LP-12-UPS-S
LP-12-LS
DB-1-L
DB-1-L-UPS
LP-1-EH LP-11-LS w
LP-11-UPS-S
LP-1-L-UPS
PP-1
DP-1-EH
EMT CONDUIT
4x2''
W
NOTES:
1- CONDUIT SIZE: COMPLY WITH NFPA 70 :
a. MINIMUM SIZE: 1 inch (25 mm) UNLESS OTHERWISE SPECIFIED TELECOM SYSTEM
b. MAXIMUM SIZE OF CONDUIT IN SLAB 1-1/4'' (32mm)
AMS
A DATA OUTLET FOR AIR MONITOR
4- BOXES IDENTIFICATION LABELED AS FOLLOW: TRIPLEX RJ45 ASSEMBLY CONSISTING OF 2 ACTIVE CONNECTORS AND
FLOOR NUMBER-FUNCTION OF BOXES IDENTIFICATION -BOXES ONE EMPTY SPACE FOR FUTURE
NUMBER UTP CABLE FOR EMPTY SPACE TO BE PROVIDED(NOT SHOWN ON THE
DWG)
5-FOR DIMENSIONS AND HEIGHTS OF WALL POINTS REFER TO DRAWING
TB TABLE MOUNTED BOX WITH TRIPLEX RJ45.
REFERENCE SD-E106CLL
TV OUTLET WALL MOUNTED
6-IF THE LENGTH OF FLEXIBLE LIQUID TIGHT OR FLEXIBLE METAL
TV
CONDUITS FROM FIXTURE TO TAP CONNECTIONS, AS PERMITTED IN
410.67 (C) IS 6FT (1.8M), OR LESS STRAPPING IS NOT REQUIRED
Wiring:
7- FOR EXACT CABLE TRAY ROOTING AND DETAILS REFER TO
CAT7 telephone or Data Cable running in
DRAWINGS REFERENCE:
slab 1" SCH40-PVC conduit unless
SD-E106CT
otherwise indicated .
8-SIZES OF CONDUITS NOT SHOWN ON THE DRAWINGS ARE TO BE CAT7 telephone or Data Cable running in
SELECTED IN ACCORDANCE WITH THE REGULATIONS AND IN RELATION EMT conduit unless otherwise indicated.
TO NUMBER AND SIZE OF CONDUCTORS AS SHOWN IN THE TABLE
BELOW: Fiber optic running in 1" EMT conduit
unless otherwise indicated.
otherwise indicated
BOXES: