IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (less than 1 Hz)

Table 3 —VLF withstand test voltages for sinusoidal and cosine-rectangular waveforms
(see Note 1)
Waveform Cable system Installation Acceptance Maintenance2
rating (phase to ground) (phase to ground) (phase to ground)
(phase to phase) (see Note 2)
[kV]
[kV rms] [kV peak] [kV rms] [kV peak] [kV rms] [kV peak]
Sinusoidal 5 9 13 10 14 7 10
8 11 16 13 18 10 14
15 19 27 21 30 16 22
20 24 34 26 37 20 28
(Note 3) (Note 3)
25 29 41 32 45 24 34
(Note 3) (Note 3) (Note 3) (Note 3)
28 32 45 36 51 27 38
(Note 3) (Note 3)
30 34 48 38 54 29 41
(Note 3) (Note 3)
35 39 55 44 62 33 47
46 51 72 57 81 43 61
69 75 106 84 119 63 89

Cosine- 5 13 13 14 14 10 10
Rectangular
8 16 16 18 18 14 14
15 27 27 30 30 22 22
20 34 34 37 37 28 28
25 41 41 45 45 34 34
28 45 45 51 51 38 38
30 48 48 54 54 41 41
35 55 55 62 62 47 47
46 72 72 81 81 61 61
69 106 106 119 119 89 89

NOTE 1—If the operating voltage is a voltage class lower than the rated voltage of the cable, it is
recommended that the maintenance test voltages should be those corresponding to the operating voltage class.
NOTE 2—The maintenance voltage is about 75% of the acceptance test voltage magnitude.
NOTE 3—Some existing test sets have a maximum voltage that is up to 5% below the values listed in the table.
These test sets are acceptable to be used. However, there is a risk that the cable may be “undertested” due to a
combination of lower test voltage and allowed uncertainty of the measuring circuit.