You are on page 1of 5

Note 12  Level 2

32 TheStructuralEngineer Technical
June 2014 Technical Guidance Note

Introduction to
steel portal frames
Introduction
Portal frames are a simple and very addressed in more detail in Technical ICON • Design principles
common type of framed (or skeleton) Guidance Note No. 10 (Level 1) LEGEND
structure. Steel portal frames, in Principles of lateral stability. Thus,
• Applied practice
particular, are a cost-effective in spite of the inherent simplicity of
structural system to support building portal frames, many aspects of their
envelopes (such as warehouses and analysis, design and detailing require • Further reading
shopping complexes) requiring large careful consideration.
column-free spaces. In general, the Portal frames can be made from • Web resources
loads and consequent deformations concrete, timber and even glass but
for these frames are in the plane of the vast majority, in the UK certainly,
the structure, and hence these are a are constructed from steel. This
2D (or plane) frame structure. Due to Technical Guidance Note gives an
the practical requirement of having introduction to steel portal frames
a clear space between the supports and their preliminary analysis. Steel
of a portal frame, providing in-plane portal frames usually have pinned
bracing is generally not feasible. bases and moment connections at the
Consequently, these frames undergo column/rafter interface and mid-span Span Steel Portal Frame Buildings to
larger deflections and are prone to apex splice in the rafter. Although Eurocode 3), for the sake of brevity
sway laterally, even under the vertical there are other forms of portal frame and clarity this note will be dedicated
loads. The concept of sway frames is (described in Elastic Design of Single- to this particular form.

c) Rafters
d) Rafter to column d) Rafter to column
connection/eave joint connection/eave joint
Design principles

Steel portal frames


Steel portal frame structures provide Eaves haunch Apex joint/splice Eaves haunch
an efficient and cost effective means of a) Base b) Columns
creating large column-free spaces. As such,
this type of structure is used for depots,
warehouses and out-of-town shopping


complexes. Portal frames are prone to
Figure 1
a significant amount of movement and Typical steel portal frame
therefore second order effects. It follows
that the deflection limits for portal frames
are less onerous than for other structures. Identified in Figure 1, the anatomy of a steel The foundations for steel portal frames
As a result, any cladding system affixed to portal frame can be broken down into four generally comprise of a column-base that
them needs to be able to accommodate key in-plane components: connects the column to a concrete pedestal.
more movement than a conventional Depending upon the detailing of the column-
building. a) Base base, it can be idealised as either a pinned
Steel portal frames typically span b) Columns or fixed support. In absence of bracings, the
between 15-50m with a height ranging c) Rafters lateral stiffness of the portal frame is largely
between 5-15m. The roof pitch is typically d) Connections between rafter and column dependent upon the height of the columns
set to 5-10º with portalised bays at 6-8m (eave joints) and splice in the rafter at apex and the type of column-base. Typically, steel
centres longitudinally. (apex joint) portal frames have pinned-base supports.

This version 1.1 published October 2016.


www.thestructuralengineer.org

33

Rafter

Roof
purlins

Rafter
Cladding
Column
rails

Haunch Haunch
stiffener stiffener

Column

• Figure 2
Typical detail of eave joint haunch
• Figure 3
Cladding rails to steel portal frame
acting as buckling restraints to outer flange

The eave and the apex joints are commonly Roof


designed to carry moments. In order to purlins

increase the stiffness of these joints,


stiffening plates (haunches) are used.
For practical purposes, these joints can
be idealised as rigid joints. While these
rigid joints reduce the deflections in the
portal frame (as opposed to non-moment
carrying pinned joints), due to their large
Rafter
spans the extent of displacements under
the loads is relatively larger for the steel
portal frames. Therefore, the serviceability
Fly bracing
criteria dictating the maximum permissible
deflections are somewhat less onerous
than usual.

Connection stiffening
With connections needing to carry a
significant bending moment, it is often
• Figure 4
Fly bracing restraint to inner
flanges of steel portal frame elements
necessary to provide some form of
stiffening to the elements. This typically
takes the form of haunches, which are either of the structure owing to the presence of flange is in compression. In the rafter the
a cut section from the elements they are large door openings in the wall cladding. inner flange is in compression towards
stiffening or fabricated plates. The required In such instances the unrestrained span the column and the outer flange is in
size and extent is dependent on the applied of the column is taken from its base to compression towards the apex.
bending on the portal frame, but in practice the connection with the rafter. Thus, the
haunches typically take up 10% of the columns are vulnerable to both lateral Preliminary analysis
portal span of the rafter element, which will torsional and Euler buckling. Figure 3 is Steel portal frames are statically
optimise the efficiency of the unstiffened a section showing the typical layout of indeterminate structures. It follows
length of the rafter (Figure 2). cladding rails in a portal frame structure. therefore, that some assumptions on the
The rails only provide direct restraint to the relative stiffness of the members within
Buckling restraints outer compression flanges of the rafter/ portal frames are required, in order to
Steel portal frames made from open column. With the ever-present risk of calculate the induced stresses within them.
sections are vulnerable to lateral torsional bending moment reversal due to negative As a preliminary guide it is reasonable to
buckling as they are placed under load. wind pressure, there is a requirement assume that the second moment area of
Cladding rails and roof purlins provide to provide restraint to the inner flange the column is 1.5 times that of the second
restraint to these primary elements. They (especially to the rafters). This restraint, moment of area of the rafter element
are typically made from cold formed thin commonly known as ‘fly bracing’ comes (Fig. 3). Another reasonable assumption
gauged steel rails and span between in the form of two flat plate strips that are is that the highest bending moments in a
portal frames. It is more often the case fixed at 45º from the cladding rail to the portal frame are generated from applied
that while the rafter is restrained, the inner flange of the primary steel element vertical actions, such as self-weight, wind
column is not. This is due to the lack of (Figure 4). and snow. During preliminary design it is
continuity of the rails in the external walls Under gravity loads, the column inner generally acceptable to account for second

Note 12  Level 2

34 TheStructuralEngineer Technical
June 2014 Technical Guidance Note

order effects by increasing the applied bending moment by 15%.


Elastic Design of Single-Span Steel Portal Frame Buildings to
Eurocode 3 provides design formulae for steel portal frames. It
advises that to determine approximate bending stresses in a steel
portal frame, the following formulae can be used:

wL2 (3 + 5m) and wL2


ME = MA = 8 + m # ME
16N
where:

ME is the bending moment in the eve joints of the steel portal frame
MA is the bending moment at the apex joint of the rafter
N = B+mC, where C is 1+2m, B is 2(k+1)+m, m is 1+ϕ, ϕ is f/h

I
and k = R $ hs
IC
For the definitions of w,f,h, IC, IR, L and s see Figure 5.

An alternative preliminary design method is described in Chapter


8 of the Manual for the design of steelwork building structures to
Eurocode 3. It uses a series of design charts from which the initial
sizing of members in a steel portal frame can be derived.
Two plastic hinges are necessary for collapse of portal frames
with pinned-foot columns. Four are commonly shown for reasons
of symmetry.

Initial member sizing


The sizing of the rafter and the column should be based on • Figure 5
Approximate
bending moments in
the design of steel beams and columns, which are described in steel portal frame due to
vertical action
Technical Guidance Notes 1 and 2 (Level 2). The rafters should
be designed assuming that there is a minor axis unrestrained
length between two consecutive cladding rails. Columns should be
designed based on the overall height of the element. The shape of
the bending moment diagram impacts on the design of both the
rafter and column. Elastic Design of Single-Span Steel Portal Frame
Buildings to Eurocode 3 advises that the rafter design should
assume a value of 1.0 for C1 as defined in BS EN 1993-1-1. With
respect to columns, the value of C1 should be set at 1.77 due to the • Figure 6
Bending moment
diagram of portal
triangular shape of the bending moment diagram (Fig. 5). frame using elastic
analysis

Types of analysis
There are two methods of analysing steel portal frames: elastic and (or four with fixed baseplates) are formed.
plastic. The elastic method assumes that the structure does not Otherwise the structure becomes an over-
undergo permanent inelastic deformations when placed under load. complete mechanism, as a portal frame has
When subjected to normal gravity loading, the resulting bending a single degree of indeterminacy when it has
moment profile has a hogging bending moment at the eave joint of pinned baseplates. However, the location of
the frame and a sagging moment in the rafter apex joint. Subject the middle hinge near the apex of the rafter
to certain conditions, it is permissible to re-distribute up to 15% of cannot be pre-determined. Therefore, it is
the maximum bending moment within the portal frame when using assumed that one will form either side of
elastic analysis according to BS EN 1993-1-1 Clause 5.4.1 (4) B. the apex for the purposes of analysis. It is
Figure 6 is the bending moment diagram developed from elastic for this reason that four plastic hinges are
analysis under symmetric gravity loads. shown in Fig. 7, with the two closest to the
Formation of three plastic hinges converts a steel portal frame apex being possible locations for a plastic
with pinned supports into a mechanism. The most likely locations hinge. More information on this subject can
for the plastic hinges to form are close to the eave and apex joints, be found in the J.M. Davies paper False
as they involve the highest hogging or sagging moments. However, mechanisms in elastic-plastic analysis.
if the geometry and loading are symmetric for a portal frame, it is
difficult to predict whether the plastic hinge near the apex joint will Second order effects
form either on its left or right side. Therefore, two plastic hinges are The plastic method certainly presents a
shown near the apex joint in Figure 7, of which only one will form more refined picture of the behaviour of a
under the loading in reality. steel portal frame compared to the elastic
No more than three plastic hinges with pinned baseplates method, and hence can produce a more
www.thestructuralengineer.org

35

efficient design. However, neither account


for the second order effects concerning the
• Figure 9
Typical
baseplate detail for
Column Baseplate
steel portal frame
stability of the steel portal frames: used in UK

• Axial compression of the columns can


cause them to bend, which leads to a
reduction in stiffness Steel packing
• Mid-span of the rafter deflects downwards plates
Holding
down bolts
under the vertical load
• Eccentricity of the vertical load onto
the columns leads to lateral deflections
over and above those generated by the
horizontally applied forces

These second order effects can be split into


two distinct categories: displacements at
connections/joints (P-Δ) and displacements
along element lengths (P-δ) (Figure 8). BS
EN 1993-1-1 Clause 5.2.2 offers a selection
of methods to account for the second order
effects while designing steel structures.
Clause 5.2 of BS EN 1993-1-1 describes the
parameters which can be used to determine
the significance of the second order effects
in the analysis of steel structures.

The factor a is the ratio between the Limiting values of acr : the UK National
cr
elastic critical buckling load Fcr of the Annex currently gives a limiting value for acr
structure for global instability and the of 10; above which second-order effects can
applied design load FEd. Second order effects be ignored for plastic analysis. (For certain
are deemed not to be significant when acr proportions of frame, the limiting value is 5
satisfies the following: for plastic analysis).
F
For elastic analysis: a cr = F cr $ 10 Nominal stiffness of base
Ed Steel portal frames are typically modelled
• Figure 7
Bending moment diagram of portal
frame using plastic analysis For plastic analysis:
F
a cr = F cr $ 15
as having pinned supports at the column
base, but in reality the base has a nominal
Ed
stiffness, acting more like semi-rigid
supports than pure pin supports. In the UK,
bases are typically formed of an unstiffened
baseplate that has four holding down
anchors fixed into the foundations (Figure 9).
It is reasonable and conservative to
consider these semi-rigid supports as
pinned supports at the ultimate limit state
condition. However, this assumption does
not remain valid at the serviceability limit
state condition. Nominally pinned base
connections do provide some additional
resistance to lateral deflection. By taking
into account this additional stiffness, it is
possible to reduce the second order effects
due to deformation of the portal frame as it
deflects under load. It is generally accepted
that 10-15% of the applied moment can be
taken (Fig. 9).

Serviceability deflection limits


BS EN 1993-1-1 does not provide any


guidance on serviceability limits on steel
Figure 8
Second order effects in portal frames portal frames. It is up to the design engineer

Note 12  Level 2

36 TheStructuralEngineer Technical
June 2014 Technical Guidance Note

Table 1 Lateral serviceability deflection limits for steel portal Eurocode 0.


frames Applied practice
Type of cladding Deflection at eaves of steel
portal frame* BS EN 1990-1 Eurocode 0: Basis of Design
Profiled metal sheeting
h/100 BS EN 1993-1-1 Eurocode 3: Design of Steel Structures – Part 1-1:
Fibre reinforced sheeting h/150 General Rules for Buildings

Brickwork masonry h/300


Hollow concrete blockwork masonry h/200 Glossary and
Where h is the height of the eaves from ground level (Fig. 5)
further reading
* All deflection limits are provided as guidance only and are dependent on other factors
not described in this table. Apex – mid-span of portal.

Eaves – top of column/stanchion of portal frame where it connects


Table 2 Vertical serviceability deflection limits for steel portal to the rafter.
frames
Haunch – additional depth into column-to-rafter connection and
Type of cladding Deflection relative to adjacent frames at apex splice connection.
ridge of roof*
Profiled metal sheeting # b/100 # (b 2 + s 2) 0.5 /125 Rafter – primary roof beam to the portal frame.

Fibre reinforced sheeting # b/100 # (b 2 + s 2) 0.5 /165 Stanchion – alternative term attributed to the columns of the portal
frame.
Where b is spacing between steel portal frames and s is the length of rafter (Fig. 5).

* All deflection limits are provided as guidance only and are dependent on other factors Further Reading
not described in this table. The Steel Construction Institute (2012) Elastic Design of Single-Span
Steel Portal Frame Buildings to Eurocode 3 (P397), Ascot, Berkshire:
SCI
to establish a reasonable deflection that
can be safely permitted depending upon The Institution of Structural Engineers (2010) Manual for the
its support conditions. Such limits must be design of steelwork building structures to Eurocode 3, London: The
agreed with the rest of the design team and Institution of Structural Engineers
the client.
As with most serviceability limits, only The Institution of Structural Engineers (2012) Technical Guidance
the unfactored imposed load/characteristic Note 10 (Level 1), The Structural Engineer, 90 (7), pp. 28-31
variable action is considered while
calculating the deflections of a steel portal The Institution of Structural Engineers (2013) Technical Guidance
frame. Note 1 (Level 2), The Structural Engineer, 91 (1), pp. 25-29
The lateral deflection limits are largely
dependent on the cladding materials that The Institution of Structural Engineers (2013) Technical Guidance
make up the walls of the structure. This can Note 2 (Level 2), The Structural Engineer, 91 (2), pp. 40-43
vary from metal sheeting to precast concrete
units. Table 1 is drawn from limits given in The Institution of Structural Engineers (1988) 'False mechanisms in
Elastic Design of Single-Span Steel Portal elastic-plastic analysis', The Structural Engineer, 66 (16), p.268
Frame Buildings to Eurocode 3. It offers
guidance on what limits may be adopted
for the lateral deflection for different types Eurocode 0.
of wall cladding material. It should be noted Web resources
that these are considered to be conservative
in most instances and some engineering The Steel Construction Institute: www.steel-sci.org/
judgement is required before applying them.
For vertical deflections of the rafters, Steel Portal Frames Wiki: www.steelconstruction.info/Portal_frames
Table 2 provides guidance on deflection
limits based on a roof slope that is at least 3º The Institution of Structural Engineers library:
with the horizontal. www.istructe.org/resources-centre/library

You might also like