You are on page 1of 40

CAMTECH/99/S/DAIDO/1.

0 1

SINGLE LINE, HANDLE TYPE


TOKEN LESS BLOCK INSTRUMENT
(FM CODED)

1. INTRODUCTION

This Hand book covers the general requirements of, Single line, Handle type Token less
Block Instrument for use in RE & Non-RE sections.

A pair of Block Instruments is connected electrically through overhead or cable to


control the movement of trains on single line Block Section in either direction.

The Instrument is designed to work on Frequency Modulation (Carrier frequency 1800


Hz or 2700 Hz and modulating frequency 65 Hz and 85 Hz).

1.1 Advantages over Token Block Instrument :

1. Less operating time.


2. No Token exchange.
3. Less physical strain.
4. Problems like token missing, token balancing, census of token, recoupment of lost
token or damaged token etc. are not encountered.
5. Avoidable detention is minimized.
6. Increase section capacity
7. Maintaining normal polarity/Reverse Polarity of Block instrument is not required.

S/ Line Tokenless B/Instrument December’ 1999


CAMTECH/99/S/DAIDO/1.0 2

2. SYSTEM COMPOSITION

The Block instrument is compact & robust in construction and fit to stand for rough
handling. It is easy to maintain. Removal/ replacement of any part or sub-assembly
does not disturb the adjoining parts/ sub-assemblies.
The following components are provided within the Block Instrument:

Bell

Galvo
Block
phone Time
Release
Train On
1 2 Line
Indicator
COUNTER PB2 PB1
LINE

S1 S2 N
Block
Handle
SM SH TGT TCF

S/ Line Tokenless B/Instrument December’ 1999


CAMTECH/99/S/DAIDO/1.0 3

2.1 Block Handle :

A mechanically operated rotary type handle, called Block Handle is located in the front
on the lower part of the Block instrument. Different contact positions of the handle are
shown in figure given below:

N Y
X

XI YI

B D
A
L R

VARIOUS POSITION OF BLOCK HANDLE

L AB X X1 N Y Y1 D R
LOCK
PAWL

FORCED DROP FORCED DROP


PROJECTION PROJECTION

FORCE DROP LOCKING ARRANGEMENT


(DEVELOPED VIEW)

S/ Line Tokenless B/Instrument December’ 1999


CAMTECH/99/S/DAIDO/1.0 4

2.1.1 The handle is free to be turned between X and Y, R and D and also between L and B.
Movement of the handle to Train Coming From, Train Going To and back to Normal
position from Train Coming From and Train Going To is controlled by an electric lock
and this lock is required to be energized at Y position for turning handle to Train
Coming From and at D or B position for turning from Train Coming From or Train
Going To to Normal. For turning to Train Going To, the lock is initially energised at X
position but gets forced dropped before X and is actuated at X position for further
movement to Train Going To. The locking effective at X is termed as check locking
and is provided to ensure the conscious cooperation of the operator at the other end.
This locking is however not effective while turning the handle from Train Going To
normal even though the lock is forced dropped. It is because of the beveled edge of the
concerned notch on which the lock just slides over and does not cause an obstruction to
the movement of the handle.

The block handle assembly consists of 24 sets of spring contacts (circuit controller),
actuated during the course of handle of operation.

2.1.2 Need for Forced Drop Arrangement

When the lock gets energised then the handle is free to move from Normal to Train
Coming From/Train Going To position depending upon the code that is received. Due
to residual magnetism there is a possibility of lock armature to stick up, then the
operator can normalise the block handle from Train Coming From/Train Going To. To
avoid such type of irregular movement there is a need to lock the handle in respective
position. The projection on the locking bracket ensure the forced drop of the lock coil
so that the operator can not normalise the block handle, once it is turned to Train
Coming From/Train Going To, with out cooperation of other operator.

2.2 Galvo

Indicates incoming and outgoing DC current. The resistance of the coil is 18.2 ohms,
working current is 110 mA and working voltage is 2 volt.

2.3 Time release Indication

It is an electromagnetic indicator to indicate the maturity of Time Element Relay during


cancellation of a line clear. The coil resistance is 200 ohms.

Normally it shows white indication with words LOCKED and when operated it shows
green indication with words FREE.

2.4 TOL Indicator

It is an electromagnetic indicator(magnetic latch type). It operates on entry of train in to


block section at either of station.

When the Block section is clear, it displays white indication and when the train enters
into the Block Section on a line clear it changes to Red indication with writing “Train
On Line” and it holds magnetically. The indicator again changes to white when block
handle is turned from any position to line closed.
2.5 Switch S1 with counter

S/ Line Tokenless B/Instrument December’ 1999


CAMTECH/99/S/DAIDO/1.0 5

Switch Sl is a two position switch. when operated to reverse it initiates the


cancellation of line clear. The counter is used to register cancellation operation.

2.6 Switch S2 with counter

Switch S2 is a two position switch. when operated to reverse it is used for normalising
the instrument during a push-back operation of a train to the starting station.

Push Back operation is performed immediately after reversing S2. The counter is used
to register Push Back operation.

2.7. Push Button PB1

It transmits DC current for exchanging bell codes.

When PB1 is pressed alone it transmit

1. DC (-ve) on Line 1 for Bell.


2. DC (+ve) on L1 for TOL acknowledgment.
3. The same button, when pressed along with PB2, is used for sending of operational
code.

2.8 Push Button PB2

It is used in conjection with PB1 to transmit operational codes to permit the operation
of block handle at other station. The code sent is frequency modulated code along with
a DC (+ve) code.

PB2 is pressed always along with PB1 to pickup PBPR, which in turn sends ;

i) Frequency modulated code by switching on the Transmitter.


ii) DC (+ve) on L1.

2.9 Single Stroke Bell

It is mounted on the top of the instrument and is used for exchanging bell code signals
i.e. It provides to receive bell code. The bell coil is wound to a resistance of 310 ohms
and requires about 70 mA for operation.

It sounds when BLR or NR picks up and used for exchanging Bell Code.

2.10 Buzzer

Two electronic buzzers (BZ1 & BZ2) are provided in side the Block instrument.

BZ1 - It is a dual tone buzzer & sounds at both stations when the train enters into the
block section and stops after acknowledgment by the pressing PB1 at the train
receiving station.
BZ2 - It Sounds at the Receiving station on train arrival on proper reception signals and
sequence. It stops by normalizing the Home Signal SM’s slide/lever.

S/ Line Tokenless B/Instrument December’ 1999


CAMTECH/99/S/DAIDO/1.0 6

2.11 SM’s Key

To avoid unauthorised operation in the absence of SM.

When this key is taken out the block instrument becomes inoperative for all functions
except for:

i) Reception of Bell Code.


ii) Reception or transmission of TOL Code.

2.12 Shunting Key

This key is used as a shunting authority to shunt in any direction beyond Last stop
signal up to first stop signal of the station. It is normally kept inserted in the Block
instrument. It can be taken out only when the block handle is in Line Closed or Train
Going To position, and when taken out, the Block handle is locked mechanically in last
position. The insertion and extraction of key can be done only when SM’s key is
inserted and turned ON.

2.13 Transmitter

It transmits a frequency modulated output (1800 or 2700 with 65 or 85 Hz) when the
DC feed is connected to it by different selections. The modulated frequency is selected
by the transmitter by an external loop completed through the relevant selection
according to the condition of the block instrument.

2.14 Receiver

This receives the frequency modulated signals transmitted from the other end and gives DC
output for energising either CR1 or CR2 depending on the modulating frequency of the
code received. The receiver is switched on when the DC feed is connected through the
relevant selections.

2.15 The block instruments are designed to work either on 1800 Hz or 2700 Hz carrier
frequencies. The modulating frequencies are 85 Hz and 65 Hz and these are common
for all the instruments.

The codes used in the Block Instrument are

2.15.1 1800 Hz or 2700 Hz modulated by 85 Hz with DC positive : To permit operation of


block handle from line closed to Train Coming From, Train Coming From to line
closed and Train Going To to line closed.

2.15.2 1800 Hz or 2700 Hz modulated by 65 Hz with DC positive : To permit operation of


block handle from line closed to Train Going To.

2.15.3 1800 Hz or 2700 Hz modulated by 65 Hz : To set the other end’s Block instrument to
“Train On Line”.

S/ Line Tokenless B/Instrument December’ 1999


CAMTECH/99/S/DAIDO/1.0 7

2.15.4 DC negative : For exchanging bell code signals.

NOTE :

• DC positive refers to line battery positive connected to line 1 and negative to line 2.

• DC negative refers to line battery negative connected to line 1 and positive to line 2.

3. RELAYS NOMENCLATURES

3.1 BLR

It is a biased Relay and picks up when (+ve) on L2 and (-ve) on L1 is received from the
line and the single stroke Bell sounds through the pickup contacts of BLR.

3.2 NR

It is also a biased Relay and pickup when (+ve) on L1 and (-ve) on L2 is received from
the line, Single stroke Bell sounds and lock magnet energised through its pickup
contact.

3.3 PBPR

Picks up when PB1 & PB2 are pressed simultaneously or only PB1 with TOLR pickup
condition during TOL code transmission. It connects DC (+ve) on L1 and (-ve) on L2
and transmitter to the local Battery.

3.4 CR1 : Coding Relay

3.5 CR2 : Coding Relay

3.6 TRSR : Train sending Relay

3.7 1R

It proves the normal condition of reception signal’s and Last stop signal’s levers and
SM’s slide.

3.8 1TPR

This is a repeater of FVT Track Relay (ASTR).

S/ Line Tokenless B/Instrument December’ 1999


CAMTECH/99/S/DAIDO/1.0 8

3.9 TOLR : Train on line relay

3.10 2R

Picks up after the complete arrival of the train with proper sequence.

3.11 3R : Cancellation Relay

When S1 is turned for normal cancellation, after a specified time (120 sec.) delay it
picks up and the ‘FREE’ indicator energised through its pick up.

3.12 TEPR

Once S1 is turned for normal cancellation the electronic timer relay gives output of 24
v after a specified time delay (120 sec.) which in turns picks up the TEPR.

3.13 Timer Relay

It is an electronic Type Relay used for pickup of TEPR relay after 120 sec. time delay
in case of normal cancellation.

3.14 TELR

Telephone Relay of resistance 70 ohms, picks up when switch of hand micro telephone
is pressed and in turns it connects the telephone on line and also disconnect the TX &
RX from the frequency line.

3.15 External Relays :

3.15.1 ASR : Advance Starter Relay

3.15.2 HSR : Home Signal Control relay.

3.15.3 TAR : Train Arrival Relay

3.15.4 SNR : Signal Normal Relay

4. POWER SUPPLY

Three sets of batteries are required :

4.1. Line Battery

Line battery is normally of dry cells. The voltage is varying from 24 V depending on
the length of the block section in order to get a working current of 100 mA on line. This
battery is connected on line whenever the DC is required to be sent either foe
exchanging the bell signals or as a part of the operational code.

S/ Line Tokenless B/Instrument December’ 1999


CAMTECH/99/S/DAIDO/1.0 9

4.2. Local Battery

Local battery is of 24 Volt and is used for giving the supply to the transmitter and
receiver and also operating relays, indicators, local magnets etc. of the instruments.
Since the current drain on the battery is high, secondary cells are generally used.

4.3 Location/External Battery

It is used for external circuits to repeat the external conditions to the instruments
according to the requirements of the circuits. Picking up of PBPR, connects +ve to L1
& -ve to L2 and also switches on the DC feed for the transmitter. Since the block
handle is in normal position, the loop circuit is connected for the modulated output is
connected to the line.

5. SPECIAL FEATURES

5.1 Special features of Daido Tokenless Block Instrument are given below:

5.1.1 To ensure that the relays “NR” and “BLR” are not picked up simultaneously back
contact of NR relay is proved in BLR circuit. Similarly in the PBPR circuit back
contact of CR1 and CR2 relays have been provided to ensure that PBPR relay will not
be energized. While receiving modulated frequencies.

5.1.2 Front contact of PBPR Relay has been proved in the DC feed circuit of transmitter,
whereas back contact has been proved to the receiver circuit to guard against receiving
its own F.M. output modulated frequency transmitted similarly, back contact of CR2
and CR2 relays have been proved in the DC feed circuit for transmitted to ensure that
no code except the code of bell signals can be generated unless the code relays are de-
energised.

5.1.3 Since TOL code has to be transmitted automatically as soon as a train occupies FVT,
Front contact of PBPR Relay is not proved in DC feed circuit to the transmitter but the
same is taken in TOLR Front contact NR Relay back contact with the block handle at L
position.

5.1.4 Similarly for the receiver to be in readiness. To receive the TOL code, the DC feed
circuit is taken via 2R Relay back contact with the block handle “R” position.
5.1.5 Pressed contact of the PB2 button in the DC feed circuit of the transmitter, proves the
positive action taken to energise PBPR Relay for transmitting modulated frequency
along with DC.

5.1.6 Block handle contacts (BX) and (DY) are included in the DC feed circuit to the
receiver so that the DC feed to the receiver is switched on only. When the Block handle
operation is initiated. Thus minimising battery consumption.

5.1.7 SM’s key contact has not been provided in the DC feed circuit of Transmitter for
transmitting and receiving of automatic TOL code to ensure that the TOL indicator will
display, immediately the block sections occupied irrespective of the position of the
SM’s key.

S/ Line Tokenless B/Instrument December’ 1999


CAMTECH/99/S/DAIDO/1.0 10

5.1.8 To ensure that the relay CR1 and CR2 are not be energised one at a time, back contact
of CR1 relay is proved to energise CR2 relay and similarly back contact of CR2 relay is
proved to energise CR1 relay.

5.1.9 Cross protection to the lock Magnet is given through the CR1 and CR2 back contacts.

5.1.10 “Transmitter” and “Receiver” are connected to line through the back contact of TELR
relay is ensure that during conversation on telephone, no code is transmitted or received
by the transmitter and receiver respectively at either end. Similarly the telephone set is
connected to the lines through the front contact of TELR Relay and TELR Relay feed is
taken through the back contact of CR1 and CR2 relays to ensure that during
Transmission and reception of Code the telephone is disconnected the back contact of
TOLR is included in the TELR PICK UP circuit to ensure that the telephone circuit is
disconnected the moment TOLR picks up to transmit TOL Code.

5.1.11 TOLR relay is made slow to release since its energising circuit is through the front
contact of TRSR released stick circuit as through the back contact of TRSR relay.

5.2 POSITION OF RELAYS IN RELAY RACK

TEPR CR1 CR2


PBPR BLR NR
TOLR TRSR ITPR
IR 2R 3R

5.3 DIFFERENT COLOUR CODE FOR INTERNAL WIRING

COLOUR DESCRIPTION

RED - Local Source (+)


BLUE - Local Source (-)
BLACK - Block Line Circuit
BROWN - Relays circuit for Reverser Control
YELLOW - Transmitter and Receiver circuit
GREEN - Relays and Lock magnet circuit
WHITE - Other circuit

6. CIRCUIT DESCRIPTIONS

6.1 NORMAL POSITION :

Normally, the Block handle is in center upright position, i.e. ‘Line Closed’ position.
The SM Key is IN, shunting (SH) key is IN, cancellation switch (S1) and push back
switch (S2) are in normal position. The TOL and time release indicator are white and
the Galvo indicator indicates zero current position. In this case, all the relays except
for ITPR and 1R are dropping away, with no current flowing in the block line and the
concerned signals and levers are in normal position (Fig. 1).

S/ Line Tokenless B/Instrument December’ 1999


CAMTECH/99/S/DAIDO/1.0 11

B1 24 V
10TPPR 5 15 1+ 2- 55 45 10TPPR
N1 24V
1 1TPR 2

B1 24V BTPR 10NBPR 3 4 10 10LCC 1+ 2- 56 46


N1 24V
N N N 1R
2 1 6 16

FIGURE 1

6.2 When a train is leaving A Station to B Station.

6.2.1 Turning the SM key to ON position at Station A completes a circuit. Push Button
PB1 is pressed to give CALL ATTENTION Bell code signal to B station. A DC (-
ve) current flows to B station in Line 1, to pick up the BLR at B station as per fig. 2
and fig. 3.

2 12 67 68 CHI SM PPB1 NR PBPR


B2 •
1 2 2 3 6A 5A 6D 2/5D

N2 3 13 1 R2 2 PB1 PB2 35 25
L1 (-)
2 3
20 OHM/2W 36 26
4 UF/160V L2 (+)

OUTGOING
FIGURE 2 CIRCUIT AT

4 UF/160V

1 2 35 25

L1

PBPR PB2 PB1 2- 1+ D2 26 PB1 NR 36 26


PBPR
BLR L2
4/7B 8B 3 2 3
BH-126 6A 5A 6D 2/5D
INCOMMING
CIRCUIT
AT B
FIGURE 3

S/ Line Tokenless B/Instrument December’ 1999


CAMTECH/99/S/DAIDO/1.0 12

Now with the BLR picking up, a current flows to ring the BELL as per fig. 4.

21
BELL
B24V 61 62 48 58 BLR N24
V
2A 1A 1 2
31
LOCAL CIRCUIT AT B

FIGURE 4

6.2.2 Upon receipt of a call attention at B station, SM inserts & turns SM key to IN. SM
presses to acknowledge call attention signal from Stn. A. The circuit is same as
described in Fig. 4 above.

6.2.3 Verbal communication for grant of Line Clear takes place between SM of Stn. A and
Stn. B over block telephone.

6.2.4 Push Button PB1 and PB2 are pressed simultaneously at Stn. A to send the IS LINE
CLEAR code. PBPR relay picks up as per fig. 5.

B24V 61 62 SM CR1 PB1 PB2 CR2 1R NR N24V


LOCAL
CIRCUIT
PBPR AT ‘A’
7D 8D 2B 1B 8B 4/7B

1 2

FIGURE 5

6.2.5 With the PBPR picking up at A the NR picks up at B station through the line circuit as
per fig. 6 & 8.
B2 2 12 67 68 CH1 PBPR 35 25

L1
OUTGOING
CIRCUIT AT
N2 3 13 1 R2 2 PPBPR ‘A’
36 26
L2
20 OHM/2W 1D 2/5D

FIGURE 6

S/ Line Tokenless B/Instrument December’ 1999


CAMTECH/99/S/DAIDO/1.0 13

TX
B 24 V 61 62 48 SM 1R PBPR PB2 TOLR 21
CR1
3 N24
4
4A 3A 4/7 D 3D 6A 2/5A 5D 6D 5D
58 1 6D
5 31
1

N 6 34
1
2
7 37
TO ISOLATION
TRANSFORMER
FIGURE 7 LINE SIDE

-2 +1 D1 18 8 PBPR 35
25
L1
NR
BY-126 8B 4/7 B

R3 / 470 ohm 2 watt

XY PBPR 36 26
LB L2
RD
6D 2/5 D

FIGURE 8

6.2.6 An FM code is generated due to picking up of PBPR at ‘A’, which connects power to
TX as per circuit in Fig. 7. The modulating frequency F1(85 Hz) is selected over
terminal TX-5 & TX-6 & modulated current flows to terminals 34, 37 to the line side
isolation transformer ( in this case the input circuit to RX of same station is isolated
by PBPR back contacts.

S/ Line Tokenless B/Instrument December’ 1999


CAMTECH/99/S/DAIDO/1.0 14

6.2.7 CR1 picks up at Stn. B on receipt of modulated current as per fig. 9.

TX
21
B24 V 61 62 48 SM 1R PBPR TOLR 41
42 3
BX
DY
N24
4
4A 3A 4/7 D 8D 5D 6D
58 1 7
31
CR2 1+ TELR

CR1 1 PBPR CR2


2
5 7A 8A

5B 6B

TO ISOLATE
FIGURE 9 TRANSFORMER
(LINE SIDE)

6.2.8 On getting the Bell & Galvo deflection at Stn. B, SM turns the block handle as far as
Y point, Lock magnet picks up to releases the Block Handle, which can be turned to
right position (Train Coming From position), as per fig. 11.

BELL
21
B 24V 61 62 48 58 NR
N24V

4A 3A 1 2
31
FIGURE 10 LOCAL CIRCUIT
AT ‘B’

S/ Line Tokenless B/Instrument December’ 1999


CAMTECH/99/S/DAIDO/1.0 15

B 24V 61 62 48 SM
S1 N1 S2 N1 TEPR TRSRT

58 R1 R2 5D 6D 4/7B 8B 1A 8/5A
21
NR 2 1
N 24V BX
4/7B 3B DY
M
31

CR1

2/5A 6A
FIGURE 11

6.2.9 While the block handle is being turned from one to another position, the circuit
controller contact (XY-RD-LB) of the handle in line circuit, in series with the relay
NR is opened between the Y&D points.
6.2.10 On opening of circuit controller contact in Line circuit, a resistance R3 to be added in
series to line circuit with a resultant reduction in the volume of line current ( which
remains substantially greater than the drop away current of NR). This cause a click on
Galvo needle at both stations, making it possible for SM of button pressing station to
know that the block handle has been turned. Then PB1 and PB2 at station A may be
released (The same procedure is followed in operating the handle as subsequently to
be described).

R3 (470 Ohm)

XY PBPR
LB •
RD
6D 2/5 D

6.2.11 After confirming that the Galvo needle has returned to zero position (indicating that A
station has stopped sending a code of signal), PB1 and PB2 are now simultaneously
pressed down at B station to send a code of signal to A station (Fig. II). PBPR relay
picks up as per fig. 5. With the PBPR picking up at A the NR picks up at B station
through the line circuit as per fig. 6 & 8.

6.2.12 An FM code is generated due to picking up of PBPR at ‘A’, which connects power to
TX as per circuit in Fig. 7. The modulating frequency F2(65 Hz) is selected over
terminal TX-5 & TX-7 & modulated current flows to terminals 34, 37 to the line side
isolation transformer

S/ Line Tokenless B/Instrument December’ 1999


CAMTECH/99/S/DAIDO/1.0 16

Local and outgoing circuit at ‘A’ (Fig. 12,13 & 14) local and incoming circuit at ‘B’
(Fig. 15 to 16).

LOCAL AND OUTGOING CIRCUITS AT B

B24V 61 62 SM K CR1 PB1 PB2 CR2 1R NR

N
7D 8D 2B PBPR 8B 4/7B 24 V
1B
1 2

FIGURE 12

S/ Line Tokenless B/Instrument December’ 1999


CAMTECH/99/S/DAIDO/1.0 17

B2 2 12 67 68 CH1 PBPR 35 25

L1 +
3B 4/7B

N2 3 13 R2 PPBPR 36 26
L2 -
20 OHM/2W 1D 2/5D

FIGURE 13

TX
B24 V 61 62 48 SM k 1R PBPR PB2 TOLR CR1 21
CR2
3 N24
4
4A 3A 4/7 D 3D 6A 2/5A 5D 6D 5D
58 1 1
6D
5 31
TELR
6 34
1
4 1
5 6 2R 2
7 37
R
2/5D 6D

TO LINE SIDE TRANS


FIGURE 14

S/ Line Tokenless B/Instrument December’ 1999


CAMTECH/99/S/DAIDO/1.0 18

LOCAL AND INCOMING CIRCUITS AT `A’


RX
B 24 V 61 62 48 SM k 1R PBPR TOLR 41 42 21
BX 3
DY N24
4
4A 3A 4/7 D 8D 5D 6D
58 31 34
7 TELR
8
4 1
CR2 1+ 2-
5 PBPR CR
CR2 2 37
7A 8A
7B 8B 6
5B 6B

TO LINE SIDE I.TRANS


FIGURE 15

18 8 1 35 25
L1
NR ‘X’
BY-126 8B 4/7 B

470 OHM/2W

R3

XY PBPR 36 26 L2
LB
RD
6D 2/5 D

FIGURE 16

BELL
21
B 24V 61 62 48 58 NR
N24V

4A 3A
31
FIGURE 17

BELL
21
B 24V 61 62 48 58 NR
N24V

4A 3A
31
FIGURE 17

S/ Line Tokenless B/Instrument December’ 1999


CAMTECH/99/S/DAIDO/1.0 19

6.2.13 On getting the Bell & Galvo deflection at Stn. B, SM turns the block handle from N
point to as far as the X point. At X point TRSR picks up & releases the lock on block
handle by picking up lock magnet as per fig. 17 & 18. TRSR remains UP till X/ and
later on sticks through its own front contact in LX/ position of Block handle. The
lock magnet is once again required to be in picked up condition to release the block
handle at check lock position at X/as per fig. 18 &19.
R1 C1 1000 UF/60V

21
61 62 48 58 3R CR2 NR ITPR 39
40
1+
B24 XX/ N24
TRSR
7B 8B
31
TRSR ITPR 37 38
/
LX
2/5 D 1D 2/5A
2A
FIGURE 18

48
B 24V SM 1R S1 S2 TRSR 2R 3R CR1 9 10 1 2
NR
XX

N 5D 6D 4/7B 5B 6B 7A 8A 1A 2/5A
M 3B 4B
2A 1A
58 CR
2
6A 2/5A
21

N24
FIGURE 19 31

6.2.14 When Block handle is in Train Going To position, i.e., Line clear is granted, Last stop
signal can be taken OFF by reversing the necessary controls like SM control on
signal, Lever/ switch/ push button operation etc. Reversing of any of above control
causes 1R to drop. An external relay ASR (Advance starter control relay) picks up as
per fig. 20. With ASR picking up, it possible to take OFF the Last Stop signal.

B3 24V 65 66 1R 2R TRSR S1 17 18 53 43 HSR

7D 6D N3 ASR N3
8B 4/7 B
12V
R3
FIGURE 20

6.2.15 Now the train can be sent into block section. On entry of train into block section, FVT
track relay drops causing 1TPR to drop, thus releasing the stick circuit of TRSR to
drop. Dropping of the TRSR causes the ASR to drop and replace the Last Stop signal
to ON automatically.

6.2.16 With the 1TPR drop, the circuit of TRSR breaks , which drops with a time lag, but
before its dropping, TOLR picks up as per fig. 21 through Path 1.

S/ Line Tokenless B/Instrument December’ 1999


CAMTECH/99/S/DAIDO/1.0 20

When TRSR drops after the time lag, TOLR sticks through Path 2. the indicator
TOLK and buzzer BZ1 are actuated through a branch of a contact LB, indicating a
train departure (TOL).
An additional Path 3 is provided to prevent the premature dropping of TOLR during
transition, when other station is transmitting TGT code & at the same time TOLR
picks up. It ensures that TOLR will not drop before transmission of TOL code.
A Normal contact of S2 switch is provided in the stick circuit to stop the transmission
of TOL code, during a failure of its transmission or acknowledgment to silence the
departure buzzer.

6.2.17 At this time the advance starter lever is restored to normal position.
CR2 NR 23 24
D3 BY-126
2B 1B 2/5B 1B LB

Path3
48 3R TRSR ITPR 13 14 21
1+
LB
B24 61 62 TOLR N24
7B 8B Path1
58 31

TRSR NR TOLR S2

2/5 D 6D 7D 8D 4B 3B N3 BZ1
R3
Path2
5

TOLK

XX’
YY’
FIGURE 21

S/ Line Tokenless B/Instrument December’ 1999


CAMTECH/99/S/DAIDO/1.0 21

B24 V 61 62 48 SM
TX
44 NR TOLR CR1 CR2
3 21
58 L 4
43 2/5D 6D 1A 2/ 5A 5D 6D 5D 6D N24
31
3R TOLR 4 3 TELR 31
5 (c) 34
L 6 1
6D 5D 3A 4/7
4 1
2 37
7

LINE SIDE I. TRANS


FIGURE 22

6.2.18 An FM code is generated due to picking up of TOLR at ‘A’, which connects power to
TX as per circuit in Fig. 22. The modulating frequency F2(65 Hz) is selected over
terminal TX-5 & TX-7 & modulated current flows to terminals 34, 37 to the line side
isolation transformer ( in this case the input circuit to RX of same station is isolated
by TOLR back contacts.

6.2.19 CR2 picks up at Stn. B on receipt of modulated code F2. The power to RX is
connected through B24-fuse (61-62)- Terminals (48-58)-2R(B)-R. TOLR picks up as
per fig. 24. With the TOLK and BZ1 operating through the same circuit as in A
station to give an indication of train departure. Local and incoming circuit at ‘B’ (Fig.
23).

S/ Line Tokenless B/Instrument December’ 1999


CAMTECH/99/S/DAIDO/1.0 22

B 24 V 61 62 48 RX
2R 45 46 21
3
4 N24 V
58 R
7A 8A 7
31 34
8 TELR

4 1
5 PBPR CR2
CR1 2
6 7A 8A 37
CR2
7B 8B
5B 6B

TO LINE - SIDE I.TANS


FIGURE 23

6.2.20 SM of Stn. B, on getting TOL buzzer, presses push button PB1 to acknowledge the
TOL code. PBPR at picks up as per fig. 5.

6.2.21 With the PBPR picking up, the NR picks up at Stn. B station through the line circuit as
per fig. 6 & 8. Picking up of NR causes TOLR to drop & stop the buzzer. As the
TOLK is a magnetic stick type, it maintains its TOL indication. (Refer Path 2 in fig.
21)

6.2.22 Dropping of TOLR at Stn. A, stops TOL code transmission by disconnecting power
to TX. As the TOLK is a magnetic stick type, it maintains its TOL indication.

6.2.23 CR2 drops at Stn. B & stops the buzzer .

48

B24 61 62
3R CR2 NR 11 12 21
1+ 2-

58 2B 1B 2/5B 6B
RD TOLR N24
7B 8B

D3 BY-126
31
01 UF/100 V
TOLR S2
TRSR NR

BZ1
2/5 D 6D 7D 8D 4B N3
R3

1 2

7A 8A 470 OHM/2W

47 48 R5
XX’ TOLR

YY’
220 OHM/2W

FIGURE 24
PBPR

2A
61 62 42 SM CR1 PB1 PB2
TOLR 19 20
S/ Line Tokenless B/Instrument December’ 1999
B24 61 62 7D 8D RD PBPR
1 2
1
CAMTECH/99/S/DAIDO/1.0 23

6.2.24 A bell code for train departure is issued from A station and a answering signal is
issued from B station. After departure of train bell code is exchanged.

6.2.25 At Stn. B, Reception signals are taken OFF. As soon as any of the control pertaining
to reception signal is disturbed from its Normal position, 1R drops. Where SM’s
control is not provided on reception signals, 1R back contact, in HSR and ASR
circuit, is looped in instrument. The HSR picks up (Fig. 26). The home operates in the
same way as advance starter.

B3 12V 65 66 1R 2R TRSR S1 N4 35 36 54 44
XY
RD
7D 6D
7D 8D 4/7D 8D
R4
LA
ASR

N3 12 HSR
2

FIGURE 26
6.2.26 On arrival of train at Stn. B, AT & BT tracks operate & sense the direction of travel
of train. 2R picks up (Fig. 27) & sticks over LX/-RY. With the relay 2R picking up
the HSR drops away and the home signal is automatically restored to normal position.
At the same time a Buzzer BZ2 sounds to announce the train arrival. The buzzer can
be stopped by restoring the SM slide or Home signal controls to their Normal position
as per fig. 27.

S/ Line Tokenless B/Instrument December’ 1999


CAMTECH/99/S/DAIDO/1.0 24

R
OUTER
4
2
R R TAR

B24 61 62 48 52 7 17 TAR 15 16 21
N24
XX’
Y’ 2
2R 31
2B 1B

HOME SM 3 4
SLIDE

R BZ2

FIGURE 27

6.2.27 Stn. B verifies the e complete arrival of train & sends Train Out Of Section signal to
Stn. A. who in turn replies to Stn. B by similar signal. Stn. B presses PB1 and PB2
simultaneously to transmit Line closed code (F1). PBPR picks up at ‘B’ station. ( see
Fig. 5).

6.2.28 An FM code is generated due to picking up of PBPR at Stn. B, which connects power
to TX as per circuit in Fig. 7. The modulating frequency F1(85 Hz) is selected over
terminal TX-5 & TX-6 & modulated current flows to terminals 34, 37 to the line side
isolation transformer.

S/ Line Tokenless B/Instrument December’ 1999


CAMTECH/99/S/DAIDO/1.0 25

6.2.29 With the PBPR picking up at Stn. B the NR picks up at Stn. A through the line circuit
as per fig. 6 & 8. CR1 picks up at Stn. A on receipt of modulated current as per fig.
9.

B 24 42 SM

1R 1

3A 4A TX
44 NR TOLR CR1
CR2 21
3 4
43 2/5D 6D 1A 2/ 5A 5D 6D 5D 6D N24
31
TELR
34
5 (c)
2R 4 1
6 2
R
37
2/5D 6D TO
I. TRANS

FIGURE 28

24 V 61 62 48 SM 1R PBPR
BX
DY
4A 3A 4 2D 5D 6D 41 42
58 1
RX
41
3 4

31
TELR
7 1

4 CR2
CR2 2
8
7B AB
CR1 TOLR
TO TRANS
FIGURE 29 5B 6B

S/ Line Tokenless B/Instrument December’ 1999


CAMTECH/99/S/DAIDO/1.0 26

B 24V 48 SM 1R
S1 N1 S2 N2 TEPR TRSR CR1 7 8 2 NR 21
B
DY
N 5D 6D 4/7B 5B 6B 7A 8A 1A 2/5A
M 5B 4/7B
61 62 2A 1A
58
CR1

FIGURE 30 6A
21

47 48 1 R5 2 N24
XX’
YY’
31
220 OHM/2W TOLK

FIGURE 31

With the NR and CR1 picking up Lock magnet is energised at B point of block handle as per
fig. 30, making it possible to restore the handle to Line Closed position. TOLK
release coil is energised to restore it Normal as per fig. 31.

6.2.30 SM at Stn. A presses PB1 and PB2 simultaneously to transmit Line closed code (F1).
PBPR picks up at Stn. A as per fig. 5.

6.2.31 An FM code is generated due to picking up of PBPR at Stn. A, which connects power
to TX as per circuit in Fig. 7. The modulating frequency F1(85 Hz) is selected over
terminal TX-5 & TX-6 & modulated current flows to terminals 34, 37 to the line side
isolation transformer.

6.2.32 With the PBPR picking up at Stn. A, NR picks up at Stn. B through the line circuit as
per fig. 6 & 8. CR1 picks up at Stn. B on receipt of modulated current as per fig. 9.

With the NR and CR1 picking up Lock magnet is energised at B point of block
handle as per fig. 30, making it possible to restore the handle to Line Closed position.
TOLK release coil is energised to restore it Normal as per fig. 31.

The same procedure is followed when a train leaves B station from A station.

S/ Line Tokenless B/Instrument December’ 1999


CAMTECH/99/S/DAIDO/1.0 27

6.3 CANCELLATION OF “LINE CLEAR” BEFORE A TRAIN ENTERS THE


BLOCK SECTION :

6.3.1 When a line clear has been taken by Stn. A, i.e., Block Handle in Train Going To, & it
becomes necessary to cancel the Line Clear, the cancellation switch S1 is put to reverse
position at Stn. The following sequence is observed:

• External relay ASR drops


• S1 counter increments to next higher number.
• All controls are to be replaced to Normal so as to pick up 1R
• Timer relay times up as per fig. 32
• On expiry of 120 seconds TEPR picks up
• TEK appears Green with wording “FREE”
• 3R picks up.

An advice for cancellation of Line clear is sent By SM at Stn. A to SM of Stn. B

6.3.2 SM at Stn. A presses PB1 and PB2 simultaneously to transmit Line closed code (F1).
PBPR picks up at Stn. A as per fig. 5.

6.3.3 An FM code is generated due to picking up of PBPR at Stn. A, which connects power to
TX as per circuit in Fig. 7. The modulating frequency F1(85 Hz) is selected over
terminal TX-5 & TX-6 & modulated current flows to terminals 34, 37 to the line side
isolation transformer.

6.3.4 With the PBPR picking up at Stn. A, NR picks up at Stn. B through the line circuit as
per fig. 6 & 8. CR1 picks up at Stn. B on receipt of modulated current as per fig. 9.

With the NR and CR1 picking up Lock magnet is energised at D point of block handle
as per fig. 30, making it possible to restore the handle to Line Closed position.

6.3.5 Similarly Stn. B takes action to bring the instrument of Stn. A to Line Closed. SM at
Stn. B presses PB1 and PB2 simultaneously to transmit Line closed code (F1). PBPR
picks up at Stn. B as per fig. 5.

An FM code is generated due to picking up of PBPR at Stn. B, which connects power


to TX as per circuit in Fig. 7. The modulating frequency F1(85 Hz) is selected over
terminal TX-5 & TX-6 & modulated current flows to terminals 34, 37 to the line side
isolation transformer.

S/ Line Tokenless B/Instrument December’ 1999


CAMTECH/99/S/DAIDO/1.0 28

6.3.6 With the PBPR picking up at Stn. B, NR picks up at Stn. A through the line circuit as
per fig. 6 & 8. CR1 picks up at Stn. A on receipt of modulated current as per fig. 9.

With the NR and CR1 picking up Lock magnet is energised at B point of block handle
as per fig. 30, making it possible to restore the handle to Line Closed position. When
Stn A turns block handle to Line Closed, TEK changes to White.

INPUT OUTPUT

B 24V SM 1R S1 N2 TIMER
2A 1A TRSR 3R 1 S1 2
61 62 58 N24
2A 1A 7D 8D
1 TER COUNTER COM
S1 2A 1A TEPR
TEPR 30
29
R1
4A 4B 3R
3R LX

3R 2B 1B
1 2
TEK
48 38

FIGURE 32

TX
IR PBPR PB2 TOLR CR1
B 24V 43 SM 21
3 4
4A 3A 4/7D 3D 1 6A 2/ 5A 5D N24
61 62 58 6D 31
TELR
34
5 (c)
4 1
TOLR 3R 6 2
L
4/7A 8A 2/5A 1A
37 TO
I. TRANS

FIGURE 33

6.4 PUSH BACK OPERATION :

When a train sent from Stn. A to Stn. B has entered the Block section, but due to
unavoidable circumstances, it has to be pushed back to departure Stn. A, it is called
PUSH BACK OPERATION .

6.4.1 The block handle at Stn. A and Stn. B are in left position (Train Going To) and right
position (Train Coming From) respectively. TOL indicator indicates that train in to
block section.

S/ Line Tokenless B/Instrument December’ 1999


CAMTECH/99/S/DAIDO/1.0 29

6.4.2 SM at Stn. A push back switch S2 to reverse position, actuates the counter S2 as per fig.
34.
Reception signals are taken OFF. As soon as any of the control pertaining to reception
signal is disturbed from its Normal position, 1R drops. HSR picks up as per fig. 26.

6.4.3 On arrival of train at Stn. B, AT & BT tracks operate & sense the direction of travel of
train. 2R picks up (Fig. 27) & sticks over LX/-RY. With the relay 2R picking up the
HSR drops away and the home signal is automatically restored to normal position. At
the same time a Buzzer BZ2 sounds to announce the train arrival. The buzzer can be
stopped by restoring the SM slide or Home signal controls to their Normal position as
per fig. 27.

6.4.4 Stn. A verifies the complete arrival of train. An advice for push back operation is sent
By SM at Stn. A to SM of Stn. B

6.4.5 SM at Stn. A presses PB1 and PB2 simultaneously to transmit Line closed code (F1).
PBPR picks up at Stn. A as per fig. 5.

6.4.6 An FM code is generated due to picking up of PBPR at Stn. A, which connects power
to TX as per circuit in Fig. 7. The modulating frequency F1(85 Hz) is selected over
terminal TX-5 & TX-6 & modulated current flows to terminals 34, 37 to the line side
isolation transformer.

6.4.7 With the PBPR picking up at Stn. A, NR picks up at Stn. B through the line circuit as
per fig. 6 & 8. CR1 picks up at Stn. B on receipt of modulated current as per fig. 9.

With the NR and CR1 picking up Lock magnet is energised at D point of block handle
as per fig. 30, making it possible to restore the handle to Line Closed position. TOL
indicator changes to White during turning of handle from Train Coming From to Line
Closed.

6.4.8 Similarly Stn. B takes action to bring the instrument of Stn. A to Line Closed. SM at
Stn. B presses PB1 and PB2 simultaneously to transmit Line closed code (F1). PBPR
picks up at Stn. B as per fig. 5.

An FM code is generated due to picking up of PBPR at Stn. B, which connects power


to TX as per circuit in Fig. 7. The modulating frequency F1(85 Hz) is selected over
terminal TX-5 & TX-6 & modulated current flows to terminals 34, 37 to the line side
isolation transformer.

6.4.9 With the PBPR picking up at Stn. B, NR picks up at Stn. A through the line circuit as
per fig. 6 & 8. CR1 picks up at Stn. A on receipt of modulated current as per fig. 9.

With the NR and CR1 picking up Lock magnet is energised at B point of block handle
as per fig. 30, making it possible to restore the handle to Line Closed position. TOL
indicator changes to White during turning of handle from Train Coming From to Line
Closed.

48 SM S2
N2
S/ Line
B24 61 Tokenless
62 B/Instrument
C2 December’ 1999
58 1
R2
1 S2 2 29 30
CAMTECH/99/S/DAIDO/1.0 30

B 24V 48 SM IR PBPR PB2

4A 3A 4/7D 3D
61 62 58 1 1
TX

TOLR CR1 CR2 21


3 4
6A 2/3A 5D 6D 5D N24
31
6D
TELR
34
5 (c)
4 1
TOLR 3R
6 2
L
37
4/7A 8A 2/5A 6A 1A
TO I. TRANS

FIGURE 35

(D) WHEN A TRAIN SHUNTING (AT ‘A’ STATION)

The Block handles are in Line Closed position at both stations ‘A’ & ‘B’, or Stn. A in
Train Going To & Stn. B in Train Coming From.

A station calls ‘B’ station to obtain authorization over the telephone.

SM at Stn. A inserts SM key & turns IN. SHUNT key is taken out & handed over to
the driver of a shunting train. The Block handle is locked at the time. The SM key is
taken out.

On completion of shunting operation, Shunt key is taken back from driver of train. SM
inserts SM key & turns to IN, thereafter inserts SHUNT key and turns IN. The advice is
sent to Stn. B over the telephone to that effect.

S/ Line Tokenless B/Instrument December’ 1999


CAMTECH/99/S/DAIDO/1.0 31

(E) TELEPHONE CIRCUIT :

While modulated current F1 to F2 is being transmitted or received, telephone circuit is


isolated from power line.

While telephone is used, transmitter and receiver are isolated from line. To explain in
detail telephone relay TELR is inserted in series connection with relay. CR1 (B)
CR2(B) and TOLR (B) in the circuit fig. 36. Also TELR(F) is connected in series in the
telephone circuit, Thus telephone circuit is isolated from signal circuit. Where
modulated current is transmitted and received by TELR which is inserted between
signal circuit and Transmitter/Receiver, Transmitter/Receiver is isolated form signal
line which telephone is used.

7. TRANSMITTER AND RECEIVER

7.1 Operating Parameters

Transmitter

Item Rating Tolerance


Transmitting frequency 1800 Hz or 2700 Hz + 2%
Transmitting output 1 mW, 3 mW, 5 mW, +10%,
adjustable -5%
Output impedance 600 Ohms, 1120 Ohms + 2%
adjustable
Modulation system Frequency modulation
Modulation frequency 65 Hz or 85 Hz + 1.5 Hz
Power consumption 1.2 watts or less at 24 V DC
Input power supply 24 V DC + 20%
Shift frequency 160 Hz + 15%

Receiver

Item Rating Tolerance


Receiving frequency 1800 Hz or 2700 Hz +2%
Level range 0 to 28 dB In step of 2
dB or less
Max. noise allowance -44 dBm + 2%
Input impedance 600 ohms, 1120
ohms adjustable
Relay output voltage 24V DC or above 21V min.
Power consumption 8 watt or less at 24 V DC
Input power supply 24V DC + 20%
Sense level for receiving less than - 29 dBm
No Sense level for More than - 38 dBm
receiving
Shift frequency 160 Hz. + 15 %

7.2 Connection Terminals & Test Blocks

7.2.1 Transmitter

S/ Line Tokenless B/Instrument December’ 1999


CAMTECH/99/S/DAIDO/1.0 32

Connection Terminals

It have 8 fixed terminals. Serial Nos. and connections are as below:

Terminal Nos. Connections


1&2 Out put
3 Positive DC input
4 Negative DC input
5 Common
6 85 Hz.
7 65 Hz.
8 Spare

Test Blocks

Test blocks are provided at the back side of the transmitter with a cover and seating
arrangements.

1. 24V DC supply
2. Regulated voltage
3. Modulated frequency 65 Hz & 85 Hz
4. Carrier frequency 1800 Hz. or 2700 Hz.
5. TX output

7.2.2 Receiver

Connection Terminals

It have 8 fixed terminals. Serial Nos. and connections are as below:

Terminals Connections
1&2 Input
3 Positive DC input
4 Negative DC input
5&6 Output for CR2 relay
7&8 Output for CR1 relay

S/ Line Tokenless B/Instrument December’ 1999


CAMTECH/99/S/DAIDO/1.0 33

Test Blocks

Test blocks are provided at the back side of the receiver with a cover and seating
arrangements.

1. 24V DC supply
2. Regulated DC supply
3. Input
4. Demodulated Signal
5. Input to CR1
6. Input to CR2

7.3 Trouble Shooting Method for Transmitter & Receiver


Sr. SYMPTOM ACTION TO BE TAKEN
1. No output from Check if the supply is OK by
receiver. pressing push to make switch in
transmitter and receiver. If power ON
indicators are glowing with red LED
it means power supply is OK. If the
red LED does not glow, check the
fuse. If the fuses are missing/blown,
replace it.
2 Power OK, Press the PTM switch which is on the
LEDs OK but front panel and see if the level
relay does not indicator green LED glows or not. If
pick up. glows that means relay driving signal
is OK & the problem is with
respective relay, so replace it and get
the desired result.

If the level indicator Amber LED


glows:

The relay driving signal is missing,


check the following:

Input to the RX between 5&6 (+10V


to +13V PP) between 7&8 (+1.5V to
+ 2.5V PP), between 9&10 or 11&12
(+21.6V to +26V PP).
If the above voltage signals are not
regular/proper, open the cabinet and
follow the signal flow and check the
voltages.

S/ Line Tokenless B/Instrument December’ 1999


CAMTECH/99/S/DAIDO/1.0 34

8. EARTHING

„ A separate earth should be provided for each block instrument.

„ The resistance of earth shall not exceed 10 Ohm.

„ The earth shall be located on lower level soft ground far from underground cable, water
and gas pipes.

9. SAFETY CHECK

• Ensure that double lock is provided and seal is intact.

• Try to operate the instrument without cooperation i.e. without receipt of functional
code, it shall not be possible to turn the block handle from Line Closed to Train Going
To or Train Coming From position.

• On receipt of TGT code, turn block handle from Line Closed towards Train Going to
& stop midway. Disconnect Line & try to turn the handle further. It shall lock in check
lock position. Ensure armature of electric lock on block handle is force dropped in
check lock notch and the block handle can not be turned to Train Going to position.

• With a train in Block Section, try to bring the block handle to Line closed with &
without cooperation from other station, it shall not be possible to turn the block handle
to line closed position. The Block handle should remain locked in last operated
position.

For Last Stop Signal :

• Try to take OFF the Last Stop Signal without taking line clear (“L” position of block
handle), the signal should not clear.

• Shunt the FVT track, the Last Stop Signal shall go back to danger automatically.

• It is not possible to take OFF the Last Stop Signal again unless a fresh line clear is
obtained.

SUGGESTION :

a) Removal of Filter unit & X, Y relays in RE area.

b) Disconnect the two condensers of the Block Filter unit

c) The rare gas lightning arrestor should be replaced with MOVR.

10. MAINTENANCE

S/ Line Tokenless B/Instrument December’ 1999


CAMTECH/99/S/DAIDO/1.0 35

10.1 Periodicity of Overhauling

A thorough periodical overhauling in Workshop is necessary and the period shall not
exceed 7 years.

10.2 Maintenance

The following points are to be kept in mind while doing maintenance for reliable
working of block instrument.

• The local battery voltage at the instrument terminals on load should not be below 24
volts. Secondary cells of sufficient capacity may be used as the maximum working
current per instrument is about 2 Amps ( when thermal time element relay is used) &
0.6 Amp (when Electronic time element relay is used)

• The upper limit of local battery on load should not exceed 29 V as it may affect the
Zener diode working.

• The line battery shall be capable of circulate 110 mA in Line circuit measured at code
receiving station.

• The line current shall be measured both at the transmitting end and the receiving end.
There shall not be an appreciable variation.
• Separate battery or DC-DC converter shall be provided for line circuit of each block
instrument. Whenever the line battery/ DC-DC converter is changed, the line current
should be checked.

• ??Whenever old type condenser units are changed ( with 4 BA fixing screw ), ensure
that the other interconnected instrument condenser unit is also changed to the same type
since the values are different.

• Care shall be taken to ensure that the relay jack boards and relays are clean and dust
free.

• During the periodical Maintenance/ Inspection, the charger shall be switched “OFF ”
and the working of the relays shall be observed for few operations. The terminal
voltage should be monitored during the code transmission in order to ensure the
condition of the battery.

• Whenever the instrument fails, interchanging of relays and units shall not be restored
to, without ascertaining the actual cause and this change may be effected only if it is
warranted.

• While plugging in relays/ units, excessive force should not be exerted as it may affect
the jack board clips.

11. TROUBLE SHOOTING

Fault Cause/ Rectification

S/ Line Tokenless B/Instrument December’ 1999


CAMTECH/99/S/DAIDO/1.0 36

Sr. Condition
no.
1. Bell beats 1. Line battery low or disconnection at
failed from station ‘A’.
Stn. ’A’ to 2. PB1 push button contact develops
Stn. B disconnection at Stn A.
3. Line is open/short circuit or offering
high resistance.
4. PB1 button contact develops
disconnection at Stn. B.
5. Local battery disconnection or weak at
Stn. B. It shall be 24 V.
6. BLR relay not picking up at Stn. ‘B’
when PB1 pressed at Stn. A due to
some fault.
7. Diode, in series with BLR/ NR
punctured.
8. Relay contacts NR, BLR, PBPR
offering high resistance at Stn. A &
Stn. B.
9. When PB1 is pressed at Stn. A, BLR
shall pick up at Stn. B. Suppose BLR
is not picking up, check up the
incoming line voltage at Stn. B across
L1 & L2(Terminal No. 25 & 26
working voltage 24 Volt. If voltage is
available and relay is not picking up,
check for working current ( 110 mA.).

S/ Line Tokenless B/Instrument December’ 1999


CAMTECH/99/S/DAIDO/1.0 37

Fault Cause/ Rectification


Sr. Condition
no.
2. Failure of Ensure the following:
Lock 1. SM’s key ‘ON’ contact is making.
Magnet. 2. Relay 1R front contact is making
(checking up the slides/ levers/ block
signals ‘ON’).
3. TER cold contact in TER.
4. Switch S1 & switch S2 in ‘N’.
5. Back contact of relay 2R & relay 3R is
making.
6. Relay TRSR front contact is making in
case of turning the block handle from
‘N’ to ‘L’ including check lock.
7. Relay TRSR back contact is making in
case of turning the block handle from
‘N’ to ‘R’, ‘T’ to ‘N’, ‘L’ to ‘N’.
8. Block handle contact XX/, in case of
turning block handle from ‘N’ to ‘L’.
9. Block handle contact BDY, in case of
turning block handle from ‘N’ to ‘R’,
‘R’ to ‘N’, ‘L’ to ‘N’ respectively..
10. Front contact of relay NR is making.
11. Front contact of relay CR2 is making
for turning the Block handle from ‘N’
to ‘L’.
12. Front contact of relay CR1 is making
for turning the Block handle from ‘N’
to ‘R’, ‘R’ to ‘N’, ‘L’ to ‘N’.
13. Local battery voltage 24 Volts.
14. Ensure cross protection contact viz.
CR1 & CR2 breaking during the
respective operations.

S/ Line Tokenless B/Instrument December’ 1999


CAMTECH/99/S/DAIDO/1.0 38

Fault Cause/ Rectification


Sr. Condition
no.
3. Failure of 1. Ensure voltage of location battery
relay 1R 24 Volt.
2. All block signals at ‘ON’ concerned
levers/slides normal.
4. Failure of Ensure
relay 2R a. TAR pickup while train arrives. If
TAR is not pickup, check TAR circuit.
b. TAR front contact making properly.
c. Stick circuit is taken through block
handle contact LB/RD, check the block
handle contacts.
4. Failure of Check TER circuit, SM’s key contact,
relay 3R. Switch S1, ‘R’ contact, TER hot contact,
TEPR circuit, TER cold contact, Block
handle LX contact.
5. Failure of Check the PB1 & PB2 contact of push
PBPR relay. button, 1R front contacts. When Block
handle is in (RD) check up Block handle
contact, TOLR front contact, check SM’s
key contacts.
6. Failure of 1. Check for CR2 front contacts NR front
relay TRSR contacts, 1 TPR front contacts.
at train 2. Block handle contracts XX/, LX.
sending 3. Local voltage 24V(Including fuses
end ‘A’ etc.)
4. 3R back contacts.
5. If stick feed is not available, check
TRSR front contacts, make before
break contacts of XX//LX/.
6. Check the condenser across TRSR.

S/ Line Tokenless B/Instrument December’ 1999


CAMTECH/99/S/DAIDO/1.0 39

Fault Cause/ Rectification


Sr. Condition
no.
7. Failure of A. Pickup circuit for TOLR.
TOLR at
‘A’ i) Ensure TRSR show to release feature
(condenser)-(slow to release)
ii) Ensure TRSR front contact making.
iii) Ensure ITPR back contact making.
iv) Ensure Block handle contacts LB
making.
v) Ensure 3R back contacts making.

B. Ensure stick feed to TOLR.

i) Ensure S2 normal contacts making.


ii) Ensure TOLR front contacts making.
iii) NR back contacts making.
iv) TRSR back contacts making.
v) 3R back contacts making.
8. Failure of i) Ensure CR2 front contacts making.
TOLR at ii) Ensure NR back contact making.
Stn. ‘B’. iii) Ensure block handle RD contact
making.
iv) Ensure local voltage 24 Volt.
9. Failure of Ensure at code receiving end.
CR1/ CR2 If CR1 & CR2 are picking up. Check at
the receiver test terminals for (a) 24V DC
input to receiver (b) FM input. If DC input
is absent check the block handle contact
XY/LB/RD. If FM input is present
checkup the level. If the level is OK,
adjust the attenuator. If the level is low at
the TX, check the level low/high/medium.
Fault Cause/ Rectification
Sr. Condition
no.
If the level is OK, check the frequency for
CR1 carrier frequency 1800/2700 Hz./
Modulated frequency 85 Hz, for CR2
carrier frequency 1800/2700 Hz./
Modulated frequency 65 Hz. If the level
and frequency OK check the FM input
path in to RX. At the TX end check DC
input, TX freq. Loop circuit for FM, which
includes block handle contacts N, R & L.
10. Failure of Check for ASR:- TRSR front contacts, S1
Last Stop normal contact, LA contact of block
Signal handle, 1R back contacts.
circuit.

S/ Line Tokenless B/Instrument December’ 1999


CAMTECH/99/S/DAIDO/1.0 40

11 Failure of Check for HSR circuit:- S1 normal


Home contacts & RY/ LB contact or ( S2 reverse
Signal contacts & L of block handle for push
back operation).
12 Premature Stick feed to TRSR cut off due to ITPR
TOL momentarily dropped due to unknown
reason before train enters into section.
Check the TPR circuit, if OK, check track
circuit & block handle’s LX/ contact .
13 Normal TRSR dropped due to momentary
cancellation dropping of 1 TPR or 3R circuit. LX/
not contact not making. Check S1 switch R
possible. contacts in TER circuit and 3R circuit are
making properly. Check 1R front contact
and SM’s key contact.

„„„„„

S/ Line Tokenless B/Instrument December’ 1999

You might also like