You are on page 1of 5

Harmonic reduction in multiplex convertors

by triple-frequency current injection


B. M. Bird, M.Sc, Ph.D., C.Eng., M.I.E.E., J. F. Marsh, B.Sc, Ph.D., and P. R. McLellan, B.Sc, Ph.D.

Abstract
Conventionally, harmonic filters have hitherto been used to reduce the very undesirable effects of current
harmonics in the input current to convertor equipment. The present paper describes an investigation into a
new method of eliminating these current harmonics at the source, this being a more fundamental method
than merely suppressing their consequences. The cost of the new method is not likely to be more expensive
than elaborate filter equipment.
The process consists of modifying the primary current waveform by the injection of triple-frequency
currents into the convertor. An explanation of the fundamental action is presented, together with an analysis
of the effects of triple-frequency current injection upon the harmonics generated by duplex convertor
equipment.

List of symbols been formulated by the supply authorities as a guide to


h = ld\2 the effect of any standard convertor upon the supply
Ia = r.m.s. value of injected current, A system.
ld = direct current, A (b) Current-harmonic reduction has been the subject of many
Im = magnetising current, A papers.6"8 Hammond and Whittaker7 state that any con-
n = order of harmonic vertor system with an infinitely inductive d.c. load will
p — pulse number have harmonics in its primary-current waveform which
are purely dependent on the pulse number p of the
Vd = direct voltage convertor, where p is the number of anode-anode com-
Vp = peak voltage per secondary phase mutations equispaced in time in one cycle of the supply.
VMN = interphase transformer voltage The harmonics present in the current waveform will be of
p = turns ratio the order Kp ± 1, where K = 1, 2, 3 etc., and the r.m.s.
magnitude of each harmonic as a percentage of the
fundamental is 100/«, where n is the order of the har-
1 Introduction monic; this is true for the line current, but additional
The development of the high-power grid-controlled triplen harmonics might be present in the phase current.
mercury-arc rectifier/invertor has had a great effect on con-
temporary power-engineering practice, and such equipment There are at least two ways of avoiding this condition:
has found very many industrial applications. The development (i) The commutations are made unequally spaced in time,
of its solid-state equivalent, the high-power thyristor, will i.e. some anodes conduct for a longer time than others.
undoubtedly serve to increase the use of rectifier/invertor This could readily be done, but, in general, the technique
equipment because the thyristor is so much more robust, causes asymmetrical currents to flow, and it introduces
smaller, lighter, more portable, and generally more acceptable even-order harmonics into the primary-current waveform,
as an engineering device than a mercury-filled bulb. In addi- (ii) The commutations could remain equispaced in time, but
tion, the power loss in a thyristor is much less than in the the shape of the current waveform could be modified in
corresponding mercury arc. Development of the technology spite of the presence of a large inductive d.c. load.
of the thyristor is steadily proceeding, and the cost of Probably the simplest way of obtaining this effect is by
thyristors is slowly being reduced. the injection of harmonic currents into the convertor.
The production of current harmonics by convertor equip-
ment is, however, a fundamental problem, and until basic The present paper seeks to establish the simple principles
remedies are invented and developed, the matter can only which underlie current-injection schemes and to indicate the
become more serious as the use of conversion equipment particular characteristics of triple-frequency current injection
spreads. in duplex convertors.
Although a convertor causes current harmonics in the
supply mains, the undesirable effects of these are usually
observed in the form of voltage harmonics. The former are 2 Duplex 6-phase common-cathode
dependent only on the type of convertor used, but the latter rectifier
also depend on the properties of the supply network. 2.1 Mode of operation
This paper describes the principle of a new method of The simplest form of convertor into which triple-
greatly reducing the harmonics in the supply current to a frequency current can be injected is the duplex 6-phase
convertor. The well-known duplex 6-phase rectifier, with an rectifier with common-cathode connection, shown in Fig. 1.
interphase transformer, is taken as an example, but the method
is applicable to other types of convertor.
Hitherto, the subject of harmonic reduction has been
subdivided into (a) voltage-harmonic reduction and (b)
current-harmonic reduction.
(a) Voltage-harmonic reduction is a complex subject, and output
the problem has usually been studied for a particular voltage
installation.1"4 Nevertheless, a few general rules5 have
Paper 5925 P, first received 21st January and in revised form 2nd June
1969
Dr. Bird is with the Department of Electrical Engineering, University group M group N
of Bristol, University Engineering Laboratories, University Walk,
Bristol BS8 1TR, England, Dr. Marsh is with English Electric Ltd., Fig. 1
Stafford, England and Dr. McLellan is with the University of Ankara, Duplex 6-phase rectifier
Ankara, Turkey
1730 PROC. IEE, Vol. 116, No. 10, OCTOBER 1969
If the interphase transformer is short-circuited, the system voltage, reduced total-load range and increased current
acts as a 6-phase common-cathode convertor with only one harmonics. Fortunately, the minimum direct current is
of the six rectifier elements conducting at any given time. small; in theory, it must be at least twice the peak mag-
Thus each rectifier element conducts for only one sixth of a netising current for the interphase transformer. When the
cycle. (Overlap is ignored here.) With the interphase trans- operating conditions make very light loads possible, it is
former interposed between the two 3-phase groups, one common to provide an auxiliary load resistance, which is
rectifier element in each group conducts at any given time switched in as the main d.c. load falls away, to prevent a
and thus each rectifier element passes current for one third voltage rise on very low loads.
of a cycle. Another method of dealing with the same problem is to
The overall effect is to produce a decrease in the current provide an additional triple-frequency magnetising circuit, so
loading of the transformer windings and rectifier elements, that the alternating magnetising current for the interphase
and hence to obtain a considerable improvement in the transformer need not flow through the rectifier elements. This
utilisation of equipment, relative to the 6-phase common- overcomes the requirement for a minimum direct load current
cathode configuration. Fig. 2 shows the secondary phase which must swamp the magnetising current. The method has
been described in a paper by Blake.9 The secondary phase
currents of a duplex 6-phase rectifier, with an interphase
transformer, are shown in Fig. 3, which also shows the super-
imposed magnetising current. This has either to be drawn
thyristor mean d.c.output from the rectifier itself, or supplied from the auxiliary mag-
conducting netising circuit.
sequence I TT 2 VP
The impedance of the interphase transformer is high, as
interphase is the open-circuit impedance of any transformer, and the
transformer current drawn from the 'triangular' voltage presented to it,
voltage by duplex operation of the rectifier, is therefore very small.
Its phase, and its effect on the phase currents of a duplex
6-phase rectifier, are shown in Fig. 3.

3 Current-injection in duplex rectifiers


Fig. 2 It is possible to use an auxiliary power source in con-
Output voltage and interphase transformer voltage for duplex 6-phase junction with a duplex rectifier for improving the input-
rectifier current waveform to the rectifier transformer, by harmonic
secondary phase voltages of group M neutralisation. This arrangement, which is shown in Fig. 4,
secondary phase voltages of group N
interphase transformer
voltages of the two groups. The difference between the two
sets of voltages for the conducting rectifier elements represents
the interphase transformer voltage, which has an approxi-
mately triangular waveform, and has a frequency three times
that of the supply voltage. output
voltage

2.2 Triple-frequency excitation of interphase


transformers
It is well known that, for the proper operation of a groupM group N
rectifier with an interphase transformer, the direct load Fig. 4
current must exceed a certain minimum value. If it does not, Duplex 6-phase rectifier
the rectifier will revert from a duplex (or multiplex) regime typical injected-current path at the instant when elements I and 2 are
to a simplex regime, with an appreciable rise in direct output conducting

may appear similar to the auxiliary magnetising circuit


phase 1 proposed by Blake,9 but it is, in fact, substantially different
in form and in function.
Consider the duplex 6-phase rectifier as an example. Sup-
pose that a heavy-current low-voltage low-impedance triple-
phase 3 frequency power supply is connected between the star points
of the two 3-phase groups. The interphase transformer
voltage, as the difference of the two rectifier secondary phases,
phase 5 is inexorable, and the heavy-current source will therefore
interphase cause current to circulate around two secondary phases of
transformer
voltage and the rectifier, and a corresponding balancing current will flow
magnetising current in the primary of the rectifier transformer. The impedance
presented to this heavy current is simply the low leakage
reactance of two phases of the transformer.
thyristor
conducting The generator must be capable of delivering a 150Hz
sequence current comparable with half the direct load current, and the
phase of this current must differ by 90° from the phase of
phase 2 the magnetising current of the interphase transformer. The
current injected can be chosen at will, although the amount
of harmonic reduction will depend on the magnitude of the
injected current, which has an optimum or, at least, a preferred
phase 4 value.
It could be said that the Blake9 circuit is basically a 'voltage'
system, which causes a working flux in the interphase trans-
phase 6
former, whereas the current-injection circuit is basically a
Fig. 3 'current' system. Their functions are, in some sense, analogous
Secondary phase currents showing the magnetising current of the
to a voltage transformer and a current transformer,
interphase transformer respectively.
The inductance of the d.c. load is assumed to be very large The operation of the current-injection circuit is explained
PROC. IEE, Vol. 116, No. 10, OCTOBER 1969 1731
in Section 3.1, and it is shown in Fig. 5 that the phase of Table 1
the injected current must be displaced by 90° from the phase
HARMONICS AS PERCENTAGES OF FUNDAMENTAL WITH VARYING
of the magnetising current, as discussed in Section 2.2 and
DEGREES OF CURRENT INJECTION FOR DUPLEX 6-PHASE
shown in Fig. 3.
CONVERTOR

Injection
(Drder of harmonic
ratio
ylh
5 7 u 13 17 19 23 25

0 20 14-28 9 0 9 7-69 5-88 5-26 4-35 4


0-64 0 2-8 2-6 2-3 1-83 1-65 1-42 1-3
0-816 5 0 0-84 1 0-83 0-77 0-68 0-63
0-926 7-9 1-7 0 018 0-21 0-25 0-28 '0-23
0-947 8-5 2 019 0 01 014 015 015
0-969 9-2 2-4 0-3 016 0 003 006 008
0-975 9-3 2-5 0-44 0-2 002 0 003 005
0-983 9-5 2-6 0-5 0-25 005 001 0 003
0-986 9-6 2-7 0-53 0-28 007 003 002 0
0-25 11-7 9-64 6-45 5-44 4-21 3-77 3 1 3 2-90
0-50 4-12 5 21 3-93 3-42 2-68 2-41 201 1-85
0-75 3-25 1 1-57 1-45 119 1-1 0-96 0-88
100 100 2-86 0-65 0-38 017 012 007 005

Table 2
RESIDUAL HARMONICS AS PERCENTAGES OF CORRESPONDING
HARMONICS WITHOUT CURRENT INJECTION FOR DUPLEX 6-PHASE
CONVERTOR

Drder of harmonic
Injection
nitio
ylh
5 7 n 13 17 19 23 25
Fig. 5
Primary phase current with 150Hz current injection at different 0-64 0 19-6 28-6 30-00 311 31-4 32-7 32-5
magnitudes and phases for duplex 6-phase rectifier 0-816 250 0 9-24 1300 141 14-65 15-65 15-75
a No current injection (phase 1, Fig. 3) 0-926 39-5 11-9 0 2-34 3-57 4-75 6-45 5-75
b Antiphase with 150Hz magnetising current 0-947 42-5 140 209 0 1-70 2-66 3-45 3-75
c 90° behind magnetising current 0-969 460 16-8 3-30 2-08 0 0-57 1-38 200
d, e 90° ahead of magnetising current
0-975 46-5 17-5 484 2-60 0-34 0 0-69 1-25
It is assumed that the d.c. load is highly inductive and that the 150Hz magnetising 0-983 47-5 18-2 "5-50 3-25 0-85 019 0 0-75
current is negligible in comparison with the injected current
0-986 480 18-9 5-83 3-65 119 0-57 0-46 0
0-25 58-5 67-5 71 00 70-7 71-6 71-7 72-00 72-5
0-50 20-6 36-5 43-2 44-5 45-6 45-8 46-2 46-3
3.1 Harmonic reduction in a duplex 6-phase 0-75 16-25 710 17-3 18-85 20-2 20:9 25-1 220
rectifier due to triple-frequency current injection 10 500 201 7-15 4-94 2-89 2-28 1 -61 1-25
3.1.1 Theoretical analysis
It is shown in Appendix 7 that, for a given magnitude
of triple-frequency injected current, the maximum harmonic third harmonic of magnitude -60 • 5y/h percent. As shown in
reduction occurs when the phase of the injected current eqn. 1, triple-frequency current injection also causes the
corresponds to the arrangement shown in Figs. 5d and e. It fundamental current to increase by 12-5 y/h percent. This
is also shown in Appendix 7 that, for this phase relation increase in the magnitude of the fundamental current repre-
between the injected current and the secondary current, the sents a transfer of power between the mains and the injection
harmonic analysis of the primary phase current of a duplex source. It is clear from the sign associated with the faylh term
6-phase rectifier with a highly inductive load is given by in eqn. 1 that, in the case of the rectifier, the triple-frequency
current source must act as a power sink capable of absorbing
up to one eighth of the rated d.c. power.
sin 30
h
3.1.2 Extra losses associated with current injection
Id
",is) *»"-&-H*) "" If the primary of the convertor is delta-connected, the
introduction of a third harmonic in the primary-current
waveform will cause a circulating current to flow in the delta
• < ' >
connection. The third harmonic will not, however, be present
in the line-current waveform. If the primary of the transformer
where h — \Id is the amplitude of the secondary-current is star-connected (which would be unconventional), it is neces-
rectangular waveform before injection and y — \/2Ia is the sary to introduce a delta-connected tertiary winding to allow
peak amplitude of the triple-frequency current. The ratio y/h an ampere-turn balance to be maintained in the transformer
gives a measure of the magnitude of the triple-frequency It is possible to arrive at a general estimate of the extra
injection current Ia with respect to the steady load current I2R losses caused by current injection in a transformer with
per group, Id/2. The ratio is assumed to be in the range a delta-connected primary, since the I2R losses in a coil are
proportional to the mean square of the current in the coil.
0<y/h<\ By simple algebra, it can be readily shown that, when current
injection is applied, the r.m.s. value of the current /, in the
It will be appreciated, by inspection of eqn. 1, that any primary winding of a duplex 6-phase configuration can be
harmonic can be reduced to zero by a suitable choice of the written as
injection ratio y\h\ e.g. the fifth harmonic is reduced to zero
when y\h = 16/5 2 = 0-64. The reduction in harmonics for a
variety of injection ratios is shown in Tables 1 and 2. • (2)
The conventional harmonics can thus be reduced or
eliminated by selecting an appropriate value for y/h, but where p = N2/Nu from which it follows that the ratio of
this is achieved, however, at the expense of introducing a the I2R losses in the primary winding, when secondary
1732 PROC. IEE, Vol. 116, No. 10, OCTOBER 1969
current injection is employed, to the corresponding losses load has also been investigated, and was found to give very
when current injection is removed, given by similar results as would be expected.
3.2 Harmonic reduction in a duplex 6-phase rectifier
2\h using a passive injection source
The corresponding loss ratio for the secondary winding is It was noted in Section 3.1 that, for a rectifier, the
the same. Thus the overall increase in I2R losses in the trans- source of triple-frequency current must act as a power sink.
former caused by current injection is 50(ylh)2 percent. It follows, therefore, that some passive network might be
Therefore current injection cannot cause more than a 50% used in place of the harmonic generator connected across the
rise in 12R losses, and a reduction in y/h causes a rapid interphase transformer. The voltage imposed across such a
diminution of these extra losses. passive network is identical to the interphase transformer
voltage shown in Fig. 2, and it remains to determine the
3.1.3 Experimental work current which would flow through the passive network when
such a voltage is applied to it. By the application of Duhamel's
For the purpose of the initial investigation, a 3-phase theorem, y\h may be expressed in terms of the resistance
150Hz alternator was adapted to behave as a constant- and time constant of the passive network. The harmonic
current source of triple-frequency current. It was possible to content of the primary current may then be calculated using
control both the magnitude and the phase of the injected Fourier analysis, and a series of curves is obtained such as
current. The phase was held at the optimum value for har- that shown in Fig. 8, which illustrates the particular case of
monic reduction (defined in Appendix 7), and a series of
harmonic analyses of the phase-current waveform, for various
values of the ratio y/h, were obtained experimentally, using •S 2 6 r
a harmonic analyser. The convert or used thyristor rectifier
elements held in the 'fully on' mode of operation; i.e. they
acted as simple diodes.
The experimental results obtained were entirely consistent
with the theoretical predictions; the reduction of the fifth
harmonic obtained by triple-frequency current injection is
shown in Fig. 6. The variation of the distortion factor asso-
ciated with the line currents of the delta-connected primary
is shown in Fig. 7. Although the distortion factor is improved 0 0-1 0-2 0-3 0-4 0-5 0-6 0-7 0 8 0 9 10
by increasing^//?, the delta-connected primary rapidly becomes Y/h
affected by circulating currentscset up by the third harmonic. Fig. 8
Figs. 6 and 7 relate to the case of a highly inductive d.c. Series RL passive-network injection, fifth harmonic
load; but the complementary case of a purely resistive d.c. theoretical
O experimental

the thyristors operating in the fully-on mode. It is clear from


such curves that little advantage is gained by incorporating
inductance or capacitance in series with a resistor to form
the passive network; a pure resistance is very close to the
optimum form of passive network. The power loss in such a
resistor can be expressed as \0-4y/h percent of the d.c. power,
and this would rarely prove acceptable in practice.
3.3 Harmonic reduction in a phase-controlled duplex
6-phase convertor
The preceding Sections have dealt with injection into
rectifier systems when the thyristors operate in the fully on
(or non-phase-controlled) condition. It is, of course, possible
to apply the same techniques to phase-controlled systems,
including invertors. It is necessary, however, to adjust the
phase of the injected currents to correspond to the phase-
0 0-1 0-2 0-3 0-4 0-5 0-6 0-7 0-8 0-9 10
shift of the secondary current. This complication is only
significant in the case of an active injection source; a passive
network would automatically produce the desired conditions.
Fig. 6 The harmonic reductions obtained for a rectifier operating
Fifth harmonic as a percentage of the fundamental without phase-control, using an active current-injection
theoretical source, are also obtained when phase control is introduced,
O measured ft is, however, important to realise that, when the convertor
is made to invert, the active injection source ceases to be a
1000 power sink and becomes a power source; this is apparent
on inspection of eqn. 1. Since this is the case, a passive net-
0-975 work can only be used when a convertor is operating as a
rectifier. Further, the waveform of the current in the passive
; 0 950 network is radically modified when phase control is used;
the results shown in Fig. 8 are only applicable to the convertor
•2 0-925 acting as a non-phase-controlled rectifier.
[_
o
.w 0-900 3.4 Harmonic current injection in bridge convertors
Although, for simplicity, this paper has dealt with one
0-875 particular convertor arrangement (the duplex 6-phase con-
vertor), injection techniques are not limited to this particular
0850 configuration, and it is possible to apply similar techniques
0 0-1 0-2 0-3 04 0-5 0-6 0-7 0-8 09 10
Y/h ' to certain bridge convertors. A specific example which does
not employ interphase transformers is the double 3-phase
Fig. 7
bridge. A typical arrangement is shown in Fig. 9, which
Distortion factor
represents two 3-phase-bridge convertors supplied from a
theoretical
O measured transformer with a single primary winding and two secondary
PROC. IEE, Vol. 116, No. 10, OCTOBER 1969 1733
phase windings. The output-voltage ripples from the bridges 7 HAMMOND, R. A., and WHITAKER, P . : 'Harmonics and transients
in relation to static convenors' in 'Abnormal loads on power
are identical in magnitude, and the bridges may be paralleled systems', IEE Conf. Rep. Ser. 8, 1963, pp. 148-155
with no circulating current. The voltage between the star 8 CORY, B. J. : 'H.V.D.C. convertors and systems' (MacDonald, 1965)
9 BLAKE, L. R. : 'The double 3-phase rectifier with inter-phase reactor
excited from a frequency tfipler', Proc. IEE, 1953, 100, Pt. II,
pp. 310-314
positive line 10 BIRD, B. M., and RAWCLIFFE, G. H. : British Patent Application
21339/68

7 Appendix
Fourier analysis of primary phase current for
duplex double 3-phase star configuration with
sinusoidal triple-frequency injected current
If it is assumed that the load is infinitely inductive,
and no overlap occurs, the general shape of the primary phase

negative line Id
groupM groupN
Fig. 9
Double 3-phase-bridge convenor
typical injected-current path at the instant when elements 1, 5' and 2, 4'
are conducting CD
The primary winding is omitted

points M and N is similar to that developed across the inter-


ro 5TT, 2TT

phase transformer of a duplex 6-phase common-cathode


convertor. Triple-frequency current-injection can be applied
to this configuration with exactly the same results as for the I \
duplex 6-phase convertor; the double 3-phase bridge requires
no interphase transformer, and the main transformer utilisa-
tion is better than that for a duplex 6-phase convertor.
Fig. 10
Primary-phase-current waveform with sinusoidal triple-frequency
4 Conclusions current injection
It has been demonstrated that, by the use of triple- 0 < e < TT/6 /(6) = 0
frequency current-injection, a very substantial reduction may TT/6 < 6 < 5TT/6
57T/6 < 6 < 71
/(9) = h - y
/(6) = 0
cos 3(6 - rc/6 - 0/3)

be made in the harmonics which are normally present in the


line-current input to a duplex 6-phase convertor. When current will be as shown in Fig. 10. This waveform is an odd
current injection is applied to a duplex 6-phase convertor harmonic function /(0), which can be expressed as
operating as a rectifier, the current-injection 'source' acts as
a power sink, and it is possible to use a passive network, /(0) = 0 0 < 0 < oJ
such as a simple resistor, to cause the required current to
flow. The current-injection 'source' must be capable of
absorbing up to one eighth of the d.c. load power. When the
convertor operates as an invertor, the current-injection source
must be capable of supplying a similar amount of power. /(0) = 0 ^ < 0 < 7T
Although, in the interests of brevity, this paper has dealt o
with a single-convertor arrangement, namely the duplex and may be represented by the Fourier series
6-phase common-cathode configuration, current-injection
techniques are not limited to this single configuration, but f{6) = *£*{] ^sin/W + (l + ^co.0) sin
can be applied to a range of convertor equipment.
1
3V3/* " (373 I™* ~ 673 I Si
5 Acknowledgments
The possibility of applying a triple-frequency power sin 3d . . . - sin j8 cos nd
(n2 - 9) h
source to the interphase transformer of a rectifier system was «2
initially suggested by El. A. Kandil, working under the super- 2 ^ cos j8) sin
vision of Prof. G. H. Rawcliffe, at the University of Bristol, n\ h
n — 9h J
in 1954. Dr. Kandil is now an associate professor at Ain The square of the amplitude of the «th harmonic can be
Shams University, Egypt. written as
The authors gratefully acknowledge their debt to Dr.
Kandil's thesis and to Prof. Rawcliffe for this continued keen
interest in the subject. Thanks are also given to the University
for the provision of excellent experimental facilities. which can be rearranged to give

References \2h2<
1 BUTTERWORTH, A: 'Flow of harmonics in a metropolitan-type supply A2 =
system feeding a large rectifier load', ERA report M/T110, 1950 | > 2 " 9)2 h2 «2 n2 - 9 ^
IT2 n2-9
2 BUTTERWORTH, A: 'The magnitude of harmonics flowing in a which is a minimum when cos j8 = h\y.
metropolitan-type system feeding a mixed rectifier load', ERA
report M/Tll8, 1955 If y\h<\,h\y>\, and the nearest approach which can
3 WHITEHEAD, s., and RADLEY, w. c : 'Generation and flow ot
harmonics in transmission systems', Proc. IEE, 1949, 96, Pt. II, be made to the optimum condition is when cos j8 = 1, i.e.
pp. 29-48 when jS = 0. When j8 = 0, the Fourier series reduces to
4 BROWNSEY, c. M., and CSUROS, L. : 'Harmonic distortion due to
rectifier loads on a.c. supply systems' in 'Abnormal loads on
power systems'. IEE Conf. Rep. Ser. 8, 1963, pp. 141-147
5 'Supplies to convertor equipment—harmonic distortion and per-
missible pulse number of consumer's rectifiers and invertors'.
Electricity Council engineering recommendation G5/2, 1967
6 BUSEMANN, F. : 'The influence of phase number of a convertor on
harmonics', ERA report B/T117, 1954
1734 PROC. IEE, Vol. 116, No. 10, OCTOBER 1969

You might also like