NPE Series Application Drawings

G H C G H C G H C

NPE-240S NPE-210S NPE-180S


Guide Only Storage Check Valve Circulator

These drawing are intended as a guide only and not as a replacement for Vessel
Pressure
20 Goodyear professionally engineered project drawings. These concept system Relief
Valve
drawings do not imply compliance with local building codes. Actual Expansion
Irvine, CA 92618 Tank
installations may vary depending on installation location & parameters Mixing
800-519-8794 and it must be done in accordance with all local building codes. Verify with Valve

www.Navien.com DHW Circulator Full-port T Aquastat


w/Aquastat & Check Valve Ball Valve
This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.
This concept system drawing does not imply compliance with local building codes. Actual installation may vary
depending on installation location & parameters and it must be done in accordance to all local building codes.
Verify with local building officials before commencement of system installation.

G H C

Domestic Hot Water Condensate


Gas

Domestic Cold Water

NPE-S Series Tankless Water Heater Check Valve Circulator


Storage
Vessel
Pressure
20 Goodyear One NPE-S Tankless Relief
Valve Expansion
Irvine, CA 92618 (Includes NPE-A, Internal Circulation Mode) Mixing
Tank

800-519-8794 Valve

www.Navien.com
T Aquastat
DHW Circulator Full-port
Drawn By: B. Fenske NPE-S-1-BF02 August 1, 2013 w/Aquastat & Check Valve Ball Valve
This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.
This concept system drawing does not imply compliance with local building codes. Actual installation may vary
depending on installation location & parameters and it must be done in accordance to all local building codes.
Verify with local building officials before commencement of system installation.

Communication
Cable

G H C G H C

Condensate

Gas
Domestic Cold Water
Domestic Hot Water

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater Check Valve Circulator


Storage
Vessel
Pressure
20 Goodyear Two NPE-S Tankless Relief
Valve Expansion
Irvine, CA 92618 (Includes NPE-A Internal Circulation Mode) Mixing
Tank

800-519-8794 Valve

www.Navien.com
T Aquastat
DHW Circulator Full-port
Drawn By: B. Fenske NPE-S-2-I-BF02 August 1, 2013 w/Aquastat & Check Valve Ball Valve
This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.
This concept system drawing does not imply compliance with local building codes. Actual installation may vary
depending on installation location & parameters and it must be done in accordance to all local building codes.
Verify with local building officials before commencement of system installation.

Low Temp
Domestic Hot Water Communication
Cable

G H C G H C
M
H C

Condensate

Gas
Domestic Cold Water
High Temp
Domestic Hot Water

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater Check Valve Circulator


Storage
Vessel
Pressure
20 Goodyear Two NPE-S Tankless Relief
Valve Expansion
Irvine, CA 92618 With Two Temperature Operation Mixing
Tank

800-519-8794 Valve

www.Navien.com
T Aquastat
DHW Circulator Full-port
Drawn By: B. Fenske NPE-S-2LT-I-BF02 August 1, 2013 w/Aquastat & Check Valve Ball Valve
This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.
This concept system drawing does not imply compliance with local building codes. Actual installation may vary
depending on installation location & parameters and it must be done in accordance to all local building codes.
Verify with local building officials before commencement of system installation.

Communication Communication
Cable Cable

G H C G H C G H C

Condensate

Gas
Domestic Cold Water
Domestic Hot Water

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater Check Valve Circulator


Storage
Vessel
Pressure
20 Goodyear Three NPE-S Tankless Relief
Valve Expansion
Irvine, CA 92618 (Includes NPE-A Internal Circulation Mode) Mixing
Tank

800-519-8794 Valve

www.Navien.com
T Aquastat
DHW Circulator Full-port
Drawn By: B. Fenske NPE-S-3-I-BF02 August 1, 2013 w/Aquastat & Check Valve Ball Valve
This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.
This concept system drawing does not imply compliance with local building codes. Actual installation may vary
depending on installation location & parameters and it must be done in accordance to all local building codes.
Verify with local building officials before commencement of system installation.

Communication Communication Communication


Cable Cable Cable

G H C G H C G H C G H C

Condensate

Gas
Domestic Cold Water
Domestic Hot Water

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater Check Valve Circulator


Storage
Vessel
Pressure
20 Goodyear Four NPE-S Tankless Relief
Valve Expansion
Irvine, CA 92618 (Includes NPE-A, Internal Circulation Mode) Mixing
Tank

800-519-8794 Valve

www.Navien.com
T Aquastat
DHW Circulator Full-port
Drawn By: B. Fenske NPE-S-4-I-BF02 August 1, 2013 w/Aquastat & Check Valve Ball Valve
This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.
This concept system drawing does not imply compliance with local building codes. Actual installation may vary
depending on installation location & parameters and it must be done in accordance to all local building codes.
Verify with local building officials before commencement of system installation.

Communication Communication Communication Communication


Cable Cable Cable Cable

G H C G H C G H C G H C G H C

Condensate

Gas
Domestic Cold Water
Domestic
Hot Water

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater Check Valve Circulator


Storage
Vessel
Pressure
20 Goodyear Five NPE-S Tankless Relief
Valve Expansion
Irvine, CA 92618 (Includes NPE-A, Internal Circulation Mode) Mixing
Tank

800-519-8794 Valve

www.Navien.com
T Aquastat
DHW Circulator Full-port
Drawn By: B. Fenske NPE-S-5-I-BF02 August 1, 2013 w/Aquastat & Check Valve Ball Valve
This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.
This concept system drawing does not imply compliance with local building codes. Actual installation may vary
depending on installation location & parameters and it must be done in accordance to all local building codes.
Verify with local building officials before commencement of system installation.

Unit 1 Unit 2 Unit 3 Unit 4 Unit 5 . . . . . Unit 6 - 16

Communication Communication Communication Communication Communication


Cable Cable Cable Cable Cable

G H C G H C G H C G H C G H C G H C

Condensate

Gas
Domestic
Domestic Cold Water
Hot Water

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater Check Valve Circulator


Storage
Vessel
Pressure
20 Goodyear Six Plus NPE-S Tankless Relief
Valve Expansion
Irvine, CA 92618 (Includes NPE-A, Internal Circulation Mode) Mixing
Tank

800-519-8794 Valve

www.Navien.com
T Aquastat
DHW Circulator Full-port
Drawn By: B. Fenske NPE-S-6P-I-BF02 August 1, 2013 w/Aquastat & Check Valve Ball Valve
This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.
This concept system drawing does not imply compliance with local building codes. Actual installation may vary
depending on installation location & parameters and it must be done in accordance to all local building codes.
Verify with local building officials before commencement of system installation.

Condensate

Gas

Domestic Cold
Domestic Hot Water
Water

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater Check Valve Circulator


Storage
Vessel
Ten NPE-S Tankless Pressure
20 Goodyear (Includes NPE-A, Internal Circulation Mode)
Relief
Valve Expansion
Irvine, CA 92618 Alternative Mounting Shown Mixing
Tank

800-519-8794 Valve

www.Navien.com
T Aquastat
DHW Circulator Full-port
Drawn By: B. Fenske NPE-A-10-E-BF02 August 1, 2013 w/Aquastat & Check Valve Ball Valve
This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.
This concept system drawing does not imply compliance with local building codes. Actual installation may vary
depending on installation location & parameters and it must be done in accordance to all local building codes. Notes:
Verify with local building officials before commencement of system installation. 1. Use Navien Cord P #30011612A
2. Set DIP Switches on Integrated Controller
#1 – OFF, #2 – OFF, #3 – ON
3. Select External Circulator Performance
to be 2 GPM Minimum, 4 GPM Maximum based
on 11 Psi drop @ 4 GPM at tankless
* Refer to NPE Installation Manual for further details

G H C

Domestic Hot Water Condensate


Gas

Domestic Cold Water

NPE-S Series Tankless Water Heater Check Valve Circulator


Storage
Vessel
One NPE-S Tankless Pressure
20 Goodyear Using External Pump for Recirculation
Relief
Valve Expansion
Irvine, CA 92618 with Part #30011612A External Pump Wire Mixing
Tank

800-519-8794 Valve

www.Navien.com
T Aquastat
DHW Circulator Full-port
Drawn By: B. Fenske NPE-S-1-PW-EC-BF02 August 1, 2013 w/Aquastat & Check Valve Ball Valve
This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.
This concept system drawing does not imply compliance with local building codes. Actual installation may vary
depending on installation location & parameters and it must be done in accordance to all local building codes.
Verify with local building officials before commencement of system installation.

Domestic Hot Water to Fixtures

(A) Tankless Circulator


(Bronze or S.S) Selected Shall
be 4 GPM Max @ 23' Total Head (10 PSI)
+ pipe, valves, fittings & tank.

Insulated G H C
Storage
Tank

Condensate
Gas
T

(A)
¾” Min
3 or 4
Tap
Tank Domestic Cold Water
Optional
DHW
Recirculation

NPE-S Series Tankless Water Heater Check Valve Circulator


Storage
Vessel
Pressure
20 Goodyear One NPE-S with Storage Relief
Valve Expansion
Irvine, CA 92618 to meet Flow/Temp Rise Requirements Tank
Mixing
800-519-8794 Valve

www.Navien.com
T Aquastat
DHW Circulator Full-port
Drawn By: B. Fenske NPE-S-1-ST-BF02 August 1, 2013 w/Aquastat & Check Valve Ball Valve
This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.
This concept system drawing does not imply compliance with local building codes. Actual installation may vary (A) Tankless Circulator
depending on installation location & parameters and it must be done in accordance to all local building codes. (Bronze or S.S) Selected Shall
Verify with local building officials before commencement of system installation. be 8 GPM Max (4 Per Tankless)
@ 23' Total Head (10 PSI)
+ pipe, valves, fittings & tank.
(B) Install Circuit Setters to
Maintain Flow into Units @ 4
Domestic Hot Water to Fixtures
GPM Maximum

Communication
Cable
Insulated
Storage G C G H C
H
Tank

Condensate
T
Gas

(B) (B)
3 or 4
Tap (A)
Tank Domestic Cold Water
Optional
DHW
Recirculation

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater Check Valve Circulator


Storage
Vessel
Pressure
20 Goodyear Two NPE-S with Storage Relief
Valve Expansion
Irvine, CA 92618 to meet Flow/Temp Rise Requirements Mixing
Tank

800-519-8794 Valve

www.Navien.com
T Aquastat
DHW Circulator Full-port
Drawn By: B. Fenske NPE-S-2-ST-BF02 August 1, 2013 w/Aquastat & Check Valve Ball Valve
This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.
This concept system drawing does not imply compliance with local building codes. Actual installation may vary (A) Tankless Circulator
depending on installation location & parameters and it must be done in accordance to all local building codes. (Bronze or S.S) Selected Shall be
Verify with local building officials before commencement of system installation.
12 GPM Max (4 Per Tankless) @
23' Total Head (10 PSI)
+ pipe, valves, fittings & tank.
(B) Install Circuit Setters to Maintain
Domestic Hot Water to Fixtures
Flow into Units @ 4 GPM Maximum

Communication Communication
Cable Cable
Insulated
Storage
G H C G H C G H C
Tank

Condensate
T
Gas

(B) (B) (B)


3 or 4
Tap (A)
Tank Domestic Cold Water
Optional
DHW
Recirculation

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater Check Valve Circulator


Storage
Vessel
Pressure
20 Goodyear Three NPE-S with Storage Relief
Valve Expansion
Irvine, CA 92618 to meet Flow/Temp Rise Requirements Mixing
Tank

800-519-8794 Valve

www.Navien.com
T Aquastat
DHW Circulator Full-port
Drawn By: B. Fenske NPE-S-3-ST-BF02 August 1, 2013 w/Aquastat & Check Valve Ball Valve
This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.
This concept system drawing does not imply compliance with local building codes. Actual installation may vary (A) Tankless Circulator
depending on installation location & parameters and it must be done in accordance to all local building codes. (Bronze or S.S) Selected Shall be
Verify with local building officials before commencement of system installation. 16 GPM Max (4 Per Tankless) @
23' Total Head (10 PSI)
+ pipe, valves, fittings & tank.
(B) Install Circuit Setters to
Maintain Flow into Units @ 4 GPM
Domestic Hot Water to Fixtures Maximum

Insulated Communication
Cable
Communication
Cable
Communication
Cable
Storage
Tank G H C G H C G H C G H C

Condensate
T
Gas

(B) (B) (B) (B)


3 or 4
Tap (A)
Tank
Optional Domestic
DHW Cold Water
Recirculation

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater Check Valve Circulator


Storage
Vessel
Pressure
20 Goodyear Four NPE-S with Storage Relief
Valve Expansion
Irvine, CA 92618 to meet Flow/Temp Rise Requirements Mixing
Tank

800-519-8794 Valve

www.Navien.com
T Aquastat
DHW Circulator Full-port
Drawn By: B. Fenske NPE-S-4-ST-BF02 August 1, 2013 w/Aquastat & Check Valve Ball Valve
This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.
This concept system drawing does not imply compliance with local building codes. Actual installation may vary (A) Tankless Circulator
depending on installation location & parameters and it must be done in accordance to all local building codes. (Bronze or S.S) Selected Shall
Verify with local building officials before commencement of system installation. be 8 GPM Max (4 Per Tankless)
@ 23' Total Head (10 PSI)
+ pipe, valves, fittings & tank.
(B) Install Circuit Setters to
Domestic Hot Water to Fixtures
Maintain Flow into Units @ 4
GPM Maximum

Insulated Insulated Communication


Storage Storage Cable
Tank Tank
G H C G H C

T T
Condensate

Gas

(B) (B)

(A)
Domestic Cold Water

Optional DHW Recirculation

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater Check Valve Circulator


Storage
Vessel
Pressure
20 Goodyear Two NPE-S with Two Storage Tanks Relief
Valve Expansion
Irvine, CA 92618 to meet Flow/Temp Rise Requirements Mixing
Tank

800-519-8794 Valve

www.Navien.com
T Aquastat
DHW Circulator Full-port
Drawn By: B. Fenske NPE-S-2-2ST-BF02 August 1, 2013 w/Aquastat & Check Valve Ball Valve
This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings. (A) Tankless Circulator
This concept system drawing does not imply compliance with local building codes. Actual installation may vary
depending on installation location & parameters and it must be done in accordance to all local building codes. (Bronze or S.S) Selected Shall be
Verify with local building officials before commencement of system installation. 12 GPM Max (4 Per Tankless) @
23' Total Head (10 PSI)
+ pipe, valves, fittings & tank.
(B) Install Circuit Setters to
Domestic Hot Water to Fixtures
Maintain Flow into Units @ 4 GPM
Maximum

Insulated Insulated Communication Communication


Storage Storage Cable Cable
Tank Tank
G H C G H C G H C

T T
Condensate

Gas

(B) (B) (B)

(A)
Domestic Cold Water

Optional DHW Recirculation

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater Check Valve Circulator


Storage
Vessel
Pressure
20 Goodyear Three NPE-S with Two Storage Tanks Relief
Valve Expansion
Irvine, CA 92618 to meet Flow/Temp Rise Requirements Mixing
Tank

800-519-8794 Valve

www.Navien.com
T Aquastat
DHW Circulator Full-port
Drawn By: B. Fenske NPE-S-3-2ST-BF02 August 1, 2013 w/Aquastat & Check Valve Ball Valve
This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.
This concept system drawing does not imply compliance with local building codes. Actual installation may vary (A) Tankless Circulator
depending on installation location & parameters and it must be done in accordance to all local building codes. (Bronze or S.S) Selected Shall be
Verify with local building officials before commencement of system installation.
16 GPM Max (4 Per Tankless) @
23' Total Head (10 PSI)
+ pipe, valves, fittings & tank.
Domestic Hot Water to Fixtures (B) Install Circuit Setters to
Maintain Flow into Units @ 4 GPM
Maximum

Insulated Insulated
Storage Storage
Tank Tank Communication Communication Communication
Cable Cable Cable

G H C G H C G H C G H C

T T Condensate

Gas

(B) (B) (B) (B)


(A)

Domestic Cold
Water

Optional DHW Recirculation

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater Check Valve Circulator


Storage
Vessel
Pressure
20 Goodyear Four NPE-S with Two Storage Tanks Relief
Valve Expansion
Irvine, CA 92618 to meet Flow/Temp Rise Requirements Mixing
Tank

800-519-8794 Valve

www.Navien.com
T Aquastat
DHW Circulator Full-port
Drawn By: B. Fenske NPE-S-4-2ST-BF02 August 1, 2013 w/Aquastat & Check Valve Ball Valve
This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.
This concept system drawing does not imply compliance with local building codes. Actual installation may vary (A) Tankless Circulator
depending on installation location & parameters and it must be done in accordance to all local building codes. (Bronze or S.S) Selected Shall
Verify with local building officials before commencement of system installation. be 8 GPM Max (4 Per Tankless)
@ 23' Total Head (10 PSI)
+ pipe, valves, fittings & tank.
(B) Install Circuit Setters to
Domestic Hot Water Low Temp Maintain Flow into Units @ 4
to Fixtures Domestic Hot Water
GPM Maximum

M
H C

Communication
Cable
Insulated
Storage G C G H C
H
Tank

Condensate
T
Gas

(B) (B)
3 or 4
Tap (A)
Tank Domestic Cold Water
Optional
DHW
Recirculation

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater Check Valve Circulator


Storage
Vessel
Two NPE-S with Storage Pressure
20 Goodyear to meet Flow/Temp Rise Requirements
Relief
Valve Expansion
Irvine, CA 92618 Two Temperature System Mixing
Tank

800-519-8794 Valve

www.Navien.com
T Aquastat
DHW Circulator Full-port
Drawn By: B. Fenske NPE-S-2-STLT-BF02 August 1, 2013 w/Aquastat & Check Valve Ball Valve
This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.
This concept system drawing does not imply compliance with local building codes. Actual installation may vary
depending on installation location & perameters and it must be done in accordance to all local building codes.
Verify with local building officials before commencement of system installation.

Vacuum Breaker
1. Tankless circulator selected should be
approved for domestic water (S.S. or Bronze).
2. Tankless circulator selected shall be 4 GPM
@ 23' H (10 PSI) + pipe, valves, fittings & tank.
3. Storage tank volume size selections:
High Temp (180°F)
6 X dishwasher GPM requirements

Low Temp (140°F)


4 X dishwasher GPM requirements
G H C

Condensate
Gas
Insulated
Storage
Tank

¾” Min

Domestic Cold Water

Opt. Recirculation

NPE-S Series Tankless Water Heater Check Valve Circulator


Storage
Vessel
One Navien NPE-S Dishwasher Application Pressure
20 Goodyear With Storage to meet Flow/Temp
Relief
Valve Expansion
Irvine, CA 92618 Rise Requirements Mixing
Tank

800-519-8794 Valve

www.Navien.com
T Aquastat
DHW Circulator Full-port
Drawn By: B. Fenske NPE-S-1-DW-BF02 August 1, 2013 w/Aquastat & Check Valve Ball Valve
This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.
This concept system drawing does not imply compliance with local building codes. Actual installation may vary
depending on installation location & perameters and it must be done in accordance to all local building codes.
Verify with local building officials before commencement of system installation.

(A) Tankless Circulator (Bronze or S.S) Selected Shall be 4 GPM Max per
Tankless @ 23' Total Head (10 PSI) + pipe, valves, fittings & tank.
(B) Install Circuit Setters to Maintain Flow into Units @ 4 GPM Maximum.
Storage tank volume size selections:
High Temp (180°F)
6 X dishwasher GPM requirements
Low Temp (140°F)
4 X dishwasher GPM requirements Domestic
Water
To Fixtures
Vacuum Communication
Cable
Breaker

G H C G H C

Condensate

M
Gas
H C (B) (B)
Insulated
Storage
Tank
1” Min

T (A)

Opt. Recirculation Domestic Cold Water

NPE-S Series Tankless Water Heater Check Valve Circulator


Storage
Vessel
Two Navien NPE-S Dishwasher Application Pressure
20 Goodyear With Storage to meet Flow/Temp
Relief
Valve Expansion
Irvine, CA 92618 Rise Requirements Mixing
Tank

800-519-8794 Valve

www.Navien.com
T Aquastat
DHW Circulator Full-port
Drawn By: B. Fenske NPE-S-2-DW-DHW-BF02 August 1, 2013 w/Aquastat & Check Valve Ball Valve
This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.
This concept system drawing does not imply compliance with local building codes. Actual installation may vary
depending on installation location & perameters and it must be done in accordance to all local building codes.
Verify with local building officials before commencement of system installation.

(A) Tankless Circulator (Bronze or S.S) Selected Shall be 4 GPM Max per
Tankless @ 23' Total Head (10 PSI) + pipe, valves, fittings & tank.
(B) Install Circuit Setters to Maintain Flow into Units @ 4 GPM Maximum.
Storage tank volume size selections:
High Temp (180°F)
6 X dishwasher GPM requirements
Low Temp (140°F)
4 X dishwasher GPM requirements

Vacuum Communication
Cable
Breaker

G H C G H C

Condensate

Gas
(B) (B)
Insulated
Storage
Tank
1” Min

T (A)

Opt. Recirculation Domestic Cold Water

NPE-S Series Tankless Water Heater Check Valve Circulator


Storage
Vessel
Two Navien NPE-S Dishwasher Application Pressure
20 Goodyear With Storage to meet Flow/Temp
Relief
Valve Expansion
Irvine, CA 92618 Rise Requirements Mixing
Tank

800-519-8794 Valve

www.Navien.com
T Aquastat
DHW Circulator Full-port
Drawn By: B. Fenske NPE-S-2-DW-BF02 August 1, 2013 w/Aquastat & Check Valve Ball Valve
This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.
This concept system drawing does not imply compliance with local building codes. Actual installation may vary
depending on installation location & perameters and it must be done in accordance to all local building codes.
Verify with local building officials before commencement of system installation.

(A) Tankless Circulator (Bronze or S.S) Selected Shall be 4 GPM Max per
Tankless @ 23' Total Head (10 PSI) + pipe, valves, fittings & tank.
(B) Install Circuit Setters to Maintain Flow into Units @ 4 GPM Maximum.
Storage tank volume size selections:
High Temp (180°F)
6 X dishwasher GPM requirements
Low Temp (140°F)
4 X dishwasher GPM requirements Domestic
Water
To Fixtures
Vacuum Communication Communication
Cable Cable
Breaker

G H C G H C G H C

Condensate

Gas
M
H C (B) (B) (B)
Insulated
Storage
Tank
(A)
1-1/4” Min

Opt. Recirculation Domestic Cold Water

NPE-S Series Tankless Water Heater Check Valve Circulator


Storage
Vessel
Three Navien NPE-S Dishwasher Application Pressure
20 Goodyear With Storage to meet Flow/Temp
Relief
Valve Expansion
Irvine, CA 92618 Rise Requirements Mixing
Tank

800-519-8794 Valve

www.Navien.com
T Aquastat
DHW Circulator Full-port
Drawn By: B. Fenske NPE-S-3-DW-DHW-BF02 August 1, 2013 w/Aquastat & Check Valve Ball Valve
This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.
This concept system drawing does not imply compliance with local building codes. Actual installation may vary
depending on installation location & parameters and it must be done in accordance to all local building codes.
Verify with local building officials before commencement of system installation.

Circulator Requirement:
Bronze or Stainless Steel
Select & Set - 4 GPM max @ 23 ft head.
(Alternate pump location shown inside AHU) Domestic
Hot Water
To
Fixtures

M
G H C
H C
AIRFLOW

Condensate
Gas
Opt. AC COIL Domestic
Cold Water

NPE-S Series Tankless Water Heater Check Valve Circulator


Storage
Vessel
Pressure
20 Goodyear Navien NPE-S Series Tankless Relief
Valve Expansion
Irvine, CA 92618 Combi Use Application with Air Handler Mixing
Tank

800-519-8794 Valve

www.Navien.com
T Aquastat
DHW Circulator Full-port
Drawn By: B. Fenske NPE-S-Combi-AH-BF02 August 1, 2013 w/Aquastat & Check Valve Ball Valve
This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.
This concept system drawing does not imply compliance with local building codes. Actual installation may vary
depending on installation location & parameters and it must be done in accordance to all local building codes.
Verify with local building officials before commencement of system installation.

(A) Circulator Requirement:


Bronze or Stainless Steel Domestic
Select & Set - 4 GPM max @ 23 ft head. Hot Water
To
(B) Maximum 30 MBTU’s/Hour & 135°F
Fixtures
Maximum Heating System Temperature
with NPE tankless set at 140°F.

Field
Supplied
T Circulator
Zone Panel
M
G H C
H C

SS Heat
Exchanger

Condensate
Gas
(B)
Domestic
Cold Water
(A)
Closed Loop
Heating Fill

NPE-S Series Tankless Water Heater Check Valve Circulator


Air
Elimination
Navien NPE-S Series Tankless Pressure
20 Goodyear Combi Use Application with Required
Relief
Valve Expansion
Irvine, CA 92618 SS Heat Exchanger Mixing
Tank

800-519-8794 Valve

www.Navien.com
T Aquastat
DHW Circulator Full-port
Drawn By: B. Fenske NPE-S-Combi-SS-BF02 August 1, 2013 w/Aquastat & Check Valve Ball Valve
This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.
This concept system drawing does not imply compliance with local building codes. Actual installation may vary
Notes:
depending on installation location & parameters and it must be done in accordance to all local building codes.
Verify with local building officials before commencement of system installation. 1. For Storage Tank/Geothermal Operation; DIP Switch #6
of 10 located on Integrated Display Panel should be set ON
(UP).
2. With Storage Tank/Geothermal Operation Enabled, NPE
Tankless DHW setting may be set at or near storage tank
thermostatic mixing valve temperature output.
DHW
Supply
To Fixtures

Domestic
Storage
Tank G H C

Geothermal Unit
or
(A)
Desuperheater
Condensate
Gas
Domestic
Cold Water

(A) Follow GeoThermal Unit and Tank Manufacturer Recommendations and Requirements

NPE-S Series Tankless Water Heater Check Valve Circulator


Storage
Vessel
NPE-S Domestic Hot Water Standard Pressure
20 Goodyear Installation with Geothermal or
Relief
Valve Expansion
Irvine, CA 92618 Desuperheater Mixing
Tank

800-519-8794 Valve

www.Navien.com
T Aquastat
DHW Circulator Full-port
Drawn By: B. Fenske NPE-S-G-BF02 August 1, 2013 w/Aquastat & Check Valve Ball Valve
This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.
This concept system drawing does not imply compliance with local building codes. Actual installation may vary Notes:
depending on installation location & parameters and it must be done in accordance to all local building codes.
Verify with local building officials before commencement of system installation. 1. For Storage Tank/Solar Operation; DIP Switch #6 of 10
located on Integrated Display Panel should be set ON (UP).
2. With Storage Tank/Solar Operation Enabled, NPE
Tankless DHW setting may be set at or near storage tank
thermostatic mixing valve temperature output.

DHW
Supply
To Fixtures

G H C

Condensate
Gas
Domestic
Cold Water

Solar Fill

NPE-S Series Tankless Water Heater Check Valve Circulator


Storage
Vessel
Pressure
20 Goodyear NPE-S Domestic Hot Water Standard Relief
Valve Expansion
Irvine, CA 92618 Installation with Solar Application Mixing
Tank

800-519-8794 Valve

www.Navien.com
T Aquastat
DHW Circulator Full-port
Drawn By: B. Fenske NPE-S-S-BF02 August 1, 2013 w/Aquastat & Check Valve Ball Valve