2.4.

4 Wiring Requirement for SLC circuits

Must meet the National Electric Code 760-51 requirements for power limited
fire protective signaling cables.
Maximum wiring resistance is 50 ohms and maximum loop length depends on
the wire gauge as per below.

Wire Gauge 22AWG 18AWG 16AWG 14AWG


mm2 .34 1.0 1.5 2.5
Maximum
1500 feet 3900 feet 6200 feet 10,000 feet
Distance
Table 7