There must be a written communication of Electrical Requirement to Client/Architect/Consultant.

Use of electrical lugs is compulsory for all electrical termination (Power & control)

A) Comprehensive Line Diagram :


B) Power Cabling

Outdoor Units:

3 phase power supply (50 Hz, 380-415 Volts strictly) for each outdoor unit module irrespective of the
combination. (Please see diagram)

Details of cable, MCCB and Earthing for outdoor units are as under.

Weatherproof isolator is required near each outdoor unit for service.

Double
Power Cable Max.Cable Field Fuse
Model HP Earthing
Size (Copper) Length MCCB
G I Wire
MMY MAP 0501T8 5 HP 4C x 4 sqmm 25 m 20A 10 g
MMY MAP 0601T8 6 HP 4C x 4 sqmm 25 m 20A 10 g
MMY MAP 0801T8 8 HP 4C x 4 sqmm 25 m 32A 10 g
MMY MAP 1001T8 10 HP 4C x 6 sqmm 25 m 32A 10 g
MMY MAP 1201T8 12 HP 4C x 6 sqmm 25 m 32A 10 g

Indoor Units:

Each indoor unit, irrespective of type, requires single phase power supply (230 Volts, 50 Hz) with MCB and 3 pin
socket near indoor unit (3C x 2.5sqmm Cu cable) with earthing.

MCB Rating:
Upto 2.5TR – 10Amps
3TR to 8.0TR – 15Amps

1. Power supply wiring shall run in 25mm hard / flexible PVC conduit.
2. There shall not be any joints between two units.
3. Electrical lugs must be used for termination.

Note that all terminations are suitable for Copper cable only. Aluminum cable shall not be used.
C) Control Cabling

1 Control/ Communication wiring shall run in 25mm Hard/ flexible PVC conduit with blue marking at interval
of 1.5m for differentiating it with other cabling at site.
2 There shall not be any joints between two units.
3 Electrical lugs must be used for termination.

D) Remote Control – Cabling & Sensor Location

1. For cabling between indoor to corded remote or indoor to sensor 2C x1 sqmm copper cable shall be used.
2. Cabling shall be concealed in wall through 25mm PVC conduit.

Normal 4 way Cassette Compact Cassette, ductable, 2 ways, 1 way

U1/U2 U1/U2

A/B A/B

A/B A/B

Header Follower Header Follower

E) Electrical Protective Equipments –

Toshiba Equipments must be protected from unhealthy power supply due to voltage fluctuation, surge etc.

Toshiba equipments are designed to work on

3 phase ---- 380V-415V + - 10% and 50 Hz +-0.5Hz


1 phase ---- 220V-240V +- 10% and 50 Hz +-0.5Hz.

Type of protection based on application:

1. Voltage Stabilizers: It shall be used when Air conditioning is required without any interruption even if there
is fluctuation in voltage.

2. Voltage Scanners: It shall be used when disruption in Air conditioning due to voltage fluctuation is
acceptable while the protection of equipment is important.