PRODUCT GUIDE

High Burden Tripping Relays


RXMN and RXMVC

The High Burden Tripping Relay
provides enhanced security in the
substations and avoids opening
of the circuit breaker due to
capacitive discharge currents
when there is an earth fault in
long DC cables. The self reset trip
relay (RXMN) and electrically or
manually resettable latched trip
relay (RXMVC) fulfill applicable
international standards.
TA B L E O F C O N T E N T S 3


Table of contents

004  High burden tripping relays

005  -006 Technical data

007 -008 Diagrams and Ordering


4 H I G H B U R D E N T R I P P I N G R E L AY S R X M N A N D R X M V C


High Burden Tripping Relays
RXMN and RXMVC

Features Design
• High burden operating coil meeting ENA TS 48 4 The relays essentially contain an electromagnetic
standard part consisting of a magnetic circuit including an
• High speed operation (≤ 10ms) armature and an electronic circuit to regulate the
• Immune to capacitive discharge due to earth fault input voltage and duration of burden.
in DC cable RXMN relay is of self-reset type. It contains a
• Electrical / hand reset and self-reset variants plunger type armature which operates the
• 8 and 15 contacts in electrical / hand reset moving contacts when the coil is energized. In the
variant, 8 and 16 contacts in self-reset variant de-energized condition, the armature is held in
• Hand reset / self-reset flag (red) available for open position by a spring. The fixed contacts are
operation indication directly mounted on the terminal plate.
• Heavy duty contacts with high continuous current RXMVC relay is of bi-stable type. It has two
carrying and breaking capacities identical stable positions with an operate and a
• Suitable for harsh environments – meets IP44 reset coil. When either coil is energized with the
when flush mounted correct polarity a repulsion occurs and the
• Design meets IEC 60255 and IEC 61810 standards armature switches to the other side where it
• Double insulation, no exposed live parts – high locks magnetically.
degree of safety In the both types, the electronic circuit comprises
of a voltage regulator at the input, a timing circuit
Application that controls the duration of burden and a
High burden tripping relays type RXMVC and switching circuit that controls the supply to the
RXMN are designed for use in high security coil. The coil supply terminals are polarized, thus
tripping applications. Such applications require safeguarding the electronic circuits. The relays
immunity to capacitive discharge due to earth occupy 4 seats in COMBIFLEX modular design.
fault in DC cables. The relays have heavy duty In RXMVC there is a built-in interlock feature that
bridge contacts for direct connection to circuit prevents electrical resetting during operation.
breaker tripping coils. All contacts are of heavy duty bridge type with
high breaking capacity and low contact
Typical applications are as master trip relays and resistance. Contact bounce is negligible.
trip lockout relays in protection schemes. Various combinations of NO and NC contacts are
High coil burden during operation that is reduced available, please see ordering information.
to either zero or a low value after pick-up provides The high operating burden of the coil persists for
immunity to capacitive discharges and at the 50ms to allow external series flag relays, if any,
same time ensures that the station battery is not to operate. The burden is reduced to a low value
overloaded. after 50ms in the self-reset variant.
It is reduced to zero after 50ms in the electrical /
hand reset variant. Thus, there is no continuous
load on the auxiliary supply and also no risk of
welding of protective relay output contacts.
T E C H N I C A L D ATA 5


Technical data


Table 1. General

Rated voltage, Ur 110, 125, 220 V DC


Duty range, % of Ur 70 to 110 %
Burden of operating coil – Self reset variant: 130 to 150 W for 50ms, reduced to approx. 6 W after 50ms
– Electrically reset variant: 130 to 150 W for 50ms, reduced to zero after 50ms
Burden of resetting coil <4W
(for electrically reset variant)
Operating time ≤ 10 ms
Resetting time < 30 ms
Immunity to capacitive discharge 10μF, 120% of rated voltage across operating coil


Table 2. Contact Ratings

Making and conducting capacity L/R > 10 ms,


200 ms/1s A 30/20
1s, 2 contacts in parallel A 30
Current carrying capacity L/R > 10ms, Self-reset Self-reset 16 contacts & all
200 ms/1s A 8 contact variant electrically reset variants
135 / 75 90 / 50
Current carrying capacity, continuous
(for already closed contact) A 10
Breaking capacity, ac, PF > 0.1, max. 250V A 20
Breaking capacity, DC, L/R < 40ms, A Self - reset Self-reset 16 contacts & electrically
8 contacts reset
at 24 V 20 20
48 V 20 12
110 V 6 3
125 V - 2.5
220 V 1.2 1.0
250 V - 0.8
Dielectric test, 50 Hz, 1 min 2.5 kV
Impulse voltage test, 1.2/50μs, 0.5J 5 kV
Modular size 4U, 12C
Degree of protection, IEC 60529 IP 44
Weight Approx. 1 kg


Table 3. Mechanical Tests

Test Severity Standard


Vibration Response IEC 60255-21-1, Class 2
Endurance IEC 60255-21-1, Class 2
Shock Response IEC 60255-21-2, Class 2
Withstand IEC 60255-21-2, Class 2
Bump Withstand IEC 60255-21-2, Class 2
Seismic IEC 60255-21-3, Class 2
6 H I G H B U R D E N T R I P P I N G R E L AY S R X M N A N D R X M V C


Table 4. Electromagnetic compatibility (EMC), immunity test

Test Severity Standard


Surge Differential mode: 0.5 and 1 kV IEC 61000-4-5
Common mode: 0.5, 1 and 2 kV
Power frequency magnetic field Continuous: 30A/m IEC 61000-4-8
1s to 3s: 300A/m
Slow damped oscillatory wave Voltage oscillation frequency 1 MHz IEC 61000-4-18
Auxiliary input supply port Test levels
Differential mode 1 kV
Common mode 2.5 kV
Fast transient IEC 61000-4-4
Auxiliary input supply port 4 kV
Electrostatic discharge IEC 61000-4-2
(Enclosure port)
Contact 2, 4, 6 kV
Air 2, 4, 8 kV

Radiated radiofrequency Sweep and spot frequencies as per IEC 61000-4-3


electromagnetic field clause 3.1 of table 3 of IEC 60255-26
(Enclosure port)
Conducted disturbance induced by Sweep and spot frequencies as per IEC 61000-4-6
radio frequency fields clause 4.1 of table 4 of IEC 60255-26,
Auxiliary input supply port Zone A
Radiated emission 30 MHz to 230 MHz IEC 60255-26
(Enclosure port) 40 dB(μV/m) quasi peak at 10 m
50 dB(μV/m) quasi peak at 3 m
230 MHz to 1 000 MHz
47 dB(μV/m) quasi peak at 10 m
57 dB(μV/m) quasi peak at 3 m
Conducted emission 0.15 MHz to 0.50 MHz IEC 60255-26
(Enclosure port) 79 dB(μV) quasi peak
66 dB(μV) average
0.5 MHz to 30 MHz
73 dB(μV) quasi peak
60 dB(μV) average


Table 5. CE compliance

Test Severity
Immunity EN 60255-26
Emissivity EN 60255-26
Low voltage directive EN 50178
DIAGR AMS AND ORDERING 7


Diagrams and ordering

RXMN 41 RXMN 42

1MYN000030-.. 1MYN000031-.. 1MYN000032-.. 1MYN000033-.. 1MYN000040-.. 1MYN000041-.. 1MYN000042-..


+ + + + + + +
121 211 121 211 121 211 121 211 121 211 121 211 121 211

111 112 111 112 111 112 111 112 111 112 111 112 111 112

113 114 113 114 113 114 113 114 113 114 113 114 113 114

221 222 221 222 221 222 221 222 115 116 115 116 115 116

223 224 223 224 223 224 223 224 117 118 117 118 117 118

115 116 115 116 115 116 115 116 221 222 221 222 221 222

117 118 117 118 117 118 117 118 223 224 223 224 223 224

225 226 225 226 225 226 225 226 225 226 225 226 225 226

227 228 227 228 227 228 227 228 227 228 227 228 227 228
311 312 311 312 311 312
313 314 313 314 313 314
315 316 315 316 315 316
317 318 317 318 317 318
421 422 421 422 421 422
423 424 423 424 423 424
425 426 425 426 425 426
427 428 427 428 427 428

Letter selection table, dc rated voltage V


110 125 220
AN AP AS
8 H I G H B U R D E N T R I P P I N G R E L AY S R X M N A N D R X M V C


Diagrams and ordering

RXMVC 41 RXMVC 42

1MYN000010-.. 1MYN000011-.. 1MYN000012-.. 1MYN000013-.. 1MYN000020-.. 1MYN000021-.. 1MYN000022-..


+ + + + + + +
121 122 121 122 121 122 121 122 121 122 121 122 121 122

113 114 113 114 113 114 113 114 111 112 111 112 111 112

115 116 115 116 115 116 115 116 113 114 113 114 113 114

117 118 117 118 117 118 117 118 115 116 115 116 115 116

111 112 111 112 111 112 111 112 117 118 117 118 117 118
221 222 221 222 221 222
223 224 223 224 223 224
221 222 221 222 221 222 221 222
225 226 225 226 225 226
227 228 227 228 227 228 227 228
227 228 227 228 227 228
225 226 225 226 225 226 225 226
223 224 223 224 223 224 223 224
317 318 317 318 317 318
+ + + +
211 212 211 212 211 212 211 212 315 316 315 316 315 316
313 314 313 314 313 314
311 312 311 312 311 312
427 428 427 428 427 428
425 426 425 426 425 426
423 424 423 424 423 424

+ + +
211 212 211 212 211 212

Letter selection table, dc rated voltage V


110 125 220
AN AP AS
10 H I G H B U R D E N T R I P P I N G R E L AY S R X M N A N D R X M V C

Note
We reserve the right to make technical
changes or modify the contents of this
document without prior notice. ABB
does not accept any responsibility
whatsoever for potential errors or
possible lack of information in this
document. We reserve all rights
in this document and in the subject
matter and illustrations contained
therein. Any reproduction, disclosure to
third parties or utilization of its
contents – in whole or in parts – is
forbidden without prior written consent
of ABB.

ABB India Limited
Grid Automation Products
Plot no. 4A, 5 & 6, II Phase
Peenya Industrial Area
Bangalore - 560 058. India
Phone: +91 80 2294 9632


ABB AB
Grid Automation Products
SE 721 59 Västerås, Sweden
Phone: +46 (0) 21 32 50 00

http://new.abb.com/substation-
automation/products/protection-control/
modular-relays-and-accessories
4CAE000328 | © Copyright 2018 ABB. All rights reserved.