Professional Documents
Culture Documents
AATC Head of
REVIEWED BY Engineering,
Maapola, Phanki
Underground
Operations
AATC Head of
REVIEWED BY Engineering,
Ford, Julian
Technical Services
and Projects
AATC Head of
APPROVED BY Engineering Services,
Coetzee, Johnny
RSA Opencast
Operations
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 1 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
CONTENTS
Page
1 AIM 3
2 SCOPE 3
3 DEFINITIONS 3
4 ABBREVIATIONS 4
5 STANDARD SPECIFICATION 6
7 REVISION HISTORY 57
8 APPENDICES 57
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 2 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
1 AIM
The aim of this standard is to ensure that fire fighting equipment complies with minimum
requirement for suppression of fire.
2 SCOPE
This standard is applicable to all the Anglo Thermal Coal Operations where the following fire
fighting equipment is required:
3 DEFINITIONS
Term Definition
Throughout these standards, measures are frequently prescribed as
‘depending on the assessed criticality of the installation’. The criticality
of an installation is to be determined by a risk assessment which takes
into account the foreseeable combined impact:
Criticality
on the safety and health of people,
in terms of property damage / loss (asset value),
in terms of business interruption, i.e. loss of revenue due to
process interruption, if the installation were to be damaged or lost.
This term refers to a material which under all normal conditions cannot
burn. Examples are brick, concrete, mineral wool, rock wool and perlite.
In most cases, project managers will need to use such materials for
walls, support structures and similar.
Incombustible
Note, though, that even ‘incombustible’ materials will lose their
structural integrity when subjected to extreme heat, although they will
never actually burn, and will therefore never contribute to the fire load in
a building. For example, steel starts to buckle at a relatively low 500O.
Even concrete will decompose under really extreme conditions (e.g. the
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 3 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
Term Definition
World Trade Centre disaster), when the concrete reverted to powder.
“Fire retardant” is one of several terms that for all practical purposes
within the context of this document mean roughly the same thing. Other
terms in the group are “fire resistant”, “flame retardant” and “flame
resistant”. The following discussion is relevant to all of these terms.
Sometimes, once the external heat source has been removed, the fire
Fire Retardant
retardant material will cease to burn, but it can happen that if sufficiently
high temperatures have been reached before the external heat source
has been removed, the ‘fire retardant’ material will still continue to burn,
despite its supposed ‘flame retardancy’.
From the above, it is obvious that ‘flame retardant’ materials have very
limited use, and actually offer little advantage. An example is styrene
which normally ignites at around 200OC. Flame retardant styrene is
claimed only to ignite at around 300OC. However, when one considers
that structure fires easily reach 1000O C quite quickly, then it is obvious
that this difference is just academic.
4 ABBREVIATIONS
Term Abbreviation
LDV Light Delivery Vehicle
TLB Tractor Loader Back actor
AATC Anglo American Thermal Coal
SHERMP Safety, Health, Environment Risk Management Plan
FRMP Fire Risk Management Plan
SME Surface Mobile Equipment
AFFF Aqueous Film-Forming Foam
SABS South African Bureau of Standards
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 4 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
Term Abbreviation
DCP Dry Chemical Powder
ASIB Automatic Sprinkler Inspection Bureau (South Africa)
NFPA National Fire Protection Association
kPa Kilopascal
MCC Motor Control Centre
MV Medium Voltage
LT Low Tension
PLC Programmable Logic Controller
SCADA Supervisory Control and Data Acquisition
CR Control Room
IT Information Technology
CO2 Carbon Dioxide
PVC Polyvinyl Chloride
FES Fire and Emergency Signs
cfm Cubic Feet per Minute
SCBA Self-Contained Breathing Apparatus
ESCF Embankment-Supported Coated Fabric
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 5 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
5 STANDARD SPECIFICATION
5.1 Hand-Held Fire Extinguishers
5.1.1 Requirements
a) A minimum of one hand-held fire extinguisher to be deployed per 200 m2 of floor area in
all structures, increasing in density in areas with a high fire load, and / or an increased risk
of ignition.
b) Normal deployment is to be 9 kg DCP hand-held fire extinguishers.
c) In offices and areas where there are many female staff members, or disabled persons,
who may find 9kg units difficult to handle, 2 x 4.5kg hand-held DCP units may be
substituted for every 9kg DCP unit. Note that this concession is never appropriate in an
industrial area such as a workshop or plant building, where 9 kg units are an absolute
requirement.
d) areas where sensitive electronic equipment, foodstuffs, and medicines are present, 5 kg
hand-held CO2 fire extinguishers should be substituted in place of the 9kg hand-held
DCP fire extinguishers.
e) Fire extinguishers are to be mounted 1.2 metres above ground or floor level, against a
wall or other suitable support.
f) The relevant symbolic signage indicating the position of each fire extinguisher shall be
posted up. Such signage must comply with SABS 0400 TT29, FPA Bulletin 19, NFPA 170
& SABS 1186.
g) Directional signage is only necessary if the extinguisher is in an obscured position (e.g.
around a corner). Otherwise the symbolic signage and the extinguisher’s colour (red) shall
serve to indicate its position.
h) An area of 1.2 metres x 1.2 metres shall be demarcated on the floor where fire
extinguishers are mounted, and shall be kept clear of obstructions at all times, to make
access to the fire extinguishers possible whenever required.
i) Three-monthly inspections must be conducted on all fire extinguishers deployed. Results
must be logged and deviations noted must be rectified within the shortest reasonable
time.
j) Servicing by an accredited external agency is to be performed on each unit once per year.
k) Pressure testing of the cylinders is to be performed every 3 years.
l) Fire extinguishers located inside plant buildings should ideally be mounted within see-
through “Extinguimate” type extinguisher cabinets, to prevent them from deterioration due
to the harsh environment.
m) Fire extinguishers located externally, and which are exposed to the elements should
ideally be mounted within glass or steel extinguisher cabinets, to protect them from the
elements.
n) Fire extinguishers inside buildings which do not constitute harsh environments, such as
office blocks, workshops, substations, stores and similar, do not require cabinets and may
be hung from a wall bracket.
o) 2 x 9 kg DCP fire extinguishers are to be mounted within 5m of every drive electric motor
associated with a belt conveyor.
They obviate the need for internal hydrants in some of the smaller buildings, since
reliance may be placed upon the area hydrants alone.
They offer a fall-back fire fighting strategy for use when a fire in a structure has
developed past the point where fire fighting operations can be conducted internally
using internally provided hydrants and hosereels. At this point, fire fighters will retreat
to a safe position outside the building, and will spray water on the flames using area
hydrants. The purpose of this activity might be to attempt to contain fire to only certain
levels of the structure, or to prevent the fire from spreading to other areas of the plant
or other complex.
Note however, that hydrants associated with specific buildings (“structural hydrants”), may
in some instances satisfy the requirement for area hydrants.
b) 65 mm fire hydrants are to be installed at the rate of one per level in all buildings
exceeding 12 metres in height.
c) In all structures with a footprint exceeding 1000 m², fire hydrants will be installed on all
levels at a rate of one per 1000 m² or part thereof.
d) In close proximity to each “structural hydrant” located in a building, a fire hose box or
cupboard must be provided, containing a minimum of 3 x 65 mm lay flat fire hoses and a
single 65 mm nozzle.
e) In the case of “area hydrants”, either a fire hose box containing at least 3 x 65 mm lay flat
fire hoses and a single 65 mm nozzle must be provided in a fire equipment box at each
hydrant point, or there must be ready access in a central position on site to a cache of at
least 9 x 65 mm lay flat fire hoses, and 3 x 65 mm nozzles.
In either case, the receptacle in which the fire equipment is kept must be colour coded red
and must be suitably demarcated with appropriate symbolic signage.
f) 65 mm fire nozzles, also called branches, shall have a 65 mm male fitting, and an internal
diameter of 16 mm. They may be fixed or variable jet, except that where nozzles are
provided primarily for the use of fire teams only, then at least 50% of the nozzles provided
shall be variable jet, to cater for specialist applications.
g) Hydrants in elevated positions, for example in multi-level plant structures or on conveyor
gantries, must be supplied off a steel rising or inclined main of minimum diameter 100 mm
which in turn is taken off a steel ring fed fire main at ground elevation which should be of
minimum diameter 300 mm.
Notwithstanding the above, no more than 3 x 65 mm fire hydrants may be taken off any
100 mm spur line leading off the ring main. If additional hydrants are required, then the
spur line must be increased to 300 mm, in diameter, in which case the number may
increase to five.
h) Single hydrants may be fed off a spur line of minimum diameter 75 mm, provided that no
such 75mm spur line should exceed 300 m in length. This requirement shall also apply to
the standpipes of single hydrants.
i) Concerning the minimum diameters specified above, note that at no point on the supply
line may the supply pipe be restricted or reduced to a lesser diameter, irrespective of for
how short a distance. This is based on the principle that the effective diameter of a pipe is
equal to its diameter at the narrowest point in its length.
j) All fire water mains and supply lines right up to the hydrant point must be of steel, unless
they are buried underground, in which case, Class 6 HDPE pipe is acceptable.
k) Colour-code all hydrant points and above ground fire mains red.
l) Irrespective of the aforegoing requirements, all hydrants on the system must be supplied
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 7 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
at a minimum static pressure of 300 kPa. If necessary, increase the diameter of the pipes
to achieve this pressure.
m) Irrespective of the aforegoing, the water supply in the fire mains must be adequate to
ensure a minimum flow rate at each hydrant of 1200 l/min, measured when any three
hydrants on the system are open simultaneously. If necessary, increase the diameter of
the fire mains to achieve this required flow.
n) All “area hydrants” are to be located at least 3 metres away from any structure or installed
equipment, so that they can be accessed even if the fire has already taken hold on that
structure or equipment. This does not apply to “structure hydrants”.
o) Hydrants should be located as close as possible to hard surfaces / roadways, so that fire
engines connecting to them do not sink into the mud that will develop from prolonged fire
fighting.
p) All 65 mm hydrant points, and fire hose boxes, cabinets, cupboards and other
receptacles, must be inspected monthly by persons appointed in writing to perform this
task. Such persons should be suitably trained and the results of the inspections must be
logged. Any deviations noted must be rectified in the shortest possible time, as befits the
importance of all emergency equipment.
q) All 65 mm hydrant points, and fire hose boxes, cabinets, cupboards and other
receptacles, must be inspected annually by an accredited external service provider.
Effective hydrants and equipment are to be replaced or repaired as directed, again in the
shortest possible time.
r) No process / service water may be drawn from a fire main. Fire mains must be dedicated
to fire fighting purposes, from the reservoir to the point of delivery.
s) 65 mm hydrants, hoses and nozzles will not be used for any purpose other than fire
fighting.
t) The relevant symbolic signage indicating the position of each structural hydrant shall be
posted up. Such signage must comply with SABS 0400 TT29, FPA Bulletin 19, NFPA 170
& SABS 1186.
u) Directional signage is only necessary if the structural hydrants are in an obscured position
(e.g. around a corner). Otherwise the symbolic signage and the red colour of the
structural signage shall serve as adequate indication of its position. This requirement
does not pertain to area hydrants.
v) Where fire hoseboxes are locked, keys must be provided in a break glass panel at the
affected hosebox.
w) ‘As built’ drawings, capacities, full instructions and a maintenance schedule must be
provided by the designer / installer in respect of every hydrant system. The owner must
determine at least once a year that these are available for every system on his site and
that they are current (i.e. include any changes made to the system). In respect of existing
systems, where such drawings, instructions and maintenance schedules are not
available, the owner must engage a suitable service provider to inspect the system(s) and
compile the missing documentation.
a) The capacity of the water supply reservoir, dam or tank which must be always readily
available via the fire water mains which supply inter alia the 65 mm hydrant points and the
25mm fire hosereels, shall be adequate to sustain fire fighting from 3 hydrants operating
simultaneously for 120 minutes, i.e. 3 x 1200 litres per minute x 120 minutes which
equates to a minimum reservoir capacity of 432 kl, dedicated to fire.
b) To ensure that this supply is dedicated to fire, a separate reservoir should be provided for
the storage of fire fighting water. Alternatively, a process water reservoir may be shared,
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 8 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
but the take-off for the fire system must be positioned sufficiently lower in the reservoir to
ensure that even when the process water supply runs ‘dry’, there is at least 432kl of water
left in the reservoir, available through the fire mains. Points from which process / service
water is drawn, must be supplied from separate and independent, and via a separate
service water main which is not interconnected with the fire main.
c) The standard governing fire water supply is SABS 0287 which deals inter alia with fire
pump requirements.
d) Ideally, water for fire fighting purposes will be gravity fed which will remove all need for
fire pumps, and all risk of a lack of fire fighting water as a result of power or pump failure.
However, if this is not possible, then fire pumps must be provided. Most importantly, the
fire pumps should comply with the following requirements:
An electrically driven jockey pump must be provided to maintain pressure in the fire
mains under normal conditions when there is no drain on the system.
This should turn on automatically in response to any pressure drop in the system,
and should turn off once the required pressure has been attained. A timing factor
should also be built into the PLC of this unit to ensure that it does not switch on
and off repeatedly at short intervals.
An electrically driven main fire pump must be provided to maintain pressure in the
fire mains under demand conditions such as will occur when there is a drain on the
system during fire fighting.
This pump should turn on automatically in response to any pressure drop in the
system with which the jockey pump cannot cope. This pump needs to be able to
supply 75% of the stated maximum demand of 3600 l/min at 300kPa static
pressure, sustainable for 120 minutes. Also refer to section referring to Fire
Hydrants and Related Equipment.
A diesel driven standby main fire pump must be provided to maintain pressure in
the fire mains under demand conditions if:
The electrically driven jockey pump conjoined with the electrically driven main fire
pump cannot cope with the demand, and / or…
There is a power failure, so that the electrically driven jockey pump and main fire
pump cannot run.
This pump should turn on automatically in response to any pressure drop in the
system with which the jockey pump and the electrically driven main fire pump
cannot cope. This pump needs to be able to supply 75% of the stated maximum
demand of 3600 l/min at 300kPa static pressure, sustainable for 120 minutes.
e) Note (1) that it is acceptable to forego the requirement to provide a main electrically
driven fire pump as contemplated in the second bullet point above, on condition that:
The capacity of the installed diesel driven fire pump is at least 120% of the stated
maximum demand of 3600 l/min at 300 kPa static pressure, sustainable for 120
minutes, and
Life-safety does not depend upon the fire fighting water supply.
f) Note (2) that it is acceptable to forego the requirement to provide a diesel driven standby
main fire pump as contemplated in the second bullet point above, on condition that.
The capacity of the installed electrically driven fire pump is at least 120% of the stated
maximum demand of 3600 l/min at 300 kPa static pressure, sustainable for 120
minutes, and
Life-safety does not depend upon the fire fighting water supply.
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 9 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
a) NFPA 14 - Standard for the Installation of Standpipe and Hose Systems (Part WW
b) NFPA 20 - Standard for the Installation of Stationary Pumps for Fire Protection
c) SABS 0287 - Automatic sprinkler installations for fire-fighting purposes
d) ASIB (compliance is mandatory only where the pumps supply sprinkler systems, upon
which life safety depends)
a) In all buildings, including inter alia warehouses, plant structures, workshops and offices
complexes, 25 mm hosereels must be installed at the rate of 1 per 500 m² of building floor
area.
b) Each 25 mm fire hosereel must be fed via a steel take-off line of minimum diameter 32
mm.
c) These 32 mm take-off lines should be fed off a steel fire water main of minimum diameter
100 mm.
d) The water supply to the 25 mm fire hosereels shall be sourced from the main ring fed
water main. Also see Fire Fighting Water Supply and Fire Pumps section.
e) Fire hose reels should be supplied at a water pressure of no less than 300 kPa static
pressure.
f) Each fire hosereel must be able to deliver a flow of no less than 0.5 litres per second (30
litres per minute).
g) Where a conveyor path is protected by 25 mm fire hosereels, these must be positioned no
further than 30 metres apart.
h) All fire hosereels in service must be inspected monthly by a member of staff appointed in
writing for that purpose. Such person shall be suitably trained, and shall log results of his
inspections in a book to be kept for that purpose. As befits critical emergency equipment,
all faults noted are to be rectified as soon as practicable.
i) All fire hosereels must be inspected annually by an accredited external service provider,
who, on completion of their inspections, shall provide a detailed report per hosereel,
indicating any faults which may have been found. As befits critical emergency equipment,
all such faults shall be rectified, or the equipment replaced as soon as practicable.
j) No process water point may be fed off the fire water main. This includes all supply lines
leading to 25 mm fire hosereels.
k) Hosereels and fire fighting water shall not be used for any purpose other than fire fighting.
l) The hosereels and above ground supply lines should be colour-coded red.
m) All supply lines, from the source to the hosereel must be of steel, unless they are buried
underground, in which case Class 6 HDPE is acceptable.
n) An area of 1.2 metres x 1.2 metres must be demarcated on the floor at all positions in
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 10 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
which 25 mm fire hosereels are mounted. This area must be kept free of obstructions at
all times, to ensure easy access to the fire hosereels in an emergency.
o) The relevant symbolic signage indicating the position of each 25 mm fire hosereel shall be
posted up. Such signage must comply with SABS 0400 TT29, FPA Bulletin 19, NFPA 170
& SABS 1186.
p) Directional signage is only necessary if the 25 mm fire hosereel is in an obscured position
(e.g. around a corner). Otherwise the symbolic signage and the red colour of the 25 mm
fire hosereel shall serve as adequate indication of its position.
q) The minimum acceptable length of hose on a 25 mm fire hosereel is 30 metres.
r) ‘As built’ drawings, capacities, full instructions and a maintenance schedule must be
provided by the designer / installer in respect of every fire hosereel system. The owner
must determine at least once a year that these are available for every system on his site
and that they are current (i.e. include any changes made to the system). In respect of
existing systems, where such drawings, instructions and maintenance schedules are not
available, the owner must engage a suitable service provider to inspect the system(s) and
compile the missing documentation.
a) At hydraulic power packs, lubrication packs, areas where flammable liquids are involved,
and in other areas where the application of foam offers an effective means of
suppression, but where the size of the risk does not justify a fixed system, a foam trolley
can offer a solution.
b) At such locations, the provision of such trolley would be deemed to satisfy the need for
advanced primary fire protection, and may justify the omission of a high velocity deluge
system, or a fixed foam system.
c) In multilevel structures, the Viking hoses provided will make it possible to use the foam
trolley to fight fires on the levels immediately above and below, without the necessity of
moving the trolley to those levels.
5.5.2 Requirements
a) The unit should be fitted with solid rubber wheels of minimum diameter 400 mm.
b) The tank should be chemically resistant to the foam.
c) The chassis should be corrosion protected and suitable for outdoor use and storage.
d) The minimum tank capacity should be 120 litres.
e) The trolley should be filled with AFFF or equivalent foam.
f) The foam trolley should be fitted with a variable foam inductor capable of 225
litres/minute, with an induction rate of 3%.
g) The trolley should be equipped with at least 2 x 15 metre long, 65 mm diameter, Viking (or
equivalent) fire hoses complete with installation connectors.
h) The trolley must be provided with a foam branch pipe capable of delivering 225
litres/minute.
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 11 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
One of the primary reasons why fire engines are often found to be inadequate when required
for service is that they are incorrectly chosen in relation to their intended purpose. There are
many classes of fire engine, but for the purposes of these standards, three classes of fire
engine are considered. These are:
A water bowser, as used in opencast operations for watering roads, etc., is suitable to be
equipped as a mobile water-supply fire appliance. Note however, that where a pumper
appliance is not available on site, or where it would foreseeably take a long time to reach an
area in which the water bowser is operating, consideration should be given to equipping the
water bowser as a hybrid mobile water supply fire appliance cum pumper appliance. In this
regard, consider the requirements stated in Pumper Fire Appliances and Mobile Water-Supply
Fire Appliances sections of this standard. At hydraulic power packs, lubrication packs, areas
where flammable liquids are involved, and in other areas where the application of foam offers
an effective means of suppression, but where the size of the risk does not justify a fixed
system, a foam trolley can offer a solution.
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 12 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
a) Ground Ladders
All ground ladders carried on the appliance shall meet the requirements of NFPA
1931.
A 3.7 metre or longer extension-type ground ladder shall be carried on the appliance.
b) Suction Hose.
A minimum of 6 m of hard suction hose shall be carried. Suction hose shall meet the
requirements of NFPA 1961. Where a hard suction hose is provided, a suction strainer
shall be furnished.
b) Miscellaneous Equipment.
The following additional equipment shall be carried on the appliance:
One 2.7 kg pick-head axe mounted in a bracket fastened to the appliance.
One 2 m pike pole or plaster hook mounted in a bracket fastened to the appliance.
Two portable hand lights mounted in brackets fastened to the appliance.
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 13 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
Two 9 kg dry chemical portable fire extinguisher mounted in a bracket fastened to the
appliance.
One gated swivel intake connection with pump intake threads on one end and one or
more female connections compatible with the supply hose carried on the other.
One SCBA complying with NFPA 1981 for each assigned seating position, but not
less than two, mounted in brackets fastened to the appliance or stored in containers
supplied by the SCBA manufacturer.
One spare SCBA cylinder for each SCBA carried, each mounted in a bracket fastened
to the appliance or stored in a specially designed storage space(s).
One first aid kit.
Two combination spanner wrenches mounted in a bracket(s) fastened to the
appliance.
One hydrant wrench mounted in a bracket fastened to the appliance.
One double female adapter, sized to fit 65 mm or larger fire hose, mounted in a
bracket fastened to the appliance.
One double male adapter, sized to fit 65 mm or larger fire hose, mounted in a bracket
fastened to the appliance.
One rubber mallet, for use on suction hose connections, mounted in a bracket
fastened to the appliance.
Two wheel chocks, mounted in readily accessible locations, that meet or exceed the
requirements of SAE J348, Standard for Wheel Chocks, for the wheel diameter on
which the chocks are to be used.
One crowbar [1 m minimum] with brackets.
One pair insulated bolt cutters with 11 mm minimum cut.
One Halligan-type tool with brackets.
One 65 mm hydrant valve (screw-type gate).
Two shovels (one pointed and one scoop).
Two hose straps.
One 38 m length of utility rope having a breaking strength of at least 2268 kg.
Toolbox with hammers, wrenches, screwdrivers, and other assorted tools.
Foam delivery equipment compatible with onboard foam system.
One hose clamp.
It is important to protect emergency and standby generators from any event which could
foreseeably interrupt normal power supply, since they are intended to provide back-up in exactly
those circumstances. Therefore, generator installations must be spatially or structurally well
separated from all other facilities, and must have automatic protection against fire originating in
the generator room.
5.8.1 Requirements
Standby and emergency generator installations on surface should comply with any relevant
Anglo American specifications. Notwithstanding anything contained therein, the following are
the minimum requirements necessary to ensure adequate fire protection in relation to such
generator installations.
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 14 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
few structural measures are required to provide preparation of the facility. One
requirement is that a 2 metre firebreak must be provided on all electrical cables entering
or leaving the generator room. See Fire Protection Standard for Electrical Equipment and
Installations regarding the requirements for intumescent coating of electrical cables.
b) Where emergency and standby generators are to be located in part of a larger structure
which they are to share with other facilities, structural separation of the generators from all
other facilities in the structure is required. The following measures are necessary to
achieve this separation:
All interior, interleading walls of the generator room must be 2-hour fire rated perfect
party walls. See Fire Protection Standard for Electrical Equipment and Installations
regarding the requirements for perfect party walls.
To ensure adequate ventilation of the generator room, and to allow heat from the
generator to be dissipated, provide an extraction fan or fans of adequate capacity to
ensure sufficient air changes to achieve the heat dissipation. These may only be
mounted in an exterior wall. Ventilation louvres or ducts of corresponding size must
also be provided in the exterior wall of the generator room.
If the structure has multiple levels, then the roof of the generator room must be of
reinforced concrete.
The generator room door must have a fire resistance rating of at least 2 hours, and
must be self-closing.
The generator room floor, roof, and interior, interleading walls should not be breached.
If an aperture exists, then it must be fire stopped in accordance with the requirements
described in Fire Protection Standard for Electrical Equipment and Installations.
Any electrical or instrumentation cables passing through a fire stopped cable
penetration aperture shall be intumescent coated for minimum distance of 1 metre on
either side of such fire stopping, using suitable intumescent coating or cables must
pass through a ‘sand box’ located at the wall. Such intumescent coating shall be
applied to the entire circumference of each cable to such thickness as is stipulated by
the manufacturer of the particular intumescent product chosen, as being adequate to
provide an SABS rated fire resistance of at least 2 hours. See Standard Fire
Protection Standard for Electrical Equipment and Installations regarding intumescent
coating.
Where plant and/or equipment is located or is required to operate in remote areas where 65 mm
fire hydrants are not available, and where the provision of such 65 mm hydrants is
impracticable, there must be ready access instead, to a mobile water supply fire appliance.
Common examples are opencast pits and overland conveyors. Thus all operations having
opencast pits, unprotected overland conveyors, and similar remote plant and equipment, must
provide one or more mobile water supply fire appliances on site.
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 15 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
5.9.1 Requirements
5.9.1.1 Pump
If the appliance is equipped with either a fire pump, transfer pump, or both, the pump(s) shall
meet the requirements of NFPA 1901 Chapter 14 or Chapter 16 respectively.
b) Miscellaneous Equipment.
Mobile water supply fire appliance shall be equipped with at least the following
equipment:
One 2.7 kg flathead or pick head axe mounted in a bracket fastened to the
appliance
One 2 m or longer pike pole or plaster hook mounted in a bracket fastened to the
appliance
Two portable hand lights mounted in brackets fastened to the appliance
Two approved 9 kg dry chemical portable fire extinguishers mounted in a bracket
fastened to the appliance
One SCBA complying with NFPA 1981 but not less than two, mounted in brackets
fastened to the appliance or stored in containers supplied by the SCBA
manufacturer
One spare SCBA cylinder for each SCBA carried, each mounted in a bracket
fastened to the appliance or stored in a specially designed storage space(s)
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 16 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 17 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
5.9.1.8 Maintenance
a) Water bowsers doubling as “water supply mobile fire appliances” must be inspected and
maintained according to the following schedule:
Weekly equipment check by supervisor.
Monthly equipment check and discharge test with fire drill by supervisor, involving
operating staff. This should alternate between hydrant 1, hydrant 2, monitor using
foam and monitor using water.
Quarterly engineering maintenance on pump, including greasing of hydrants.
5.9.1.9 Operators
All water bowser operators are to be trained as fire team members, and must be able to
operate both water and foam equipment on the bowser.
a) Ground Ladders
All ground ladders carried on the appliance shall meet the requirements of NFPA
1931.
At a minimum, the following ladders shall be carried on the appliance:
One straight ladder equipped with roof hooks
One extension ladder.
b) Suction Hose
A minimum of 6 m of hard suction hose shall be carried. Suction hose shall meet the
requirements of NFPA 1961. Where a hard suction hose is provided, a suction strainer
shall be furnished.
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 18 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
a) Minor Equipment
Brackets or compartments shall be furnished so as to organize and protect the equipment.
b) Miscellaneous Equipment
The following additional equipment shall be carried on the appliance:
One 2.7 kg flathead axe mounted in a bracket fastened to the appliance.
One 2.7 kg pick head axe mounted in a bracket fastened to the appliance.
One 2 m pike pole or plaster hook mounted in a bracket fastened to the appliance.
One 2.4 m or longer pike pole mounted in a bracket fastened to the appliance.
Two portable hand lights mounted in brackets fastened to the appliance.
Two approved 9 kg dry chemical portable fire extinguishers mounted in a bracket
fastened to the appliance.
One gated swivel intake connection with pump intake threads on one end and one or
more female connections compatible with the supply hose carried on the other.
One self-contained breathing appliance (SCBA) complying with NFPA 1981 for each
assigned seating position, but not less than four, mounted in brackets fastened to the
appliance or stored in containers supplied by the SCBA manufacturer.
One spare SCBA cylinder for each SCBA carried, each mounted in a bracket fastened
to the appliance or stored in a specially designed storage space.
One first aid kit.
Four combination spanner wrenches mounted in brackets fastened to the appliance.
Two hydrant wrenches mounted in brackets fastened to the appliance.
Two double female adapters, sized to fit 65 mm fire hose, mounted in brackets
fastened to the appliance.
Two double male adapters, sized to fit 65 mm fire hose, mounted in brackets fastened
to the appliance.
One rubber mallet, suitable for use on suction hose connections, mounted in a bracket
fastened to the appliance.
Two salvage covers, each a minimum size of 3.7 m x 4.3 m.
Two wheel chocks, mounted in readily accessible locations, that meet or exceed the
requirements of SAE J348, Standard for Wheel Chocks, for the wheel diameter on
which the chocks are to be used.
One fire service claw tool.
One crowbar (1 m minimum) with brackets.
One pair of insulated bolt cutters with 11 mm minimum cut.
One Halligan-type tool with brackets.
One 65 mm hydrant valve (screw-type gate).
One double-gated reducing leader sized to fit hose used in department.
Two shovels (one pointed and one scoop).
Four hose straps.
One 38m length of utility rope of breaking strength of at least 2,268 kg.
One 3000 W (minimum) portable generator.
Two 500 W portable lights.
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 19 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
Two cord reels with minimum 61 m cord on each with connectors that are compatible
with lights, generator, and smoke ejector.
Toolbox with hammers, wrenches, screwdrivers, and other assorted tools.
Master stream appliance, 3785 l/min minimum.
Foam delivery equipment compatible with onboard foam system.
One hose clamp.
a) Surface fire team members must form the core of the fire response effort on site. As such,
they must be adequately trained and equipped to deal with the following fire-related
situations:
Fires where the use of breathing apparatus is necessary. To this end, each team
member must be trained in the use of breathing apparatus.
Fires where the manual application of fire suppressant foam by means of hoses and
foam generators is necessary. Typically, this would include flammable liquid fires,
such as at bulk diesel storage facilities or transformers.
Fires in elevated structures. This would include tall plant buildings, and elevated
conveyor belt paths.
Fires in confined spaces. This could also include elevated, enclosed conveyor belt
paths, draglines, and some areas in the plant.
Electrical fires, for example, at substations or transformers.
b) Volunteer fire team members may not need to be trained to the same level of proficiency
as professional fire team members. Cognisance must be taken of the likely response
times of the available professional teams in the area, allowing for a worst case situation in
which there is already one significant emergency in the area served by the professional
team(s) when this new emergency is declared. Where external professional response is
available within 60 minutes, the onsite team(s) may be regarded as ‘first responders’. First
responders must be adequately trained, in the opinion of a professional fire training body
such as the FPASA, to conduct and lead initial fire fighting efforts on site until the arrival
of professional fire teams from e.g. local municipalities. Where response will take longer
than 60 minutes, they need to be trained to the same standard as professional fire team
members.
c) An adequate number of volunteer fire team members should be trained to ensure that at
any time, day or night, there are at least 8 members at work on site. A further 8 members
should be available on call, able to be on site and ready for fire fighting within 30 minutes.
Where this is not practicable, there should be at least 16 members at work on site at any
time, day or night.
d) With regard to equipment, at least the following must be provided:
Personal protective equipment for at least 16 (2 teams of 8 members each) surface
fire fighters. PPE would include a fire fighter’s helmet complete with visor, a fireman’s
jacket, a fire retardant overall, boots and gloves.
Breathing apparatus (SCBA) should be provided for at least 8 fire team members and
preferably 16 fire team members.
Means should be available on site for re-charging cylinders for the SCBA sets
described above.
Adequate supplies of large bore hoses and nozzles should be kept available at a
central position, ready for deployment as required.
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 20 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
e) Irrespective of the availability of the abovementioned surface fire team, all employees on
site must also be proficient to some degree in the use of the fire fighting equipment
provided on site. Expected minimum proficiency levels of the general workforce are as
follows:
At least 75% of the workforce must be adequately trained in the use of primary fire
fighting equipment, which includes 25 mm fire hosereels and hand-held fire
extinguishers. Such persons must be able to use this equipment appropriately, and
must have knowledge of how to raise a fire alarm and initiate the evacuation of
persons from the affected area. Their training must also include knowledge of different
types of fire and appropriate response to each type.
At least 25% of the workforce, and this may include the volunteer fire team discussed
above, must be proficient in the use of both primary fire fighting measures (as
described above) and secondary fire fighting measures (65 mm hydrants and hoses)
as provided on site. These persons do not require the specialist skills required of the
volunteer fire team members (see above), but should be proficient in the use of all
primary and secondary fire fighting measures on site, so that they can assist volunteer
and professional fire team members under their direction.
This standard must be read in addition to the section on hand held fire extiunguishers.
5.12.1.1 Distribution
a) The number (density) and distribution of fire extinguishers is dependent on various
practical considerations, but always the nature of the risk to be protected (called the
‘occupancy’), and the floor area.
b) The provision of portable fire extinguishers is regulated by:
SABS 0400 (The application of the National Building Regulations) and
SABS 0105 (Classification, use & control of fire-fighting equipment)
The following are examples for some of the more common occupancy types.
Table 1 - Examples of Quantities, Rating & Distribution of Portable Fire Extinguishers in various
occupancy classes
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 21 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
In AATC, the ‘Wholesaler’ classification would apply to Mine Stores and Mine Offices, and
‘High Risk Commercial would apply to all plant areas, for example.
5.12.1.2 Siting
a) Extinguishers should be correctly sited to expedite their use during an emergency.
Whenever inspecting extinguishers, their location should always be re-evaluated to
ensure that each location is appropriate and offers the greatest coverage and ease of use
possible, given the conditions and arrangement of the area in which each extinguisher is
deployed. The points below are guidelines only, and it may be necessary to deviate from
them in certain situations:
Extinguishers should not normally be more than 46 m apart.
To ensure ready access, distribute units evenly over the entire floor area.
Extinguishers should be conspicuously sited in main escape ways and near exits.
To obviate the likelihood of an extinguisher creating an obstruction, it should be
positioned in a well-marked recess in a wall.
Extinguishers should be mounted on brackets fitted to walls or columns with their
carrying handles 1.2 m, and never more than 1.5 m, above floor level. Extinguishers
must never be left standing on the floor where they may be obscured or knocked over.
However, if the situation warrants a small shelf for the extinguisher then the base of
the unit should not be less than 0.75 m from the floor.
Extinguishers must be easily accessible and conspicuously marked. Mounting
extinguishers against a background of alternating red and white diagonal stripes will
considerably improve their visibility from a distance. SABS Standard 1186 gives
guidance on suitable Symbolic Safety Signs.
Extinguishers located outdoors should be in cabinets with their operating instructions
facing outwards. The appliances should be positioned so they may easily be removed.
Fire extinguishers should preferably be located as part of “fire equipment points”
comprising hosereels, fire alarm activation points etc, so that anyone sounding an
alarm also has immediate access to other fire equipment.
Special risk areas such as flammable liquid magazines, dip tanks, transformer rooms,
spray booths etc. should have extinguishers near at hand but not too close to the risk
where they could become involved in the fire themselves, or be impossible to reach.
Position units in cases such as this, more than 15 m from the risk, but not more than
25 m away, or around a corner.
Fire extinguishers should not be located within confined spaces.
Low temperatures are liable to affect the operation of most extinguishers and for this
reason they should not be sited in areas where the temperature is likely to drop below
4°C. If water extinguishers are exposed to severe weather conditions then suitable
antifreeze should be considered (consult the manufacturers).
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 22 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
b) The high-level red and white diagonal stripes with the symbolic sign below should be
easily seen from a distance. Demarcated lines on the floor indicate that nothing may be
placed on the floor below the extinguisher.
c) High temperatures could lead to the rupturing of stored pressure type, vaporising liquid
and carbon dioxide extinguishers. The foam compound in foam extinguishers could
deteriorate in hot areas and if temperatures are likely to exceed 43°C it is advisable to
consult the extinguisher suppliers or manufacturers.
d) Corrosive atmospheres could reduce the life expectancy of the extinguisher body and it is
therefore important that inspections are carried out at most frequent intervals than is
normally recommended.
e) Vibration also constitutes a siting problem in that dry chemical powder may become
compacted in areas such as hammer mills, and when mounted on vehicles. Under such
conditions it is essential that the extinguisher is securely bracketed and frequently
inspected.
5.12.1.3 Maintenance
a) It is important that extinguishers be maintained in accordance with SABS 1475. Service
intervals are as reflected in Table 2 below.
1 1
Mild steel Cartridge NA
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 23 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
b) More frequent maintenance is required for extinguishers that are mounted on vehicles or
that are subject to vibration, because the powder is more likely to become compacted.
c) Fire extinguishers may only be filled, recharged, reconditioned, repaired or inspected by
an SABS 1475 mark permit holder.
For convenience, the following checklists are organised into two parts. The first, Table 3, is
arranged by mechanical parts (components and containers) common to most fire extinguishers.
The second, Table 4, is arranged by extinguishing material and expelling means and involves a
description of the problems peculiar to each agent. Tanks not equipped with supervised water
level alarms connected to a constantly attended location must be inspected monthly.
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 24 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 26 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 27 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 28 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
b) Use proper recharge materials when refilling a fire extinguisher. Mixing of some
extinguishing agents could cause a chemical reaction resulting in a dangerous pressure
build-up in the container.
c) The weight of agent as specified on the nameplate is critical. Overfilling could render the
fire extinguisher dangerous or ineffective.
d) All sealing components should be cleaned and properly lubricated to prevent leakage
after recharge.
e) Check pressure-indicating device to ascertain that it is reading properly.
f) Most manufacturers recommend the use of dry nitrogen as an expellant gas for stored-
pressure fire extinguishers. Limiting charging pressure regulator setting to (172 kPa)
above service pressure prevents gauge damage and loss of calibration.
WARNING: Never connect the fire extinguisher to be charged directly to the high-
pressure source. Connecting directly to the high-pressure source could cause the
container to rupture, resulting in injury. Never leave a fire extinguisher connected to the
regulator of a high-pressure source for an extended period of time. A defective regulator
could cause the container to rupture due to excess pressure.
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 29 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
g) Use the manufacturer’s recommended charging adaptor to prevent damage to valve and
its components.
h) When recharging separate expellant source fire extinguishers, make sure filled enclosure
is in place and tightened down. Replace all safety devices prior to installing replacement
cartridges.
i) Use only gas cartridges recommended by the manufacturer. Cartridge features such as
pressure relief, puncturing capabilities, fill density, and thread compatibility are designed
and approved to specific functional requirements.
j) Use proper safety seals, as other types, such as meter seals, could possibly fail to break
at the prescribed requirements.
k) Regulators utilised on wheeled fire extinguishers are factory pinned at the operating
pressure and should not be field adjusted.
l) The temperature of water tanks must not be less than 4°C (40°F).
m) The temperature of water in tanks with low temperature alarms connected to a constantly
attended location must be inspected and recorded weekly during the heating season.
n) The temperature of water in tanks without low temperature alarms connected to a
constantly attended location must be inspected and recorded daily during the heating
season.
o) Some manufacturers require that their fire extinguishers be returned to the factory for
recharging.
p) To determine the gross weight, the entire fire extinguisher should be weighed empty. The
weight of the specified recharge agent should be added to this amount.
Mixing multipurpose dry chemicals with alkaline based dry chemicals could result in a
chemical reaction capable of developing sufficient pressures to rupture a fire extinguisher.
Substituting a different formulation for the one originally employed could cause malfunctioning
of the fire extinguisher or result in substandard performance.
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 30 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 31 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
The compressor/dryer module must be a fully enclosed, factory-assembled, and factory tested
package of a vertical design (compressor above motor). It must incorporate the compressor
driver, purification system, controls, interconnecting piping, and wiring. The scope of supply
must include the following:
a) Compressor. The compressor block must be multistage, air-cooled, oil-lubricated, and
rated for continuous duty at 34,475 kPa with a charging rate of [________ cfm]. The
crankcase must be fully enclosed with oversized ball bearings on each end. The
connecting rods must utilize needle bearings on both ends. Pistons must be aluminium or
cast iron and must incorporate piston rings on all stages. Cylinders must be of cast iron.
Relief valves and individually mounted intercoolers must be utilised after each stage of
compression. The after-cooler must be designed to deliver final air at a temperature not to
exceed -6.67°C above ambient. The compressor flywheel must incorporate a high-velocity
cooling fan for maximum heat dissipation. An automatic condensate drain system must be
supplied as standard equipment on all systems.
b) Dryer System. The system must be of a multi-chamber arrangement; each constructed of
aluminium alloy with a tensile strength of 572,285 kPa and designed for 34,475 kPa
working pressure with a 4 to 1 safety factor. The first chamber must be a mechanical
separator to eliminate oil and water. Subsequent chambers must utilise replacement
cartridges to further remove moisture and oil vapour. The dryer system must process
[______ cf] before cartridge replacement. The air delivered must have a -51.1°C dew
point or lower.
This standard must be read in addition to sections on 65 mm Fire Hydrants and Related
Equipment, Fighting Water Supply and Fire Pumps and 25 mm Fire Hosereels.
5.13.1.1 General
This Standard provides the minimum requirements for the routine inspection, testing, and
maintenance of standpipe and hose systems. Table 1 must be used to determine the minimum
required frequencies for inspection, testing, and maintenance.
a) Valves and Connections. Valves and fire department connections must be inspected,
tested, and maintained in accordance with NFPA 25.
b) Impairments. Where the inspection, testing, and maintenance of standpipe and hose
systems results or involves a system that is out of service, the procedures outlined in
NFPA 25 must be followed.
Table 1 - Summary of Standpipe and Hose System Inspection, Testing and Maintenance
5.13.1.2 Inspection
a) Components of standpipe and hose systems must be visually inspected quarterly or as
specified in Table 1.
b) Table 2 must be used for the inspection, testing, and maintenance of all classes of
standpipe and hose systems.
c) Checkpoints and corrective actions outlined in Table 2 must be followed to determine that
components are free of corrosion, foreign material, physical damage, tampering, or other
conditions that adversely affect system operation.
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 33 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
5.13.1.3 Testing
The tests must be conducted by a qualified person. Where water damage is a possibility, an
air test must be conducted on the system at 1700 kPa prior to introducing water to the system.
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 34 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
f) A main drain test must be performed on all standpipe systems with automatic water
supplies in accordance with the requirements of NFPA 25.
g) The test must be performed at the low point drain for each standpipe or the main drain
test connection where the supply main enters the building (when provided).
h) Pressure gauges must be provided for the test and must be maintained.
5.13.1.6 Maintenance
a) Maintenance and repairs must be in accordance with Table 1 and Table 2.
b) Hose Connections. After each use, all hose connected to sprinkler systems must be
cleaned, drained, and thoroughly dried before being placed in service. Hose that has
been exposed to hazardous materials must be disposed of in an approved manner or
must be decontaminated by a method approved for the contaminant and by the hose
manufacturer’s recommendation. Equipment that does not pass the inspection or the
testing requirements must be repaired and tested again or replaced.
5.13.2.1 Introduction
A water pressure and flow test must be conducted at intervals not exceeding 90 days on all
fire water distribution systems to determine the rate of flow and pressure available for fire-
fighting purposes.
5.13.2.2 Procedure
a) Tests must be conducted during a period of expected normal demand. The procedure
must consist of discharging water at a measured rate of flow from the system at a given
location and observing the corresponding pressure drop in the mains.
b) All new systems must be tested prior to the occupancy of the building or area which they
serve. Any installing contractor must provide an appropriate test certificate.
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 35 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
a) The water supply must be tested to verify compliance with the design.
b) This test must be conducted by flowing water from the hydraulically most remote and high
hose connection (hydrant).
5.13.4.4 Instructions
The installing contractor must provide the owner with:
a) All literature and instructions provided by the manufacturer of any device or equipment
installed as part of the work, describing the proper operation and maintenance of such
equipment or device.
b) A copy of NFPA 25, the Standard for the Inspection, Testing, and Maintenance of Water-
Based Fire Protection Systems.
5.13.5.1 Frequency
A hydrant test under simulated fire conditions must be conducted at intervals not exceeding 12
months, in every building or area served by the fire water system.
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 36 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
Figure 1
c) In the figure above, test layouts are indicated showing the residual hydrant (designated
‘R’) and hydrants to be flowed (designated ‘F’). The number of hydrants used in any test
depends upon the number of hydrants which will foreseeably be used in combating a fire
in the particular area, save that in no case are more than 3 hydrants required to be tested
simultaneously.
d) To obtain satisfactory test results of theoretical calculation of expected flows or rated
capacities, sufficient discharge should be achieved to cause a drop in pressure at the
residual hydrant of at least 25%, or to flow the total demand necessary for the system
demand or fire-fighting purposes.
e) It is preferable to flow water past the residual hydrant.
5.13.5.3 Equipment
a) The equipment necessary for field work consists of a single Bourdon pressure gauge, a
number of Pitot tubes and a special hydrant cap tapped with a hole into which a short
length of brass pipe is fitted. This pipe is provided with a T connection for the gauge and a
cock at the end for relieving air pressure. Pressure gauges are to be calibrated every 12
months, or more frequently, depending on use.
b) When more than one hydrant is flowed, it can be desirable and necessary to use portable
radios to facilitate communications.
c) It is preferred to use an “Underwriter’s Playpipe”, or some other form of stream
straightener with a known coefficient of discharge when testing hydrants, due to the more
streamlined flow and more accurate Pitot reading which may be thus achieved.
of the pressure drop can be controlled by the number of hydrants used and the number of
outlets opened on each.
d) After the readings have been taken, hydrants should be shut down slowly, one at a time,
to prevent undue surges in the system.
Figure 2
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 38 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
supplied by pumps at one location and having no elevated storage. If the pressure at the
pump station drops during the test, it is an indication that the distribution system is
capable of delivering more than the pumps can deliver at their normal operating pressure.
b) It is necessary to use a value for the drop in pressure for the test that is equal to the
actual drop obtained in the field during the test, minus the drop in discharge pressure at
the pumping station.
c) If sufficient pumping capacity is available at the station and the discharge pressure could
be maintained by operating additional pumps, the water system as a whole could deliver
the computed quantity. If, however, additional pumping units are not available, the
distribution system would be capable of delivering the computed quantity, but the water
system as a whole would be limited by the pumping capacity.
d) The portion of the pressure drop for which a correction can be made for tests on systems
with storage is generally estimated upon the basis of a study of all the tests made and the
pressure drops observed on the recording gauge at the station for each. The corrections
can vary from very substantial portions of the observed pressure drops for tests near the
pumping station, to zero for tests remote from the station. It is preferable to flow water
past the residual hydrant.
b) Moreover, supply to meet domestic and service water requirements must be provided
separately and independently of the supply for fire fighting purposes.
c) Regarding water supply to the hydrant system,
Water supplies to hydrants must be installed in compliance with existing legislation,
and any Municipal bye-laws which may apply.
As a general rule the requirements of the National Building Regulations must be
regarded as a minimum standard. Based on these Regulations the minimum flow and
accompanying pressure for hydrants is 20 litres per second (1200 litres/minute) per
unit at an open-ended flow pressure of not less than 300 kPa for a minimum duration
of four hours. These requirements must be met by each hydrant unit in a system with
3 units operating simultaneously.
5.13.6.4 Testing
a) A fire team member, fire officer, fire marshal, or other appointed person must carry out
daily visual checks on lugs, washers, hand wheels, open and shut valve indicators and
water pressures (where a gauge is provided).
b) The minimum frequency for hydrant testing under simulated fire conditions is once in
every 12 months, and following any structural maintenance or alterations to system(s).
c) The water level must be checked daily in all supply dams, tanks or reservoirs.
This standard must be read in addition to section on Fire Fighting Water Supply and Fire Pumps
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 40 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
5.14.1 General
a) This Standard provides the minimum requirements for the routine inspection, testing, and
maintenance of private fire service mains and their appurtenances. Table 1 must be used
to determine the minimum required frequencies for inspection, testing, and maintenance.
Table 1 – Summary of Private Fire Service Main Inspection, Testing and Maintenance
Valves and fire department connections must be inspected, tested, and maintained in
accordance with NFPA 25.
Fire hose must be maintained in accordance with NFPA 1962, Standard for the Care, Use, and
Service Testing of Fire Hose Including Couplings and Nozzles.
a) To avoid false alarms where a supervisory service is provided, the alarm receiving
facilities must always be notified by the owner or designated representative as follows:
Before conducting any test or procedure that could result in the activation of an alarm
After such tests or procedures are concluded
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 41 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
Generally, underground piping cannot be inspected on a routine basis. However, flow testing
can reveal the condition of underground piping.
Mainline strainers must be inspected and cleaned after each system flow exceeding that of a
nominal 50 mm orifice and must be removed and inspected annually for failing, damage, and
corroded parts with the necessary corrective action taken as shown in Table 3.
Dry barrel and wall hydrants shall be inspected annually and after each operation with the
necessary corrective action taken as shown in Table 4.
Wet barrel hydrants must be inspected annually and after each operation the necessary
corrective action as shown in Table 5 must be taken.
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 42 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
Monitor nozzles must be inspected semi-annually with the necessary corrective action taken as
shown in Table 6 below.
Hose houses must be inspected quarterly with the necessary corrective action taken as shown
in Table 7.
5.14.12 Testing
a) Underground and Exposed Piping Flow Tests. Underground and exposed piping must
be flow tested to determine the internal condition of the piping at minimum 5-year
intervals.
b) Flow tests must be made at flows representative of those expected during a fire for the
purpose of comparing the friction loss characteristics of the pipe with those expected for
the particular type of pipe involved, with due consideration given to the age of the pipe
and to the results of previous flow tests.
c) Any flow test results that indicate deterioration of available water flow and pressure must
be investigated to the complete satisfaction of the authority having jurisdiction to ensure
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 43 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
that the required flow and pressure are available for fire protection.
d) Where underground piping supplies individual fire sprinkler, standpipe, water spray, or
foam - water sprinkler systems and there are no means to conduct full flow tests, tests
generating the maximum available flows must be permitted.
5.14.13 Maintenance
5.14.13.1 General
a) All equipment must be maintained in proper working condition, consistent with the
manufacturer’s recommendations.
b) Mainline strainers must be cleaned annually and after each operation.
c) Records must be maintained.
a) This Standard provides the minimum requirements for the routine inspection, testing, and
maintenance of water storage tanks. Table 1 must be used to determine the minimum
required frequencies for inspection, testing, and maintenance.
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 44 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
b) Valves and Connections. Valves and fire department connections must be inspected,
tested, and maintained in accordance with NFPA 25.
c) Impairments. The procedures outlined in NFPA 25 must be followed where impairment to
protection occurs.
d) Notification to Supervisory Service. To avoid false alarms where a supervisory service
is provided, the alarm receiving facility always must be notified by the owner or
designated representative as follows:
Before conducting any test or procedure that could result in the activation of an alarm
After such tests or procedures are concluded.
a) Tanks equipped with supervised water level alarms that are connected to a constantly
attended location must be inspected quarterly.
b) Tanks not equipped with supervised water level alarms connected to a constantly
attended location must be inspected monthly.
a) The temperature of water tanks must not be less than 4°C (40°F).
b) The temperature of water in tanks with low temperature alarms connected to a constantly
attended location must be inspected and recorded weekly during the heating season.
c) The temperature of water in tanks without low temperature alarms connected to a
constantly attended location must be inspected and recorded daily during the heating
season.
a) The exterior of the tank, supporting structure, vents, foundation, and catwalks or ladders,
where provided, must be inspected quarterly for signs of obvious damage or weakening.
b) The area surrounding the tank and supporting structure, where provided, must be
inspected quarterly to ensure that the following conditions are met:
The area is free of combustible storage, trash, debris, brush, or material that could
present a fire exposure hazard.
The area is free of the accumulation of material on or near parts that could result in
accelerated corrosion or rot.
The tank and support are free of ice build-up.
The exterior sides and top of embankments supporting coated fabric tanks are free of
erosion.
c) Expansion joints, where provided, must be inspected annually for leaks and cracks.
d) The hoops and grillage of wooden tanks must be inspected annually.
e) Exterior painted, coated, or insulated surfaces of the tank and supporting structure, where
provided, must be inspected annually for signs of degradation.
a) The interior of steel tanks without corrosion protection must be inspected every 3 years.
b) The interior of all other types of tanks must be inspected every 5 years.
c) Where interior inspection is made by means of underwater evaluation, silt must first be
removed from the tank floor.
d) The tank interior must be inspected for signs of pitting, corrosion, spalling, rot, other forms
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 45 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
of deterioration, waste materials and debris, aquatic growth, and local or general failure of
interior coating.
e) Steel tanks exhibiting signs of interior pitting, corrosion or failure of coating must be
tested.
f) The anti-vortex plate must be inspected for deterioration or blockage.
5.15.6 Testing
a) Level indicators must be tested every 5 years for accuracy and freedom of movement.
b) High and low water level alarms must be tested semi-annually.
c) Pressure gauges must be tested every 5 years with a calibrated gauge in accordance with
the manufacturer’s instructions. Gauges not accurate to within 3% of the scale of the
gauge being tested must be recalibrated or replaced.
d) Where a drained interior inspection of a steel tank is conducted the following tests must
be conducted:
Evaluation of tank coatings must be made in accordance with the adhesion test of
ASTM D 3359, Standard Test Methods for Measuring Adhesion by Tape Test,
generally referred to as the “cross-hatch test.”
Dry film thickness measurements must be taken at random locations to determine the
overall coating thickness.
Non-destructive ultrasonic readings must be taken to evaluate the wall thickness
where there is evidence of pitting or corrosion.
Interior surfaces must be spot wet-sponge tested to detect pinholes, cracks, or other
compromises in the coating. Special attention must be given to sharp edges such as
ladder rungs, nuts, and bolts.
Tank bottoms must be tested for metal loss and/or rust on the underside by use of
ultrasonic testing where there is evidence of pitting or corrosion. Removal, visual
inspection, and replacement of random floor coupons must be an acceptable
alternative to ultrasonic testing.
Tanks with flat bottoms must be vacuum-box tested at bottom seams in accordance
with test procedures found in NFPA 22, Standard for Water Tanks for Private Fire
Protection.
5.15.7 Maintenance
a) Voids discovered beneath the floors of tanks must be filled by pumping in grout or
accessing the sand and replenishing.
b) The tank must be maintained full or at the designed water level.
c) The hatch covers in the roofs and the door at the top of the frost-proof casing must always
be kept securely fastened with substantial catches as a protection against freezing and
windstorm damage.
d) No waste materials, such as boards, paint cans, trim, or loose material, must be left in the
tank or on the surface of the tank.
e) The exposed surfaces of embankment-supported coated fabric (ESCF) tanks must be
cleaned and painted every 2 years or in accordance with the manufacturer's instructions.
f) Silt must be removed during interior inspections or more frequently as needed to avoid
accumulation to the level of the tank outlet.
g) The maintenance of ESCF tanks must be completed in accordance with this section and
the tank manufacturer’s instructions.
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 46 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
5.15.8 Records
a) Hosereel stop valves must be sealed with lead or plastic seals and reserved solely for fire
fighting purposes.
b) The internal diameter of the service pipe feeding a hosereel system must be a minimum
of:
32 mm if it serves 1 to 3 hosereels.
38 mm if it serves 4 or 5 hosereels.
50 mm if it serves more than 5 hosereels.
c) Service feeder pipes for hosereels may be connected to a hydrant main, or upstream from
the main stop valve of a sprinkler system.
d) All piping and fittings used in a hosereel system must be capable of withstanding a
pressure of up to 2 500 kPa.
e) Every hosereel system must be fitted with one or more pressure gauges reading up to 2
500 kPa. One must be situated at the hosereel furthest from the incoming water supply.
f) Hosereels must contain not less than 30 m of 25 mm reinforced plastic or rubber hose,
complete with adjustable jet / spray shut off nozzle.
g) The following is a typical hosereel system layout, illustrating the application of the above
requirements.
Figure 1
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 47 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
a) Reconditioning
Carry out reconditioning in accordance with SABS 1475: Part I once every 3 years or
more frequently when circumstances so require.
b) On-Site Maintenance
In years where reconditioning is not required, carry out on-site maintenance annually in
accordance with the following guidelines:
Remove and check the nozzle-cock for blockage, then refit the nozzle-cock.
Hosereels must be fully extended once a year. Note that more frequent extension
causes damage to the hosereel spindle and glands. Completely unwind the hose from
the reel. During the unwinding operation, check:
Whether the reel rotates freely on its spindle. If necessary, lubricate the spindle or
replace the spindle and / or spindle bush.
The hose condition
Whether the coverage and overlap of adjacent hosereels is adequate to protect all
areas.
Whether the hose runs out freely through the hose run-out guide. If necessary,
lubricate or replace the run-out guide.
Open the discharge nozzle-cock and, using water, purge all air from the reel and
hose. Close the nozzle-cock, increase the water pressure to 2 000 kPa and, while the
hose is under pressure, check
The waterway for leaks. If necessary, adjust or renew glands/seals.
All hose connections for leaks. Rectify where necessary.
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 48 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
Check the entire hose-reel assembly for corrosion. Repair or replace as necessary.
Ensure that the hosereel base is firmly affixed to the wall.
Rewind the hose neatly but without undue tension on the reel. Place the discharge
nozzle-cock in its stowage bracket.
Sign the maintenance label or sign and attach a new maintenance label.
This standard must be read in addition to section Fire Fighting Water Supply and Fire Pumps.
5.17.1 General
a) This Standard provides the minimum requirements for the routine inspection, testing, and
maintenance of fire pump assemblies. Table 1 must be used to determine the minimum
required frequencies for inspection, testing, and maintenance.
b) Valves and Connections. Valves and fire department connections must be inspected,
tested, and maintained in accordance with NFPA 25.
c) Auxiliary Equipment. The pump assembly auxiliary equipment must include the
following:
a) Pump accessories as follows:
b) Pump shaft coupling
c) Automatic air release valve
d) Pressure gauges
e) Circulation relief valve (not used in conjunction with diesel engine drive with heat
exchanger)
f) Pump test device(s)
g) Pump relief valve and piping (where maximum pump discharge pressure exceeds the
rating of the system components or the driver is of variable speed)
h) Alarm sensors and indicators
i) Right-angle gear sets (for engine-driven vertical shaft turbine pumps)
j) Pressure maintenance (jockey) pump and accessories
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 49 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
d) Water Supply to Pump Suction. The suction supply for the fire pump must provide the
required flow at a gauge pressure of zero (0) bar [zero (0) psi] or higher at the pump
suction flange to meet the system demand.
e) Energy Source. The energy sources for the pump driver must supply the necessary
brake horsepower of the driver so that the pump meets system demand.
f) Driver. The pump driver must not overload beyond its rating (including any service factor
allowance) when delivering the necessary brake horsepower.
g) Controller. Automatic and manual controllers for applying the energy source to the driver
must be capable of providing this operation for the type of pump used.
h) Impairments. The procedures outlined in NFPA 25 must be followed where impairment to
protection occurs.
i) Notification to Supervisory Service. To avoid false alarms where a supervisory service
is provided, the alarm receiving facility always must be notified by the owner or
designated representative as follows:
k) Before conducting any test or procedure that could result in the activation of an alarm
l) After such tests or procedures are concluded
5.17.2 Inspection
The purpose of inspection must be to verify that the pump assembly appears to be in operating
condition and is free from physical damage.
The pertinent visual observations specified in the following checklists must be performed
weekly:
5.17.3 Testing
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 51 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
i) Alarm conditions must be simulated by activating alarm circuits at alarm sensor locations,
and all such local or remote alarm indicating devices (visual and audible) must be
observed for operation.
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 52 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
j) Safety procedures must be followed while working near electric motor-driven fire pumps.
k) After the water-flow portions of the annual test or fire protection system activations, the
suction screens must be inspected and cleared of any debris or obstructions.
5.17.3.11 Reports
a) Any abnormality observed during inspection or testing must be reported promptly to the
person responsible for correcting the abnormality.
b) Test results must be recorded and retained for comparison.
c) All time delay intervals associated with the pump’s starting, stopping, and energy source
transfer must be recorded.
5.17.3.12 Maintenance
a) A preventive maintenance program must be established on all components of the pump
assembly in accordance with the manufacturer’s recommendations.
b) Records must be maintained on all work performed on the pump, driver, controller, and
auxiliary equipment.
c) In the absence of manufacturer’s recommendations for preventive maintenance, Table 2
must be used for alternative requirements.
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 53 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
Visual
Complete as Applicable Check Change Clean Test Frequency
Inspection
A. Pump System
1. Lubricate pump bearings x Annually
2. Check pump shaft end play x Annually
Check accuracy of pressure
3. x x Annually
gauges and sensors
Check pump coupling
4. x Annually
alignment
After each
5. Wet pit suction screens x x pump
operation
B. Mechanical Transmission
1. Lubricate coupling x Annually
Lubricate right-angle gear
2. x Annually
drive
C. Electrical System
Exercise isolating switch and
1. x Monthly
circuit breaker
Trip circuit breaker (if
2. x Annually
mechanism provided)
Operate manual starting Semi-
3. x
means (electrical) annually
Inspect and operate
4. emergency manual starting x x Annually
means (without power)
Tighten electrical connections
5. x Annually
as necessary
Lubricate mechanical moving
6. parts (excluding starters and x Annually
relays)
Calibrate pressure switch
7. x Annually
settings
8. Grease motor bearings x Annually
D. Diesel Engine System
1. Fuel
a) Tank level x x Weekly
b) Tank float switch x Weekly
c) Solenoid valve operation x Weekly
Strainer, filter, or dirt leg, or
d) x Quarterly
combination thereof
Water and foreign material in
e) x Annually
tank
f) Water in system X x Weekly
h) Flexible hoses and connectors x Weekly
Tank vents and overflow
i) x x Annually
piping unobstructed
j) Piping x Annually
2. Lubrication System
a) Oil level x x Weekly
b) Oil change x 50 hours or
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 54 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
Visual
Complete as Applicable Check Change Clean Test Frequency
Inspection
annually
50 hours or
c) Oil filter(s) x
annually
d) Lube oil heater x Weekly
e) Crankcase breather x x x Quarterly
3. Cooling System
a) Level x x Weekly
Semi-
b) Antifreeze protection level x
annually
c) Antifreeze x Annually
Adequate cooling water to
d) x Weekly
heat exchanger
e) Rod out heat exchanger x Annually
f) Water pump(s) x Weekly
Condition of flexible hoses
g) x x Weekly
and connection
h) Jacket water heater x Weekly
Inspect duct work, clean
i) x x x Annually
louvres (combustion air)
j) Water strainer x Quarterly
4. Exhaust System
a) Leakage x x Weekly
b) Drain condensate trap x Weekly
c) Insulation and fire hazards x Quarterly
d) Excessive back pressure x Quarterly
Exhaust system hangers &
e) x Annually
supports
Semi-
f) Flexible exhaust section x
annually
5. Battery System
a) Electrolyte level x Weekly
b) Terminals clean and tight x x Quarterly
Remove corrosion, case
c) x x Monthly
exterior clean and dry
Specific gravity or state of
d) x Monthly
charge
e) Charger and change rate x Monthly
f) Equalise charge x Monthly
6. Electrical System
a) General inspection x Weekly
Tighten control and power
b) x Annually
wiring connections
Wire chafing where subject to
c) x x Quarterly
movement
Operation of safe ties and Semi-
d) x x
alarms annually
Semi-
e) Boxes, panels, & cabinets x
annually
f) Circuit breakers or fuses x x Monthly
g) Circuit breakers or fuses x Bi-annually
d) The preventive maintenance program must be initiated immediately after the pump
assembly has passed acceptance tests.
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 55 of 57
company.
IMPLEMENTATION DATE 9/2/2013
HEAD OFFICE FIRE PROTECTION STANDARD FOR FIRE FIGHTING
EQUIPMENT DOC NO AATC000171
6 REFERENCES
Quality Requirements For Suppliers Of Critical And Major Equipment
(GTS041)
NFPA 17 and 17A (National
Standard For Dry Chemical And Wet Extinguishing Systems
Fire Protection Association):
Fire Protection Standard for Fire Sprinkler, Deluge, Water and
Gaseous Suppression Systems
Fire Protection Standard for Vehicles and Moving Machines
Fire Protection Standard for Electrical Equipment and Installations
Fire Protection Standard for Buildings and Structures
Fire Protection Standard for Fire Fighting Equipment
Protection
SABS 0287 Automatic Sprinkler Installations For Fire-Fighting Purposes
Compliance Is Mandatory Only Where The Pumps Supply Sprinkler
ASIB
Systems, Upon Which Life Safety Depends
SABS 543 Fire Hose Reels
Standard For The Installation Of Foam-Water Sprinkler And Foam-
NFPA 16
Water Spray Systems
NFPA 1901 Standard For Automotive Fire Apparatus
Standard On Design Of And Design Verification Tests For Fire
NFPA 1931
Department Ground Ladders
NFPA 1961 Standard On Fire Hose
Standard On Open-Circuit Self-Contained Breathing Apparatus For
NFPA 1981
Fire And Emergency Services
SAE J348 Wheel Chocks
NFPA 72 National Alarm Code
Standard For The Inspection, Testing, And Maintenance Of Water
NFPA 25
Based Fire Protection Systems
Standard For The Care, Use And Service Testing Of Fire Hose
NFPA 1962
Including Coupling And Nozzles
NFPA 110 Standard For Emergency And Standby Power Systems
Hand Held Fire Extinguishers Fire Checklist
65 mm Hydrants And Related Equipment Checklist
25 mm Fire Hosereels Checklist
7 REVISION HISTORY
Version No. Reason for Change Date
00 New Document 01/08/2013
8 APPENDICES
Refer to the AATC Document Management System for the latest version of the document. Copyright resides with the
Page 57 of 57
company.