly American electrical Code requirements. certification agencies.
responsible for popularizing the term in Would it thus be proper to conclude
Europe on a broader basis. Among that we are indirectly dealing with the As a result of relaxed trade restrictions
many motor starter related topics, this imposition of North American trade brought about by the NAFTA-
standard concerns itself with the restrictions meant specifically to Agreement9 it is now possible for
co-ordination and performance of exclude European goods in favor of clients to obtain product certifications
components such as contactors, functionally equivalent, but from either UL or CSA which have
overload relay and manual motor dimensionally larger, North American legitimacy in both countries. The
controllers under the effects of short products? We see things in a more equipment would then bear a
circuit currents. These concepts have positive light and consider the certification label from each agency
in the meantime been incorporated into availability of the UL 60947-4-1A [2]
the relatively recent set of North standard as a true sign of a more
American harmonized standards, UL globally harmonized future. That base 4 OSHA = Occupational Safety and Health Act
(http://www.osha.gov)
60947-4-1A [2] in the US, and CSA- number, not coincidentally, is well 5 NRTL = Nationally Recognized Testing Labora-
C22.2 No. 60947-4-1-07 [3] in Canada. established throughout European and tories
international communities and relates 6 UL = Underwriter‘s Laboratories (http://www.
ul.com)
Motor starters designed in accordance to the family of design and product 7 CSA = Canadian Standards Association (http://
with international and European performance standards for low voltage www.csagroup.org)
standards (excluding North America), electrical equipment. The international 8 Access to UL database = http://database.
ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/
standard for motor starters is assigned index.html,
a similar number even though the Access to CSA database =
1 IEC = International Electro-Technical Commis- performance requirements of motor http://www.csagroup.org/
sion 9 NFTA = North American Free Trade Agreement
2 NEC = National Electrical Code starters in both IEC and NA based http://www.csagroup.org/services/testing-and-
3 CEC = Canadian Electrical Code certification/certified-product-listing/

5
with appropriately distinctive markings. requirements of all major global involves the establishment of two or
Eaton has, up to this point, made markets and can therefore be even possibly three different versions
relatively little use of this dual country successfully applied world wide. of the same product. Circuit Breakers
marking option from a single (Examples of these include are a good example. These products
certification agency, simply because contactors, overload relays, are sometimes subject to certain
many local inspectors and end-users pushbuttons and pilot devices, i.e. modifications when certified to North
appear reluctant to accept them. components for which the IEC based American product standards and are
design can be certified as is to North correspondingly identified with the
Eaton Germany has adopted two American standards and bear the suffix „-NA“ or „-CNA“. These North
product related solutions with respect appropriate North American American versions then become part
to product certification requirements: certification marks). of the follow-up reexamination
testing requirements imposed by the
• Eaton refers to a component as a • In cases where North American and North American certification
„World Market device“ whenever international requirements cannot be agencies. From a design point of
the requirements of both North unified under one design, or when view, these devices are only slightly
American and international standards production volume of components is different from their IEC counterparts,
are satisfied by the same product strictly monitored by third party and in some cases are identical.
design. A World Market device authorities and subject to additional
signifies that the product in question inspection costs, the necessary As highlighted in Table 2, UL in the US
is in compliance with the certification course of action for Eaton usually differentiates between „Listed
Equipment“ and „Recognized
Equipment“. This also applies to
Industrial Control equipment. Each type
Type suffix is identified with respective markings
added to the on products.
part number Type of Certification Certification marks
Influence of specifiers and users of
-NA The device is fully UL listed or CSA
certified electrical equipment
certified as a stand-alone component.
In Europe, people are familiar with
-CNA The device is component recognized
so-called installation standards, such as
by UL and its proper application is
subject to additional Conditions of IEC / EN 60 204-1 [5] (Electrical
Acceptability. (COAs). The device is apparatus for machinery), which include
CSA certified and its proper many application based requirements
application may also be subject to that place greater emphasis on overall
similar constraints from Canadian control panel engineering rather than
based Codes and Standards. just a simple component selection
process. The responsibility for
Table 1: Eaton makes use of both types of UL component certifications and compliance and conformity with the
­correspondingly identifies each classification with part number suffixes. Refer also to standard, therefore, goes beyond the
Table 2. CSA does not use separate marks to differentiate component certification in purview of the component
the same manner as UL does, but the application of recognized products in Canada
manufacturer and extends to design
may be subject to similar constraints and conditions.
engineers, panel builders, contractors
and users alike.
Listed Industrial Control Equipment Component Recognized Industrial
Control Equipment Application based The same situation applies in North
No restrictions in terms of application on conditions of acceptability America, and closely ties in to the
equipment certification process. A type
• Devices listed for „field wiring“ • As components, products are
PKZM0 manual motor controller, as a
• „factory wiring“ is covered by suitable for „factory wiring“ only
„field wiring“ provisions stand-alone component, is UL listed
and CSA-certified. That is certainly an
- Listed devices are suitable for control - Component selection is conducted important part of the picture, but not
panels when used per the guidelines by trained personnel and subject to the only criteria for a successful and
of the industrial control panel Conditions of Acceptability proper application of the product per
standard (UL 508A). - For use in control panels; designed, North American codes and standards.
- Listed devices are not subject to wired and tested by technically Millions of IEC design based manual
additional conditions of acceptability. trained personnel in certified
factories and panel shops. motor controllers have been
successfully applied globally over
decades, yet these identical controllers
Certification Marks: Certification Marks: are simply not allowed to be used in
North America under the same
performance guidelines. For example,
their base certification only allows
them the ability to switch motors
Table 2: In the US, industrial control equipment falling under UL 508 could be certified
as „Listed Industrial Control Equipment„ or „Recognized Component Industrial Control directly across-the-line, and to provide
Equipment”. Other NRTLs do not differentiate in the same way with their certification motor starting and running overload
marks. protection. This is an important point to

6
always keep in mind. It is Eaton’s
intent, therefore, to insure that Electrical Equipment Groupings in North America
products are not only certified, but that Energy distribution components Motor control components
they are also being applied properly, (Distribution Equipment) (Industrial Control Equipment)
and in accordance with the installation
guidelines established by the local UL 508, UL 60947-1, UL 60947-4-
e.g. UL 489, UL 98, UL 248 and
North American electrical codes. 1(A), and CSA-C22.2 No.14-05,
CSA-C22.2 No. 5-09, CSA-C22.2
CSA-C22.2 No.60947-1-07, CSA-
No. 5-04, CSA-C22.2 No. 248,
Requirements of various sales C22.2 No.60947-4-1-07
channels for certified electrical • Molded Case Circuit Breakers (UL 489) • Magnetic controllers (contactors)
equipment • Molded Case Switches (UL 489) • Control Relays
• Enclosed and Dead-Front Switches • Overload Relays
Eaton Germany considers the following (UL 98)
• Manual Motor Controllers (protectors)
sales channels to be its primary outlets • Fusible Disconnect Switches (UL 98)
for certified components and • Rotary Cam Switches
• Fuses (UL 248)
assemblies: • Pushbuttons and Pilot Devices
UL:CSA equivalent standards:
• Solid State controls and systems
UL 98 : CSA-C22.2 No. 4
• D
irect sales in North America • Programmable Controllers1)
UL 248: CSA-C22.2 No. 248
–– For applications in North Special requirements: Special requirements:
America
• These devices need to be particularly • These components are smaller in size
robust in their construction and have and electrical clearances are not as
Component certification is a must in
larger electrical clearances than indus- large as those of energy distribution
this case. Even then, certified IEC
trial control equipment: equipment.
based equipment in many instances
(e.g. for 301...600 V: 1 Inch through • Industrial control devices are installed
provides a local buyer with, at best, a
air, 2 Inches over surface in the area of primarily in control panels, in motor
compromise if their preference is for field terminations).
traditional NEMA10 products and branch and associated load circuits, in
• Lower permissible temperature rise. Motor Control Centers (MCC) and also
design philosophies. That has made
• Product construction generally larger as components in some energy distri-
the sale of IEC based equipment
than IEC equivalent. bution assemblies.
harder to achieve, although it now
stands to make significant progress • Incoming and outgoing power cir- • They can be combined in the same cir-
due to the strength and presence of cuit components for energy distribu- cuit as energy distribution equipment
Eaton. On the other hand, there are a tion assemblies (Switchgear, Switch- in control panels, e.g. with a circuit
number of applications for which boards, Panelboards) must conform to breaker used as a main disconnect and
smaller physical dimensions, and a these standards. protective switch in a motor branch cir-
fuseless, or almost fuseless, design • Main disconnect and protective cuit.
approach, provide Eaton with switches used in industrial control • Factory production is also monitored
excellent opportunities to showcase assemblies must also conform to by the certification agencies, but not
its products. These applications these standards. to the same extent as applies to circuit
provide an additional benefit from the • Safety testing for these products breakers.
point of view that much of what is maintain strict standards and factory • Generally speaking, more compatible
learned from local field experience production quality is closely monitored with conventional IEC-designs.
can be fed back directly into the by inspectors from each certification
design department in Germany, and agency.
thus positively influence current and • UL/CSA Molded Case Circuit Breaker
future product developments for the testing standards are amongst the
North American market. most stringent in the industry world-
wide.
–– For export out of North America • Quarterly and extensive re-examination
testing as a function of production.
The overwhelming requirement in
global export applications calls for 1) in Canada per CSA-C22.2 No. 142-M1987, as of 2012 per CSA-C22.2 No. E61131-2.
IEC based electrical equipment
designs and the overall smaller Table 3: Differences in North American product grouping based on construction and
certification requirements in product standards, e.g. UL 489 [6] and CSA C22.2 No.5-09
dimensional space these [7] for circuit breakers and UL 508 and CSA C22.2 No.14-05 [8] for industrial control
components will provide. That’s equipment.
especially the case whenever
electrical equipment needs to
conform to IEC based engineered market. However, for obvious also bear the CE-Mark11, particularly
assembly standards. Equipment reasons, there is a definite tendency when they are subject for export to
certified to North American standards on the part of North American the European market.
is of very little significance to this exporters to seek and standardize on
equipment that conforms to both
North American and IEC standards.
11 CE = Conformite Europeenne. This mark allows
10 NEMA = National Electrical Manufacturer’s It’s advantageous for business products and equipment free access to markets
Association (www.nema.org) purposes too that Eaton components within the European Common Market.

7
• The export of electrical equipment primarily located closer to the load the term “Circuit Breakers” to describe
to North America from IEC- (industrial control equipment). Please them, in spite of their relatively smaller
countries refer to Table 3. These two groupings nominal current ratings.
are subject to different product
The indirect export sector has historically certification standards, which entail a
been more significant commercially than varying level of testing requirements The term „Motor Protective Switch“ is
going through direct sales channels in and performance criteria. It’s crucial to actually not spelled out quite that way
North America. The focus for Eaton keep these two groupings in mind in the IEC product standards. However,
Europe is mainly on machinery and its since they will often be referenced in all understand the device to be a 3
associated electrical controls, which this paper. They provide important phase, manually operated protective
typically are built in Germany or in the insights in properly understanding the switch rated for nominal currents up to
rest of Europe. This explains in part why differences between products such as 63A, that has been optimized for the
the support provided by Eaton Electric to manual motor controllers and circuit protection of electric motors. According
the machinery and panel assembly breakers with respect to their to international classifications it belongs
sector is so intensive. Exporting machine evaluation and application per the North in the grouping of „current sensitive,
manufacturers would ideally like to build American standards. Both product thermally delayed (inverse time)
(series production) machinery with an categories will be frequently referred to overcurrent protective devices“. This
identical electrical control scheme that in the ensuing text. norm recognizes overload relays (with
would be suitable world-wide, or, if that’s relay output circuitry) or overload
not possible, end up with an electrical Manual Motor Controller or Circuit tripping elements, which are
control panel layout for North America Breaker? functionally designed to interact directly
that only differs slightly from the IEC with the switching mechanism of a
model to account for specialized North The term „Motor Protective Switch“ protective switch and open its main
American electrical code requirements. (“Motorschutzschalter” in German) power contacts. These main contacts
Machinery buyers in North America are was coined by Kloeckner-Moeller many can also be used to switch motors
generally very appreciative of European years ago in Germany. To many direct-on-line. The motor protective
expertise in machine building, and they electricians in Europe the Eaton part switch is usually combined with one or
also recognize many of the technological number PKZM is synonymous with more magnetic controllers (contactors)
advantages that modern European motor protective switches, regardless in cases where a higher degree of
electrical controls offer as part of the of manufacturer., or Kloeckner-Moeller, switching frequency is required. The
package. Fuseless based solutions as the company was formerly known, optimized motor protective features
remain an important and desirable has been manufacturing these manual mentioned earlier mostly refer to the
characteristic of modern electrical control switches since 1932. Other provision for phase failure sensitivity in
panel design. The use of equipment manufacturers also refer to their own accordance with IEC / EN 60 947-4-1
which can be used in both 50Hz and devices as „Motor Protective [1] and the capability of these switches
60Hz supply systems is also Switches“, or they might interchange to handle AC-4 type currents without
recommended for export purposes.
Nominal voltage differences can be easily
taken care of with the use of matching
transformers. The field of export Load Load Duty Ratings
business is where Eaton’s considerable Rating data on equipment
experience and know-how can translate
into real benefits for our clients. The main
goal is to design an electrical control 1) Motors Horsepower (HP)
panel which will both maximize the use
of European technological know-how and
secure immediate approval by local 2) Coils Coils: Volts, Frequency, Voltampere
electrical inspection authorities. This (Coils in auxiliary and Coil switching Control Circuit Contacts:
sector represents the single largest control circuits) Standard Pilot Duty or Heavy Pilot Duty.
demand for the type of IEC style
components which Kloeckner-Moeller 3) Resistance (heating) Amperes, resistance only
and subsequently were designing and
producing for decades. Now, the North
American Eaton organization can offer 4) Incandescent lamps Amperes or Watts,
even better service and support for these Tungsten
products, as well as more efficiently
provide spare parts replacement
business locally through its vast network 5) Ballast Amperes,
of suppliers. (electric discharge lamps) Ballast

Electrical equipment groupings in 6) General Use1 Amperes


North America (A)

A marked differentiation exists in the


US and Canada between components 1 The category „General Use“ applies for general usage, and is in accordance the IEC/EN utilization cate-
gory AC1.
designed for installation in energy
distribution circuits, and those that are Table 4: Types of switching loads (Load Duty ratings)

8
nuisance tripping for the duration of function, isolating characteristics and cases for export to North America,
motor start-up sequences. Generally functionality as a main disconnect are particularly since in many instances the
speaking, a phase failure sensitivity only minimally recognized per North North American ratings can be less
feature for circuit breakers, which are American standards (see ensuing than their IEC equivalent.
frequently subject to uneven loading sections for further clarifications).
across the phases, would be Equipment approvals conducted by
problematic since it could lead to North American electrical ratings for electrical inspectors
nuisance and unwarranted circuit Industrial Control Equipment
breaker tripping. Eaton does offer Generally speaking, there is a great
circuit breakers with an optional phase The US and Canadian standards have deal of uncertainty on the part of North
failure sensitivity feature for nominal defined various types or categories of American electrical inspectors with
current ratings exceeding the range of switching duty requirements for respect to equipment imported from
motor protective switches. industrial control equipment in similar overseas. That aspect, combined with
fashion to the IEC standards, which a fundamental lack of knowledge of
In addition to the overload protective define „Utilization categories for low North American standards on the part
function, Eaton motor protective voltage switching devices“ (AC-1, of European machinery exporters,
switches built in accordance with the AC-3, AC-4 etc.). Each „Load Type” in invariably cause frequent
international standards IEC / EN 60 North America is assigned a Load duty misunderstandings and commissioning
947-1 [10] and IEC / EN 60 947-2 [11] rating as indicated in Table 4, which delays for any equipment being newly
also include magnetic trips for short either appears on the rating label of installed and subject for evaluation. The
circuit protection as well as power each device or in technical data sheets inspectors (AHJ-Authorities Having
circuit isolating capabilities. They are supplied with the product, and Jurisdiction) are local town and county
thus able to be applied, with the use of identifies its suitability for the government employees who are
appropriate accessories, as main respective loading requirements. empowered to insure that electrical
disconnect switches per the installations are properly evaluated and
requirements of the IEC / EN 60 204-1 It’s important that these load duty in compliance with local electrical
[5] standard. The short circuit protective classifications be strictly observed in all codes and ordinances, which are

National Electrical Code - Motor Circuits


NEC Article 430 – Figure 1

To Supply
Part
430-24
Motor feeder 430-25, 430-26 /II
Motor feeder
short-circuit and
ground-fault protection Part V
Motor disconnecting means Part IX Main Disconnect
Motor branch-circuit
short-circuit and
ground-fault protection Part IV Short Circuit
Motor circuit conductor Part II
Motor controller Part VII Motor Controller
Motor control circuits Part VI
Motor overload protection Part III Overload
Motor Part I
Thermal protection Part III
Secondary controller Part II
Secondary conductors 430-23
Secondary resistor Part II
430-23 and Article 470

Figure 1: Diagram 430-1 from the National Electrical Code points out the important elements of the Motor Branch circuit. Differences
between international and North American definitions of key terms are the basis for much of the misunderstandings and problems
which can occur during equipment evaluation by North American inspection authorities. A similar diagram is also found in the CEC.

9
primarily derived from the NEC. The
evaluation conducted by these Group Installations
electrical inspectors is a vital element North American European perspective
in determining whether or not power perspective
from the local utility company can
ultimately be delivered to the
installation. Clearance granted by the Back-up (NZM…S(E)-…,
protective device PKM…)
inspection authority is also essential for
building owners to secure insurance
coverage for their plant and installation.

(PKZ) (DIL / Z.)


The provisions of the NEC require that
electrical components and assemblies
be “listed” by third party certification
agencies (NRTL - Nationally Recognized
Testing Laboratories) e.g. UL, in
accordance with their application. The
inspectors depend heavily on the use Figure 2: Misunderstandings can arise from differing interpretations of Group
Installations.

Short Circuit Current Ratings for single protection, group protection, tap conductor protectors, UL 508 Type E and
UL 508 Type F controllers
Type Overload Contactor Accessories SCCR Fuse max. Circuit
trip Breaker max.
[A] [kA] [kA] [A] [A] [A] [A]
1. Manual motor controller in group installations with 480 V 600 V 480 V 600 V 480 V 600 V
upstream back-up protective device
PKZM0-… 0,1 - 6,3 - - 50 50 600 600 600 600
PKZM0-10 6,3 - 11 - - 30 30 600 600 600 600
PKZM0-… 9 -12 65 18 600 600 600 600
PKZM0-… 10 - 16 - - 10 10 150 150 125 125
PKZM0-… 10 - 16 with CL-PKZ0 50 50 600 600 600 600
PKZM0-… 16 - 25 - - 10 10 150 150 125 125
PKZM0-… 16 - 25 - with CL-PKZ0 18 18 600 600 600 600
PKZM0-… 24 - 32 - - 18 10 600 600 150 125
PKZM0-… 24 - 32 - with CL-PKZ0 18 18 600 600 600 600
PKZM4-50 up to 52 - - 65 42 600 600 600 600
PKZM4-58 up to 56 - - 65 42 600 600 600 600
PKZM4-63 up to 58 - - 65 42 600 600 600 600
2. Tap Conductor Protectors suitable for use in group installations 480 Y/277 V* 600 Y/347 V*
PKZM0-… up to 11 50 50 The maximum rating of the
PKZM0-… up to 16 42 18 branch circuit protective
fuse or circuit breaker is
PKZM0-… up to 32 18 - determined per the 1/10th
PKZM4-… up to 40 - - 65 25 rule.
PKZM4-… up to 58 - - 65 -
3. UL 508 Manual Type E Self-Protected Combination Controller (Starter) 480 Y/277 V* 600 Y/347 V*
PKZM0-… 0,1 - 10 - with BK25/3-PKZ0-E 65 50 - - - -
PKZM0-… 10 - 12 65 18
PKZM0-… 12 - 16 - 42 - - - - -
PKZM0-… 16 - 27 - 18 - - - - -
PKZM4-… 10 - 40 - with BK50/3-PKZ4-E 65 25 - - - -
PKZM4-… up to 52 - 65 - - - - -
4. UL 508 Type F- Combination Controller (Starter) 480 Y/277 V* 600 Y/347 V*
PKZM0-… 0,1 - 10 DILEM, with BK25/3-PKZ0-E 50 50 - - - -
PKZM0-… 10 - 12 DILM7, 9, 12 65 18 - - - -
PKZM0-… 12 - 15 DILM15 50 - - - - -
PKZM0-… 15 - 27 DILM17, 20, 25, 32 18 - - - - -
PKZM4-… 10 - 40 DILM32, 40 with BK50/3-PKZ4-E 65 50 - - - -
PKZM4-… up to 52 DILM65 65 - - - - -
* solidly grounded system Status: April 2016

Table 5: Maximum short circuit current rating and sizing of back-up overcurrent protective fuses and circuit breakers in group installa-
tions per NEC, Article 430-53 and CEC Part 1, Rule 28-206. PKZM0 with and without CL-PKZM0 current limiter.

10
of UL listing and UL marks on products
to conduct their evaluation work,
simply because it greatly minimizes the
risk they would otherwise have to
undertake if the equipment to be Ratio between
evaluated were uncertified. A similar Branch Circuit incoming supply and
situation exists in Canada. A case could protective device outgoing cables
certainly be made that inspectors are 3:1 (1/3 Rule)
generally more wary and critical of
foreign equipment, and that there is a
PKZM0
varying degree of tolerance among PKZM4
them as to what they would deem to
be acceptable. Nevertheless, there is
always a keen interest on the part of
inspectors to look for, and find, familiar
UL and CSA marks on the equipment
they evaluate, and to make sure that
the products are applied properly per
Figure 3: Maximum ratio between incoming supply and outgoing motor circuit conduc-
their North American electrical ratings. tors in group installations per the 1/3 rule
It’s also helpful in their view to be
confronted by panel layouts and wiring
schematics which are in obvious circuit protective devices by the
conformity with local conventions and Note that the current NEC has electrical codes. (Exceptions to this are
installation guidelines. It can’t be switched from using letters to denote UL 508 Type E and F controllers, to be
emphasized enough that exporters Part A through Part J to roman covered later.)
need to pay close and strict attention to numerals Part I through Part IX.
North American requirements, because Group installations per NEC,
approval issues raised by electrical The Code requires that the Motor Article 430-53 and CEC Part 1,
inspectors can have serious Branch circuit include 4 basic functions: Rule 28-206 („Group Protection“)
consequences and should be avoided
at all costs. • Main Disconnect The use of a PKZM manual motor
In line with their philosophy of • Short Circuit protection controller in a North American motor
supplying „more than products“, Eaton • Motor Controller (Contactor) branch circuit usually means that both
offers consulting sessions and • Motor Overload protection motor main disconnect and short circuit
extensive customer seminars on the functions will be fulfilled by an upstream
export of electrical equipment to North The main difference in the evaluation of protective switch. That protection will
America. Our sales offices will be more conventional European style motor need to be provided by either a circuit
than happy to put you in touch with the protective switches, like PKZM or breaker (Molded case circuit breaker per
right people. similar devices, is that they are certified UL 489, CSA-C22.2 No. 5-09) or fuses.
in North America as „Manual Motor This motor branch circuit protective
An important guide used by electrical Controllers“ and fulfill only a motor device is mounted separately.
inspectors in their evaluation work is overload protective function, even
the chart provided by figure 430-1 of when they are additionally evaluated The North American HVAC (Heating,
the NEC (Figure 1). This chart will also for group installations. Devices of this Ventilation and Air Conditioning) group,
be the basis for many of the construction and certification are not many years ago, was the industry
clarifications provided. considered as motor branch short mostly responsible for pushing through

Evaluation per Figure 1 NEC 430-1,

UL listed / CSA certified Components and Combinations Part IX Part IV Part VII Part III
Main Short Circuit Controller Overload
Disconnect protection (Contactor) protection

1 Inverse Time Circuit Breakers NZM...A(V)(E)(F)...-NA Yes Yes No No

2 Manual Motor Starter with PZM0 + Contactor DIL M No No Yes Yes

Motor Controller MSC-...-...-.M...-SP Type E Self-Protected


3 Yes Yes Yes Yes
Combination Motor Controller

Instantaneous only circuit breaker + magnetic contactor +


4 Yes Yes Yes Yes
overload relay NZM...-S(E)...-CNA + DILM + Z

Table 6: Functional evaluation of various motor protective and circuit breaker component combinations of European design, from the
perspective of Figure 430-1 of the NEC. The peculiar aspects of these component combinations will be highlighted further in the body
of the text.

11
Group Installation regulations through From the European standpoint group incoming feeder conductors and
the NEC/CEC. Group Installation refers protection would refer to one outgoing supply cables cannot exceed
to the practice of setting up a number protective device protecting many a factor of 3:1 (1/3 rule). (Figure 3)
of tapped circuits, each with a motor circuits e.g. consisting of multiple
controller and motor overload contactors with overload relays. There are additional possibilities to
protective device, under one back-up (Figure 2). reduce conductor cross-sections in
(group) branch circuit overcurrent group installations with the use of „Tap
protective device. This type of • Consequences of group Conductor Protectors“. Tap Conductor
installation can also be used when installation wiring requirements Protectors, as explained later, can
manual motor starters such as PKZM on motor branch circuit conductor represent a suitable alternative to Type
are applied as manually operated motor sizing E Combination Motor Controllers.
controllers incorporating motor Conductor sizing in group installations
overload protection. There are also specific rules in must always be within the guidelines
Controllers and motor overload devices, European and international standards established by the NEC/CEC electrical
for example PKZM0 manual motor governing sizing and co-ordination of codes. There are also a number of
controllers in this case, are specifically conductor cross-sections and additional wiring factors to consider
evaluated and certified for use in group overcurrent protective devices. A strict besides limited conductor lengths on
Installations. All PKZM0-.. and PKZM4-.. set of conditions must be observed taps, incl. cable bundling and ambient
manual motor controllers are UL listed when reducing the cross-section of a temperature, protection against
and CSA certified for this application conductor, simply because the damage etc…
and can be thus grouped under one overcurrent protective device could
overcurrent protective device per NEC otherwise end up being too oversized Examples of popular components
and CEC group installation guidelines.12 to provide adequate protection for the and combinations in Motor Branch
smaller conductor. The same reasoning Circuits
applies with respect to North American
sizing requirements. In group Table 6 shows how several popular
12 At the time of this writing the certification pro-
cess for the new electronic PKE controller had installations per NEC/CEC, the general component combinations are evaluated
been initiated. rule is that the ampacity ratio between in motor branch circuits from the

Rated Current Three Phase HP ratings1)


Three Phase NEMA
Contactors 460 V / 60 Hz Service-Limit
200 V / 60 Hz 230 V / 60 Hz
575 V / 60 Hz Current Ratings
NEMA-Sizes
A HP (PS) HP (PS) HP (PS) A

00 9 1m 1m 2 11

0 18 3 3 5 21

1 27 7m 7m 10 32

2 45 10 15 25 52

3 90 25 30 50 104

4 135 40 50 100 156

5 270 75 100 200 311

6 540 150 200 400 621

7 810 - 300 600 932

8 1215 - 450 900 1400

9 2250 - 800 1600 2590

1) HP ratings for 3-Phase contactors, single speed motors, with no jogging, reversing and dynamic current braking.
Table 7: NEMA-Sizes for contactors in relation to HP-ratings and rated nominal current levels.

12
DILM/Z Non-Combination motor starters for applications in North America
Maximum Motor HP Rating Motor Contactor Overload Maximum upstream short circuit protective
3 Phase, 60Hz Full Load Relay device in North America
Current
Fuses Circuit Breaker
208 V 240 V 480 V 600 V FLC per Rated Short Circuit
(200 V) (230 V) (460 V) (575 V) CEC / NEC1) Current Instantaneous Trip

HP HP HP HP A Type Type A A A
– – m m 1 DILEEM ZE-1 3 15 –
– – o 1 1.4 DILEEM ZE-1.6 6 15 –
m m 1 1m 2.3 DILEEM ZE-2.4 6 15 –
1 1 2 3 3.9 DILEEM ZE-4 15 15 –
1m 1m 3 – 6 DILEEM ZE-6 20 15 –
1m 2 – – 6.8 DILEEM ZE-9 35 15 –
1m 2 5 5 7.8 DILEM ZE-9 35 15 –
1m 3 5 5 9.6 DILEM ZE-12 45 – –
- - m m 1 DILM7 ZB12-1 3 25 200
- - m 1 1.4 DILM7 ZB12-1.6 6 25 200
m m 1 1m 2.3 DILM7 ZB12-2.4 6 25 200
1 1 2 3 3.9 DILM7 ZB12-4 15 25 200
1m 1m 3 - 6 DILM7 ZB12-6 20 25 200
3 - - 7m 9 DILM9 ZB12-10 25 25 200
3 3 5 7m 9.6 DILM12 ZB12-10 25 25 200
3 - 7m 10 11 DILM12 ZB12-12 40 25 200
5 5 10 - 15.2 DILM15 ZB12-16 40 30 320
- - m m 1 DILM17 ZB32-1 3 25 200
- - o 1 1.4 DILM17 ZB32-1.6 6 25 200
m m 1 1m 2.3 DILM17 ZB32-2.4 6 25 200
1 1 2 3 3.9 DILM17 ZB32-4 15 25 200
1m 1m 3 - 6 DILM17 ZB32-6 20 25 200
- 3 5 7m 9.6 DILM17 ZB32-10 25 25 200
- - 7m 10 11 DILM17 ZB32-12 40 30 320
5 5 10 - 15.2 DILM17 ZB32-16 40 30 320
7m 7m 15 20 22 DILM25 ZB32-24 90 100 1200
10 10 20 25 32.2 DILM32 ZB32-32 125 125 1200
- 3 5 7.5 9.6 DILM40 ZB65-10 40 40 380
- 5 10 10 15.2 DILM40 ZB65-16 60 60 760
- 7m 20 25 32.2 DILM40 ZB65-24 90 90 1200
10 10 20 30 34 DILM40 ZB65-40 125 125 1200
15 20 40 50 54 DILM50 ZB65-57 200 150 2000
20 20 50 50 63 DILM65/72 ZB65-65 200 150 2000
25 30 60 75 80 DILM80 ZB150-70 250 250 2500
25 40 75 100 104 DILM95 ZB150-100 J 400 J 400 3200
40 50 100 100 130 DILM115 ZB150-125 J 400 J 500 4000
40 60 125 125 156 DILM150/170 ZB150-150 J 600 J 600 4800
50 60 125 150 156 DILM185A Z5-160 700 CLASS L 600 7200
60 75 150 200 192 DILM225A Z5-220 700 CLASS L 600 7200
75 100 200 250 248 DILM250 Z5-250 700 CLASS L 600 7200
100 125 250 300 312 DILM300A ZW7-400 800 CLASS L 600 7200
125 150 300 400 382 DILM400 ZW7-400 800 CLASS L 600 7200
150 200 400 500 480 DILM500 ZW7-540 800 CLASS L 600 7200
- 200 400 600 480 DILM580 ZEV-XSW820 2000 - -
- 250 500 600 600 DILM650 ZEV-XSW820 2000 - -
- 300 600 700 700 DILM750 ZEV-XSW820 2000 - -
- 350 700 860 860 DILM820 ZEV-XSW820 2000 - -
1) Applicable for North American branch circuit fuse classes only. Status: April 2016

Table 8: “Contactor + Overload Relay” combinations for the North American market, with data on the maximum back-up branch
­circuit protective fuse or molded case circuit breaker (UL 489).

13
perspective of Figure 1 (NEC-Figure be driven without exceeding adjustable motor overload protective
430-1.) temperatures that would otherwise devices of European design have an
lead to overheating. The overload overload tripping point that is 125% of
Additional items worthy of protective settings Ir of UL/CSA the dial setting current, which allows
consideration with respect to certified overload relays and manual the devices to be set to the motor full
enclosed equipment. motor controllers take motor service load current and provide protection for
factor into account in order to provide motors with a service factor of 1.15
International IP..- code environmental the required motor overload tripping and greater. Most motors up to 200HP
ratings for enclosures are not officially protection required by Code. Nearly all will fall in that category. In cases where
recognized by electrical inspectors. A the motor has a service factor less than
North American environmental rating in 1.15, a corrective factor would need to
accordance with NEC 430-110.20 / CEC be applied. This can be easily
must appear on the equipment itself or accommodated by adjusting the dial
on accompanying technical setting of the motor overload protective
documentation. Individual conductors devices accordingly. Typically, the
are enclosed in conduits which are following values would apply:
terminated directly onto the enclosure.
These conduits, which are offered in SF = 1,15 ➞  Ir = 1 x In mot
various “NPT” (National Pipe Thread) SF = 1 ➞  Ir = 0,9 x In mot
Trade Sizes, can be part of an
installation’s grounding circuit. • Motor contactors for the North
European PG fixtures13 or metric sized American market
conduits are unknown. Eaton offers for
that reason product dedicated Motor contactors in North America are
insulating material enclosures CI-K2- industrial control devices (Industrial
PKZ0-NA-G(R)(V) with smooth sided Control Equipment per UL 508 and
bases and drill starts to better CSA-C22-2 No. 14). North American
accommodate cable entries with North buyers specify contactors either in
American style NPT trade size conduits. „NEMA-Sizes“ or, as it is commonly
Continuity of ground must be done in the IEC world, by matching
established when conductors are motor and controller Horsepower (HP)
connected to the enclosures via ratings to more closely fit the
conduits. If fuses are involved, care application. Table 7 shows the
must be taken to include only certified relationship of power and nominal
North American fuses and fuse bases. current ratings corresponding to each
Use only wiring material that is certified respective NEMA-size.
per North American standards (UL/
CSA). Conductor cross-section sizing –– Combination “Contactor +
and color schemes must be in Overload Relay” („Non-
accordance with North American combination Motor Starter“)
electrical code requirements.
Table 8 provides an overview of Eaton
Basic concepts related to electrical contactor HP ratings. Contactors and
products on the North American overload relays make up an assembly
market that is referred to in North America as a
„non-combination motor starter“.
Certain aspects related to the North American buyers usually order
application of motor starters in North these assemblies by specifying the
America will be briefly touched upon required HP rating, much like the
since product evaluation and Figure 4: Manual Motor Controllers, such purchase of individual contactors.
performance capabilities of low voltage as PKZM0, PKZM4 and PKE with a base Table 8 clearly indicates that combining
equipment designed per North certification per UL 508 / CSA-C22.2 „IEC style“ contactors DIL M with
American and international guidelines No. 14, would require an upstream over- overload relays Type Z creates many
current protective device in the motor
can vary so much from each other. It’s more starter combinations than the
branch circuit per NEC/CEC regulations.
necessary to know these differences in UL 489 listed molded case circuit break- choice of starter assemblies based on
order to gain better insight into the ers would be suitable for the purpose, NEMA sizing. Table 8 would infer a
proper application of these products in and are part of the certification testing more efficient way of applying
North America. process for all manual motor controllers. contactors than using NEMA sized
The presence of a full voltage1) rated
By design, electrical motors in North controllers.
upstream protective would allow the
America are assigned load duty ratings controllers to be used in both grounded Such motor branch circuit combinations
referred to as Service Factor (SF) and ungrounded North ­American power (with overload relay!) under European
which, generally speaking, provides an distribution networks. practices, with very few exceptions,
indication as to how much over the 1) Full voltage in this case refers to the voltage would be combined with fuses as the
nameplate current rating a motor can rating of the network, e.g. 480 VAC, which short circuit protective element, and
would require a full voltage rated protective would then be identified as fusible or
device, as opposed to a slash rated, solidly
grounded distribution networks such as “fuse based” motor starters
13 PG, from the German Panzerrohr-Gewinde 480Y/277 VAC. accordingly.

14
• Manual Motor Controllers • Main Disconnect and isolating Eaton manual motor controllers are
(Starters) for the North American characteristics available for North American
market • Short circuit protection applications in current ranges up to
• Overload protection 58 A and come in several family
–– PKZ Manual Motor Controllers • and direct-on-line switching versions (PKZM0, PKZM4 and PKE).
capabilities Availability of the PKE controller
Manual motor controllers are should expand the current range to
Industrial Control devices that are and, with the provision of certain key higher levels.
evaluated and certified per UL 508 accessories, can also be applied as a
and CSA-C22.2 No.14-05. PKZM supply circuit disconnecting means –– Motor Protective Switches,
manual motor controllers are world (Main Disconnect and Emergency- NZM…-ME…-NA “Motor
market devices. They feature fixed OFF switches). Devices in the Protective Circuit Breaker”
instantaneous trips (PKZM0, PKZM4 smaller adjustable current ranges are
and PKE) magnetic trips for short all short circuit proof and self- Motors, of course, also come in larger
circuit protection, adjustable bimetal protective. Self-protective means sizes. Eaton is now introducing a new
or electronic trips for motor overload that their inner resistance (primarily range of NZM…-ME…-NA motor
protection and they can switch the bimetal trip assembly) is so great, protective circuit breakers to cater to
motors directly across the line. The that available short circuit currents as North American motor starter
PKE electronic controllers have an high as 150 kA are reduced to a level applications in higher ratings. These
additional trip class selection setting low enough to allow the switch, devices have been certified as full
(Class 5 through 20) as well as a without the need of an additional fledged inverse time circuit breakers
motor overload setting range that is back-up protective device, to protect per UL 489 and CSA-C22.2 No. 5-09,
much broader than conventional, itself and safely handle the fault but have also undergone calibration
thermal based controllers. These current without any damage. These testing per the motor overload
devices can all be equipped with devices are well established globally protective function requirements of the
auxiliary contacts for control circuit and provide international end-users industrial control product standards UL
switching requirements. Per current with a technically viable and 508 and CSA-C22.2 No. 14-05.
North American product standards, economically attractive solution to At the time of this writing this type of
the functionality of the instantaneous meet their needs. The protective circuit breaker had not yet been
short circuit trips built into these features of these switches have incorporated into the North American
controllers is not recognized as been verified so often, and in so standards. The circuit breaker is
providing the necessary branch many millions of cases, that no one normally combined with a magnetic
circuit overcurrent protective outside North America would ever contactor to form a 2 component style
function. ( Exception: UL 508 Type E doubt their effectiveness and overall combination motor starter as an
and F controllers, to be described performance capabilities. alternative to the more traditional 3
later.) component North American
From a North American perspective, combination starter (circuit breaker +
Manual motor controllers of this the IEC motor protective switch is contactor + overload relay).
design are used primarily as manually categorized simply as a „manual
operated protective switches in motor controller“, and does not • Molded Case Circuit Breakers for
industrial control panels as well as provide a short circuit protective the North American market
individually enclosed starters for function to the branch circuit. All of
single motor loads. They are selected these controllers, aside from those Molded case circuit breakers for the
In North America in accordance with that have undergone additional North American market, as referenced in
the motor HP rating and are primarily evaluation as explained in a later Table 3, are considered to be low voltage
used in motor branch circuits for section, require an upstream energy distribution equipment and are
motor switching and protective overcurrent protective device in the designed, tested and certified per the
functions. circuit. (Figure 4). This applies product safety standards UL 489 und
equally in cases where the device is CSA-C22.2 No. 5-09. These standards
As is the case with molded case operating in its self-protective range are amongst the most demanding and
circuit breakers, North American and and also when it is additionally UL stringent of all component standards in
international approaches and listed and CSA certified for group North America. The main task of molded
viewpoints with respect to manual installations. This reduced case circuit breakers and fuses in
motor controllers tend to be far apart performance capability is not the industrial applications is to protect control
philosophically. It would be preferable result of failed product testing. equipment, conductors and assemblies
if North American standards could Rather, it has to do with the fact that, against the destructive effects of short
better recognize the performance historically, North American product circuit currents. They are often applied in
capabilities and greater application standards have assigned the short this respect as “branch circuit protective
range possibilities offered by these circuit protective function to a devices (BCPD)” for outgoing loads such
components. separate grouping of overcurrent as motor circuits. Both fuses and circuit
protective devices specifically listed breakers are the only types of protective
From an international point of or certified for the purpose. However, devices which the North American
view, these devices represent as the following clarifications will electrical codes allow for non-motor
compact and stand-alone manually show, there has been a loads.
operated motor protective switches rapprochement of sorts between
which offer all of the following both the NA and IEC worlds in this All NZM type circuit breakers
functionality aspects: regard. mentioned in this paper refer to

15
„Molded Case Circuit Breakers“ per –– NZM…-S(E)…-CNA These devices contain adjustable
UL and CSA standards. The smallest Instantaneous Trip Circuit magnetic or electronic trips for short
certified molded case circuit breaker in Breakers (without thermal or circuit protection. They do not feature
Eaton’s line is the IEC/EN miniature electronic overload trips) any bimetal or electronic overload trips.
circuit breaker type ­FAZ…-NA14, followed They do not provide any motor overload
in size by the PKZM4…-CB. protective function. It’s possible in
certain cases for these breakers to still
incorporate a bimetal element, but this
14 These devices are commonly referred to as place even though that term does not appear in would be done strictly to provide a
“Mini-Breakers” in the North American market- any standard or norm.

Standards terminology: Motor Controller


Generally speaking, All power components and assemblies that are used for switching electrical motors
a „Motor Controller“ refers to the ON and OFF, and which may or may not include additional protective functions.
following concept in North America:
Significance: Controller is the official term used in the NEC, and since UL-standards are based on
the NEC, it is the term most commonly used throughout UL-standards to identify
components and assemblies used in motor switching applications.

Some examples within the Eaton 1. Contactors DIL M, without protective function,
family of components and assemblies: 2. Motor starter combinations DIL / Z with overload protective function,
3. Manually operated P und T switches, without protective function,
4. Manual Motor Controller PKZM0 with overload protective function,
5. Manual self-protected combination starter PKZM0-..+BK25…-E (Type E-Starter)
with motor overload and motor branch short circuit protective functions.

Market terminology: Motor Starter


Generally speaking, a „Motor Starter“ Individual or group of „Motor Controller“ components which additionally feature a
refers to the following concept in North protective function.
America:
Significance: The industry in North America refers to this term much more commonly when
denoting motor controllers with protective functions.
Some examples within the Eaton 1. Motor protective switches PKZM and PKZ (manual motor starters)
family of components and assemblies: 2. Magnetic motor starter combination DIL / Z,
(Non-combination motor starter)
3. Combination magnetic motor starter combination
NZM / DIL / Z, (Combination motor starter)

Further differentiation within Motor Starter groupings


without Contactor with Contactor

Non-combination motor starter Combination motor starter1) or


Combination motor controller2)
1)
+ 2) identical terms:
1)
Industry terminology,
2)
UL 508 terminology
fulfills all 4 motor branch circuit functions per
NEC Figure 430-1:
• No isolation function (main disconnect), • Isolation (main disconnect),
• No short circuit protection • Motor switching (controller),
Both these functions need to be separately • Short circuit protection,
provided. • Overload protection
Examples within the Eaton MSC-…-…-M…-SP PKZM0-..+BK25/3-PKZ0-E 3) + DILM (UL 508
family of components and Type F- Combination motor controller)
assemblies:
Manual Self-protected Combination
3)

Controller

Table 9: Clarifications on commonly used terms „Motor Controller“, „Motor Starter“, „Combination Motor Controller“, „Combination
Motor Starter“ and „Non-Combination Motor Starter“

16
North America IEC-World

P2-.../F-...-CNA „Combination Motor • Fuse

motor starters
+ Class H, R or J Fuses Starter“ + Contactor

Fuse based
+ DILM + Overload relay
+Z • Fusible Type

MSC-...-...-M...-SP • Self-Protected Type • Motor protective switch


+ Contactor

NZM..-A(E)..-NA, • Inverse Time Circuit • Circuit Breaker


NZM..-VE..-NA Breaker Type + Contactor
+ DILM
Remotely (magnetically) operated

Fuseless motor starters


NZM..-A(E)F..-NA, • Circuit Breaker
NZM..-VEF..-NA + Contactor
+ DILM + Overload relay
+Z

Motorstarter
not allowed, respectively • Motor protective switch (with-
consider additional conditions out overload function)
+ Contactor
+ Overload relay

NZM...-S(E)..-CNA • Instantaneous Trip • Circuit Breaker (without


+ DILM ­Circuit Breaker Type overload function)
+Z + Contactor
+ Overload relay

 2 HP und 300 V: • Fusible Type • Fuse Fuseless motor Fuse based motor
P1 + Cam switch
+ Class CC or J Fuse
starters
+ Contactor
+ DILM + Overload relay
+Z

PKZM0 „manual motor controller“ • Motor protective switch


Manually operated

PKE
starters

not allowed, respectively


consider additional conditions
Legend:
= commonly used

= less conventional

Table 10: Differences between typical North American and IEC motor starter assemblies.

17
better degree of internal self-protection fulfills the motor overload protective through testing. Per the NEC, all
and not be mechanically linked in any function and the circuit breaker combination motor starters featuring
way to the external tripping function. provides short circuit protection. This instantaneous trip circuit breakers must
These breakers are rated in continuous array makes it possible, with the use of be listed.(e.g. UL)
nominal amperes. They can also be overload relay and circuit breaker
equipped with auxiliary contacts (pilot auxiliary contacts, to differentiate –– NZM...-A(V)(E)(F)…-NA Inverse
duty rated) for control circuit switching between overload and short circuit Time Circuit Breakers
purposes. UL/CSA certification does tripping indications, an aspect which is
not allow for individual short circuit also considered advantageous in the These are the typical circuit breakers
interrupting ratings to be marked on IEC world. In addition, they are found in energy distribution assemblies
these breakers. Any short circuit rating considered useful in applications throughout North America and also
would be applicable to the entire motor involving long duration motor starting featured prominently in motor control
starter assembly into which they are sequences which could otherwise centers and industrial control panels.
contained (refer to next section). That’s cause an inverse time circuit breaker to They are rated in amperes and are
the main reason why instantaneous-trip possibly nuisance trip during start. clearly marked with short circuit
circuit breakers are recognized only per interrupting capacities, usually shown
UL standards, and subject to These starters are primarily installed in in kA. They can also be equipped with
“Conditions of Acceptability” (CoAs). North America as Motor Control auxiliary contacts that generally feature
These types of circuit breakers are Centers (MCC) units or as industrial pilot duty control circuit load ratings.
always combined with a magnetic control panel assemblies. They are also
contactor and overload relay to form a often separately mounted in individual These breakers feature an adjustable
„Combination Motor Starter“. enclosures. They can be installed in magnetic or electronic instantaneous
circuits up to their maximum short response trip for short circuit protection
In these 3 component type circuit rating. The determining factor in and either a fixed (Type suffix –A(E)F)
combination starters, the contactor the short circuit rating is always based or adjustable bimetal- or electronic,
provides across-the-line motor on the weakest component within the (Type suffix (-A(E)) long time response
switching duties, the overload relay motor starter and must always verified setting overload range for the

Constructive solutions for „Combination Motor Controllers“ per the UL 508 standard
Configuration Part IX Part IV Part VII Part III

Construction Type Main Disconnect Branch Circuit Short Motor Controller Motor Overload
Circuit Protection
A Listed component Listed branch circuit Listed component Listed component
certified to UL 98 / 489 fuses certified to UL 248 certified to UL 508 certified to UL 508
series
Molded Case Switch Class J or RK5 Ex: + DIL M Ex: + Z, + PKZM 0
e.g.: NS1…-NA

B This particular constructive design is no longer available in the market place.

C Inverse Time Breaker UL 489 Listed component Listed component


e.g. NZM…-A(E)..-NA, certified to UL 508 certified to UL 508
NZM..-VE..-NA e.g.: + DILM
Or: NZM…-ME...-NA In this case:
NZM…-ME...-NA
• By virtue of additional
calibration tests per
UL 508
D Instantaneous Trip Breaker UL 489 Listed component Listed component
certified to UL 508 certified to UL 508
Ex: NZM..-S(E)..-CNA Ex: + DIL M Ex: + Z
E Self-Protected Combination Motor Controller
Ex: MSC-…-…-M…-SP
F Manual Self-Protected Combination Motor Listed component
Controller, Manual Type-E-starter certified to UL 508
Ex: PKZM0-..+BK25…-E Ex: + DIL M

Table 11: Various solutions of „UL 508 - Combination Motor Starters“, alphabetically identified in the standard by construction types
„A” through „F“. Construction Types E und F are particularly interesting in view of this paper’s focus on IEC style motor protective
components. Note that Types „A“ through „E“ are also currently described in the analog CSA-C22.2 No. 14-05 standard, whereas
Type F starters are only found in the UL standard. Although not officially a part of Canadian based product standards, Type F starters
find acceptance amongst Canadian based regulatory agencies and inspection authorities.

18
protection of cables and non-motor
loads. They are also utilized as the main
disconnect and short circuit protective Back-up protective „Type E“-Devices fulfill all 4
device for motor branch circuits, usually switch functions (Main Disconnect,
in association with contactors and
UL 508 „Type E“ Short Circuit, Overload,
separately provided motor overload
relays. Their auxiliary contacts are used Controller).
to switch associated control circuitry.
They can be installed in circuits with The Back-up protective
available faults up to their maximum switch can be eliminated.
short circuit interrupting ratings without
the need for any additional upstream
overcurrent protection and also fulfill all
Code requirements as Main Disconnect
switches in service entrance and/or
feeder circuit applications. Circuit
breakers Type NZM…V(E)(F)…-NA
Figure 5: UL / CSA „Type E“-Controllers fulfill all 4 functions required in the motor
feature an additional, intentionally branch circuit. There is no need for a back-up protective switch up to the controller’s
delayed short circuit trip element. highest short circuit rating. „UL 508 Type E“- controllers are also referred to as Self-
protected. For electronic motor-protective circuit-breakers PKE a contactor, as shown in
–– Advantages of molded case circuit Figures 6 and 9, is required already for Type E.
breakers over fuses in North
American motor branch circuits
offer significant advantages over fuse  Fusebases for certain types of
Assuming that proper component based engineering: fuses, e.g. Class R, are relatively
selection guidelines, as highlighted in large, and take up a lot of panel
previous sections, have been followed,  OnlyNorth American fuses are room. Combining such fuses with
the choice of fuseless based solutions considered suitable for applications in contactors and overload relays does
using circuit breakers and suitably North America. The use of IEC/EN not usually lead to optimal utilization
certified manual motor controllers can type fuses is not accepted. of available space.

To Supply
Part
430-24 MSC-...-...-M...-SP
Motor feeder 430-25, 430-26 /II
Motor feeder
short-circuit and
ground-fault protection Part V
Motor disconnecting means Part IX
Motor branch-circuit
short-circuit and
ground-fault protection Part IV
Motor circuit conductor Part II
Motor controller Part VII
Motor control circuits Part VI
Motor overload protection Part III
M
3~
Motor Part I
Thermal protection Part III
Secondary controller Part II
Secondary conductors 430-23 VII
Secondary resistor Part II
430-23 and Article 470 NEC Article 430, Figure 430-1

Figure 6: The above diagram shows that the essential requirements of the motor branch circuit outlined in NEC Diagram 430-1 are ful-
filled by the constructive elements of the UL listed and CSA certified MSC-…-…-M…-SP Self-protected Combination Motor Controller.
Both The PKZ 2’s disconect(Part IX) and contactor (Part VII) modules each feature a set of current limiting contacts which provide the
starter with its high capacity and high fault rating performance capability. The device can also be used world-wide.

19
 An
NZM inverse time circuit breaker certified per the North American
combines the functions of isolator, industrial control equipment UL 508
short circuit protection, overload und CSA-C22.2 No.14 product
protection and trip signalization all in standards as HP rated manual motor
one device, and is often smaller and controllers and have been additionally
more economical than a comparable evaluated as fuse protected motor
fusible disconnect device. circuit disconnect switches per the
requirements of the electrical codes. In
 It’s
possible in certain cases to mix most applications, this would mean
incompatible fuses and fuse bases. installation on the load side of the final
The use of additional markings branch circuit overcurrent protective
indicating the correct type of fuses is device (BCPD) which, in the case of
necessary to avoid mishaps. fuses, would make it necessary for the
upstream supply circuit disconnect to
 Machine exporters often complain of isolate the circuit in order to exchange
long delivery times and high prices blown fuses. Unlike in the IEC world,
when sourcing North American fuse the P and T products are not suitable
equipment in Europe. as feeder circuit main disconnect
switches. They are, however,
• Manually operated disconnect particularly well suited as individually
switches in motor circuits enclosed lock-out/tag-out isolator
switches local to the motor per the
Type T rotary cam switches and Type intent of NFPA 70E [12] since their
P1 and P3 motor circuit disconnects location in this regard would place
Figure 7: Self-Protected Combination
are also products that are primarily them on the load side of the motor
Starter, UL 508 Type E for motor-protec- applied in North American motor branch circuit protective fuse. They all
tive circuit-breakers PKE up to 32 A a branch circuits. All of these feature pilot duty rated auxiliary
contactor is always required. components have been listed and contacts as accessories which can be

PKZM0(4), UL 508 Type E „Manual self-protected combination motor controllers”


Maximum Motor HP Rating Trip settings Short Circuit Current Rating Components
3 Phase, 60Hz (SCCR)
200 V 230 V 460V 575 V Adjustable Instantaneous 240 V 480Y/277 V * 600Y/347V * Motor Protector Asseccories
208 V 240 V 480 V 600 V thermal Trip, Fixed
[HP] [HP] [HP] [HP] [A] [A] [kA] [kA] [kA] Type Type
1) 0.1 - 0.16 2.5 65 65 50 PKZM0-0,16 BK25/3-PKZ0-E
0.16 - 0.25 3.9 65 65 50 PKZM0-0,25 BK25/3-PKZ0-E
0.25 - 0.4 6.2 65 65 50 PKZM0-0,4 BK25/3-PKZ0-E
0.4 - 0.63 9.8 65 65 50 PKZM0-0,63 BK25/3-PKZ0-E
0.63 - 1 16 65 65 50 PKZM0-1 BK25/3-PKZ0-E
¾ ¾ 1 - 1.6 25 65 65 50 PKZM0-1,6 BK25/3-PKZ0-E
½ ½ 1 1½ 1.6 - 2.5 39 65 65 50 PKZM0-2,5 BK25/3-PKZ0-E
¾ ¾ 2 3 2.5 - 4 62 65 65 50 PKZM0-4 BK25/3-PKZ0-E
1½ 1½ 3 5 4 - 6.3 98 65 65 50 PKZM0-6,3 BK25/3-PKZ0-E
2 3 5 7½ 6.3 -11 155 65 65 50 PKZM0-10 BK25/3-PKZ0-E
3 3 7½ 10 9 - 12 186 65 65 18 PKZM0-12 BK25/3-PKZ0-E
3 5 10 - 10 - 16 248 42 42 - PKZM0-16 BK25/3-PKZ0-E
5 - - - 16 - 20 310 18 18 - PKZM0-20 BK25/3-PKZ0-E
- 7½ 15 - 20 - 25 388 18 18 - PKZM0-25 BK25/3-PKZ0-E
7½ 10 20 - 24 - 32 496 18 18 - PKZM0-32 BK25/3-PKZ0-E
3 5 10 10 10 - 16 248 65 65 25 PKZM4-16 BK50/3-PKZ4-E
5 7½ 15 20 16 - 27 388 65 65 25 PKZM4-25 BK50/3-PKZ4-E
7½ 10 20 30 24 - 34 496 65 65 25 PKZM4-32 BK50/3-PKZ4-E
10 - 30 30 32 - 40 620 65 65 25 PKZM4-40 BK50/3-PKZ4-E
- 15 30 - 40 - 52 775 65 65 - PKZM4-50 BK50/3-PKZ4-E
- - 40 - 50 - 56 899 65 65 - PKZM4-58 BK50/3-PKZ4-E
- - 40 - 52 - 58 977 65 65 - PKZM4-63 BK50/3-PKZ4-E
1) In this range, select devices per motor full load current. Refer to NEC Table 430-250.
2) Solidly grounded power distribution system. Status: April 2016

Table 12: UL 508 Type E “Manual self-protected combination motor controllers”

20
Type E Combination Motor Controller
Maximum motor rating Setting Ranges Rated short-circuit breaking capacity Combination
Three-phase current overload release Motor Starter

200V HP 230V HP 460V HP 575V HP A 240V kA 480Y/277V kA 600Y/347V kA


1
/2 1
/2 0,3–1,2 14 14 14 MSC-DE-1,2-M17-SP(…)
3
/4 3
/4 2 - 1–4 18 18 - MSC-DE-4-M17-SP(…)
3 3 71/2 - 3–12 18 18 - MSC-DE-12-M17-SP(…)
5 71/2 15 - 8–32 18 18 - MSC-DE-32-M32-SP(…)
Table 13: MSC-DE-...-M...-SP, Type E Combination Motor Controller with PKE

Figure 8: A group of PKZM0 manual motor controllers


is linked via a commoning link bus connector. The con-
trollers are fed by a common BK25/3-PKZ0-E terminal
block. The incoming terminal’s large electrical clear-
ances at the point of supply enable the entire assembly
to meet self-protected “Construction Type E” require-
ments. The circuit breakers’ thumb grips must be lock-
able.

used to switch associated control these starters are by definition overload relays follows the same
circuitry loads. considered to be individually enclosed process as referred to in Table 8.
assemblies in North America, which is
Motor Starters in accordance with again a departure from traditional Various constructive solutions for
North American specifications European definitions. They can more or „Combination Motor Starters“
less be thought of as small engineered
Table 9 provides basic clarifications of control panels which include all the The functional composition of a North
the most commonly used terms and necessary parts and pieces to complete American motor starter was presented
expressions used in association with a stand alone motor starter assembly. earlier in Figure 1. From an international
various motor starter configurations. The selection of contactors and viewpoint, however, the figure does not
The concept of non-combination motor
Starters was already introduced on
page 12. Table 10 compares a wide
range of the most popular, as well as
lesser known, motor starter assemblies
Back-up protective „Type F“-Combination Motor
used throughout the IEC-world and
switch Controllers consist of a manual
North America.
Type E- controller combined with a
UL 508 „Type F“ magnetic or solid state contactor
• C
ombination Motor Starter (controller).

A motor starter of European origin, The upsteam branch circuit


which includes all the necessary protective device can be
eliminated.
components to fulfill motor short circuit
and overload protective functions, as
well as motor switching duties (e.g.
Circuit breaker + Contactor + Overload 1 = (Manual) „Type E“-Starter
2 = Magnetic contactor
relay) is referred to in the US and
Canada as a “Combination Motor
Starter”. Apart from Type E self-
protected combination starters Figure 9: „Type F Combination Motor Starters“ fulfill all 4 functions of a combination
(explained in the upcoming section) motor starter per UL 508. The back-up protective switch can be eliminated.

21
readily highlight a fundamental • UL 508 Type E Self-protected E controllers in the Eaton family of
difference in motor starter Combination Motor Controller components all feature very high short
configuration, namely, that components circuit ratings (SCCR) which by design
fulfilling Parts IX „Main Disconnect“ The introduction of “Construction Type are both voltage and current dependent
und IV „Short circuit protection“ are E” in the product standards UL 508 [8] due to varying levels of impedance in
often provided separately in the North and CSA-C22.2 No. 14 [9] represented the overall component assembly15 .
American motor branch circuit (refer to a significant step in the expansion of Currently available „Type E“- Self-
Figure 4). In ensuing years, combination motor controller design in protected combination controllers are
conventions changed and progress North America. The larger electrical certified for use in solidly grounded, 4
opened the door for more global and clearances, which are specified in wire power distribution networks (e.g.
technologically diverse solutions to product standards such as UL 489 [6] 480Y/277 VAC Slash voltage rating).
emerge and establish themselves. and CSA-C22.2 No. 5-05 [7], are
Table 11 highlights the developments necessary on the incoming supply side The use of Type E Self-protected
in motor starter construction in this field wiring terminals of these combination controllers provides
respect. The various combination motor controllers since they also fulfill the numerous benefits:
starter configurations currently available main disconnect and short circuit
are alphabetically tagged as a function protective functional requirements of ▶ Simplified engineering, no need to
of their construction (Types A through F the motor branch circuit into which co-ordinate with a back-up
at this time per UL standards). they are installed (Figure 5). The Type overcurrent protective device (often

PKZM0(4), „UL 508 Type F Combination Motor Controllers“


Maximum Motor HP Rating Trip settings Short Circuit Current Rating Components
3 Phase, 60Hz (SCCR)
200 V 230 V 460V 575 V Adjustable Instantaneous 240 V 480Y/ 600Y/ Motor Supply Contac-
208 V 240 V 480 V 600 V thermal Trip, Fixed 277 V2) 347V2) Protector Terminal tor
[HP] [HP] [HP] [HP] [A] [A] [kA] [kA] [kA] Type Type Type
1) 0.1 - 0.16 2.5 50 50 50 PKZM0-0,16 BK25/3-PKZ0-E DILEM
0.16 - 0.25 3.9 50 50 50 PKZM0-0,25 BK25/3-PKZ0-E DILEM
0.25 - 0.4 6.2 50 50 50 PKZM0-0,4 BK25/3-PKZ0-E DILEM
0.4 - 0.63 9.8 50 50 50 PKZM0-0,63 BK25/3-PKZ0-E DILEM
0.63 - 1 16 50 50 50 PKZM0-1 BK25/3-PKZ0-E DILEM
¾ ¾ 1 - 1.6 25 50 50 50 PKZM0-1,6 BK25/3-PKZ0-E DILEM
½ ½ 1 1½ 1.6 - 2.5 39 50 50 50 PKZM0-2,5 BK25/3-PKZ0-E DILEM
¾ ¾ 2 3 2.5 - 4 62 50 50 50 PKZM0-4 BK25/3-PKZ0-E DILEM
1 1½ 3 5 4 - 6.3 98 50 50 50 PKZM0-6,3 BK25/3-PKZ0-E DILEM
2 3 5 7½ 6.3 - 11 155 50 50 50 PKZM0-10 BK25/3-PKZ0-E DILEM
1) - 0.1 - 0.16 2.5 65 65 18 PKZM0-0,16 BK25/3-PKZ0-E DILM7
- 0.16 - 0.25 3.9 65 65 18 PKZM0-0,25 BK25/3-PKZ0-E DILM7
- 0.25 - 0.4 6.2 65 65 18 PKZM0-0,4 BK25/3-PKZ0-E DILM7
- 0.4 - 0.63 9.8 65 65 18 PKZM0-0,63 BK25/3-PKZ0-E DILM7
- 0.63 - 1 16 65 65 18 PKZM0-1 BK25/3-PKZ0-E DILM7
¾ ¾ 1 - 1.6 25 65 65 18 PKZM0-1,6 BK25/3-PKZ0-E DILM7
½ ½ 1 1½ 1.6 - 2.5 39 65 65 18 PKZM0-2,5 BK25/3-PKZ0-E DILM7
¾ ¾ 2 3 2.5 - 4 62 65 65 18 PKZM0-4 BK25/3-PKZ0-E DILM7
1 1½ 3 5 4 - 6.3 98 65 65 18 PKZM0-6,3 BK25/3-PKZ0-E DILM7
2 3 5 7½ 6.3 -11 155 65 65 18 PKZM0-10 BK25/3-PKZ0-E DILM12
3 3 7½ 10 9 - 12 186 50 50 18 PKZM0-12 BK25/3-PKZ0-E DILM12
3 5 10 - 10 - 16 248 18 18 - PKZM0-16 BK25/3-PKZ0-E DILM17
5 - - - 16 - 20 310 18 18 - PKZM0-20 BK25/3-PKZ0-E DILM25
- 7½ 15 - 20 - 25 388 18 18 - PKZM0-25 BK25/3-PKZ0-E DILM25
7½ 10 20 - 24 - 32 496 18 18 - PKZM0-32 BK25/3-PKZ0-E DILM32
3 5 10 10 10 - 16 248 65 65 50 PKZM4-16 BK50/3-PKZ4-E DILM32
5 7½ 15 20 16 - 27 388 65 65 50 PKZM4-25 BK50/3-PKZ4-E DILM32
7½ 10 20 30 24 - 34 496 65 65 50 PKZM4-32 BK50/3-PKZ4-E DILM32
10 - 30 30 32 - 40 620 65 65 50 PKZM4-40 BK50/3-PKZ4-E DILM40
- 15 30 - 40 - 52 775 65 65 - PKZM4-50 BK50/3-PKZ4-E DILM50
- - 40 - 50 - 56 899 65 65 - PKZM4-58 BK50/3-PKZ4-E DILM65
- - 40 - 52 - 58 977 65 65 - PKZM4-63 BK50/3-PKZ4-E DILM65
1) In this range, select motor protector per motor full load current. Refer to NEC Table 430-250.
2) Suitable for solidly grounded power distribution systems. Stand: April 2016

Table 14: Motor-protective circuit-breaker – UL 508 Typ F Combination Starters

22
unknown) due to its stand-alone branch circuit protective functionality of a 3 phase bus connector and the
rating. without the need of additional back-up large spacing BK25/3-PKZ0-E incoming
protection. This version covers motor supply terminal (Figure 8), it’s possible
▶ The amount of necessary layout full load currents up to 28A. (Order to create an array or grouping of open
space is greatly reduced. number for the BK25/3-PKZ0-E mounted Type E controllers for
terminal:262518). The Type E PKZM4 application in industrial control panels.
▶ No assembly and wiring required controller with terminal BK50/3-PKZ4-E The larger electrical clearances in this
between individually mounted starter provides the same starter configuration case are required only on the incoming
components. in a larger size and covers motor full terminal BK25...-E, since this is the
load currents up to 52A. At the time of point at which the controller grouping
▶ Lower component costs this writing the certification process for receives its supply from the feeder
the new electronic PKE controller had portion of the circuit. A wide selection
▶ Lower panel wiring and assembly been initiated. of certified Type E and Type F
charges controllers can be configured in this
The requirements in North America for fashion to suit a broad range of
▶ A design more in line with current this style of controller are not always industrial control panel applications.
control panel technology used regionally identical: This use of modern wiring techniques is
throughout the IEC-world. very much in line with current IEC
–– For applications in the US control panel design and engineering
• Self-Protected Combination methods which cater to a more
Starter MSC-…-…-M…-SP The large electrical clearances are ergonomic and efficient use of space in
required on the device’s incoming engineered assemblies. The need for
The MSC-…-…-M…-SP Self-Protected supply side field wiring terminals. the larger clearance terminal block does
Combination Starter (Figure 6) fulfills When the controller is mounted represent a more stringent requirement
all requirements for Type E controllers. „open“ (i.e. on a mounting plate in a for starters mounted in this particular
This compact combination starter control panel equipped with an configuration, but is really the only issue
consists of a thermal-magnetic manual upstream padlockable main disconnect that differentiates the assembly from a
motor protective switch PKE combined switch) each individual device is not true IEC design. The larger spacing
with a contactor. The PKE manual required to be padlockable. terminal block, moreover, can be used
motor protective portion features the world-wide without any restriction, and
large electrical clearances on its On the other hand, if the self-protected both the terminal and the commoning
incoming supply side field wiring controller is individually enclosed (e.g. bus links from Eaton are fully UL and
terminals in accordance with UL 489. in a Motor Control Center unit or in a CSA certified.
The high capacity magnetic contactor separate CI-..-K-NA insulating material
features a set of current limiting power enclosure) a padlocking feature is • UL 508 Type F Combination Starter
contacts and a customized internal required. That’s because, as an
magnetic trip to provide the Type E individually enclosed combination The UL 508 standard established a
starter’s high level short circuit rating motor starter, the Type E controller “Type F Combination Motor Controller”
and fault clearing capability. assumes the main disconnect and as its most recent category of
isolator functions for the branch circuit, combination motor controller
The self-protected starter’s main design and must thus be padlockable in the constructions: A Type F combination
features include: OFF position. controller consists of a manual self-
protected „Type E“ combination motor
▶ A plug-in, adjustable thermal- –– For applications in Canada controller (e.g. a PKZM0-.. with the
magnetic trip module in line with large clearance terminal block Type
North American motor full load The PKZM0-…, PKE-…or the PKZM4, BK25-..-E) combined with a magnetic or
current ratings, and a high capacity, as Type E manual self-protected solid state contactor (controller). As
high fault current limiting contactor combination controllers per CLASS shown in Figure 9 „Type F
for motor switching purposes that is 3211-08, must always be equipped Combination Motor controllers“ do not
contoured to mould fit directly into with the padlockable knob AK-PKZ0(4) require additional back-up overcurrent
the protective switch portion. for applications in Canada. The larger protective devices in the motor branch
clearances on the switch’s supply side circuit up to the controller’s highest
All system component modules, e.g. terminals, a requirement in the US, are short circuit rating. All combinations
auxiliary contacts, voltage trips and (as of this writing) not necessary in must be UL and CSA certified. (Table
remote control drive are UL listed and Canada, however, they are certainly 14) (Figure 10). As is the case with
CSA certified accessories which can be acceptable when provided. In Canada, Type E controllers, currently certified
field installed (Figure 7). therefore, the PKZM0-.., PKE or PKZM4 Type F controllers are suitable only for
manual Type E controllers can be applications in solidly grounded power
• PKZM0-..+BK25/3-PKZ0-E Manual applied with or without the larger distribution networks at their highest
Type E Self-Protected Combination clearances as stand-alone branch circuit voltage rating (e.g. 480Y/277 V). Please
Controller protective controllers without the need note that „Type F“- combination
for any back-up protection, as long as controllers are not yet recognized by
Even the smaller sized PKZM0 manual they are equipped with the padlockable Canadian standards and are only part of
motor controller, when equipped with knob accessory. US based product standards at this
the BK25/3-PKZ0-E incoming supply time. However, the combinations are
terminal, fulfills the stringent „Type E“-­ By using specialized wiring generally accepted by all CSA and
requirements to provide stand-alone accessories, primarily the combination

23
would combine products from various
manufacturers. Mixed combinations
are also not common in the IEC world
because manufacturers are best able to
verify the electrical coordination and
performance of components of their
own make, particularly with respect to
short circuit testing and determination
of proper overcurrent coordination
performance levels. Product
„Declarations of Conformity“ provided
by manufacturers for their equipment
must, by definition, be current because
they essentially serve as the user’s
verification that a particular product or
assembly reflects the actual ongoing
production quality levels which is in
place at the time the “Declaration of
Conformity” is being issued. Practically
speaking, mixing and matching
Figure 10: Example of a UL 508 Type F combination motor controller array, each con- components of different makes to
sisting of a manual Type E self-protected controller and associated magnetic contactor. produce starters and assemblies would
make it difficult to keep up with
ongoing design changes in
provincial based inspection authorities component manufacturer at a manufacturer products, which could be
throughout Canada. disadvantage but can also be significant in view of the consequences
detrimental to the end-user, since the it may have on short circuit
The capability of a manufacturer or introduction of certain technological coordination values and component
independent panel builder to combine innovations could translate into performance levels.
UL and CSA products and self-certify significant improvements and benefits
the resulting starter or assembly, as is for their own business endeavors. Tap Conductor Protector
done in the IEC world per IEC Because of the very high export quota
regulations, does not exist as such in of European based industrial machinery The „Tap Conductor Protector“ can
North America. It is possible, however, it is also neither practical nor feasible sometimes be an adequate alternative
to have a UL listed or CSA certified for a manufacturer to develop and to the use of stand-alone manual Type
panel shop or manufacturing location introduce new products and E controllers. The controller in that
which is able to label or certify technologies that are not yet certifiable particular configuration does not require
assemblies that are covered by a to North American standards, even the large distribution clearances on its
procedure or file. In the case of UL when a significant portion of this incoming supply terminals which is
508A industrial control panels, it is also equipment is destined for the domestic required for Type E starters. A „base
possible for listed panel builders to EU market and would remain in model“ PKZM0 manual motor
independently access combination Europe. The equipment certification controller can be used for the purpose,
motor starter offerings by multiple process also effectively rules out but only because it has been
manufacturers from UL’s database of customized assembly designs that
short circuit rated controllers in order to
design their own UL 508A assemblies.
It is strongly recommended, therefore,
that manufacturing locations and/or
panel builders work closely with the
component manufacturer for the latest
certification updates and component „Tap Conductor Protector“
rating information, since there are Group protective Ratio of group device rated
always ongoing design improvements device (BCPD)
being developed which could represent current to ampacity of tap
significant technological and conductors:
economical advantages to their
business needs and application PKZM0,  Maximum 10:1
requirements. PKZM4

It is generally accepted that the


equipment certification process is both
necessary and vital for the industry, but = Tapped Conductors
it can also be a timely and cost
intensive undertaking which can often
unduly delay the introduction of new Figure 11: Maximum ratio between the rated current of the Back-up protective switch
products and technology into the and the ampacity of the outgoing motor circuit conductors when using “Tap Conductor
market place. This not only puts the Protectors”.

24
additionally certified by UL for this Validity:
application, and carries the necessary
markings. Both the PKZM0 and PKZM4 This paper reflects the standards and
controllers have been successfully product certification status in effect as
certified by UL in this regard and are of August 2012.
listed as “tap conductor protectors
suitable for group installations” per References:
NEC requirements in motor full load
[1] IEC / EN 60947-4-1 und DIN VDE 0660-102
current ranges of 28 A and 52A resp. @ „Niederspannungsschaltgeraete - Teil 4-1:
480Y/277VAC and 16A and 40A resp. @ Schuetze und Motorstarter - Elektromecha-
600Y/347VAC. nische Schuetze und Motorstarter“ (IEC
60947-4-1:2000 + Corrigendum:2001 +
Tap Conductor Protectors provide A1:2002 + A2:2005); Deutsche Fassung EN
overload and short circuit protection for 60947-4-1:2001 + A1:2002 + A2:2005
outgoing motor circuit conductors, as [2] UL 60 947-4-1A „Low-Voltage Switchgear
well as overload protection for the and Controlgear - Part 4-1: Contactors and
motor-starters - Electromechanical contactors
motor. The drawback is, however, that and motor-starters
the use of a tap conductor protector [3] CSA-C22.2 NO. 60947-4-1-07, „Low-Voltage
does not eliminate the need for a Switchgear and Controlgear - Part 4-1: Con-
back-up (and group) branch circuit tactors and Motor-Starters - Electromechani-
cal Contactors and Motor-Starters”
overcurrent protective device as shown
[4] UL 60 947-1, „Low-Voltage Switchgear and
in Figure 1. Controlgear - Part 1: General rules, third edi-
tion (Edition date: 2007-01-26) “
The use of Tap Conductor Protectors [5] IEC / EN 60 204-1 und EN 60204-1, „Sicher-
means that, as shown in Figure 11 and heit von Maschinen - Elektrische Ausrüstung
von Maschinen - Teil 1: Allgemeine Anforder-
as per NEC requirements, the ratio ungen“ (IEC 60204-1:2005, modifiziert);
between the rating of the branch circuit Deutsche Fassung EN 60204-1:2006
protective device and the ampacity of [6] UL 489, „Molded Case Circuit Breakers,
the tapped conductors cannot exceed Molded Case Switches and Circuit Breaker
Enclosures“
10:1. Example:
[7] CSA-C22.2 No. 5-09, „ Moulded Case Circuit
Breakers“
• The ampacity of an AWG 14- [8] UL 508, „Industrial Control Equipment”
conductor is 15A, [9] CSA-C22.2 No. 14-05, “Industrial Control
• The maximum rating of the group Equipment, Industrial Products”
branch circuit protective device is [10] IEC / EN 60 947-1, „Niederspannungsschalt-
150A and could be accommodated geräte Teil 1: Allgemeine Festlegungen“ (IEC
60947-1:2007); Deutsche Fassung EN 60947-
by a NZM..2-AF150-NA UL listed and 1:2007“
CSA certified molded case circuit [11] IEC / EN 60 947-2, „Niederspannungsschalt-
breaker. geräte - Teil 2: Leistungsschalter“ (IEC
60947-2:2006); Deutsche Fassung EN 60947-
2:2006
Summary of Figure 12 (next page)
[12] NFPA 70E, „Standard for Electrical Safety in
the Workplace, 2009 Edition”
On the next page there is a graphical National Fire Protection Association,
representation of the major starter Quincy, MA, 02169, www.nfpa.org

concepts presented in this paper and


Please take note of additional technical papers
dwells in particular on the significant accessible at the following internet link:
aspects of Construction Types E, F and www.eaton.eu/publications,
the Tap Conductor Protector. To use the These papers are also available in print form and
can be requested in either German or English
chart effectively it’s important to first versions.
determine whether a particular
controller configuration requires a
back-up overcurrent protective device
in the circuit, or if, more in line with IEC
practices, the controller design
eliminates the need for an additional
branch circuit protective in the motor
branch circuit.

25
26
North American Motor Starters in accordance with UL 508 and CSA C 22.2 No. 14
Solution Processing Chart, Search criteria: Favoring fuseless installations and, wherever possible, in line with IEC design solutions.

Main Disconnect and Branch Circuit protective devices Main Disconnect and Branch Circuit protective devices
per UL 489 and CSA C 22.2 No. 5-02 per UL 489 and CSA C 22.2 No. 5-02
are in the supply circuit or intended are not in the supply circuit and not known or
to be provided otherwise separately provided

Combination Motor Starter

Tap Conductor Protector Use of certified perUL 508 and Main Disconnect
components CSA C22.2 No.14 Short Circuit Protection
per UL 508 per UL 508 and Fulfill all 4 main functions
USA only CSA C22.2 No.14 Controller
in a North American motor
for motor controller switching branch circuit: Overload Protection
functions For motor controller
switching functions
for motor overload and circuit
conductor protection for overload protection
Not the main focus of this paper.
Shown for completeness
purposes only. Protection with fuses Fuseless protection (short circuit ratings may vary)

Construction Type " A " Construction Type " B " Construction Type " C " Construction Type " D " Construction Type " E "
Refer to Table 11 for examples No Eaton offering Refer to Table 11 for Refer to Table 11 for Characteristics:
of Eaton offerings in this examples of Eaton offerings examples of Eaton offerings - High short circuit rating
M category. in this category. in this category. - Large electrical clearances on the
component incoming supply side
per UL 508 and
The above construction types are not the main focus of this technical paper and are shown here for completeness purposes only. CSA C22.2 No. 14

Type " E " Combination Motor Controllers

Manually operated Electro-magnetically operated Manually operated


Tap Conductor Protector Self-Protected Starter Manual Self-Protected Starter
PKZM0 PKZM4 High fault rated, compact PKZM0 PKZM4
combination motor controller + Supply terminal + Supply terminal
MSC-DE…-...-SP BK25-..-E BK50-..-E
optional: Commoning link optional: Commoning link
Current range up to 32 A Current range up to 58 A Current range up to 32 A Current range up to 27A Current range up to 58A
AC-Rated Voltage and AC-Rated Voltage and AC-Rated Voltage AC-Rated Voltage and short AC-Rated Voltage and
short circuit rating (SCCR) short circuit rating (SCCR) up to 1,2A: 600Y/347V circuit rating (SCCR) short circuit rating (SCCR)
up to 10 A: 50 kA /600Y/347V up to 40 A: 25 kA /600Y/347V > 1,2A: 480Y/277V up to 10A: 50 kA /600Y/347V up to 40 A: 25 kA /600Y/347V
16 A: 42 kA /480Y/277V 65 kA /480Y/277V Short circuit current rating: 16A: 42 kA /480Y/277V 65 kA /480Y/277V
18 kA /600Y/347V 58 A: 65 kA /480Y/277V 18kA /480Y/277V 20..32A: 18 kA /480Y/277V 58 A: 65 kA /480Y/277V
20..32 A: 18 kA /480Y/277V 14kA /600Y/347V
For solidly grounded networks For solidly grounded networks For solidly grounded wye type 4 wire power distribution systems
Suitable as tap conductor Suitable as tap conductor protector If ratings are insufficient are otherwise unsuitable:
protector in group installations in group installations per the Refer to Table 5 for group installation ratings.
per the 1/10 rule, refer to Diagram 11 1/10 rule, refer to Diagram 11 Conductor protection subject to the 1/3 rule per Diagram 3

M M Electro-magnetically operated starters M M M

Type " F " Combination Motor Starters


per UL 508 (USA only at this time)

PKZM0 PKZM4
+ Commoning link + Commoning link
+ Supply terminal + Supply terminal
BK25-..-E BK50-..-E
+ Contactor + Contactor

PKZM0 + DIL EM PKZM0 + DILM7,9,12 PKZM0 + DILM15,17,25,32 PKZM4 + DILM32-65


Current range up to 6,3 A Current range up to 11 A Current range up to 32 A Current range up to 58 A
AC-Rated Voltage and AC-Rated Voltage and AC-Rated Voltage and AC-Rated Voltage and
short circuit rating (SCCR): short circuit rating (SCCR): short circuit rating (SCCR): short circuit rating (SCCR):
50 kA /600Y/347V 18 kA /600Y/347V 15 A: 50 kA /480Y/277V 65 kA /480Y/277V
50 kA /480Y/277V 65 kA /480Y/277V 17..32 A: 18 kA /480Y/277V bis 40 A: 50 kA /600Y/347V

For solidly grounded wye type 4 wire power distribution systems


If ratings are insufficient are otherwise unsuitable:
Refer to Table 5 for group installation ratings. Conductor protection subject to the 1/3 rule per Diagram 3

Note:
This table does not yet include motor-protective circuit-breaker
M M M M PKE and starter variants with the PKE. A separate publication
will be issued on completion of the approvals.

27
Useful Tables

Table 310-16. Allowable Ampacities of Insulated Conductors Rated


0 through 2000 Volts, 60° to 90°C (140° to 194°F)
Not More Than Three Current-Carrying Conductors in Raceway or Cable or
Earth (Directly Buried), Based on Ambient Temperature of 30°C (86°F)
Size Temperature Rating of Conductor. See Table 310-13 Size
60°C 75°C 90°C 60°C 75°C 90°C
(140°F) (167°F) (194°F) (140°) (167°F) 194°F)
(

Types Types Types Types Types Types


TWA, FEPWA, TBS, SA TWA, RHA, RHWA TBS,
UFA RHA, RHWA SIS, FEPA, UFA THHWA, SA, SIS,
THHWA, FEPBA, MI THWA, THHNA,
THWA, RHHA, RHW-2, THWNA, THHWA,
THWNA, THHNA, XHHWA THW-2A,
AWG XHHWA THHWA, USEA THWN-2A AWG
kcmil USEA, ZWA THW-2A, RHHA kcmil
THWN-2A RHW-2,
USE-2, XHH, USE-2,
XHHWA XHH, XHHW,
XHHW-2, XHHW-2,
ZW-2 ZW-2
Copper Aluminum or Copper-Clad Aluminum
18 .... .... 14 .... .... .... ....
16 .... .... 18 .... .... .... .... Table 110.20. Motor Controller Enclosure Selection Table
14 20A 20A 25A .... .... .... ....
12 25A 25A 30A 20A 20A 25A 12 For Outdoor Use
10 30 35A 40A 25 30A 35A 10 Provides a Degree of Protection Enclosure Type Number A
8 40 50 55 30 40 45 8 Against the Following
6 55 65 75 40 50 60 6 Environmental Conditions 3 3R 3S 4 4X 6 6P
4 70 85 95 55 65 70 4
3 85 100 110 65 75 85 3 Incidental contact with the
2 95 115 130 75 90 100 2 enclosed equipment X X X X X X X
1 110 130 150 85 100 115 1 Rain, snow and sleet X X X X X X X
1/0 125 150 170 100 120 135 1/0 Sleet* - - X - - - -
2/0 145 175 195 115 135 150 2/0
3/0 165 200 225 130 155 175 3/0 Windblown dust X - X X X X X
4/0 195 230 260 150 180 205 4/0 Hosedown - - - X X X X
250 215 255 290 170 205 230 250 Corrosive agents - - - - X - X
300 240 285 320 190 230 255 300 Occasional temporary submersion - - - - - X X
350 260 310 350 210 250 280 350
400 280 335 380 225 270 305 400 Occasional prolonged submersion - - - - - - X
500 320 380 430 260 310 350 500 *Mechanism shall be operable when ice covered
600 355 420 475 285 340 385 600
700 385 460 520 310 375 420 700 For Indoor Use
750 400 475 535 320 385 435 750
800 410 490 555 330 395 450 800 Provides a Degree of Protection Enclosure Type Number A
900 435 520 585 355 425 480 900 Against the Following
1000 455 545 615 375 445 500 1000 Environmental Conditions 1 2 4 4X 5 6 6P 12 12K 13
1250 495 590 665 405 485 545 1250
1500 520 625 705 435 520 585 1500 Incidental contact with the
1750 545 650 735 455 545 615 1750 enclosed equipment X X X X X X X X X X
2000 560 665 750 470 560 630 2000 Falling dirt X X X X X X X X X X
CORRECTION F ACT ORS Falling liquids and light splashing - X X X X X X X X X
Ambient For ambient temperatures other than 30°C (86°F), multiply the allowable ampacities Ambient
Temp°C shown above by the appropriate factor shown below. Temp°F Circulating dust, lint, fibers,
21-25 1.08 1.05 1.04 1.08 1.05 1.04 70-77
and flyings - - X X - X X X X X
26-30 1.00 1.00 1.00 1.00 1.00 1.00 78-86 Settling airborne dust, lint,
31-35 .91 .94 .96 .91 .94 .96 87-95 fibers and flyings - - X X X X X X X X
36-40 .82 .88 .91 .82 .88 .91 96-104 Hosedown and splashing water - - X X - X X - - -
41-45 .71 .82 .87 .71 .82 .87 105-113 Oil and coolant seepage - - - - - - - X X X
46-50 .58 .75 .82 .58 .75 .82 114-122
51-55 .41 .67 .76 .41 .67 .76 123-131 Oil or coolant spraying and
56-60 .... .58 .71 .... .58 .71 132-140 splashing - - - - - - - - - X
61-70 .... .33 .58 .... .33 .58 141-158 Corrosive agents - - - X - - X - - -
71-80 .... .... .41 .... .... .41 159-176 Occasional temporary submersion - - - - - X X - - -
AUnless otherwise specifically permitted elsewhere in thiscode, the overcurrent protection for conductor types Occasional prolonged submersion - - - - - - X - - -
marked with an obelisk (A) shall not exceed 15 amperes for No. 14, 20 amperes for No. 12, and 30 amperes for
No. 10 copper; or 15 amperes for No. 12 and 25 amperes for No. 10 aluminum and copper-clad aluminum after A Enclosure type number shall be marked on the motor controller enclosure.
any correction factors for ambient temperature and number of conductors have been applied.

28
Useful Tables

Table A (millimeters to inches) Table B


mm inches mm inches mm inches mm inches mm inches mm inches fraction decimal fraction
decimal equivalent equivalent
1 0.0393 26 1.0236 51 2.0078 76 2.9921 105 4.1338 260 10.2362
2 0.0787 27 1.0629 52 2.0472 77 3.0315 110 4.3307 270 10.6299 0.0156 1/64 0.5156 33/64
3 0.1181 28 1.1023 53 2.0866 78 3.0708 115 4.5275 280 11.0236 0.0312 1/32 0.5312 17/32
4 0.1574 29 1.1417 54 2.1259 79 3.1102 120 4.7244 290 11.4173 0.0469 3/64 0.5469 35/64
5 0.1968 30 1.1811 55 2.1653 80 3.1496 125 4.9212 300 11.811 0.0625 1/16 0.5625 9/16
0.0781 5/64 0.5781 37/64
6 0.2362 31 1.2204 56 2.2047 81 3.1889 130 5.1181 325 12.7952
7 0.2755 32 1.2598 57 2.2440 82 3.2283 135 5.3149 350 13.7795 0.0937 3/32 0.5937 19/32
8 0.3149 33 1.2992 58 2.2834 83 3.2677 140 5.5118 375 14.7637 0.1094 7/64 0.6094 39/64
9 0.3543 34 1.3385 59 2.3228 84 3.3070 145 5.7086 400 15.748 0.125 1/8 0.625 5/8
10 0.3937 35 1.3779 60 2.3622 85 3.3464 150 5.9055 425 16.7322 0.1406 9/64 0.6406 41/64
0.1562 5/32 0.6562 21/32
11 0.4330 36 1.4173 61 2.4015 86 3.3858 155 6.1023 450 17.7165
12 0.4724 37 1.4566 62 2.4409 87 3.4252 160 6.2992 475 18.7007 0.1719 11/64 0.6719 43/64
13 0.5118 38 1.4960 63 2.4803 88 3.4645 165 6.4960 500 19.685 0.1875 3/16 0.6875 11/16
14 0.5511 39 1.5354 64 2.5196 89 3.5039 170 6.6929 525 20.6692 0.2031 13/64 0.7031 45/64
15 0.5905 40 1.5748 65 2.5590 90 3.5433 175 6.8897 550 21.6535 0.2187 7/32 0.7187 23/32
0.2344 15/64 0.7344 47/64
16 0.6299 41 1.6141 66 2.5984 91 3.5826 180 7.0866 575 22.6377
17 0.6692 42 1.6535 67 2.6378 92 3.6220 185 7.2834 600 23.622 0.25 14 0.75 3/4
18 0.7086 43 1.6929 68 2.6771 93 3.6614 190 7.4803 650 25.5905 0.2656 17/64 0.7656 49/64
19 0.7480 44 1.7322 69 2.7165 94 3.7007 195 7.6771 700 27.559 0.2812 9/32 0.7812 25/32
20 0.7874 45 1.7716 70 2.7559 95 3.7401 200 7.874 750 29.5275 0.2969 19/64 0.7969 51/64
0.3125 5/16 0.8125 13/16
21 0.8267 46 1.8110 71 2.7952 96 3.7795 210 8.2677 800 31.496
22 0.8661 47 1.8503 72 2.8346 97 3.8189 220 8.6614 850 33.4645 0.3281 21/64 0.8281 53/64
23 0.9055 48 1.8897 73 2.8740 98 3.8582 230 9.0551 900 35.433 0.3437 11/32 0.8437 27/32
24 0.9448 49 1.9291 74 2.9133 99 3.8976 240 9.4488 950 37.4015 0.3594 23/64 0.8594 55/64
25 0.9842 50 1.9685 75 2.9527 100 3.937 250 9.8425 1000 39.37 0.375 3/8 0.875 7/8
0.3906 25/64 0.8906 57/64
How to use conversion table A and B
To convert millimeters to inches: 0.4062 13/32 0.9062 29/32
0.4219 27/64 0.9219 59/64
a) 27 mm - from table A, 27 mm = 1.0629" 0.4375 7/16 0.9375 15/16
+ from table B, 0.0629 = 1/16" Therefore 27 mm = 1-1/16" 0.4531 29/64 0.9531 61/64
b) 295 mm - from table A, 290 mm = 11.4173" 0.4687 15/32 0.9687 31/32
+ 5 mm = 0.1968" 0.4844 31/64 0.9844 63/64
+ from Table B, 0.6141 = 39/64" Therefore 295 mm = 11-39/64" 0.5 1/2 1.0 1

To convert to... multiply by....


Atmospheres pounds per square inch 14.7
Cubic centimeters cubic inches 0.06102 BP-212
Cubic Inches cubic centimeters 16.39 200 100
Feet meters 0.3048
liters 4.546 190 90
Gallons (Br. imp.)
Gallons (U.S.) liters 3.785 180
170 80
Grams ounces (avoirdupois) 0.0353 160
HP kilowatts 0.7457 150 70
Kilograms pounds 2.205 140
Kilograms tons (2,000 lb) 0.001102
130 60
kilograms tons (2,240 lb) 0.0009842
120 50
Kilometers miles 0.6214 110
Kilowatts HP 1.341 100 40
Joules calories 0.239 90
Liters gallons (Br. imp.) 0.220 80 30
Liters gallons (U.S.) 0.2642
feet 3.281 70 20
Meters
60
Meters yards 1.094 50 10
Miles kilometers 1.609 40
Millimeters inches 0.03937 FP- 30 0
Newton (force) pounds 0.2248 20
Ounces (avoirdupois) grams 28.349
10 -10
Pounds kilograms 0.4536 0 -20
Tons (2,000 lb) kilograms 907.18
Tons (2,240 lb) kilograms 1016.0 F° C°
Yards meters 0.9144

Newton meter foot-pounds .737

29
At Eaton, we’re energized by the challenge of powering a world
that demands more. With over 100 years experience in electrical
power management, we have the expertise to see beyond today.
From groundbreaking products to turnkey design and engineering
services, critical industries around the globe count on Eaton.

We power businesses with reliable, efficient and safe electrical


power management solutions. Combined with our personal
service, support and bold thinking, we are answering tomorrow’s
needs today. Follow the charge with Eaton. Visit eaton.eu.

To contact an Eaton salesperson


or local distributor/agent, please visit
www.eaton.eu/electrical/customersupport

Eaton Industries GmbH


Hein-Moeller-Str. 7–11
D-53115 Bonn / Germany Eaton is a registered trademark of Eaton
© 2016 by Eaton Corporation Corporation
All rights reserved All other trademarks are property of their
Printed in Germany 04/16 respective owners.
Publication No.: VER1210+1280-928EN