HEAT LOAD SHEET - E 20

JOB NAME: Training Centre DATE:


SPACE FOR: Class Room 1 GF Estimated By:
SIZE: 1541.92 Sq ft Cu ft ESTIMATE FOR : SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 110 75.4 20 59.9 77.4

(Sq ft) (Btu/h.sq ft) ROOM 75 62.5 50 55.1 64.9


N - Glass 14 0.56 0 DIFFERENCE 35 xx xx xx 12.5
NE - Glass 12 0.56 0
E - Glass 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 14 0.56 0 201 People X 7.5 CFM/Person 1508
S - Glass 66.93 12 0.56 450 18503 Cu ft X 1 Air change per hour 308
SW - Glass 100 0.56 0 Ventillation CFM 1508
W - Glass 62.17 164 0.56 5710
NW - Glass 123 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.82
Sky light 123 0.56 0
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 18.06 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 10824 CFM
0.35
N - Wall 21.5 0 NOTES
NE - Wall 27.5 0.35 0 Occupancy = 201 Nos
E - Wall 35.5 0.35 0 Lighting = 1.24 W/Sq ft
SE - Wall 35.5 0.35 0 Eq. Load = 30.13 KW
S - Wall 464.4 33.5 0.35 5450 Height = 12.00 FT

SW - Wall 31.5 0.35 0 Load Summary


W - Wall 355.7 29.5 0.35 3676

NW - Wall 23.5 0.35 0 Summer Load:


Roof Sun 49.5 0.50 0 TR = 27.86 TR
Roof Shaded DEHUMIDIFIED CFM = 10824 CFM
TRANS. GAIN EXCEPT WALLS & ROOF

ITEM Area Temp. diff. U

(Sq ft) (°F) (Btu/h.sq ft)

All Glass 129.10 35 1.13 5106

Partition 375.98 30 0.30 3353

Ceiling 25 0.4 0

Floor 25 0.4 0

INTERNAL HEAT GAIN


People 201 Nos X 245 49245
Light 1912 W X 1.25 3.412 8155
Eq. Load 30130 WX 3.412 102804
CHECK FIGURES
OUTSIDE AIR Btu/h/ Sq ft = 216.8
CFM °F BF FACTOR CFM / Sq ft = 7.02
1508 35 0.14 1.08 7978 Sq ft / TR = 55
ROOM SENSIBLE HEAT (RSH) 191925 CFM/ TR = 388
Supply duct Supply duct leak. Heat gain from 0
heat gain + loss + fan HP(%)
Safety factor (%) 10.0 19193

EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 211118


LATENT HEAT
People 201 Nos X 205 41205
OUTSIDE AIR
CFM GR/LB BF FACTOR
1508 12.5 0.14 0.68 1794
RLH 42999
Supply duct leakage los Safety factor % 10.0 4300
EFFECTIVE ROOM LATENT HEAT (ERLH) 47299
EFFECTIVE ROOM TOTAL HEAT (ERTH) 258417
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF FACTOR
1508 35 0.86 1.08 49006
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF FACTOR
1508 12.5 0.86 0.68 11020
HEAT SUB TOTAL 318442
Return duct HP Pump + Dehum. & Pipe 5.0 15922
heat gain & loss (%)
TR 27.86 GRAND TOTAL HEAT 334364
U factor for Partition wall
Building Weight (
Resistance of Building Materials Resistance
lb/sqft)
R1 Resistance of still Air 0.68
R2 Resistance of 15 mm inner plaster 0.121 5.8
R3 Resistance of 230 mm masnory Unit 1.7625 41
R4 Resistance of 15 mm outer plaster 0.121 5.8
R5 Resistance of still Air 0.68
R R1+R2+R3+R4+R5 3.3645 52.6
U 1/R 0.30

Building Weight (
Resistance of Building Materials Resistance
lb/sqft)
R1 Resistance of still Air 0.68
R2 Resistance of 15 mm inner plaster 0.121 5.8
R3 Resistance of 230 mm masnory Unit 1.7625 41
R4 Resistance of 15 mm outer plaster 0.121 5.8

R5 Resistance of moving Air 0.17

R R1+R2+R3+R4+R5 2.8545 52.6

U 1/R 0.35

Eq Temp Diff Outside DBT - Correction Final Eq.


Exposure Weight of wall/ roof (lb/sqft) Daily range
at 4 Pm Inside DBT Temp Temp Diff
N 4 35 25 17.5 21.5

NE 10 35 25 17.5 27.5

E 18 35 25 17.5 35.5

SE 18 35 25 17.5 35.5
100 lb /sqft
S 16 35 25 17.5 33.5

SW 14 35 25 17.5 31.5

W 12 35 25 17.5 29.5

NW 6 35 25 17.5 23.5
Roof Sun 80 lb/sqft 32 35 25 17.5 49.5