You are on page 1of 23

Installation Total

S.No. Description. Unit. Quantity


Rate Amount

SUBHEAD 1: H.T. SUB STATION. 0

1.01 HT Panel (ESS-1 FOR REGIONAL CANCER HOSPITAL , MEDICAL COLLEGE, NURSING
0
COLLEGE)

Supply, erection, testing and commissioning of 4 panel, 800 A ,11 kV, 3 Phase, 50 Hz., metal
clad, dead front, 26.3 KA rupturing capacity Vacuum Circuit Breaker Incoming & Outgoings as
0
per the detailed specifications and drawings including connections etc. including door
interlocking and expendable as required.

A. INCOMER : 0
i) 1 No. VCB having following 0

1 No. 800A, 11kV, 3 Phase, 50Hz., metal clad, dead front, 26.3 KA rupturing capacity, Fully
0
Draw out type, Vacuum Circuit Breaker (VCB)

1 set of 11kV/110V Potential Transformers with HRC fuses for metering & protection. 0

1 Set of Phase indicating lamps with HRC fuses 0

1 No. Digital voltmeter with selector Switch . 0

1 set of indicating lamps to indicate OPEN, CLOSE, TRIP, SPRING CHARGED, TRIP
0
CIRCUIT HEALTHY

Push button for ON, OFF,TRIP&TRIP circuit healthy 0


1 set of 500/5-5A Current Transformer for metering and protection. 0

1 No. digital Ammeter with selector switch to select R, Y or B phase current. 0

1 Set of Microcontroller based numerical relay having 4 element relay (3O/C+1E/F). Relay
0
should have display of phase current and trip history.

Digital frequency meter, Digital Tri vector meter.

I Set of undervoltage relay and Overvoltage relay. 0


Trip circuit supervision relay, Auxiliary relays with shunt trip coil (WTI & Door open trip). 0

I No. Master Trip relay. 0

1 No. Digital Power factor meter. 0

8 window annunciator. 0

1 no. Phase reversal Relay. 0


0
B. BUSBARS : 0
11kV, 800 Amps 26.3 KA rupturing Capacity, Three Phase busbars of copper. 0
0
C. OUTGOINGS : 0
3 No. VCB each having following 0

1 No. 800A, 11kV, 3 Phase, 50Hz., metal clad, dead front, 26.3KA rupturing capacity, Fully
0
Drawout type, Vacuum Circuit Breaker (VCB)

1 set of 11kV/110V-110 V Potential Transformers with HRC fuses for metering & protection. 0

1 Set of Phase indicating lamps with HRC fuses. 0

1 No. Digital voltmeter. 0

1 set of indicating lamps to indicate OPEN, CLOSE, TRIP, SPRING CHARGED, TRIP
0
CIRCUIT HEALTHY.

Push button for ON, OFF,TRIP&TRIP circuit healthy. 0

1 No. Digital ammeter with selector switch and one set of C.T 150/5-5 A, For measurement &
0
protection.

1 Set of Microcontroller based numerical relay having 4 element relay (3O/C+1E/F). Relay
0
should have display of phase current and trip history.

Digital frequency meter,Digital Tri vector meter. 0

I Set of undervoltage relay and Overvoltage relay. 0

Trip circuit supervision relay,Auxiliary relays with shunt trip coil. 0

8 window annunciator. 0

I No. Master Trip relay. 0

1 No. Digital Power factor meter. 0

HT Panel as mentioned above Set 1 42,000 42,000.00

0 -
1.02 HT Panel :(ESS-2) (HOSTEL BLOCKS & DINING BLOCK) 0 -
-
Supply, erection, testing and commissioning of 3 panel, 630 A ,11 kV, 3 Phase, 50 Hz., metal
clad, dead front, 26.3 KA rupturing capacity Vacuum Circuit Breaker Incoming & Outgoings as
0
per the detailed specifications and drawings including connections etc. including door
interlocking and expendable as required.

A. -
INCOMER : 0
i) 1 No. VCB having following 0 -

1 No. 630 A, 11kV, 3 Phase, 50Hz., metal clad, dead front, 26.3 KA rupturing capacity, Fully -
0
Draw out type, Vacuum Circuit Breaker (VCB)
1 set of 11kV/110V -110 V Potential Transformers with HRC fuses for metering & protection. 0 -

1 Set of Phase indicating lamps with HRC fuses. 0 -

1 No. Digital voltmeter. 0 -


-
1 set of indicating lamps to indicate OPEN, CLOSE, TRIP, SPRING CHARGED, TRIP
0
CIRCUIT HEALTHY.

Push button for ON, OFF & TRIP circuit healthy. 0 -

1 set of 150/5-5A Current Transformer for metering and protection. 0 -

1 No. digital Ammeter with selector switch to select R, Y or B phase current. 0 -

1 Set of Microcontroller based numerical relay having 4 element relay (3O/C+1E/F). Relay -
0
should have display of phase current and trip history.
-
Digital frequency meter, Digital Tri vector meter. 0

I Set of undervoltage relay and Overvoltage relay. 0 -

Trip circuit supervision relay, Auxiliary relays with shunt trip coil (WTI & Door open trip). 0 -

I No. Master Trip relay. 0 -

1 No. Digital Power factor meter. 0 -

8 window annunciator. 0 -

1 no. Phase reversal Relay. 0 -

0 -
B. BUSBARS : 0 -

11kV, 630 Amps 26.3 KA rupturing Capacity Three Phase busbars of copper. 0 -

0 -
C. OUTGOINGS : 0 -
2 No. VCB each having following 0 -
1 No. 630A, 11kV, 3 Phase, 50Hz., metal clad, dead front, 26.3KA rupturing capacity, Fully -
0
Drawout type, Vacuum Circuit Breaker (VCB)
1 set of 11kV/110V-110 V Potential Transformers with HRC fuses for metering & protection. -
1 Set of Phase indicating lamps with HRC fuses. -
1 No. Digital voltmeter. -
1 set of indicating lamps to indicate OPEN, CLOSE, TRIP, SPRING CHARGED, TRIP -
CIRCUIT HEALTHY.
Push button for ON, OFF,TRIP&TRIP circuit healthy. -

1 No. Digital ammeter with selector switch and one set of C.T 75/5-5 A, For measurement & -
protection.
-
1 Set of Microcontroller based numerical relay having 4 element relay (3O/C+1E/F). Relay
should have display of phase current and trip history.

Digital frequency meter,Digital Tri vector meter. -

-
I Set of undervoltage relay and Overvoltage relay.

Trip circuit supervision relay,Auxiliary relays with shunt trip coil. -

8 window annunciator. -

I No. Master Trip relay. -


1 No. Digital Power factor meter. -
-

HT Panel as mentioned above Set 1 39,000 39,000.00

Ring main Unit -

HSCC_NEIGRIHMS_Shillong Est-E 1_R1


Installation Total
S.No. Description. Unit. Quantity
Rate Amount
1.03 -

Supply Installation testing and commissioning of Ring Main Unit - Single Unit consisting of 2
Nos 800A Load break switches and 1 No. 800 A Tee-Off with SF6 / vaccum Circuit Breaker
and with O/C + E/F relay type (for Local Transformer control.) with SF6 Gas Pressure Indicator
0
suitable for outdoor installation for use on 11 KV 50 C/S earthed system having a short circuit
rating of 21KA for 1 Sec. at 11 KV including copper bus bars. Panel shall be equipped with
following accessories as per specifications and schematic drawing.

0 -

A. Each load breaking switch shall be comprising of: 0 -

0 -

a. -
Manually operated 800A Load Break switch and Earthing Switch with making capacity 0

b. Mechanical ON/OFF/EARTH Indication. 0 -

c. Cable Testing facility without opening the cable compartment and without disconnecting the -
0
cable terminations.
d. Live Cable Indicating LEDs energized through Capacitive Voltage Dividers 0 -

e. Cable box suitable for cable termination of 2 nos. 3Cx 300 sq.mm. PILC/XLPE cable. 0 -

f. Right angle boots eqvt to TP 300 of MECP make ( Push on type ) . 0 -

0 -

B. Each SF-6/ Vaccum Circuit Breaker shall be comprising of: 0 -

0 -

a. -
Manually operated 800 A SF6 / Vaccum circuit breaker and Earthing Switch with full making
0
capacity

b. Anti reflex operating handle. 0 -

c. Shunt Trip coil (230V AC) for external trip signal 0 -

d. Self powered O/C + E/F relay type VIP35 0 -

e. Mechanical ON/OFF/EARTH Indication. 0 -

f. Live Cable “ Indicating LEDs energized through Capacitive Voltage Dividers 0 -

g. Cable box for termination of cable upto 2 No. 3Cx 300 sq.mm. PILC/XLPE cable 0 -

h. Right angle boots eqvt to TP 300 of MECP make ( Push on type ) . Set 2 -

Ring main Unit as 0 -


1.04 TRANSFORMER :( FOR ESS-1) 0 -
i
Supply, installation, testing and commissioning of 2000 KVA, 11/0.433 kV, 3 Phase, 4 wire, 50
Hz., ON-AN Transformer, Dyn11 Vector group, copper bound Class F insulation with outdoor
duty type, On load tap changer on HV Side range -15%, 0, +5% in the steps of 1.25% per
step, type transformer with RTCC+AVR inclusive of all control cable. Cable box connection
including cable adapter box at primary and secondary end (LT side) shall be connected
through busduct/ cable, complete with all accessories including first filling of oil, double float
Each 3 36,000 108,000.00
buchholz relay protection, high winding temperature, oil temperture sensors and gauges etc.
confirming to IS 2026 (Part -1 & Part -2 ) ammended upto date, interconnection of control
cables and accessories etc complete.
Note -Transformer will have metering CT & PT of class 0.5 or better. including interconnection
of control cables as per detailed technical specifications and as required. Transformer losses
must be as per ECBC norms ammended up to date.

0 -
1.05 TRANSFORMER :( FOR ESS-2) 0 -
i
Supply, installation, testing and commissioning of 1250 KVA, 11/0.433 kV, 3 Phase, 4 wire, 50
Hz., ON-AN Transformer, Dyn11 Vector group, copper bound Class F insulation with outdoor
duty type, On load tap changer on HV Side range -15%, 0, +5% in the steps of 1.25% per
step, type transformer with RTCC+AVR inclusive of all control cable. Cable box connection
including cable adapter box at primary and secondary end (LT side) shall be connected
through busduct/ cable, complete with all accessories including first filling of oil, double float
Each 2 32,000 64,000.00
buchholz relay protection, high winding temperature, oil temperture sensors and gauges etc.
confirming to IS 2026 (Part -1 & Part -2 ) ammended upto date, interconnection of control
cables and accessories etc complete.
Note -Transformer will have metering CT & PT of class 0.5 or better. including interconnection
of control cables as per detailed technical specifications and as required. Transformer losses
must be as per ECBC norms ammended up to date.

-
1.06 BATTERY CHARGER PANEL 0 -
-
Supply, erection, testing and commissioning of battery charger panel with 24 V DC continuous
out put for control supply of HT panel complete with battery, control cabling etc. as required. 0
Capacity of battery charger panel should be suitable for above mentioned H.T. Panels.

-
2 numbers battery of minimum 180 AH ampere hour capacity. 0

-
Boost and Trickle charger suitable for above items. 0

1 No. AC Voltmeter (0-500Volt) 0 -


I No. DC Voltmeter 0 -

I No. DC Ammeter 0 -

1 set of AC and DC indicating lamps 0 -

1 No. DC Battery charging position indicator 0 -

DC distribution board suitable for above application to incoming & outgoing MCBs include -
0
tripping, closing and indication etc.
30,000.00
Control cabling between DC Distribution panel to the HT panel of the Substation with suitable
Each 2 15,000
core 1.5 sqmm copper cable
0 -
1.07 BUS DUCTS : 0 -
i) 430,000.00
Supply, Installation, testing and commissioning of 3200 Amp phase and neutral , 415 V, 3
Phase, 4 Wire, sandwich construction Aluminium Bus Duct including bends, flexible joints,
Meter 100 4,300
earth bus (2 runs of aluminum strips), supports for installation, supporting arrangements,
etc.outdoor /indoor duty type complete as per technical specifications and as requirment.

ii) 342,100.00
Supply, Installation, testing and commissioning of 1600 Amp phase and neutral , 415 V, 3
Phase, 4 Wire, sandwich construction Aluminium Bus Duct including bends, flexible joints,
Meter 110 3,110
earth bus (2 runs of aluminum strips), supports for installation, supporting arrangements,
etc.outdoor /indoor duty type complete as per technical specifications and as requirment.

iii) 265,500.00
Supply, Installation, testing and commissioning of 1250 Amp phase and neutral , 415 V, 3
Phase, 4 Wire, sandwich construction Aluminium Bus Duct including bends, flexible joints,
Meter 90 2,950
earth bus (2 runs of aluminum strips), supports for installation, supporting arrangements,
etc.outdoor /indoor duty type complete as per technical specifications and as requirment.

0 -
1.08 H.T. CABLE 0 -
-
Supply of following sizes of 11 kV grade multicore aluminum conductor XLPE armoured power
0
cable as per IS : 7098.
i) 3 Core, 300 sq mm Meter 2000 -
ii 3 Core, 240 sq mm Meter 300 -
iii 3 Core, 185 sq mm Meter 200 -
0 -
1.09 -
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade
of following size direct in ground including excavation, sand cushioning, protective covering 0
and refilling the trench etc as required.

i) upto 400 Sq mm Meter 1200 420 504,000.00


0 -
1.1 -
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade
0
of following size in the existing RCC/ HUME/ METAL pipe as required.

i) upto 400 Sq mm Metre 200 450 90,000.00


0 -
1.11 -
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade
0
of following size in the existing masonry open duct /cable tray as required.

i) upto 400 Sq mm Metre 100 430 43,000.00


0 -
1.12 -
Supplying and making end termination with heat shrinkable jointing kit complete with all
accessories including lugs suitable for following size 3 Core, XLPE aluminium conductor cable 0
of 11kV grade as required.

i) 300 sqmm 3 core (Heat Shrunk Type ) Indoor Type Each 8 3,250 26,000.00
ii) 300 sqmm 3 core (Heat Shrunk Type ) Outdoor Type Each 4 3,250 13,000.00
iii) 240 sqmm 3 core (Heat Shrunk Type ) Indoor Type Each 8 2,850 22,800.00
iv) 240 sqmm 3 core (Heat Shrunk Type ) Outdoor Type Each 4 2,850 11,400.00
0 -
1.13 -
Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete
with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching 0
(75 cm deep) and refilling etc as required.

i) 300 mm dia Metre 40 580 23,200.00

1.14 Cable Route Marker 0 -

Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with 16,500.00
inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and Each 50 330
fixing the same in ground as required.
0 -
1.15 Providing & Fixing of Safety Equipmet 0 -
i) Providing and fixing H.T. (11kV) danger notice plate of 250mmX150mm made of mild steel, 380.00
atleast 2mm thick and vitreous enameled white on both sides and with inscription in signal red Each 4 95
colour on front side as required.
ii) 2,850.00
Providing and fixing M.V. danger notice plate of 200mmX150mm made of mild steel, atleast
2mm thick and vitreous enammelled white on both sides and with inscription in signal red Each 30 95
colour on front side as required.

iii) -
Supply & erection of the following Safetyand testing Equipment including miscellanoes items
0
like Clamps, nuts & Bolts , rawl plugs etc at suib;e laces in the Substation building as required.

a) G.I buckets of 3 nos of 5 Litres Capacity duly painted white inside and red oxide paint out side 1,900.00
and witten 'FIRE' with white paint & Filled with Dry sand and mounted on M.S angel iron
Each 4 475
bracket of Size 50x50x6mm thick and 1200mm long including grounting in walll /floor etc as
required .
b) Supplying, storing, handling and fixing in position First Aid Medical Box complete as per 360.00
Each 4 90
technical specifications as required.
c) Shock Treatment Chart duly glazed mounted on Aluminum Frame with Sheet Glass as 380.00
Each 4 95
required.
d) Supplying and laying of 12kV grade 1 metre wide anti skid chequered type rubber mat. Metre 60 95 5,700.00

e) 7,600.00
Supplying and laying of 1.1kV grade 1 metre wide anti skid chequered type rubber mat. Metre 80 95

f) Supply rubber hand gloves 11kV grade as per I.S. Code. set 4 -

g) -
Supplying of digital Earth Tester complete with probes etc as required Set 2

h) Supplying of Telesscopic folding Aluminium ladder folding double with sitting stand 6 M etc as -
Each 4
required
0 -
1.16 Providing and fixing of M.S Slotted angle iron with fixing materials and painting for cable racks 16,000.00
Kg 200 80
in trenches /on wall etc. as required
0 -
1.17 Providing and fixing of M.S Slotted angle 'C' channel /Ladder type rack /tray including fixing 18,000.00
material grouted in wall or haning with M.S rod hanger from ceiling including 2 coat synthetic Kg 200 90
enamel painting over 1 coat of res oxide primer etc. as required
0 -

HSCC_NEIGRIHMS_Shillong Est-E 2_R1


Installation Total
S.No. Description. Unit. Quantity
Rate Amount
1.18 -
Fabrication and Installing following size of preforted M.S Cable tray including Horizontal and
vertical bends, reducers,tee, crossmember and other accessories as required and duly
0
Suspended from the ceiling with M.S 12mm rod suspenders and including painting etc. as
required.

i) 33,600.00
150mmwidth x 50mm depth x1.6mm thickness Metre 800 42

ii) 33,000.00
450mmwidth x 50mm depth x2.0mm thickness Metre 600 55

iii) 600mmwidth x 50mm depth x2.0mm thickness Metre 100 62 6,200.00

0 -
1.19 -
Fabrication and Installing following size of Ladder type M.S Cable tray including Horizontal
and vertical bends, reducers,tee, crossmember and other accessories as required and duly
0
Suspended from the ceiling with M.S 12mm rod suspenders and including painting etc. as
required.

i) 450mmwidth x 62.5mm depth x2.0mm thickness Metre 500 210 105,000.00


ii) 600mmwidth x 62.5mm depth x2.0mm thickness Metre 200 250 50,000.00
iii) 750 mmwidth x 75mm depth x2.0mm thickness Metre 200 290 58,000.00
0 -
TOTAL SUBHEAD 1: H.T. SUB STATION 0 -
0 -
2.00 SUBHEAD 2: MAIN LT PANEL. 0 -
2.01 -
MAIN L.T. PANEL (For Cancer Hosptial , Medical & Nursing College Location -ESS-1) 0

-
Supply, installation, testing and commissioning of LT Panel, Type Tested Assembly (TTA),
panel cubicle type, totally enclosed, free standing type, dust ,damp and vermin proof panel ,
powder coated, made up of CRCA sheet, complete with aluminum busbars, danger notice
0
plate, interconnections with suitable capacity aluminum leads/solid aluminum strips/rods,
necessary interlocking, and having incoming and outgoing switchgears as mentioned below.
Complete as per technical specifications and as required.

Note : 0 -
1 All ACBs shall have spare contacts 0 -

2 All relays to operate at 240Volts, Single phase, 50Hz., AC supply through UPS. UPS of -
0
suitable Rating is also in the scope of Supply
3 -
Intellignet Panel Meter: Flush mounting, 96X96 mm size class 1 accuracy and LCD display.
Panel meter should be suitable for true RMS reading. Meter should measure line and phase
voltage, current of all 3 phasees and neutral, HZ, PF, KW, KWH, KVAR, KVARH, KVA, KVAH, 0
Voltage and current including one set of CT. Meter should be EMI/ EMC complaint. Meter
should be with RS 485 port for communication on Modbus protocol.

4 All ACBs shall have 50 KA for 1 second. 0 -


5 All ACBs should have Icw =Ics=Icu=100% -
6 All MCCBs shall have Ics=Icu=100% -
7 Separate fault indication for O/L, S/C, & E/F to be provided on Panel Door for all -
Microprocessor Based outgoing MCCB
-
A INCOMER: 0 -
i) 4 No. ACB Panels each having following: 0 -
-
3200 A, 415 V, Motorised, Fully Drawout type (EDO), Four Pole, Air Circuit Breaker with
microprocessor based overload, short circuit , Instantaneous & Earth Fault trip including under 0
voltage release and lockable trip push button. ACB should have Icw=Ics=Icu=50 KA for 1 sec.

Indicating lamps with 2A protection MCBs to indicate OPEN, CLOSE, TRIP for ACB 0 -

Push button to CLOSE the ACB. 0 -

R, Y & B Phase indicating lamps (LED type) with 6A control SP MCBs 0 -

Intellgent Panel Meter as mention above 0 -

One set of dual core dual ratio CT of 3200/1600/5/5A for capacitor panel. 0 -
0 -
B. BUSBARS : 0 -
3200 Amps TPN busbars of aluminium with temperture rise of 40 ° C over and above Ambient -
0
temperture of 45 Degree Celsius.(Total 85 ° C)
0 -
C. BUS COUPLER : 0 -
i) 2 No. ACB Panels each having following: 0 -
-
3200 A, 415 V, Motorised, Fully Drawout type (EDO), Four Pole, Air Circuit Breaker with
microprocessor based overload, short circuit , Instantaneous & Earth Fault trip including and 0
lockable trip push button. The ACB should have Icw=Ics=Icu=50 KA for 1 sec.

1 set of indicating lamps to indicate OPEN, CLOSE, TRIP. 0 -

Push button to CLOSE the ACB. 0 -

1 Set of Ammeter with ASS and CTs. 0 -


0 -
D. OUTGOING. 0 -
i) 5 No. ACB Panels each having following: 0 -

-
1600 A, 415/V, Motorised, Fully Drawout type (EDO), Four Pole, Air Circuit Breaker with
microprocessor based overload, short circuit , Instantaneous & Earth Fault trip including and 0
lockable trip push button. The ACB should have Icw=Ics=Icu=50 KA for 1 sec.

-
Indicating lamps with 6A protection MCBs to indicate OPEN, CLOSE, TRIP for ACB 0

Push button to CLOSE the ACB 0 -

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -

Digital energy metre with CT 0 -

0 -
ii) -
6 No. ACB Panels each having following: 0
-
1250 A, 415/V, Motorised, Fully Drawout type (EDO), Four Pole, Air Circuit Breaker with
microprocessor based overload, short circuit , Instantaneous & Earth Fault trip including and 0
lockable trip push button. The ACB should have Icw=Ics=Icu=50 KA for 1 sec.

-
Indicating lamps with 2A protection MCBs to indicate OPEN, CLOSE, TRIP for ACB 0

Push button to CLOSE the ACB 0 -

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -

Digital energy metre with CT 0 -


0 -
iii) 2 No. ACB Panels each having following: 0 -

-
1000 A, 415/V, Motorised, Fully Drawout type (EDO), Four Pole, Air Circuit Breaker with
microprocessor based overload, short circuit , Instantaneous & Earth Fault trip including and 0
lockable trip push button. The ACB should have Icw=Ics=Icu=50 KA for 1 sec.

-
Indicating lamps with 2A protection MCBs to indicate OPEN, CLOSE, TRIP for ACB 0

Push button to CLOSE the ACB 0 -

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -

Digital energy metre with CT 0 -


iv) 2 No. ACB Panels each having following: 0 -
-
800 A, 415/V, Motorised, Fully Drawout type (EDO), Four Pole, Air Circuit Breaker with
microprocessor based overload, short circuit , Instantaneous & Earth Fault trip including and 0
lockable trip push button. The ACB should have Icw=Ics=Icu=50 KA for 1 sec.

Indicating lamps with 2A protection MCBs to indicate OPEN, CLOSE, TRIP for ACB 0 -

Push button to CLOSE the ACB 0 -

-
Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0

Digital energy metre with CT 0 -


0 -
v) 7 Nos. MCCB FEEDER as per following details/ specifications: 0 -
-
630Amp 415 volts, 50 KA ( Ics) Four Pole, Microprocessor release based MCCB with variable
0
current settings and having O/L, S/C & inbuilt E/F protection.

Extended rotary operating mechanism with door interlock with defeat feature and padlock -
0
facility. MCCB should be with spreader link and phase barriers.
-
Indicating lamps (LED Type) with 2A protection MCBs to indicate ON, OFF, TRIP . 0

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -

Digital Energy meter 0 -


0 -
vi) 1 Nos. MCCB FEEDER as per following details/ specifications: 0 -
-
500 Amp 415 volts, 50 KA ( Ics) Four Pole, Microprocessor release based MCCB with variable
0
current settings and having O/L, S/C & inbuilt E/F protection.

-
Extended rotary operating mechanism with door interlock with defeat feature and padlock
0
facility. MCCB should be with spreader link and phase barriers.

-
Indicating lamps (LED Type) with 2A protection MCBs to indicate ON, OFF, TRIP . 0

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -

Digital Energy meter 0 -

0 -
vii) 3 Nos. MCCB FEEDER as per following details/ specifications: 0 -
-
400Amp 415 volts, 50 KA ( Ics) Four Pole, Microprocessor release based MCCB with variable
0
current settings and having O/L, S/C & inbuilt E/F protection.

-
Extended rotary operating mechanism with door interlock with defeat feature and padlock
0
facility. MCCB should be with spreader link and phase barriers.

-
Indicating lamps (LED Type) with 2A protection MCBs to indicate ON, OFF, TRIP . 0

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -

Digital Energy meter 0 -


0 -
viii) 10 Nos. MCCB FEEDER as per following details/ specifications: 0 -
-
250 Amp 415 volts, 50 KA ( Ics) Four Pole, Microprocessor release based MCCB with variable
0
current settings and having O/L, S/C & inbuilt E/F protection.

-
Extended rotary operating mechanism with door interlock with defeat feature and padlock
0
facility. MCCB should be with spreader link and phase barriers.

-
Indicating lamps (LED Type) with 2A protection MCBs to indicate ON, OFF, TRIP . 0

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -

Digital Energy meter 0 -

0 -
ix) 13 Nos. MCCB FEEDER as per following details/ specifications: 0 -
160 Amp 415 volts, 50 KA ( Ics) Four Pole, Microprocessor release based MCCB with variable -
0
current settings and having O/L, S/C & inbuilt E/F protection.
-
Extended rotary operating mechanism with door interlock with defeat feature and padlock
0
facility. MCCB should be with spreader link and phase barriers.

Indicating lamps (LED Type) with 2A protection MCBs to indicate ON, OFF, TRIP . 0 -

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -

Digital Energy meter 0 -

HSCC_NEIGRIHMS_Shillong Est-E 3_R1


Installation Total
S.No. Description. Unit. Quantity
Rate Amount
0 -

Main LT Panel ( For Cancer Hosptial , Medical & Nursing College) as mentioned above. Set 1 67,200 67,200.00

0 -
2.02 -
CAPACITOR PANEL ESS-1 (For Cancer Hosptial , Medical & Nursing College ) 800
0
kVAr

-
Supply, installation, testing and commissioning of MV cubicle type totally enclosed free
standing type, powder coated, dust, damp and vermin proof Capacitor Panel complete with
busbars, MV danger notice plate, ammeter, ammeter selector switch, indicating lamps, CTs,
heavy duty, MPP resin filled, type Capacitors suitable for non linear loads upto 15% with
Copper wound 14% D-tunned filters, total operating losses of capacitor shall not more than 0.5
W/ KVAR, Power contactors suitable for capacitor switching or Capacitor duty with current
limiting contactor circuit to suppress switching inrush current interconnections with suitable
capacity aluminium leads/ solid aluminium strips, rods, connection of incoming and outgoing
cables with thimbles, and having following incoming and outgoing switchgears complete as
per techinical Specifications as required.

a) INCOMER: -

1250 A, 415 Volts, Fully Motorised, Fully Drawout type (EDO), 50 KA, Four Pole, Air Circuit -
Breaker with microprocessor based overload, short circuit & Instantanious Earth fault trip
including lockable trip push button.
Indicating lamps with 6A protection MCBs to indicate OPEN, CLOSE, TRIP. -
R, Y & B Phase indicating lamps (LED type) with 6A control SP MCBs. -
Day & Night mode selector switch. -
14 steps Intelligent microprocessor based Automatic Power factor Correction relay having -
measurment sensitivity of 1 % or better.
Extension of incoming busbars for connection of multicore armoured aluminium cables. -
-
b) METERING: -
1 set of Digital Amp. Meter, Digital Power factor meter and Digital voltmeter. -
-
c) BUSBARS: -
1250 Amps TPN busbars of aluminium with temperture rise of 40 ° C over and above Ambient -
temperture of 45 Degree Celsius.(Total 85 ° C)
-

d) OUTGOINGS: -
i) 4 Nos. MCCB as per following details/ specification: -
200 Amps, 415 volts, 50 KA TP MCCB with Thermal Magnetic release having variable current -
settings.
Extended rotary operating mechanism with door interlock, defeat feature and padlock facility. -
MCCB should be with spreader link and phase barriers.
415 volts, TP Power Contactor suitable for capacitive switching including current limiting -
contactor circuit to supress switching inrush current.
ON/ OFF delay timers for switching capacitor circuit. -
"ON" and "OFF" LED indicating lamp and 2A control SP MCBs. -
Push button for CLOSE and TRIP. 0 -

100 KVAR heavy duty MPP type resin filled capacitors suitable for non linear loads upto 15%, -
0
& total operating losses not more than 0.5 W per KVAR.
-
ii) 8 Nos. MCCB as per following details/ specification: -
-
100 Amps, 415 volts, 50 KA TP MCCB with Thermal Magnetic release having variable current
settings.

Extended rotary operating mechanism with door interlock, defeat feature and padlock facility. -
MCCB should be with spreader link and phase barriers.
415 volts, TP Power Contactor suitable for capacitive switching including current limiting -
contactor circuit to supress switching inrush current.
ON/ OFF delay timers for switching capacitor circuit. -

"ON" and "OFF" LED indicating lamp and 2A control SP MCBs. -

50 KVAR heavy duty MPP type resin filled capacitors suitable for non linear loads upto 15% & -
total operating losses not more than 0.5 W per KVAR.
-
CAPACITOR PANEL AS MENTIONED ABOVE Set 3 35,000 105,000.00
0 -
2.03 MAIN L.T. PANEL (NORMAL) (For Hostels & Dinning Blocks) Location -ESS-2 0 -
-
Supply, installation, testing and commissioning of LT Panel, cubicle type, totally enclosed, free
standing type, dust ,damp and vermin proof panel , powder coated, made up of CRCA sheet,
complete with aluminum busbars, danger notice plate, interconnections with suitable capacity
0
aluminum leads/solid aluminum strips/rods, necessary interlocking, and having incoming and
outgoing switchgears with cable alley in front as mentioned below and complete as per
technical specifications and as required.

Note : 0 -
1 All ACBs shall have spare contacts 0 -

2 All relays to operate at 240Volts, Single phase, 50Hz., AC supply through UPS. UPS of -
0
suitable Rating is also in the scope of Supply
3 -
Intellignet Panel Meter: Flush mounting, 96X96 mm size class 1 accuracy and LCD display.
Panel meter should be suitable for true RMS reading. Meter should measure line and phase
voltage, current of all 3 phasees and neutral, HZ, PF, KW, KWH, KVAR, KVARH, KVA, KVAH, 0
Voltage and current including one set of CT. Meter should be EMI/ EMC complaint. Meter
should be with RS 485 port for communication on Modbus protocol.

4 All ACBs shall have 50 KA for 1 second. 0 -


5 All ACBs should have Icw =Ics=Icu=100% -
6 All MCCBs shall have Ics=Icu=100% -
7 Separate fault indication for O/L, S/C, & E/F to be provided on Panel Door for all -
Microprocessor Based outgoing MCCB
0 -
A. INCOMER: 0 -
i) 2 No. ACB Panels each having following: 0 -
-
2000 A, 415/500V Motorised, Fully Drawout type (EDO), Four Pole, Air Circuit Breaker with
microprocessor based overload, short circuit , Instantaneous & Earth Fault trip including under 0
voltage release and lockable trip push button. ACB should have Icw=Ics=Icu=50 KA for 1 sec.

Indicating lamps with 2A protection MCBs to indicate OPEN, CLOSE, TRIP for ACB 0 -

Push button to CLOSE the ACB. 0 -


R, Y & B Phase indicating lamps (LED type) with 2A control SP MCBs 0 -

Intellgent Panel Meter as mention above 0 -


One set of dual core dual ratio CT of 2000/1000/5/5A for capacitor panel. 0 -
0 -
B. BUSBARS : 0 -
2000 Amps 50 KA, TPN busbars of aluminium with temperture rise of 40 ° C over and above -
0
Ambient temperture of 45 Degree Celsius.(Total 85 ° C)
0 -
C. BUS COUPLER : 0 -
i) 1No. ACB Panels each having following: 0 -
-
2000 A, 415/500V,415 V, Motorised, Fully Drawout type (EDO), Four Pole, Air Circuit Breaker
with microprocessor based overload, short circuit , Instantaneous & Earth Fault trip including 0
and lockable trip push button. The ACB should have Icw=Ics=Icu=50 KA for 1 sec.

1 set of indicating lamps to indicate OPEN, CLOSE, TRIP. 0 -


Push button to CLOSE the ACB. 0 -
1 Set of A meter with ASS and CTs. 0 -
0 -
D. OUTGOING. 0 -
0 -
i) 3 No. ACB Panels each having following: 0 -
-
1000 A, 415/500V, 415 V, Motorised, Fully Drawout type (EDO), Four Pole, Air Circuit Breaker
with microprocessor based overload, short circuit , Instantaneous & Earth Fault trip including 0
and lockable trip push button. The ACB should have Icw=Ics=Icu=50 KA for 1 sec.

Indicating lamps with 2A protection MCBs to indicate OPEN, CLOSE, TRIP for ACB 0 -

Push button to CLOSE the ACB 0 -

R, Y & B Phase indicating lamps (LED type) with 2A control SP MCBs 0 -


-
Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0

Digital energy metre with CT 0 -


0 -
ii) 9 Nos. MCCB FEEDER as per following details/ specifications: 0 -
400 Amp 415 volts, 50 KA ( Ics)Four Pole, Microprocessor release based MCCB with variable -
0
current settings and having O/L, S/C & inbuilt E/F protection.

Extended rotary operating mechanism with door interlock with defeat feature and padlock -
0
facility. MCCB should be with spreader link and phase barriers.

Indicating lamps (LED Type) with 2A protection MCBs to indicate ON, OFF, TRIP . 0 -

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -

Digital Energy meter 0 -


0 -
iii) 2 Nos. MCCB FEEDER as per following details/ specifications: 0 -
-
320 Amp 415 volts, 50 KA ( Ics)Four Pole, Microprocessor release based MCCB with variable
0
current settings and having O/L, S/C & inbuilt E/F protection.
-
Extended rotary operating mechanism with door interlock with defeat feature and padlock
0
facility. MCCB should be with spreader link and phase barriers.

Indicating lamps (LED Type) with 2A protection MCBs to indicate ON, OFF, TRIP . 0 -

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -

-
Digital Energy meter 0

iii) 3 Nos. MCCB FEEDER as per following details/ specifications: 0 -


-
250 Amp 415 volts, 50 KA ( Ics) Four Pole, Microprocessor release based MCCB with variable
0
current settings and having O/L, S/C & inbuilt E/F protection.

-
Extended rotary operating mechanism with door interlock with defeat feature and padlock
0
facility. MCCB should be with spreader link and phase barriers.

Indicating lamps (LED Type) with 2A protection MCBs to indicate ON, OFF, TRIP . 0 -

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -

Digital Energy meter 0 -

0 -
iv) 8 Nos. MCCB FEEDER as per following details/ specifications: 0 -
200Amp 415 volts, 50 KA (Isc), Four Pole, Microprocessor release based MCCB with variable -
0
current settings and having O/L, S/C & inbuilt E/F protection.
-
Extended rotary operating mechanism with door interlock with defeat feature and padlock
0
facility. MCCB should be with spreader link and phase barriers.

-
Indicating lamps (LED Type) with 2A protection MCBs to indicate ON, OFF, TRIP . 0

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -

Digital Energy meter 0 -

0 -
Main LT Panel (NORMAL) (For Hostels & Dinning Blocks) as mentioned above. Set 1 36,000 36,000.00
0 -
2.04 -
Main LT Panel (EMERGENCY) (For Hostels & Dinning Blocks) Loction -ESS-2 ) 0

A INCOMER: 0 -
i 2 Nos. MCCB as per following details / specifications: 0 -
630 A, 415/500V, 415/500V Motorised, Fully Drawout type (EDO), Four Pole, Air Circuit -
Breaker with microprocessor based overload, short circuit , Instantaneous & Earth Fault trip
0
including under voltage release and lockable trip push button. ACB should have
Icw=Ics=Icu=50 KA for 1 sec.

Indicating lamps with 2A protection MCBs to indicate OPEN, CLOSE, TRIP for ACB 0 -

HSCC_NEIGRIHMS_Shillong Est-E 4_R1


Installation Total
S.No. Description. Unit. Quantity
Rate Amount
Push button to CLOSE the ACB 0 -

R, Y & B Phase indicating lamps (LED type) with 2A control SP MCBs 0 -


Intellgent Panel Meter as mention above 0 -

DG should start automatically and will have automatic change over at LT panel through auto -
0
change over arrangement of suitable capacity.
B BUSBARS: 0 -
630 Amp TPN busbars of aluminium with temperture rise of 40 ° C over and above Ambient -
0
temperture of 45 Degree Celsius.(Total 85 ° C)
0 -
C BUS COUPLER : 0 -
i 1 Nos. MCCB as per following details / specifications: 0 -
-
630 A, 415/500V,415 V, Motorised, Fully Drawout type (EDO), Four Pole, Air Circuit Breaker
with microprocessor based overload, short circuit , Instantaneous & Earth Fault trip including 0
and lockable trip push button. The ACB should have Icw=Ics=Icu=50 KA for 1 sec.

Indicating lamps with 2A protection MCBs to indicate OPEN, CLOSE, TRIP for ACB 0 -

Push button to CLOSE the ACB 0 -

R, Y & B Phase indicating lamps (LED type) with 2A control SP MCBs 0 -


1 Set of A meter with ASS and CTs. 0 -
0 -
D OUTGOING: 0 -
i 13 Nos. MCCB as per following details / specifications: 0 -
100 Amps,415 volts, FP, 35 KA Moulded Case Circuit Breaker with thermal magnetic release -
0
having variable current settings .
-
R,Y&B phase indicating lamp (LED type) with 2A control SP MCB to indicate ON, OFF, TRIP . 0

-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -
0 -
25,000.00
Main LT Panel (EMERGENCY) (For Hostels & Dinning Blocks) as mentioned above. Set 1 25,000

0 -
2.05 CAPACITOR PANEL ESS-2 (For Hostels & Dinning Blocks) 500 KVAR 0 -
-
Supply, installation, testing and commissioning of MV cubicle type totally enclosed free
standing type, powder coated, dust, damp and vermin proof Capacitor Panel complete with
busbars, MV danger notice plate, ammeter, ammeter selector switch, indicating lamps, CTs,
heavy duty, MPP resin filled, type Capacitors suitable for non linear loads upto 15% with
Copper wound 14% D-tunned filters, total operating losses of capacitor shall not more than 0.5
W/ KVAR, Power contactors suitable for capacitor switching or Capacitor duty with current
limiting contactor circuit to suppress switching inrush current interconnections with suitable
capacity aluminium leads/ solid aluminium strips, rods, connection of incoming and outgoing
cables with thimbles, and having following incoming and outgoing switchgears complete as
per techinical Specifications as required.

0 -
A. INCOMER : 0 -

-
800 A, 415 Volts,415/500V,415 V, Motorised, Fully Drawout type (EDO), Four Pole, Air Circuit
Breaker with microprocessor based overload, short circuit , Instantaneous & Earth Fault trip 0
including and lockable trip push button. The ACB should have Icw=Ics=Icu=50 KA for 1 sec.

Indicating lamps with 2A protection MCBs to indicate OPEN, CLOSE, TRIP. 0 -

R, Y & B Phase indicating lamps (LED type) with 2A control SP MCBs 0 -

-
Day & Night mode selector switch 0

14 steps Intelligent microprocessor based Automatic Power factor Correction relay having -
0
measurment sensitivity of 1 % or better.
-
Extension of incoming busbars for connection of multicore armoured aluminium cables. 0

0 -
B. METERING : 0 -

1 set of digital Amp. Meter, digital Power factor meter and Digital voltmeter 0 -
0 -
C. BUSBARS : 0 -

800 Amps TPN busbars of aluminium with temperture rise of 40 ° C over and above Ambient -
0
temperture of 45 Degree Celsius.(Total 85 ° C)
0 -
D. OUTGOINGS : 0 -
i) 2 Nos . MCCB as per following details/ specification: 0 -
200 Amps, 415 volts, 50 KA TP MCCB with Thermal Magnetic release having variable current -
settings.
Extended rotary operating mechanism with door interlock, defeat feature and padlock facility. -
MCCB should be with spreader link and phase barriers.

415 volts, TP Power Contactor suitable for capacitive switching including current limiting -
contactor circuit to supress switching inrush current.
ON/ OFF delay timers for switching capacitor circuit. -
"ON" and "OFF" LED indicating lamp and 2A control SP MCBs. -
Push button for CLOSE and TRIP. 0 -
100 KVAR heavy duty MPP type resin filled capacitors suitable for non linear loads upto 15%, -
0
& total operating losses not more than 0.5 W per KVAR.
0 -
ii) 4 Nos . MCCB as per following details/ specification: 0 -
100 Amps, 415 volts, 50 KA TP MCCB with Thermal Magnetic release having variable current -
settings.
-
Extended rotary operating mechanism with door interlock, defeat feature and padlock facility.
MCCB should be with spreader link and phase barriers.

415 volts, TP Power Contactor suitable for capacitive switching including current limiting -
contactor circuit to supress switching inrush current.

ON/ OFF delay timers for switching capacitor circuit. -

-
"ON" and "OFF" LED indicating lamp and 2A control SP MCBs.

Push button for CLOSE and TRIP. 0 -

50 KVAR heavy duty MPP type resin filled capacitors suitable for non linear loads upto 15%, & -
0
total operating losses not more than 0.5 W per KVAR.
0 -
iii) 4 Nos . MCCB as per following details/ specification: 0 -
63 Amps, 415 volts, 50 KA TP MCCB with Thermal Magnetic release having variable current -
settings.
Extended rotary operating mechanism with door interlock, defeat feature and padlock facility. -
MCCB should be with spreader link and phase barriers.
415 volts, TP Power Contactor suitable for capacitive switching including current limiting -
contactor circuit to supress switching inrush current.

ON/ OFF delay timers for switching capacitor circuit. -


"ON" and "OFF" LED indicating lamp and 2A control SP MCBs. -
Push button for CLOSE and TRIP. 0 -
25 KVAR heavy duty MPP type resin filled capacitors suitable for non linear loads upto 15%, & -
0
total operating losses not more than 0.5 W per KVAR.
0 -
56,000.00
Capacitor panel (For Hostels & Dinning Blocks) as mentioned above. Set 2 28,000

0 -
Total SubHead 2: Main LT Panel as mentioned above. 0 -

0 -
4.00 SUBHEAD 4: RISING MAINS 0 -
-
Supply, installation, testing and commissioning of plug in type , indoor sandwich type with
high conductivity Aluminium Conductor , 415 V,3 phase, 4 wire, vertical Aluminium Rising
main Class B or better in following sizes including bends, flexible, provision of the tap off's as
per requirment , Adoptor boxes for cable connection if required are inclusive , 2 nos of 0
aluminium earthing strips 50 X 6mm through out the length of the rising mains, end cover,
including all types of support and necessary hardware for installation of the rising main etc.
complete as per specifications and as required. (Exact lengths to be measured at site).
4.01
i 1000 A , 415 volts Metre 40 2,890 115,600.00
ii 1250 A,415 volts Metre 80 2,960 236,800.00
0 -
Supply, fixing, testing and commissioning of Direct End Feed Unit of following ratings, wall -
mounted, dust, damp and vermin proof complete with M.V. danger notice plate,
interconnections with suitable capacity aluminium strips / bars, connection of incoming cables 0
with thimbles, powder coat painted and having following incoming switchgears for rising main
4.02 complete as required.
i) 1 No. ACB Panels each having following 0 -
1000A 415V, 4P 50 kA EDO ACB with Microprocessor based release having Overload , Short 6,000.00
circuit and Earth fault Protection with overvoltage, undervoltage protection and ON /OFF/TRIP Set 1 6,000
Indications with MCB.
0 -
ii) 1 No. ACB Panels each having following 0 -
1250A 415V, 4P 50 kA EDO ACB with Microprocessor based release having Overload , Short 12,000.00
circuit and Earth fault Protection with overvoltage, undervoltage protection and ON /OFF/TRIP Set 2 6,000
Indications with MCB.
0 -
Supply, fixing, testing and commissioning of distribution tap off box of following Capacity on -
the existing rising mains complete with Four Pole, Moulded Case Circuit Breaker, 0
4.03 interconnection, earthing etc. complete as required.
0 -
i 100 Amps with MCCB 35 KA Nos 18 1,100 19,800.00
ii 125 Amps with MCCB 35 KA Nos 4 1,100 4,400.00
iii 160 Amps with MCCB 35 KA Nos 11 1,100 12,100.00
iv 200 Amps with MCCB 35 KA Nos 5 1,100 5,500.00
vi 400 Amps with MCCB 35 KA Nos 5 1,100 5,500.00
0 -
TOTAL SUBHEAD - 4: RISING MAINS as mentioned above 0 -
0 -
5.00 SUB HEAD 5 :MV PANELS 0 -
-
Supply, installation, testing and commissioning of following M.V. cubicle type totally enclosed,
wall mounted/Free standing type, powder coated, dust, damp and vermin proof, indoor type
Distribution Board/Panel complete with busbars, M.V. danger notice plate, interconnections
0
with suitable capacity aluminium leads/solid aluminium strips/rods, connection of incoming and
outgoing cables with thimbles, and having following incoming and outgoing switchgears
complete as per techinical specification and as required.

NOTE -
All MCCBs shall have Ics=Icu. 0 -

MCB Should be connected through terminal Strip of suitable rating -

REGIONAL CANCER HOSPITAL 0 -

5.01 MV PANEL FOR{ LEVEL+1, +2, +4,+5,+6 FLOOR (SECTION -1)} -


0
a) INCOMER: 0 -
-
400 Amp 415 volts, 35 KA FP MCCB with microprocessor based release having variable
0
current settings of O/L, S/C & inbuilt E/F protection release.

-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP -
0
indication (LED Type)
Separate fault indication for O/L, S/C, & E/F to be provided on Panel Door. 0 -

1 No. 0 to 500 V Digital voltmeter with selector switch. 0 -

Digital ammeter with selector switch with one set Suitable C.Ts. 0 -
0 -
b) BUSBARS: 0 -
630 Amp TPN Aluminium busbars 0 -
0 -
c) OUTGOING: 0 -
0 -

HSCC_NEIGRIHMS_Shillong Est-E 5_R1


Installation Total
S.No. Description. Unit. Quantity
Rate Amount
i) 8 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0 -
ii) -
8 no. 40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0

40,000.00
MV PANEL FOR{ LEVEL+1, +2, +4,+5,+6 FLOOR (SECTION -1)} : as mentioned above Set 5 8,000

0 -

5.02 MV PANEL FOR{ LEVEL+3, +7 FLOOR (SECTION -1) & LOWER GROUND FLOOR & -
LEVEL +3 (SECTION -2)} 0

a) INCOMER: 0 -
-
125 Amp 415 volts, 35 KA FP MCCB with thermal magnetic release having variable current
0
settings of O/L, S/C protection and E/ F Module.

-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP -
0
indication (LED Type)
1 No. 0 to 500 V Digital voltmeter with selector switch. 0 -
Digital ammeter with selector switch with one set Suitable C.Ts. 0 -
0 -
b) BUSBARS: 0 -
300 Amp FP Aluminium busbars 0 -
0 -
c) OUTGOING: 0 -
0 -
i) -
5 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0

ii) -
5 no. 40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0

MV PANEL FOR{ LEVEL+3, +7 FLOOR (SECTION -1) & LOWER GROUND FLOOR & 32,000.00
Set 4 8,000
LEVEL +3 Floor (SECTION -2)} : as mentioned above
0 -
5.03 MV PANEL FOR{ LEVEL+1, +2, +4,+5,+6 FLOOR (SECTION -2)} -
0
a) INCOMER: 0 -
-
200 Amps,415 volts, FP 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal magnetic
0
release having variable current settings of O/L, S/C protection and E/ F Module.

-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP -
0
indication (LED Type)

1 No. 0 to 500 V Digital voltmeter with selector switch. 0 -

Digital ammeter with selector switch with one set Suitable C.Ts. 0 -

0 -
b) BUSBARS: 0 -
300 Amp TPN Aluminium busbars 0 -
0 -
c) OUTGOING: 0 -

i) 8 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0 -

ii) -
8 no.40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0

70,000.00
MV PANEL FOR{ LEVEL+1, +2, +4,+5,+6 FLOOR (SECTION -2)} : as mentioned above Set 5 14,000

0 -
5.04 MV PANEL FOR { ENTRY &+7 LEVEL FLOOR (SECTION -2)} 0 -
a) INCOMER: 0 -
-
160 Amps,415 volts, FP 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection and E/ F Module.

-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP -
0
indication (LED Type)
1 No. 0 to 500 V Digital voltmeter with selector switch. 0 -
Digital ammeter with selector switch with one set Suitable C.Ts. 0 -

0 -
b) BUSBARS: 0 -
300 Amp TPN Aluminium busbars 0 -
0 -
c) OUTGOING: 0 -
i) 6 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0 -
ii) -
6 no.40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0

28,000.00
MV PANEL FOR { ENTRY &+7 LEVEL FLOOR (SECTION -2)} : as mentioned above Set 2 14,000

0 -
5.05 OT / ICU PANEL 0 -
a) INCOMER: 0 -
2 Nos. MCCB as per following details/ specifications: 0 -
-
200 Amps,415 volts, FP 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection and E/ F Module.

-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP -
0
indication (LED Type)

1 No. 0 to 500 V Digital voltmeter with selector switch. 0 -

Digital ammeter with selector switch with one set Suitable C.Ts. 0 -

0 -
b) BUSBARS: 0 -
400 Amp TPN Aluminium busbars 0 -

0 -
c) OUTGOING: 0 -

i) -
12 no.63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0

14,000.00
OT / ICU PANEL as mentioned above Set 1 14,000

-
5.06 Main MV PANEL Computer Panel (LEVEL +1 (SECTION -1 ) 0 -
a) INCOMER: 0 -
2 Nos. MCCB as per following details/ specifications: -
-
200 Amps,415 volts, FP 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection and E/ F Module.

-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP -
0
indication (LED Type)

1 No. 0 to 500 V Digital voltmeter with selector switch. 0 -

Digital ammeter with selector switch with one set Suitable C.Ts. 0 -

0 -
b) BUSBARS: 0 -
400 Amp TPN Aluminium busbars 0 -
0 -
c) OUTGOING: 0 -
i) 2 Nos. MCCB as per following details / specifications: 0 -
-
125 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection.

-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

-
ON, OFF, TRIP indication (LED Type). 0

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -

ii) 8 Nos. MCCB as per following details / specifications: 0 -


-
63 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection.

-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

-
ON, OFF, TRIP indication (LED Type). 0

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -

iii) 6 no. 25 Amps , 240 volts, 9 KA ,Double Pole, Miniature Circuit Breaker. 0 -

0 -
14,000.00
MV PANEL Computer Panel (LEVEL +1 (SECTION -1 ) as mentioned above Set 1 14,000

5.07 MV PANEL Computer Panel (LEVEL +1 (SECTION -2 ) 0 -


a) INCOMER: 0 -
-
125 Amps,415 volts, FP 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection and E/F module.

-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP -
0
indication (LED Type)
1 No. 0 to 500 V Digital voltmeter with selector switch. 0 -

Digital ammeter with selector switch with one set Suitable C.Ts. 0 -

0 -
b) BUSBARS: 0 -
300 Amp TPN Aluminium busbars 0 -
0 -
c) OUTGOING: 0 -
i) 8 Nos. MCCB as per following details / specifications: 0 -
-
63 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection.

-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

-
ON, OFF, TRIP indication (LED Type). 0

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -

ii) 6 no. 25 Amps , 240 volts, 9 KA ,Double Pole, Miniature Circuit Breaker. 0 -

0 -
14,000.00
MV PANEL Computer Panel (LEVEL +1 SECTION-2) as mentioned above Set 1 14,000

0 -

HSCC_NEIGRIHMS_Shillong Est-E 6_R1


Installation Total
S.No. Description. Unit. Quantity
Rate Amount
5.08 -
SUB COMPUTER/ UPS PANEL (SECTION -1 {Level+2,+3,+4,+5,+6,+7}& SECTION -2
0
{ Level+2,+3,+4,+5,+6,+7 & Entry Floor} )

a) INCOMER: 0 -
-
63 Amps,415 volts, FP 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal magnetic
0
release having variable current settings of O/L, S/C protection and E/F module.
-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP -
0
indication (LED Type)
1 No. 0 to 500 V Digital voltmeter with selector switch. 0 -

Digital ammeter with selector switch with one set ofsuitable C.Ts. 0 -

0 -
b) BUSBARS: 0 -
300 Amp TPN Aluminium busbars 0 -
c) OUTGOING: 0 -

i) -
6 no. 25 Amps , 240 volts, 9 KA ,Double Pole, Miniature Circuit Breaker. 0

104,000.00
SUB COMPUTER/ UPS PANEL (SECTION -1 {Level+2,+3,+4,+5,+6,+7}& SECTION -2
Set 13 8,000
{ Level+2,+3,+4,+5,+6,+7 & Entry Floor} ) as mentioned Above

5.09 LIFT PANEL (SECTION-1 & SECTION-2) 0 -


a) INCOMER: 0 -
-
160 Amps,415 volts, FP 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection and E/F module.

-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP -
0
indication (LED Type)

1 No. 0 to 500 V Digital voltmeter with selector switch. 0 -

Digital ammeter with selector switch with one set Suitable C.Ts. 0 -

0 -
b) BUSBARS: 0 -
300 Amp TPN Aluminium busbars 0 -
0 -
c) OUTGOING: 0 -
i) 4 Nos. MCCB as per following details / specifications: 0 -
-
63 Amps,415 volts, FP, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal magnetic
0
release having variable current settings of O/L, S/C protection.

-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

-
ON, OFF, TRIP indication (LED Type). 0

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -

0 -

LIFT PANEL (SECTION-1 & SECTION-2) as mentioned above Set 2 8,000 16,000.00

0 -
5.10 EQUIPMENT PANEL : Regional Cancer Hospital 0 -
A) INCOMER: 0 -

800 Amp 415 volts, 35 KA FP MCCB with microprocessor based release having variable -
0
current settings of O/L, S/C & inbuilt E/F protection release.
-
Extended rotary operating mechanism with door interlock with defeat feature and padlock
0
facility. MCCB should be with spreader link and phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP -
0
indication (LED Type)
-
Separate fault indication for O/L, S/C, & E/F to be provided on Panel Door.

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -

1 No. 0 to 500 V Digital voltmeter with selector switch. 0 -

0 -
B) BUSBARS : 0 -

1000 Amps Phase TPN busbars of aluminium. 0 -


0 -
C) OUTGOING: 0 -
i) 2 Nos. MCCB as per following details/ specifications: 0 -
-
400 Amp 415 volts, 35 KA TP+NL MCCB with microprocessor based release having variable
0
current settings of O/L, S/C & inbuilt E/F protection release.

-
Extended rotary operating mechanism with door interlock with defeat feature and padlock
0
facility. MCCB should be with spreader link and phase barriers.

ON, OFF, TRIP indication (LED Type) 0 -

Separate fault indication for O/L, S/C, & E/F to be provided on Panel Door. -

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -

ii) 3 Nos. MCCB as per following details/ specifications: 0 -


-
320 Amp 415 volts, 35 KA TP+NL MCCB with microprocessor based release having variable
0
current settings of O/L, S/C & inbuilt E/F protection release.

Extended rotary operating mechanism with door interlock with defeat feature and padlock -
0
facility. MCCB should be with spreader link and phase barriers.
ON, OFF, TRIP indication (LED Type) 0 -

Separate fault indication for O/L, S/C, & E/F to be provided on Panel Door. -

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -

0 -
iii) 2 Nos. MCCB as per following details/ specifications: 0 -
-
250 Amp 415 volts, 35 KA TP+NL MCCB with microprocessor based release having variable
0
current settings of O/L, S/C & inbuilt E/F protection release.

Extended rotary operating mechanism with door interlock with defeat feature and padlock -
0
facility. MCCB should be with spreader link and phase barriers.

ON, OFF, TRIP indication (LED Type) 0 -

Separate fault indication for O/L, S/C, & E/F to be provided on Panel Door. -
-
Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0

0 -
iv) 4 Nos. MCCB as per following details/ specifications: 0 -

160 Amp 415 volts, 35 KA TP+NL MCCB with thermal magnetic release having variable -
0
current settings of O/L, S/C protection.
-
Extended rotary operating mechanism with door interlock with defeat feature and padlock
0
facility. MCCB should be with spreader link and phase barriers.

ON, OFF, TRIP indication (LED Type) 0 -

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -

0 -
EQUIPMENT PANEL as mentioned above : Set 1 30,000 30,000.00
0 -
NURSING COLLEGE 0 -
5.11 MV PANEL: NURSING COLLEGE (SECTION -1 (LOCATION : GROUND FLOOR ELEC. -
0
ROOM)
a) INCOMER: 0 -
630 Amp 415 volts, 35 KA FP MCCB with microprocessor based release having variable -
0
current settings of O/L, S/C & inbuilt E/F protection release.
-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP -
0
indication (LED Type)

Separate fault indication for O/L, S/C, & E/F to be provided on Panel Door. -

1 No. 0 to 500 V Digital voltmeter with selector switch. 0 -


Digital ammeter with selector switch with one set Suitable C.Ts. 0 -

0 -
b) BUSBARS: 0 -
800 Amp TPN Aluminium busbars 0 -
0 -
c) OUTGOING: 0 -
i) 2 Nos. MCCB as per following details / specifications: 0 -
320 Amp 415 volts, 35 KA TP+NL MCCB with microprocessor based release having variable -
0
current settings of O/L, S/C & inbuilt E/F protection release.
-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

-
Separate fault indication for O/L, S/C, & E/F to be provided on Panel Door.

ON, OFF, TRIP indication (LED Type) 0 -

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -

0 -
ii) 2 Nos. MCCB as per following details / specifications: 0 -
250 Amp 415 volts, 35 KA TP+NL MCCB with microprocessor based release having variable -
0
current settings of O/L, S/C & inbuilt E/F protection release.
-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

-
Separate fault indication for O/L, S/C, & E/F to be provided on Panel Door.

ON, OFF, TRIP indication (LED Type) 0 -

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -

0 -
iii) 2 Nos. MCCB as per following details / specifications: 0 -
63 Amp 415 volts, 35 KA TP+NL MCCB with thermal magnetic release having variable current -
0
settings of O/L, S/C protection.
-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

ON, OFF, TRIP indication (LED Type) 0 -


Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -
0 -
iv) 11 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0 -
v) -
8 no.40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0

MV PANEL (NORMAL PANEL)Section -1 : as mentioned above Set 1 30,000 30,000.00


0 -
5.12 MV PANEL: NURSING COLLEGE (SECTION -2 LOCATION : GROUND FLOOR ELEC. -
0
ROOM)
a) INCOMER: 0 -
320 Amp 415 volts, 35 KA (Ics= Icu), FP MCCB with variable current settings and having -
0
microprocessor based O/L, S/C & inbuilt E/F protection release.

HSCC_NEIGRIHMS_Shillong Est-E 7_R1


Installation Total
S.No. Description. Unit. Quantity
Rate Amount
Extended rotary operating mechanism with door interlocking with defeat feature and padlock -
0
facility. MCCB should have spreader links & phase barriers.

Separate fault indication for O/L, S/C, & E/F to be provided on Panel Door. -

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP -
0
indication (LED Type)
1 No. 0 to 500 V Digital voltmeter with selector switch. 0 -
Digital ammeter with selector switch with one set Suitable C.Ts. 0 -
0 -
b) BUSBARS: 0 -
500 Amp FP Aluminium busbars 0 -
0 -
c) OUTGOING: 0 -
i) 2 Nos. MCCB as per following details / specifications: 0 -
-
63 Amps,415 volts, TP+NL, 35 KA (Ics= Icu),Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C .

Extended rotary operating mechanism with door interlocking with defeat feature and padlock -
0
facility. MCCB should have spreader links & phase barriers.

ON, OFF, TRIP indication (LED Type) 0 -

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -
0 -
ii) -
11 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0

iii) -
8 no.40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breakr. 0

30,000.00
MV PANEL NURSING COLLEGE (SECTION -2 ): as mentioned above Set 1 30,000

0 -
5.13 MV PANEL: NURSING COLLEGE (EMERGENCY PANEL LOCATION : GROUND FLOOR -
0
ELEC. ROOM)
a) INCOMER: 0 -
-
250 Amp 415 volts, 35 KA (Ics= Icu), FP MCCB with variable current settings and having
0
microprocessor based O/L, S/C & inbuilt E/F protection release.

-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP -
0
indication (LED Type)
-
Separate fault indication for O/L, S/C, & E/F to be provided on Panel Door.
1 No. 0 to 500 V Digital voltmeter with selector switch. 0 -
Digital ammeter with selector switch with one set Suitable C.Ts. 0 -

0 -
b) BUSBARS: 0 -
300 Amp TPN Aluminium busbars 0 -
0 -
c) OUTGOING: 0 -
i) 2 Nos. MCCB as per following details / specifications: 0 -
200Amps,415 volts, TP+NL, 35 KA (Ics= Icu),Moulded Case Circuit Breaker with thermal -
0
magnetic release having variable current settings of O/L, S/C protection.
-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

ON, OFF, TRIP indication (LED Type) 0 -

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -
0 -
ii) 4 Nos. MCCB as per following details / specifications: 0 -
-
63 Amps,415 volts, TP+NL, 35 KA (Ics= Icu),Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection.

-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

ON, OFF, TRIP indication (LED Type) 0 -

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -

0 -
iii) -
4 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0

iv) -
8 no.40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0

14,000.00
MV PANEL (Emergency) : as mentioned above Set 1 14,000

5.14 MAIN COMPUTER/ UPS PANEL NURSING COLLEGE 0 -


a) INCOMER: 0 -
2 Nos. MCCB as per following details / specification -
100 Amps,415 volts, FP, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal -
0
magnetic release having variable current settings of O/L, S/C protection and E/ F Module.
-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP -
0
indication (LED Type)
-
Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0

0 -
b) BUSBARS: 0 -
300 Amp TPN Aluminium busbars 0 -
c) OUTGOING: 0 -
i) 2 Nos. MCCB as per following details / specifications: 0 -
-
63 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection.

-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

ON, OFF, TRIP indication (LED Type) 0 -


-
Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0

iii) 12 no. 32 Amps , 240 volts, 9 KA ,Double Pole, Miniature Circuit Breaker 0 -
0 -
8,000.00
MAIN COMPUTER/ UPS PANEL NURSING COLLEGE (SECTION -1) as mentioned above Set 1 8,000

5.15 SUB COMPUTER/ UPS PANEL NURSING COLLEGE-(SECTION -2) 0 -


a) INCOMER: 0 -
63 Amps,415 volts, FP, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal magnetic -
0
release having variable current settings of O/L, S/C protection and E/ F Module.
-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP -
0
indication (LED Type)
-
Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0

0 -
b) BUSBARS: 0 -
300 Amp TPN Aluminium busbars 0 -
c) OUTGOING: 0 -
i) 12 no. 32 Amps , 240 volts, 9 KA ,Double Pole, Miniature Circuit Breaker. 0 -
0 -
SUB COMPUTER/ UPS PANEL NURSING COLLEGE-(SECTION -2) as mentioned above Set 1 8,000 8,000.00

0 -

MEDICAL COLLEGE 0 -
5.16 MV PANEL (NORMAL): MEDICAL COLLEGE (SECTION -1) (G. FLOOR LEVEL-1929.75) 0 -
a) INCOMER: 0 -
-
630 Amp 415 volts, 35 KA (Ics= Icu), FP MCCB with variable current settings and having
0
microprocessor based O/L, S/C & inbuilt E/F protection release.

-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP -
0
indication (LED Type)

Separate fault indication for O/L, S/C, & E/F to be provided on Panel Door. -

1 No. 0 to 500 V Digital voltmeter with selector switch. 0 -

Digital ammeter with selector switch with one set Suitable C.Ts. 0 -

0 -
b) BUSBARS: 0 -
800 Amp FP Aluminium busbars 0 -
0 -
c) OUTGOING: 0 -
i) 2 Nos. MCCB as per following details / specifications: 0 -
320 Amp 415 volts, 35 KA (Ics= Icu), TP+NL MCCB with variable current settings and having -
0
microprocessor based O/L, S/C & inbuilt E/F protection release.
-
ON, OFF, TRIP indication (LED Type) 0

Separate fault indication for O/L, S/C, & E/F to be provided on Panel Door. -

-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

Digital ammeter with selector switch with one set Suitable C.Ts. 0 -

0 -
ii) 2 Nos. MCCB as per following details / specifications: 0 -
-
160 Amps,415 volts, TP+NL 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection.

ON, OFF, TRIP indication (LED Type) 0 -


-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

Digital ammeter with selector switch with one set Suitable C.Ts. 0 -

0 -
iii) 3 Nos. MCCB as per following details / specifications: 0 -

-
125 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection.

ON, OFF, TRIP indication (LED Type) 0 -

Extended rotary operating mechanism with door interlocking with defeat feature and padlock -
0
facility. MCCB should have spreader links & phase barriers.

Digital ammeter with selector switch with one set Suitable C.Ts. 0 -

0 -
iv) 6 Nos. MCCB as per following details / specifications: 0 -
100 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal -
0
magnetic release having variable current settings of O/L, S/C protection .
ON, OFF, TRIP indication (LED Type) 0 -
Extended rotary operating mechanism with door interlocking with defeat feature and padlock -
0
facility. MCCB should have spreader links & phase barriers.
Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -

HSCC_NEIGRIHMS_Shillong Est-E 8_R1


Installation Total
S.No. Description. Unit. Quantity
Rate Amount
0 -
v) 2 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0 -
vi) 6 no.40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0 -
14,000.00
MV PANEL (NORMAL): MEDICAL COLLEGE (SECTION -1) (G. FLOOR LEVEL-1929.75) :
Set 1 14,000
as mentioned above

0 -
5.17 -
MV PANEL (NORMAL): MEDICAL COLLEGE {(SECTION -1) (1st FLOOR LEVEL-
1933.50 & 2nd FLOOR LEVEL-1937.25)}{(SECTION -2) (1st FLOOR LEVEL-1933.50 & 0
4th FLOOR LEVEL-1944.75)}

a) INCOMER: 0 -
-
125 Amps,415 volts, FP, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection and E/ F Module.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock -
0
facility. MCCB should have spreader links & phase barriers.
R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP -
0
indication (LED Type)
1 No. 0 to 500 V Digital voltmeter with selector switch. 0 -
Digital ammeter with selector switch with one set Suitable C.Ts. 0 -
0 -
b) BUSBARS: 0 -
300 Amp TPN Aluminium busbars 0 -
0 -
c) OUTGOING: 0 -
i) 8 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0 -
0 -
56,000.00
MV PANEL (NORMAL): MEDICAL COLLEGE {(SECTION -1) (1st FLOOR LEVEL-
1933.50 & 2nd FLOOR LEVEL-1937.25)}{(SECTION -2) (1st FLOOR LEVEL-1933.50 & Set 4 14,000
4TH FLOOR LEVEL-1944.75)}as mentioned above

0 -
5.18 -
MV PANEL (NORMAL): MEDICAL COLLEGE {(SECTION -1) (LG FLOOR LEVEL - 1926,
4th FLOOR LEVEL -1944.75 & 5TH FLOOR LEVEL1948.50) & (SECTION -2) (3rd FLOOR 0
LEVEL -1941 & 5TH FLOOR LEVEL1948.50)}

a) INCOMER: 0 -
-
100 Amps,415 volts, FP, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection and E/ F Module.

-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP -
0
indication (LED Type)

1 No. 0 to 500 V Digital voltmeter with selector switch. 0 -

Digital ammeter with selector switch with one set Suitable C.Ts. 0 -
0 -
b) BUSBARS: 0 -
300 Amp TPN Aluminium busbars 0 -
0 -
c) OUTGOING: 0 -
i) 4 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0 -
ii) 4 no. 40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0 -
0 -
110,000.00
MV PANEL (NORMAL): MEDICAL COLLEGE {(SECTION -1) (LG FLOOR LEVEL - 1926,
4th FLOOR LEVEL -1944.75 & 5TH FLOOR LEVEL1948.50) & (SECTION -2) (3rd FLOOR Set 5 22,000
LEVEL -1941 & 5TH FLOOR LEVEL1948.50)}:as mentioned above

0 -
5.19 -
MV PANEL (NORMAL): MEDICAL COLLEGE (SECTION -2) (G. FLOOR LEVEL-1929.75) 0

a) INCOMER: 0 -
320 Amp 415 volts, 35 KA (Ics= Icu),FP MCCB with variable current settings and having -
0
microprocessor based O/L, S/C & inbuilt E/F protection release.
R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP -
0
indication (LED Type)
-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

Separate fault indication for O/L, S/C, & E/F to be provided on Panel Door. -
1 No. 0 to 500 V Digital voltmeter with selector switch. 0 -
Digital ammeter with selector switch with one set Suitable C.Ts. 0 -
0 -
b) BUSBARS: 0 -
500 Amp FP Aluminium busbars 0 -
0 -
c) OUTGOING: 0 -
i) 1 Nos. MCCB as per following details / specifications: 0 -
200 Amps,415 volts, TP+NL, 35 KA (Ics= Icu),Moulded Case Circuit Breaker with thermal -
0
magnetic release having variable current settings of O/L, S/C protection .
ON, OFF, TRIP indication (LED Type) 0 -
Extended rotary operating mechanism with door interlocking with defeat feature and padlock -
0
facility. MCCB should have spreader links & phase barriers.
Digital ammeter with selector switch with one set Suitable C.Ts. 0 -
0 -
ii) 4 Nos. MCCB as per following details / specifications: 0 -
125 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal -
0
magnetic release having variable current settings of O/L, S/C protection.
-
ON, OFF, TRIP indication (LED Type) 0

-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

Digital ammeter with selector switch with one set Suitable C.Ts. 0 -
0 -
iii) 3 Nos. MCCB as per following details / specifications: 0 -
100 Amps,415 volts, TP+NL, 35 KA Moulded Case Circuit Breaker with thermal magnetic -
0
release having variable current settings of O/L, S/C protection .
-
ON, OFF, TRIP indication (LED Type) 0

-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -
0 -
iv) 6 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0 -
v) 2 no.40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0 -
MV PANEL (NORMAL): MEDICAL COLLEGE (SECTION -2) (G. FLOOR LEVEL- 14,000.00
Set 1 14,000
1929.75)) : as mentioned above
0 -
0 -
5.20 -
MV PANEL (NORMAL): MEDICAL COLLEGE (SECTION -1) (3rd FLOOR LEVEL -1941) &
0
(SECTION -2) (2nd FLOOR LEVEL -1937.25)

a) INCOMER: 0 -
200 Amps,415 volts, FP, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal -
0
magnetic release having variable current settings of O/L, S/C protection and E/ F Module.
R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP -
0
indication (LED Type)
-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

1 No. 0 to 500 V Digital voltmeter with selector switch. 0 -


Digital ammeter with selector switch with one set Suitable C.Ts. 0 -
0 -
b) BUSBARS: 0 -
300 Amp TPN Aluminium busbars 0 -
0 -
c) OUTGOING: 0 -
i) -
8 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0

0 -
28,000.00
MV PANEL (NORMAL): MEDICAL COLLEGE (SECTION -1) (3rd FLOOR LEVEL -1941) &
Set 2 14,000
(SECTION -2) (2nd FLOOR LEVEL -1937.25) :as mentioned above

0 -
5.21 MV PANEL (EMERGENCY): MEDICAL COLLEGE (SECTION -1) (G. FLOOR LEVEL- -
0
1929.75)
a) INCOMER: 0 -
-
630 Amp 415 volts, 35 KA (Ics= Icu), FP MCCB with variable current settings and having
0
microprocessor based O/L, S/C & inbuilt E/F protection release.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP -
0
indication (LED Type)
-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

Separate fault indication for O/L, S/C, & E/F to be provided on Panel Door. -
1 No. 0 to 500 V Digital voltmeter with selector switch. 0 -
Digital ammeter with selector switch with one set Suitable C.Ts. 0 -
0 -
b) BUSBARS: 0 -
800 Amp FP Aluminium busbars 0 -
0 -
c) OUTGOING: 0 -
i) 2 Nos. MCCB as per following details / specifications: 0 -
-
320 Amp 415 volts, 35 KA (Ics= Icu), FP MCCB with variable current settings and having
0
microprocessor based O/L, S/C & inbuilt E/F protection release.

-
ON, OFF, TRIP indication (LED Type) 0

-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

Separate fault indication for O/L, S/C, & E/F to be provided on Panel Door. -
-
Digital ammeter with selector switch with one set Suitable C.Ts. 0

0 -
ii) 2 Nos. MCCB as per following details / specifications: 0 -
200 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal -
0
magnetic release having variable current settings of O/L, S/C protection.
ON, OFF, TRIP indication (LED Type) 0 -
-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

Digital ammeter with selector switch with one set Suitable C.Ts. 0 -
0 -
iii) 9 Nos. MCCB as per following details / specifications: 0 -
100 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal -
0
magnetic release having variable current settings of O/L, S/C protection.
ON, OFF, TRIP indication (LED Type) 0 -
Extended rotary operating mechanism with door interlocking with defeat feature and padlock -
0
facility. MCCB should have spreader links & phase barriers.
Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -
iv) 3 Nos. MCCB as per following details / specifications: 0 -

HSCC_NEIGRIHMS_Shillong Est-E 9_R1


Installation Total
S.No. Description. Unit. Quantity
Rate Amount
-
63 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection.
ON, OFF, TRIP indication (LED Type) 0 -
Extended rotary operating mechanism with door interlocking with defeat feature and padlock -
0
facility. MCCB should have spreader links & phase barriers.
Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -
0 -
v) -
6 no.40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0

MV PANEL (Emergency): MEDICAL COLLEGE (SECTION -1) (G. FLOOR LEVEL- 14,000.00
Set 1 14,000
1929.75)) : as mentioned above
0 -
5.22 MV PANEL (EMERGENCY): MEDICAL COLLEGE (SECTION -2) (G. FLOOR LEVEL- -
0
1929.75)
a) INCOMER: 0 -
320 Amp 415 volts, 35 KA (Ics= Icu), FP MCCB with variable current settings and having -
0
microprocessor based O/L, S/C & inbuilt E/F protection release.
R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP -
0
indication (LED Type)

Separate fault indication for O/L, S/C, & E/F to be provided on Panel Door. -
-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

1 No. 0 to 500 V Digital voltmeter with selector switch. 0 -


-
Digital ammeter with selector switch with one set Suitable C.Ts. 0

0 -
b) BUSBARS: 0 -
500 Amp FP Aluminium busbars 0 -
0 -
c) OUTGOING: 0 -
0 -
i) 7 Nos. MCCB as per following details / specifications: 0 -
-
100 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection.

-
ON, OFF, TRIP indication (LED Type) 0

-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -
ii) 2 Nos. MCCB as per following details / specifications: 0 -
-
63 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection .

ON, OFF, TRIP indication (LED Type) 0 -

-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -
0 -
iii) 8 no.40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0 -
0 -
MV PANEL (Emergency): MEDICAL COLLEGE (SECTION -2) (G. FLOOR LEVEL- 14,000.00
Set 1 14,000
1929.75)) : as mentioned above
0 -
5.23 -
MV PANEL(EMERGENCY): MEDICAL COLLEGE {SECTION -1 (LGF LEVEL - 1926),
(1ST.FLOOR LEVEL-1933.50) ,(2ND FLOOR LEVEL-1937.25)& (3rd FLOOR LEVEL
-1941),(4th FLOOR- 1944.75)& (5th FLOOR LEVEL-1948.50)} & {SECTION -2 0
1ST.FLOOR LEVEL-1933.50) ,(2ND FLOOR LEVEL-1937.25)& (3rd FLOOR LEVEL -1941),
(4th FLOOR- 1944.75)& (5th FLOOR LEVEL-1948.50)}

a) INCOMER: 0 -
100 Amps,415 volts, FP, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal -
0
magnetic release having variable current settings of O/L, S/C protection and E/ F Module.
-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.
-
R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP
0
indication (LED Type)

1 No. 0 to 500 V Digital voltmeter with selector switch. 0 -


Digital ammeter with selector switch with one set Suitable C.Ts. 0 -
0 -
b) BUSBARS: 0 -
300 Amp TPN Aluminium busbars 0 -
0 -
c) OUTGOING: 0 -
i) 6 no. 40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0 -
ii) 2 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0 -
0 -
242,000.00
MV PANEL(EMERGENCY): MEDICAL COLLEGE {SECTION -1 (LGF LEVEL - 1926),
(1ST.FLOOR LEVEL-1933.50) ,(2ND FLOOR LEVEL-1937.25)& (3rd FLOOR LEVEL
-1941),(4th FLOOR- 1944.75)& (5th FLOOR LEVEL-1948.50)} & {SECTION -2 Set 11 22,000
1ST.FLOOR LEVEL-1933.50) ,(2ND FLOOR LEVEL-1937.25)& (3rd FLOOR LEVEL -1941),
(4th FLOOR- 1944.75)& (5th FLOOR LEVEL-1948.50)} :as mentioned above

0 -
5.24 MAIN COMPUTER/ UPS PANEL MEDICAL COLLEGE-(SECTION -1) 0 -
a) INCOMER: 0 -
2 Nos. MCCB as per following details / specifications: -
160 Amps,415 volts, FP, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal -
0
magnetic release having variable current settings of O/L, S/C protection and E/ F Module.
-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP -
0
indication (LED Type)

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -

0 -
b) BUSBARS: 0 -
300 Amp TPN Aluminium busbars 0 -
c) OUTGOING: 0 -
i) 2 Nos. MCCB as per following details / specifications: 0 -
-
100 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection.

-
ON, OFF, TRIP indication (LED Type) 0

-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

-
Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0

ii) 9 Nos. MCCB as per following details / specifications: 0 -


-
63 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection.

-
ON, OFF, TRIP indication (LED Type) 0

Extended rotary operating mechanism with door interlocking with defeat feature and padlock -
0
facility. MCCB should have spreader links & phase barriers.

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -

iii) 4 no. 32 Amps , 240 volts, 9 KA ,Double Pole, Miniature Circuit Breaker. 0 -
0 -
14,000.00
MAIN COMPUTER/ UPS PANEL MEDICAL COLLEGE-(SECTION -1) as mentioned above Set 1 14,000

0 -
5.25 MAIN COMPUTER/ UPS PANEL MEDICAL COLLEGE-(SECTION -2) 0 -
a) INCOMER: 0 -
-
100 Amps,415 volts, FP 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal magnetic
0
release having variable current settings of O/L, S/C protection and E/ F Module.

-
R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP
0
indication (LED Type)
-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -
0 -
b) BUSBARS: 0 -
300 Amp TPN Aluminium busbars 0 -
c) -
OUTGOING: 0

i) 8 Nos. MCCB as per following details / specifications: 0 -


-
63 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection .

-
ON, OFF, TRIP indication (LED Type) 0

-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -
iii) 4 no. 32 Amps , 240 volts, 9 KA ,Double Pole, Miniature Circuit Breaker. 0 -
0 -
8,000.00
MAIN COMPUTER/ UPS PANEL MEDICAL COLLEGE-(SECTION -2) as mentioned above Set 1 8,000

0 -
5.26 -
SUB COMPUTER/ UPS PANEL MEDICAL COLLEGE -(SECTION -1 &2) 0

0 -
a) INCOMER: 0 -
-
63 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection and E/ F Module.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP -
0
indication (LED Type)
-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -
0 -
b) BUSBARS: 0 -
300 Amp TPN Aluminium busbars 0 -
c) OUTGOING: 0 -
i 8 no. 32 Amps , 240 volts, 9 KA ,Double Pole, Miniature Circuit Breaker. 0 -
0 -
SUB COMPUTER/ UPS PANEL MEDICAL COLLEGE -(SECTION -1 &2) as mentioned 88,000.00
Set 11 8,000
above

0 -

UG -1 & UG -2 HOSTELS 0 -

5.27 NORMAL MAIN MV PANEL {UG HOSTEL-1& UG HOSTEL-2 SECTION- B (LOCATION : -


0
ELECTRICAL ROOM GROUND FLOOR)}
a) INCOMER: 0 -

HSCC_NEIGRIHMS_Shillong Est-E 10_R1


Installation Total
S.No. Description. Unit. Quantity
Rate Amount
-
400 Amp 415 volts, 35 KA (Ics= Icu), FP MCCB with variable current settings and having
0
microprocessor based O/L, S/C & inbuiltE/F protection release.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP -
0
indication (LED Type)
Separate fault indication for O/L, S/C, & E/F to be provided on Panel Door. -
-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.
1 No. 0 to 500 V Digital voltmeter with selector switch. 0 -
Digital ammeter with selector switch with one set Suitable C.Ts. 0 -
0 -
b) BUSBARS: 0 -
500 Amp TPN Aluminium busbars 0 -
0 -
c) OUTGOING: 0 -
i) 2 Nos. MCCB as per following details / specifications: 0 -
200 Amps,415 volts, TP+NL, (Ics= Icu), Moulded Case Circuit Breaker with thermal magnetic -
0
release having variable current settings of O/L, S/C protection.
ON, OFF, TRIP indication (LED Type) 0 -

Extended rotary operating mechanism with door interlocking with defeat feature and padlock -
0
facility. MCCB should have spreader links & phase barriers.

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -

0 -
ii) 2 Nos. MCCB as per following details / specifications: 0 -
63 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal -
0
magnetic release having variable current settings of O/L, S/C protection .

ON, OFF, TRIP indication (LED Type) 0 -

Extended rotary operating mechanism with door interlocking with defeat feature and padlock -
0
facility. MCCB should have spreader links & phase barriers.
Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -
0 -
iii) 10 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0 -
iv) 6 no. 40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0 -
NORMAL MAIN MV PANEL {UG HOSTEL-1& UG HOSTEL-2 SECTION- B }: as mentioned 28,000.00
Set 2 14,000
above
0 -
5.28 NORMAL MAIN MV PANEL {UG HOSTEL-1& UG HOSTEL-2 SECTION- A (LOCATION : -
0
ELECTRICAL ROOM GROUND FLOOR)}
a) INCOMER: 0 -
200 Amps,415 volts, FP, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal -
0
magnetic release having variable current settings of O/L, S/C protection and E/ F Module.
-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

-
R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP
0
indication (LED Type)

1 No. 0 to 500 V Digital voltmeter with selector switch. 0 -

Digital ammeter with selector switch with one set Suitable C.Ts. 0 -

0 -
b) BUSBARS: 0 -
300 Amp TPN Aluminium busbars 0 -
0 -
c) OUTGOING: 0 -
i) -
10 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0

ii) -
6 no. 40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0

NORMAL MV PANEL SECTION- A : as mentioned above Set 2 8,000 16,000.00


0 -
5.29 EMERGENCY MV PANEL {UG HOSTEL-1& UG HOSTEL-2 (LOCATION : ELECTRICAL -
0
ROOM GROUND FLOOR)}
a) INCOMER: 0 -
-
100 Amps,415 volts, FP, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection and E/ F Module.

-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

-
R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP
0
indication (LED Type)
1 No. 0 to 500 V Digital voltmeter with selector switch. 0 -
Digital ammeter with selector switch with one set Suitable C.Ts. 0 -
0 -
b) BUSBARS: 0 -
300 Amp TPN Aluminium busbars 0 -
0 -
c) OUTGOING: 0 -
i) 3 Nos. MCCB as per following details / specifications: 0 -
-
63 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection .

-
ON, OFF, TRIP indication (LED Type) 0

-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

-
Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0

ii) -
4 no. 40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0

EMERGENCY MV PANEL {UG HOSTEL-1& UG HOSTEL-2} : as mentioned above Set 2 8,000 16,000.00
0 -
INTERNEE HOSTEL , UG-3 , Nursing -1 Nursing -2 0 -
5.30 NORMAL MAIN MV PANEL (INTERNEE HOSTEL , UG-3 , Nursing -1& Nursing -2) -
0
SECTION- B (LOCATION : ELECTRICAL ROOM GROUND FLOOR)
a) INCOMER: 0 -
-
320 Amp 415 volts, 35 KA (Ics= Icu), FP MCCB with variable current settings and having
0
microprocessor based O/L, S/C & inbuilt E/F protection release.

-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

-
R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP
0
indication (LED Type)

Separate fault indication for O/L, S/C, & E/F to be provided on Panel Door. -
1 No. 0 to 500 V Digital voltmeter with selector switch. 0 -
Digital ammeter with selector switch with one set Suitable C.Ts. 0 -
0 -
b) BUSBARS: 0 -
500 Amp TPN Aluminium busbars 0 -
0 -
c) OUTGOING: 0 -
i) 2 Nos. MCCB as per following details / specifications: 0 -
-
160 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection .

-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -

0 -
ii) 2 Nos. MCCB as per following details / specifications: 0 -
-
63 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection .

-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

-
ON, OFF, TRIP indication (LED Type) 0

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -

0 -
iii) -
10 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0

iv) -
4 no. 40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0

NORMAL MAIN MV PANEL (INTERNEE HOSTEL , UG-3 , Nursing -1& Nursing -2) 42,000.00
Set 3 14,000
SECTION- B : as mentioned above
0 -
5.31 NORMAL MAIN MV PANEL (INTERNEE HOSTEL , UG-3 , Nursing -1& Nursing -2) -
0
SECTION- A (LOCATION : ELECTRICAL ROOM GROUND FLOOR)
a) INCOMER: 0 -

-
160 Amps,415 volts, FP, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection and E/ F Module.

-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP -
0
indication (LED Type)

1 No. 0 to 500 V Digital voltmeter with selector switch. 0 -

Digital ammeter with selector switch with one set Suitable C.Ts. 0 -
0 -
b) BUSBARS: 0 -
300 Amp TPN Aluminium busbars 0 -
0 -
c) -
OUTGOING: 0

i) -
8 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0
ii) 6 no. 40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0 -
NORMAL MV PANEL (INTERNEE HOSTEL , UG-3 , Nursing -1& Nursing -2) SECTION- A 24,000.00
Set 3 8,000
: as mentioned above
0 -
5.32 -
EMERGENCY MV PANEL (INTERNEE HOSTEL , UG-3 , Nursing -1& Nursing -2)
0
(LOCATION : ELECTRICAL ROOM GROUND FLOOR)

a) INCOMER: 0 -
-
100Amps,415 volts, FP, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal magnetic
0
release having variable current settings of O/L, S/C protection and E/ F Module.

-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP -
0
indication (LED Type)

1 No. 0 to 500 V Digital voltmeter with selector switch. 0 -

Digital ammeter with selector switch with one set Suitable C.Ts. 0 -
0 -
b) BUSBARS: 0 -

HSCC_NEIGRIHMS_Shillong Est-E 11_R1


Installation Total
S.No. Description. Unit. Quantity
Rate Amount
300 Amp TPN Aluminium busbars 0 -
0 -
c) OUTGOING: 0 -
i) 3 Nos. MCCB as per following details / specifications: 0 -
-
63 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection.

-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

-
ON, OFF, TRIP indication (LED Type) 0

-
Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0

ii) -
4 no. 40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0

EMERGENCY MV PANEL (INTERNEE HOSTEL , UG-3 , Nursing -1& Nursing -2) : as 42,000.00
Set 3 14,000
mentioned above
0 -
5.33 -
NORMAL MV PANEL (UG DINING BLOCK & NURSING DINING BLOCK) 0

a) INCOMER: 0 -
200 Amps,415 volts, FP, 35 KA Moulded Case Circuit Breaker with thermal magnetic release -
0
having variable current settings of O/L, S/C protection and E/ F Module.
-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP -
0
indication (LED Type)
1 No. 0 to 500 V Digital voltmeter with selector switch. 0 -
Digital ammeter with selector switch with one set Suitable C.Ts. 0 -
0 -
b) BUSBARS: 0 -
300 Amp TPN Aluminium busbars 0 -
0 -
c) OUTGOING: 0 -
i) 4 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0 -
ii) 8 no. 40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0 -
NORMAL MV PANEL (UG DINING BLOCK & NURSING DINING BLOCK) : as mentioned 16,000.00
Set 2 8,000
above
0 -
5.34 -
EMERGENCY MV PANEL (UG DINING BLOCK & NURSING DINING BLOCK) 0

a) INCOMER: 0 -
-
100 Amps,415 volts, FP, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection and E/ F Module.
-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP -
0
indication (LED Type)
1 No. 0 to 500 V Digital voltmeter with selector switch. 0 -
Digital ammeter with selector switch with one set Suitable C.Ts. 0 -
0 -
b) BUSBARS: 0 -
300 Amp TPN Aluminium busbars 0 -
0 -
c) OUTGOING: 0 -
i) 2 Nos. MCCB as per following details / specifications: 0 -
63 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal -
0
magnetic release having variable current settings of O/L, S/C protection
-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

-
ON, OFF, TRIP indication (LED Type) 0

-
Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0

ii) 2 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0 -
iii) 6 no. 40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0 -
NORMAL MV PANEL (UG DINING BLOCK & NURSING DINING BLOCK) : as mentioned 16,000.00
Set 2 8,000
above
0 -
5.35 -
MV PANEL GUEST HOUSE (LOCATION : ELECTRICAL ROOM GROUND FLOOR) 0

a) INCOMER: 0 -
-
250 Amp 415 volts, 35 KA (Ics= Icu), FP MCCB with variable current settings and having
0
microprocessor based O/L, S/C & inbuilt E/F protection release

-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP -
0
indication (LED Type)

Separate fault indication for O/L, S/C, & E/F to be provided on Panel Door. -
1 No. 0 to 500 V Digital voltmeter with selector switch. 0 -
Digital ammeter with selector switch with one set Suitable C.Ts. 0 -
0 -
b) BUSBARS: 0 -
400 Amp TPN Aluminium busbars 0 -
0 -
c) OUTGOING: 0 -
i) 2 Nos. MCCB as per following details / specifications: 0 -
-
200 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection .

-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -

0 -
ii) 4 Nos. MCCB as per following details / specifications: 0 -
-
63 Amps,415 volts, TP+NL, 35 KA (Ics= Icu),Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock -
0
facility. MCCB should have spreader links & phase barriers.

ON, OFF, TRIP indication (LED Type) 0 -

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0 -

0 -
iii) -
6 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0

iv) 6 no. 40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0 -

MV PANEL GUEST HOUSE (LOCATION : ELECTRICAL ROOM GROUND FLOOR) : as 8,000.00


Set 1 8,000
mentioned above
0 -
TOTAL SUB HEAD 5 : MV PANEL 0 -
0 -
6.00 SUBHEAD 6 : UPS SYSTEM 0 -
6.01 UPS 80 KVA. (REGIONAL CANCER CENTER OT'S AND ICU'S) 0 -
-
Supply, Installation, Testing and Commissioning of micro processor based 2 x 80 KVA at 0.8
power factor at out put. with over all efficiency of minimum 94% at full load, True Online
Double Conversion UPS using PWM IGBT technology. 3 Phase input 415 V +10% -15% and 0
input frequency 50 Hertz plus minus 5%, 3 phase input and 3 phase output. UPS operating in
parallel redundant load sharing mode (N+1) configration and each comprising of the following:

-
(a) 125% rated Rectifier cum charger unit + 100% rated inverter, integrated in UPS module 0

-
(b) IGBT Rectifier input for achieving THDi<5% and Input power factor of greater than 0.99 0

(c)100% rated external isolation transformer of H-class Delta/Star at the UPS output, after -
0
static bypass including cabling between UPS and transformer
(d) 100% rated Inbuilt static switch 0 -
(f) 100% rated Inbuilt Maintenance Bypass 0 -
-
(g) 100% rated moulded case circuit breaker having I thermal, magnetic and automatic U/V
0
trip mechanics

(i) RS 485 port for BMS connectivity 0 -


(j) Supplying and installing Built-in suitable air-circulating fan . 0 -
Input phase reversal protection to be provided as standard, UPS should shift on battery and -
0
provide alarm.
-
(k) Supply, Installation, Testing and Commissioning of 12 V sealed maintenance free, Valve
Regulated Lead Acid (VRLA) batteries for providing 30 minutes back up on each UPS at full 0
load at 0.8 power factor.

-
(l) Supply, Fixing of battery rack for each UPS system along with inteconnecting links, BCB
0
etc as required

(m) UPS Should be provided with of Static Bypass Module having High Switching Frequency -
Microprocessor Based with builtin Technical Protections like Short Circuit, Overload, High/
Low Voltage cutoff protection of load from source inclusive of Bypass facility, SBM is
activated during malfunctioning conditions of Load like:-
-Short Circuit
0
-Overload
-Over temprature
-Bypassing of particular load if reqd.

UPS 80 KVA SYSTEM AS MENTIONED ABOVE. SET 1 26,000 26,000.00


0 -
6.02 UPS 80 KVA. (COMPUTER POINTS ) 0 -
-
Supply, Installation, Testing and Commissioning of micro processor based 80 KVA at 0.8
power factor at out put. with over all efficiency of minimum 94% at full load, True Online
Double Conversion UPS using PWM IGBT technology. 3 Phase input 415 V +10% -15% and 0
input frequency 50 Hertz plus minus 5%, 3 phase input and 3 phase output, each comprising
of the following:

-
(a) 125% rated Rectifier cum charger unit + 100% rated inverter, integrated in UPS module 0

-
(b) IGBT Rectifier input for achieving THDi<5% and Input power factor of greater than 0.99 0

(c)100% rated external isolation transformer of H-class Delta/Star at the UPS output, after -
0
static bypass including cabling between UPS and transformer
(d) 100% rated Inbuilt static switch 0 -
(f) 100% rated Inbuilt Maintenance Bypass 0 -
-
(g) 100% rated moulded case circuit breaker having I thermal, magnetic and automatic U/V
0
trip mechanics

(i) RS 485 port for BMS connectivity 0 -


(j) Supplying and installing Built-in suitable air-circulating fan . 0 -
Input phase reversal protection to be provided as standard, UPS should shift on battery and -
0
provide alarm.
-
(k) Supply, Installation, Testing and Commissioning of 12 V sealed maintenance free, Valve
Regulated Lead Acid (VRLA) batteries for providing 30 minutes back up on each UPS at full 0
load at 0.8 power factor.

-
(l) Supply, Fixing of battery rack for each UPS system along with inteconnecting links, BCB
0
etc as required

HSCC_NEIGRIHMS_Shillong Est-E 12_R1


Installation Total
S.No. Description. Unit. Quantity
Rate Amount
(m) UPS Should be provided with of Static Bypass Module having High Switching Frequency -
Microprocessor Based with builtin Technical Protections like Short Circuit, Overload, High/
Low Voltage cutoff protection of load from source inclusive of Bypass facility, SBM is
activated during malfunctioning conditions of Load like:-
-Short Circuit
0
-Overload
-Over temprature
-Bypassing of particular load if reqd.

UPS 80 KVA SYSTEM AS MENTIONED ABOVE. SET 2 22,000 44,000.00


-
6.03 UPS 120 KVA. (COMPUTER POINTS ) 0 -
Supply, Installation, Testing and Commissioning of micro processor based 80 KVA at 0.8 -
power factor at out put. with over all efficiency of minimum 94% at full load, True Online
Double Conversion UPS using PWM IGBT technology. 3 Phase input 415 V +10% -15% and 0
input frequency 50 Hertz plus minus 5%, 3 phase input and 3 phase output, each comprising
of the following:
-
(a) 125% rated Rectifier cum charger unit + 100% rated inverter, integrated in UPS module 0

-
(b) IGBT Rectifier input for achieving THDi<5% and Input power factor of greater than 0.99 0

(c)100% rated external isolation transformer of H-class Delta/Star at the UPS output, after -
0
static bypass including cabling between UPS and transformer
(d) 100% rated Inbuilt static switch 0 -

(f) 100% rated Inbuilt Maintenance Bypass 0 -


-
(g) 100% rated moulded case circuit breaker having I thermal, magnetic and automatic U/V
0
trip mechanics

(i) RS 485 port for BMS connectivity 0 -


(j) Supplying and installing Built-in suitable air-circulating fan . 0 -
Input phase reversal protection to be provided as standard, UPS should shift on battery and -
0
provide alarm.
(k) Supply, Installation, Testing and Commissioning of 12 V sealed maintenance free, Valve -
Regulated Lead Acid (VRLA) batteries for providing 30 minutes back up on each UPS at full 0
load at 0.8 power factor.
(l) Supply, Fixing of battery rack for each UPS system along with inteconnecting links, BCB -
0
etc as required
(m) UPS Should be provided with of Static Bypass Module having High Switching Frequency -
Microprocessor Based with builtin Technical Protections like Short Circuit, Overload, High/
Low Voltage cutoff protection of load from source inclusive of Bypass facility, SBM is
activated during malfunctioning conditions of Load like:-
-Short Circuit
0
-Overload
-Over temprature
-Bypassing of particular load if reqd.

UPS 120 KVA SYSTEM AS MENTIONED ABOVE. SET 1 22,000 22,000.00


0 -
TOTAL SUBHEAD 6 : UPS SYSTEMS 0 -
0 -
SUB HEAD- 7: MCB DISTRIBUTION BOARDS. 0 -
7.00 MCB DISTRIBUTION BOARD 0 -
7.01 -
Supplying & fixing following way, three pole and neutral sheet steel, MCB distribution board,
415 volts,on recess/surface complete with loose wire box, terminal blocks, tinned copper
busbar, neutral link, earth bar,din bar, detachable gland plate, interconnections, phosphatized 0
and powder coated including earthing connection bolt etc. as per technical specifications and
as required.(but without MCB & RCCB).

i 4 way (8+12), Double door Each 82 1,750 143,500.00


ii 6 way (8+12) Double door Each 169 1,900 321,100.00
iii 8 way (8+24), Double door Each 157 2,400 376,800.00
0 -
7.02 -
Supplying & fixing following way, single pole and neutral,sheet steel, MCB distribution board,
240 volts,on recess/surface complete with loose wire box, terminal blocks, tinned copper
busbar, neutral link, earth bar,din bar, detachable gland plate, interconnections, phosphatized
0
and powder painted including earthing etc.Before procurement of DB the contractor has to
take approval of DB schedule/ drawing of each DB from the Electrical Engineer, HSCC, as
per technical specifications and as required.(but without MCB & RCCB),

i 6 way Double door Each 27 1,580 42,660.00


ii 8 way Double door Each 70 1,690 118,300.00

iii 12 way Double door Each 25 1,870 46,750.00


0 -
7.03 -
Supplying & fixing 6 Amps to 32 Amps rating, 240 volts,'B' series, miniature circuit breaker
suitable for lighting & other loads of following poles in the existing MCB DB complete with 0
connections, testing & commissioning etc. as per technical specifications & as required.

i Single pole Each 8660 90 779,400.00


ii Triple pole & neutral Each 20 90 1,800.00
0 -
7.04 -
Supplying & fixing following rating, four pole, 415 volts, Miniature Circuit Breaker (MCB),in the
existing MCB DB complete with connections, testing & commissioning etc. as per technical 0
specifications and as required.

i 25 Amps Each 47 90 4,230.00


i 40 Amps Each 131 90 11,790.00
ii 63 Amps Each 224 100 22,400.00
0 -
7.05 -
Supplying & fixing following rating, four pole, 415 volts, Residual Current Circuit Breaker
(RCCB) having a sensitivity current upto 300 mA in the existing MCB DB complete with 0
connections, testing & commissioning etc. as per technical specifications and as required.

i 25 Amps Each 33 90 2,970.00


iii 40 Amps Each 131 90 11,790.00
iv 63 Amps Each 224 100 22,400.00
0 -
7.06 -
Supplying and fixing following rating, double pole, 240 volts, MCB (B/C/D/ Curve) in the
0
existing MCB DB complete with connections, testing and commissioning etc. as required.

i 16 amps Each 87 90 7,830.00


ii 25 amp Each 31 90 2,790.00
0 -
7.07 1,665.00
Supplying and fixing Single pole Blanking plate in the existing MCB DB complete as required. Each 111 15

0 -
TOTAL SUB HEAD-7: MCB DISTRIBUTION BOARDS. 0 -
0 -
SUB HEAD 8: WIRING 0 -
8.00 WIRING 0 -
0 -
8.01 i -
Wiring for light point/fanpoint/ exhaust fan point/call bell point with 1.5 sq.mm. PVC insulated,
fire retardant low smoke (FRLS) copper conductor cable, single core/ multi strand, in steel
0
conduit (Including supplying & recess laying of MS conduit and accessories) including the
following and complete as required.
ii -
Supplying and Fixing Modular type switches (modular Bell push in case of call bell points) in
suitable size modular metal boxes, base plate & modular cover plates, space for fixing
0
electronic fan regulator in case of fan point wiring & space for fixing 5A socket on the board
etc.

iii Supplying and fixing Hexagonal fan Boxes with 3 mm thick hylem sheet covers in case of Fan -
0
Points
iv Supplying & Fixing Ceiling Rose in case of Exhaust Fan Points etc. 0 -

Note : 0 -
i) Unless otherwise specified all the conduiting work to be done in recess 0 -
0 -
Point wiring as mentioned above Group B ( HOSTEL BLOCK) Point 12730 380 4,837,400.00
Point wiring as mentioned above Group C (Non Residential) Point 3600 410 1,476,000.00
0 -
8.02 i -
Wiring for twin control light points with 1.5 sq.mm. PVC insulated, FRLS copper conductor
cable in MS conduit (including supplying and recess laying of MS conduit) including the 0
following and complete as required.

ii -
Supplying and Fixing Modular type two numbers 2 Way switches in suitable size modular
0
metal boxes, base plate & modular cover plates etc.

Note : 0 -
i) Unless otherwise specified all the conduiting work to be done in recess 0 -

Wiring for twin control light points as mentioned above Point 699 420 293,580.00
0 -
8.03 -
Wiring for Submain/ circuit wiring with following size of PVC insulated FRLS copper conductor
single core/multi strand cable in recessed steel conduit (including supply & laying of recessed 0
conduit) as required.

i 3,963,000.00
2X1.5 Sqmm with 1 No. 1.5 sqmm PVC FRLS insulated, copper conductor for earthing. Metre 52840 75

ii 1,270,600.00
2X2.5 Sqmm with 1 No. 2.5 sqmm PVC FRLS insulated, copper conductor for earthing. Metre 15882.5 80

iii 5,112,000.00
2X4 Sqmm with 1 No. 4 sqmm PVC insulated FRLS copper conductor for earthing Metre 56800 90

iv 367,400.00
2X6 Sqmm with 1 No. 6 sqmm PVC insulated FRLS copper conductor for earthing Metre 3340 110

v 209,000.00
2X10 Sqmm with 1 No. 10 sqmm PVC insulated FRLS copper conductor for earthing Metre 1900 110

vi 168,000.00
4X4 Sqmm with 2 No. 4 sqmm PVC insulated FRLS copper conductor for earthing Metre 1200 140

vii 184,500.00
4X6 Sqmm with 2 No. 6 sqmm PVC insulated FRLS copper conductor for earthing Metre 1230 150

viii 405,600.00
4X10 Sqmm with 2 No. 10 sqmm PVC insulated FRLS copper conductor for earthing Metre 2535 160

ix 423,900.00
4X16 Sqmm with 2 nos 16 sq mm PVC insulated FRLS copper conductor for earthing. Metre 2355 180

0 -
8.04 189,912.00
Supplying and fixing suitable Module GI box on surface or in recess including providing and
fixing 3 pin 5/6 amps. modular socket outlet with shutters and 5/6 amps. modular type switch
Each 2316 82
with indicator type, base plate, modular cover plate, connections etc. and all civil works
'complete as required.

0 -
8.05 Supplying and fixing suitable modular GI box on surface or in recess including providing and 216,000.00
fixing 6 pin 15/16 A modular socket outlet with shutters and 15/16 A modular switch with
Each 2400 90
indicator, base plate, modular cover plate, connections, etc. and all civil works complete as
required.
0 -
8.06 131,280.00
Supplying and fixing suitable Modular metal box on surface or in recess including providing
and fixing three nos 3 pin 5/6 amps. modular socket outlet with shutters and one no. 10 amps.
Each 547 240
modular type switch, base plate, modular cover plate, connections etc. and all civil works
'complete as required. ( For computer Points)

0 -
8.07 Supplying and fixing suitable Module metal box on surface or in recess including providing and 152,600.00
fixing two nos 3 pin 5/6 amps. & two 6 pin 15/16 amp modular socket outlet with shutters and
one no. 25 amps. modular Indicating type switch, base plate, modular cover plate, connections Each 545 280
etc. and all civil works 'complete as required. (For
Comb-1/ Bed Point)
-
8.08 39,000.00
Supplying and fixing suitable Module metal box on surface or in recess including providing and
fixing two nos 3 pin 5/6 amps. & one 6 pin 15/16 amp modular socket outlet with shutters and
one no. 20 amps. modular Indicating type switch, base plate, modular cover plate, connections Each 150 260
etc. and all civil works 'complete as required. (For
Comb-2)

HSCC_NEIGRIHMS_Shillong Est-E 13_R1


Installation Total
S.No. Description. Unit. Quantity
Rate Amount
0 -
8.09 24,800.00
Supplying and fixing suitable Modular metal box surface or in recess including providing and
fixing two nos 3 pin 5/6 amps. modular socket outlet with shutters and one no. 5 amps.
Each 155 160
modular type switch, base plate, modular cover plate, connections etc. and all civil works
'complete as required. ( COMBO POINT3 )

0 -
8.10 7,150.00
Supply and fixing following 20 Amps, 240 volts, 2P+E, Industrial Socket Outlet (with plugs) in a
metal box with 20 SP MCB in a sheet steel cover on surface or recess complete with all Each 65 110
accessories including connections, testing and commissioning etc. as required.

0 -
8.11 12,240.00
Supply and fixing following 32 Amps, 240 volts, 2P+E, Industrial Socket Outlet (with plugs) in
a metal box with 20 SP MCB in a sheet steel cover on surface or recess complete with all Each 102 120
accessories including connections, testing and commissioning etc. as required.

0 -
8.12 2,400.00
Supplying, providing & fixing cordless musical bell with batteries etc of approved make
Each 30 80
complete as required.

8.13 -
Supply and fixing following FP MCCB, 415 volts, 35 KA (Isc), Four Pole with thermal magnetic
release having variable current setting (0.8 to 1.0 In) with Extended rotary operating
mechanism including door interlocking with defeat feature and padlock facility in a sheet steel 0
enclosure on surface complete with all accessories including , connections, testing and
commissioning etc. as required.

i 63 Amp Each 30 2,000 60,000.00


ii 100 Amp Each 2 2,000 4,000.00
iii 125 Amp Each 2 3,000 6,000.00

iv 160 Amp Each 4 3,000 12,000.00

v 250 Amp Each 2 3,500 7,000.00

vi 3,500.00
320 Amp Each 1 3,500

vii 8,000.00
400 Amp Each 2 4,000

8.14 Supplying and fixing suitable Modular metal box surface or in recess including providing and 3,840.00
fixing one no.32A DPmains switch with one no. key ring modular type switch, base plate,
Each 32 120
modular cover plate, connections etc. and all civil works 'complete as required. Anchor
21770,20868 or approved equivalent) (key lock)
-

8.15 1,200.00
Supply, Installation, Testing & Commissioning of 360 degree Ceiling recess mountable 360
degree multifunction sensor that combines motion detection (PIR), Infrared remote control Each 10 120
reception (IR) and ambient light level detection (PE) into one device.

0 -

8.16 Supply, Installation, Testing & Commissioning of Standalone Ceiling Mounted Motion PIR 16,000.00
Nos. 100 160
sensor 360 degree.
0 -
8.17 Supply, Installation, Testing & Commissioning of Standalone Wall Mounted Motion PIR sensor 7,200.00
Nos. 40 180
90 degree.
-
TOTAL SUBHEAD: 8- WIRING 0 -
0 -
SUB HEAD:9 - LIGHT FIXTURE AND FANS 0 -
9.00 LIGHT FIXTURES AND FANS 0 -
0 -
9.01 Supply of following light fixture with high efficiency electronic ballast, starter, tubes/lamps, -
capacitor, reflector, diffuser, MS body/housing holder etc. complete with all fixing accessories 0
as required.
i -
1X 20 W LED box type fluorescent light fixture ( LED LINEA , Philips BN 550 WLED 20-
Each 2310
6500 with minimum system lumen 2000 or approved equivalent )

ii -
1X20 W LED box type fluorescent light fixture ( Philips TMC 501 P 1XT-LED with minimum
Each 1351
system lumen 2100 or approved equivalent )

iii -
2 X 20 W LED box type fluorescent light fixture ( Philips TMC 501 P 2XT-LED with minimum
Each 105
system lumen 4200 or approved equivalent )

iv LED recessed flush mounted light fixture ( Full Glow , Philips RC380B LED-30-6500 PSE -
OD WH Size 600x600mm / 1200 mm as per requirment with minimum system lumen 3000 Each 485
or approved equivalent )
v LED recessed flush mounted light fixture ( Sereno Philips RC869B LED-30S-6500 PSE -
W30L 120 D8 GR Size 600x600mm / 1200 mm as per requirment with minimum system Each 1377
lumen 3000 or approved equivalent )
vi LED Surface mounted light fixture (philips SP824 P LED 29S-5000 GR OD,Size -
600x600mm / 1200 mm as per requirment with minimum system lumen 3000 or approved Each 1489
equivalent )
vii -
2X 36 watt Recess mounted clean room flourscent light fixture with bottom opening and Clear
Each 62
acrylic version (Philips TBS670 2X36WTL-D FOP GT or approved equivalent).(2x36 CRF)

viii 4X 14 watt recess mounted clean room flourscent light fixture with bottom opening and and -
Clear acrylic version (Philips TBS651 4 XTL5 -14 W EB CR FOP GT or approved Each 62
equivalent).
ix -
4 X 14/2x28 watt Recess Mounted flourscent light fixture (Philips TBS 869 4XTL5 -14 W EBP
Each 150
D8 /TBS 869 2XTL5 -28 W EBP D8 or approved equivalent). (236 RMO1)

x 1X36 watt surface mounted type fluorescent light fixture with opal acrylic diffuser (Philips -
Each 348
TCS019 1XTL-D36W EBT or approved equivalent) (136AC1)
xi -
2X36 watt surface mounted type fluorescent light fixture with opal acrylic diffuser (Philips
Each 95
TCS019 2XTL-D36W EBT or approved equivalent) (236AC1)
xii -
1XTL-5 28 watt box type fluorescent light fixture without reflector(Philips TMS 122M 1XTL5
Each 400
28 W EBT or approved equivalent) (136b/136w)

xiii -
2XTL-5 28 watt box type fluorescent light fixture with reflector(Philips TMS 122M 2XTL5 28
Each 100
W EBT or approved equivalent) (236b/)
xiv -
1X 36 watt Recess Mounted flourscent light fixture (Philips TCS 306 1XTL-36W EBE or
Each 72
approved equivalent). (136 RMO1)
xv -
1 X TL-5 28 watt Surface Mounted flourscent light fixture (Philips TCS 150 1 XTL-5-28 W MI
Each 60
EBT or approved equivalent). (136 SM01)

xvi -
1X TL5-28 watt LineLUX Recess Mounted flourscent light fixture (Philips RC720B 1XTL5 -28
Each 200
W EBT OD or approved equivalent). (136 ROM1)

9.02 -
Supply of following compact fluorescent light fixture with electronic ballast, starter, capacitor,
yellow light lamps, reflector, diffuser, MS body/housing holder etc. complete with all fixing 0
accessories as required.

i -
1X10 watt Bulk Head light fixture (Philips WT202W LED6S CW PSU S1 PC or approved
Each 156
equivalent) BH

ii 1X10 watt Mirror top with Diffuser ( Crompton Greaves LINNET # LCL-10-CDL or approved -
Each 566
equivalent ) (w toilet)
iii Surface mounted Batten holder (Plastic) with 9 watt LED Each 50 -
iv -
1X18 watt wall Bracket Sri lanka (DECON:CFL-1X18 W 03WZ 01 or approved equivalent)WB Each 262

v 1X24 Watt LED Recessed flush mounted down light fixture (Philips DN194B LED 15S -6500 -
Each 240
PSU WH or approved equivalent ) (DL2)
vi 1X15 Watt LED Surface mounted down light fixture (philips DN170C LED 105-6500 PSU WH -
Each 536
or approved equivalent ) (DL)
vii -
1X18Watt LED Surface mounted down light fixture (Crompton Greaves Pearl Round
Each 1274
LCDSPL-R-18-CDL ) or approved equivalent ) DL-1

viii -
2 X 11 watt surface mounted mirror optics (Philips FCS 518 2XPLS/2P 11 W I 240 V or
Each 50
approved equivalent)
ix -
2 X 18 watt surface mounted down light frosted glass (DECON:PL-2X18 W 03NBS 01 or
Each 100
approved equivalent)
-
1 X 11 watt Bed side light Fixture (DECON:PL-05GF01 or approved equivalent) Each 270

-
1x13 W recessed flush mounted light fixture (Anchor 92472 or approved equivalent )
Each 60
(NLCM)

-
LED Recessed flush mounted light fixture (Anchor Roma Viola 89688 or approved
Each 32
equivalent ) (NLWM)
9.03 -
Supply of following ceiling fans (BEE -5 Star Rated) complete with double ball bearing, motor,
blades, downrod, canopies, capacitor, modular type electronic fan regulator, suitable for 0
operation on 230 volts, 50 Hz., 1 phase, AC supply complete as required.

i 1200 mm sweep Each 2234 -


900 mm sweep Each 50 -
0 -
9.04 Supply of 900 RPM, 300 mm (Crompton Greaves Trans Air or approved equivalent) exhaust -
fan suitable for single phase 230 volts, 50 Hz., AC supply complete with motor,
Each 398
louvers/shutters etc. complete as required.

0 -
9.05 Supply of 400 mm sweep, Crompton greaves model high flow 16'' wall mounted fan complete -
with double ball bearing, motor, blades, capacitor etc suitable for single phase 230 volts, 50 Each 6
Hz., AC supply, complete as required.
0 -
9.06 Installation, testing and commissioning of prewired, fluorescent fittings of all types, complete 779,940.00
with all accessories and tube etc. directly on ceiling/wall, including connections with 1.5
Each 8666 90
sq.mm. PVC insulated, FRLS copper conductor, single core/ multi strand cable etc. as
required.
0 -
9.07 Installation, testing and commissioning of prewired, compact fluorescent lamp fixture (CFL 319,140.00
fixtures)of all types, complete with all accessories and lamp etc. directly on ceiling/wall,
Each 3546 90
including connections with 1.5 sq.mm. PVC insulated, FRLS copper conductor, single core/
multi strand cable etc. as required.
0 -
9.08 352,320.00
Installation, testing and commissioning of ceiling fan and modular type electronic fan
regulator(Electronic regulator to be fixed in switch board) including wiring the down rod and
Each 2202 160
connection with 1.5 sqmm FR PVC insulated, copper conductor single core/multi strand cable
including providing & fixing phenolic laminated sheet cover on the fan box, etc. as required.

0 -
9.09 Installation, testing and commissioning of exhaust fan up to 400 mm sweep in the opening, 56,250.00
including making the hole to suit the size of the above fan including , fixing of louvers/ shutters Each 375 150
with frame making good the damages etc. as required.
0 -
9.10 Installation, testing and commissioning of wall mounted fan up to 400 mm sweep including 1,350.00
Each 15 90
supply and fixing wall bracket arrangement complete as required.
0 -
9.11 270.00
Supply , installation, testing and Commissioning of LED Type Aviation light Philips XGP400
Each 3 90
1xLED-K2/RD240V or approved equivalent including its wiring.

0 -
TOTAL SUBHEAD 9 : LIGHT FIXTURE & FANS 0 -
0 -
SUBHEAD 15: LT CABLES 0 -
LT CABLES 0 -
0 -
15.01 Supply of following sizes of 1.1 kV grade multicore aluminium conductor PVC sheathed -
0
armoured XLPE cable as per IS 7098.
i 3.5 Core 25 Sqmm. Metre 3300 -
ii 3.5 Core 35 Sqmm. Metre 500 -
iii 3.5 Core 50 Sqmm. Metre 3375 -

HSCC_NEIGRIHMS_Shillong Est-E 14_R1


Installation Total
S.No. Description. Unit. Quantity
Rate Amount
iv 3.5 Core 70 Sqmm. Metre 700 -
v 3.5 Core 95 Sqmm. Meter 450 -
vi 3.5 Core 120 Sqmm. Mter 800 -
vii 3.5 Core 150 Sqmm. Meter 1000 -
viii 3.5 Core 185Sqmm. Metre 1400 -
ix 3.5 Core 240 Sqmm. Metre 1000 -
x 3.5 Core 300 Sqmm. Metre 5000 -
xi 3.5 Core 400 Sqmm Metre 500 -
xii 4 Core 10Sq mm Metre 800 -
xiii 4 Core 6 Sq mm Meter 700 -
xiv 3 Core 6 Sqmm. Meter 800 -
xv 3 Core 4 Sqmm. Meter 700 -
xvi 2 Core 10 Sq mm Metre 2000 -
xvii 2 Core 16 Sq mm Meter 1500 -
0 -
15.02 Laying of one number PVC insulated and PVC sheathed power cable 1.1kV grade direct in -
ground including excavation, sand cushioning, protective covering and refilling the trench etc. 0
as required
i Up to 35 sq.mm Metre 6860 60 411,600.00
ii Above 35 Sq mm and upto 95 Sq mm Metre 3202.5 70 224,175.00
iii Above 95 Sq mm and up to 185 Sq mm Metre 2240 80 179,200.00
iv Above 185 Sq mm and up to 400 Sq mm Metre 5530 92 508,760.00
0 -
15.03 Laying of one number PVC insulated and PVC sheathed power cable 1.1kV grade direct in the -
0
existing RCC/ Hume/Stoneware/Metal pipe as required
i Up to 35 sq.mm Metre 1470 32 47,040.00
ii 26,106.00
Above 35 Sq mm and upto 95 Sq mm Metre 687 38

iii Above 95 Sq mm and up to 185 Sq mm Metre 480.75 40 19,230.00


iv Above 185 Sq mm and up to 400 Sq mm Metre 1185 50 59,250.00
0 -
15.04 Laying of one number PVC insulated and PVC sheathed power cable 1.1kV grade on surface -
0
or on existing cable tray complete as required.
i Up to 35 sq.mm Metre 1470 52 76,440.00
ii Above 35 Sq mm and upto 95 Sq mm Metre 701.75 58 40,701.50
iii Above 95 Sq mm and up to 185 Sq mm Metre 537 60 32,220.00
iv Above 185 Sq mm and up to 400 Sq mm Metre 1395 69 96,255.00
0 -
15.05 Supplying and making end termination with suitable size Aluminium lugs including double -
compression glands of following sizes of 1.1. kv grade multicore aluminium conductor PVC 0
insulated and PVC sheathed
i 3.5 Core 25 Sqmm. Each 80 220 17,600.00
ii 3.5 Core 35 Sqmm. Each 50 240 12,000.00
iii 3.5 Core 50 Sqmm. Each 60 250 15,000.00
iv 3.5 Core 70 Sqmm. Each 20 255 5,100.00
v 3.5 Core 95 Sqmm. Each 20 260 5,200.00
vi 3.5 Core 120 Sqmm. Each 40 262 10,480.00
vii 3.5 Core 150 Sqmm. Each 20 270 5,400.00
viii 3.5 Core 185Sqmm. Each 110 280 30,800.00
ix 3.5 Core 240 Sqmm. Each 90 282 25,380.00
x 3.5 Core 300 Sqmm. Each 70 290 20,300.00
xi 3.5 Core 400 Sqmm Each 20 310 6,200.00
xii 4 Core 10Sq mm Each 90 210 18,900.00
xiii 4 Core 6 Sq mm Each 120 200 24,000.00
xiv 3 Core 6 Sqmm. Each 60 190 11,400.00
xv 3 Core 4 Sqmm. Each 80 190 15,200.00

HSCC_NEIGRIHMS_Shillong Est-E 15_R1


Installation Total
S.No. Description. Unit. Quantity
Rate Amount
xvi 2 Core 10 Sq mm Each 80 170 13,600.00
0 -
TOTAL SUBHEAD 15 : LT CABLES 0 -
0 -
SUBHEAD 16: EARTHING PROTECTION 0 -
16.00 EARTHING PROTECTION 0 -
0 -
16.01 Supply and installation of one number earth pit with advance maintinance free Earthing 96,000.00
System consisting of one Number, CPRI tested copper bonded steel electrode of minimum
25 mm dia. (as per IE C62561-2 ) With a minimum coating thickness of 250 microns and
length of 3 meters, 25 kg/Electrode of earth enhancing compound (tested as per IEC-62561-7)
fill the 100mm augered hole surrounding to the electrode , SS Universal Clamp of Size Set 30 3,200
175X50X3 mm for terminal Connection including Poly Propylene Heavy duty Pit cover
including all accessories , excavation of earth, filling with back fill compound, and earth pit
marking. The Complete installation shall be as per the drawing, technical specifications and as
required
0 -
16.02 Supply and installation of one number earth pit with advance maintinance free Earthing 59,600.00
System consisting of one Number, CPRI tested copper bonded steel electrode of minimum
19 mm dia (as per IE C62561-2 ) With a minimum. coating thickness of 250 microns and
length of 3 meters. 25 kg/Electrode of earth enhancing compound (tested as per IEC-62561-
7) fill the 100mm augered hole surrounding to the electrode , SS Universal Clamp of Size Set 20 2,980
175X50X3 mm for terminal Connection including Poly Propylene Heavy duty Pit cover
including all accessories , excavation of earth, filling with back fill compound, and earth pit
marking. The Complete installation shall be as per the drawing, technical specifications and as
required
0 -
16.03 Supply and installation of one number earth pit with of advance maintinance free Earthing 145,000.00
System consisting of one Number UL Listed CPRI tested copper bonded steel electrode of
minimum 13 mm dia. (as per IE C62561-2 ) With a minimum. coating thickness of 250
microns and length of 3 meters. 25 kg/Electrode of earth enhancing compound (tested as per
IEC-62561-7) fill the 100mm augered hole surrounding to the electrode , SS Universal Clamp Set 50 2,900
of Size 175X50X3 mm for terminal Connection including Poly Propylene Heavy duty Pit cover
including all accessories , excavation of earth, filling with back fill compound, and earth pit
marking. The Complete installation shall be as per the drawing, technical specifications and as
required
0 -
16.04 23,200.00
Supply and installation of one number earth pit with of maintenance free earthing system
consisting of 1250 mm long copper bonded steel electrode of minimum 13 mm dia. tested
as per IEC 62561-2.Minimum copper coating thickness on Rod is 100 microns. 5
kg/Electrode of earth enhancing compound tested as per IEC 62561-7 fill the 75-100mm
Set 8 2,900
augured hole surrounding to the electrode.It consist the fallowing Item opper Alloy clamp
suitable Poly PropyleneHeavy duty Pit cover including all accessories , excavation of earth,
filling with back fill compound, and earth pit marking. The Complete installation shall be as per
the drawing, technical specifications and as required

HSCC_NEIGRIHMS_Shillong Est-E 16_R1


Installation Total
S.No. Description. Unit. Quantity
Rate Amount
0 -
16.05 60,000.00
Supplying and laying 25mmX5mm GI strip at 0.5m below ground level as strip earth electrode,
Metre 500 120
including soldering etc. as required.
0 -
16.06 Providing and fixing 25mmX5mm GI strip on surface/on existing cable trench/RCC pipe/GI 88,000.00
Metre 800 110
pipe or in recess for earth electrode as required.
0 -
16.07 Supplying and laying 50mmX6mm GI strip at 0.5m below ground level as strip earth 45,000.00
Metre 300 150
electrode, including soldering etc. as required.
0 -
16.08 Providing and fixing 50mmX6mm GI strip on surface/on existing cable trench/RCC pipe/GI 28,000.00
Metre 200 140
pipe or in recess for earth electrode as required.
0 -
16.09 Providing and fixing25mmX5mm Copper strip on surface/on existing cable trench/RCC pipe/GI 33,000.00
Metre 300 110
pipe or in recess for earth electrode as required.
0 -
16.10 Supplying and laying 25mmX5mm Copper strip at 0.5m below ground level as strip earth 22,000.00
Metre 200 110
electrode, including soldering etc. as required.
0 -
16.11 Supplying and laying 50mmX6mm Copper strip at 0.5m below ground level as strip earth 7,500.00
Metre 50 150
electrode, including soldering etc. as required.
0 -
16.12 Providing and fixing 50mmX6mm Copper strip on surface/on existing cable trench/RCC 15,000.00
Metre 100 150
pipe/GI pipe or in recess for earth electrode as required.
0 -
16.13 Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I.pipe from earth electrode 24,000.00
including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as Metre 200 120
required
0 -
16.14 Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode 60,000.00
including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as Metre 500 120
required.
0 -
16.15 Metre 300 36,000.00
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. 120

0 -
16.16 Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete -
with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching 0
(75 cm deep) and refilling etc as required.
i) 300 mm dia Metre 200 70 14,000.00
ii) 150 mm dia Metre 200 60 12,000.00
0 -
TOTAL SUBHEAD 16: EARTHING AS MENTIONED ABOVE 0 -
0 -
0 -
17.00 SUBHEAD 17: LIGHTENING PROTECTION 0 -
LIGHTENING PROTECTION 0 -
17.01 Supply and installation of one number earth pit with of advance maintinance free Earthing 220,400.00
System consisting of one Number UL Listed CPRI tested copper bonded steel electrode of
minimum 13 mm dia. (as per IE C62561-2 ) With a minimum. coating thickness of 250
microns and length of 3 meters. 25 kg/Electrode of earth enhancing compound (tested as per
IEC-62561-7) fill the 100mm augered hole surrounding to the electrode , SS Universal Clamp Set 76 2,900
of Size 175X50X3 mm for terminal Connection including Poly Propylene Heavy duty Pit cover
including all accessories , excavation of earth, filling with back fill compound, and earth pit
marking. The Complete installation shall be as per the drawing, technical specifications and as
required

0 -
17.02 Providing and fixing of lightening conductor finial, made of 25mm. dia. 300mm., long GI tube, 7,680.00
having single prong at top, with 85 mm. dia. 6 mm. thick GI base plate including holes etc. Each 64 120
complete as required.
0 -
17.03 Providing and and fixing GI tape 20mm X 3 mm thick on parapet or surface of wall for lightning 192,000.00
Metre 1600 120
conductor as required. (For horizontal runs).
0 -
17.04 Providing and and fixing GI tape 20mm X 3 mm thick on parapet or surface of wall for lightning 264,000.00
Metre 2200 120
conductor as required. (For vertical runs).
0 -
17.05 Providing and fixing testing joint, made of 20mmX3mm thick GI strip, 125 mm. long, with 4 -
no.'s of GI bolts, nuts, check nuts, bar shaddles, and spring washers etc. complete as Each 76
required.
0 -

Providing and laying GI tape, 32 mm X 6 mm thick, from test joint upto earth electrode directly 129,600.00
Metre 1080 120
in ground as required.
0 -
TOTAL SUBHEAD 17: LIGHTENING PROTECTION 0 -
0 -
SUBHEAD 22: OUT DOOR LIGHTING 0 -
22.00 OUT DOOR LIGHTING 0 -
0 -
22.01 -
Supply, erection, testing and commissioning of external swaged steel tubular pole with
0
following specifications & items :

i 9.0 Mtrs. high swaged steel tubular pole with arm length around 1.5 Metre, the construction of -
the pole shall be as per IS:2713 - 1980 410 SP-30 with base plate 450mmX450mmX6mm 0
complete as per requirement with two coats of spray paints of approved shade.
ii -
90 watts LED street light fixture in die cast aliuminum body with 90 watts LED lamp complete
with control gear, cover etc. similar to Compton Greeves LSTO45-90/CDL or approved
0
equivalent including its wiring with 2X2.5 sq.mm. PVC insulated, FRLS copper conductor and
1.5 sqmm PVC insulated, FRLS copper earth wire from control box complete as required.

iii Suitable size 32 A DP MS Control box with 2 no. incoming and outgoing terminals and 2 nos. -
0
tap-out terminal with 6A DP MCB complete as required - 1 Set
iv -
Suitable number(s) 40mm dia Class-B GI Pipe(s) from above control box to upto 0.5 metre
0
below ground level for power cable entry

v -
Providing foundation including excavation, shuttering, alingment of poles, casting etc.
0
including lean concrete at the bottom as per CPWD/ BIS specifications.

vi -
The above installations shall be completed as CPWD specifications and as required 0

a. 380,000.00
Steet Tubular Poles(9M) Single Arm as mention above Set 100 3,800

b. Steet Tubular Poles (9M) same as above but for Double Arm as mention above Set 30 3,900 117,000.00

0 -
22.02 -
Supply, installation, testing and commissioning of external post top lantern with following
0
accessories and complete as required :

i 4m high (3.3m above ground) 80mm dia GI pole as approved, adopting socket at top for -
fixture mentioned below, base plate 300 x 300 x 6mm and provision for mounting junction box 0
etc. - 1 set.

HSCC_NEIGRIHMS_Shillong Est-E 17_R1


Installation Total
S.No. Description. Unit. Quantity
Rate Amount
ii 1 x 40 LED Post top lantern with 40W LED lamp (Crompton Greeves LPTO-40-CDL or -
equivalent) and its wiring with 2 x 2.5 sq.mm PVC insulated copper wire and 1.5 sqmm PVC 0
insulated copper earth wire from control box .
iii -
Suitable size 20A DP MS Control box with 2 no. incoming and outgoings terminals and 2 nos.
0
tap-out terminal with 1 nos. 5A HRC fuses complete 1 set.

iv -
Suitable number(s) 40mm dia Class-B GI Pipe(s) from above control box to upto 0.5 metre
0
below ground level for power cable entry

v Providing 400x400x1000mm deep 1:3:6 ratio cement concrete including excavation shuttering -
alignment of poles casting etc. including 100mm thick lean concrete shall be provided at the 0
bottom
Supply, installation, testing and commissioning of external post top lantern as mentioned 100,000.00
Set 50 2,000
above
0 -
22.03 40,000.00
Supply, installation, testing and commissioning of Post top lantern 1 x 40 LED Post top
lantern with 40W LED lamp (Crompton Greeves LPTO-40-CDL or equivalent) and its wiring
Set 20 2,000
with 2 x 2.5 sq.mm PVC insulated copper wire and 1.5 sqmm PVC insulated copper earth wire
from control box .

0 -
22.04 12,000.00
Supply, installation, testing and commissioning of bollard lamps 1X10watts LED Light Fixture
Each 60 200
(Crompton Greeves LBLS1-10-CDl (LIARA) or equivalent) control box - 1 set.

0 -

22.05 HIGH MAST LIGHT 0 -

-
Supply, Installation , Testing and Commisioning of 20 M High Masts with following: 0

-
20 Mrt High mast, material of construction as per IS 5986/ BSEN 10025. Febricated in two
parts of 10.3 metre each with base and top dia 410 mm and 150 mm aprox respectively,
thickness 4 mm and 3 mm of bottom section and top section repectively, Base Plate -dia 570
mmX 30 mm thick, PCD foundation bolt 490 mm, Head Frame & Lantern crrriage with 12 nos
metal halide fixture as per Crompton Greaves catalogue no. FDH1624_2x400 W MHT with
2x400 W MH flood light with minimum lumen/lamp 35,000, including its foundation, all Nos 2
accessories like double drum winch, SS wire rope, trailing cableL-stopper, manual operating
handle, motor mounting, lightening arresters, junction box, double dome LED aviation light,
wiring of all light fixture from junction box , earthing of the pole etc including any other item
required for the proper functioning of the high mast complete as per technical specification and
as required.

-
Road Lighting Panel 0 -

HSCC_NEIGRIHMS_Shillong Est-E 18_R1


Installation Total
S.No. Description. Unit. Quantity
Rate Amount
22.06 -
Supply, installation, testing and commissioning of following outdoor type with canopy, IP-54
protected M.V. cubicle type totally enclosed, free standing type, dust, damp and vermin proof,
MV Panel, busbars, M.V. danger notice plate, interconnections with suitable capacity
0
aluminium leads/solid aluminium strips/rods, connection of incoming and outgoing cables with
thimbles, stove enamelled painted and having following incoming and outgoing switchgears
complete as required.
INCOMER: 0 -
-
100 Amps,415 volts, TP+NL, 35 KA Moulded Case Circuit Breaker with thermal magnetic
0
release having variable current settings .

-
R,Y&B phase indicating lamp (LED type) with 2A control SP MCB ,ON, OFF , TRIP for MCCB 0

-
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

1 Set of timer switch & 100A TP contactor with nuetral link (for street lights control) . 0 -

BUSBARS: 0 -
100 Amp TPN Aluminium busbars 0 -
0 -
OUTGOING: 0 -
i 30 Nos. 16 Amp 415 volts, DP MCB 0 -
Feeder Pillar as mention above Set 12 -
0 -
22.07 -
Spiral earthing made out of 6 SWG GI wire , 50mm Dia, 115 turns closely wound ,1.5 mtr
below ground, earth pit of 350 Dia., 1.5 mtr depth including providing charcoal and salt for
Set 155.25
earthing at alternate layers of 300 mm depth (total 3 layers),connections etc. complete as
required.

-
TOTAL SUBHEAD 22: OUTDOOR LIGHTING 0

-
23.00 -
SUBHEAD 23 SOLAR PHOTVOLTAIC POWER GENERATION 0

23.00 -
SOLAR PHOTVOLTAIC POWER GENERATION

23.01 -
Supply, installation, testing and commissioning of grid interactive roof top solar photovoltaic
power generation system of following grid interactive solar inverters, Data logger with
0
temperature and irriadance sensor, AC Distribution Board,Cables, interconnections, chemical
earthing, GI Strip(25mmx5mm) etc. complete as required.
i -
20KWp Set 2

ii -
Extra for providing space frame for above 20KWp solar system. Set 2

-
TOTAL SUBHEAD 23: SOLAR PHOTVOLTAIC POWER GENERATION 0
Plumbing BOQ -
0.00 -
WATER SUPPLY PUMP PANEL -(Nursing College, UG Medical College and Regional -
14A 0.00
Cancer Centre)
Supply, installation, testing and commissioning of following M.V. cubicle type totally enclosed, -
powder coated, wall mounted/ free standing type, dust, damp and vermin proof, indoor type
Distribution Board/Panel complete with busbars, M.V. danger notice plate, interconnections
0.00
with suitable capacity aluminium leads/solid aluminium strips/rods, connection of incoming and
outgoing cables with thimbles, and having following incoming and outgoing switchgears
complete as required.
INCOMER : 0.00 -
125 Amp 415 volts, 35 KA (Isc), FP MCCB with thermal magnetic release having variable -
0.00
current settings.
R,Y&B phase indicating lamp (LED type) with 2A control SP MCB 0.00 -
"ON" ,"OFF" and "TRIP" LED indicating lamp and 2A control SP MCBs 0.00 -
Extended rotary operating mechanism with door interlock with defeat feature and padlock -
0.00
facility. MCCB should have spreader links & phase barriers.
1 no. Digital voltmeter with selectot switch 0.00 -
1 no Digital ammeter with selector switch with one set of suitable C.T. s 0.00 -
BUSBARS : 0.00 -
300 Amp TPN busbars of aluminium 0.00 -
0.00 -
OUTGOINGS : 0.00 -
i 2 Sets of following( Treated water transfer pump to terrace tank) 0.00 -
1 No. 32 Amp. 415 volts,35 KA, three Pole, MCCB with thermal magnetic release having -
0.00
variable current settings.
Extended rotary operating mechanism with door interlock with defeat feature and padlock -
0.00
facility. MCCB should have spreader links & phase barriers.
-
1 No. 3 Phase, fully automatic star-delta starter of 10 HP with thermal overload relay,
0.00
contactor, Timer, Push Buttons and switch, Single phase Preventer etc complete as required.
Digital ammeter with selector switch with one set of suitable CT,s. 0.00 -
1 Set of phase indicating lamp with 2A SP control MCBs 0.00 -
LED indicating Lamps for "ON" , "OFF" & "TRIP". 0.00 -
0.00 -
ii 2 Sets of following (Raw water transfer pump) 0.00 -
1 No. 32 Amp. 415 volts,35 KA, three Pole, MCCB with thermal magnetic release having 0.00 -
variable current settings.
Extended rotary operating mechanism with door interlock with defeat feature and padlock -
0.00
facility. MCCB should have spreader links & phase barriers.
1 No. 3 Phase, DOL starter of 7.5 HP with thermal overload relay, contactor, Push Buttons -
0.00
and switch, Single phase preventer etc complete as required.
Digital ammeter with selector switch with one set of suitable CT,s. 0.00 -
1 Set of phase indicating lamp with 2A SP control MCBs 0.00 -
LED indicating Lamps for "ON" , "OFF" & "TRIP". 0.00 -
0.00 -
iii 2 Sets of following (Raw water (filter) feed pump) 0.00 -
1 No. 32 Amp. 415 volts,25 KA, three Pole, MCCB with thermal magnetic release having -
0.00
variable current settings.
Extended rotary operating mechanism with door interlock with defeat feature and padlock -
0.00
facility. MCCB should have spreader links & phase barriers.
1 No. 3 Phase, DOL starter of 5 HP with thermal overload relay, contactor, Push Buttons and -
0.00
Switches, single phase preventer etc complete as required.
Digital ammeter with selector switch with one set of suitable CT,s. 0.00 -
1 Set of phase indicating lamp with 2A SP control MCBs 0.00 -
LED indicating Lamps for "ON" , "OFF" & "TRIP". 0.00 -
0.00 -
6 Sets of following (Softner transfer pump,softner feed pump & Submersible Drainage -
iv 0.00
Pump)
1 No. 32 Amp. 415 volts,35 KA, three Pole, MCCB with thermal magnetic release having -
0.00
variable current settings.
Extended rotary operating mechanism with door interlock with defeat feature and padlock -
0.00
facility. MCCB should have spreader links & phase barriers.
1 No. 3 Phase, DOL starter of 2 HP with thermal overload relay, contactor, Push Buttons and -
0.00
Switches, single phase preventer etc complete as required.
Digital ammeter with selector switch with one set of suitable CT,s. 0.00 -
1 Set of phase indicating lamp with 2A SP control MCBs 0.00 -
LED indicating Lamps for "ON" , "OFF" & "TRIP". 0.00 -
0.00 -
v 2 Sets of following (TUBE WELL) 0.00 -
1 No. 32 Amp. 415 volts,32 KA, three Pole, MCCB with thermal magnetic release having -
0.00
variable current settings.
Extended rotary operating mechanism with door interlock with defeat feature and padlock -
0.00
facility. MCCB should have spreader links & phase barriers.
Digital ammeter with selector switch with one set of suitable CT,s. 0.00 -
1 Set of phase indicating lamp with 2A SP control MCBs 0.00 -
LED indicating Lamps for "ON" , "OFF" & "TRIP". 0.00 -
0.00 -
WATER SUPPLY PUMP Panel as mentioned above Set 1.00 -
SubTotal(Pump panel) 0.00 -
0.00 -
14B WATER SUPPLY PUMP PANEL -UG Hostels and Nursing Hostels 0.00 -
Supply, installation, testing and commissioning of following M.V. cubicle type totally enclosed, -
powder coated, wall mounted/ free standing type, dust, damp and vermin proof, indoor type
Distribution Board/Panel complete with busbars, M.V. danger notice plate, interconnections
0.00
with suitable capacity aluminium leads/solid aluminium strips/rods, connection of incoming and
outgoing cables with thimbles, and having following incoming and outgoing switchgears
complete as required.
0.00 -
INCOMER : 0.00 -
125 Amp 415 volts, 35 KA (Isc), FP MCCB with thermal magnetic release having variable -
0.00
current settings.
R,Y&B phase indicating lamp (LED type) with 2A control SP MCB 0.00 -
"ON" ,"OFF" and "TRIP" LED indicating lamp and 2A control SP MCBs 0.00 -
Extended rotary operating mechanism with door interlock with defeat feature and padlock -
0.00
facility. MCCB should have spreader links & phase barriers.
1 no. Digital voltmeter with selectot switch 0.00 -
1 no Digital ammeter with selector switch with one set of suitable C.T. s 0.00 -
0.00 -
BUSBARS : 0.00 -
300 Amp TPN busbars of aluminium 0.00 -
0.00 -
OUTGOINGS : 0.00 -
0.00 -
i 4 Sets of following(treated water transfer pump to terrace) 0.00 -
1 No. 32 Amp. 415volts, 35 KA, three Pole, MCCB with thermal magnetic release having -
0.00
variable current settings.
Extended rotary operating mechanism with door interlock with defeat feature and padlock -
0.00
facility. MCCB should have spreader links & phase barriers.
1 No. 3 Phase, DOL starter of 5 HP with thermal overload relay, contactor, Push Buttons and -
0.00
Switches, single phase preventer etc complete as required.
Digital ammeter with selector switch with one set of suitable CT,s. 0.00 -
1 Set of phase indicating lamp with 2A SP control MCBs 0.00 -
LED indicating Lamps for "ON" , "OFF" & "TRIP". 0.00 -
0.00 -
ii 2 Sets of following (raw water transfer pump) 0.00 -
1 No. 32 Amp. 415 volts, 35 KA, three Pole, MCCB with thermal magnetic release having -
0.00
variable current settings.
Extended rotary operating mechanism with door interlock with defeat feature and padlock -
0.00
facility. MCCB should have spreader links & phase barriers.
1 No. 3 Phase, DOL starter of 3 HP with thermal overload relay, contactor, Push Buttons and -
0.00
Switches, single phase preventer etc complete as required.
Digital ammeter with selector switch with one set of suitable CT,s. 0.00 -
1 Set of phase indicating lamp with 2A SP control MCBs 0.00 -
LED indicating Lamps for "ON" , "OFF" & "TRIP". 0.00 -
0.00 -
iii 4 Sets of following (raw water (filter) feed pump 7 Submersible Drainage Pump) 0.00 -
1 No. 32 Amp. 415 volts, 35 KA, three Pole, MCCB with thermal magnetic release having -
0.00
variable current settings.
Extended rotary operating mechanism with door interlock with defeat feature and padlock -
0.00
facility. MCCB should have spreader links & phase barriers.
1 No. 3 Phase, DOL starter of 2 HP with thermal overload relay, contactor, Push Buttons and -
0.00
Switches, single phase preventer etc complete as required.
Digital ammeter with selector switch with one set of suitable CT,s. 0.00 -
1 Set of phase indicating lamp with 2A SP control MCBs 0.00 -
LED indicating Lamps for "ON" , "OFF" & "TRIP". 0.00 -
0.00 -
iv 2 Sets of following ( TUBE WELL) 0.00 -
1 No. 32 Amp. 415 volts,35 KA, three Pole, MCCB with thermal magnetic release having -
0.00
variable current settings.
Extended rotary operating mechanism with door interlock with defeat feature and padlock -
0.00
facility. MCCB should have spreader links & phase barriers.
Digital ammeter with selector switch with one set of suitable CT,s. 0.00 -
1 Set of phase indicating lamp with 2A SP control MCBs 0.00 -
LED indicating Lamps for "ON" , "OFF" & "TRIP". 0.00 -
0.00 -
WATER SUPPLY PUMP Panel as mentioned above each 1.00 -
6.00 Starter for Tubewell -
1 No. 3 Phase, fully automatic star Delta starter of 10 HP with thernal overload relay with -
inbuilt/separatre single phase preventer, contactor,Timer,Push Button and Auto manual
i each 2.00
selector switch etc including its mounting on the wall and control cables for starting of the
motor complete as required
-
SubTotal(Pump panel) -
1.00 FIRE FIGHTING SYSTEM -
-
0.0 -
Supplying, Installation, Testing & Commissioning modular construction master control annciation panel -
for sprinkler with provision for requider No. of Zone (30% additional spares),eachsprinkler hydrant will
1.25 0.0
have atleast 4 zone on each floor as approved by engineer.The panel shall have but not limited to the
following arrangment.
a) Indication of Zone sprinkler 0.0 -
b) Indication of zone fault 0.0 -
c) Fire/fault hooter 0.0 -
d) Alarm cancel for fire/fault 0.0 -
e) Battery for emergency back up of 4 Hrs. Set 2.0 -

HSCC_NEIGRIHMS_Shillong Est-E 19_R1


Installation Total
S.No. Description. Unit. Quantity
Rate Amount
0.0 -
1.00 FIRE FIGHTING SYSTEM 0.0 -
A Fire Fighting Panel(Electrical ) 0.0 -
-
Supply, installation, testing and commissioning of following M.V. cubicle type totally enclosed,powder
coated, free standing type, dust, damp and vermin proof, indoor type Distribution Board/Panel
complete with busbars, M.V. danger notice plate, interconnections with suitable capacity aluminium 0.0
leads/solid aluminium strips/rods, connection of incoming and outgoing cables with thimbles and having
following incoming and outgoing switchgears complete as required.

INCOMER : 0.0 -
630 Amp 415 volts, 35 KA (Isc), FP MCCB with microprocessor based release having variable current
0.0 -
settings.
Extended rotary operating mechanism with door interlock with defeat feature and padlock facility.
0.0
-
MCCB should have spreader links & phase barriers.
R,Y&B phase indicating lamp (LED type) with 2A control SP MCB 0.0 -
"ON" , "OFF" and "TRIP" LED indicating lamp and 2A control SP MCBs 0.0 -
1 no. Digital voltmeter with selector switch 0.0 -
1 no. Digital ammeter with selector switch with one set of suitable set of C.T. s 0.0 -
BUSBARS : 0.0 -
800 Amp TPN busbars of aluminium 0.0 -
OUTGOINGS : 0.0 -
0.0 -
i 2 Sets of following (Main Fire Pump & Sprinkler Pump) 0.0 -
1 No. 200 Amp. 415 volts,35 KA, three Pole, MCCB with thermal magnetic release having variable
0.0 -
current settings.
Extended rotary operating mechanism with door interlock with defeat feature and padlock facility.
0.0 -
MCCB should have spreader links & phase barriers.
-
1 No. 3 Phase, fully automatic star-delta starter of 90 HP with thermal overload relay, contactor, Timer,
0.0
Push Buttons, Auto-manual selector switch, single phase preventer etc complete as required.

Digital ammeter with selector switch with one set of suitable CT,s. 0.0 -
1 Set of phase indicating lamp with 2A SP control MCBs 0.0 -
LED indicating Lamps for "ON" , "OFF" & "TRIP" . 0.0 -
0.0 -
ii 1 Sets of following (Jockey Pump) 0.0 -
1 No. 32 Amp. 415 volts, 35 KA, three Pole, MCCB with thermal magnetic release having variable
0.0 -
current settings.
Extended rotary operating mechanism with door interlock with defeat feature and padlock facility.
0.0 -
MCCB should have spreader links & phase barriers.
1 No. 3 Phase, DOL starter of 7.5 HP with thermal overload relay, contactor, Push Buttons, Auto-
0.0 -
manuel selector switch, Single phase preventer etc complete as required.
Digital ammeter with selector switch with one set of suitable CT,s. 0.0 -
1 Set of phase indicating lamp with 2A SP control MCBs 0.0 -
LED indicating Lamps for "ON" , "OFF" & "TRIP" . 0.0 -
0.0 -
iii 8.00 1 Set of following (in a separate cubicle) 0.0 -
One no. Diesel engine auto starting kit with all necessary relay, controls, wiring etc to start 90 HP diesel -
engine when electrical driven fire pump fail to start including one no rectifier circuit, battery charger, 0.0
batteries, DC Voltmeter, DC Ammeter etc. complete as required.
Fire Fighting Panel as mentioned above Set 1.0 -
0.0 -
TERRACE PUMP PANEL (For Each building: to be fed through MV panel of Top floor of that -
2.00 NS
building)
0.0

-
Supply, installation, testing and commissioning of following M.V. cubicle type totally enclosed, powder
coated, wall mounted/ free standing type, dust, damp and vermin proof, indoor type Distribution
Board/Panel complete with busbars, M.V. danger notice plate, interconnections with suitable capacity 0.0
aluminium leads/solid aluminium strips/rods, connection of incoming and outgoing cables with thimbles,
and having following incoming and outgoing switchgears complete as required.

INCOMER : 0.0 -
63 Amp 415 volts, 35 KA (Isc), FP MCCB with thermal magnetic release having variable current
0.0 -
settings.
R,Y&B phase indicating lamp (LED type) with 2A control SP MCB -
"ON" ,"OFF" and "TRIP" LED indicating lamp and 2A control SP MCBs -
Extended rotary operating mechanism with door interlock with defeat feature and padlock facility. -
MCCB should have spreader links & phase barriers.
1 no. Digital voltmeter with selectot switch -
1 no Digital ammeter with selector switch with one set of suitable C.T. s -
BUSBARS : -
300 Amp TPN busbars of aluminium -
-
OUTGOINGS : -
i 2 Sets of following( terrace pump ) -
1 No. 32 Amp. 415 volts, 35 KA, three Pole, MCCB with thermal magnetic release having variable -
current settings.
Extended rotary operating mechanism with door interlock with defeat feature and padlock facility. -
MCCB should have spreader links & phase barriers.
1 No. 3 Phase, fully automatic star-delta starter of 10 HP with thermal overload relay, contactor, Timer, -
Push Buttons and switch, Single phase Preventer etc complete as required.
Digital ammeter with selector switch with one set of suitable CT,s. -
1 Set of phase indicating lamp with 2A SP control MCBs -
LED indicating Lamps for "ON" , "OFF" & "TRIP". -
TERRACE PUMP Panel as mentioned above Each 12.0 -

Total Amount 31,701,434.50

HSCC_NEIGRIHMS_Shillong Est-E 20_R1


Project Name:- Construction of Under Graduate Medical College & Hostel, Regional Cancer Centre &
Guest House and Nursing College and Hostel including internal & external Electrical, HVAC, PHE, fire
fighting, external developments works etc. and their Maintenance during Defect Liability Period at
NEIGRIHMS, Mawdiangdiang Shillong, Meghalaya.

PART-B- Optional Item


Bill of Quantity for Optional item (shall not considered for evaluation) for Part B – Comprehensive
operation and Maintenance

Name of Bidder

S. No. Description Total Qty Unit

Comprehensive Maintenance for five years and operation during defect liability period for the works
namely
• HVAC/air conditioning
• Internal and external Electrification
• Lifts
• Comprehensive fire Protection System
• CCTV and Security System
• Solar Panel
• Modular OTs
• Medical Gases Manifold System
1.00
• Boiler
• Mortuary
• Central Hot Water Supply
• EPABX/ Communication System
• IT works
• Dish Antenna/ TV Cabling
• STP/ WTP
• Water Supply for site
• Horticulture

(The quoted rates shall become a part of financial bid but shall not be considered for the purpose of
evaluation of financial bids of the bidder. The employer ( NEIGRIHMS) reserves the right for placement
of order for this maintenance work. However the quoted rates by the bidders shall remain binding on
the bidder. The BOQ items shall be read in conjunction with a technical specification, GCC, SCC and
their quoted rates shall deem to include all works/requirements in the technical specification, GCC,
SCC etc. The quoted amount of PART-B (Comprehensive Maintenance for five year and operation
during defect liability period only) should not include the amount/liabilities/ provisions already covered
in respect of PART-A of the work i.e Construction of Under Graduate Medical College & Hostel,
Regional Cancer Centre & Guest House and Nursing College and Hostel including internal & external
Electrical, HVAC, PHE, fire fighting, external developments works etc. and their Maintenance during
Defect Liability Period at NEIGRIHMS, Mawdiangdiang Shillong, Meghalaya).

Providing comprehensive operation & maintenance for five year ( one year warantee and one more
year extended warrantee shall be included with all specilized items as mentioned above) of all
specialized services mentioned above executed for this projects from the date of hand over/
completion of work whichever is later for a period of 05 years. The Comprehensive maintenance
1.01
charges of whole work including equipments supplied shall include all the spare parts, consumables
(excluding the cost of diesel required for running of DG sets), manpower, periodical changes of
lubricants etc. including replacement/repair to keep the building in usable condition with least
disturbance of the occupants

a Comprehensive Maintenance during 1st Year after completion of work 1 Job


b Comprehensive Maintenance during 2nd Year 1 Job

c Comprehensive Maintenance during 3rd Year 1 Job

d Comprehensive Maintenance during 4th Year 1 Job

e Comprehensive Maintenance during 5th Year 1 Job

Total
Following works shall be in the scope of BA
Sl. No Description of Work

1 Panel: Supply of channel,paint and grouting nut bolt,chequre plate cutting and fixing.

2 Transformer: Supply of Channel/paint/ Associated Civil works.

3 HT Cable: Supply of Sand/ Bricks/Cable tie and tag.

4 RCC Hume Pipe: Supply of Sand/Cemet

5 LT Cable: Supply of Bricks/Sand/Cable tie/Tag/shaddle

6 Bus duct: Supply of Slotted angle/Channel/threaded rod/ Ancor Fastner making of cutout and refilling.

7 Earthing: Supply of bricks/cement/PIT Cover/Cu/GI/SS nut bolts/shaddle/Bimatelic Strip(if required)

8 Loading/Unloading/Draging of materials.

9 Ladder,Scafholding,All other tools tackles

10 Labour hutmet, water,power

11 All safety PPE, like helmet, shoe, handgloves, jacket (ISI marked)

12 Construction power extension, touch lightening.

Class C item like - Wooden screw, PVC Slip for Saddle, PVC Insulation tape, Ferrule for DB dressing and each light
and power points, Cable Tag (Al/Printed), Connector (10/16A) in Point Wiring (Each Light & Power Point), Structure
13 Paint (Red oxide paint two cote and one cote Al/Black/Red as required at site Reputed brand like (Barger or Asian
Paint), Welding Rod,Chase/Angle cutting Blade, 6 - 1.5 sq mm pin and Ring type lugs for DB dressing ,point wiring
in switch socket and each points as per site requirement & Cable Tie in cable dressing.

14 2 No. dedicated Supervisor required above 10L order

15 Group insurance to be maintained by the vendor.


ESI & PF registration to be maintained by vendor for all workers working in said project and submitted to Blue Star's
16
authorized person on regular basis.
17 Wage register is mandatory for all manpower

18 P Tax need to be paid to those manpower having wages more than Rs. 10000/month

19 Requirement of health checkup & fitness certificate from local authorized doctor on monthly basis

20 At least 40% of workers should have electrical License and Welder license required for said project