You are on page 1of 3

power transmission

transmission lines. As an
example, under contract to

Enhancing Transmission a Midwestern utility com-


pany, POWER performed
Line Performance: Using detailed studies of corona

Simulation to Optimize Design


performance for special
345-kilovolt transmission
line equipment proposed to
The design of high-voltage transmission lines involves optimization mitigate mechanical stress
under a complex series of economic, electrical, mechanical, and due to wind and ice loads.
environmental constraints. Using simulation, POWER Engineers, Inc. These studies provided a
better understanding of the
analyzed transmission line corona performance prior to device device’s electrical perfor-
manufacturing and high-voltage testing, saving both time and money. mance prior to high-voltage
testing in the laboratory.

By Alexandra Foley » Calculating


Electric Fields for
Complex Geometries
Le veraging highly Transmission struc tures
accurate simulation tech- designed to support sig-
nology and knowledge nificant lateral forces
gained from decades of from conductor tension
analyzing in-service equip- are called dead-end struc-
ment, today’s engineers are tures. Insulator assemblies
able to investigate, model, mounted on these struc-
and neutralize subtle effects tures provide an electri-
that were impossible to cally isolated connection
assess without expensive between the structure and
and rigorous testing even the energized conductor
just a few years ago. One (see Figure 1). Electric fields
area in which simulation is near the surface of these
successfully being applied high-voltage conductors
is in the analysis of the and dead-end assemblies
adverse effects of corona can ionize the surround-
discharge in bulk power ing air molecules, resulting
transmission lines and their in corona discharge. The
associated equipment. effects of this phenomenon
While analyses of this include energy losses, elec-
sort are usually conducted tromagnetic (AM radio)
through testing in high- interference, audible noise,
voltage labs or by evaluat- visible light, and possible
ing in-service equipment, erosion of materials.
POWER Engineers, Inc. “If you’ve ever stood near
(POWER), a global consult- a transmission line, you’ve
ing engineering firm, found probably heard the buzz-
that finite element simula- ing noise it makes,” says
Figure 1: Top: A dead-end structure. Bottom: CAD representation
tion software was an effec- Jon Leman, Senior Project
of the dead-end insulator assembly.
tive tool for analyzing the Images courtesy of Danny Frederick and Charlie Koenig,
Engineer at POWER.
corona performance of POWER Engineers, Inc. “Above a certain voltage, the

may 2014 comsol multiphysics 3


power transmission

Surface Voltage Plotted


as log (Volts+1)
The COMSOL
software
combines the tools
necessary for us to
provide our customers
with an accurate
analysis of how the
proposed transmission
hardware will perform.”
—Jon Leman,
Senior Project
Engineer at POWER

Figure 3: Electric field strength at the surface of the dead-end


electric field ionizes air mol- insulator assembly. Areas with high electrical fields occur at the
ecules and creates corona pins of the insulator units and at the square mounting pads.
discharge. Usually that’s
what causes the noise you
hear. Minimizing this noise ductor. Leman performed pins are shown in Figure 4.
Figure 2: A 2-D axisymmetric
and other negative effects custom postprocessing of In addition to audible
model showing the electric
requires reducing corona potential distribution along the electric field results by noise and radio interfer-
discharge.” A certain level of the insulator string. entering empirical, space- ence, severe corona dis-
corona activity and associ- dependent equations into charge can deteriorate the
ated effects are tolerable for COMSOL to estimate the insulator unit over time,
transmission line conduc- insulator string to deter- net number of air ioniza- possibly resulting in loss
tors, but attachment hard- mine the floating poten- tions near regions with high of strength and insulating
ware is typically supposed tial on the last insulator electric fields. This allowed capability. “Now that we
to be free of noticeable unit’s cap (see Figure 2). him to estimate the prob- have identified where the
corona activity. Leman used Knowing this boundary ability of corona activity. issues are likely to occur
COMSOL Multiphysics® to voltage allowed POWER to Results showed that there on the hardware, it will
determine the electric field build a reasonably accurate were two areas with elec- provide an opportunity to
strength near the surface 3-D model without hav- tric fields strong enough to modify the design prior to
of the energized hardware ing to include the repetitive result in corona discharge: testing,” says Leman. Rob
and to estimate the proba- geometric complexity and The energized pins of the Schaerer, a project engi-
bility of corona discharge computational burden of insulator units and the neer at POWER who also
at locations with high the whole insulator string. corner of the upper square participated in the project,
electric fields. mounting pads (shown as coordinates procedures
“In order to set up a lean » Predicting red areas in Figure 3). and witnesses high-voltage
simulation, we modeled Device Corona “Our results demon- corona testing for clients.
the insulator assembly for Performance strated that the outside He says, “Laboratory test-
one of the three transmis- Corona discharge is a corners of the square ing is an important part of
sion line phases and only complex physical phenom- mounting pads are likely new hardware design, but
included the first unit of enon affected by a combina- susceptible to corona dis- there are costs that can be
the insulator string,” says tion of electric field strength, charge, but only marginally saved by up-front analysis,
Leman. POWER then device geometry, atmo- so,” explains Leman. “The particularly if retesting is
used a 2-D axisymmet- spheric conditions, and the insulator pins, however, required. Scheduling time
ric model of the complete surface condition of the con- may experience significant in high-voltage labs can be
corona discharge.” Detailed difficult on short notice, so
views of the electric fields by having a reasonably vet-
4 comsol multiphysics may 2014 present at the insulator ted design prior to testing,
Jon Leman, Senior Project
Engineer at POWER

Rob Schaerer, project


engineer at POWER

Charlie Koenig, Visualization/


Animation Specialist at POWER

tomers with an accurate


analysis of how the pro-
posed transmission hard-
Figure 4: Top: Electric potential cross-section of the air surrounding the insulator pin. ware will perform, allow-
Bottom: Electric field results for the insulator pin. ing opportunities to
reduce design iterations
that would otherwise take
a project is less likely to be form prior to its construc- tant that we combine that place after high-voltage
impacted by a design that’s tion. When combined with ingenuity with the use testing.” Examples such
found to be insufficient in results from empirical test- of advanced tools to effi- as this show how simula-
the first round of testing.” ing, engineers can arrive ciently design tomorrow’s tion can change the pro-
at a reasonable prediction grid,” says Leman. “The cess by which devices are
» Accurate of how a new device design COMSOL software com- designed in order to reduce
Simulations Drive will perform. “I have great bines the tools necessary costs and more quickly
Real-World Results respect for the engineers for us to provide our cus- optimize solutions.
Simul ation c an be used to who built the electric grid
provide information about without the use of mod-
how a device will per- ern computing. It’s impor- may 2014 comsol multiphysics 5