Company: Contractor:

Project No.
REVAMPING OF WASTE WATER TREATMENT FACILITY IN ETHYLENE PLANT AT
QAPCO

COMMENTS RESOLUTION SHEET

WWT-P06-45450-004_A- CRS PIPING GA FOR UTILITY & PAC SILO AREA- CRS Rev. A

Sl. No QAPCO Comments Contractor Response QAPCO Reply

GENERAL COMMENTS
Drawing scale shall be assigned generally for the Comment incorporated.
drawing. For special view or detail there may be different Submitted Piping GAs are in 1:50 scale meeting QAPCO
1.1
scale that shall be shown on the view. General scale for requirement. Three sheets are added now to include sections
piping GA shall not be less than 1:60. and details to provide more clarity as required by QAPCO.
This will require major revision on all piping GAs hence
1.2 Please draw line size 8" and larger with double line. deliverables will be delayed. Will revise the drawing to show
double lines for 12” and above as per normal practice.
1.3 Please draw piping lines bolder than accessory lines. Comment incorporated.

1.4 Please show all equipment tag no. Comment incorporated.


Show coordinate of equipment on the CL or a reference
Comment incorporated.
1.5 point. Deviation angle from normal co-ordinate lines
shall be shown.
Line numbers shall be shown on each edge of the line
(or at borderline), when any change in direction and Comment incorporated.
1.6
when interfere with other line. Or whenever needed to
show any unclear portion.
1.7 Pipe elevation shall be shown. For flat lines, BOP shall Comment incorporated.
be shown under the line number. For slope lines, WP
elevation shall be shown on every change in direction or

Page 1 of 2 439386954.doc
Company: Contractor:

Project No.
REVAMPING OF WASTE WATER TREATMENT FACILITY IN ETHYLENE PLANT AT
QAPCO

COMMENTS RESOLUTION SHEET


elevation and branches.

Deviation angle between true and Plant North shall be Comment incorporated.
1.8 shown.
Piping GA dedicated for pipe racks may be prepared if
1.9 there is no any piping connection to equipment (optional Separate piping GA shall be provided for pipe rack detail
to simplify/minimize drawings quantity).
See comments on drawing legends in drawing no.
1.10 WWT-P06-45450-009 Noted and incorporated

Page 2 of 2 439386954.doc