DISEÑO DEL REFUERZO PARA VIGAS CONTINUAS DE CIMENTACION

ACERO LONGITUDINAL
VIGAS CONTINUAS DE CIMENTACION EJE FD-FA
1. Colocar dimensiones de la viga continua

50.0 cm
9 Ø 3/4 '' As Positivo 8.83 cm² Verificar As min y As max
77.0 cm
2 Ø 1/2" Para evitar el pandeo del estribo
24.05 cm²

73.0 cm
As Negativo 11.19 cm² Verificar As min y As max
13 Ø 5/8 '' 250.0 cm

24.05 cm²

2. Colocar Diametro de Barra Longitudinal asumida, Estribo y Momento.


REFUERZO POSITIVO REFUERZO NEGATIVO ACERO MINIMO:
f`c = 210.00 Kg/cm2 f`c = 210.00 Kg/cm2 ρ min = 0.0033
fy = 4200.00 Kg/cm2 fy = 4200.00 Kg/cm2 As min = 24.05 cm² 120.25
b = 250.00 cm b = 50.00 cm Ø barra = 5/8 ''
h = 150.00 cm h = 150.00 cm As = 1.979 cm²
Ø barra = 5/8 '' Ø barra = 5/8 '' Tomamos 13 Ø 5/8 ''
Ø estribo = 3/8 '' Ø estribo = 3/8 '' ACERO MAXIMO
recub. = 2.50 cm recub. = 7.50 cm ρmax = 0.0163
d = 145.75 cm d = 140.75 cm As max = 118.55 cm²
M = 48.53 Tn-m M = 58.40 Tn-m Ø barra = 5/8 ''
a = 0.831 cm a = 5.264 cm As = 1.979 cm²
As = 8.83 cm² As = 11.19 cm² Tomamos 60 Ø 5/8 ''

3. Aceros Negativos y Positivos Finales


ACERO POSITIVO ACERO NEGATIVO
As Positivo 24.05 cm² As Negativo 24.05 cm² 0.43
Ø barra = 3/4 '' Ø barra = 5/8 ''
As = 2.850 cm² As = 1.979 cm²
Tomamos 9 Ø 3/4 '' Tomamos 13 Ø 5/8 '' 41.75
ACERO TRANSVERSAL
sadm Suelo = 25.000 Tn/m² REFUERZO NEGATIVO
s diseño = 37.500 Tn/m² f`c = 210.00 Kg/cm2
Tomando B = 1.00 m □Ø 3/8 '' @ 0.3 fy = 4200.00 Kg/cm2
Mom. Neg = 18.75 Tn-m b = 100.00 cm
50.0 cm h = 73.00 cm
Ø barra = 5/8 ''
77.0 cm 5/8 '' @ 0.25 Ø estribo = 3/8 ''
recub. = 7.50 cm
100.0 cm d = 63.75 cm
M = 18.75 Tn-m
73.0 cm a = 1.858 cm
As = 7.90 cm²
250.0 cm Ø barra = 5/8 ''
As = 1.979 cm²
37.50 Tn/m @= 25.00
VERIFICACION POR CORTANTE
Vu = 25.000 Tn A cara de columna Ø.Vc = Vud =
Wu = 1.49 Tn/m 104.311 Tn > 24.051 Tn Ok
recub. = 7.50 cm
Ø barra = 1/2 ''
Ø estribo = 3/8 ''
b= 250.00 cm
d= 63.91 cm
DISEÑO DE REFUERZO TRANSVERSAL
REFUERZO DENTRO DE LA ZONA DE CONFINAMIENTO
Se colocará refuerzo Transversal por confinamiento a una distancia "2d" medida desde la cara del apoyo.
2d = 2.815 m
Ø estribo = 3/8 ''
La separacion de los estribos debe ser:
S ≤ d/4 = 35.19 cm S = 30.00 cm □Ø 3/8 '' @ 0.3
S ≤ 30.00 cm

REFUERZO FUERA DE LA ZONA DE CONFINAMIENTO


La separacion de los estribos debe ser:
S= 70.00 cm □Ø 3/8 '' @ 0.7
DISEÑO DEL REFUERZO PARA VIGAS CONTINUAS DE CIMENTACION
ACERO LONGITUDINAL
VIGAS CONTINUAS DE CIMENTACION EJE FD-FA
1. Colocar dimensiones de la viga continua

50.0 cm
9 Ø 3/4 '' As Positivo 14.77 cm² Verificar As min y As max
77.0 cm
2 Ø 1/2" Para evitar el pandeo del estribo
24.05 cm²

73.0 cm
As Negativo 29.66 cm² Cumple con As min y As max
6 Ø 1/1 '' 250.0 cm

29.66 cm²

2. Colocar Diametro de Barra Longitudinal asumida, Estribo y Momento.


REFUERZO POSITIVO REFUERZO NEGATIVO ACERO MINIMO:
f`c = 210.00 Kg/cm2 f`c = 210.00 Kg/cm2 ρ min = 0.0033
fy = 4200.00 Kg/cm2 fy = 4200.00 Kg/cm2 As min = 24.05 cm² 120.25
b = 250.00 cm b = 50.00 cm Ø barra = 5/8 ''
h = 150.00 cm h = 150.00 cm As = 1.979 cm²
Ø barra = 5/8 '' Ø barra = 5/8 '' Tomamos 13 Ø 5/8 ''
Ø estribo = 3/8 '' Ø estribo = 3/8 '' ACERO MAXIMO
recub. = 2.50 cm recub. = 7.50 cm ρmax = 0.0163
d = 145.75 cm d = 140.75 cm As max = 118.55 cm²
M = 81.00 Tn-m M = 150.00 Tn-m Ø barra = 5/8 ''
a = 1.390 cm a = 13.959 cm As = 1.979 cm²
As = 14.77 cm² As = 29.66 cm² Tomamos 60 Ø 5/8 ''

3. Aceros Negativos y Positivos Finales


ACERO POSITIVO ACERO NEGATIVO
As Positivo 24.05 cm² As Negativo 29.66 cm² 0.43
Ø barra = 3/4 '' Ø barra = 1/1 ''
As = 2.850 cm² As = 5.067 cm²
Tomamos 9 Ø 3/4 '' Tomamos 6 Ø 1/1 '' S 41.75
ACERO TRANSVERSAL
sadm Suelo = 25.000 Tn/m² REFUERZO NEGATIVO
s diseño = 37.500 Tn/m² f`c = 210.00 Kg/cm2
Tomando B = 1.00 m □Ø 3/8 '' @ 0.3 fy = 4200.00 Kg/cm2
Mom. Neg = 18.75 Tn-m b = 100.00 cm
50.0 cm h = 73.00 cm
Ø barra = 5/8 ''
77.0 cm 5/8 '' @ 0.25 Ø estribo = 3/8 ''
recub. = 7.50 cm
100.0 cm d = 63.75 cm
M = 18.75 Tn-m
73.0 cm a = 1.858 cm
As = 7.90 cm²
250.0 cm Ø barra = 5/8 ''
As = 1.979 cm²
37.50 Tn/m @= 25.00
VERIFICACION POR CORTANTE
Vu = 25.000 Tn A cara de columna Ø.Vc = Vud =
Wu = 1.49 Tn/m 104.311 Tn > 24.051 Tn Ok
recub. = 7.50 cm
Ø barra = 1/2 ''
Ø estribo = 3/8 ''
b= 250.00 cm
d= 63.91 cm
DISEÑO DE REFUERZO TRANSVERSAL
REFUERZO DENTRO DE LA ZONA DE CONFINAMIENTO
Se colocará refuerzo Transversal por confinamiento a una distancia "2d" medida desde la cara del apoyo.
2d = 2.815 m
Ø estribo = 3/8 ''
La separacion de los estribos debe ser:
S ≤ d/4 = 35.19 cm S = 30.00 cm □Ø 3/8 '' @ 0.3
S ≤ 30.00 cm

REFUERZO FUERA DE LA ZONA DE CONFINAMIENTO


La separacion de los estribos debe ser:
S= 70.00 cm □Ø 3/8 '' @ 0.7
DISEÑO DEL REFUERZO PARA VIGAS CONTINUAS DE CIMENTACION
ACERO LONGITUDINAL
VIGAS CONTINUAS DE CIMENTACION EJE FD-FA
1. Colocar dimensiones de la viga continua

50.0 cm
13 Ø 5/8 '' As Positivo 18.19 cm² Verificar As min y As max
77.0 cm
2 Ø 1/2" Para evitar el pandeo del estribo
24.05 cm²

73.0 cm
As Negativo 56.91 cm² Cumple con As min y As max
12 Ø 1/1 '' 250.0 cm

56.91 cm²

2. Colocar Diametro de Barra Longitudinal asumida, Estribo y Momento.


REFUERZO POSITIVO REFUERZO NEGATIVO ACERO MINIMO:
f`c = 210.00 Kg/cm2 f`c = 210.00 Kg/cm2 ρ min = 0.0033
fy = 4200.00 Kg/cm2 fy = 4200.00 Kg/cm2 As min = 24.05 cm² 120.25
b = 250.00 cm b = 50.00 cm Ø barra = 5/8 ''
h = 150.00 cm h = 150.00 cm As = 1.979 cm²
Ø barra = 5/8 '' Ø barra = 5/8 '' Tomamos 13 Ø 5/8 ''
Ø estribo = 3/8 '' Ø estribo = 3/8 '' ACERO MAXIMO
recub. = 2.50 cm recub. = 7.50 cm ρmax = 0.0163
d = 145.75 cm d = 140.75 cm As max = 118.55 cm²
M = 99.63 Tn-m M = 274.00 Tn-m Ø barra = 5/8 ''
a = 1.712 cm a = 26.783 cm As = 1.979 cm²
As = 18.19 cm² As = 56.91 cm² Tomamos 60 Ø 5/8 ''

3. Aceros Negativos y Positivos Finales


ACERO POSITIVO ACERO NEGATIVO
As Positivo 24.05 cm² As Negativo 56.91 cm² 0.43
Ø barra = 5/8 '' Ø barra = 1/1 ''
As = 1.979 cm² As = 5.067 cm²
Tomamos 13 Ø 5/8 '' Tomamos 12 Ø 1/1 '' 27.8333333
ACERO TRANSVERSAL
sadm Suelo = 25.000 Tn/m² REFUERZO NEGATIVO
s diseño = 37.500 Tn/m² f`c = 210.00 Kg/cm2
Tomando B = 1.00 m □Ø 3/8 '' @ 0.3 fy = 4200.00 Kg/cm2
Mom. Neg = 18.75 Tn-m b = 100.00 cm
50.0 cm h = 73.00 cm
Ø barra = 5/8 ''
77.0 cm 5/8 '' @ 0.25 Ø estribo = 3/8 ''
recub. = 7.50 cm
100.0 cm d = 63.75 cm
M = 18.75 Tn-m
73.0 cm a = 1.858 cm
As = 7.90 cm²
250.0 cm Ø barra = 5/8 ''
As = 1.979 cm²
37.50 Tn/m @= 25.00
VERIFICACION POR CORTANTE
Vu = 25.000 Tn A cara de columna Ø.Vc = Vud =
Wu = 1.49 Tn/m 104.311 Tn > 24.051 Tn Ok
recub. = 7.50 cm
Ø barra = 1/2 ''
Ø estribo = 3/8 ''
b= 250.00 cm
d= 63.91 cm
DISEÑO DE REFUERZO TRANSVERSAL
REFUERZO DENTRO DE LA ZONA DE CONFINAMIENTO
Se colocará refuerzo Transversal por confinamiento a una distancia "2d" medida desde la cara del apoyo.
2d = 2.815 m
Ø estribo = 3/8 ''
La separacion de los estribos debe ser:
S ≤ d/4 = 35.19 cm S = 30.00 cm □Ø 3/8 '' @ 0.3
S ≤ 30.00 cm

REFUERZO FUERA DE LA ZONA DE CONFINAMIENTO


La separacion de los estribos debe ser:
S= 70.00 cm □Ø 3/8 '' @ 0.7
DISEÑO DEL REFUERZO PARA VIGAS CONTINUAS DE CIMENTACION
ACERO LONGITUDINAL
VIGAS CONTINUAS DE CIMENTACION EJE F10-F6
1. Colocar dimensiones de la viga continua

30.0 cm
4 Ø 3/4 '' As Positivo 9.20 cm² Cumple con As min y As max
80.0 cm
2 Ø 1/2" Para evitar el pandeo del estribo
9.20 cm²

40.0 cm
As Negativo 14.93 cm² Cumple con As min y As max
8 Ø 5/8 '' 180.0 cm

14.93 cm²

2. Colocar Diametro de Barra Longitudinal asumida, Estribo y Momento.


REFUERZO POSITIVO REFUERZO NEGATIVO ACERO MINIMO:
f`c = 210.00 Kg/cm2 f`c = 210.00 Kg/cm2 ρ min = 0.0024
fy = 4200.00 Kg/cm2 fy = 4200.00 Kg/cm2 As min = 8.40 cm²
b = 180.00 cm b = 30.00 cm Ø barra = 3/4 ''
h = 120.00 cm h = 120.00 cm As = 2.850 cm²
Ø barra = 1/2 '' Ø barra = 1/2 '' Tomamos 3 Ø 3/4 ''
Ø estribo = 3/8 '' Ø estribo = 3/8 '' ACERO MAXIMO
recub. = 2.50 cm recub. = 7.50 cm ρmax = 0.0163
d = 115.91 cm d = 110.91 cm As max = 56.57 cm²
M = 40.08 Tn-m M = 59.29 Tn-m Ø barra = 3/4 ''
a = 1.202 cm a = 11.710 cm As = 2.850 cm²
As = 9.20 cm² As = 14.93 cm² Tomamos 20 Ø 3/4 ''

3. Aceros Negativos y Positivos Finales


ACERO POSITIVO ACERO NEGATIVO
As Positivo 9.20 cm² As Negativo 14.93 cm² 0.43
Ø barra = 3/4 '' Ø barra = 5/8 ''
As = 2.850 cm² As = 1.979 cm²
Tomamos 4 Ø 3/4 '' Tomamos 8 Ø 5/8 ''
ACERO TRANSVERSAL
sadm Suelo = 15.000 Tn/m² REFUERZO NEGATIVO
s diseño = 22.500 Tn/m² f`c = 210.00 Kg/cm2
Tomando B = 1.00 m □Ø 3/8 '' @ 0.27 fy = 4200.00 Kg/cm2
Mom. Neg = 6.33 Tn-m b = 100.00 cm
30.0 cm h = 40.00 cm
Ø barra = 1/2 ''
80.0 cm 1/2 '' @ 0.225 Ø estribo = 3/8 ''
recub. = 7.50 cm
75.0 cm d = 30.91 cm
M = 6.33 Tn-m
40.0 cm a = 1.302 cm
As = 5.53 cm²
180.0 cm Ø barra = 1/2 ''
As = 1.267 cm²
22.50 Tn/m @= 22.50
VERIFICACION POR CORTANTE
Vu = 25.000 Tn A cara de columna Ø.Vc = Vud =
Wu = 1.49 Tn/m 36.325 Tn > 24.541 Tn Ok
recub. = 7.50 cm
Ø barra = 1/2 ''
Ø estribo = 3/8 ''
b= 180.00 cm
d= 30.91 cm
DISEÑO DE REFUERZO TRANSVERSAL
REFUERZO DENTRO DE LA ZONA DE CONFINAMIENTO
Se colocará refuerzo Transversal por confinamiento a una distancia "2d" medida desde la cara del apoyo.
2d = 2.218 m
Ø estribo = 3/8 ''
La separacion de los estribos debe ser:
S ≤ d/4 = 27.73 cm S = 27.00 cm □Ø 3/8 '' @ 0.27
S ≤ 30.00 cm

REFUERZO FUERA DE LA ZONA DE CONFINAMIENTO


La separacion de los estribos debe ser:
S= 55.00 cm □Ø 3/8 '' @ 0.55
DISEÑO DEL REFUERZO PARA VIGAS CONTINUAS DE CIMENTACION - CONECTADAS
ACERO LONGITUDINAL
VIGAS CONTINUAS DE CIMENTACION EJE FB-FC
1. Colocar dimensiones de la viga continua

30.0 cm
3 Ø 3/4 '' As Positivo 5.01 cm² Verificar As min y As max
80.0 cm
2 Ø 1/2" Para evitar el pandeo del estribo
8.40 cm²

40.0 cm
As Negativo 11.52 cm² Cumple con As min y As max
10 Ø 1/2 '' 180.0 cm

11.52 cm²

2. Colocar Diametro de Barra Longitudinal asumida, Estribo y Momento.


REFUERZO POSITIVO REFUERZO NEGATIVO ACERO MINIMO:
f`c = 210.00 Kg/cm2 f`c = 210.00 Kg/cm2 ρ min = 0.0024
fy = 4200.00 Kg/cm2 fy = 4200.00 Kg/cm2 As min = 8.40 cm²
b = 180.00 cm b = 30.00 cm Ø barra = 3/4 ''
h = 120.00 cm h = 120.00 cm As = 2.850 cm²
Ø barra = 1/2 '' Ø barra = 1/2 '' Tomamos 3 Ø 3/4 ''
Ø estribo = 3/8 '' Ø estribo = 3/8 '' ACERO MAXIMO
recub. = 2.50 cm recub. = 7.50 cm ρmax = 0.0163
d = 115.91 cm d = 110.91 cm As max = 56.57 cm²
M = 21.90 Tn-m M = 46.33 Tn-m Ø barra = 3/4 ''
a = 0.655 cm a = 9.035 cm As = 2.850 cm²
As = 5.01 cm² As = 11.52 cm² Tomamos 20 Ø 3/4 ''

3. Aceros Negativos y Positivos Finales


ACERO POSITIVO ACERO NEGATIVO
As Positivo 8.40 cm² As Negativo 11.52 cm² 0.43
Ø barra = 3/4 '' Ø barra = 1/2 ''
As = 2.850 cm² As = 1.267 cm²
Tomamos 3 Ø 3/4 '' Tomamos 10 Ø 1/2 ''
ACERO TRANSVERSAL
sadm Suelo = 15.000 Tn/m² REFUERZO NEGATIVO
s diseño = 22.500 Tn/m² f`c = 210.00 Kg/cm2
Tomando B = 1.00 m □Ø 3/8 '' @ 0.27 fy = 4200.00 Kg/cm2
Mom. Neg = 6.33 Tn-m b = 100.00 cm
30.0 cm h = 40.00 cm
Ø barra = 1/2 ''
80.0 cm 1/2 '' @ 0.225 Ø estribo = 3/8 ''
recub. = 7.50 cm
75.0 cm d = 30.91 cm
M = 6.33 Tn-m
40.0 cm a = 1.302 cm
As = 5.53 cm²
180.0 cm Ø barra = 1/2 ''
As = 1.267 cm²
22.50 Tn/m @= 22.50
VERIFICACION POR CORTANTE
Vu = 25.000 Tn A cara de columna Ø.Vc = Vud =
Wu = 1.49 Tn/m 36.325 Tn > 24.541 Tn Ok
recub. = 7.50 cm
Ø barra = 1/2 ''
Ø estribo = 3/8 ''
b= 180.00 cm
d= 30.91 cm
DISEÑO DE REFUERZO TRANSVERSAL
REFUERZO DENTRO DE LA ZONA DE CONFINAMIENTO
Se colocará refuerzo Transversal por confinamiento a una distancia "2d" medida desde la cara del apoyo.
2d = 2.218 m
Ø estribo = 3/8 ''
La separacion de los estribos debe ser:
S ≤ d/4 = 27.73 cm S = 27.00 cm □Ø 3/8 '' @ 0.27
S ≤ 30.00 cm

REFUERZO FUERA DE LA ZONA DE CONFINAMIENTO


La separacion de los estribos debe ser:
S= 55.00 cm □Ø 3/8 '' @ 0.55