Client xxxx

Project Building xxxx Renovation


Location xxxx
Project# xxxx
Proj.Area Penthouse
HVAC Engineering Dept. Form By: xxxx
Check By:
Determine Expansion Tank Size: Calc.By:
Rev. By:
Application: Hot Water System 2
3
Known Piping Quantities

Location Pipe Size Linear Feet Material Gallons of Equipment Quantity Gallons / Total Gallons of
(Inches) Water Unit Water
Penthouse and 1st Floor 0.75 502 Type L 13 HX-1 1 20 20
1 214 Type L 9 RHC's 25 2 50
1.25 195 Type L 13 P-1-1 1 2 2
1.5 523 Type L 48 P-1-2 1 2 2
2 76 Type L 12 UH-1-1 1 5 5
2.5 0 Schedule 40 0 UH-1-2 1 5 5
3 139 Schedule 40 53 UH-1-3 1 5 5
4 Schedule 40 0 UH-1-4 1 2 2
6 Schedule 40 0 AS-1-1 1 10 10
8 Schedule 40 0 CF-1-1 1 5 5
10 Schedule 40 0
12 SW (.375" Wall) 0
14 SW (.375" Wall) 0
16 SW (.375" Wall) 0
18 SW (.375" Wall) 0
20 SW (.375" Wall) 0
24 SW (.375" Wall) 0
TOTAL 148 TOTAL 106

Volume of Water in System, Vs 254 gallons


Lower Temperature, T1 50 Deg. F
Higher Temperature, T2 180 Deg. F
Atomspheric Pressure, Pa 14.70 psia
Abs. Pressure @ T1, P1 24.70 psia, Lower Pressure
Abs. Pressure @ T2, P2 59.38 psia, Higher Pressure
Specific Volume of Water @ T10.16020 Cu. Ft. / lb
Specific Volume of Water @ T20.16510 Cu. Ft. / lb
Linear Coefficient of Expansion
0.0000065 In / in Deg F for steel
Delta T (T2-T1) 130 Deg. F
Volume of Expansion Tank 20.53 gallons

EXPANSION TANK SCHEDULE

CLOSED EXPANSION TANK (FURNISHED AND INSTALLED BY CONTRACTOR)


EQUIP. LOCATIONMANUF./ TYPE CAPACITY SERVICE OPER. WT. REMARKS/NOTES
NUMBER MODEL No. (GAL) (LBS.)

ET-1 PENTHOUSE B&G/30 NON-DIAPHRAGM 25 HOT WATER 75 Provide Airtrol Fitting, ATF-12