A bipolar 2 terminal HVDC Transmission System has a 12 pulse converter per pole at each terminal.
The systemhas following data :
Rated DC voltage Ud = ± 500 kV. Rated bipolar power = 1500 MW. Line resistanve per pole = 5 ohms.
DC voltage at rectifier end = ± 500 kV. Rectifier terminal feeds rated power in DC line.
Calculate the following : 5. DC voltage of 6 pulse converter at rectifier-
1. DC line current end
2. DC line losses 6. DC voltage of 6 pulse converter at inverter-
3. Inverter-end DC voltage end
4. DC power delivered to inverter-end
Solusi :
1. Rated power per pole = Pd = 1500/2 = 750 MW
Rated DC current = Id = Pd/Ud = 750MW/500kV = 1500 A.
As line on rated load, Id = 1500 A.
2. DC line losses per pole =Px = Id2R = 15002x5 = 11,25 MW.
Rectifier-end DC power Pd1 = 750 MW per pole (given)
Inverter DC power Pd2 = Pd1 – Px = 750 – 11,25 MW = 738,75 MW.
Bipolar DC power at inverter-end = 2 x 738,75 = 1477,50 MW.
3. DC voltage inverter-end per pole = Ud2 =Ud1 – Id.R = 500 kV – 1500.5 = 492,5 kV DC.
4. DC power delivered to inverter-end = 738,75 MW
5. DC voltage of 6 pulse bridge = 0,5 x voltage of 12 pulse bridge
DC voltage of 6 pulse converter at rectifier-end = 500/2 = 250 kV.
6. DC voltage of 6 pulse converter at inverter-end = 492,5 kV/2 = 246,25 kV.