GRUNDFOS DATA BOOKLET

Flow sensors
Grundfos Direct Sensors™
Flow sensors

1. Product overview 3
Table of contents

2. Product introduction 4
Vortex principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Construction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

3. Vortex Flow sensor, Industry (VFI and VFI+T2) 5


General data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
VFI and VFI+T2, 0.3 - 6 m3/h (1.3 - 26.4 gpm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
VFI and VFI+T2, 0.6 - 12 m3/h (2.6 - 52.8 gpm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
VFI and VFI+T2, 1.3 - 25 m3/h (5.7 - 110 gpm). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
VFI and VFI+T2, 2-40 m3/h (8.8 - 176 gpm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
VFI and VFI+T2, 3.2 - 64 m3/h (14-282 gpm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
VFI and VFI+T2, 5.2 - 104 m3/h (23-458 gpm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
VFI and VFI+T2, 8-160 m3/h (35-704 gpm). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
VFI and VFI+T2, 12-240 m3/h (53-1057 gpm). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

4. Vortex Flow sensor, Standard (VFS and VFS QT) 15


VFS, 1-20 l/min (0.2 - 5.3 gpm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
VFS, 2-40 l/min (0.5 - 10.6 gpm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
VFS, 5-100 l/min (1.3 - 26 gpm). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
VFS, 10-200 l/min (2.6 - 53 gpm). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
VFS, 20-400 l/min (5.3 - 106 gpm). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
VFS QT, 1-18 l/min (0.2 - 4.8 gpm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
VFS QT, 2-40 l/min (0.5 - 10.6 gpm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
VFS QT, 5-100 l/min (1.3 - 26 gpm). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
VFS QT, 10-200 l/min (2.6 - 53 gpm). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

5. Multi Flow sensor, standard (MFS and MFS QT) 26


General data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
MFS 2-20 l/min (0.53 - 5.3 gpm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
MFS 4-40 l/min (1.06 - 10.6 gpm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
MFS 10-100 l/min (2.6 - 26 gpm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
MFS 20-200 l/min (5.3 - 53 gpm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
MFS 40-400 l/min (10.6 - 106 gpm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
MFS QT 2-18 l/min (0.39 - 4.8 gpm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
MFS QT 4-40 l/min (1 - 10.6 gpm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
MFS QT 10-100 l/min (2.6 - 26 gpm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
MFS QT 20-200 l/min (5.3 - 53 gpm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

6. Product range 37
VFI transmitters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
VFS and VFS QT sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

7. Accessories 39
Sensor interface, converter unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
M12 cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Snap-on cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

8. Appendix 40
Pressure drop curves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Installation of the VFI sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Intended use for pressurised systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

9. Grundfos Product Center 44

2
Flow sensors
1

1. Product overview

Product overview
This data booklet is for the latest version of Grundfos Direct Sensors™. Customers already buying Grundfos Direct
Sensors™ might be buying a sensor with another specification.
Variant Description Technical data
VFI
Flow range: 0.3 - 240 m3/h (1.3 - 1057 gpm)
System pressure: Maximum 30 bar (435 psig)
Vortex flow sensor, industry
System temperature: -30 to +110 °C (-22 to +230 °F)
• all stainless steel
Signal: 4-20 mA (2-wire)
• Grundfos flanges or fittings.
Power supply: 12.5 - 30 VDC
Enclosure class: IP67

VFI+T
Flow range: 0.3 - 240 m3/h (1.3 - 1057 gpm)
Temperature range: 0-100 °C (32-212 °F)
Vortex flow sensor, industry
System pressure: Maximum 30 bar (435 psig)
• combined flow and temperature
System temperature: -30 to +110 °C (-22 to +230 °F)
measurement
Signal: 4-20 mA (2-wire)
• Grundfos flanges or fittings.
Power supply: 12.5 - 30 VDC
Enclosure class: IP67

VFS
Flow range: 1.3 - 400 l/min (0.2 - 106 gpm)
Temperature range: 0-120 °C (32-248 °F)
Vortex flow sensor, standard
System pressure: Maximum 24 bar (348 psig)
• combined flow and temperature
System temperature: 0-100 °C (32-212 °F)
measurement
Signal: 2 x 0.5 - 3.5 VDC (4-wire)
• composite flow pipe.
Power supply: 5 VDC (PELV)
Enclosure class: IP44

VFS QT Flow range: 1-200 l/min (0.2-53 gpm)


Vortex flow sensor, standard QT Temperature range: 0-120 °C (32-248 °F)
• combined flow and temperature System pressure: Maximum 30 bar (435 psig)
measurement System temperature: 0-120 °C (32-248 °F)
• stainless-steel pipe with composite Signal: 2 x 0.5 - 3.5 VDC (4-wire)
insert. Power supply: 5 VDC (PELV)
Enclosure class: IP44
MFS Flow range: 2.6 - 400 l/min (0.5 - 106 gpm)
Multiflow sensor, standard
Temperature range: 0-120 °C (32-248 °F)
• combined flow, pressure and
Pressure range: 0-10 bar (0-145 psig)
temperature measurement
System pressure: Maximum 24 bar (348 psig)
• output: two analog signals or proprietary
System temperature: 0-100 °C (32-212 °F)
digital bus for three signals (flow,
Signal: Digital or analog communication, 2 x 0.5 - 3.5 VDC (4-wire)
temperature and pressure)
Power supply: 5 VDC (PELV)
• composite flow pipe.
Enclosure class: IP44
MFS QT Flow range: 2-200 l/min (0.5 - 53 gpm)
Multiflow sensor, standard QT
Temperature range: 0-120 °C (32-248 °F)
• combined flow, pressure and
Pressure range: 0-10 bar (0-145 psig)
temperature measurement
System pressure: Maximum 30 bar (435 psig)
• output: two analog signals or proprietary
System temperature: 0-120 °C (32-248 °F)
digital bus for three signals (flow,
Signal: Digital or analog communication, 2 x 0.5 - 3.5 or 4.1 VDC
temperature and pressure)
(4-wire)
• stainless-steel pipe with composite
Power supply: 5 VDC (PELV)
insert.
Enclosure class: IP44

3
Flow sensors
2

2. Product introduction
Product introduction

This data booklet gives an overview of the Grundfos


vortex flow sensor range and related products. Bluff body Pipe

TM04 7362 1610 - TM05 4739 2412 - TM05 4746 2412


Flow direction

TM04 7155 1610


Fig. 3 Operating principle

The bluff body is designed to optimise the pulse


strength of the pressure variations at the position of
the differential pressure sensor.
Flow ranges are determined by the pipe diameter and
the signal processing parameters. The differential
pressure sensor key elements are a bulk
micromachined silicon chip and a
microprocessor-based signal-conditioning circuit, both
Fig. 1 Grundfos vortex flow sensors
on the same PCB. The conditioning circuit converts the
The Grundfos vortex flow sensor range comprises flow pressure reading to a signal proportional to the flow.
measurement systems as well as combined flow and
temperature measurement systems (two-in-one) Construction
designed for harsh aqueous environments.
The bluff body is either integrated in the composite
flow pipe, or supplied as a separate composite or
Vortex principle stainless steel part to be inserted in the flow pipe.
The flow measurement is based on the vortex The square chip membrane warps due to the pressure
principle. The system elements include a flow pipe with difference. This is registered as a change of resistance
an integrated bluff body and a differential pressure in the strain gauges of a Wheatstone bridge. The
sensor. pressure and temperature sensitive area, the
membrane region, is coated on both sides by an
extremely corrosion- and diffusion-resistive thin film
(Silicoat®). The coating makes the chip
environmentally robust. The liquid-free zone is sealed
by an O-ring.

Material
The Grundfos vortex flow sensors are available in
three material variants, suitable for different liquids:
• EPDM O-rings: Suitable for water; drinking-water
approved.
TM04 9236 3710

• FKM O-rings: Suitable for oily liquids and water in


heating applications.
• EPDM sealing cap with FKM O-rings: Suitable for
water in heating applications with a high volume of
Fig. 2 Bluff body inside a vortex flow sensor calcium and magnetite.
When a bluff body is placed inside a pipe, a series of
vortices will be generated on either side of the bluff Definitions
body. These vortices propagate downstream, giving
rise to periodic pressure variations which can be Burst Pressure
detected by the pressure sensor. The frequency of the
pressure variations is proportional to the volume flow The maximum allowable pressure (relative to ambient)
through the pipe. in a system, which will not destroy the sensor or
transmitter. Measured in [bar].

Maximum System Pressure


Maximum allowable static pressure (relative to ambient
pressure) in a system, where the flow is zero.

4
Flow sensors
3

3. Vortex Flow sensor, Industry (VFI and VFI+T2)

Vortex Flow sensor, Industry (VFI and VFI+T2)


General data Features and benefits
• Measurement principle with no movable parts,
resulting in no wear and tear
• MEMS technology
• direct contact with the aqueous media resulting in a

TM04 7362 2210


fast response time
• plug and play for quick setup
• smart system solution with Grundfos pump controls
• compact and robust design
Fig. 4 VFI sensor • compatible with aqueous media
• suitable for a wide temperature range
Technical overview • suitable for a wide range of application.
The VFI flow transmitter from Grundfos Direct • For aqueous media below 2 µS/cm contact your
Sensors™ is designed for industrial applications. The local Grundfos sensor representative.
transmitter is based on the principle of vortex shedding
behind a bluff body. Flow range
The VFI transmitter is fully compatible with wet,
aggressive liquids. The transmitter is based on MEMS m3/h gpm
sensing technology in combination with the 0.3 - 6 1.32 - 26.42
corrosion-resistant Silicoat® coating technology on the 0.6 - 12 2.64 - 52.83
transmitter chip. 1.3 - 25 5.72 - 110.07
2-40 8.81 - 176.11
This makes the VFI transmitters very robust and ideal 3.2 - 64 14.09 - 281.78
for pump integration and monitoring in harsh 5.2 - 104 22.89 - 457.89
environments. 8-160 35.22 - 704.46
The transmitter is supplied with a stainless steel flow 12-240 52.83 - 1056.69
pipe, available with flanges or in a threaded version.
Approvals (w/EPDM O-rings)
• WRAS
• KTW
• AS4020
TM04 9228 3710

• ACS.

Certificates

Fig. 5 Bluff body in a VFI transmitter

Applications + 75
CE C, CSA, US EAC
• Pump control
• HVAC systems
• temperature control and chiller systems
• renewable energies such as heat pumps, solar
thermals, fresh water and micro-CHP systems
• monitoring and control systems
• water treatment plants
• water utility and distribution systems
• HPC (High-Performance Computing) and IT cooling
systems.

5
Flow sensors
3
Electrical connections
Vortex Flow sensor, Industry (VFI and VFI+T2)

2 1
3 4

TM06 1070 1514


Fig. 6 Electrical connections

VFI Signal condition: 2-wire, loop-powered.

Pin 1 2 3 4

Wire colour Brown White Blue Black


Power Flow signal
I/O Not used Not used
supply 4-20 mA

Power supply: 12.5 - 30 V, screened cable.


VFI+T Signal condition: 4-wire

Pin 1 2 3 4

Wire colour Brown White Blue Black


Power Flow signal Temperature
I/O GND*
supply 0-10 V signal 0-10 V

* Common ground for pressure and temperature signals.


Power supply, screened cable: SELV or PELV.

Directives
The Grundfos Direct Sensors™ are in conformity with
these council directives on the approximation of the
laws of the EC member states:
• Low Voltage Directive (2014/35/EU)
– Standards used: EN 61010-1:2010
• EMC Directive (2014/30/EU).
– Standards used: EN 61326-1:2013 and EN
61326-2-3:2013
The Grundfos Direct Sensors™ are exempted from the
Pressure Equipment Directive (PED) according to
Article 4, paragraph 3 in the PED 2014/68/EU.

6
Flow sensors
3
VFI and VFI+T2, 0.3 - 6 m3/h (1.3 - Specifications

Vortex Flow sensor, Industry (VFI and VFI+T2)


26.4 gpm) Flow
Measuring range 0.3 - 6 m3/h (1.32 to 26.42 gpm)

TM04 7142 1710 - TM04 4250 1710


Accuracy (± 1 σ) in water, 0-100
± 1.5 % FS
°C (32-212 °F)
Response time (63.2 %) Less than 1 s
Resolution 0.0075 m3/h (0.03 gpm)
Temperature, VFI+T with temperature output
Measuring range -10 - 120 °C (14-248 °F)
Accuracy (± 1 σ),
± 0.5 K
15-90 °C (59-194 °F)
Accuracy (± 1 σ),
±1K
-10 - 120 °C (14-248 °F)
Response time
250 ms
(63.2 % at 50 % FS flow)
Fig. 7 VFI sensor with flanges and thread
Resolution 0.1 K
System conditions and environment
Dimensions
Aqueous media compatible with
wetted materials. Kinematic viscosity
Liquid types
less than or equal to 6 mm2/s (cSt).
See appendix Pressure drop curves
Maximum system pressure 30 bar (435 psig)
Burst pressure 40 bar (580 psig)
-30 to +110 °C (-22 to +230 °F),
Liquid temperature, operation
non-freezing
-30 to +110 °C (-22 to +230 °F),
Liquid temperature, peak
TM04 7154 1610

non-freezing
Ambient temperature, operation -25 to +60 °C (-13 to +140 °F)
Ambient temperature, peak -55 to +70 °C (-67 to +158 °F)
Storage temperature -55 to +70 °C (-67 to +158 °F)
Humidity, relative 0-95 %, non-condensing
Electrical data, VFI without temperature output
Fig. 8 Dimensions, VFI with flanges
Power supply, VFI 12.5 - 30 VDC
Output signals 4-20 mA
A B C D ISO/DIN flange, DN 18 pipe – Signal cut off 21 mA
mm 200 18 120 140 Maximum power consumption 660 mW
DN 25/32 PN 25/40 60 Ω at 12.5 VDC
in 7.87 0.71 4.72 5.51
100 Ω at 13.3 VDC
Maximum load impedance
For flanges according to ANSI and JIS standards or for 600 Ω at 24 VDC
900 Ω at 30 VDC
other pressure ranges, contact Grundfos Direct Maximum cable length 30 m (98 ft)
Sensors™. Electrical data, VFI+T with temperature output
Power supply 16.6 - 30 VDC
Output signals 0-10 VDC
(-10 °C at 0 V, 120 °C at 10 V)
– Signal cut off 11 VDC
Maximum power consumption 270 mW
Maximum load impedance 10 kΩ
TM04 7153 1610

Maximum cable length 30 m (98 ft)


Materials
Sensing element Silicon-based MEMS
O-ring EPDM or FKM
Housing Stainless steel 1.4404 (AISI 316 L)
Fig. 9 Dimensions, VFI with thread
Flow pipe Stainless steel 1.4408 (AISI 316)
Flange. no liquid contact Cast iron or stainless steel
A B C Thread size Bluff body Stainless steel 1.4401 (AISI 316 L)
mm 200 18 120 Corrosion-resistant coating, EPDM
G1 1/4" Wetted materials or FKM, Stainless steel 1.4401/04/08
in 7.87 0.71 4.72 (AISI 316 L)
Environmental standards
Sensor output signals Enclosure class IP67, cable connected
Temperature cycling IEC 68-2-14
VFI VFI+T
Vibration, non-destructive 20-2000 Hz, 10G, 4 h
TM06 0951 1316 - TM07 2164 2918

Electromagnetic compatibility EN 61326-1


10 V Complete weight
with cast iron flanges, cable etc 6.4 kg (14.1 lbs)
with stainless steel flanges,
5.2 kg (12.1 lbs)
cable etc
with thread, unions, fittings,
3.4 kg (7.5 lbs)
cable etc
0.5
Install the VFI sensor with threaded ends by means of
0 Q min Q max
T max union nuts with threaded ends by means of union nuts.
Fig. 10 Flow response

7
Flow sensors
3
VFI and VFI+T2, 0.6 - 12 m3/h (2.6 - Specifications
Vortex Flow sensor, Industry (VFI and VFI+T2)

52.8 gpm) Flow


Measuring range 0.6 - 12 m3/h (2.64 to 52.83 gpm)
Accuracy (± 1 σ) in water,

TM04 7143 1710 - TM04 4251 1710


± 1.5 % FS
0-100 °C (32-212 °F)
Response time (63.2 %) Less than 1 s
Resolution 0.015 m3/h (0.07 gpm)
Temperature, VFI+T with temperature output
Measuring range -10 - 120 °C (14-248 °F)
Accuracy (± 1 σ),
± 0.5 K
15-90 °C (59-194 °F)
Accuracy (± 1 σ),
±1K
-10 - 120 °C (14-248 °F)
Response time
250 ms
(63.2 % at 50 % FS flow)
Dimensions Resolution 0.1 K
System conditions and environment
Aqueous media compatible with
wetted materials. Kinematic viscosity
Liquid types
less than or equal to 6 mm2/s (cSt).
See appendix Pressure drop curves
Max. system pressure 30 bar (435 psig)
Burst pressure 40 bar (580 psig)
-30 to +110 °C (-22 to +230 °F),
Liquid temperature, operation
non-freezing
TM04 7154 1610

-30 to +110 °C (-22 to +230 °F),


Liquid temperature, peak
non-freezing
Ambient temperature,
-25 to +60 °C (-13 to +140 °F)
operation
Ambient temperature, peak -55 to +70 °C (-67 to +158 °F)
Fig. 11 Dimensions, VFI with flanges Storage temperature -55 to +70 °C (-67 to +158 °F)
Humidity, relative 0-95 %, non-condensing
Electrical data, VFI without temperature output
A B C D ISO/DIN flange, DN 25 pipe
Power supply 12.5 - 30 VDC (± 5 %)
mm 200 18 124 140 Output signals 4-20 mA
DN 25/32 PN 16/25/40
in 7.87 0.71 4.88 5.51 – Signal cut off 21 mA
Maximum power consumption 660 mW
For flanges according to ANSI and JIS standards or for 60 Ω at 12.5 VDC
other pressure ranges, contact Grundfos Direct 100 Ω at 13.3 VDC
Maximum load impedance
600 Ω at 24 VDC
Sensors™. 900 Ω at 30 VDC
Maximum cable length 30 m (98 ft)
Electrical data, VFI+T with temperature output
Power supply, VFI 16.6 - 30 VDC
Output signals 0-10 VDC
(-10 °C at 0 V, 120 °C at 10 V)
TM04 7153 1610

– Signal cut off 11 VDC


Maximum power consumption 270 mW
Maximum load impedance 10 kΩ
Maximum cable length 30 m (98 ft)
Materials
Fig. 12 Dimensions, VFI with thread Sensing element Silicon-based MEMS
O-ring EPDM or FKM
Housing Stainless steel 1.4404 (AISI 316 L)
A B C Thread size Flow pipe Stainless steel 1.4408 (AISI 316)
mm 200 18 124 Flange, no liquid contact Cast iron or stainless steel
G1 1/4"
in 7.87 0.71 4.88 Bluff body Stainless steel 1.4401 (AISI 316 L)
Corrosion-resistant coating, EPDM or
Wetted materials FKM, Stainless steel 1.4401/04/08
Sensor output signals (AISI 316 L)
VFI VFI+T Environmental standards
Enclosure class IP67, cable connected
TM06 0951 1316 - TM07 2164 2918

Temperature cycling IEC 68-2-14


10 V Vibration, non-destructive 20-2000 Hz, 10G, 4 h
Electromagnetic compatibility EN 61326-1
Complete weight
with cast iron flanges, cable etc 6.5 kg (14.3 lbs)
with stainless steel flanges,
5.6 kg (12.3 lbs)
cable etc
0.5
with thread, unions, fittings,
3.6 kg (7.9 lbs)
0 Q min Q max cable etc
T max
Install the VFI sensor with threaded ends by means of
Fig. 13 Flow response
union nuts.

8
Flow sensors
3
VFI and VFI+T2, 1.3 - 25 m3/h (5.7 - Specifications

Vortex Flow sensor, Industry (VFI and VFI+T2)


110 gpm) Flow
Measuring range 1.3 - 25 m3/h (5.72 to 110.07 gpm)
Accuracy (± 1 σ) in water,

TM04 7144 1710 - TM04 4252 1710


± 1.5 % FS
0-100 °C (32-212 °F)
Response time Less than 1 s
Resolution 0.031 m3/h (0.14 gpm)
Temperature, VFI+T with temperature output
Measuring range -10 - 120 °C (14-248 °F)
Accuracy (± 1 σ),
± 0.5 K
15-90 °C (59-194 °F)
Accuracy (± 1 σ),
±1K
-10 - 120 °C (14-248 °F)
Response time
250 ms
(63.2 % at 50 % FS flow)
Resolution 0.1 K
Dimensions
System conditions and environment
Aqueous media compatible with
wetted materials. Kinematic viscosity
Liquid types
less than or equal to 6 mm2/s (cSt).
See appendix Pressure drop curves
Max. system pressure 30 bar (435 psig)
Burst pressure 40 bar (580 psig)
-30 to +110 °C (-22 to +230 °F),
Liquid temperature, operation
non-freezing
TM04 7154 1610

-30 to +110 °C (-22 to +230 °F),


Liquid temperature, peak
non-freezing
Ambient temperature, operation -25 to +60 °C (-13 to +140 °F)
Ambient temperature, peak -55 to +70 °C (-67 to +158 °F)
Storage temperature -55 to +70 °C (-67 to +158 °F)
Humidity, relative 0-95 %, non-condensing
Fig. 14 Dimensions, VFI with flanges
Electrical data, VFI without temperature output
Power supply, VFI 12.5 - 30 VDC
A B C D ISO/DIN flange, DN 32 pipe Output signals 4-20 mA
mm 200 18 128 140 – Signal cut off 21 mA
DN 25/32 PN 16/25/40 Maximum power consumption 660 mW
in 7.87 0.71 5.04 5.51
60 Ω at 12.5 VDC
For flanges according to ANSI and JIS standards or for 100 Ω at 13.3 VDC
Maximum load impedance
600 Ω at 24 VDC
other pressure ranges, contact Grundfos Direct 900 Ω at 30 VDC
Sensors™. Maximum cable length 30 m (98 ft)
Electrical data, VFI+T with temperature output
Power supply, VFI 16.6 - 30 VDC
Output signals 0-10 VDC
(-10 °C at 0 V, 120 °C at 10 V)
– Signal cut off 11 VDC
Maximum power consumption 270 mW
TM04 7153 1610

Maximum load impedance 10 kΩ


Maximum cable length 30 m (98 ft)
Materials
Sensing element Silicon-based MEMS
O-ring EPDM or FKM
Fig. 15 Dimensions, VFI with thread housing Stainless steel 1.4404 (AISI 316 L)
Flow pipe Stainless steel 1.4408 (AISI 316)
A B C Thread size Flange, no liquid contact Cast iron or stainless steel
Bluff body Stainless steel 1.4401 (AISI 316 L)
mm 200 19 128
G1 1/2" Corrosion-resistant coating, EPDM
in 7.87 0.75 5.04 Wetted materials or FKM, Stainless steel
1.4401/04/08 (AISI 316 L)
Sensor output signals Environmental standards
Enclosure class IP67, cable connected
VFI VFI+T
Temperature cycling IEC 68-2-14
TM06 0951 1316 - TM07 2164 2918

Vibration, non-destructive 20-2000 Hz, 10G, 4 h


10 V Electromagnetic compatibility EN 61326-1
Complete weight
with cast iron flanges, cable etc 6.5 kg (14.3 lbs)
with stainless steel flanges,
5.6 kg (12.3 lbs)
cable etc
with thread, unions, fittings,
3.9 kg (8.6 lbs)
0.5 cable etc

0 Q min Q max Install the VFI sensor with threaded ends by means of
T max
union nuts.
Fig. 16 Flow response

9
Flow sensors
3
VFI and VFI+T2, 2-40 m3/h (8.8 - 176 Specifications
Vortex Flow sensor, Industry (VFI and VFI+T2)

gpm) Flow
Measuring range 2-40 m3/h (8.81 to 176.11 gpm)
Accuracy (± 1 σ) in water,
± 1.5 % FS
0-100 °C (32-212 °F)
Response time Less than 1 s
Resolution 0.05 m3/h (0.22 gpm)
Temperature, VFI+T with temperature output

TM04 7145 1710


Measuring range -10 - 120 °C (14-248 °F)
Accuracy (± 1 σ),
± 0.5 K
15-90 °C (59-194 °F)
Accuracy (± 1 σ),
±1K
-10 - 120 °C (14-248 °F)
Fig. 17 VFI 2-40 sensor Response time
250 ms
(63.2 % at 50 % FS flow)
Resolution 0.1 K
Dimensions
System conditions and environment
Aqueous media compatible with
wetted materials. Kinematic viscosity
Liquid types
less than or equal to 6 mm2/s (cSt).
See appendix Pressure drop curves
Maximum system pressure 30 bar (435 psig)
Burst pressure 40 bar (580 psig)
-30 to +110 °C (-22 to +230 °F),
Liquid temperature, operation
non-freezing
-30 to +110 °C (-22 to +230 °F),
Liquid temperature, peak
TM04 7154 1610

non-freezing
Ambient temperature,
-25 to +60 °C (-13 to +140 °F)
operation
Ambient temperature, peak -55 to +70 °C (-67 to +158 °F)
Storage temperature -55 to +70 °C (-67 to +158 °F)
Fig. 18 Dimensions, VFI with flanges Humidity, relative 0-95 %, non-condensing
Electrical data, VFI without temperature output
Power supply 12.5 - 30 VDC (± 5 %)
A B C D ISO/DIN flange
Output signals 4-20 mA
mm 200 18 131 150 – Signal cut off 21 mA
DN 40 PN 16/25/40
in 7.87 0.71 5.16 5.91 Maximum power consumption 660 mW
60 Ω at 12.5 VDC
For flanges according to ANSI and JIS standards or for 100 Ω at 13.3 VDC
Maximum load impedance
other pressure ranges, contact Grundfos Direct 600 Ω at 24 VDC
900 Ω at 30 VDC
Sensors™.
Maximum cable length 30 m (98 ft)
Electrical data, VFI+T with temperature output
Sensor output signals
Power supply, VFI 16.6 - 30 VDC
VFI VFI+T Output signals 0-10 VDC
(-10 °C at 0 V, 120 °C at 10 V)
TM06 0951 1316 - TM07 2164 2918

– Signal cut off 11 VDC


10 V Maximum power consumption 270 mW
Maximum load impedance 10 kΩ
Maximum cable length 30 m (98 ft)
Materials
Sensing element Silicon-based MEMS
O-ring EPDM or FKM
0.5
Housing Stainless steel 1.4404 (AISI 316 L)
0 Q min Q max Flow pipe Stainless steel 1.4408 (AISI 316)
T max
Flange, no liquid contact Cast iron or stainless steel
Fig. 19 Flow response Bluff body Stainless steel 1.4401 (AISI 316 L)
Corrosion-resistant coating, EPDM or
Wetted materials FKM, Stainless steel 1.4401/04/08
(AISI 316 L)
Environmental standards
Enclosure class IP67, cable connected
Temperature cycling IEC 68-2-14
Vibration, non-destructive 20-2000 Hz, 10G, 4 h
Electromagnetic compatibility EN 61326-1
Complete weight
With cast iron flanges, cable
7.4 kg (16.3 lbs)
etc
With stainless steel flanges,
6.5 kg (14.3 lbs)
cable etc

10
Flow sensors
3
VFI and VFI+T2, 3.2 - 64 m3/h Specifications

Vortex Flow sensor, Industry (VFI and VFI+T2)


(14-282 gpm) Flow
Measuring range 3.2 - 64 m3/h (14.09 to 281.78 gpm)
Accuracy (± 1 σ) in water,
± 1.5 % FS
0-100 °C (32-212 °F)
Response time (63.2 %) Less than 1 s
Resolution 0.08 m3/h (0.35 gpm)
Temperature, VFI+T with temperature output

TM04 7146 1710


Measuring range -10 - 120 °C (14-248 °F)
Accuracy (± 1 σ),
± 0.5 K
15-90 °C (59-194 °F)
Accuracy (± 1 σ),
±1K
-10 - 120 °C (14-248 °F)
Fig. 20 VFI sensor Response time
250 ms
(63.2 % at 50 % FS flow)
Dimensions Resolution 0.1 K
System conditions and environment
Aqueous media compatible with
wetted materials. Kinematic viscosity
Liquid types
less than or equal to 6 mm2/s (cSt).
See appendix Pressure drop curves
Maximum system pressure 30 bar (435 psig)
Burst pressure 40 bar (580 psig)
-30 to +110 °C (-22 to +230 °F),
Liquid temperature, operation
non-freezing
-30 to +110 °C (-22 to +230 °F),
TM04 7154 1610

Liquid temperature, peak


non-freezing
Ambient temperature,
-25 to +60 °C (-13 to +140 °F)
operation
Ambient temperature, peak -55 to +70 °C (-67 to +158 °F)
Storage temperature -55 to +70 °C (-67 to +158 °F)
Fig. 21 Dimensions, VFI with flanges Humidity, relative 0-95 %, non-condensing
Electrical data, VFI without temperature output
A B C D ISO/DIN flange Power supply 12.5 - 30 VDC
mm 200 22 138 165 Output signals 4-20 mA
DN 50 PN16/25/40 – Signal cut off 21 mA
in 7.87 0.87 5.43 6.50
Maximum power consumption 660 mW
For flanges according to ANSI and JIS standards or for 60 Ω at 12.5 VDC
100 Ω at 13.3 VDC
other pressure ranges, contact Grundfos Direct Maximum load impedance
600 Ω at 24 VDC
Sensors™. 900 Ω at 30 VDC
Maximum cable length 30 m (98 ft)
Sensor output signals Electrical data, VFI+T with temperature output
Power supply 16.6 - 30 VDC
VFI VFI+T
Output signals 0-10 VDC
TM06 0951 1316 - TM07 2164 2918

(-10 °C at 0 V, 120 °C at 10 V)
– Signal cut off 11 VDC
10 V
Maximum power consumption 270 mW
Maximum load impedance 10 kΩ
Maximum cable length 30 m (98 ft)
Materials
Sensing element Silicon-based MEMS
0.5
O-ring EPDM or FKM
0 Q min Q max
Housing Stainless steel 1.4404 (AISI 316 L)
T max Flow pipe Stainless steel 1.4408 (AISI 316)
Fig. 22 Flow response Flange, no liquid contact Cast iron or stainless steel
Bluff body Stainless steel 1.4401 (AISI 316 L)
Corrosion-resistant coating, EPDM
Wetted materials or FKM, Stainless steel 1.4401/04/08
(AISI 316 L)
Environmental standards
Enclosure class IP67, cable connected
Temperature cycling IEC 68-2-14
Vibration, non-destructive 20-2000 Hz, 10G, 4 h
Electromagnetic compatibility EN 61326-1
Complete weight
With cast iron flanges, cable
9.4 kg (20.7 lbs)
etc
With stainless steel flanges,
8.2 kg (18.0 lbs)
cable etc

11
Flow sensors
3
VFI and VFI+T2, 5.2 - 104 m3/h Specifications
Vortex Flow sensor, Industry (VFI and VFI+T2)

(23-458 gpm) Flow


Measuring range 5.2 - 104 m3/h (22.89 - 457.89 gpm)
Accuracy (± 1 σ) in water,
± 1.5 % FS
0-100 °C (32-212 °F)
Response time Less than 1 s
Resolution 0.13 m3/h (0.57 gpm)
Temperature, VFI+T with temperature output

TM04 7147 1710


Measuring range -10 - 120 °C (14-248 °F)
Accuracy (± 1 σ),
± 0.5 K
15-90 °C (59-194 °F)
Accuracy (± 1 σ),
±1K
-10 - 120 °C (14-248 °F)
Fig. 23 VFI sensor Response time
250 ms
(63.2 % at 50 % FS flow)
Resolution 0.1 K
Dimensions
System conditions and environment
Aqueous media compatible with
wetted materials. Kinematic
Liquid types viscosity less than or equal to 6
2
mm /s (cSt). See appendix Pressure
drop curves
Maximum system pressure 30 bar (435 psig)
Burst pressure 40 bar (580 psig)
-30 to +110 °C (-22 to +230 °F),
Liquid temperature, operation
non-freezing
TM04 7154 1610

-30 to +110 °C (-22 to +230 °F),


Liquid temperature, peak
non-freezing
Ambient temperature, operation -25 to +60 °C (-13 to +140 °F)
Ambient temperature, peak -55 to +70 °C (-67 to +158 °F)
Storage temperature -55 to +70 °C (-67 to +158 °F)
Fig. 24 Dimensions, VFI with flanges Humidity, relative 0-95 %, non-condensing
Electrical data, VFI without temperature output
A B C D ISO/DIN flange Power supply, VFI 12.5 - 30 VDC (± 5 %)
Output signals 4-20 mA
mm 200 25 145 185
DN 65 PN 16/25/40 – Signal cut off 21 mA
in 7.87 0.98 5.71 7.28
Maximum power consumption 660 mW
For flanges according to ANSI and JIS standards or for 60 Ω at 12.5 VDC
100 Ω at 13.3 VDC
other pressure ranges, contact Grundfos Direct Maximum load impedance
600 Ω at 24 VDC
Sensors™. 900 Ω at 30 VDC
Maximum cable length 30 m (98 ft)
Sensor output signals Electrical data, VFI+T with temperature output
Power supply, VFI 16.6 - 30 VDC
VFI VFI+T Output signals 0-10 VDC
TM06 0951 1316 - TM07 2164 2918

(-10 °C at 0 V, 120 °C at 10 V)
– Signal cut off 11 VDC
10 V
Maximum power consumption 270 mW
Maximum load impedance 10 kΩ
Maximum cable length 30 m (98 ft)
Materials
Sensing element Silicon-based MEMS
0.5 O-ring EPDM or FKM
0 Q min
Housing Stainless steel 1.4404 (AISI 316 L)
Q max
T max Flow pipe Stainless steel 1.4408 (AISI 316)
Flange, no liquid contact Cast iron or stainless steel
Fig. 25 Flow response
Bluff body Stainless steel 1.4401 (AISI 316 L)
Corrosion-resistant coating,PDM or
Wetted materials FKM,tainless steel 1.4401/04/08
(AISI 316 L)
Environmental standards
Enclosure class IP67, cable connected
Temperature cycling IEC 68-2-14
Vibration, non-destructive 20-2000 Hz, 10G, 4 h
Electromagnetic compatibility EN 61326-1
Complete weight
With cast iron flanges, cable etc 11.5 kg (25.3 lbs)
With stainless steel flanges,
11.9 kg (26.2 lbs)
cable etc

12
Flow sensors
3
VFI and VFI+T2, 8-160 m3/h (35-704 Specifications

Vortex Flow sensor, Industry (VFI and VFI+T2)


gpm) Flow
Measuring range 8-160 m3/h (35.22 to 704.46 gpm)
Accuracy (± 1 σ) in water,
± 1.5 % FS
0-100 °C (32-212 °F)
Response time Less than 1 s
Resolution 0.2 m3/h (0.88 gpm)
Temperature, VFI+T with temperature output

TM04 7148 1710


Measuring range -10 - 120 °C (14-248 °F)
Accuracy (± 1 σ),
± 0.5 K
15-90 °C (59-194 °F)
Accuracy (± 1 σ),
±1K
-10 - 120 °C (14-248 °F)
Fig. 26 VFI sensor Response time
250 ms
(63.2 % at 50 % FS flow)
Resolution 0.1 K
Dimensions
System conditions and environment
Aqueous media compatible with
wetted materials. Kinematic
Liquid types viscosity less than or equal to 6
2
mm /s (cSt). See appendix Pressure
drop curves
Maximum system pressure 30 bar (435 psig)
Burst pressure 40 bar (580 psig)
-30 to +110 °C (-22 to +230 °F),
Liquid temperature, operation
non-freezing
TM04 7154 1610

-30 to +110 °C (-22 to +230 °F),


Liquid temperature, peak
non-freezing
Ambient temperature, operation -25 to +60 °C (-13 to +140 °F)
Ambient temperature, peak -55 to +70 °C (-67 to +158 °F)
Storage temperature -55 to +70 °C (-67 to +158 °F)
Fig. 27 Dimensions, VFI with flanges Humidity, relative 0-95 %, non-condensing
Electrical data, VFI without temperature output
Power supply 12.5 - 30 VDC (± 5 %)
A B C D ISO/DIN flange
Output signals 4-20 mA
mm 200 25 152 200 – Signal cut off 21 mA
DN 80 PN 16/25/40
in 7.87 0.98 5.98 7.87 Maximum power consumption 660 mW
60 Ω at 12.5 VDC
For flanges according to ANSI and JIS standards or for 100 Ω at 13.3 VDC
other pressure ranges, contact Grundfos Direct Maximum load impedance
600 Ω at 24 VDC
Sensors™. 900 Ω at 30 VDC
Maximum cable length 30 m (98 ft)
Sensor output signals Electrical data, VFI+T with temperature output
Power supply 16.6 - 30 VDC
VFI VFI+T Output signals 0-10 VDC
TM06 0951 1316 - TM07 2164 2918

(-10 °C at 0 V, 120 °C at 10 V)
– Signal cut off 11 VDC
10 V
Maximum power consumption 270 mW
Maximum load impedance 10 kΩ
Maximum cable length 30 m (98 ft)
Materials
Sensing element Silicon-based MEMS
0.5 O-ring EPDM or FKM
0
Housing Stainless steel 1.4404 (AISI 316 L)
Q min Q max
T max Flow pipe Stainless steel 1.4408 (AISI 316)
Flange, no liquid contact Cast iron or stainless steel
Fig. 28 Flow response
Bluff body Stainless steel 1.4401 (AISI 316 L)
Corrosion-resistant coating, EPDM
Wetted materials or FKM, Stainless steel
1.4401/04/08 (AISI 316 L)
Environmental standards
Enclosure class IP67, cable connected
Temperature cycling IEC 68-2-14
Vibration, non-destructive 20-2000 Hz, 10G, 4 h
Electromagnetic compatibility EN 61326-1
Complete weight
With cast iron flanges, cable etc 13.2 kg (29.0 lbs)
With stainless steel flanges,
13.7 kg (30.1 lbs)
cable etc

13
Flow sensors
3
VFI and VFI+T2, 12-240 m3/h Specifications
Vortex Flow sensor, Industry (VFI and VFI+T2)

(53-1057 gpm) Flow


Measuring range 12-240 m3/h (52.83 to 1056.69 gpm)
Accuracy (± 1 σ) in water,
± 1.5 % FS
0-100 °C (32-212 °F)
Response time Less than 1 s
Resolution 0.30 m3/h (1.32 gpm)
Temperature, VFI+T with temperature output

TM04 7149 1710


Measuring range -10 - 120 °C (14-248 °F)
Accuracy (± 1 σ),
± 0.5 K
15-90 °C (59-194 °F)
Accuracy (± 1 σ),
±1K
-10 - 120 °C (14-248 °F)
Fig. 29 VFI sensor Response time
250 ms
(63.2 % at 50 % FS flow)
Resolution 0.1 K
Dimensions
System conditions and environment
Aqueous media compatible with
wetted materials. Kinematic viscosity
Liquid types
less than or equal to 6 mm2/s (cSt).
See appendix Pressure drop curves
Maximum system pressure 30 bar (435 psig)
Burst pressure 40 bar (580 psig)
-30 to +110 °C (-22 to +230 °F),
Liquid temperature, operation
non-freezing
-30 to +110 °C (-22 to +230 °F),
Liquid temperature, peak
TM04 7154 1610

non-freezing
Ambient temperature,
-25 to +60 °C (-13 to +140 °F)
operation
Ambient temperature, peak -55 to +70 °C (-67 to +158 °F)
Storage temperature -55 to +70 °C (-67 to +158 °F)
Fig. 30 Dimensions, VFI with flanges Humidity, relative 0-95 %, non-condensing
Electrical data
Power supply 12.5 - 30 VDC (± 5 %)
A B C D ISO/DIN flange
Output signals 4-20 mA
mm 250 25 163 235 – Signal cut off 21 mA
DN 100 PN 25/40
in 9.84 0.98 6.42 9.25 Maximum power consumption 660 mW
60 Ω at 12.5 VDC
For flanges according to ANSI and JIS standards or for 100 Ω at 13.3 VDC
other pressure ranges, contact Grundfos Direct Maximum load impedance
600 Ω at 24 VDC
Sensors™. Flanged with PN 16 available upon 900 Ω at 30 VDC
request. Maximum cable length 30 m (98 ft)
Electrical data, VFI+T with temperature output
Sensor output signals Power supply 16.6 - 30 VDC
Output signals 0-10 VDC
VFI VFI+T (-10 °C at 0 V, 120 °C at 10 V)
– Signal cut off 11 VDC
TM06 0951 1316 - TM07 2164 2918

Maximum power consumption 270 mW


10 V Maximum load impedance 10 kΩ
Maximum cable length 30 m (98 ft)
Materials
Sensing element Silicon-based MEMS
O-ring EPDM or FKM
0.5 Housing Stainless steel 1.4404 (AISI 316 L)
Flow pipe Stainless steel 1.4408 (AISI 316)
0 Q min Q max
T max Flange, no liquid contact Cast iron or stainless steel
Bluff body Stainless steel 1.4401 (AISI 316 L)
Fig. 31 Flow response Corrosion-resistant coating, EPDM or
Wetted materials FKM, Stainless steel 1.4401/04/08
(AISI 316 L)
Environmental standards
Enclosure class IP67, cable connected
Temperature cycling IEC 68-2-14
Vibration, non-destructive 20-2000 Hz, 10G, 4 h
Electromagnetic compatibility EN 61326-1
Complete weight
With cast iron flanges, cable
18.1 kg (39.8 lbs)
etc
With stainless steel flanges,
18.1 kg (39.8 lbs)
cable etc

14
Flow sensors
4

4. Vortex Flow sensor, Standard (VFS and VFS QT)

Vortex Flow sensor, Standard (VFS and VFS QT)


General data Flow range
l/min gpm
1-18 0.26 - 4.76
1.3 - 20 0.34 - 5.28

TM05 4745 2412


2-40 0.53 - 10.57
5-100 1.32 - 26.42
10-200 2.64 - 52.83
20-400 5.28 - 105.67

Fig. 32 VFS and VFS QT sensors Approvals (w/EPDM O-rings)


• WRAS
Technical overview • KTW
The VFS is a combined flow and temperature sensor • AS4020
(two-in-one) from Grundfos Direct Sensors™. The • ACS.
sensor is based on the principle of vortex shedding
behind a bluff body. Certificates
The VFS sensor is fully compatible with wet,
aggressive liquids. The sensor is based on MEMS
sensing technology in combination with the
corrosion-resistant Silicoat® coating technology on the + 75
sensor chip. CE C, CSA, US EAC
The sensor is supplied with a flow pipe.
Electrical connections
Applications Analog signal Digital signal
• Pump control
Electrical
• HVAC systems connector
• temperature control and chiller systems
1 2 3 4 Pin No 1 2 3 4
• renewable energies such as heat pumps, solar
thermals, fresh water and micro-CHP systems Analog signal 1
• monitoring and control systems Analog signal 2
V 3Y
• water treatment plants
V 5Y

TM04 7156 1610


• water utility and distribution systems Pipe system

• HPC (High-Performance Computing) and IT cooling


systems.
PE PE

Features and benefits Fig. 33 Electrical connections


• Measurement principle with no movable parts,
resulting in no wear and tear Description Description
Pin Colour
Analogue signal Digital signal
• flow and temperature measurement in one sensor
(two-in-one solution) for easy and cost-efficient 1 Temperature signal Rx Yellow

installation 2 Pressure signal Tx White


3 GND, 0 V PELV GND, 0 V PELV Green
• MEMS technology
4 Voltage supply, +5 VDC Power supply, +5 VDC Brown
• direct contact with the aqueous media resulting in a
fast response time Power supply requirements
• plug and play for quick setup • 5 VDC ± 5 %, PELV
• smart system solution with Grundfos pump controls • Ratiometric
• compact and robust design • Max. 10 mV ripple: 50 Hz
• compatible with aqueous media • Min. output current: 25 mA
• suitable for a wide temperature range • Separated from hazardous live circuitry by double or
• suitable for a wide range of applications. reinforced insulation.
• For aqueous media below 2 µS/cm contact your • Grounding of the sensor supply is required.
local Grundfos sensor representative.

15
Flow sensors
4
Directives VFS QT sensors
Vortex Flow sensor, Standard (VFS and VFS QT)

The Grundfos Direct Sensors™ are in conformity with


these council directives on the approximation of the
laws of the EC member states:
• Low Voltage Directive (2014/35/EU)
– Standards used: EN 61010-1:2010
• EMC Directive (2014/30/EU).
– Standards used: EN 61326-1:2013 and EN
61326-2-3:2013

TM05 4743 2512


The Grundfos Direct Sensors™ are exempted from the
Pressure Equipment Directive (PED) according to
Article 4, paragraph 3 in the PED 2014/68/EU.

VFS sensors Fig. 35 The VFS QT family

The VFS QT flow sensor consists of a composite


insert, a stainless steel flow pipe and a sensor fitted
with cable.
The VFS QT flow sensor is available in 1-18, 2-40,
5-100, 10-200 l/min versions.

Snap-on sensor

TM05 4750 2512 - TM05 4752 2512


TM05 4744 2512

Fig. 34 The VFS family

The VFS flow sensor consists of a composite flow pipe Fig. 36 Snap-on sensor
and a sensor fitted with cable.
The VFS flow sensor is available in 1-20, 2-40, 5-100, Differential Temperature
10-200, 20-400 l/min versions.
The differential temperature is between two standard
Direct Sensors TM from Grundfos.

16
Flow sensors
4
VFS, 1-20 l/min (0.2 - 5.3 gpm) Specifications

Vortex Flow sensor, Standard (VFS and VFS QT)


Flow
Measuring range 1.3-20 l/min (0.34 to 5.3 gpm)
Accuracy (± 1 σ) in water,
± 1 % FS
0-120 °C (32-248 °F)
Response time (63.2 %) Less than 1 s
Resolution max flow/16384 l/min or gpm

TM05 4751 2512


Temperature
Measuring range 0-120 °C (32-248 °F)
Accuracy (± 1 σ),
± 0.5 K
15-90 °C (59-194 °F)
Accuracy (± 1 σ),
±1K
Fig. 37 VFS, 1-20 l/min 0-120 °C (32-248 °F)
Response time
250 ms
(63.2 % at 50 % FS flow)
Dimensions Resolution 0.006 K
Differential Temperature
Accuracy 15-90 °C (59-194 °F) 0.3 K
Accuracy 0-120 °C (32-248 °F) 0.5 K
System conditions and environment
Aqueous media compatible with
TM06 3420 0314 Liquid types wetted materials. Kinematic viscosity
less than 2 mm2/s (cSt)
Liquid temperature, operation Water: 0-100 °C (32-212 °F)
-25 °C (-13 °F), non-freezing 120 °C
Liquid temperature, peak (248 °F) for 5 minutes, up to 3 weeks
in sensor lifetime
Fig. 38 Dimensions, VFS, 1-20 l/min, without adapter
Ambient temperature, operation -25 to +60 °C (-13 to -140 °F)
Ambient temperature, peak -55 to +90 °C (-67 to 194 °F)
Humidity, relative 0-95 %, non-condensing
Maximum System Pressure 24 bar (348 psig)
Burst Pressure 30 bar (435 psig)
Maximum system pressure Max 10 bar (145 psig) at 100 °C
TM06 3425 0314

examples (212 °F)


Electrical data
5 VDC (± 5 %), PELV
Power supply
Grounding of sensor supply required
Output signals Ratiometric
Fig. 39 Dimensions, VFS, 1-20 l/min, with adapters Digital output signals Grundfos open data protocol
0.5 - 3.5 V for flow (zero at 0.35 V)
Analog output signals 0.5 - 4.1 V for temperature
A B C D E F (zero at 0.5 V and 100 °C at 3.5 V)
mm 82 ∅19.8 65 36 153.6 ISO 228 - G 1/2 A Power consumption Appr. 75 mW
in 3.23 ∅0.78 2.56 1.42 6.05 1/2" NPT Load impedance > 47 kΩ
Maximum cable length 3 m (9.10 ft)
Sensor output signals Materials
Sensing element Silicon-based MEMS
EPDM O-rings, FKM O-rings or
3.5 Sealing
EPDM sealing cap with FKM O-rings
Flow output signal

3.0
2.5 Housing Composite (PPS, PA66)
TM07 2484 3618

2.0 Flow pipe PPA 40-GF


1.5 Corrosion-resistant coating, EPDM
1.0 Wetted materials
or FKM, PPS, PPA 40-GF
0.5
Environmental standards
0.0
0 Q min Q max Enclosure class IP44, cable connected
Temperature cycling IEC 68-2-14
Fig. 40 Flow response in Analogue mode
Vibration, non-destructive 20-2000 Hz, 10G, 4 h
Electromagnetic compatibility EN 61326-1
[V]
Temperature output signal

4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
TM06 3354 5214

0.5
0.0
0 120
Tmax
T max ==
Peak temperature
peak temperature

Fig. 41 Temperature response in Analogue mode

17
Flow sensors
4
VFS, 2-40 l/min (0.5 - 10.6 gpm) Specifications
Vortex Flow sensor, Standard (VFS and VFS QT)

Flow
Measuring range 2-40 l/min (0.5 - 10.6 gpm)
Accuracy (± 1 σ) in water,
± 1 % FS
0-100 °C (32-212 °F)
Response time (63.2 %) Less than 1 s
Resolution max flow/16384 l/min or gpm

TM05 4749 2512


Temperature
Measuring range 0-120 °C (32-248 °F)
Accuracy (± 1 σ),
± 0.5 K
15-90 °C (59-194 °F)
Accuracy (± 1 σ),
±1K
0-120 °C (32-248 °F)
Fig. 42 VFS, 2-40 l/min Response time
250 ms
(63.2 % at 50 % FS flow)
Dimensions Resolution 0.006 K
Differential Temperature
Accuracy 15-90 °C (59-194 °F) 0.3 K
Accuracy 0-120 °C (32-248 °F) 0.5 K
System conditions and environment
TM06 3421 0314 Aqueous media compatible with
wetted materials. Kinematic
Liquid types
viscosity less than or equal to 2
mm2/s (cSt)
Liquid temperature, operation Water: 0-100 °C (32-212 °F)
-25 °C (-13 °F), non-freezing
Fig. 43 Dimensions, VFS, 2-40 l/min, without adapter Liquid temperature, peak 120 °C (248 °F) for 5 minutes, up to
3 weeks in sensor lifetime
Ambient temperature,
-25 to +60 °C (-13 to +140 °F)
operation
Ambient temperature, peak -55 to +90 °C (-67 to +194 °F)
Humidity, relative 0-95 %, non-condensing
TM06 3426 0314

Maximum System Pressure 24 bar (348 psig)


Burst Pressure 30 bar (435 psig)
Maximum system pressure Max 10 bar (145 psig) at 100 °C
examples (212 °F)
Electrical data
Fig. 44 Dimensions, VFS, 2-40 l/min, with adapters 5 VDC (± 5 %), PELV
Power supply
Grounding of sensor supply required
Output signals Ratiometric
A B C D E F Digital output signals Grundfos open data protocol
ISO 228/1 - 0.5 - 3.5 V for flow (zero at 0.35 V)
mm 88 ∅22.8 66 38 157.4
G 3/4 A Analog output signals 0.5 - 4.1 V for temperature
in 3.46 ∅0.19 2.60 1.50 6.20 3/4" NPT (zero at 0.5 V and 100 °C at 3.5 V)
Power consumption Appr. 75 mW
Sensor output signals Load impedance > 47 kΩ
Maximum cable length 3 m (9.10 ft)
Materials
3.5
Sensing element Silicon-based MEMS
Flow output signal

3.0
2.5 EPDM-O-rings or FKM O-rings or
Sealing
TM07 2484 3618

2.0 EPDM sealing cap with FKM O-rings


1.5 Housing Composite (PPS, PA66)
1.0
0.5 Flow pipe PPA 40-GF
0.0 Corrosion-resistant coating, EPDM
0 Q min Q max Wetted materials
or FKM, PPS, PPA 40-GF

Fig. 45 Flow response in Analogue mode Environmental standards


Enclosure class IP44, cable connected
Temperature cycling IEC 68-2-14
[V] Vibration, non-destructive 20-2000 Hz, 10G, 4 h
Temperature output signal

4.5
Electromagnetic compatibility EN 61326-1
4.0
3.5
3.0
2.5
2.0
1.5
1.0
TM06 3354 5214

0.5
0.0
0 120
Tmax
T max ==
Peak temperature
peak temperature

Fig. 46 Temperature response in Analogue mode

18
Flow sensors
4
VFS, 5-100 l/min (1.3 - 26 gpm) Specifications

Vortex Flow sensor, Standard (VFS and VFS QT)


Flow
Measuring range 5-100 l/min (1.3 to 26.4 gpm)
Accuracy (± 1 σ) in water,
± 1 % FS
0-100 °C (32-212 °F)
Response time (63.2 %) Less than 1 s

TM05 4748 2512


Resolution max flow/16384 l/min or gpm
Temperature
Measuring range 0-120 °C (32-248 °F)
Accuracy (± 1 σ),
± 0.5 K
15-90 °C (59-194 °F)
Fig. 47 VFS, 5-100 l/min Accuracy (± 1 σ),
±1K
0-120 °C (32-248 °F)
Response time
Dimensions (63.2 % at 50 % FS flow)
250 ms

Resolution 0.006 K
Differential Temperature
Accuracy 15-90 °C (59-194 °F) 0.3 K

TM06 3422 0314


Accuracy 0-120 °C (32-248 °F) 0.5 K
System conditions and environment
Aqueous media compatible with
wetted materials. Kinematic
Liquid types
viscosity less than or equal to 2
mm2/s (cSt)
Fig. 48 Dimensions, VFS, 5-100 l/min, without adapter Liquid temperature, operation Water: 0-100 °C (32-212 °F)
-25 °C (-13 °F), non-freezing
Liquid temperature, peak 120 °C (248 °F) for 5 minutes, up to
3 weeks in sensor lifetime
TM06 3427 0314

Ambient temperature,
-25 to +60 °C (-13 to +140 °F)
operation
Ambient temperature, peak -55 to +90 °C (-67 to +194 °F)
Humidity, relative 0-95 %, non-condensing
Maximum System Pressure 24 bar (348 psig)
Fig. 49 Dimensions, VFS, 5-100 l/min, with adapters Burst Pressure 30 bar (435 psig)
Maximum system pressure Max 10 bar (145 psig) at 100 °C
examples (212 °F)
A B C D E F
Electrical data
ISO 7/1 - 5 VDC (± 5 %), PELV
mm 129 ISO 228/1 - 65 - 223 Power supply
Rc 3/4 Grounding of sensor supply required
G1A
in 5.08 2.56 - 8.78 3/4" NPT Output signals Ratiometric
Digital output signals Grundfos open data protocol
Sensor output signals 0.5 - 3.5 V for flow (zero at 0.35 V)
Analog output signals 0.5 - 4.1 V for temperature
(zero at 0.5 V and 100 °C at 3.5 V)
3.5
Power consumption Appr. 75 mW
Flow output signal

3.0
2.5 Load impedance > 47 kΩ
TM07 2484 3618

2.0 Maximum cable length 3 m (9.10 ft)


1.5
1.0 Materials
0.5 Sensing element Silicon-based MEMS
0.0 EPDM O-rings, FKM O-rings or
0 Q min Q max Sealing
EPDM sealing cap with FKM O-rings
Fig. 50 Flow response in Analog mode Housing Composite (PPS, PA66)
Flow pipe PPA 40-GF
Corrosion-resistant coating, EPDM
[V] Wetted materials
or FKM, PPS, PPA 40-GF
Temperature output signal

4.5
4.0 Environmental standards
3.5 Enclosure class IP44, cable connected
3.0 Temperature cycling IEC 68-2-14
2.5
Vibration, non-destructive 20-2000 Hz, 10G, 4 h
2.0
1.5 Electromagnetic compatibility EN 61326-1
1.0
TM06 3354 5214

0.5
0.0
0 120
Tmax
T max ==
Peak temperature
peak temperature

Fig. 51 Temperature response in Analogue mode

19
Flow sensors
4
VFS, 10-200 l/min (2.6 - 53 gpm) Specifications
Vortex Flow sensor, Standard (VFS and VFS QT)

Flow
Measuring range 10-200 l/min (2.6 to 52.8 gpm)
Accuracy (± 1 σ) in water,
± 1 % FS
0-100 °C (32-212 °F)
Response time (63.2 %) Less than 1 s
Resolution max flow/16384 l/min or gpm

TM05 4747 2512


Temperature
Measuring range 0-120 °C (32-248 °F)
Accuracy (± 1 σ),
± 0.5 K
15-90 °C (59-194 °F)
Accuracy (± 1 σ),
±1K
Fig. 52 VFS, 10-200 l/min 0-120 °C (32-248 °F)
Response time
250 ms
(63.2 % at 50 % FS flow)
Dimensions Resolution 0.35 K
Differential Temperature
Accuracy 15-90 °C (59-194 °F) 0.3 K
Accuracy 0-120 °C (32-248 °F) 0.5 K
System conditions and environment
TM06 3423 0314 Aqueous media compatible with
wetted materials. Kinematic
Liquid types
viscosity less than or equal to 2
mm2/s (cSt)
Liquid temperature, operation Water: 0-100 °C (32-212 °F)
Fig. 53 Dimensions, VFS, 10-200 l/min, without adapter -25 °C (-13 °F), non-freezing
Liquid temperature, peak 120 °C (248 °F) for 5 minutes, up to
3 weeks in sensor lifetime
Ambient temperature,
-25 to +60 °C (-13 to +140 °F)
operation
TM06 3428 0314

Ambient temperature, peak -55 to +90 °C (-67 to +194 °F)


Humidity, relative 0-95 %, non-condensing
Maximum System Pressure 24 bar (348 psig)
Burst Pressure 30 bar (435 psig)
Maximum system pressure Max 10 bar (145 psig) at 100 °C
Fig. 54 Dimensions, VFS, 10-200 l/min, with adapters examples (212 °F)
Electrical data
5 VDC (± 5 %), PELV
A B C D E F Power supply
Grounding of sensor supply required
mm 137.5 ISO 228/1 - 73 - 252 ISO 7/1-R 1 Output signals Ratiometric
in 5.41 G 1 1/4 A 2.87 - 9.92 1" NPT Digital output signals Grundfos open data protocol
0.5 - 3.5 V for flow (zero at 0.35 V)
Sensor output signals Analog output signals 0.5 - 4.1 V for temperature
(zero at 0.5 V and 100 °C at 3.5 V)
Power consumption Appr. 75 mW
3.5 Load impedance > 47 kΩ
Flow output signal

3.0
2.5 Maximum cable length 3 m (9.10 ft)
TM07 2484 3618

2.0 Materials
1.5
Sensing element Silicon-based MEMS
1.0
0.5 EPDM-O-rings or FKM O-rings or
Sealing
0.0 EPDM sealing cap with FKM O-rings
0 Q min Q max Housing Composite (PPS, PA66)
Fig. 55 Flow response in Analogue mode Flow pipe PPA 40-GF
Corrosion-resistant coating, EPDM
Wetted materials
or FKM, PPS, PPA 40-GF
[V] Environmental standards
Temperature output signal

4.5
Enclosure class IP44, cable connected
4.0
3.5 Temperature cycling IEC 68-2-14
3.0 Vibration, non-destructive 20-2000 Hz, 10G, 4 h
2.5 Electromagnetic compatibility EN 61326-1
2.0
1.5
1.0
TM06 3354 5214

0.5
0.0
0 120
Tmax
T max ==
Peak temperature
peak temperature

Fig. 56 Temperature response in Analogue mode

20
Flow sensors
4
VFS, 20-400 l/min (5.3 - 106 gpm) Specifications

Vortex Flow sensor, Standard (VFS and VFS QT)


Flow
Measuring range 20-400 l/min (5.3 to 105.7 gpm)
Accuracy (± 1 σ) in water,
± 1 % FS
0-120 °C (32-248 °F)
Response time (63.2 %) Less than 1 s

TM05 4746 2512


Resolution max flow/16384 l/min or gpm
Temperature
Measuring range 0-120 °C (32-248 °F)
Accuracy (± 1 σ),
± 0.5 K
15-90 °C (59-194 °F)
Fig. 57 VFS, 20-400 l/min Accuracy (± 1 σ),
±1K
0-120 °C (32-248 °F)
Response time
Dimensions (63.2 % at 50 % FS flow)
250 ms

Resolution 0.006 K
Differential Temperature
Accuracy 15-90 °C (59-194 °F) 0.3 K
Accuracy 0-120 °C (32-248 °F) 0.5 K

TM06 3424 0314


System conditions and environment
Aqueous media compatible with
Liquid types wetted materials. Kinematic viscosity
less than or equal to 2 mm2/s (cSt)
Liquid temperature, operation Water: 0-100 °C (32-212 °F)
Fig. 58 Dimensions, VFS, 20-400 l/min, without adapter -25 °C (-13 °F), non-freezing
Liquid temperature, peak 120 °C (248 °F) for 5 minutes, up to
3 weeks in sensor lifetime
Ambient temperature,
-25 to +60 °C (-13 to +140 °F)
TM06 3429 0314

operation
Ambient temperature, peak -55 to +90 °C (-67 to +194 °F)
Humidity, relative 0-95 %, non-condensing
Maximum System Pressure 24 bar (348 psig)
Burst Pressure 30 bar (435 psig)
Fig. 59 Dimensions, VFS 20-400 l/min, with adapters Maximum system pressure Max 10 bar (145 psig) at 100 °C
examples (212 °F)
Electrical data
A B C D E F
5 VDC (± 5 %), PELV
ISO 7/1- R Power supply
mm 180 ISO 228/1 - 80 - 293 Grounding of sensor supply required
1 1/4
G 1 1/2 A Output signals Ratiometric
in 7.09 3.15 - 11.54 1 1/4" NPT
Digital output signals Grundfos open data protocol
0.5 - 3.5 V for flow (zero at 0.35 V)
Sensor output signals Analog output signals 0.5 - 4.1 V for temperature
(zero at 0.5 V and 100 °C at 3.5 V)
Power consumption Appr. 75 mW
3.5
Load impedance > 47 kΩ
Flow output signal

3.0
2.5 Maximum cable length 3 m (9.10 ft)
TM07 2484 3618

2.0
Materials
1.5
1.0 Sensing element Silicon-based MEMS
0.5 EPDM O-rings, FKM O-rings or
0.0 Sealing
EPDM sealing cap with FKM O-rings
0 Q min Q max
Housing Composite (PPS, PA66)
Fig. 60 Flow response in Analogue mode Flow pipe PPA 40-GF
Corrosion-resistant coating, EPDM
Wetted materials
or FKM, PPS, PPA 40-GF
[V]
Temperature output signal

Environmental standards
4.5
4.0 Enclosure class IP44, cable connected
3.5 Temperature cycling IEC 68-2-14
3.0 Vibration, non-destructive 20-2000 Hz, 10G, 4 h
2.5
2.0 Electromagnetic compatibility EN 61326-1
1.5
1.0
TM06 3354 5214

0.5
0.0
0 120
Tmax
T max ==
Peak temperature
peak temperature

Fig. 61 Temperature response in Analogue mode

21
Flow sensors
4
VFS QT, 1-18 l/min (0.2 - 4.8 gpm) Specifications
Vortex Flow sensor, Standard (VFS and VFS QT)

Flow
Measuring range 1-18 l/min (0.2 to 4.8 gpm)
Accuracy (± 1 σ) in water,
± 1 % FS
0-120 °C (32-248 °F)
Response time (63.2 %) Less than 1 s
Resolution max flow/16384 l/min or gpm

TM05 4741 2512


Temperature
Measuring range 0-120 °C (32-248 °F)
Accuracy (± 1 σ),
± 0.5 K
15-90 °C (59-194 °F)
Accuracy (± 1 σ),
Fig. 62 VFS QT, 1-18 l/min ±1K
0-120 °C (32-248 °F)
Response time
250 ms
Dimensions (63.2 % at 50 % FS flow)
Resolution 0.006 K
Differential Temperature
Accuracy 15-90 °C (59-194 °F) 0.3 K
Accuracy 0-120 °C (32-248 °F) 0.5 K
System conditions and environment
Aqueous media compatible with
C

TM05 4671 2512


wetted materials. Kinematic
Liquid types
viscosity less than or equal to 2
2xB mm2/s (cSt)
Liquid temperature, operation Water: 0-120 °C (32-248 °F)
A
-25 °C (-13 °F), non-freezing
Liquid temperature, peak
120 °C (248 °F)
Fig. 63 Dimensions, VFS QT, 1-18 l/min, with threads
Ambient temperature, operation -25 to +60 °C (-13 to +140 °F)
Ambient temperature, peak -55 to +90 °C (-67 to +194 °F)
A B C Humidity, relative 0-95 %, non-condensing
mm 110 58.8 Maximum System Pressure 30 bar (435 psig)
ISO 228/1 - G3/4 A Burst Pressure 40 bar (580 psig)
in 4.33 2.31 Max 16 bar (232 psig) at 100 °C
Maximum system pressure (212 °F)
examples Max 8 bar (116 psig) at 120 °C (248
Sensor output signals °F)
Electrical data
4.5
4.0 5 VDC (± 5 %), PELV
Power supply Grounding of sensor supply
Flow output signal

3.5
3.0 required
2.5 Output signals Ratiometric
TM07 2747 4118

2.0 Digital output signals Grundfos open data protocol


1.5
1.0 0.5 - 4.1 V for flow (zero at 0.28 V
0.5 and 15 l/m at 3.5 V)
Analog output signals
0.0 0.5 - 4.1 V for temperature
0 Q min Q max (zero at 0.5 V and 100 °C at 3.5 V)
Power consumption Appr. 75 mW
Fig. 64 Flow response in Analogue mode
Load impedance > 47 kΩ
Maximum cable length 3 m (9.10 ft)
[V] Materials
Temperature output signal

4.5
Sensing element Silicon-based MEMS
4.0
3.5 EPDM O-rings, FKM O-rings or
3.0 Sealing EPDM sealing cap with FKM
2.5 O-rings
2.0 Housing Composite (PPS, PA66)
1.5 Flow pipe Stainless steel AISI 316 EN 1.4408
1.0
TM06 3354 5214

0.5 Insert PPA 40 GF


0.0 Corrosion-resistant coating EPDM
120 Wetted materials
0 or FKM, PPS, PPA 40-GF, 1.4408
Tmax
T max ==
Peak temperature Environmental standards
peak temperature
Enclosure class IP44, cable connected
Fig. 65 Temperature response in Analogue mode Temperature cycling IEC 68-2-14
Vibration, non-destructive 20-2000 Hz, 10G, 4 h
Electromagnetic compatibility EN 61326-1

22
Flow sensors
4
VFS QT, 2-40 l/min (0.5 - 10.6 gpm) Specifications

Vortex Flow sensor, Standard (VFS and VFS QT)


Flow
Measuring range 2-40 l/min (0.5 - 10.6 gpm)
Accuracy (± 1 σ) in water,
± 1 % FS
0-120 °C (32-248 °F)
Response time (63.2 %) Less than 3 s
Resolution max flow/16384 l/min or gpm

TM05 4741 2512


Temperature
Measuring range 0-120 °C (32-248 °F)
Accuracy (± 1 σ),
± 0.5 K
15-90 °C (59-194 °F)
Accuracy (± 1 σ),
Fig. 66 VFS QT, 2-40 l/min ±1K
0-120 °C (32-248 °F)
Response time
250 ms
Dimensions (63.2 % at 50 % FS flow)
Resolution 0.006 K
Differential Temperature
Accuracy 15-90 °C (59-194 °F) 0.3 K
Accuracy 0-120 °C (32-248 °F) 0.5 K
System conditions and environment
C

TM05 4671 2512 Aqueous media compatible with


wetted materials. Kinematic
Liquid types
viscosity less than or equal to 2
2xB mm2/s (cSt)
A Liquid temperature, operation Water: 0-100 °C (32-212 °F)
-25 °C (-13 °F), non-freezing
Liquid temperature, peak
Fig. 67 Dimensions, VFS QT, 2-40 l/min, with threads 120 °C (248 °F)
Ambient temperature,
-25 to +60 °C (-13 to +140 °F)
operation
A B C Ambient temperature, peak -55 to +90 °C (-67 to +194 °F)
mm 110 58.8 Humidity, relative 0-95 %, non-condensing
ISO 228/1 - G3/4 A Maximum System Pressure 30 bar (435 psig)
in 4.33 2.31
Burst Pressure 40 bar (580 psig)
Max 16 bar (232 psig) at 100 °C
Sensor output signals Maximum system pressure (212 °F)
examples Max 8 bar (116 psig) at 120 °C (248
°F)
3.5 Electrical data
Flow output signal

3.0
2.5 5 VDC (± 5 %), PELV
Power supply
TM07 2484 3618

2.0 Grounding of sensor supply required


1.5 Output signals Ratiometric
1.0 Digital output signals Grundfos open data protocol
0.5
0.0 0.5 - 3.5 V for flow (zero at 0.35 V)
0 Q min Q max Analog output signals 0.5 - 4.1 V for temperature
(zero at 0.5 V and 100 °C at 3.5 V)
Fig. 68 Flow response in Analogue mode Power consumption Appr. 75 mW
Load impedance > 47 kΩ
[V] Maximum cable length 3 m (9.10 ft)
Temperature output signal

4.5 Materials
4.0 Sensing element Silicon-based MEMS
3.5
EPDM O-rings, FKM O-rings or
3.0 Sealing
2.5 EPDM sealing cap with FKM O-rings
2.0 Housing Composite (PPS, PA66)
1.5 Flow pipe Stainless steel AISI 316 EN 1.4408
1.0
TM06 3354 5214

Insert PPA 40 GF
0.5
0.0 Corrosion-resistant coating,
0 120 Wetted materials EPDM or FKM,
Tmax
T max == PPS, PPA 40-GF, 1.4408
Peak temperature
peak temperature Environmental standards
Fig. 69 Temperature response in Analogue mode Enclosure class IP44, cable connected
Temperature cycling IEC 68-2-14
Vibration, non-destructive 20-2000 Hz, 10G, 4 h
Electromagnetic compatibility EN 61326-1

23
Flow sensors
4
VFS QT, 5-100 l/min (1.3 - 26 gpm) Specifications
Vortex Flow sensor, Standard (VFS and VFS QT)

Flow
Measuring range 5-100 l/min (1.3 to 26.4 gpm)
Accuracy (± 1 σ),
± 1 % FS
0-100 °C (32-212 °F)
Response time (63.2 %) Less than 1 s
Resolution max flow/16384 l/min or gpm

TM05 4740 2512


Temperature
Measuring range 0-120 °C (32-248 °F)
Accuracy (± 1 σ),
± 0.5 K
15-90 °C (59-194 °F)
Accuracy (± 1 σ),
±1K
Fig. 70 VFS QT, 5-100 l/min 0-120 °C (32-248 °F)
Response time
250 ms
Dimensions (63.2 % at 50 % FS flow)
Resolution 0.006 K
Differential Temperature
Accuracy 15-90 °C (59-194 °F) 0.3 K
Accuracy 0-120 °C (32-248 °F) 0.5 K
System conditions and environment
C

Aqueous media compatible with


wetted materials. Kinematic
TM05 4672 2512
Liquid types
viscosity less than or equal to 2
mm2/s (cSt)
2xB
Liquid temperature, operation Water: 0-120 °C (32-248 °F)
A -25 °C (-13 °F), non-freezing
Liquid temperature, peak
120 °C (248 °F)
Fig. 71 Dimensions, VFS QT, 5-100 l/min, with threads Ambient temperature,
-25 to +60 °C (-13 to +140 °F)
operation
Ambient temperature, peak -55 to +90 °C (-67 to +194 °F)
A B C
Humidity, relative 0-95 %, non-condensing
mm 129 66.5 Maximum System Pressure 30 bar (435 psig)
ISO 228/1 - G1A Burst Pressure 40 bar (580 psig)
in 5.08 2.62
Max 16 bar (232 psig) at 100 °C
Maximum system pressure (212 °F)
Sensor output signals examples Max 8 bar (116 psig) at 120 °C (248
°F)
Electrical data
3.5
5 VDC (± 5 %). We recommend
Flow output signal

3.0
2.5 Power supply grounding of the sensor supply
TM07 2484 3618

2.0 (PELV).
1.5 Output signals Ratiometric
1.0 Digital output signals Grundfos open data protocol
0.5
0.0 0.5 - 3.5 V for flow (zero at 0.35 V)
0 Q min Q max Analog output signals 0.5 - 4.1 V for temperature
(zero at 0.5 V and 100 °C at 3.5 V)
Fig. 72 Flow response in Analogue mode Power consumption Appr. 75 mW
Load impedance > 47 kΩ
[V] Maximum cable length 3 m (9.10 ft)
Temperature output signal

4.5 Materials
4.0 Sensing element Silicon-based MEMS
3.5
EPDM O-rings, FKM O-rings or
3.0 Sealing
2.5 EPDM sealing cap with FKM O-rings
2.0 Housing Composite (PPS, PA66)
1.5 Flow pipe Stainless steel AISI 316 EN 1.4408
1.0
TM06 3354 5214

Insert PPA 40-GF


0.5
0.0 Corrosion-resistant coating, EPDM
0 120 Wetted materials or FKM,
Tmax
T max == PPS, PPA 40-GF, 1.4408
Peak temperature
peak temperature Environmental standards
Fig. 73 Temperature response in Analogue mode Enclosure class IP44, cable connected
Temperature cycling IEC 68-2-14
Vibration, non-destructive 20-2000 Hz, 10G, 4 h
Electromagnetic compatibility EN 61326-1

24
Flow sensors
4
VFS QT, 10-200 l/min (2.6 - 53 gpm) Specifications

Vortex Flow sensor, Standard (VFS and VFS QT)


Flow
Measuring range 10-200 l/min (2.6 to 52.8 gpm)
Accuracy (± 1 σ) in water,
± 1 % FS
0-100 °C (32-212 °F)
Response time (63.2 %) Less than 1.0 s
Resolution max flow/16384 l/min or gpm

TM05 4739 2512


Temperature
Measuring range 0-120 °C (32-248 °F)
Accuracy (± 1 σ),
± 0.5 K
15-90 °C (59-194 °F)
Accuracy (± 1 σ),
±1K
Fig. 74 VFS QT, 10-200 l/min 0-120 °C (32-248 °F)
Response time
250 ms
Dimensions (63.2 % at 50 % FS flow)
Resolution 0.006 K
Differential Temperature
Accuracy 15-90 °C (59-194 °F) 0.3 K
Accuracy 0-120 °C (32-248 °F) 0.5 K
System conditions and environment
C

TM05 4673 2512 Aqueous media compatible with


wetted materials. Kinematic
Liquid types
viscosity less than or equal to 2
2xB mm2/s (cSt)
Liquid temperature, operation Water: 0-120 °C (32-248 °F)
A
-25 °C (-13 °F), non-freezing
Liquid temperature, peak
Fig. 75 Dimensions, VFS QT, 10-200 l/min, with threads 120 °C (248 °F)
Ambient temperature,
-25 to +60 °C (-13 to +140 °F)
operation
A B C Ambient temperature, peak -55 to +90 °C (-67 to +194 °F)
mm 137.5 74.1 Humidity, relative 0-95 %, non-condensing
ISO 228/1 - G1 1/4 A Maximum System Pressure 30 bar (435 psig)
in 5.41 2.92 Burst Pressure 40 bar (580 psig)
Max 16 bar (232 psig) at 100 °C
Sensor output signals Maximum system pressure (212 °F)
examples Max 8 bar (116 psig) at 120 °C (248
°F)
3.5 Electrical data
Flow output signal

3.0
2.5 5 VDC (± 5 %), PELV
Power supply
Grounding of sensor supply required
TM07 2484 3618

2.0
1.5 Output signals Ratiometric
1.0 Digital output signals Grundfos open data protocol
0.5
0.5 - 3.5 V for flow (zero at 0.35 V)
0.0
0 Q min Q max Analog output signals 0.5 - 4.1 V for temperature
(zero at 0.5 V and 100 °C at 3.5 V)
Fig. 76 Flow response in Analogue mode Power consumption Appr. 75 mW
Load impedance > 47 kΩ
Maximum cable length 3 m (9.10 ft)
[V]
Temperature output signal

4.5 Materials
4.0 Sensing element Silicon-based MEMS
3.5
EPDM O-rings, FKM O-rings or
3.0 Sealing
EPDM sealing cap with FKM O-rings
2.5
2.0 Housing Composite (PPS, PA66)
1.5 Flow pipe Stainless steel 1.4408 (AISI 316)
1.0
TM06 3354 5214

Insert PPA 40-GF


0.5
Corrosion-resistant coating, EPDM
0.0
0 120 Wetted materials or FKM,
Tmax
T max == PPS, PPA 40-GF, 1.4408
Peak temperature
peak temperature Environmental standards
Enclosure class IP44, cable connected
Fig. 77 Temperature response in Analogue mode
Temperature cycling IEC 68-2-14
Vibration, non-destructive 20-2000 Hz, 10G, 4 h
Electromagnetic compatibility EN 61326-1

25
Flow sensors
5

5. Multi Flow sensor, standard (MFS and MFS QT)


Multi Flow sensor, standard (MFS and MFS QT)

General data • suitable for a wide temperature range


• suitable for a wide range of application.

TM05 4752 2412 - TM05 4741 2412


Approvals (w/EPDM O-rings)
• WRAS
• KTW
• ACS.

Certificates

Fig. 78 MFS and MFS QT, 4-40 l/min + 75


CE C, CSA, US EAC
Technical overview
The MFS is a combined flow, pressure and Electrical connections
temperature sensor (three-in-one) from Grundfos
Analogue signal Digital signal
Direct Sensors™. The sensor is based on the principle
of vortex shedding behind a bluff body. Electrical
The MFS sensor is designed for high-volume connector
production and fully compatible with wet, aggressive 1 2 3 4 1 2 3 4
Pin No
liquids.
Temperature signal
The sensor is based on MEMS sensing technology in
combination with a unique packaging concept using V Flow signal 3Y
corrosion-resistant coating on the MEMS sensor chip.

TM04 7156 1610


V 5Y
This makes the sensor very robust and ideal for Pipe system
high-volume OEM (Original Equipment Manufacturer)
applications.
PE PE
Applications Fig. 79 Electrical connections
• Pump control
• HVAC systems Pin configuration Pin configuration
Colour
Analog signal Digital signal
• temperature control and chiller systems
1 Analog signal 1 Rx Yellow
• renewable energies such as heat pumps, solar
2 Analog signal 2 Tx White
thermals, fresh water and micro-CHP systems
3 GND (0 V), PELV GND (0 V), PELV Green
• monitoring and control systems 4 Power supply, + 5 VDC Power supply, + 5 VDC Brown
• water treatment plants
Power supply requirements
• water utility and distribution systems
• 5 VDC ± 5 %, PELV
• HPC (High-Performance Computing) and IT cooling
systems. • maximum 10 mV ripple, 50 Hz
• minimum output current, 25 mA
Features and benefits • separated from hazardous live circuitry by double or
• Flow, pressure and temperature measurement in reinforced insulation
one sensor (three-in-one solution) for easy and • grounding of sensor supply is required.
cost-efficient installation
• Measurement principle with no movable parts, Directives
resulting in no wear and tear The Grundfos Direct Sensors™ are in conformity with
• self-configuring digital or analog output these council directives on the approximation of the
• MEMS technology laws of the EC member states:
• direct contact with the liquid resulting in a fast • • Low Voltage Directive (2014/35/EU)
response time – Standards used: EN 61010-1:2010
• plug and play for quick setup • EMC Directive (2014/30/EU).
• smart system solution with Grundfos pump controls – Standards used: EN 61326-1:2013 and EN
• compact and robust design 61326-2-3:2013
• compatible with aqueous media The Grundfos Direct Sensors™ are exempted from the
Pressure Equipment Directive (PED) according to
• For aqeous media below 2 µS/cm contact your local
Article 4, paragraph 3 in the PED 2014/68/EU.
Grundfos sensor representative

26
Flow sensors
5
MFS sensors Snap-on sensor

Multi Flow sensor, standard (MFS and MFS QT)


TM05 4750 2512 - TM05 4752 2512
Fig. 82 Snap-on sensor
TM05 4744 2512

Differential Temperature
The differential temperature is between two standard
Direct Sensors TM from Grundfos.
Fig. 80 The MFS family

The MFS flow sensor consists of a composite flow pipe


and a sensor fitted with cable.
The MFS flow sensor is available in 2-20, 4-40,
10-100, 20-200, 40-400 l/min versions.

MFS QT sensors
TM05 4743 2512

Fig. 81 The MFS QT family

The MFS QT flow sensor consists of a composite


insert, a stainless steel flow pipe and a sensor fitted
with cable.
The MFS QT flow sensor is available in 2-18, 4-40,
10-100, 20-200 l/min versions.

27
Flow sensors
5
MFS 2-20 l/min (0.53 - 5.3 gpm) Specifications
Multi Flow sensor, standard (MFS and MFS QT)

Flow
Measuring range 2-20 l/min (0.53 to 5.3 gpm)
Accuracy (± 1 σ) in water,
± 1 % FS

TM05 4751 2512


0-120 °C (32-248 °F)
Response time (63.2 %) Less than 4 s
Resolution max flow/16384 l/min or gpm
Pressure
Measuring range 0-10 bar (0-145 psig)
Fig. 83 MFS 2-20 l/min Accuracy (± 1 σ),
± 2.0 % FS
15-90 °C (59-194 °F)
Dimensions Accuracy (± 1 σ),
± 2.5 % FS
0-120 °C (32-248 °F)
Response time for sensor
250 ms
electronic
Resolution 0.6 mbar (0.009 psig)
Temperature

TM06 3420 0314


Measuring range 0-120 °C (32-248 °F)
Accuracy (± 1 σ),
± 0.5 K
15-90 °C (59-194 °F)
Accuracy (± 1 σ),
±1K
0-120 °C (32-248 °F)
Fig. 84 Dimensions, MFS 2-20 l/min, without adapter Response time
250 ms
(63.2 % at 50 % FS flow)
Resolution 0.006 K
Differential Temperature
Accuracy 15-90 °C (59-194 °F) 0.3 K
Accuracy 0-120 °C (32-248 °F) 0.5 K
System conditions and environment
TM06 3425 0314

Aqueous media compatible with


wetted materials. Kinematic
Liquids
viscosity less than or equal to 2
mm2/s (cSt)
System temperature, operation 0-100 °C (32-212 °F)
Fig. 85 Dimensions, MFS 2-20 l/min, with adapters -25 °C (-13 °F), non-freezing
System temperature, peak 120 °C (248 °F) for 5 minutes, up to
3 weeks in sensor lifetime
A B C D E F Ambient temperature,
-25 to +60 °C (-13 to +140 °F)
operation
ISO 228 -
mm 82 ∅19.8 65 36 153.6 Ambient temperature, peak -55 to +90 °C (-67 to +194 °F)
G 1/2 A
in 3.23 ∅0.78 2.56 1.42 6.05 1/2" NPT Humidity, relative 0-95 %, non-condensing
Maximum System Pressure 24 bar (348 psig)
Sensor output signals Burst Pressure 30 bar (435 psig)
Maximum system pressure Max 10 bar (145 psig) at 100 °C
example (212 °F)
3.5
Electrical data
3.0
Flow output signal

2.5 5 VDC (± 5 %), PELV


Power supply
2.0 Grounding of sensor supply required
TM07 2485 3618

1.5 Digital output signals Grundfos open data protocol


1.0 0.5 - 3.5 for flow (zero at 0.35 V) and
Analog output signals, only two
pressure (zero at 0.5 V)
0.5 signals possible (analogue
0.5 - 4.1 V for temperature (zero at
0.0 variants are upon request)
0.5 V and 100 °C at 3.5 V)
0 Q min Q max
Power consumption Approximately 75 mW
Fig. 86 Flow response in Analogue mode Load impedance > 47 kΩ
Materials
[V] Sensing element Silicon-based MEMS
4.5 Sealing EPDM O-ring or FKM O-ring
Pressure and temperature

4.0 Housing Composite (PPS, PA66)


3.5
Flow pipe PPA 40-GF
3.0
Corrosion-resistant coating, EPDM
2.5 Wetted materials
or FKM, PPS, PPA 40-GF
2.0
output signal

Environmental standards
TM06 6560 1716

1.5
1.0 Enclosure class IP44, cable connected
0.5 Temperature cycling IEC 68-2-14
0.0 Vibration, non-destructive 20-2000 Hz, 10G, 4 h
0 P max T max
T Peak Electromagnetic compatibility EN 61326-1

Fig. 87 Pressure and temperature response in Analogue


mode

28
Flow sensors
5
MFS 4-40 l/min (1.06 - 10.6 gpm) Specifications

Multi Flow sensor, standard (MFS and MFS QT)


Flow
Measuring range 4-40 l/min (1.06 - 10.6 gpm)
Accuracy (± 1 σ) in water

TM05 4749 2512


± 1 % FS
0-120 °C (32-248 °F)
Response time (63.2 %) Less than 4 s
Resolution max flow/16384 l/min or gpm
Pressure
Measuring range 0-10 bar (0-145 psig)
Fig. 88 MFS 4-40 l/min
Accuracy (± 1 σ),
± 2.0 % FS
15-90 °C (59-194 °F)
Dimensions Accuracy (± 1 σ),
± 2.5 % FS
0-120 °C (32-248 °F)
Response time for sensor
250 ms
electronic
Resolution 0.6 mbar (0.009 psig)
Temperature
0-120 °C (32-248 °F).

TM06 3421 0314


Measuring range

Accuracy (±1 σ),


± 0.5 K
15-90 °C (59-194 °F)
Accuracy (±1 σ),
±1K
0-120 °C (32-248 °F)
Fig. 89 Dimensions, MFS 4-40 l/min, without adapter Response time
250 ms
(63.2 % at 50 % FS flow)
Resolution 0.006 K
System conditions and environment
Aqueous media compatible with
wetted materials. Kinematic
Liquids
viscosity less than or equal to 2
mm2/s (cSt)
System temperature, operation 0-100 °C (32-212 °F)
TM06 3426 0314

-25 °C (-13 °F), non-freezing


System temperature, peak 120 °C (248 °F) for 5 minutes, up to
3 weeks in sensor lifetime
Ambient temperature,
-25 to +60 °C (-13 to +140 °F)
operation
Fig. 90 Dimensions, MFS 4-40 l/min, with adapter Ambient temperature, peak -55 to +90 °C (-67 to +194 °F)
Humidity, relative 0-95 %, non-condensing
Maximum System Pressure 24 bar (348 psig)
A B C D E F
Burst Pressure 30 bar (435 psig)
mm 88 ∅22.8 66 38 157.4 ISO 228/1 -G 3/4 A
Maximum system pressure Max 10 bar (145 psig) at 100 °C
in 3.46 ∅0.19 2.60 1.50 6.20 3/4" NPT example (212 °F)
Electrical data
Sensor output signals 5 VDC (± 5 %), PELV
Power supply
Grounding of sensor supply required
3.5 Digital output signals Grundfos open data protocol
3.0 0.5 - 3.5 for flow (zero at 0.35 V) and
Flow output signal

2.5 Analog output signals, only two


pressure (zero at 0.5 V)
signals possible (analogue
2.0 variants are upon request)
0.5 - 4.1 V for temperature (zero at
TM07 2485 3618

1.5 0.5 V and 100 °C at 3.5 V)


1.0 Power consumption Approximately 75 mW
0.5 Load impedance > 47 kΩ
0.0 Materials
0 Q min Q max Sensing element Silicon-based MEMS
Fig. 91 Flow response in Analogue mode Sealing EPDM O-ring or FKM O-ring
Housing Composite (PPS, PA66)
Flow pipe PPA 40-GF
[V]
4.5 Corrosion-resistant coating, EPDM
Wetted materials
or FKM, PPS, PPA 40-GF
Pressure and temperature

4.0
3.5 Environmental standards
3.0 Enclosure class IP44, cable connected
2.5 Temperature cycling IEC 68-2-14
2.0 Vibration, non-destructive 20-2000 Hz, 10G, 4 h
output signal

TM06 6560 1716

1.5
Electromagnetic compatibility EN 61326-1
1.0
0.5
0.0
0 P max T max
T Peak

Fig. 92 Pressure and temperature response in Analogue


mode

29
Flow sensors
5
MFS 10-100 l/min (2.6 - 26 gpm) Specifications
Multi Flow sensor, standard (MFS and MFS QT)

Flow
Measuring range 10-100 l/min (2.6-26 gpm)
Accuracy (± 1 σ) in water
± 1 % FS
0-120 °C (32-248 °F)
Response time (63.2 %) Less than 4 s

TM05 4748 2512


Resolution max flow/16384 l/min or gpm
Pressure
Measuring range 0-10 bar (0-145 psig)
Accuracy (± 1 σ),
± 2.0 % FS
15-90 °C (59-194 °F)
MFS 10-100 l/min Accuracy (± 1 σ),
Fig. 93 ± 2.5 % FS
0-120 °C (32-248 °F)
Response time for sensor
Dimensions 250 ms
electronic
Resolution 0.6 mbar (0.009 psig)
Temperature
Measuring range 0-120 °C (32-248 °F)
Accuracy (± 1 σ),
± 0.5 K

TM06 3422 0314


15-90 °C (59-194 °F)
Accuracy (± 1 σ),
±1K
0-100 °C (32-212 °F)
Response time
250 ms
(63.2 % at 50 % FS flow)
Resolution 0.006 K
Fig. 94 Dimensions, MFS 10-100 l/min, without adapter Differential Temperature
Accuracy 15-90 °C (59-194 °F) 0.3 K
Accuracy 0-120 °C (32-248 °F) 0.5 K
System conditions and
environment
TM06 3427 0314

Aqueous media compatible with


wetted materials. Kinematic
Liquid types
viscosity less than or equal to 2
mm2/s (cSt)
System temperature, operation 0-100 °C (32-212 °F)
Fig. 95 Dimensions, MFS 10-100 l/min, with adapters -25 °C (-13 °F), non-freezing
System temperature, peak 120 °C (248 °F) for 5 minutes, up to
3 weeks in sensor lifetime
A B C D E F Ambient temperature, operation -25 to +60 °C (-13 to +140 °F)
mm 129 ISO 228/1 - 65 - 223 ISO 7/1-Rc 3/4 Ambient temperature, peak -55 to +90 °C (-67 to +194 °F)
in 5.08 G1A 2.56 - 8.78 3/4" NPT Humidity, relative 0-95 %, non-condensing
Maximum System Pressure 24 bar (348 psig)
Sensor output signals Burst Pressure 30 bar (435 psig)
Maximum system pressure Max 10 bar (145 psig) at 100 °C
example (212 °F)
3.5
Electrical data
3.0
Flow output signal

2.5 Power supply


5 VDC (± 5 %), PELV
2.0 Grounding of sensor supply required
TM07 2485 3618

1.5 Digital output signals Grundfos open data protocol


1.0 0.5 - 3.5 for flow (zero at 0.35 V)
Analog output signals, only two
0.5 and pressure (zero at 0.5 V)
signals possible (analogue
0.5 - 4.1 V for temperature (zero at
0.0 variants are upon request)
0.5 V and 100 °C at 3.5 V)
0 Q min Q max
Power consumption Approximately 75 mW
Fig. 96 Flow response in Analogue mode Load impedance > 47 kΩ
Materials
[V] Sensing element Silicon-based MEMS
4.5 Sealing EPDM O-ring or FKM O-ring
Pressure and temperature

4.0
Housing Composite (PPS, PA66)
3.5
Flow pipe PPA 40-GF
3.0
2.5 Corrosion-resistant coating, EPDM
Wetted materials
2.0
or FKM, PPS, PPA 40-GF
output signal

TM06 6560 1716

1.5 Environmental standards


1.0 Enclosure class IP44, cable connected
0.5 Temperature cycling IEC 68-2-14
0.0
0 P max T max Vibration, non-destructive 20-2000 Hz, 10G, 4 h
T Peak Electromagnetic compatibility EN 61326-1

Fig. 97 Pressure and temperature response in Analogue


mode

30
Flow sensors
5
MFS 20-200 l/min (5.3 - 53 gpm) Specifications

Multi Flow sensor, standard (MFS and MFS QT)


Flow
Measuring range MFS 20-200 (5.3 - 53 gpm)
Accuracy (± 1 σ) in water
± 1 % FS
0-120 °C (32-248 °F)
Response time (63.2 %) Less than 4 s
Resolution max flow/16384 l/min or gpm

TM05 4747 2512


Pressure
Measuring range 0-10 bar (0-145 psig)
Accuracy (± 1 σ),
± 2.0 % FS
15-90 °C (59-194 °F)
Accuracy (± 1 σ),
± 2.5 % FS
0-120 °C (32-248 °F)
Fig. 98 MFS 20-200 l/min
Response time for sensor
250 ms
electronic
Dimensions Resolution 0.6 mbar (0.009 psig)
Temperature
Measuring range 0-120 °C (32-248 °F)
Accuracy (± 1 σ),
± 0.5 K
15-90 °C (59-194 °F)
Accuracy (± 1 σ),
TM06 3423 0314 0-120 °C (32-248 °F)
±1K

Response time
250 ms
(63.2 % at 50 % FS flow)
Resolution 0.006 K
Differential Temperature
Fig. 99 Dimensions, MFS 20-200 l/min, without adapter Accuracy 15-90 °C (59-194 °F) 0.3 K
Accuracy 0-120 °C (32-248 °F) 0.5 K
System conditions and
environment
TM06 3428 0314

Aqueous media compatible with


wetted materials
Liquid types
Kinematic viscosity less than or
equal to 2 mm2/s (cSt)
System temperature, operation 0-100 °C (32-212 °F)
-25 °C (-13 °F), non-freezing
Fig. 100 Dimensions, MFS 20-200 l/min, with adapters System temperature, peak 120 °C (248 °F) for 5 minutes, up to
3 weeks in sensor lifetime
Ambient temperature,
A B C D E F -25 to +60 °C (-13 to +140 °F)
operation
mm 137.5 ISO 228/1 - 73 - 252 ISO 7/1-R 1 Ambient temperature, peak -55 to +90 °C (-67 to +194 °F)
in 5.41 G 1 1/4 A 2.87 - 9.92 1" NPT Humidity, relative 0-95 %, non-condensing
Maximum System Pressure 24 bar (348 psig)
Sensor output signals Burst Pressure 30 bar (435 psig)
Maximum system pressure Max 10 bar (145 psig) at 100 °C
3.5 example (212 °F)
3.0
Flow output signal

Electrical data
2.5 5 VDC (± 5 %), PELV
2.0 Power supply
Grounding of sensor supply required
TM07 2485 3618

1.5 Digital output signals Grundfos open data protocol


1.0 0.5 - 3.5 for flow (zero at 0.35 V) and
0.5 Analog output signals, only two
pressure (zero at 0.5 V)
signals possible (analogue
0.0 variants are upon request)
0.5 - 4.1 V for temperature (zero at
0 Q min Q max 0.5 V and 100 °C at 3.5 V)
Power consumption Approximately 75 mW
Fig. 101 Flow response in Analogue mode
Load impedance > 47 kΩ
Materials
[V]
4.5
Sensing element Silicon-based MEMS
Pressure and temperature

4.0 Sealing EPDM O-ring or FKM O-ring


3.5 Housing Composite (PPS, PA66)
3.0 Flow pipe PPA 40-GF
2.5 Corrosion-resistant coating, EPDM
Wetted materials
2.0 or FKM, PPS, PPA 40-GF
output signal

TM06 6560 1716

1.5 Environmental standards


1.0
Enclosure class IP44, cable connected
0.5
Temperature cycling IEC 68-2-14
0.0
0 P max T max Vibration, non-destructive 20-2000 Hz, 10G, 4 h
T Peak
Electromagnetic compatibility EN 61326-1
Fig. 102 Pressure and temperature response in Analogue
mode

31
Flow sensors
5
MFS 40-400 l/min (10.6 - 106 gpm) Specifications
Multi Flow sensor, standard (MFS and MFS QT)

Flow
Measuring range MFS 40-400 (10.6 - 106 gpm)
Accuracy (± 1 σ), in water
± 1 % FS
0-120 °C (32-248 °F)
Response time (63.2 %) Less than 4 s

TM05 4746 2512


Resolution max flow/16384 l/min or gpm
Pressure
Measuring range 0-10 bar (0-145 psig)
Accuracy (± 1 σ),
± 2.0 % FS
15-90 °C (59-194 °F)
Fig. 103 MFS 40-400 l/min Accuracy (± 1 σ),
± 2.5 % FS
0-120 °C (32-248 °F)
Response time for sensor
Dimensions 250 ms
electronic
Resolution 0.6 mbar (0.009 psig)
Temperature
Measuring range 0-120 °C (32-248 °F)
Accuracy (± 1 σ),
± 0.5 K
15-90 °C (59-194 °F)

TM06 3424 0314


Accuracy (± 1 σ),
±1K
0-120 °C (32-248 °F)
Response time
250 ms
(63.2 % at 50 % FS flow)
Resolution 0.006 K
Fig. 104 Dimensions, MFS 40-400 l/min, without adapter Differential Temperature
Accuracy 15-90 °C (59-194 °F) 0.3 K
Accuracy 0-120 °C (32-248 °F) 0.5 K
TM06 3429 0314

System conditions and environment


Aqueous media compatible with
wetted materials. Kinematic
Liquid types
viscosity less than or equal to 2
mm2/s (cSt)
System temperature, operation 0-100 °C (32-212 °F)
Fig. 105 Dimensions, MFS 40-400 l/min, with adapters -25 °C (-13 °F), non-freezing
System temperature, peak 120 °C (248 °F) for 5 minutes, up to
3 weeks in sensor lifetime
A B C D E F
Ambient temperature, operation -25 to +60 °C (-13 to +140 °F)
mm 180 ISO 228/1 - 80 - 293 ISO 7/1- R 1 1/4 Ambient temperature, peak -55 to +90 °C (-67 to +194 °F)
in 7.09 G 1 1/2 A 3.15 - 11.54 1 1/4" NPT Humidity, relative 0-95 %, non-condensing
Maximum System Pressure 24 bar (348 psig)
Sensor output signals Burst Pressure 30 bar (435 psig)
Maximum system pressure Max 10 bar (145 psig) at 100 °C
3.5 example (212 °F)
3.0 Electrical data
Flow output signal

2.5 5 VDC (± 5 %), PELV


2.0 Power supply Grounding of sensor supply
TM07 2485 3618

1.5 required
1.0 Digital output signals Grundfos open data protocol
0.5 0.5 - 3.5 for flow (zero at 0.35 V)
0.0 Analog output signals, only two and
0 Q min Q max signals possible (analogue pressure (zero at 0.5 V)
variants are upon request) 0.5 - 4.1 V for temperature
Fig. 106 Flow response in Analogue mode (zero at 0.5 V and 100 °C at 3.5 V)
Power consumption Approximately 75 mW
[V] Load impedance > 47 kΩ
4.5 Materials
Pressure and temperature

4.0 Sensing element Silicon-based MEMS


3.5
Sealing EPDM O-ring or FKM O-ring
3.0
Housing Composite (PPS, PA66)
2.5
Flow pipe PPA 40-GF
2.0
output signal

Corrosion-resistant coating, EPDM


TM06 6560 1716

1.5 Wetted materials


or FKM, PPS, PPA 40-GF
1.0
0.5 Environmental standards
0.0 Enclosure class IP44, cable connected
0 P max T max
T Peak Temperature cycling IEC 68-2-14
Vibration, non-destructive 20-2000 Hz, 10G, 4 h
Fig. 107 Pressure and temperature response in Analogue
Electromagnetic compatibility EN 61326-1
mode

32
Flow sensors
5
MFS QT 2-18 l/min (0.39 - 4.8 gpm) Specifications

Multi Flow sensor, standard (MFS and MFS QT)


Flow
Measuring range 2-18 l/min (0.39 - 4.8 gpm)
Accuracy (± 1 σ) in water,
± 1 % FS
0-120 °C (32-248 °F)
Response time (63.2 %) Less than 4 s
Resolution max flow/16384 l/min or gpm

TM05 4741 2512


Pressure
Measuring range 0-10 bar (0-145 psig)
Accuracy (± 1 σ),
± 2.0 % FS
15-90 °C (59-194 °F)
Accuracy (± 1 σ),
± 2.5 % FS
0-120 °C (32-248 °F)
Fig. 108 MFS QT 2-18 l/min Response time for sensor
250 ms
electronic
Dimensions Resolution 0.6 mbar (0.009 psig)
Temperature
Measuring range 0-120 °C (32-248 °F)
Accuracy (± 1 σ),
± 0.5 K
15-90 °C (59-194 °F)
Accuracy (± 1 σ),
TM05 4671 2512
±1K
C

0-120 °C (32-248 °F)


Response time
250 ms
2xB (63.2 % at 50 % FS flow)
Resolution 0.006 K
A
Differential Temperature
Fig. 109 Dimensions, MFS QT 2-18 l/min, with threads Accuracy 15-90 °C (59-194 °F) 0.3 K
Accuracy 0-120 °C (32-248 °F) 0.5 K
A B C System conditions and environment
Aqueous media compatible with
mm 110 58.8 wetted materials
ISO 228/1 - G3/4 A Liquid types
Kinematic viscosity less than or
in 4.33 2.31
equal to 2 mm2/s (cSt)
System temperature, operation 0-120 °C (32-248 °F)
Sensor output signals -25 °C (-13 °F), non-freezing
System temperature, peak
120 °C (248 °F)
4.5 Ambient temperature,
-25 to +60 °C (-13 to +140 °F)
4.0 operation
Flow output signal

3.5 Ambient temperature, peak -55 to +90 °C (-67 to +194 °F)


3.0 Humidity, relative 0-95 %, non-condensing
2.5 Maximum System Pressure 30 bar (435 psig)
2.0 Burst Pressure 40 bar (580 psig)
TM07 2747 4118

1.5 Max 16 bar (232 psig) at 100 °C


1.0 Maximum system pressure (212 °F)
0.5 example Max 8 bar (116 psig) at 120 °C (248
0.0 °F)
0 Q min Q max Electrical data
Fig. 110 Flow response in Analogue mode 5 VDC (± 5 %), PELV
Power supply
Grounding of sensor supply required
Digital output signals Grundfos open data protocol
[V]
0.5 - 4.1 for flow (zero at 0.28 V and
4.5 Analog output signals, only two 15 l/m at 3.5 V) and pressure (zero
Pressure and temperature

4.0 signals possible (analogue at 0.5 V)


3.5 variants are upon request) 0.5 - 4.1 V for temperature
3.0 (zero at 0.5 V and 100 °C at 3.5 V)
2.5 Power consumption Approximately 75 mW
2.0 Load impedance > 47 kΩ
output signal

TM06 6560 1716

1.5
Materials
1.0
Sensing element Silicon-based MEMS
0.5
0.0 Sealing EPDM O-ring or FKM O-ring
0 P max T max Housing Composite (PPS, PA66)
T Peak
Flow pipe Stainless steel AISI 316 EN 1.4408
Fig. 111 Pressure and temperature response in Analogue Insert PPA 40 GF
mode Corrosion-resistant coating, EPDM
Wetted materials
or FKM, PPS, PPA 40-GF, 1.4408
Environmental standards
Enclosure class IP44, cable connected
Temperature cycling IEC 68-2-14
Vibration, non-destructive 20-2000 Hz, 10G, 4 h
Electromagnetic compatibility EN 61326-1

33
Flow sensors
5
MFS QT 4-40 l/min (1 - 10.6 gpm) Specifications
Multi Flow sensor, standard (MFS and MFS QT)

Flow
Measuring range QT 4-40 l/min (1-10.6 gpm)
Accuracy (± 1 σ) in water
± 1 % FS
0-120 °C (32-248 °F)
Response time (63.2 %) Less than 4 s
Resolution max flow/16384 l/min or gpm

TM05 4741 2512


Pressure
Measuring range 0-10 bar (0-145 psig)
Accuracy (± 1 σ),
± 2.0 % FS
15-90 °C (59-194 °F)
Accuracy (± 1 σ),
± 2.5 % FS
0-120 °C (32-248 °F)
Fig. 112 MFS QT 4-40 l/min Response time for sensor
250 ms
electronic
Dimensions Resolution 0.6 mbar (0.009 psig)
Temperature
Measuring range 0-120 °C (32-248 °F)
Accuracy (± 1 σ),
± 0.5 °C
15-90 °C (59-194 °F)
Accuracy (± 1 σ),
TM05 4671 2512 ± 1 °C
C

0-120 °C (32-248 °F)


Response time
2xB
250 ms
(63.2 % at 50 % FS flow)
A Resolution 0.006 K
Differential Temperature
Fig. 113 Dimensions, MFS QT 4-40 l/min, with threads Accuracy 15-90 °C (59-194 °F) 0.3 K
Accuracy 0-120 °C (32-248 °F) 0.5 K
A B C System conditions and environment
mm 110 58.8 Aqueous media compatible with
ISO 228/1 - G3/4 A wetted materials
in 4.33 2.31 Liquid types
Kinematic viscosity less than or
equal to 2 mm2/s (cSt)
Sensor output signals System temperature, operation 0-120 °C (32-248 °F)
-25 °C (-13 °F), non-freezing
System temperature, peak
3.5 120 °C (-248 °F)
3.0 Ambient temperature, operation -25 to +60 °C (-13 to +140 °F)
Flow output signal

2.5 Ambient temperature, peak -55 to +90 °C (-67 to +194 °F)


2.0 Humidity, relative 0-95 %, non-condensing
TM07 2485 3618

1.5 Maximum System Pressure 30 bar (435 psig)


1.0 Burst Pressure 40 bar (580 psig)
0.5
Max 16 bar (232 psig) at 100 °C
0.0 Maximum system pressure (212 °F)
0 Q min Q max example Max 8 bar (116 psig) at 120 °C (248
Fig. 114 Flow response in Analogue mode °F)
Electrical data
5 VDC (± 5 %), PELV
[V]
Power supply Grounding of sensor supply
4.5
required
Pressure and temperature

4.0
Digital output signals Grundfos open data protocol
3.5
0.5 - 3.5 for flow (zero at 0.35 V)
3.0
Analog output signals, only two and
2.5
signals possible (analogue pressure (zero at 0.5 V)
2.0 variants are upon request) 0.5 - 4.1 V for temperature
output signal

TM06 6560 1716

1.5 (zero at 0.5 V and 100 °C at 3.5 V)


1.0 Power consumption Approximately 75 mW
0.5 Load impedance > 47 kΩ
0.0
0 P max T max Materials
T Peak
Sensing element Silicon-based MEMS
Fig. 115 Pressure and temperature response in Analogue Sealing EPDM O-ring or FKM O-ring
mode Housing Composite (PPS, PA66)
Flow pipe Stainless steel AISI 316 EN 1.4408
Insert PPA 40 GF
Corrosion-resistant coating, EPDM
Wetted materials
or FKM, PPS, PPA 40-GF, 1.4408
Environmental standards
Enclosure class IP44, cable connected
Temperature cycling IEC 68-2-14
Vibration, non-destructive 20-2000 Hz, 10G, 4 h
Electromagnetic compatibility EN 61326-1

34
Flow sensors
5
MFS QT 10-100 l/min (2.6 - 26 gpm) Specifications

Multi Flow sensor, standard (MFS and MFS QT)


Flow
Measuring range 10-100 (2.6 -26 gpm)
Accuracy (± 1 σ) in water
± 1 % FS
0-120 °C (32-248 °F)
Response time (63.2 %) Less than 4 s
Resolution max flow/16384 l/min or gpm

TM05 4740 2512


Pressure
Measuring range 0-10 bar (0-145 psig)
Accuracy (± 1 σ),
± 2.0 % FS
15-90 °C (59-194 °F)
Accuracy (± 1 σ),
± 2.5 % FS
0-120 °C (32-248 °F)
Fig. 116 MFS QT 10-100 l/min Response time for sensor
250 ms
electronic
Dimensions Resolution 0.6 mbar (0.009 psig)
Temperature
Measuring range 0-120 °C (32-248 °F)
Accuracy (± 1 σ),
± 0.5 K
15-90 °C (59-194 °F)
Accuracy (± 1 σ),
±1K
0-120 °C (32-248 °F)
C

Response time
TM05 4672 2512

250 ms
(63.2 % at 50 % FS flow)
2xB Resolution 0.006 K
Differential Temperature
A
Accuracy 15-90 °C (59-194 °F) 0.3 K
Accuracy 0-120 °C (32-248 °F) 0.5 K
Fig. 117 Dimensions, MFS QT 10-100 l/min, with threads
System conditions and environment
Aqueous media compatible with
A B C wetted materials
Liquid types
mm 129 66.5 Kinematic viscosity less than or
ISO 228/1 - G1A equal to 2 mm2/s (cSt)
in 5.08 2.62
System temperature, operation 0-120 °C (32-248 °F)
-25 °C (-13 °F), non-freezing
Sensor output signals System temperature, peak
120 °C (-248 °F)
Ambient temperature,
-25 to +60 °C (-13 to +140 °F)
3.5 operation
3.0 Ambient temperature, peak -55 to +90 °C (-67 to +194 °F)
Flow output signal

2.5 Humidity, relative 0-95 %, non-condensing


2.0 Maximum System Pressure 30 bar (435 psig)
TM07 2485 3618

1.5 Burst Pressure 40 bar (580 psig)


1.0 Max 16 bar (232 psig) at 100 °C
0.5 Maximum system pressure (212 °F)
0.0 example Max 8 bar (116 psig) at 120 °C (248
0 Q min Q max °F)
Fig. 118 Flow response in Analogue mode Electrical data
5 VDC (± 5 %), PELV
Power supply
Grounding of sensor supply required
[V]
Digital output signals Grundfos open data protocol
4.5
0.5 - 3.5 for flow (zero at 0.35 V) and
Pressure and temperature

4.0 Analog output signals, only two


pressure (zero at 0.5 V)
3.5 signals possible (analogue
0.5 - 4.1 V for temperature
3.0 variants are upon request)
(zero at 0.5 V and 100 °C at 3.5 V)
2.5
Power consumption Approximately 75 mW
2.0
Load impedance > 47 kΩ
output signal

TM06 6560 1716

1.5
1.0 Materials
0.5 Sensing element Silicon-based MEMS
0.0 Sealing EPDM O-ring or FKM O-ring
0 P max T max
T Peak Housing Composite (PPS, PA66)
Flow pipe Stainless steel AISI 316 EN 1.4408
Fig. 119 Pressure and temperature response in Analogue Insert PPA 40 GF
mode Corrosion-resistant coating, EPDM
Wetted materials
or FKM, PPS, PPA 40-GF, 1.4408
Environmental standards
Enclosure class IP44, cable connected
Temperature cycling IEC 68-2-14
Vibration, non-destructive 20-2000 Hz, 10G, 4 h
Electromagnetic compatibility EN 61326-1

35
Flow sensors
5
MFS QT 20-200 l/min (5.3 - 53 gpm) Specifications
Multi Flow sensor, standard (MFS and MFS QT)

Flow
Measuring range 20-200 l/min (5.3 - 53 gpm)
Accuracy (± 1 σ) in water
± 1 % FS
0-120 °C (32-248 °F)

TM05 4739 2512


Response time (63.2 %) Less than 4 s
Resolution max flow/16384 l/min or gpm
Pressure
Measuring range 0-10 bar (0-145 psig)
Accuracy (± 1 σ),
± 2.0 % FS
Fig. 120 MFS QT 20-200 l/min 15-90 °C (59-194 °F)
Accuracy (± 1 σ),
± 2.5 % FS
Dimensions 0-120 °C (32-248 °F)
Response time for sensor
250 ms
electronic
Resolution 0.6 mbar (0.009 psig)
Temperature
Measuring range 0-120 °C (32-248 °F)
Accuracy (± 1 σ),
C
± 0.5 K

TM05 4673 2512


15-90 °C (59-194 °F)
Accuracy (± 1 σ),
±1K
2xB 0-120 °C (32-248 °F)
Response time
A 250 ms
(63.2 % at 50 % FS flow)
Resolution 0.006 K
Fig. 121 Dimensions, MFS QT 20-200 l/min, with threads
Differential Temperature
Accuracy 15-90 °C (59-194 °F) 0.3 K
Sensor output signals Accuracy 0-120 °C (32-248 °F) 0.5 K
System conditions and environment
A B C
Aqueous media compatible with
mm 137.5 74.1 wetted materials
ISO 228/1 - G1 1/4 A Liquid types
in 5.41 2.92 Kinematic viscosity less than or
equal to 2 mm2/s (cSt)
3.5 System temperature, operation 0-120 °C (32-248 °F)
3.0 -25 °C (-13 °F), non-freezing
System temperature, peak
Flow output signal

120 °C (-248 °F)


2.5
2.0 Ambient temperature,
-25 to +60 °C (-13 to +140 °F)
operation
TM07 2485 3618

1.5
Ambient temperature, peak -55 to +90 °C (-67 to +194 °F)
1.0
0.5 Humidity, relative 0-95 %, non-condensing
0.0 Maximum System Pressure 30 bar (435 psig)
0 Q min Q max Burst Pressure 40 bar (580 psig)
Max 16 bar (232 psig) at 100 °C
Fig. 122 Flow response in Analogue mode Maximum system pressure (212 °F)
example Max 8 bar (116 psig) at 120 °C (248
°F)
[V]
4.5 Electrical data
Pressure and temperature

4.0 5 VDC (± 5 %), PELV


Power supply
3.5 Grounding of sensor supply required
3.0 Digital output signals Grundfos open data protocol
2.5 0.5 - 3.5 for flow (zero at 0.35 V) and
Analog output signals, only two
2.0 pressure (zero at 0.5 V)
output signal

signals possible (analogue


0.5 - 4.1 V for temperature
TM06 6560 1716

1.5
variants are upon request)
1.0 (zero at 0.5 V and 100 °C at 3.5 V)
0.5 Power consumption Approximately 75 mW
0.0 Load impedance > 47 kΩ
0 P max T max
T Peak Materials
Sensing element Silicon-based MEMS
Fig. 123 Pressure and temperature response in Analogue
Sealing EPDM O-ring or FKM O-ring
mode
Housing Composite (PPS, PA66)
Flow pipe Stainless steel AISI 316, EN 1.4408
Insert PPA 40 GF
Corrosion-resistant coating, EPDM
Wetted materials
or FKM, PPS, PPA 40-GF, 1.4408
Environmental standards
Enclosure class IP44, cable connected
Temperature cycling IEC 68-2-14
Vibration, non-destructive 20-2000 Hz, 10G, 4 h
Electromagnetic compatibility EN 61326-1

36
Flow sensors
6

6. Product range

Product range
VFI transmitters
Scope of delivery
• Flow pipe with transmitter
• flanges, only for flange versions
• fittings and union nuts for threaded versions
• 5 m (16.4 ft) cable with free cable end
• quick guide.
O-ring Connection type
Complete product Flow range Flange size Cast iron Stainless Outside
EPDM FKM Thread
flange steel flange usage*
VFI/--0.3-6m/1/C/M5.00-X/EG6/SG/30F/AC-1 ● ● ●
VFI/--0.3-6m/1/C/M5.00-X/VG6/SG/30F/AC-1 ● ● ●
VFI/--0.3-6m/1/C/M5.00-X/EG6/SS/30F/AC-1 0.3 - 6 m3/h DN 25/32 ● ● ●
VFI/--0.3-6m/1/C/M5.00-X/VG6/SS/30F/AC-1 1.32 - 26.4 gpm ANSI 1 1/4" ● ● ●
VFI/--0.3-6m/1/C/M5.00-X/EG6/SS/07P/AC-1 ● ● ●
VFI/--0.3-6m/1/C/M5.00-X/VG6/SS/07P/AC-1 ● ● ●
VFI/-0.6-12m/1/C/M5.00-X/EG6/SG/30F/AC-1 ● ● ●
VFI/-0.6-12m/1/C/M5.00-X/VG6/SG/30F/AC-1 ● ● ●
VFI/-0.6-12m/1/C/M5.00-X/EG6/SS/30F/AC-1 0.6 - 12 m3/h DN 25/32 ● ● ●
VFI/-0.6-12m/1/C/M5.00-X/VG6/SS/30F/AC-1 2.64 - 52.8 gpm ANSI 1 1/4" ● ● ●
VFI/-0.6-12m/1/C/M5.00-X/EG6/SS/07P/AC-1 ● ● ●
VFI/-0.6-12m/1/C/M5.00-X/VG6/SS/07P/AC-1 ● ● ●
VFI/-1.3-25m/1/C/M5.00-X/EG6/SG/30F/AC-1 ● ● ●
VFI/-1.3-25m/1/C/M5.00-X/VG6/SG/30F/AC-1 ● ● ●
VFI/-1.3-25m/1/C/M5.00-X/EG6/SS/30F/AC-1 1.3 - 25 m3/h DN 25/32 ● ● ●
VFI/-1.3-25m/1/C/M5.00-X/VG6/SS/30F/AC-1 5.72 - 110.1 gpm ANSI 1 1/4" ● ● ●
VFI/-1.3-25m/1/C/M5.00-X/EG6/SS/09P/AC-1 ● ● ●
VFI/-1.3-25m/1/C/M5.00-X/VG6/SS/09P/AC-1 ● ● ●
VFI/---2-40m/1/C/M5.00-X/EG6/SG/31F/AC-1 ● ● ●
VFI/---2-40m/1/C/M5.00-X/VG6/SG/31F/AC-1 2-40 m3/h DN 40 ● ● ●
VFI/---2-40m/1/C/M5.00-X/EG6/SS/31F/AC-1 8.81 - 176.1 gpm ANSI 1 1/2" ● ● ●
VFI/---2-40m/1/C/M5.00-X/VG6/SS/31F/AC-1 ● ● ●
VFI/-3.2-64m/1/C/M5.00-X/EG6/SG/32F/AC-1 ● ● ●
VFI/-3.2-64m/1/C/M5.00-X/VG6/SG/32F/AC-1 3.2 - 64 m3/h DN 50 ● ● ●
VFI/-3.2-64m/1/C/M5.00-X/EG6/SS/32F/AC-1 14.09 - 281.8 gpm ANSI 2" ● ● ●
VFI/-3.2-64m/1/C/M5.00-X/VG6/SS/32F/AC-1 ● ● ●
VFI/5.2-104m/1/C/M5.00-X/EG6/SG/33F/AC-1 ● ● ●
VFI/5.2-104m/1/C/M5.00-X/VG6/SG/33F/AC-1 5.2 - 104 m3/h DN 65 ● ● ●
VFI/5.2-104m/1/C/M5.00-X/EG6/SS/33F/AC-1 22.89 - 457.9 gpm ANSI 2 1/2" ● ● ●
VFI/5.2-104m/1/C/M5.00-X/VG6/SS/33F/AC-1 ● ● ●
VFI/--8-160m/1/C/M5.00-X/EG6/SG/35F/AC-1 ● ● ●
VFI/--8-160m/1/C/M5.00-X/VG6/SG/35F/AC-1 8-160 m3/h DN 80 ● ● ●
VFI/--8-160m/1/C/M5.00-X/EG6/SS/35F/AC-1 35.22 - 704.5 gpm ANSI 3" ● ● ●
VFI/--8-160m/1/C/M5.00-X/VG6/SS/35F/AC-1 ● ● ●
VFI/-12-240m/1/C/M5.00-X/EG6/SG/42F/AC-1 ● ● ●
VFI/-12-240m/1/C/M5.00-X/VG6/SG/42F/AC-1 12-240 m3/h DN 100 ● ● ●
VFI/-12-240m/1/C/M5.00-X/EG6/SS/42F/AC-1 52.83 - 1057 gpm ANSI 4" ● ● ●
VFI/-12-240m/1/C/M5.00-X/VG6/SS/42F/AC-1 ● ● ●

* Outside usage only with cable connected.

37
Flow sensors
6
VFS and VFS QT sensors
Product range

Scope of delivery
• Flow pipe with sensor
• composite flow pipe with brass adapter (only VFS)
• stainless steel flow pipe (only VFS QT)
• quick guide.

O-ring Flow pipe Connection type


Complete product Flow range Stainless
EPDM FKM Composite Brass adapter Stainless steel
steel
VFS/---1-20l/1/D/S------/EG4/CB/03P/SW-1 ● ● ISO 228-G1/2 A
1.3 - 20 l/min
VFS/---1-20l/1/D/S------/VG4/CB/03P/SW-1 ● ● ISO 228-G1/2 A
VFS/---2-40l/1/D/S------/EG4/CB/04P/SW-1 ● ● ISO 228-G3/4 A
2-40 l/min
VFS/---2-40l/1/D/S------/VG4/CB/04P/SW-1 ● ● ISO 228-G3/4 A
VFS/--5-100l/1/D/S------/EG4/CB/04B/SW-1 ● ● ISO 7/1 R 3/4
VFS

5-100 l/min
VFS/--5-100l/1/D/S------/VG4/CB/04B/SW-1 ● ● ISO 7/1 R 3/4
VFS/-10-200l/1/D/S------/EG4/CB/05B/SW-1 ● ● ISO 7/1 R 1
10-200 l/min
VFS/-10-200l/1/D/S------/VG4/CB/05B/SW-1 ● ● ISO 7/1 R 1
VFS/-20-400l/1/D/S------/EG4/CB/07B/SD-1 ● ● ISO 7/1 R 1 1/4
20-400 l/min
VFS/-20-400l/1/D/S------/VG4/CB/07B/SD-1 ● ● ISO 7/1 R 1 1/4
VFS/---1-18l/l/D/S------/EG4/Q-/04P/SW-1 ● ● ISO 228/1-G3/4 A
1-18 l/min
VFS/---1-18l/l/D/S------/VG4/Q-/04P/SW-1 ● ● ISO 228/1-G3/4 A
VFS/---2-40l/1/D/S------/EG4/Q-/04P/SW-1 ● ● ISO 228/1-G3/4 A
2-40 l/min
VFS QT

VFS/---2-40l/1/D/S------/VG4/Q-/04P/SW-1 ● ● ISO 228/1-G3/4 A


VFS/--5-100l/1/D/S------/EG4/Q-/05P/SW-1 ● ● ISO 228/1-G1 A
5-100 l/min
VFS/--5-100l/1/D/S------/VG4/Q-/05P/SW-1 ● ● ISO 228/1-G1 A
VFS/-10-200l/1/D/S------/EG4/Q-/07P/SW-1 ● ● ISO 228/1-G1 1/4 A
10-200 l/min
VFS/-10-200l/1/D/S------/VG4/Q-/07P/SW-1 ● ● ISO 228/1-G1 1/4 A

38
Flow sensors
7

7. Accessories

Accessories
Sensor interface, converter unit Snap-on cable
The SI Converter sensor interface from Grundfos Cable with snap-on connection in sensor end and
Direct Sensors™ is an external power supply, signal different variants in the equipment end, such as open
amplifier and signal converter for Grundfos sensors, end, ferrules and various types of connectors.
standard variants (MFS, VFS, RPS and DPS). Use the cable for the standard sensor series such as
SI Converter has built-in precision resistors enabling MFS, VFS, RPS and DPS.
the sensor to give 4-20 mA, 1-5 V and 2-10 V output The cable is available in various lengths, mainly 1.2 m
signals. and 2.9 m.
SI Converter is designed for applications where
sensors from the standard product range are used. Description Length [mm]
The sensor interface delivers a 4-20 mA input signal to
Ferrules, 1.2 m 1200
external controllers.
Ferrules, 2.9 m 2900

TM04 4882 2209

Fig. 124 Sensor interface, SI Converter

Specifications
• Voltage range: 115-230 VAC ± 10 % or 24 VDC
• frequency: 50-60 Hz
• power consumption: Maximum 2.5 W
• ambient temperature: -20 to +50 °C (-4 to +122 °F)
• enclosure class: IP20.

Part
Sensor interface, SI Converter, IP20

M12 cable
The 4-wire screened cable with M12 connector in the
sensor end and open end in the equipment end is
available as an accessory. Use the cable for the
industrial sensor series such as RPI, DPI II and VFI.

Description Length

Cable, industry
2 m (6.6 ft)
M2.000X

Cable, industry
5 m (16.4 ft)
M5.000X

39
Flow sensors
8

8. Appendix
Appendix

Pressure drop curves


VFI sensor
Selection of flow sensor to minimise pressure drop at 1 cSt

[psig]
[psi]
Δp [bar]
0.6 8.7

DN100 SBB
B
0.5 7.3

SB
B
B

SB
B
0.4

80
5.8

SB

SB
Head loss:

50

DN
25

40

B
DN
BB
0.3

DN
4.4

SB
DN
B
S

SB

65
18

DN
32
DN
0.2 2.9

DN
0.1 1.5
0.08 1.16
0.06 0.87
0.05 0.73
0.04 0.58
0.03 0.44

0.02 0.29

0.01 0.15
0.008 0.116
0.006 0.087
0.005 0.073
0.004 0.058
0.003 0.044

0.002 0.029

0.001 0.015
0.0008
0.0116
0.0006 0.0087
0.0005 0.0073
0.0004 0.0058
0.0003 0.0044
TM06 6536 1716

0.3 0.4 0.6 0.8 1 1.2 1.5 2 3 4 5 6 8 10 12 15 20 30 40 50 60 80100 150 200 300 Q [m3/h]

2.6 5.3 7.9 11 13 16 21 26.4 52.8 79.3 106 159 264.2 528.3 792.5 1057 Q [gpm (US)]

40
Flow sensors
8
VFS sensor

Appendix
Selection of flow sensor to minimise pressure drop at 1 cSt

Δp [mbar] [psid]
1000 14.5038

00
0
Head loss:

1 - - 18

-2
100
40

-4
20

2-

10
1

5-

20
12
1-
100 1.4504

10 0.1450

1 0.0145

0.1 0.0015

TM06 6537 4118


0.1 1 10 100 1000 Q [l/min]

0.026 0.13 0.26 1.32 2.64 13.2 26.4 132 264 Q [gpm (US)]

41
Flow sensors
8
Installation of the VFI sensor
Appendix

min. 10 x D min. 5 x D

min. 20 x D min. 0,2 bar


(2.9 PSI) -25 to 60 °C
(-13 to 140 °F)
IP67
-30 to 120 °C
(-22 to 248 °F)

0 bar Max.28 bar


(406 PSI)

TM05 2306 2118

42
Flow sensors
8
Intended use for pressurised systems

Appendix
1
3
2 3

1 2

6
4
6 Qmax 5

4 Flow < 125% x Qmax


5 Speed < 125% x Qmax

125% x Qmax Qmax 125% x Qmax Qmax


• sec.

6
TM07 1885 2018

43
Flow sensors
9

9. Grundfos Product Center


Grundfos Product Center

Online search and sizing tool to help you


make the right choice.

http://product-selection.grundfos.com

SIZING enables you to REPLACEMENT enables you to find a


size a pump based on replacement product.
entered data and Search results will include information on
selection choices.
• the lowest purchase price
• the lowest energy consumption
• the lowest total life cycle cost.

CATALOGUE gives you LIQUIDS enables you to find pumps


access to the Grundfos and sensors designed for aqueous
product catalogue. media or other special liquids.

All the information you need in one place Downloads


Performance curves, technical specifications, pictures, dimensional drawings, motor On the product pages, you can download
curves, wiring diagrams, spare parts, service kits, 3D drawings, documents, system parts. installation and operating instructions, data
The Product Center displays any recent and saved items - including complete projects - booklets, service instructions, etc. in PDF format.
right on the main page. For aqueous media below 2 µS/cm contact your
local Grundfos sensor representative.

44
45
46
47
ECM: 1245557
97790189 1018

GRUNDFOS A/S

www.grundfos.com
Telephone: +45 87 50 14 00
DK-8850 Bjerringbro . Denmark
The name Grundfos, the Grundfos logo, and be think innovate are registered trademarks owned by Grundfos Holding A/S or Grundfos A/S, Denmark. All rights reserved worldwide. © Copyright Grundfos Holding A/S

You might also like