001 Emergency circuit open (general)

Emergency circuit has been activated.

Alarm class: 1

 One or more emergency push buttons are activated.


 Check the signal layout windows on OP panel to find out which one is
pressed.
 Release the button.

003 Circuit safeties operator machine open (general)

Circuit safeties has been activated.

Alarm class: 1

 Zone 1 fences are opened.


 Check the signal layout windows on OP panel to find out which one is
opened.
 Close the fence.

004 Circuit safeties operator infeed product conveyor open [Pos. 2]


(general)

Circuit safeties has been activated.

Alarm class: 1

 Zone 2 fences are opened.


 Check the signal layout windows on OP panel to find out which one is
opened.
 Close the fence.

005 Circuit safeties operator pallet store open

Circuit safeties has been activated.

Alarm class: 1

 Pad store fence opened.


 Close the fence.

006 Circuit safeties wrapper conveyors open

Circuit safeties has been activated.

Alarm class: 1

 Wrapper fence opened.


 Close the fence.

Guillermo A. Schilpp 1
03/07/2010
Sidel

007 Circuit safeties operator infeed product conveyor open [Pos. 3]


(general)

Circuit safeties has been activated.

Alarm class: 1

 Zone 5 fences are opened.


 Check the signal layout windows on OP panel to find out which one is
opened.
 Close the fence.

017 Infeed conveyors Disable [Pos. 2]

Bottles infeed has been blocked by operator.

Alarm class: 3

 Message. Operator has disabled the bottles infeed at position 2.


 No actions to be taken.

018 Pallet Infeed conveyor Disable

Pallet infeed has been blocked by operator.

Alarm class: 3

 Message. Operator has disabled the pallets infeed.


 No actions to be taken.

020 Machine stopped without alarms

This message came out after 5 minutes that the machine is not running and no
alarms are present.

Alarm class: 3

 Message. Machine has been stopped by operator.


 No actions to be taken.

021 Machine phased stop by operator

The machine was stopped using the stop button when no alarms were presents.

Alarm class: 3

 Message. Machine has been stopped by operator.


 No actions to be taken.

Guillermo A. Schilpp 2
03/07/2010
Sidel
022 Robot 1 Disable

Bottles pick up has been blocked by operator.

Alarm class: 3

 Message. . Operator has disabled the robot 1 pick-up.


 No actions to be taken.

023 Robot 2 Disable

Pad/frame pick up has been blocked by operator.

Alarm class: 3

 Message. . Operator has disabled the robot 2 pick-up.


 No actions to be taken.

025 Tapping Machine Disable

Tapping has been blocked by operator.

Alarm class: 3

 Message. Operator has disabled the tapping machine. The machine is now
in by-pass and it will not tye the pallet.
 No actions to be taken.

026 Infeed conveyors Disable [Pos. 3]

Bottles infeed has been blocked by operator.

Alarm class: 3

 Message. Operator has disabled the bottles infeed at position 3.


 No actions to be taken.

027 Manual Selector Pad Store [OP.8].

The manual selector is used to open “manualy” the pads store to refill it.

Alarm class: 3

 Message. The selector key on OP. 8 is at “open” position.


 No actions to be taken.

028 Select Automatic or Manual Conveyors [Pos.2].

Alarm class: 3

 Message.
 No actions to be taken.

Guillermo A. Schilpp 3
03/07/2010
Sidel
029 Select Automatic or Manual Conveyors [Pos.3].

Alarm class: 3

 Message.
 No actions to be taken.

030 Pallet Elevator Disable

Pallet lift has been blocked by operator.

Alarm class: 3

 Message. . Operator has disabled the pallet lift.


 No actions to be taken.

031 Straping Machine Disable

Pallets wrapper has been blocked by operator.

Alarm class: 3

 Message. . Operator has disabled the wrapper machine.


 No actions to be taken.

033 Emergency button pressed OP1

Emergency circuit has been activated.

Alarm class: 1

 Emergency push button at OP1 has been activated.


 Release the button.

044 Emergency button pressed OP Robot 1

Emergency circuit has been activated.

Alarm class: 1

 Emergency push button at Robot 1 cabinet has been activated.


 Release the button.

045 Emergency button pressed OP Robot 2

Emergency circuit has been activated.

Alarm class: 1

 Emergency push button at Robot 2 cabinet has been activated.


 Release the button.

Guillermo A. Schilpp 4
03/07/2010
Sidel
049 Emergency button pressed OP10

Emergency circuit has been activated.

Alarm class: 1

 Emergency push button at OP10 has been activated.


 Release the button.

065 Machine area 1 guard open

Fence has been opened.

Alarm class: 1

 Zone 1 fence opened.


 Check the signal layout windows on OP panel to find out which one is
opened.
 Close the fence.

066 Product infeed conveyors area 2 guard open [Pos.2]

Fence has been opened.

Alarm class: 1

 Zone 2 fence opened.


 Check the signal layout windows on OP panel to find out which one is
opened.
 Close the fence.

067 Pallet magazine pallet infeed conveyors area 3 guard open

Fence has been opened.

Alarm class: 1

 Zone 3 fence opened.


 Check the signal layout windows on OP panel to find out which one is
opened.
 Close the fence.

068 Pallet Tapping conveyors area 4 guard open

Fence has been opened.

Alarm class: 1

 Zone 4 fence opened.


 Check the signal layout windows on OP panel to find out which one is
opened.
 Close the fence.

Guillermo A. Schilpp 5
03/07/2010
Sidel
069 Product infeed conveyors area 5 guard open [Pos.3]

Fence has been opened.

Alarm class: 1

 Zone 5 fence opened.


 Check the signal layout windows on OP panel to find out which one is
opened.
 Close the fence.

067 Pallet magazine pallet infeed conveyors area 3 guard open

Fence has been opened.

Alarm class: 1

 Zone 3 fence opened.


 Check the signal layout windows on OP panel to find out which one is
opened.
 Close the fence.

073 Machine area 1 barrier triggered

Safety barrier has been activated.

Alarm class: 1

 Zone 1 safety barrier triggered.


 Check the signal layout windows on OP panel to find out which one is
triggered.
 Reset the barrier.

075 Pallet magazine pallet infeed conveyors area 3 barrier triggered

Safety barrier has been activated.

Alarm class: 1

 Zone 3 safety barrier triggered.


 Check the signal layout windows on OP panel to find out which one is
triggered.
 Reset the barrier.

076 Pallet Taping conveyors area 4 barrier triggered

Safety barrier has been activated.

Alarm class: 1

 Zone 4 safety barrier triggered.


 Check the signal layout windows on OP panel to find out which one is
triggered.
 Reset the barrier.

Guillermo A. Schilpp 6
03/07/2010
Sidel
077 Pallet Wrapper conveyors area 4 barrier triggered

Safety barrier has been activated.

Alarm class: 1

 Zone 4 safety barrier triggered.


 Check the signal layout windows on OP panel to find out which one is
triggered.
 Reset the barrier.

145 Space Safety Disable Robot 1

The safety zone is an area where the robot can move freely. While the robot is
moving inside this area, other robots can not enter into this.

Alarm class: 2

 Safety zone has been disable from robot 1 TP (robot OP panel).


 Enable the safety zone.

146 Space Safety Disable Robot 2

The safety zone is an area where the robot can move freely. While the robot is
moving inside this area, other robots can not enter into this.

Alarm class: 2

 Safety zone has been disable from robot 2 TP (robot OP panel).


 Enable the safety zone.

148 Robot 1 Remote Not Enable

Remote control has been disable. Thus, the robot can’t be controled remotly by the
PLC.

Alarm class: 2

 The selector key at robot 1 cabinet “+RB1” is not in “AUTO” position.


 Put the selector in AUTO.

 The button “STEP” at TP has been pressed.


 Release the button.

 An axis limit has been reached.


 Contact Sidel Assistant Service.

Guillermo A. Schilpp 7
03/07/2010
Sidel
149 Robot 2 Remote Not Enable

Remote control has been disable. Thus, the robot can’t be controled remotly by the
PLC.

Alarm class: 2

 The selector key at robot 2 cabinet “+RB2” is not in “AUTO” position.


 Put the selector in AUTO.

 The button “STEP” at TP has been pressed.


 Release the button.

 An axis limit has been reached.


 Contact Sidel Assistant Service.

151 Robot 1 Program Not Running

The program inside the robot controler has stopped.

Alarm class: 2

 Contact Sidel Assistant Service.

152 Robot 2 Program Not Running

The program inside the robot controler has stopped.

Alarm class: 2

 Contact Sidel Assistant Service.

154 Robot 1 Teach Pendant Enable

The teach pendant (TP) is used to program the robot as well as to move it. So, to
do this, is necesary enable the TP.

Alarm class: 2

 The selector key at robot 1 TP (Teach Pendant) is at “ON” position.


 Switch the key to “OFF” position.

155 Robot 2 Teach Pendant Enable

The teach pendant (TP) is used to program the robot as well as to move it. So, to
do this, is necesary enable the TP.

Alarm class: 2

 The selector key at robot 2 TP (Teach Pendant) is at “ON” position.


 Switch the key to “OFF” position.

Guillermo A. Schilpp 8
03/07/2010
Sidel
241 Auxiliary overload switch triggered

Overload protection has been triggered.

Alarm class: 1

 Overload on electrical system of auxiliary circuit.


 Check the electrical failure.

242 Motor overload switch triggered area 1 (all motors)

Overload protection has been triggered.

Alarm class: 1

 Pallet blocked.
 Check if some pallet has blocked along the conveyors.
 Motor circuit problem.
 Check the motor as well as the wiring.

243 Motor overload switch triggered area 2. Pos.2 (all motors)

Overload protection has been triggered.

Alarm class: 1

 Motor circuit problem.


 Check the motor as well as the wiring.

244 Motor overload switch triggered area 3 (all motors)

Overload protection has been triggered.

Alarm class: 1

 Forks motor or up/down motor are blocked.


 Check if there is some block.
 Motor circuit problem.
 Check the motor as well as the wiring.

245 Motor overload switch triggered area 4 (all motors)

Overload protection has been triggered.

Alarm class: 1

 Pallet blocked.
 Check if some pallet has blocked along the conveyors.
 Motor circuit problem.
 Check the motor as well as the wiring.

Guillermo A. Schilpp 9
03/07/2010
Sidel
246 Motor overload switch triggered area 5. Pos.3 (all motors)

Overload protection has been triggered.

Alarm class: 1

 Motor circuit problem.


 Check the motor as well as the wiring.

261 Center Device sensors blocked

Center Device Parachute out of position. When the fence is opened or the air supply
fails the parachutes are inserted. If they are not inserted in a period of 5 seconds,
the alarm come out. When the air supply has been restablished or the fence has
been closed the parachute are desinserted. If it isn’t happend in 5 seconds the
alarm come our.

Alarm class: 1

 Parachutes cylinder sensor failure.


 Check sensor.
 Parachutes cylinder blocked or cylinder air supply is missing.
 Check cylinder as well cylinder air supply.

273 Encoder Center Device blocked

The centerer motor is moving upward/downward and the value of encoder remains
unchanged.

Alarm class: 1

 Encoder failure.
 Check the encoder.
 Axis encoder-motor cupler failure.
 Check cupler.

512 Fault C200

The Elau C200 PLC has a fault. Refer to the diagnostic page to get the diagnostic
code of the alarm.

Alarm class: 1

 Check the diagnostic code in Elau Controler Manual.


 Switch off and switch on the main power supply. To reset some failures it’s
necesary to take off the power supply.
 Contact Sidel Assistance.

513 Pallet profile error input pallet conveyor (530M1)

The photocell of precense and shape are not occupped.

Alarm class: 2

 The pallet is not right positioned.


 Center the pallet between the two photocell.

Guillermo A. Schilpp 10
03/07/2010
Sidel
514 Pallet outfeed error

One pallet reaches the 1st outfeed conveyor photocell while a second finished pallet
is going out.

Alarm class: 2

 The 1st pallet was block between the two conveyors and unfinished its
movement.
 In manual mode ,move the 1st pallet to the 2nd outfeed conveyor and move
the new finished pallet to the 1st outfeed conveyor.
 Reset the alarm and restart the machine.

515 Pallet profile Error centrar conveyor

The photocell of precense and shape are not occupped.

Alarm class: 2

 The pallet is not right positioned.


 Center the pallet between the two photocell.

516 Centerer Device Guide compacting Blocked

Opening or closing action failures.

Alarm class: 2

 Check if the guides are blocked.

518 Centerer Device Level

Both photocell, level and safety are not occupped.

Alarm class: 2

 Level Photocell was moved.


 Put the photocell in right position.
 Encoder problem.
 Check the encoder.
 Motor’s brake is not working.
 Check the brake.

525 Axis-Z Limit Pos.2


526 Axis-Y Limit Pos.2
541 Axis-Z Limit Pos.3
522 Axis-Y Limit Pos.3

The axis has reached the limit sensor.

Alarm class: 2

 Movement error.
 Encoder reading error.
 Do a home positioning.

Guillermo A. Schilpp 11
03/07/2010
Sidel
561 Robot 1 – Head Sensors Not Functioning

The robot is going down to realease and it detects that the safety sensors on the its
head are not working.

Alarm class: 3

 Check the sensors.

562 Robot 1 – Robot head safety device

The safety sensors were actived at pick-up phase.

Alarm class: 3

 Check bottles profile.

574 Robot 1 – Head Bottle not Open

Opening error when traing to open the head’s grips.

Alarm class: 3

 Check the sensor.


 Check the cylinder.

593 Frame lost during transfer

Complete Frame or Frame’s sensor lost when the robot was traslating.

Alarm class: 2

 In manual, release the pad (if there is one) on pad store and then release
the frame on the frame store.
 Restart in auto.

Guillermo A. Schilpp 12