EQUIPMENT LIST INSIDE PIB BUILDING, BULK PLANT, JIZAN

HEAT**
IDENT.

EQUIPMENT TAG DESCRITION DISSIPATION REMARK


Peff Unit
1 ELECTRICAL ROOM EQUIPMENTS
2 4.16 KVA SWITCHGEAR 2600 W NOTE - 2
3 4.16 KVA SWITCHGEAR 2600 W NOTE - 2
4 4.16 KVA SWITCHGEAR 2600 W NOTE - 2
3 4.16 KVA SWITCHGEAR 2600 W NOTE - 2
6 LIGHTING PANELBOARD 300 W NOTE - 1
7 POWER PANELBOARD 450 W NOTE - 1
8 DRY TYPE TRANSFORMER (5kva, assumed) 500 W NOTE - 1
9 UPS SYSTEM PANEL 300 W NOTE - 2
10 UPS PANELBOARD 300 W NOTE - 2
480VAC PANELBOARD 300 W
11 125VDC PANELBOARD 300 W NOTE - 2
12 DC CHARGER 1200 W NOTE - 2
13 LCP 300 W NOTE - 1
14
15 SUB TOTAL 14350 W
16
RACK ROOM EQUIPMENTS
MARSHALLING CABINET 500 NOTE - 1
ELECT/INST INTERFACE CABINET 300 NOTE - 1
PLC CABINET 500 NOTE - 1
MOV MASTER STATION (PAKSKAN) 400 NOTE - 1
VIB/TEMP MONITORING SYSTEM 100 NOTE - 1
LDS SYSTEM CABINET 100 NOTE - 1
METERING SYSTEM/FLOW COMPUTORS 450 NOTE - 1
DACS SERVERS (2 EA)/FTE SWICHES 750 NOTE - 1
PRINTERS (2EA) 400 NOTE - 1
ENGINEERING WORK STATION (2EA) 450 NOTE - 1
METERING SUPERVISORY COMPUTERS (2EA) 900 NOTE - 1
DACS SERVERS/WORKSTATION 900 NOTE - 1
CODITON MONITORING SYS (W/STATION) 450 NOTE - 1
LEAK DETECTION SYSTEM 450 NOTE - 1

SUB TOTAL 6650 W

17 BATTERY ROOM EQUIPMENTS


18 SWITCHGEAR BATTERIES (15 kva, 15 batts) 750 W NOTE - 2
19 UPS BATTERIES (15 kva, 15 batts) 750 W NOTE - 2
20 BATTERY DISCONNECT SWITCH (2 SETS) 150 W NOTE - 2
21 NOTE - 1
22
23 SUB TOTAL 1650 W
24
25 UPS ROOM EQUIPMENTS
26 EQUIPMENT LIST HOLD 2500 W NOTE - 2
27 MISCELLANEOUS 250 W NOTE - 1
28
29 SUB TOTAL 2750 W
COMMUNICATION ROOM EQUIPMENTS
SERVERS Etc. 2500 W

30 SUB TOTAL 2500 W

31 HVAC MECHANICAL ROOM EQUIPMENTS


32 HVAC CONTROL PANEL 450 W NOTE - 1
33 AHU DISCONNECT SWITCH 150 W NOTE - 1
34 AIR HANDLING UNIT 500 W NOTE - 1
35 NOTE - 1
36
37 SUB TOTAL 1100 W
38
39
40

TOTAL

NOTES:
1. EQUIPMENT SIZE AND QUANTITY TO BE DETERMINED LATTER.
2. WAITING FOR INFORMATION.
3. ** ESTIMATION OF HEAT DISSPATION IS BASED ON BEST ENGINEERING
PRACTICES IN ACTUAL SUB STATION INSTALLATIONS.
PIB BUILDING, JIZAN
HVAC Load Analysis
for

PIB BUILDING, JIZAN (CONDITION-II)


BULK PLANT, JIZAN
S'ARAMCO

Prepared By:

Arif
AMCDE
P. B. # 2502
AL-KHOBAR-31952
03-858-8877 Extn. 231
Saturday, January 23, 2010
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
AMCDE PIB BUILDING, JIZAN
Al-Khobar, 31952 Page 2

General Project Data Input


General Project Information
Project file name: C:\OLD COMPUTER\MYCOMPUTER\NEW
D\ARIF\MYDOCU~1\KBR\PHIL TAYLOR- SUB#2,3&4
PIB
SHELTOR-\PIB\PRELIM CALCS COND-II PIB.CHV
Project title: PIB BUILDING, JIZAN
Project date: 02 DEC'2009
Project comment: ONDITION-II: Cooling Load is calculated with Summer Design Wet
Bulb and Mean coincident Dry Bulb Temperatures
Weather reference city: JIZAN, SAUDI ARABIA
Client name: PIB BUILDING, JIZAN (CONDITION-II)
Client address: BULK PLANT, JIZAN
Client city: S'ARAMCO
Company name: AMCDE
Company representative: Arif
Company address: P. B. # 2502
Company city: AL-KHOBAR-31952
Company phone: 03-858-8877 Extn. 231
Company fax: 03-858-0061
Company e-mail address: arif@amcde.com
Barometric pressure: 29.910 in.Hg.
Altitude: 10 feet
Latitude: 17 Degrees
Mean daily temperature range: 14 Degrees
Starting & ending time for HVAC load calculations: 1am - 12am
Number of unique zones in this project: 6

Building Default Values


Calculations performed: Both heating and cooling loads
Lighting requirements: 2.50 Watts per square foot
Equipment requirements: 3.00 Watts per square foot
People sensible load multiplier: 250 Btuh per person
People latent load multiplier: 200 Btuh per person
Zone sensible safety factor: 10 %
Zone latent safety factor: 10 %
Zone heating safety factor: 10 %
People diversity factor: 100 %
Lighting profile number: 1
Equipment profile number: 1
People profile number: 1
Building default ceiling height: 0.00 feet
Building default wall height: 17.00 feet

Internal Operating Load Profiles (C = 100)


hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 C C C C C C C C C C C C C C C C C C C C C C C C
2 C C C C C C C C C C C C C C C C C C C C C C C C
3 C C C C C C C C C C C C C C C C C C C C C C C C
4 C C C C C C C C C C C C C C C C C C C C C C C C
5 C C C C C C C C C C C C C C C C C C C C C C C C
6 C C C C C C C C C C C C C C C C C C C C C C C C
7 C C C C C C C C C C C C C C C C C C C C C C C C
8 C C C C C C C C C C C C C C C C C C C C C C C C
9 C C C C C C C C C C C C C C C C C C C C C C C C
10 C C C C C C C C C C C C C C C C C C C C C C C C

C:\ ...\PRELIM CALCS COND-II PIB.CHV Saturday, January 23, 2010, 08:10 AM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
AMCDE PIB BUILDING, JIZAN
Al-Khobar, 31952 Page 3

General Project Data Input (cont'd)


Building-Level Design Conditions

Design Outdoor Outdoor Indoor Indoor Grains In/Outdoor


Month Dry Bulb Wet Bulb Rel.Hum Dry Bulb Diff Correction
July 93 86 50% 72 120.37 7
August 86 86 50% 72 132.09 0
Winter 68 72

Master Roofs
Roof ASHRAE Roof Dark Susp.
No. Roof# U-Fac Color Ceil
1 6 0.080 Yes No
Roof #1 Description: Flat roof, 6" lightweight concrete deck with 2" insulation, no ceiling below

Master Walls
Wall ASHRAE Wall Wall
No. Group U-Fac Color
1 B 0.144 D
Wall #1 Description: Block wall, 8" sand & gravel, filled core, bare block exterior, interior finish

Master Glass
Glass Summer Winter Glass Interior Interior
No. U-Factor U-Factor Shd.Coef. Shading Shd.Coef
1 0.610 0.760 0.850 2 0.640

C:\ ...\PRELIM CALCS COND-II PIB.CHV Saturday, January 23, 2010, 08:10 AM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
AMCDE PIB BUILDING, JIZAN
Al-Khobar, 31952 Page 4

Air Handler Input


Air Handler Number 1 Input Data
Name: AHU-1 Or 2
Terminal type: Constant Volume
Method for CV Sum of Peaks
Supply fan type: Draw-thru fan
Calculations performed: Both heating and cooling loads
Excess supply air: Reserve
Occurrences: 1
People profile number: 1
Lighting profile number: 1
Equipment profile number: 1
Exhaust may not exceed supply air: No
Leaving heating coil temp (deg.F): 110.0
Leaving cooling coil temp (deg.F): 56.0
Cooling coil CFM 0
Misc. Btuh gain - supply side: 0
Misc. Btuh gain - return side: 0
Combined fan & motor efficiency: 65
Static pressure across fan (in.wg.): 1.20
Summer supply duct temp rise (deg.F): 0.000
Summer return duct temp rise (deg.F): 0.000
Winter supply duct temp drop (deg.F): 0.000
Winter return duct temp drop (deg.F): 0.000
Chilled water temp difference (deg.F): 0.000
Hot water temp difference (deg.F): 0.000
Cooling ventilation: 1000 Direct
Cooling infiltration: 0 Direct
Heating ventilation: 1000 Direct
Heating infiltration: 0 Direct
Pretreated outside air: none
Pretreated air Summer DB (deg.F): 0
Pretreated air Summer WB (deg.F): 0
Pretreated air Winter DB (deg.F): 0

Design Outdoor Outdoor Indoor Indoor Grains In/Outdoor


Month Dry Bulb Wet Bulb Rel.Hum Dry Bulb Diff Correction
July 93 86 50% 74 116.97 7
August 86 86 50% 74 128.71 0
Winter 68 72

C:\ ...\PRELIM CALCS COND-II PIB.CHV Saturday, January 23, 2010, 08:10 AM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
AMCDE PIB BUILDING, JIZAN
Al-Khobar, 31952 Page 5

Zone Input
Zone 1: BATTERY RM (120 sq.ft) (Group 1)
Air Handler number: 1 Zone occurrences: 1
Zone length: (feet) 12.00 Zone width (feet): 10.00
Lighting Watts: 300 Equipment Watts: 1,650
Number of people in zone: 0 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 15.00 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: Direct Cooling ventilation value: 500.000
Cooling infiltration method: Direct Cooling infiltration value: 0.000
Heating ventilation method: Direct Heating ventilation value: 500.000
Heating infiltration method: Direct Heating infiltration value: 0.000
Winter exhaust air CFM: 500 Summer exhaust air CFM: 500
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 0 Exposed floor slab perimeter (ft): 0
Both heating and cooling loads are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 1 6 0.080 Yes 12.00 10.00 120.0 No

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 B 0.144 D 15.00 10.00 150.0 S

Zone 2: HVAC MECH RM (544.5 sq.ft) (Group 1)


Air Handler number: 1 Zone occurrences: 1
Zone length: (feet) 33.00 Zone width (feet): 16.50
Lighting Watts: 1,361 Equipment Watts: 1,200
Number of people in zone: 1 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 15.00 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 250
Cooling ventilation method: Direct Cooling ventilation value: 100.000
Cooling infiltration method: Direct Cooling infiltration value: 0.000
Heating ventilation method: Direct Heating ventilation value: 100.000
Heating infiltration method: Direct Heating infiltration value: 0.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 0 Exposed floor slab perimeter (ft): 0
Both heating and cooling loads are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 1 6 0.080 Yes 33.00 16.00 528.0 No

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 B 0.144 D 15.00 33.00 495.0 W
2 1 B 0.144 D 15.00 16.50 247.5 N
3 1 B 0.144 D 15.00 16.50 247.5 S

Design Outdoor Outdoor Indoor Indoor Grains In/Outdoor


Month Dry Bulb Wet Bulb Rel.Hum Dry Bulb Diff Correction
July 93 86 50% 75 114.08 4
August 86 86 50% 75 125.80 -3
Winter 68 72

C:\ ...\PRELIM CALCS COND-II PIB.CHV Saturday, January 23, 2010, 08:10 AM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
AMCDE PIB BUILDING, JIZAN
Al-Khobar, 31952 Page 6

Zone Input (cont'd)


Zone 2: HVAC MECH RM (544.5 sq.ft) (Group 1)

Zone 3: COMMUNICATION RM (90 sq.ft) (Group 1)


Air Handler number: 1 Zone occurrences: 1
Zone length: (feet) 9.00 Zone width (feet): 10.00
Lighting Watts: 225 Equipment Watts: 1,500
Number of people in zone: 1 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 15.00 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 250
Cooling ventilation method: Direct Cooling ventilation value: 50.000
Cooling infiltration method: Direct Cooling infiltration value: 0.000
Heating ventilation method: Direct Heating ventilation value: 50.000
Heating infiltration method: Direct Heating infiltration value: 0.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 0 Exposed floor slab perimeter (ft): 0
Both heating and cooling loads are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 1 6 0.080 Yes 9.00 10.00 90.0 No

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 B 0.144 D 15.00 9.00 135.0 N

Zone 4: UPS RM (120 sq.ft) (Group 1)


Air Handler number: 1 Zone occurrences: 1
Zone length: (feet) 10.00 Zone width (feet): 12.00
Lighting Watts: 300 Equipment Watts: 2,750
Number of people in zone: 1 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 15.00 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 250
Cooling ventilation method: Direct Cooling ventilation value: 50.000
Cooling infiltration method: Direct Cooling infiltration value: 0.000
Heating ventilation method: Direct Heating ventilation value: 50.000
Heating infiltration method: Direct Heating infiltration value: 0.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 0 Exposed floor slab perimeter (ft): 0
Both heating and cooling loads are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 1 6 0.080 Yes 10.00 12.00 120.0 No

Zone 5: RACK RM (759 sq.ft) (Group 1)


Air Handler number: 1 Zone occurrences: 1
Zone length: (feet) 33.00 Zone width (feet): 23.00
Lighting Watts: 1,898 Equipment Watts: 6,650
Number of people in zone: 3 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 15.00 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10

C:\ ...\PRELIM CALCS COND-II PIB.CHV Saturday, January 23, 2010, 08:10 AM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
AMCDE PIB BUILDING, JIZAN
Al-Khobar, 31952 Page 7

Zone Input (cont'd)


Zone 5: RACK RM (759 sq.ft) (Group 1)
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: Direct Cooling ventilation value: 150.000
Cooling infiltration method: Direct Cooling infiltration value: 0.000
Heating ventilation method: Direct Heating ventilation value: 150.000
Heating infiltration method: Direct Heating infiltration value: 0.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 0 Exposed floor slab perimeter (ft): 0
Both heating and cooling loads are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 1 6 0.080 Yes 33.00 23.00 759.0 No

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 B 0.144 D 15.00 23.00 345.0 N
2 1 B 0.144 D 15.00 23.00 345.0 S

Zone 6: ELECTRICAL RM (660 sq.ft) (Group 1)


Air Handler number: 1 Zone occurrences: 1
Zone length: (feet) 33.00 Zone width (feet): 20.00
Lighting Watts: 1,650 Equipment Watts: 14,350
Number of people in zone: 0 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 15.00 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: Direct Cooling ventilation value: 150.000
Cooling infiltration method: Direct Cooling infiltration value: 0.000
Heating ventilation method: Direct Heating ventilation value: 150.000
Heating infiltration method: Direct Heating infiltration value: 0.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 0 Exposed floor slab perimeter (ft): 0
Both heating and cooling loads are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 1 6 0.080 Yes 33.00 20.00 660.0 No

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 B 0.144 D 15.00 20.00 300.0 N
2 1 B 0.144 D 15.00 33.00 495.0 E
3 1 B 0.144 D 15.00 20.00 300.0 S

Design Outdoor Outdoor Indoor Indoor Grains In/Outdoor


Month Dry Bulb Wet Bulb Rel.Hum Dry Bulb Diff Correction
July 93 86 50% 75 114.08 4
August 86 86 50% 75 125.80 -3
Winter 68 72

C:\ ...\PRELIM CALCS COND-II PIB.CHV Saturday, January 23, 2010, 08:10 AM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
AMCDE PIB BUILDING, JIZAN
Al-Khobar, 31952 Page 8

Building Envelope Report


Envelope Report Using Summer U-Factors
Material Gross Glass Net -U- Area x Average
Types Area Area Area Factor U-Factor U-Factor
Roof 1 2,277.0 0.0 2,277.0 0.080 182.160 0.080
Tot.Roof 2,277.0 0.0 2,277.0 N/A 182.160 0.080
Wall 1 3,060.0 0.0 3,060.0 0.144 440.640 0.144
Tot.Wall 3,060.0 0.0 3,060.0 N/A 440.640 0.144

Totals 5,337.0 622.800 0.117

Wall Wall Glass Wall Net Wall Avg Glass Avg Glass Avg
Direction Area Area Area U-Factor U-Factor Shd.Coef
N 1,027.5 0.0 1,027.5 0.144 0.000 0.000
NE 0.0 0.0 0.0 0.000 0.000 0.000
E 495.0 0.0 495.0 0.144 0.000 0.000
SE 0.0 0.0 0.0 0.000 0.000 0.000
S 1,042.5 0.0 1,042.5 0.144 0.000 0.000
SW 0.0 0.0 0.0 0.000 0.000 0.000
W 495.0 0.0 495.0 0.144 0.000 0.000
NW 0.0 0.0 0.0 0.000 0.000 0.000
Totals 3,060.0 0.0 3,060.0 0.144 0.000 0.000

C:\ ...\PRELIM CALCS COND-II PIB.CHV Saturday, January 23, 2010, 08:10 AM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
AMCDE PIB BUILDING, JIZAN
Al-Khobar, 31952 Page 9

Building Summary Loads


Building peaks in July at 5pm.
Bldg Load Area Sen %Tot Lat Sen Net %Net
Descriptions Quan Loss Loss Gain Gain Gain Gain
Roof 2,277 802 11.35 0 13,537 13,537 5.13
Wall 3,060 1,939 27.47 0 9,689 9,689 3.67
Glass 0 0 0.00 0 0 0 0.00
Floor Slab 0 0 0.00 0 0 0 0.00
Skin Loads 2,740 38.82 0 23,226 23,226 8.80
Lighting 5,734 0 0.00 0 21,521 21,521 8.16
Equipment 28,100 0 0.00 0 105,469 105,469 39.97
People 6 0 0.00 1,485 1,650 3,135 1.19
Partition 0 0 0.00 0 0 0 0.00
Cool. Pret. 0 0 0.00 0 0 0 0.00
Heat. Pret. 0 0 0.00 0 0 0 0.00
Cool. Vent. 1,000 0 0.00 80,155 19,793 99,948 37.88
Heat. Vent. 1,000 4,318 61.18 0 0 0 0.00
Cool. Infil. 0 0 0.00 0 0 0 0.00
Heat. Infil. 0 0 0.00 0 0 0 0.00
Draw-Thru Fan 0 0 0.00 0 6,096 6,096 2.31
Blow-Thru Fan 0 0 0.00 0 0 0 0.00
Reserve Cap. 0 0 0.00 0 4,474 4,474 1.70
Reheat Cap. 0 0 0.00 0 0 0 0.00
Supply Duct 0 0 0.00 0 0 0 0.00
Return Duct 0 0 0.00 0 0 0 0.00
Misc. Supply 0 0 0.00 0 0 0 0.00
Misc. Return 0 0 0.00 0 0 0 0.00
Building Totals 7,059 100.00 81,640 182,228 263,869 100.00

Building Sen %Tot Lat Sen Net %Net


Summary Loss Loss Gain Gain Gain Gain
Ventilation 4,318 61.18 80,155 19,793 99,948 37.88
Infiltration 0 0.00 0 0 0 0.00
Pretreated Air 0 0.00 0 0 0 0.00
Zone Loads 2,740 38.82 1,485 156,340 157,825 59.81
Plenum Loads 0 0.00 0 0 0 0.00
Fan & Duct Loads 0 0.00 0 6,096 6,096 2.31
Building Totals 7,059 100.00 81,640 182,228 263,869 100.00

Check Figures
Total Building Supply Air (based on a 18° TD): 8,272 CFM
Total Building Vent. Air (12.09% of Supply): 1,000 CFM
Total Conditioned Air Space: 2,294 Sq.ft
Supply Air Per Unit Area: 3.6067 CFM/Sq.ft
Area Per Cooling Capacity: 104.3 Sq.ft/Ton
Cooling Capacity Per Area: 0.0096 Tons/Sq.ft
Heating Capacity Per Area: 3.08 Btuh/Sq.ft
Total Heating Required With Outside Air: 7,059 Btuh
Total Cooling Required With Outside Air: 21.99 Tons

C:\ ...\PRELIM CALCS COND-II PIB.CHV Saturday, January 23, 2010, 08:10 AM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
AMCDE PIB BUILDING, JIZAN
Al-Khobar, 31952 Page 10

Air Handler #1 - AHU-1 Or 2 - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
1 BATTERY RM 120 137 8,527 0 Direct Direct
7pm July 0 50 506 500 500 500
1,800 0.42 4.22 500 50 61

2 HVAC MECH RM 545 813 16,492 275 Direct Direct


8pm July 1 297 818 0 100 100
8,168 0.54 1.50 0 297 99

COMMUNICATION
90 117 7,802 275 Direct Direct
3 RM
1 43 463 0 50 50
7pm July
1,350 0.48 5.14 0 43 56

4 UPS RM 120 42 12,474 275 Direct Direct


6pm July 1 15 740 0 50 50
1,800 0.13 6.17 0 15 89

5 RACK RM 759 704 39,939 660 Direct Direct


6pm July 3 257 2,369 0 150 150
11,385 0.34 3.12 0 257 286

6 ELECTRICAL RM 660 926 68,050 0 Direct Direct


7pm July 0 338 3,376 0 150 150
9,900 0.51 5.12 0 338 408
Zone Peak Totals: 2,294 2,740 153,284 1,485
Total Zones: 6 6 1,000 8,273 500 1,000 1,000
Unique Zones: 6 34,403 0.44 3.61 500 1,000 1,000

C:\ ...\PRELIM CALCS COND-II PIB.CHV Saturday, January 23, 2010, 08:10 AM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
AMCDE PIB BUILDING, JIZAN
Al-Khobar, 31952 Page 11

Air Handler #1 - AHU-1 Or 2 - Total Load Summary


Air Handler Description: AHU-1 Or 2 Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 2.40 HP
Fan Input: 65% motor and fan efficiency with 1.2 in. water across the fan
Sensible Heat Ratio: 0.99 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 5pm in July.
Outdoor Conditions: Clg: 92° DB, 86° WB, 181.09 grains, Htg: 68° DB
Indoor Conditions: Clg: 74° DB (avg.), 50% RH, Htg: 72° DB
Because of the diversity in zone, plenum and ventilation loads, the zone sensible peak time in July at 7pm is different from
the total system peak time, hence the air system CFM was computed using a zone sensible load of 153,158.
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 2,740 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 4,318 Btuh 1,000 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 7,059 Btuh
Heating Supply Air: 2,740 / (1.000 X 1.08 X 3) = 1,000 CFM
Winter Vent Outside Air (100.0% of supply) = 1,000 CFM
Zone space sensible gain: 151,866 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 6,096 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 4,474 Btuh
Total sensible gain on supply side of coil: 162,436 Btuh
Cooling Supply Air: 163,727 / (1.000 X 1.1 X 18) = 8,272 CFM
Summer Vent Outside Air (12.1% of supply) = 1,000 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 19,793 Btuh 1,000 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 19,793 Btuh
Total sensible gain on air handling system: 182,228 Btuh
Zone space latent gain: 1,485 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 80,155 Btuh
Total latent gain on air handling system: 81,640 Btuh
Total system sensible and latent gain: 263,869 Btuh

Check Figures
Total Air Handler Supply Air (based on a 18° TD): 8,272 CFM
Total Air Handler Vent. Air (12.09% of Supply): 1,000 CFM
Total Conditioned Air Space: 2,294 Sq.ft
Supply Air Per Unit Area: 3.6067 CFM/Sq.ft
Area Per Cooling Capacity: 104.3 Sq.ft/Ton
Cooling Capacity Per Area: 0.0096 Tons/Sq.ft
Heating Capacity Per Area: 3.08 Btuh/Sq.ft
Total Heating Required With Outside Air: 7,059 Btuh
Total Cooling Required With Outside Air: 21.99 Tons

C:\ ...\PRELIM CALCS COND-II PIB.CHV Saturday, January 23, 2010, 08:10 AM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
AMCDE PIB BUILDING, JIZAN
Al-Khobar, 31952 Page 12

Zone Detailed Loads (At Zone Peak Times)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Zone 1-BATTERY RM peaks (sensible) in July at 7pm, Air Handler 1 (AHU-1 Or 2), Group 1, 12.0 x 10.0,
Construction Type: 22 (Medium)
Roof-1-6-No.Clg-D 120 1.00 69.1 0.080 664 0.320 38
Wall-1-S-B-D 150 1 20.1 0.144 435 0.576 86
Lights-Prof=1 300 1.000 1,024
Equipment-Prof=1 1,650 1.000 5,630 0
Sub-total 7,752 0 125
Safety factors: +10% +10% +10%
--------- --------- ---------
Total w/ safety factors: 8,527 0 137

Zone 2-HVAC MECH RM peaks (sensible) in July at 8pm, Air Handler 1 (AHU-1 Or 2), Group 1, 33.0 x
16.5, Construction Type: 22 (Medium), SIDB: 75°F, WIDB: 72°F
Roof-1-6-No.Clg-D 528 1.00 61.1 0.080 2,582 0.320 169
Wall-1-W-B-D 495 1 28.1 0.144 2,005 0.576 285
Wall-2-N-B-D 248 1 21.6 0.144 771 0.576 143
Wall-3-S-B-D 248 1 18.1 0.144 646 0.576 143
Lights-Prof=1 1,361 1.000 4,645
Equipment-Prof=1 1,200 1.000 4,095 0
People-Prof=1 1.0 1.000 250 250
Sub-total 14,993 250 739
Safety factors: +10% +10% +10%
--------- --------- ---------
Total w/ safety factors: 16,492 275 813

Zone 3-COMMUNICATION RM peaks (sensible) in July at 7pm, Air Handler 1 (AHU-1 Or 2), Group 1, 9.0
x 10.0, Construction Type: 22 (Medium)
Roof-1-6-No.Clg-D 90 1.00 69.1 0.080 498 0.320 29
Wall-1-N-B-D 135 1 23.6 0.144 459 0.576 78
Lights-Prof=1 225 1.000 768
Equipment-Prof=1 1,500 1.000 5,118 0
People-Prof=1 1.0 1.000 250 250
Sub-total 7,093 250 107
Safety factors: +10% +10% +10%
--------- --------- ---------
Total w/ safety factors: 7,802 275 117

Zone 4-UPS RM peaks (sensible) in July at 6pm, Air Handler 1 (AHU-1 Or 2), Group 1, 10.0 x 12.0,
Construction Type: 22 (Medium)
Roof-1-6-No.Clg-D 120 1.00 71.1 0.080 683 0.320 38
Lights-Prof=1 300 1.000 1,024
Equipment-Prof=1 2,750 1.000 9,383 0
People-Prof=1 1.0 1.000 250 250
Sub-total 11,340 250 38
Safety factors: +10% +10% +10%
--------- --------- ---------
Total w/ safety factors: 12,474 275 42

C:\ ...\PRELIM CALCS COND-II PIB.CHV Saturday, January 23, 2010, 08:10 AM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
AMCDE PIB BUILDING, JIZAN
Al-Khobar, 31952 Page 13

Zone Detailed Loads (At Zone Peak Times) (cont'd)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Zone 5-RACK RM peaks (sensible) in July at 6pm, Air Handler 1 (AHU-1 Or 2), Group 1, 33.0 x 23.0,
Construction Type: 22 (Medium)
Roof-1-6-No.Clg-D 759 1.00 71.1 0.080 4,319 0.320 243
Wall-1-N-B-D 345 1 22.6 0.144 1,124 0.576 199
Wall-2-S-B-D 345 1 19.1 0.144 950 0.576 199
Lights-Prof=1 1,898 1.000 6,475
Equipment-Prof=1 6,650 1.000 22,691 0
People-Prof=1 3.0 1.000 750 600
Sub-total 36,308 600 640
Safety factors: +10% +10% +10%
--------- --------- ---------
Total w/ safety factors: 39,939 660 704

Zone 6-ELECTRICAL RM peaks (sensible) in July at 7pm, Air Handler 1 (AHU-1 Or 2), Group 1, 33.0 x
20.0, Construction Type: 1 (Light), SIDB: 75°F, WIDB: 72°F
Roof-1-6-No.Clg-D 660 1.00 66.1 0.080 3,491 0.320 211
Wall-1-N-B-D 300 1 20.6 0.144 891 0.576 173
Wall-2-E-B-D 495 1 30.1 0.144 2,147 0.576 285
Wall-3-S-B-D 300 1 17.1 0.144 740 0.576 173
Lights-Prof=1 1,650 1.000 5,630
Equipment-Prof=1 14,350 1.000 48,964 0
Sub-total 61,864 0 842
Safety factors: +10% +10% +10%
--------- --------- ---------
Total w/ safety factors: 68,050 0 926

C:\ ...\PRELIM CALCS COND-II PIB.CHV Saturday, January 23, 2010, 08:10 AM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
AMCDE PIB BUILDING, JIZAN
Al-Khobar, 31952 Page 14

Air System #1 (AHU-1 Or 2) Psychrometric Analysis


System Load Analysis Latent Grains Sensible Temp CFM
Leaving Coil Condition 62.240 56.000
Draw-Thru Fan 6,096 0.670 308
Misc Load on Supply Side 0 0.000 0
Supply Air Duct 0 0.000 0
Zone Loads 1,485 0.264 153,158 16.838 7,738
Sensible Reserve 4,474 0.492 226
Zone Condition 1,485 62.504 163,727 73.654 8,272
Return Air Duct 0 0.000
Return Air Plenum 0 0.000
Misc Load on Return Side 0 0.000
Vent Air 1,000 CFM 80,155 14.255 19,793 2.176
Blow-Thru Fan 0 0.000
Entering Coil Condition 81,640 76.759 183,520 76.176 8,272

General Psychrometric Equations Used In Analysis:


PR = (Barometric pressure of site / Standard ASHRAE pressure of 29.921)
TSH = PR x 1.10 x CFM x (DB entering - DB leaving)
TLH = PR x 0.68 x CFM x (Grains entering - Grains leaving)
GTH = PR x 4.50 x CFM x (Enthalpy entering - Enthalpy leaving)

TSH = 1.000 x 1.10 x 8,272 x( 76.176 - 56.000 )= 183,519 Btuh


TLH = 1.000 x 0.68 x 8,272 x( 76.759 - 62.240 )= 81,640 Btuh
----------
SUM = 265,160 Btuh
GTH = 1.000 x 4.50 x 8,272 x( 30.290 - 23.097 )= 267,661 Btuh
Total System Load = 263,869 Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM = 267,661 / ( 0.00 x 500 ) = 0.0 GPM
Heating GPM = 7,059 / ( 0.00 x 500 ) = 0.0 GPM
Steam Req. = 7,059 / 0 = 0.0 lb./hr

Entering Cooling Coil Conditions Entering Heating Coil Conditions


Dry bulb temperature: 76.18 Dry bulb temperature: 68.00
Wet bulb temperature: 65.47
Relative humidity: 56.91
Enthalpy: 30.29 Btu/lbm

Leaving Cooling Coil Conditions Leaving Heating Coil Conditions


Dry bulb temperature: 56.00 Dry bulb temperature: 74.54
Wet bulb temperature: 54.86
Relative humidity: 93.26
Enthalpy: 23.10 Btu/lbm

C:\ ...\PRELIM CALCS COND-II PIB.CHV Saturday, January 23, 2010, 08:10 AM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
AMCDE PIB BUILDING, JIZAN
Al-Khobar, 31952 Page 15

Air System #1 (AHU-1 Or 2) Psychrometric Chart


ZC Zone Condition OC Outdoor Condition
LC Leaving Coil Condition EC Entering Coil Condition
SD Supply Duct Temperature Rise RD Return Duct Temperature Rise
DTF Draw Through Fan Sensible Gain BTF Blow Through Fan Sensible Gain
RE Reserve or Reheat Sensible Gain PL Return Air Plenum Sensible Gain
SM Supply Side Miscellaneous Sensible Gain RM Return Side Miscellaneous Gain
PRE Pretreated Air Condition HRV Heat Recovery Ventilator Condition

C:\ ...\PRELIM CALCS COND-II PIB.CHV Saturday, January 23, 2010, 08:10 AM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
AMCDE PIB BUILDING, JIZAN
Al-Khobar, 31952 Page 16

Building Pie Charts


Building peaks in July at 5pm.

Reserve Cap. - 1.70%


Roof - 5.13% Draw-Thru Fan - 2.31%
Wall - 3.67%

Lighting - 8.16%

Cool. Vent. - 37.88%


Building
Net Gain
263,869
Btuh

Equipment - 39.97%

People - 1.19%

Roof - 11.35%

Building Wall - 27.47%


Loss 7,059
Btuh

Heat. Vent. - 61.18%

C:\ ...\PRELIM CALCS COND-II PIB.CHV Saturday, January 23, 2010, 08:10 AM
PIB BUILDING, JIZAN
HVAC Load Analysis
for

PIB BUILDING, JIZAN (CONDITION-1)


BULK PLANT, JIZAN
S'ARAMCO

Prepared By:

Arif
AMCDE
P. B. # 2502
AL-KHOBAR-31952
03-858-8877 Extn. 231
Saturday, January 23, 2010
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
AMCDE PIB BUILDING, JIZAN
Al-Khobar, 31952 Page 2

General Project Data Input


General Project Information
Project file name: C:\OLD COMPUTER\MYCOMPUTER\NEW
D\ARIF\MYDOCU~1\KBR\PHIL TAYLOR- SUB#2,3&4
PIB
SHELTOR-\PIB\PRELIM CALCS COND-1 PIB.CHV
Project title: PIB BUILDING, JIZAN
Project date: 02 DEC'2009
Project comment: ONDITION-I: Cooling Load is calculated with Summer Design Dry
Bulb and Mean coincident Wet Bulb Temperatures
Weather reference city: JIZAN, SAUDI ARABIA
Client name: PIB BUILDING, JIZAN (CONDITION-1)
Client address: BULK PLANT, JIZAN
Client city: S'ARAMCO
Company name: AMCDE
Company representative: Arif
Company address: P. B. # 2502
Company city: AL-KHOBAR-31952
Company phone: 03-858-8877 Extn. 231
Company fax: 03-858-0061
Company e-mail address: arif@amcde.com
Barometric pressure: 29.910 in.Hg.
Altitude: 10 feet
Latitude: 17 Degrees
Mean daily temperature range: 14 Degrees
Starting & ending time for HVAC load calculations: 1am - 12am
Number of unique zones in this project: 6

Building Default Values


Calculations performed: Both heating and cooling loads
Lighting requirements: 2.50 Watts per square foot
Equipment requirements: 3.00 Watts per square foot
People sensible load multiplier: 250 Btuh per person
People latent load multiplier: 200 Btuh per person
Zone sensible safety factor: 10 %
Zone latent safety factor: 10 %
Zone heating safety factor: 10 %
People diversity factor: 100 %
Lighting profile number: 1
Equipment profile number: 1
People profile number: 1
Building default ceiling height: 0.00 feet
Building default wall height: 17.00 feet

Internal Operating Load Profiles (C = 100)


hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 C C C C C C C C C C C C C C C C C C C C C C C C
2 C C C C C C C C C C C C C C C C C C C C C C C C
3 C C C C C C C C C C C C C C C C C C C C C C C C
4 C C C C C C C C C C C C C C C C C C C C C C C C
5 C C C C C C C C C C C C C C C C C C C C C C C C
6 C C C C C C C C C C C C C C C C C C C C C C C C
7 C C C C C C C C C C C C C C C C C C C C C C C C
8 C C C C C C C C C C C C C C C C C C C C C C C C
9 C C C C C C C C C C C C C C C C C C C C C C C C
10 C C C C C C C C C C C C C C C C C C C C C C C C

C:\ ...\PRELIM CALCS COND-1 PIB.CHV Saturday, January 23, 2010, 08:13 AM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
AMCDE PIB BUILDING, JIZAN
Al-Khobar, 31952 Page 3

General Project Data Input (cont'd)


Building-Level Design Conditions

Design Outdoor Outdoor Indoor Indoor Grains In/Outdoor


Month Dry Bulb Wet Bulb Rel.Hum Dry Bulb Diff Correction
July 99 82 50% 72 80.06 13
August 99 82 50% 72 80.06 13
Winter 68 72

Master Roofs
Roof ASHRAE Roof Dark Susp.
No. Roof# U-Fac Color Ceil
1 6 0.080 Yes No
Roof #1 Description: Flat roof, 6" lightweight concrete deck with 2" insulation, no ceiling below

Master Walls
Wall ASHRAE Wall Wall
No. Group U-Fac Color
1 B 0.144 D
Wall #1 Description: Block wall, 8" sand & gravel, filled core, bare block exterior, interior finish

Master Glass
Glass Summer Winter Glass Interior Interior
No. U-Factor U-Factor Shd.Coef. Shading Shd.Coef
1 0.610 0.760 0.850 2 0.640

C:\ ...\PRELIM CALCS COND-1 PIB.CHV Saturday, January 23, 2010, 08:13 AM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
AMCDE PIB BUILDING, JIZAN
Al-Khobar, 31952 Page 4

Air Handler Input


Air Handler Number 1 Input Data
Name: AHU-1 Or 2
Terminal type: Constant Volume
Method for CV Sum of Peaks
Supply fan type: Draw-thru fan
Calculations performed: Both heating and cooling loads
Excess supply air: Reserve
Occurrences: 1
People profile number: 1
Lighting profile number: 1
Equipment profile number: 1
Exhaust may not exceed supply air: No
Leaving heating coil temp (deg.F): 110.0
Leaving cooling coil temp (deg.F): 56.0
Cooling coil CFM 0
Misc. Btuh gain - supply side: 0
Misc. Btuh gain - return side: 0
Combined fan & motor efficiency: 65
Static pressure across fan (in.wg.): 1.20
Summer supply duct temp rise (deg.F): 0.000
Summer return duct temp rise (deg.F): 0.000
Winter supply duct temp drop (deg.F): 0.000
Winter return duct temp drop (deg.F): 0.000
Chilled water temp difference (deg.F): 0.000
Hot water temp difference (deg.F): 0.000
Cooling ventilation: 1000 Direct
Cooling infiltration: 0 Direct
Heating ventilation: 1000 Direct
Heating infiltration: 0 Direct
Pretreated outside air: none
Pretreated air Summer DB (deg.F): 0
Pretreated air Summer WB (deg.F): 0
Pretreated air Winter DB (deg.F): 0

Design Outdoor Outdoor Indoor Indoor Grains In/Outdoor


Month Dry Bulb Wet Bulb Rel.Hum Dry Bulb Diff Correction
July 99 82 50% 74 76.65 13
August 99 82 50% 74 76.65 13
Winter 68 72

C:\ ...\PRELIM CALCS COND-1 PIB.CHV Saturday, January 23, 2010, 08:13 AM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
AMCDE PIB BUILDING, JIZAN
Al-Khobar, 31952 Page 5

Zone Input
Zone 1: BATTERY RM (120 sq.ft) (Group 1)
Air Handler number: 1 Zone occurrences: 1
Zone length: (feet) 12.00 Zone width (feet): 10.00
Lighting Watts: 300 Equipment Watts: 1,650
Number of people in zone: 0 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 15.00 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: Direct Cooling ventilation value: 500.000
Cooling infiltration method: Direct Cooling infiltration value: 0.000
Heating ventilation method: Direct Heating ventilation value: 500.000
Heating infiltration method: Direct Heating infiltration value: 0.000
Winter exhaust air CFM: 500 Summer exhaust air CFM: 500
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 0 Exposed floor slab perimeter (ft): 0
Both heating and cooling loads are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 1 6 0.080 Yes 12.00 10.00 120.0 No

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 B 0.144 D 15.00 10.00 150.0 S

Zone 2: HVAC MECH RM (544.5 sq.ft) (Group 1)


Air Handler number: 1 Zone occurrences: 1
Zone length: (feet) 33.00 Zone width (feet): 16.50
Lighting Watts: 1,361 Equipment Watts: 1,200
Number of people in zone: 1 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 15.00 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 250
Cooling ventilation method: Direct Cooling ventilation value: 100.000
Cooling infiltration method: Direct Cooling infiltration value: 0.000
Heating ventilation method: Direct Heating ventilation value: 100.000
Heating infiltration method: Direct Heating infiltration value: 0.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 0 Exposed floor slab perimeter (ft): 0
Both heating and cooling loads are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 1 6 0.080 Yes 33.00 16.00 528.0 No

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 B 0.144 D 15.00 33.00 495.0 W
2 1 B 0.144 D 15.00 16.50 247.5 N
3 1 B 0.144 D 15.00 16.50 247.5 S

Design Outdoor Outdoor Indoor Indoor Grains In/Outdoor


Month Dry Bulb Wet Bulb Rel.Hum Dry Bulb Diff Correction
July 99 82 50% 75 73.77 10
August 99 82 50% 75 73.77 10
Winter 68 72

C:\ ...\PRELIM CALCS COND-1 PIB.CHV Saturday, January 23, 2010, 08:13 AM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
AMCDE PIB BUILDING, JIZAN
Al-Khobar, 31952 Page 6

Zone Input (cont'd)


Zone 2: HVAC MECH RM (544.5 sq.ft) (Group 1)

Zone 3: COMMUNICATION RM (90 sq.ft) (Group 1)


Air Handler number: 1 Zone occurrences: 1
Zone length: (feet) 9.00 Zone width (feet): 10.00
Lighting Watts: 225 Equipment Watts: 1,500
Number of people in zone: 1 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 15.00 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 250
Cooling ventilation method: Direct Cooling ventilation value: 50.000
Cooling infiltration method: Direct Cooling infiltration value: 0.000
Heating ventilation method: Direct Heating ventilation value: 50.000
Heating infiltration method: Direct Heating infiltration value: 0.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 0 Exposed floor slab perimeter (ft): 0
Both heating and cooling loads are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 1 6 0.080 Yes 9.00 10.00 90.0 No

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 B 0.144 D 15.00 9.00 135.0 N

Zone 4: UPS RM (120 sq.ft) (Group 1)


Air Handler number: 1 Zone occurrences: 1
Zone length: (feet) 10.00 Zone width (feet): 12.00
Lighting Watts: 300 Equipment Watts: 2,750
Number of people in zone: 1 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 15.00 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 250
Cooling ventilation method: Direct Cooling ventilation value: 50.000
Cooling infiltration method: Direct Cooling infiltration value: 0.000
Heating ventilation method: Direct Heating ventilation value: 50.000
Heating infiltration method: Direct Heating infiltration value: 0.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 0 Exposed floor slab perimeter (ft): 0
Both heating and cooling loads are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 1 6 0.080 Yes 10.00 12.00 120.0 No

Zone 5: RACK RM (759 sq.ft) (Group 1)


Air Handler number: 1 Zone occurrences: 1
Zone length: (feet) 33.00 Zone width (feet): 23.00
Lighting Watts: 1,898 Equipment Watts: 6,650
Number of people in zone: 3 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 15.00 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10

C:\ ...\PRELIM CALCS COND-1 PIB.CHV Saturday, January 23, 2010, 08:13 AM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
AMCDE PIB BUILDING, JIZAN
Al-Khobar, 31952 Page 7

Zone Input (cont'd)


Zone 5: RACK RM (759 sq.ft) (Group 1)
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: Direct Cooling ventilation value: 150.000
Cooling infiltration method: Direct Cooling infiltration value: 0.000
Heating ventilation method: Direct Heating ventilation value: 150.000
Heating infiltration method: Direct Heating infiltration value: 0.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 0 Exposed floor slab perimeter (ft): 0
Both heating and cooling loads are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 1 6 0.080 Yes 33.00 23.00 759.0 No

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 B 0.144 D 15.00 23.00 345.0 N
2 1 B 0.144 D 15.00 23.00 345.0 S

Zone 6: ELECTRICAL RM (660 sq.ft) (Group 1)


Air Handler number: 1 Zone occurrences: 1
Zone length: (feet) 33.00 Zone width (feet): 20.00
Lighting Watts: 1,650 Equipment Watts: 14,350
Number of people in zone: 0 People profile number: 1
Lighting profile number: 1 Equipment profile number: 1
Ceiling height (feet): 15.00 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 250 Latent heat per person (Btuh): 200
Cooling ventilation method: Direct Cooling ventilation value: 150.000
Cooling infiltration method: Direct Cooling infiltration value: 0.000
Heating ventilation method: Direct Heating ventilation value: 150.000
Heating infiltration method: Direct Heating infiltration value: 0.000
Winter exhaust air CFM: 0 Summer exhaust air CFM: 0
Minimum supply CFM: 0 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 0 Exposed floor slab perimeter (ft): 0
Both heating and cooling loads are calculated for this zone.

Roof Type ASHRAE# U-Factor Dark Length Width Area Susp.Ceil


1 1 6 0.080 Yes 33.00 20.00 660.0 No

Wall Type ASHRAE# U-Factor Color Height Width Area Direction


1 1 B 0.144 D 15.00 20.00 300.0 N
2 1 B 0.144 D 15.00 33.00 495.0 E
3 1 B 0.144 D 15.00 20.00 300.0 S

Design Outdoor Outdoor Indoor Indoor Grains In/Outdoor


Month Dry Bulb Wet Bulb Rel.Hum Dry Bulb Diff Correction
July 99 82 50% 75 73.77 10
August 99 82 50% 75 73.77 10
Winter 68 72

C:\ ...\PRELIM CALCS COND-1 PIB.CHV Saturday, January 23, 2010, 08:13 AM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
AMCDE PIB BUILDING, JIZAN
Al-Khobar, 31952 Page 8

Building Envelope Report


Envelope Report Using Summer U-Factors
Material Gross Glass Net -U- Area x Average
Types Area Area Area Factor U-Factor U-Factor
Roof 1 2,277.0 0.0 2,277.0 0.080 182.160 0.080
Tot.Roof 2,277.0 0.0 2,277.0 N/A 182.160 0.080
Wall 1 3,060.0 0.0 3,060.0 0.144 440.640 0.144
Tot.Wall 3,060.0 0.0 3,060.0 N/A 440.640 0.144

Totals 5,337.0 622.800 0.117

Wall Wall Glass Wall Net Wall Avg Glass Avg Glass Avg
Direction Area Area Area U-Factor U-Factor Shd.Coef
N 1,027.5 0.0 1,027.5 0.144 0.000 0.000
NE 0.0 0.0 0.0 0.000 0.000 0.000
E 495.0 0.0 495.0 0.144 0.000 0.000
SE 0.0 0.0 0.0 0.000 0.000 0.000
S 1,042.5 0.0 1,042.5 0.144 0.000 0.000
SW 0.0 0.0 0.0 0.000 0.000 0.000
W 495.0 0.0 495.0 0.144 0.000 0.000
NW 0.0 0.0 0.0 0.000 0.000 0.000
Totals 3,060.0 0.0 3,060.0 0.144 0.000 0.000

C:\ ...\PRELIM CALCS COND-1 PIB.CHV Saturday, January 23, 2010, 08:13 AM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
AMCDE PIB BUILDING, JIZAN
Al-Khobar, 31952 Page 9

Building Summary Loads


Building peaks in July at 5pm.
Bldg Load Area Sen %Tot Lat Sen Net %Net
Descriptions Quan Loss Loss Gain Gain Gain Gain
Roof 2,277 802 11.35 0 14,740 14,740 5.96
Wall 3,060 1,939 27.47 0 12,597 12,597 5.09
Glass 0 0 0.00 0 0 0 0.00
Floor Slab 0 0 0.00 0 0 0 0.00
Skin Loads 2,740 38.82 0 27,337 27,337 11.05
Lighting 5,734 0 0.00 0 21,521 21,521 8.70
Equipment 28,100 0 0.00 0 105,469 105,469 42.63
People 6 0 0.00 1,485 1,650 3,135 1.27
Partition 0 0 0.00 0 0 0 0.00
Cool. Pret. 0 0 0.00 0 0 0 0.00
Heat. Pret. 0 0 0.00 0 0 0 0.00
Cool. Vent. 1,000 0 0.00 52,742 26,390 79,132 31.98
Heat. Vent. 1,000 4,318 61.18 0 0 0 0.00
Cool. Infil. 0 0 0.00 0 0 0 0.00
Heat. Infil. 0 0 0.00 0 0 0 0.00
Draw-Thru Fan 0 0 0.00 0 6,258 6,258 2.53
Blow-Thru Fan 0 0 0.00 0 0 0 0.00
Reserve Cap. 0 0 0.00 0 4,559 4,559 1.84
Reheat Cap. 0 0 0.00 0 0 0 0.00
Supply Duct 0 0 0.00 0 0 0 0.00
Return Duct 0 0 0.00 0 0 0 0.00
Misc. Supply 0 0 0.00 0 0 0 0.00
Misc. Return 0 0 0.00 0 0 0 0.00
Building Totals 7,059 100.00 54,227 193,184 247,411 100.00

Building Sen %Tot Lat Sen Net %Net


Summary Loss Loss Gain Gain Gain Gain
Ventilation 4,318 61.18 52,742 26,390 79,132 31.98
Infiltration 0 0.00 0 0 0 0.00
Pretreated Air 0 0.00 0 0 0 0.00
Zone Loads 2,740 38.82 1,485 160,536 162,021 65.49
Plenum Loads 0 0.00 0 0 0 0.00
Fan & Duct Loads 0 0.00 0 6,258 6,258 2.53
Building Totals 7,059 100.00 54,227 193,184 247,411 100.00

Check Figures
Total Building Supply Air (based on a 18° TD): 8,492 CFM
Total Building Vent. Air (11.78% of Supply): 1,000 CFM
Total Conditioned Air Space: 2,294 Sq.ft
Supply Air Per Unit Area: 3.7027 CFM/Sq.ft
Area Per Cooling Capacity: 111.2 Sq.ft/Ton
Cooling Capacity Per Area: 0.0090 Tons/Sq.ft
Heating Capacity Per Area: 3.08 Btuh/Sq.ft
Total Heating Required With Outside Air: 7,059 Btuh
Total Cooling Required With Outside Air: 20.62 Tons

C:\ ...\PRELIM CALCS COND-1 PIB.CHV Saturday, January 23, 2010, 08:13 AM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
AMCDE PIB BUILDING, JIZAN
Al-Khobar, 31952 Page 10

Air Handler #1 - AHU-1 Or 2 - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
1 BATTERY RM 120 137 8,761 0 Direct Direct
7pm August 0 50 520 500 500 500
1,800 0.42 4.33 500 50 61

2 HVAC MECH RM 545 813 17,712 275 Direct Direct


8pm July 1 297 879 0 100 100
8,168 0.54 1.61 0 297 103

COMMUNICATION
90 117 7,978 275 Direct Direct
3 RM
1 43 473 0 50 50
7pm July
1,350 0.48 5.26 0 43 56

4 UPS RM 120 42 12,537 275 Direct Direct


6pm July 1 15 744 0 50 50
1,800 0.13 6.20 0 15 88

5 RACK RM 759 704 40,995 660 Direct Direct


6pm July 3 257 2,432 0 150 150
11,385 0.34 3.20 0 257 286

6 ELECTRICAL RM 660 926 69,439 0 Direct Direct


7pm July 0 338 3,445 0 150 150
9,900 0.51 5.22 0 338 406
Zone Peak Totals: 2,294 2,740 157,423 1,485
Total Zones: 6 6 1,000 8,493 500 1,000 1,000
Unique Zones: 6 34,403 0.44 3.70 500 1,000 1,000

C:\ ...\PRELIM CALCS COND-1 PIB.CHV Saturday, January 23, 2010, 08:13 AM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
AMCDE PIB BUILDING, JIZAN
Al-Khobar, 31952 Page 11

Air Handler #1 - AHU-1 Or 2 - Total Load Summary


Air Handler Description: AHU-1 Or 2 Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 2.47 HP
Fan Input: 65% motor and fan efficiency with 1.2 in. water across the fan
Sensible Heat Ratio: 0.99 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 5pm in July.
Outdoor Conditions: Clg: 98° DB, 82° WB, 140.75 grains, Htg: 68° DB
Indoor Conditions: Clg: 74° DB (avg.), 50% RH, Htg: 72° DB
Because of the diversity in zone, plenum and ventilation loads, the zone sensible peak time in July at 7pm is different from
the total system peak time, hence the air system CFM was computed using a zone sensible load of 157,268.
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 2,740 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 4,318 Btuh 1,000 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 7,059 Btuh
Heating Supply Air: 2,740 / (1.000 X 1.08 X 3) = 1,000 CFM
Winter Vent Outside Air (100.0% of supply) = 1,000 CFM
Zone space sensible gain: 155,977 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 6,258 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 4,559 Btuh
Total sensible gain on supply side of coil: 166,794 Btuh
Cooling Supply Air: 168,085 / (1.000 X 1.1 X 18) = 8,492 CFM
Summer Vent Outside Air (11.8% of supply) = 1,000 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 26,390 Btuh 1,000 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 26,390 Btuh
Total sensible gain on air handling system: 193,184 Btuh
Zone space latent gain: 1,485 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 52,742 Btuh
Total latent gain on air handling system: 54,227 Btuh
Total system sensible and latent gain: 247,411 Btuh

Check Figures
Total Air Handler Supply Air (based on a 18° TD): 8,492 CFM
Total Air Handler Vent. Air (11.78% of Supply): 1,000 CFM
Total Conditioned Air Space: 2,294 Sq.ft
Supply Air Per Unit Area: 3.7027 CFM/Sq.ft
Area Per Cooling Capacity: 111.2 Sq.ft/Ton
Cooling Capacity Per Area: 0.0090 Tons/Sq.ft
Heating Capacity Per Area: 3.08 Btuh/Sq.ft
Total Heating Required With Outside Air: 7,059 Btuh
Total Cooling Required With Outside Air: 20.62 Tons

C:\ ...\PRELIM CALCS COND-1 PIB.CHV Saturday, January 23, 2010, 08:13 AM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
AMCDE PIB BUILDING, JIZAN
Al-Khobar, 31952 Page 12

Zone Detailed Loads (At Zone Peak Times)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Zone 1-BATTERY RM peaks (sensible) in August at 7pm, Air Handler 1 (AHU-1 Or 2), Group 1, 12.0 x
10.0, Construction Type: 22 (Medium)
Roof-1-6-No.Clg-D 120 1.00 75.0 0.080 720 0.320 38
Wall-1-S-B-D 150 1 27.4 0.144 591 0.576 86
Lights-Prof=1 300 1.000 1,024
Equipment-Prof=1 1,650 1.000 5,630 0
Sub-total 7,965 0 125
Safety factors: +10% +10% +10%
--------- --------- ---------
Total w/ safety factors: 8,761 0 137

Zone 2-HVAC MECH RM peaks (sensible) in July at 8pm, Air Handler 1 (AHU-1 Or 2), Group 1, 33.0 x
16.5, Construction Type: 22 (Medium), SIDB: 75°F, WIDB: 72°F
Roof-1-6-No.Clg-D 528 1.00 67.1 0.080 2,835 0.320 169
Wall-1-W-B-D 495 1 34.1 0.144 2,432 0.576 285
Wall-2-N-B-D 248 1 27.6 0.144 985 0.576 143
Wall-3-S-B-D 248 1 24.1 0.144 860 0.576 143
Lights-Prof=1 1,361 1.000 4,645
Equipment-Prof=1 1,200 1.000 4,095 0
People-Prof=1 1.0 1.000 250 250
Sub-total 16,102 250 739
Safety factors: +10% +10% +10%
--------- --------- ---------
Total w/ safety factors: 17,712 275 813

Zone 3-COMMUNICATION RM peaks (sensible) in July at 7pm, Air Handler 1 (AHU-1 Or 2), Group 1, 9.0
x 10.0, Construction Type: 22 (Medium)
Roof-1-6-No.Clg-D 90 1.00 75.1 0.080 541 0.320 29
Wall-1-N-B-D 135 1 29.6 0.144 576 0.576 78
Lights-Prof=1 225 1.000 768
Equipment-Prof=1 1,500 1.000 5,118 0
People-Prof=1 1.0 1.000 250 250
Sub-total 7,253 250 107
Safety factors: +10% +10% +10%
--------- --------- ---------
Total w/ safety factors: 7,978 275 117

Zone 4-UPS RM peaks (sensible) in July at 6pm, Air Handler 1 (AHU-1 Or 2), Group 1, 10.0 x 12.0,
Construction Type: 22 (Medium)
Roof-1-6-No.Clg-D 120 1.00 77.1 0.080 740 0.320 38
Lights-Prof=1 300 1.000 1,024
Equipment-Prof=1 2,750 1.000 9,383 0
People-Prof=1 1.0 1.000 250 250
Sub-total 11,397 250 38
Safety factors: +10% +10% +10%
--------- --------- ---------
Total w/ safety factors: 12,537 275 42

C:\ ...\PRELIM CALCS COND-1 PIB.CHV Saturday, January 23, 2010, 08:13 AM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
AMCDE PIB BUILDING, JIZAN
Al-Khobar, 31952 Page 13

Zone Detailed Loads (At Zone Peak Times) (cont'd)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Zone 5-RACK RM peaks (sensible) in July at 6pm, Air Handler 1 (AHU-1 Or 2), Group 1, 33.0 x 23.0,
Construction Type: 22 (Medium)
Roof-1-6-No.Clg-D 759 1.00 77.1 0.080 4,683 0.320 243
Wall-1-N-B-D 345 1 28.6 0.144 1,422 0.576 199
Wall-2-S-B-D 345 1 25.1 0.144 1,248 0.576 199
Lights-Prof=1 1,898 1.000 6,475
Equipment-Prof=1 6,650 1.000 22,691 0
People-Prof=1 3.0 1.000 750 600
Sub-total 37,269 600 640
Safety factors: +10% +10% +10%
--------- --------- ---------
Total w/ safety factors: 40,995 660 704

Zone 6-ELECTRICAL RM peaks (sensible) in July at 7pm, Air Handler 1 (AHU-1 Or 2), Group 1, 33.0 x
20.0, Construction Type: 1 (Light), SIDB: 75°F, WIDB: 72°F
Roof-1-6-No.Clg-D 660 1.00 72.1 0.080 3,808 0.320 211
Wall-1-N-B-D 300 1 26.6 0.144 1,150 0.576 173
Wall-2-E-B-D 495 1 36.1 0.144 2,575 0.576 285
Wall-3-S-B-D 300 1 23.1 0.144 999 0.576 173
Lights-Prof=1 1,650 1.000 5,630
Equipment-Prof=1 14,350 1.000 48,964 0
Sub-total 63,127 0 842
Safety factors: +10% +10% +10%
--------- --------- ---------
Total w/ safety factors: 69,439 0 926

C:\ ...\PRELIM CALCS COND-1 PIB.CHV Saturday, January 23, 2010, 08:13 AM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
AMCDE PIB BUILDING, JIZAN
Al-Khobar, 31952 Page 14

Air System #1 (AHU-1 Or 2) Psychrometric Analysis


System Load Analysis Latent Grains Sensible Temp CFM
Leaving Coil Condition 62.247 56.000
Draw-Thru Fan 6,258 0.670 316
Misc Load on Supply Side 0 0.000 0
Supply Air Duct 0 0.000 0
Zone Loads 1,485 0.257 157,268 16.842 7,946
Sensible Reserve 4,559 0.488 230
Zone Condition 1,485 62.504 168,085 73.661 8,492
Return Air Duct 0 0.000
Return Air Plenum 0 0.000
Misc Load on Return Side 0 0.000
Vent Air 1,000 CFM 52,742 9.137 26,390 2.826
Blow-Thru Fan 0 0.000
Entering Coil Condition 54,227 71.641 194,476 76.826 8,492

General Psychrometric Equations Used In Analysis:


PR = (Barometric pressure of site / Standard ASHRAE pressure of 29.921)
TSH = PR x 1.10 x CFM x (DB entering - DB leaving)
TLH = PR x 0.68 x CFM x (Grains entering - Grains leaving)
GTH = PR x 4.50 x CFM x (Enthalpy entering - Enthalpy leaving)

TSH = 1.000 x 1.10 x 8,492 x( 76.826 - 56.000 )= 194,475 Btuh


TLH = 1.000 x 0.68 x 8,492 x( 71.641 - 62.247 )= 54,227 Btuh
----------
SUM = 248,702 Btuh
GTH = 1.000 x 4.50 x 8,492 x( 29.648 - 23.098 )= 250,231 Btuh
Total System Load = 247,411 Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM = 250,231 / ( 0.00 x 500 ) = 0.0 GPM
Heating GPM = 7,059 / ( 0.00 x 500 ) = 0.0 GPM
Steam Req. = 7,059 / 0 = 0.0 lb./hr

Entering Cooling Coil Conditions Entering Heating Coil Conditions


Dry bulb temperature: 76.83 Dry bulb temperature: 68.00
Wet bulb temperature: 64.64
Relative humidity: 52.05
Enthalpy: 29.65 Btu/lbm

Leaving Cooling Coil Conditions Leaving Heating Coil Conditions


Dry bulb temperature: 56.00 Dry bulb temperature: 74.54
Wet bulb temperature: 54.87
Relative humidity: 93.29
Enthalpy: 23.10 Btu/lbm

C:\ ...\PRELIM CALCS COND-1 PIB.CHV Saturday, January 23, 2010, 08:13 AM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
AMCDE PIB BUILDING, JIZAN
Al-Khobar, 31952 Page 15

Air System #1 (AHU-1 Or 2) Psychrometric Chart


ZC Zone Condition OC Outdoor Condition
LC Leaving Coil Condition EC Entering Coil Condition
SD Supply Duct Temperature Rise RD Return Duct Temperature Rise
DTF Draw Through Fan Sensible Gain BTF Blow Through Fan Sensible Gain
RE Reserve or Reheat Sensible Gain PL Return Air Plenum Sensible Gain
SM Supply Side Miscellaneous Sensible Gain RM Return Side Miscellaneous Gain
PRE Pretreated Air Condition HRV Heat Recovery Ventilator Condition

C:\ ...\PRELIM CALCS COND-1 PIB.CHV Saturday, January 23, 2010, 08:13 AM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
AMCDE PIB BUILDING, JIZAN
Al-Khobar, 31952 Page 16

Building Pie Charts


Building peaks in July at 5pm.

Reserve Cap. - 1.84%


Roof - 5.96% Draw-Thru Fan - 2.53%
Wall - 5.09%

Lighting - 8.70%

Cool. Vent. - 31.98%

Building
Net Gain
247,411
Btuh

People - 1.27%
Equipment - 42.63%

Roof - 11.35%

Building Wall - 27.47%


Loss 7,059
Btuh

Heat. Vent. - 61.18%

C:\ ...\PRELIM CALCS COND-1 PIB.CHV Saturday, January 23, 2010, 08:13 AM