You are on page 1of 59

WATER-COOLED SCREW CHILLER

60Hz/R134a 60~400RT 6CHW3-01B(Replaces 6CHW3-01A)

WATER-COOLED SCREW CHILLER


60Hz/R134a 60~400RT 6CHW3-01B(Replaces 6CHW3-01A)

WATER-COOLED SCREW CHILLER


Water-Cooled Screw Chiller
60~400RT
1. Model Line Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 2. Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 3. Construction Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 4. Features & Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 5. Options & Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 6. Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 7. ARI Capacity Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 8. Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 9. Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 10. Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 11. Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 12. Pressure Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 13. Piping Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 14. Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 15. Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 16. Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 17. Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

Water-Cooled Screw

1. Model Line Up
Nominal size 60 70 80 90 100 110 120 140 150 180 200 220 260 300 340 400 1 Compressor Type RCWW0609AAA RCWW0709AAA RCWW0809AAA RCWW0909AAA RCWW1009AAA RCWW1109AAB RCWW1209AAB RCWW1409AAB RCWW1509AAB RCWW1809AAB RCWW2009AAB RCWW2209AAB RCWW2609AAB RCWW3009AAB RCWW3409AAB RCWW4009AAB 2 Compressors Type

These models are standard model line-up. If you want to order special model which is outside of standard line-up, contact LGE.

CHILLER 60Hz/R134a _ 1

Water-Cooled Screw

2. Nomenclature
Identification Rule
R C W W 200 9 A A A
Development sequence A: 1 Compressor B: 2 Compressors Ice storage / BMS type A : General / Modbus Port B : General / BACnet Port C : General / LonWork Port D : Ice Storage / Modbus Port E : Ice Storage / BACnet Port F : Ice Storage / LonWork Port

Model Type A : High Efficiency Model B : Compact Model

Unit Voltage (V / Hz / ) 1 : 115 / 60 / 1 2 : 220 / 60 / 1 5 : 200-220 / 50 / 1 6 : 220-240 / 50 / 1 9 : 380 / 60 / 3 A : 220 / 50 / 3 B : 220 / 60 / 3 D : 440-460 / 60 / 3 E : 265 / 60 / 1 G : 220-240 / 50, 60 / 1 L : 380-415 / 50, 60 / 3 N : 6,600 / 60 / 3 J : 6,000 / 60 / 3 P : 380 / 50 / 3 Q : 400 / 50 / 3 S : 380-400/50/3 T : 440/60/3 Nominal size-Tons Ex) 060-58.0 070-68.3

3 : 208-230 / 60 / 1 7 : 100 / 50, 60 / 1 C : 575 / 60 / 3 F : 200 / 50, 60 / 1 M : 3,300 / 60 / 3 K :10,000 / 60 / 3 R: 415 / 50 / 3

Compressor Type : W = Screw Compressor

Chiller Type : W = Water cooled

Product Type : C = Chiller

Refrigerant type & code : R = R134a

2 _ CHILLER 60Hz/R134a

Water-Cooled Screw

3. Construction Details
HMI Oil separator Compressor Power box Control box

Economizer

Safety valves

Condenser

Drier Evaporator

CHILLER 60Hz/R134a _ 3

Water-Cooled Screw

4. Features & Benefits


High efficiency, High reliability
The RCWW series is a kind of water-cooled spray screw chiller produced by LGE Corporation. Because of the special structure design, the chiller has high efficiency and high reliability.

Compressor
Semi-hermetical twin-rotor screw compressor. Direct-drive, low speed/RPM for high efficiency and high reliability. Only three moving parts, resulting in high reliability with simple solution. Field serviceable compressor and easy maintenance. Precise rotor tip clearance. The worlds advanced patent screw tooth with low noise, smooth operation long life advantages. A refrigerant dispersing cooling device is set internally for compressor cooling, which uses return-refrigerant cooling. Years of research and testing. The LG air cooled screw chiller has amassed thousands of hours of testing, and conditions beyond normal air conditioning applications.

Optimized dedicated motor for R134a with high efficiency


Made of premium grade, low-loss core steel with the special slot design, the motors of R134a dedicated compressors can gain the highest efficiency with low power consumption. Besides, different winding for specific voltage and frequency requirement contributes to the best power factor and excellent performance.

Constructional design of dedicated screw compressor


The screw compressor is characterized by a very compact design. Most of inner dimensions have been totally modified considering displacement volume, size of compression chamber, length & profile of rotors, oil separator specification and oil piping rearrangement, etc. to ensure consistency and cost effectiveness of the compressor.

4 _ CHILLER 60Hz/R134a

Water-Cooled Screw

4. Features & Benefits


Compression Process
As shown in picture below, during rotation of the rotors the meshing shifts from the suction side to the discharge side. The meshing rotors enclose a working space, which is continuously reduced as it moves in the axial direction. This causes a V-shaped lobe space to form between each of the male and female lobes. This lobe space increases to a maximum size (suction and sealing process). As the rotors rotate further, the new meshing on the suction side closes the V-shaped lobe space. The lobe space is then constantly reduced by continuous intermeshing of the lobes (compression process). The reduction in lobe space takes place on the lower side of the rotors towards the discharge side. The volume is steadily reduced and it is thereby compressed in the sealed condition. As soon as the peaks of the rotor teeth are free to the outlet port, the vapor is discharged to the high-pressure side and flows to the oil separator where the high-pressure gas will be separated from the lubrication oil. The size and geometry of the discharge port determine the so called internal volume ratio (Vi) of the compressor. This ratio must have a defined relationship to operate pressure ratio to avoid losses in efficiency due to under or over compression.

Improves evaporating temperature


Spray type evaporator. Increases low-pressure technique High efficiency heat exchange copper pipe.

Improves cooling capacity


Double compression technique. Improves evaporating temperature.

Improves heat exchange effect


Unique condenser design. High efficiency heat exchange tube.

Decreases condensing temperature


Choosing special compressor cylinder volume ratio. Improves heat exchange effect.

Operating conditions range are:


Cooling water inlet : 75F ~ 95F(23.9C ~ 35.0C) Chilled water outlet : 40F ~ 60F(4.4C ~ 15.6C)

CHILLER 60Hz/R134a _ 5

Water-Cooled Screw

4. Features & Benefits


Applications
Standard RS-485, RS-422 industrial interface. Infinity group control unit. Built-in Web functionunits operating state can be observed from the Intel network. Expandable GMS message functionsunit can send phone message to show its operation.

Unit performance testing


LG began promoting factory performance tests for air-cooled chillers and water-cooled chillers, to show we stand behind the products we design and build. The benefits of a performance test include verification of performance, prevention of operational problems, and assurance of a smooth start-up. Only a performance test conducted in a laboratory or laboratory grade facility will confirm both performance and operation of a specific chiller. Mostly factory performance tests go smoothly. If a problem occurs, LG personnel easily correct them and chiller is shipped to job site. When a factory performance test is requested, the test can be conducted at the specified, design conditions. The test facility has the capability to control ambient test conditions to assure our customers that our chillers will perform as predicted.

[Water-cooled run test facility shown with an RCWW 200 ton unit]

6 _ CHILLER 60Hz/R134a

Water-Cooled Screw

4. Features & Benefits


High entering condenser water temperature Option
The High entering condenser water temperature option consists of special control logic to permit High entering condenser water temperature (Up to 95F / 35C) operation.

Wye-delta compressor start type(standard)


For low inrush current and reduced starting torque.

Suction service valves(standard)


Provide a service valve on the suction line of each refrigerant circuit to facilitate compressor servicing.

Flow switch(standard)
Supplied separately to be wired and installed on the evaporator water piping and condenser water piping.

Flooded type evaporator


The flooded type evaporator which have the higher evaporating temperature of refrigerant than direct expansion can increase the performance. The distributor can make the uniform refrigerant flow.

Eco-friendly refrigerant R134a


System designed with Eco-friendly refrigerant R134a which does not harm the ozone layer & protects the environment. The HCFC (R22) series cannot produce any more from 2020 according to the Montreal Protocol for protection of ozone layer.

CHILLER 60Hz/R134a _ 7

Water-Cooled Screw

5. Options & Accessories


Standard accessories
1. Y Delta compressors starter. 2. Flow switch supplied separately to be wired and installed on the evaporator water piping and condensing water piping. 3. Suction line service valve for compressor servicing. 4. Standard MODBUS connectivity for building management system

Option & Accessories


1. Low leaving chilled water temperature. -4F~40F(-20C~4.4C) 2. Spring isolator/Standard Neoprene pad (field installed) 3. Discharge line shut off valves Installed on the discharge port of the compressor. 4. High entering condenser water temperature - Above 95F / 35C. 5. Soft starter. 6. Unit Sound Attenuator. 7. Electric and control accessories as provided in various options. (1) Standard terminal block with dual or single point power connection with no capacitor for power correction or capacitor for power correction. (2) Circuit breakers with dual or single point power connection with no capacitor for power correction or capacitor for power correction.. (3) Unit-mounted non-fused disconnect switch with circuit breaker and dual or single point power connection with no capacitor for power correction or capacitor for power correction. 8. For 2 compressors type model, dual points power connection is standard and single point power connection is optionally provided, see table below. Type Water cooled Hz Type 1 comp. 2 comp. RT all all No. of Comp. 1 2 Standard point single dual terminal 1 2 Option point single terminal 1

60Hz

Note: These options should be attached in factory.

8 _ CHILLER 60Hz/R134a

Water-Cooled Screw

6. Controls
Unit controls of the LGE water cooled screw chiller include following benefits and features.

1. Sequence of controls
When the product starts to run, the condenser water pump and chilled water pump run simultaneously. In the same time, the magnetic valve 1 is turned on for the minimum low capacity operation. Condenser water flow and chilled water flow are also checked a few seconds later after water pump run. In case of having no problem with both water flow, startup delay will be activated. Approximately after one minute delay outlet temperature of chilled water is checked whether the water temperature is reached up enough to operate the compressor. When the PLC decides to operate the compressor, compressor starts with wye start and then delta start after a few seconds. During the starting process of compressor, while the compressor contactor is checking for problem, the solenoid valve for oil is opened in order to achieve proper oil circulation. After starting process, normal control starts. The normal control include capacity control, refrigerant mid pressure control for motor cooling, alarm control. When the chiller is decided to turn off, compressor load of the compressor is changed to minimum load position by changing magnetic valve 1 and turning off magnetic valve 2 and magnetic valve 3. After the delay for shutdown, the compressor is stopped. When the compressor is stopped, the water pumps will still run for a period in order to protect the compressor from frequent restart or withdraw latent heat from evaporator of chiller.

2. Adaptive chiller control and higher level protection.


The latest chiller control technologies provide enhanced operations of the chiller. The chiller control system is based on recent PLC (Programmable Logic Controller) technology. Because the PLC is designed to be compatible with several electromagnetic interference and also compatible with severe ambient conditions, the unit has reliable controllability in any conditions. The adaptive chiller control is designed to operate the unit to withstand severe conditions and maintain its operation. Good examples are capacity override controls in case of high chilled water temperature. Along with the adaptive control, the control also provides higher level protection through multiple protective devices. For example triple protective devices are used for the detection of abnormal oil circulation. The control system continues to monitor the hazardous conditions of the unit, and shutdown the unit to protect the unit safely when any condition meets safety limit.

3. Rich human machine interface


Menu structure of HMI machine is indicated in picture. It consists of 7 menus about User interface. HMI is touch screen, and user can move to the menu which user wants, if user clicks the menu item with his hand. User Setting, Parameter Setting and Function Setting of menu limit is accessed by certification code system.

4. Seamless power supply monitoring


Superior power supply monitoring function of the control system is enabled by protective function against high voltage, low voltage, power loss, phase reverse, and phase imbalance. The superior function of safe power supply to the unit is provided as standard.

5. Standard wye-delta start type and optional soft start type


The wye-delta start provides reduced starting current by 1/3. The LGE chiller is equipped with the wye-delta start of the compressor. Optionally, soft start type shall be provided for soft start of the compressor by linear voltage increase.

CHILLER 60Hz/R134a _ 9

Water-Cooled Screw

6. Controls
6. Standard MODBUS connectivity and optional BACnet and LonWorks connectivity.
The control system of the LGE chiller provides measure to be integrated in modern BMS system seamlessly. Because the control system provides MODBUS connectivity by standard, no additional cost for the BMS integration is needed for the system integration based on the MODBUS. Specially, BACnet or LonWorks can be applied to the system on the request of customer as option.

7. Versatile electric and control options satisfying customers requirements.


Customer can have various option for the electric and control system. For example: (1) Standard terminal block with dual point power connection and no capacitor for power correction. (2) Circuit breakers with single point power connection and capacitor for power correction. (3) Unit-mounted non-fused disconnect switch with circuit breaker and dual point power connection with no capacitor for power correction. These all options are factory installed as per customer requirement. Please refer table below for more options.
Content Option 1 Standard terminal block Option 2 Dual point power connection Single point power connection Circuit breakers Electric and control Dual point power connection Single point power connection Unit-mounted non-fused disconnect switch with circuit breaker Dual point power connection Single point power connection Option 3 No capacitor for power factor correction Capacitor for power factor correction No capacitor for power factor correction Capacitor for power factor correction No capacitor for power factor correction Capacitor for power factor correction No capacitor for power factor correction Capacitor for power factor correction No capacitor for power factor correction Capacitor for power factor correction No capacitor for power factor correction Capacitor for power factor correction

10 _ CHILLER 60Hz/R134a

Water-Cooled Screw

7. ARI capacity ratings


1 Compressor Type Unit (1Comp. Type) RCWW0609AAA RCWW0709AAA RCWW0809AAA RCWW0909AAA RCWW1009AAA Capacity Tons 60.7 71.8 82.2 89.4 98.4 kW 214 252 289 314 346 Input Power kW 42.8 48.7 55.7 60.1 67.5 Full Load COP 5.0 5.2 5.2 5.2 5.1 EER 17.03 17.68 17.70 17.84 17.50 IPLV COP 5.83 6.05 6.06 6.11 5.99 EER 19.89 20.66 20.68 20.85 20.44 Cooler Flow Cooler Pressure Rate Drop l/s 9.2 10.9 12.4 13.5 14.9 gpm kPa 146 172 197 214 236 63 100 116 114 117 Ft wg 21.0 33.4 38.7 38.2 39.0 Condenser Flow Rate l/s 11.5 13.6 15.6 17.0 18.7 183 216 247 269 296 Condenser Pressure Drop 85 18 19 19 19 28.3 6.1 6.4 6.3 6.4

gpm kPa Ft wg

COP-Coefficient of Performance EER-Energy Efficiency Ratio IPLV-Integrated Part Load Value Cooling Conditions : Condenser water inlet temperature is 29.4C(85F), condenser water flow is 0.054 l/s per kW(3.0gpm/ton), chilled water leaving temperature is 6.7C(44F) and chilled water flow is 0.043 l/s per kW(2.4gpm/ton). All data in this table is rated in accordance with ARI Standard 550/590.

CHILLER 60Hz/R134a _ 11

Water-Cooled Screw

7. ARI capacity ratings


2 Compressors Type Unit (2Comp. Type) RCWW1109AAB RCWW1209AAB RCWW1409AAB RCWW1509AAB RCWW1809AAB RCWW2009AAB RCWW2209AAB RCWW2609AAB RCWW3009AAB RCWW3409AAB RCWW4009AAB Capacity Tons 113 122 144 152 179 199 226 268 304 352 407 kW 396 430 508 536 628 698 794 942 1070 1238 1432 Input Power kW 78 86 98 102 120 136 152 180 200 230 266 Full Load COP 5.1 5.0 5.2 5.3 5.2 5.1 5.2 5.2 5.4 5.4 5.4 EER 17.32 17.06 17.69 17.93 17.86 17.51 17.82 17.86 18.25 18.37 18.37 IPLV COP 6.10 6.01 6.23 6.31 6.29 6.16 6.27 6.29 6.43 6.47 6.47 EER 20.81 20.49 21.25 21.54 21.45 21.04 21.41 21.45 21.93 22.06 22.06 Cooler Flow Cooler Pressure Rate Drop l/s 17.0 18.5 21.8 23.0 27.0 30.0 34.1 40.5 46.0 53.2 61.6 gpm kPa 270 293 346 365 428 476 541 642 729 844 976 41 41 40 50 50 50 62 66 112 112 131 Ft wg 13.6 13.6 13.5 16.7 16.8 16.8 20.9 22.0 37.4 37.5 43.7 Condenser Flow Rate l/s 21.4 23.2 27.4 28.9 33.9 37.7 42.9 50.9 57.8 66.9 77.3 339 368 435 459 538 597 680 806 916 1060 1226 Condenser Pressure Drop 28 27 28 34 34 34 41 49 79 79 99 9.3 9.1 9.3 11.4 11.5 11.4 13.6 16.3 26.4 26.5 33.1

gpm kPa Ft wg

COP-Coefficient of Performance EER-Energy Efficiency Ratio IPLV-Integrated Part Load Value Cooling Conditions : Condenser water inlet temperature is 29.4C(85F), condenser water flow is 0.054 l/s per kW(3.0gpm/ton), chilled water leaving temperature is 6.7C(44F) and chilled water flow is 0.043 l/s per kW(2.4gpm/ton). All data in this table is rated in accordance with ARI Standard 550/590.

12 _ CHILLER 60Hz/R134a

Water-Cooled Screw

8. Specifications

English Unit
1 Compressor Type

Unit : RCWW Series (1 Comp. Type) General Unit Data Unit Capacity at ARI Conditions Refrigerant Charge, R134a Oil Charge Shipping Weight Operating Weight Compressors Compressor Type Quantity per Chiller Condenser Maximum Water Side Pressure Maximum Refrigerant Side Pressure Water Connections Minimum Chilled Water Flow Rate Maximum Chilled Water Flow Rate Evaporator, Flooded Maximum Water Side Pressure Maximum Refrigerant Side Pressure Water Connections Minimum Chilled Water Flow Rate Maximum Chilled Water Flow Rate Dimensions Length Width Height

Model Tons lbs gal. lbs lbs

RCWW0609AAA 60.7 154 4.8 5,732 5,997 Semi-Hermetical Twin Screw

RCWW0709AAA RCWW0809AAA 71.8 187 4.8 5,952 6,261 Semi-Hermetical Twin Screw 1 145 232 80 108.0 432.1 145 232 80 86.0 344.1 113.39 38.58 72.83 82.2 209 4.8 6,482 6,834 Semi-Hermetical Twin Screw 1 145 232 100 123.7 494.7 145 232 100 98.5 394.0 120.08 39.37 74.80

RCWW0909AAA 89.4 238 5.3 6,746 7,143 Semi-Hermetical Twin Screw 1 145 232 100 134.5 538.0 145 232 100 107.1 428.4 120.08 39.37 74.80

RCWW1009AAA 98.4 265 5.3 7,231 7,672 Semi-Hermetical Twin Screw 1 145 232 100 148.1 592.5 145 232 100 117.9 471.8 120.08 39.37 78.74

EA psig psig DN gpm gpm psig psig DN gpm gpm inch inch inch

1 145 232 80 91.4 365.7 145 232 80 72.8 291.2 99.61 38.58 72.83

NOTES: 1. Account for unit operating conditions : Evaporator : Leaving water temperature is 44(6.7) Condenser : Entering water temperature is 85(29.4) Evaporator fouling factor 0.0001 ft2hrF/ Btu (0.0186 /kW) Condenser fouli

CHILLER 60Hz/R134a _ 13

Water-Cooled Screw

8. Specifications

SI Unit
1 Compressor Type

Unit : RCWW Series (1 Comp. Type) General Unit Data Unit Capacity at ARI Conditions Refrigerant Charge, R134a Oil Charge Shipping Weight Operating Weight Compressors Compressor Type Quantity per Chiller Condenser Maximum Water Side Pressure Maximum Refrigerant Side Pressure Water Connections Minimum Chilled Water Flow Rate Maximum Chilled Water Flow Rate Evaporator, Flooded Maximum Water Side Pressure Maximum Refrigerant Side Pressure Water Connections Minimum Chilled Water Flow Rate Maximum Chilled Water Flow Rate Dimensions Length Width Height

Model kW kg
l

RCWW0609AAA 214 70 18 2,600 2,720 Semi-Hermetical Twin Screw

RCWW0709AAA 252 85 18 2,700 2,840 Semi-Hermetical Twin Screw 1 1 1.6 80 6.8 27.3 1 1.6 80 5.4 21.7 2,880 980 1,850

RCWW0809AAA 289 95 18 2,940 3,100 Semi-Hermetical Twin Screw 1 1 1.6 100 7.8 31.2 1 1.6 100 6.2 24.9 3,050 1,000 1,900

RCWW0909AAA 314 108 20 3,060 3,240 Semi-Hermetical Twin Screw 1 1 1.6 100 8.5 33.9 1 1.6 100 6.8 27.0 3,050 1,000 1,900

RCWW1009AAA 346 120 20 3,280 3,480 Semi-Hermetical Twin Screw 1 1 1.6 100 9.3 37.4 1 1.6 100 7.4 29.8 3,050 1,000 2,000

kg kg

EA Mpa Mpa DN l/s l/s Mpa Mpa DN l/s l/s mm mm mm

1 1 1.6 80 5.8 23.1 1 1.6 80 4.6 18.4 2,530 980 1,850

NOTES: 1. Account for unit operating conditions : Evaporator : Leaving water temperature is 44(6.7) Condenser : Entering water temperature is 85(29.4) Evaporator fouling factor 0.0001 ft2hrF/ Btu (0.0186 /kW) Condenser fouling factor 0.00025 ft2hrF/ Btu (0.043 /kW) 2. Working voltage : 380V 3Phase 60Hz, 3Phase 5 Wire 3. Evaporator and condenser connection pipe connect with Flange 4. Unit conversion 1kW= 860kcal/h, 1RT = 3.517kW 5. Optional 21 Bar(300 PSIG) Waterside available

14 _ CHILLER 60Hz/R134a

Water-Cooled Screw

8. Specifications

English Unit
2 Compressors Type

Unit : RCWW Series (2 Comp. Type) General Unit Data Unit Capacity at ARI Conditions Refrigerant Charge, R134a Oil Charge Shipping Weight Operating Weight Compressors Compressor Type Quantity per Chiller Condenser Maximum Water Side Pressure Maximum Refrigerant Side Pressure Water Connections Minimum Chilled Water Flow Rate Maximum Chilled Water Flow Rate Evaporator, Flooded Maximum Water Side Pressure Maximum Refrigerant Side Pressure Water Connections Minimum Chilled Water Flow Rate Maximum Chilled Water Flow Rate Dimensions Length Width Height

Model Tons lbs gal. lbs lbs

RCWW1109AAB 112.6 287 6.6 9,612 10,075 Semi-Hermetical Twin Screw

RCWW1209AAB 122.3 320 6.6 10,053 10,582 Semi-Hermetical Twin Screw 2 145 232 100 184.0 736.1 145 232 100 146.5 586.2 135.83 66.14 64.96

RCWW1409AAB 144.5 364 7.9 11,244 11,861 Semi-Hermetical Twin Screw 2 145 232 100 217.4 869.6 145 232 100 173.1 692.5 135.83 66.93 66.14

RCWW1509AAB 152.4 397 7.9 11,508 12,147 Semi-Hermetical Twin Screw 2 145 232 150 229.4 917.6 145 232 150 182.7 730.7 143.70 66.93 66.14

EA psig psig DN gpm gpm psig psig DN gpm gpm inch inch inch

2 145 232 100 169.5 677.9 145 232 100 135.0 539.8 135.83 66.14 62.99

NOTES: 1. Account for unit operating conditions : Evaporator : Leaving water temperature is 44(6.7) Condenser : Entering water temperature is 85(29.4) Evaporator fouling factor 0.0001 ft2hrF/ Btu (0.0186 /kW) Condenser fouling factor 0.00025 ft2hrF/ Btu (0.043 /kW) 2. Working voltage : 380V 3Phase 60Hz, 3Phase 5 Wire 3. Evaporator and condenser connection pipe connect with Flange 4. Unit conversion 1kW= 860kcal/h, 1RT = 3.517kW 5. Optional 21 Bar(300 PSIG) Waterside available

CHILLER 60Hz/R134a _ 15

Water-Cooled Screw

8. Specifications

English Unit
2 Compressors Type

Unit : RCWW Series (2 Comp. Type) General Unit Data Unit Capacity at ARI Conditions Refrigerant Charge, R134a Oil Charge Shipping Weight Operating Weight Compressors Compressor Type Quantity per Chiller Condenser Maximum Water Side Pressure Maximum Refrigerant Side Pressure Water Connections Minimum Chilled Water Flow Rate Maximum Chilled Water Flow Rate Evaporator, Flooded Maximum Water Side Pressure Maximum Refrigerant Side Pressure Water Connections Minimum Chilled Water Flow Rate Maximum Chilled Water Flow Rate Dimensions Length Width Height

Model Tons lbs gal. lbs lbs

RCWW1809AAB 178.6 474 9.2 12,500 13,272 Semi-Hermetical Twin Screw

RCWW2009AAB 198.5 529 10.0 13,558 14,418 Semi-Hermetical Twin Screw 2 145 232 150 298.7 1194.9 145 232 150 237.9 951.5 143.70 72.83 73.23

RCWW2209AAB 225.8 584 10.6 14,088 15,058 Semi-Hermetical Twin Screw 2 145 232 150 339.8 1359.2 145 232 150 270.6 1082.4 153.54 74.02 73.23

RCWW2609AAB 267.9 688 10.6 15,432 16,579 Semi-Hermetical Twin Screw 2 145 232 150 403.1 1612.6 145 232 150 321.0 1284.1 160.63 78.74 74.80

EA psig psig DN gpm gpm psig psig DN gpm gpm inch inch inch

2 145 232 150 268.8 1075.1 145 232 150 214.0 856.1 143.70 70.87 68.90

NOTES: 1. Account for unit operating conditions : Evaporator : Leaving water temperature is 44(6.7) Condenser : Entering water temperature is 85(29.4) Evaporator fouling factor 0.0001 ft2hrF/ Btu (0.0186 /kW) Condenser fouling factor 0.00025 ft2hrF/ Btu (0.043 /kW) 2. Working voltage : 380V 3Phase 60Hz, 3Phase 5 Wire 3. Evaporator and condenser connection pipe connect with Flange 4. Unit conversion 1kW= 860kcal/h, 1RT = 3.517kW 5. Optional 21 Bar(300 PSIG) Waterside available

16 _ CHILLER 60Hz/R134a

Water-Cooled Screw

8. Specifications

English Unit
2 Compressors Type

Unit : RCWW Series (2 Comp. Type) General Unit Data Unit Capacity at ARI Conditions Refrigerant Charge, R134a Oil Charge Shipping Weight Operating Weight Compressors Compressor Type Quantity per Chiller Condenser Maximum Water Side Pressure Maximum Refrigerant Side Pressure Water Connections Minimum Chilled Water Flow Rate Maximum Chilled Water Flow Rate Evaporator, Flooded Maximum Water Side Pressure Maximum Refrigerant Side Pressure Water Connections Minimum Chilled Water Flow Rate Maximum Chilled Water Flow Rate Dimensions Length Width Height

Model Tons lbs gal. lbs lbs

RCWW3009AAB 304.3 794 11.9 16,711 18,012

RCWW3409AAB 352.1 926 13.2 18,166 19,665

RCWW4009AAB 407.2 1,058 14.5 20,613 22,333

Semi-Hermetical Twin Screw EA psig psig DN gpm gpm psig psig DN gpm gpm inch inch inch 2 145 232 200 457.9 1831.7 145 232 200 364.6 1458.6 185.04 81.89 79.53

Semi-Hermetical Twin Screw 2 145 232 200 529.8 2119.3 145 232 200 421.9 1687.6 187.01 86.61 87.40

Semi-Hermetical Twin Screw 2 145 232 200 612.9 2451.4 145 232 200 488.0 1952.1 194.88 87.80 87.40

NOTES: 1. Account for unit operating conditions : Evaporator : Leaving water temperature is 44(6.7) Condenser : Entering water temperature is 85(29.4) Evaporator fouling factor 0.0001 ft2hrF/ Btu (0.0186 /kW) Condenser fouling factor 0.00025 ft2hrF/ Btu (0.043 /kW) 2. Working voltage : 380V 3Phase 60Hz, 3Phase 5 Wire 3. Evaporator and condenser connection pipe connect with Flange 4. Unit conversion 1kW= 860kcal/h, 1RT = 3.517kW 5. Optional 21 Bar(300 PSIG) Waterside available

CHILLER 60Hz/R134a _ 17

Water-Cooled Screw

8. Specifications

SI Unit
2 Compressors Type

Unit : RCWW Series (2 Comp. Type) General Unit Data Unit Capacity at ARI Conditions Refrigerant Charge, R134a Oil Charge Shipping Weight Operating Weight Compressors Compressor Type Quantity per Chiller Condenser Maximum Water Side Pressure Maximum Refrigerant Side Pressure Water Connections Minimum Chilled Water Flow Rate Maximum Chilled Water Flow Rate Evaporator, Flooded Maximum Water Side Pressure Maximum Refrigerant Side Pressure Water Connections Minimum Chilled Water Flow Rate Maximum Chilled Water Flow Rate Dimensions Length Width Height

Model kW kg
l

RCWW1109AAB 396 130 25 4,360 4,570 Semi-Hermetical Twin Screw

RCWW1209AAB 430 145 25 4,560 4,800 Semi-Hermetical Twin Screw 2 1 1.6 100 11.6 46.4 1 1.6 100 9.2 37.0 3,450 1,680 1,650

RCWW1409AAB 508 165 30 5,100 5,380 Semi-Hermetical Twin Screw 2 1 1.6 100 13.7 54.9 1 1.6 100 10.9 43.7 3,450 1,700 1,680

RCWW1509AAB 536 180 30 5,220 5,510 Semi-Hermetical Twin Screw 2 1 1.6 150 14.5 57.9 1 1.6 150 11.5 46.1 3,650 1,700 1,680

kg kg

EA Mpa Mpa DIN l/s l/s Mpa Mpa DIN l/s l/s mm mm mm

2 1 1.6 100 10.7 42.8 1 1.6 100 8.5 34.1 3,450 1,680 1,600

NOTES: 1. Account for unit operating conditions : Evaporator : Leaving water temperature is 44(6.7) Condenser : Entering water temperature is 85(29.4) Evaporator fouling factor 0.0001 ft2hrF/ Btu (0.0186 /kW) Condenser fouling factor 0.00025 ft2hrF/ Btu (0.043 /kW) 2. Working voltage : 380V 3Phase 60Hz, 3Phase 5 Wire 3. Evaporator and condenser connection pipe connect with Flange 4. Unit conversion 1kW= 860kcal/h, 1RT = 3.517kW 5. Optional 21 Bar(300 PSIG) Waterside available

18 _ CHILLER 60Hz/R134a

Water-Cooled Screw

8. Specifications

SI Unit
2 Compressors Type

Unit : RCWW Series (2 Comp. Type) General Unit Data Unit Capacity at ARI Conditions Refrigerant Charge, R134a Oil Charge Shipping Weight Operating Weight Compressors Compressor Type Quantity per Chiller Condenser Maximum Water Side Pressure Maximum Refrigerant Side Pressure Water Connections Minimum Chilled Water Flow Rate Maximum Chilled Water Flow Rate Evaporator, Flooded Maximum Water Side Pressure Maximum Refrigerant Side Pressure Water Connections Minimum Chilled Water Flow Rate Maximum Chilled Water Flow Rate Dimensions Length Width Height

Model kW kg
l

RCWW1809AAB 628 215 35 5,670 6,020 Semi-Hermetical Twin Screw

RCWW2009AAB 698 240 38 6,150 6,540 Semi-Hermetical Twin Screw 2 1 1.6 150 18.8 75.4 1 1.6 150 15.0 60.0 3,650 1,850 1,860

RCWW2209AAB 794 265 40 6,390 6,830 Semi-Hermetical Twin Screw 2 1 1.6 150 21.4 85.8 1 1.6 150 17.1 68.3 3,900 1,880 1,860

RCWW2609AAB 942 312 40 7,000 7,520 Semi-Hermetical Twin Screw 2 1 1.6 150 25.4 101.7 1 1.6 150 20.3 81.0 4,080 2,000 1,900

kg kg

EA Mpa Mpa DIN l/s l/s Mpa Mpa DIN l/s l/s mm mm mm

2 1 1.6 150 17.0 67.8 1 1.6 150 13.5 54.0 3,650 1,800 1,750

NOTES: 1. Account for unit operating conditions : Evaporator : Leaving water temperature is 44(6.7) Condenser : Entering water temperature is 85(29.4) Evaporator fouling factor 0.0001 ft2hrF/ Btu (0.0186 /kW) Condenser fouling factor 0.00025 ft2hrF/ Btu (0.043 /kW) 2. Working voltage : 380V 3Phase 60Hz, 3Phase 5 Wire 3. Evaporator and condenser connection pipe connect with Flange 4. Unit conversion 1kW= 860kcal/h, 1RT = 3.517kW 5. Optional 21 Bar(300 PSIG) Waterside available

CHILLER 60Hz/R134a _ 19

Water-Cooled Screw

8. Specifications

SI Unit
2 Compressors Type

Unit : RCWW Series (2 Comp. Type) General Unit Data Unit Capacity at ARI Conditions Refrigerant Charge, R134a Oil Charge Shipping Weight Operating Weight Compressors Compressor Type Quantity per Chiller Condenser Maximum Water Side Pressure Maximum Refrigerant Side Pressure Water Connections Minimum Chilled Water Flow Rate Maximum Chilled Water Flow Rate Evaporator, Flooded Maximum Water Side Pressure Maximum Refrigerant Side Pressure Water Connections Minimum Chilled Water Flow Rate Maximum Chilled Water Flow Rate Dimensions Length Width Height

Model kW kg
l

RCWW3009AAB 1070 360 45 7,580 8,170

RCWW3409AAB 1238 420 50 8,240 8,920

RCWW4009AAB 1432 480 55 9,350 10,130

kg kg

Semi-Hermetical Twin Screw EA Mpa Mpa DIN l/s l/s Mpa Mpa DIN l/s l/s mm mm mm 2 1 1.6 200 28.9 115.6 1 1.6 200 23.0 92.0 4,700 2,080 2,020

Semi-Hermetical Twin Screw 2 1 1.6 200 33.4 133.7 1 1.6 200 26.6 106.5 4,750 2,200 2,220

Semi-Hermetical Twin Screw 2 1 1.6 200 38.7 154.7 1 1.6 200 30.8 123.2 4,950 2,230 2,220

NOTES: 1. Account for unit operating conditions : Evaporator : Leaving water temperature is 44(6.7) Condenser : Entering water temperature is 85(29.4) Evaporator fouling factor 0.0001 ft2hrF/ Btu (0.0186 /kW) Condenser fouling factor 0.00025 ft2hrF/ Btu (0.043 /kW) 2. Working voltage : 380V 3Phase 60Hz, 3Phase 5 Wire 3. Evaporator and condenser connection pipe connect with Flange 4. Unit conversion 1kW= 860kcal/h, 1RT = 3.517kW 5. Optional 21 Bar(300 PSIG) Waterside available

20 _ CHILLER 60Hz/R134a

Water-Cooled Screw

9. Dimensional Drawings

Unit : RCWW Series 0609AAA 0709AAA 0809AAA 0909AAA 1009AAA inch mm inch mm inch mm inch mm inch mm A(L) 99.61 2,530 113.39 2,880 120.08 3,050 120.08 3,050 120.08 3,050 B(H) 72.83 1,850 72.83 1,850 74.80 1,900 74.80 1,900 78.74 2,000

Outline Dimension C(W) 38.58 980 38.58 980 39.37 1,000 39.37 1,000 39.37 1,000 D 73.15 1,858 88.90 2,258 92.83 2,358 92.83 2,358 92.83 2,358 E 19.09 485 19.09 485 19.09 485 19.09 485 21.06 535

CHILLER 60Hz/R134a _ 21

NOTES: 1. Recommended service clearance around machine is 900 mm(35.4 in). 2. Upper connection pipe of condenser or evaporator is water outlet, lower connection pipe is water inlet pipe. 3. Flow switch is factory installed in outlet of condense and evaporator. 4. Dimensions are in mm(inch).

22 _ CHILLER 60Hz/R134a

Water-Cooled Screw

9. Dimensional Drawings

Unit : RCWW Series

1109AAB

1209AAB

1409AAB

1509AAB

1809AAB

2009AAB

inch mm inch mm inch mm inch mm inch mm inch mm

A(L) 135.83 3,450 135.83 3,450 135.83 3,450 143.7 3,650 143.7 3,650 143.7 3,650

B(H) 62.99 1,600 64.96 1,650 66.14 1,680 66.14 1,680 68.9 1,750 73.23 1,860

Outline Dimension C(W) 66.14 1,680 66.14 1,680 66.93 1,700 66.93 1,700 70.87 1,800 72.83 1,850

D 104.65 2,658 104.65 2,658 104.65 2,658 112.52 2,858 112.52 2,858 112.52 2,858

E 44.09 1,120 45.28 1,150 49.21 1,250 49.21 1,250 53.54 1,360 53.54 1,360

NOTES: 1. Recommended service clearance around machine is 900 mm(35.4 in). 2. Upper connection pipe of condenser or evaporator is water outlet, lower connection pipe is water inlet pipe. 3. Flow switch is factory installed in outlet of condense and evaporator. 4. Dimensions are in mm(inch).

Water-Cooled Screw

9. Dimensional Drawings

Unit : RCWW Series 2209AAB 2609AAB inch mm inch mm A(L) 153.54 3,900 160.63 4,080 B(H) 73.23 1,860 74.80 1,900

Outline Dimension C(W) 74.02 1,880 78.74 2,000 D 120.39 3,058 128.27 3,258 E 57.09 1,450 59.06 1,500

CHILLER 60Hz/R134a _ 23

NOTES: 1. Recommended service clearance around machine is 900 mm(35.4 in). 2. Upper connection pipe of condenser or evaporator is water outlet, lower connection pipe is water inlet pipe. 3. Flow switch is factory installed in outlet of condense and evaporator. 4. Dimensions are in mm(inch).

24 _ CHILLER 60Hz/R134a

Water-Cooled Screw

9. Dimensional Drawings

Unit : RCWW Series

3009AAB

3409AAB

4009AAB

inch mm inch mm inch mm

A(L) 185.04 4,700 187.01 4,750 194.88 4,950

B(H) 79.53 2,020 87.40 2,220 87.40 2,220

Outline Dimension C(W) 81.89 2,080 86.61 2,200 87.80 2,230

D 151.89 3,858 151.73 3,854 159.61 4,054

E 61.02 1,550 66.93 1,700 66.93 1,700

NOTES: 1. Recommended service clearance around machine is 900 mm(35.4 in). 2. Upper connection pipe of condenser or evaporator is water outlet, lower connection pipe is water inlet pipe. 3. Flow switch is factory installed in outlet of condense and evaporator. 4. Dimensions are in mm(inch).

Water-Cooled Screw

10. Selection Procedure


LG Chiller selection program will help to select LG water cooled screw chiller quickly and easily. To select RCWW series chiller, use the LATs chiller selection program or follow one of the procedures below.

1) Determine RCWW series unit size and operating conditions required to meet given capacity at given conditions.
English
Given: Capacity ......................................................98.4 Tons Leaving Chilled Water Temp. ............................... 44F Chilled Water Flow.................................. 2.4 gpm/Ton Entering Condenser Water Temp. ........................ 85F Condenser Water Flow .............................3.0 gpm/Ton Evaporator Fouling Factor ............................. 0.00010 Condenser Fouling Factor ............................... 0.00025 NOTE: For other than the above water Flow, contact nearest LG office.

SI
Given: Capacity ........................................................ 346 kW Leaving Chilled Water Temp................................6.7C Chilled Water Flow ............................ 0.043 l/s per kW Entering Condenser Water Temp. ......................29.4C Condenser Water Flow........................0.054 l/s per kW Evaporator Fouling Factor ...................................0.018 Condenser Fouling Factor .................................. 0.043 NOTE: For other than the above water Flow, contact nearest LG office.

2) From Cooling capacities table and pressure drop curves, determine operating data for selected unit.
English
Unit ............................................. RCWW1009AAA Capacity ............................................... 98.4 Tons Power Input ................................................68 kW Chilled Water Flow .................................. 236 gpm Chilled Water Pressure Drop ......................39 ft wg Condenser Water Flow ....... 296 gpm Condenser Water Pressure Drop .............. 6.4 ft wg

SI
Unit ............................................. RCWW1009AAA Capacity................................................... 346 kW Power Input ............................................... 68 kW Chilled Water Flow .................................... 15.0 l/s Chilled Water Pressure Drop ..................... 117 kPa Condenser Water Flow .............................. 18.7 l/s Condenser Water Pressure Drop ................. 19 kPa

CHILLER 60Hz/R134a _ 25

Water-Cooled Screw

11. Performance Data


RCWW Ratings All performance data is based on : 1. Chilled water flow is 0.043 l/s per kW(2.4gpm/ton), condenser water flow is 0.054 l/s per kW(3.0gpm/ton) 2. Cooler fouling factor of 0.0001 ft2hrF/ Btu (0.0186 m2C/kW) 3. Condenser fouling factor of 0.00025 ft2hrF/ Btu (0.043 m2C/kW) 4. 2C (3.6F) Subcooling. 1 Compressor Type 5. Refrigerant 134a
CONDENSER ENTERING WATER TEMPERATURE(F) 85 95
Cond Flow Rate (gpm)
167.6 196.9 225.4 244.9 270.5 173.3 203.7 233.2 253.3 279.7 179.3 210.7 241.2 262.1 289.4 182.3 214.3 245.3 266.5 294.3 185.3 217.9 249.4 271.0 299.2 191.5 225.1 257.8 280.0 309.2 197.8 232.6 266.3 289.3 319.4

Unit : RCWW Series 1comp Type


Cap.

75
Input kW
37.5 42.6 48.8 52.6 59.1 37.7 42.9 49.1 52.9 59.5 38.0 43.2 49.5 53.4 59.9 38.1 43.4 49.6 53.5 60.1 38.3 43.5 49.8 53.7 60.4 38.6 43.9 50.2 54.2 60.8 38.9 44.2 50.6 54.6 61.3

105
Cond Flow Rate (gpm)
156.6 183.6 210.2 228.2 252.3 161.9 189.9 217.4 236.1 260.9 167.2 196.2 224.6 243.9 269.6 170.0 199.5 228.4 248.0 274.1 172.8 202.8 232.1 252.1 278.6 178.5 209.5 239.8 260.5 287.8 184.4 216.4 247.7 269.1 297.3

Cooler Flow Rate (gpm)


142.2 168.1 192.5 209.3 230.5 147.8 174.6 200.0 217.5 239.5 153.6 181.5 207.8 226.0 248.9 156.5 185.0 211.8 230.3 253.6 159.5 188.4 215.8 234.7 258.4 165.4 195.5 223.8 243.4 268.0 171.5 202.7 232.1 252.4 278.0

Cap.

Input kW
42.4 48.2 55.2 59.5 66.9 42.6 48.4 55.4 59.8 67.1 42.8 48.7 55.7 60.1 67.5 42.9 48.8 55.8 60.3 67.7 43.0 49.0 56.0 60.4 67.9 43.3 49.2 56.3 60.7 68.2 43.6 49.6 56.7 61.2 68.7

Cooler Flow Rate (gpm)


133.5 157.7 180.6 196.4 216.3 138.9 164.1 187.9 204.4 225.0 144.4 170.7 195.4 212.5 234.0 147.2 174.0 199.2 216.7 238.6 150.1 177.3 203.0 220.8 243.1 155.8 184.2 210.9 229.3 252.5 161.7 191.1 218.8 238.0 262.0

LCWT (F)

UNIT SIZE
0609AAA 0709AAA 59.8 70.7 80.9 88.0 96.9 62.2 73.5 84.1 91.5 100.7 64.6 76.3 87.4 95.1 104.7 65.8 77.8 89.1 96.9 106.7 67.1 79.3 90.7 98.7 108.7 69.6 82.2 94.1 102.4 112.7 72.2 85.3 97.6 106.2 116.9

Cond Flow Rate (gpm)


162.2 190.4 217.9 236.7 261.5 167.7 196.9 225.4 244.8 270.4 173.4 203.6 233.1 253.2 279.7 176.3 207.0 237.0 257.4 284.3 179.1 210.4 240.9 261.7 289.0 185.1 217.4 248.9 270.4 298.6 191.2 224.6 257.1 279.3 308.5

Cap.

Input kW
48.1 54.7 62.6 67.5 75.9 48.2 54.9 62.8 67.7 76.1 48.4 55.1 63.0 68.0 76.3 48.5 55.2 63.1 68.1 76.5 48.6 55.3 63.2 68.2 76.6 48.8 55.5 63.5 68.5 77.0 49.0 55.8 63.8 68.8 77.3

Cooler Flow Rate (gpm)


124.1 146.6 167.9 182.6 201.0 129.3 152.8 174.9 190.3 209.5 134.5 159.0 182.0 197.9 218.0 137.2 162.2 185.7 201.9 222.4 140.0 165.4 189.4 206.0 226.8 145.5 172.0 196.9 214.1 235.8 151.2 178.7 204.6 222.5 245.1

Cap.

Input kW
53.9 61.3 70.1 75.7 85.0 54.0 61.4 70.3 75.8 85.2 54.1 61.5 70.4 75.9 85.3 54.1 61.6 70.5 76.0 85.4 54.2 61.7 70.5 76.1 85.5 54.4 61.9 70.8 76.4 85.8 54.5 62.0 71.0 76.6 86.0

Cooler Flow Rate (gpm)


114.7 135.5 155.1 168.7 185.8 119.7 141.5 162.0 176.2 194.0 124.6 147.2 168.6 183.3 201.9 127.2 150.4 172.2 187.2 206.2 129.9 153.5 175.7 191.1 210.5 135.2 159.8 182.9 199.0 219.1 140.8 166.3 190.4 207.1 228.1

Cond Flow Rate (gpm)


151.1 177.0 202.6 219.9 243.3 156.2 183.0 209.5 227.4 251.6 161.2 188.8 216.2 234.7 259.6 163.9 192.0 219.8 238.6 263.9 166.5 195.2 223.4 242.6 268.3 172.0 201.6 230.8 250.6 277.1 177.6 208.3 238.4 258.9 286.2

56.1 66.3 76.0 82.6 91.0 58.4 69.0 79.0 85.9 94.6 60.7 71.8 82.2 89.4 98.4 61.9 73.2 83.8 91.1 100.3 63.1 74.6 85.4 92.9 102.3 65.5 77.5 88.7 96.4 106.2 68.0 80.4 92.0 100.1 110.2

52.2 61.7 70.6 76.8 84.6 54.4 64.3 73.6 80.0 88.1 56.6 66.9 76.5 83.2 91.7 57.7 68.2 78.1 84.9 93.5 58.9 69.6 79.7 86.6 95.4 61.2 72.3 82.8 90.1 99.2 63.6 75.2 86.1 93.6 103.1

48.2 57.0 65.2 71.0 78.1 50.4 59.5 68.1 74.1 81.6 52.4 61.9 70.9 77.1 84.9 53.5 63.2 72.4 78.8 86.7 54.6 64.6 73.9 80.4 88.5 56.9 67.2 76.9 83.7 92.1 59.2 70.0 80.1 87.1 95.9

40

0809AAA 0909AAA 1009AAA 0609AAA 0709AAA

42

0809AAA 0909AAA 1009AAA 0609AAA 0709AAA

44

0809AAA 0909AAA 1009AAA 0609AAA 0709AAA

45

0809AAA 0909AAA 1009AAA 0609AAA 0709AAA 0809AAA

46

0909AAA 1009AAA 0609AAA 0709AAA

48

0809AAA 0909AAA 1009AAA 0609AAA 0709AAA

50

0809AAA 0909AAA 1009AAA

LEGEND

Cap. Capacity, Tons of Refrigeration Cond Condenser

kW Compressor Motor Input Power at Rated Voltage LCWT Leaving Chilled-Water Temperature (F)

26 _ CHILLER 60Hz/R134a

Water-Cooled Screw

11. Performance Data


RCWW Ratings
All performance data is based on : 1. Chilled water flow is 0.043 l/s per kW(2.4gpm/ton), condenser water flow is 0.054 l/s per kW(3.0gpm/ton) 2. Cooler fouling factor of 0.0001 ft2hrF/ Btu (0.0186 m2C/kW) 3. Condenser fouling factor of 0.00025 ft2hrF/ Btu (0.043 m2C/kW) 4. 2C (3.6F) Subcooling. 2 Compressor Type 5. Refrigerant 134a
CONDENSER ENTERING WATER TEMPERATURE(F) 85 95
Cond Flow Rate (gpm)
309.3 336.6 395.6 416.5 488.3 544.3 617.6 732.5 829.4 958.8 1109.0 320.0 348.3 409.3 431.1 505.3 563.2 639.1 758.0 858.4 992.3 1147.8 331.1 360.4 423.6 446.1 522.9 582.8 661.3 784.4 888.3 1026.9 1187.8 336.8 366.5 430.8 453.7 531.9 592.8 672.7 797.8 903.6 1044.6 1208.3 342.5 372.6 438.1 461.4 540.9 602.7 684.0 811.3 918.8 1062.3 1228.7

Unit : RCWW Series 2comp Type


Cap.

75
Input kW
68.2 75.2 85.7 89.2 105.0 119.0 132.9 157.4 174.9 201.2 232.7 68.6 75.7 86.2 89.7 105.6 119.7 133.7 158.4 176.0 202.4 234.0 69.1 76.1 86.8 90.3 106.2 120.4 134.6 159.4 177.1 203.6 235.5 69.3 76.4 87.1 90.6 106.6 120.8 135.0 159.9 177.7 204.3 236.3 69.5 76.7 87.3 90.9 107.0 121.2 135.5 160.4 178.3 205.0 237.1

105
Cond Flow Rate (gpm)
290.1 316.0 370.6 389.9 457.2 510.2 578.3 685.8 775.6 896.3 1036.7 299.9 326.7 383.2 403.3 472.8 527.6 598.1 709.3 802.2 927.1 1072.4 309.8 337.4 395.9 416.6 488.5 545.0 617.9 732.8 829.0 958.0 1108.1 315.1 343.1 402.6 423.7 496.8 554.2 628.4 745.3 843.1 974.4 1127.1 320.3 348.8 409.3 430.8 505.1 563.5 638.9 757.7 857.3 990.8 1146.0

Cooler Flow Rate (gpm)


263.2 285.8 337.6 356.2 417.4 463.9 527.7 626.0 711.1 822.8 951.7 273.6 297.1 351.0 370.4 434.0 482.3 548.7 650.9 739.4 855.5 989.5 284.4 308.9 364.9 385.0 451.1 501.4 570.3 676.6 768.6 889.2 1028.6 289.9 314.8 372.0 392.5 459.8 511.1 581.4 689.7 783.4 906.4 1048.5 295.5 320.8 379.0 399.9 468.5 520.8 592.4 702.8 798.3 923.7 1068.4

Cap.

Input kW
77.4 85.3 97.2 101.2 119.0 134.9 150.7 178.5 198.4 228.1 263.8 77.7 85.6 97.6 101.6 119.5 135.4 151.4 179.3 199.2 229.0 264.9 78.0 86.0 98.0 102.0 120.0 136.0 152.0 180.0 200.0 230.0 266.0 78.2 86.2 98.2 102.2 120.3 136.3 152.4 180.4 200.5 230.6 266.6 78.4 86.4 98.5 102.5 120.6 136.7 152.7 180.9 201.0 231.1 267.3

Cooler Flow Rate (gpm)


247.3 268.5 317.2 334.7 392.2 435.9 495.9 588.3 668.2 773.1 894.3 257.4 279.5 330.2 348.4 408.3 453.8 516.2 612.4 695.6 804.8 930.9 267.8 290.8 343.5 362.4 424.6 472.0 536.9 637.0 723.5 837.1 968.3 273.1 296.5 350.3 369.6 433.0 481.3 547.5 649.6 737.8 853.7 987.5 278.4 302.3 357.1 376.8 441.5 490.7 558.2 662.2 752.2 870.3 1006.6

LCWT (F)

UNIT SIZE
1109AAB 1209AAB 1409AAB 1509AAB 1809AAB 2009AAB 2209AAB 2609AAB 3009AAB 3409AAB 4009AAB 1109AAB 1209AAB 1409AAB 1509AAB 1809AAB 2009AAB 2209AAB 2609AAB 3009AAB 3409AAB 4009AAB 1109AAB 1209AAB 1409AAB 1509AAB 1809AAB 2009AAB 2209AAB 2609AAB 3009AAB 3409AAB 4009AAB 1109AAB 1209AAB 1409AAB 1509AAB 1809AAB 2009AAB 2209AAB 2609AAB 3009AAB 3409AAB 4009AAB 1109AAB 1209AAB 1409AAB 1509AAB 1809AAB 2009AAB 2209AAB 2609AAB 3009AAB 3409AAB 4009AAB 110.7 120.2 142.0 149.8 175.5 195.1 221.9 263.3 299.1 346.0 400.3 115.1 125.0 147.6 155.8 182.5 202.9 230.8 273.8 311.0 359.8 416.2 119.6 129.9 153.5 161.9 189.7 210.9 239.9 284.6 323.3 374.0 432.6 121.9 132.4 156.4 165.1 193.4 214.9 244.5 290.1 329.5 381.2 441.0 124.3 134.9 159.4 168.2 197.1 219.0 249.2 295.6 335.8 388.5 449.4

Cond Flow Rate (gpm)


299.6 326.2 383.0 403.1 472.7 527.1 597.8 709.0 802.3 927.4 1072.7 310.0 337.4 396.2 417.1 489.1 545.3 618.5 733.6 830.3 959.7 1110.0 320.5 348.9 409.8 431.4 505.8 563.9 639.7 758.7 858.7 992.6 1148.1 325.9 354.8 416.7 438.7 514.4 573.5 650.5 771.6 873.4 1009.6 1167.8 331.4 360.7 423.7 446.1 523.0 583.1 661.4 784.5 888.1 1026.5 1187.4

Cap.

Input kW
87.9 97.0 110.5 115.0 135.3 153.3 171.4 203.0 225.5 259.3 299.9 88.2 97.2 110.8 115.3 135.6 153.7 171.8 203.4 226.1 260.0 300.7 88.4 97.5 111.1 115.6 136.0 154.2 172.3 204.1 226.7 260.7 301.5 88.6 97.7 111.3 115.8 136.3 154.5 172.6 204.4 227.1 261.2 302.1 88.7 97.9 111.5 116.1 136.5 154.7 172.9 204.8 227.6 261.7 302.7

Cooler Flow Rate (gpm)


230.6 250.4 295.8 312.1 365.7 406.5 462.4 548.6 623.1 721.0 833.9 240.3 261.0 308.3 325.3 381.1 423.6 481.9 571.7 649.4 751.4 869.1 250.1 271.5 320.8 338.5 396.6 440.8 501.4 594.8 675.7 781.7 904.2 255.2 277.1 327.4 345.4 404.7 449.8 511.7 607.0 689.5 797.8 922.8 260.3 282.7 333.9 352.3 412.8 458.8 522.0 619.2 703.4 813.8 941.4

Cap.

Input kW
98.7 108.8 124.0 129.1 151.8 172.1 192.3 227.8 253.1 291.0 336.6 98.8 108.9 124.1 129.2 152.0 172.3 192.5 228.0 253.3 291.3 336.9 99.0 109.2 124.4 129.5 152.3 172.6 192.9 228.5 253.9 291.9 337.6 99.1 109.3 124.6 129.6 152.5 172.9 193.2 228.8 254.2 292.3 338.1 99.3 109.5 124.7 129.8 152.7 173.1 193.5 229.1 254.6 292.7 338.6

Cooler Flow Rate (gpm)


213.9 232.3 274.4 289.6 339.3 377.1 428.9 508.9 578.0 668.8 773.6 223.2 242.4 286.4 302.2 354.0 393.5 447.6 531.0 603.2 697.9 807.2 232.3 252.3 298.1 314.5 368.5 409.5 465.9 552.7 627.8 726.4 840.2 237.3 257.7 304.4 321.2 376.3 418.3 475.8 564.5 641.2 741.9 858.1 242.3 263.1 310.8 327.9 384.2 427.0 485.7 576.3 654.6 757.4 876.1

Cond Flow Rate (gpm)


280.7 305.9 358.3 376.8 441.9 493.4 559.0 662.9 749.2 865.6 1001.2 290.0 316.1 370.3 389.5 456.8 510.0 577.8 685.2 774.5 894.9 1035.1 299.3 326.1 382.2 402.0 471.5 526.3 596.3 707.2 799.5 923.8 1068.5 304.3 331.6 388.6 408.9 479.5 535.2 606.4 719.2 813.1 939.6 1086.7 309.4 337.1 395.1 415.7 487.5 544.1 616.6 731.2 826.7 955.3 1105.0

40

42

44

45

46

104.0 112.9 133.4 140.8 164.9 183.3 208.5 247.4 281.0 325.2 376.1 108.3 117.6 138.9 146.6 171.7 190.8 217.1 257.6 292.6 338.5 391.5 112.6 122.3 144.5 152.4 178.6 198.5 225.8 267.9 304.3 352.1 407.2 114.8 124.7 147.3 155.5 182.1 202.4 230.3 273.2 310.3 359.1 415.3 117.1 127.1 150.2 158.5 185.7 206.4 234.8 278.5 316.4 366.0 423.4

97.0 105.3 124.4 131.3 153.8 171.0 194.5 230.7 262.1 303.2 350.7 101.1 109.8 129.7 136.8 160.3 178.2 202.7 240.5 273.1 316.0 365.5 105.2 114.2 134.9 142.4 166.8 185.4 210.9 250.2 284.2 328.8 380.3 107.3 116.5 137.7 145.3 170.2 189.2 215.2 255.3 290.0 335.5 388.1 109.5 118.9 140.5 148.2 173.6 193.0 219.5 260.4 295.8 342.3 395.9

90.0 97.7 115.4 121.8 142.7 158.6 180.4 214.0 243.1 281.3 325.4 93.9 102.0 120.4 127.1 148.9 165.5 188.3 223.3 253.7 293.5 339.5 97.7 106.1 125.4 132.3 155.0 172.2 195.9 232.5 264.0 305.5 353.4 99.8 108.4 128.0 135.1 158.3 175.9 200.1 237.4 269.7 312.0 360.9 101.9 110.6 130.7 137.9 161.6 179.6 204.3 242.4 275.3 318.5 368.5

CHILLER 60Hz/R134a _ 27

Water-Cooled Screw

11. Performance Data


2 Compressor Type
CONDENSER ENTERING WATER TEMPERATURE(F) 85 95
Cond Flow Rate (gpm)
354.0 385.2 452.9 477.0 559.2 623.1 707.2 838.8 950.1 1098.4 1270.5 365.9 398.2 468.2 493.1 578.1 644.1 731.1 867.1 982.2 1135.6 1313.5

Unit : RCWW Series 2comp Type


Cap.

75
Input kW
70.0 77.2 87.9 91.5 107.7 122.0 136.4 161.5 179.4 206.4 238.7 70.5 77.8 88.6 92.2 108.5 123.0 137.4 162.8 180.8 208.0 240.5

105
Cond Flow Rate (gpm)
330.8 360.2 422.8 445.0 521.8 581.9 659.9 782.6 885.5 1023.5 1183.9 341.7 372.1 436.8 459.8 539.1 601.2 681.8 808.6 915.0 1057.6 1223.3

Cooler Flow Rate (gpm)


306.7 333.1 393.5 415.2 486.4 540.6 615.0 729.6 828.8 958.9 1109.2 318.3 345.6 408.3 430.8 504.7 561.0 638.1 757.1 859.9 995.0 1150.9

Cap.

Input kW
78.8 86.9 99.0 103.0 121.2 137.4 153.5 181.8 202.0 232.3 268.7 79.2 87.4 99.6 103.6 121.9 138.2 154.4 182.9 203.2 233.7 270.2

Cooler Flow Rate (gpm)


289.2 314.0 371.0 391.4 458.6 509.7 579.8 687.9 781.4 904.0 1045.7 300.4 326.2 385.3 406.6 476.4 529.5 602.3 714.6 811.7 939.1 1086.3

LCWT (F)

UNIT SIZE
1109AAB 1209AAB 1409AAB 1509AAB 1809AAB 2009AAB 2209AAB 2609AAB 3009AAB 3409AAB 4009AAB 1109AAB 1209AAB 1409AAB 1509AAB 1809AAB 2009AAB 2209AAB 2609AAB 3009AAB 3409AAB 4009AAB 129.0 140.1 165.5 174.6 204.6 227.4 258.7 306.9 348.6 403.3 466.5 133.9 145.3 171.7 181.2 212.3 235.9 268.4 318.4 361.7 418.5 484.0

Cond Flow Rate (gpm)


342.4 372.7 437.9 461.1 540.5 602.6 683.6 810.8 917.9 1061.1 1227.4 354.0 385.3 452.7 476.7 558.8 622.9 706.7 838.2 949.0 1097.1 1269.0

Cap.

Input kW
89.1 98.2 111.9 116.5 137.0 155.3 173.6 205.6 228.4 262.6 303.8 89.4 98.6 112.3 116.9 137.6 155.9 174.3 206.4 229.3 263.7 304.9

Cooler Flow Rate (gpm)


270.6 293.8 347.1 366.2 429.1 476.9 542.5 643.6 731.1 845.9 978.5 281.3 305.4 360.8 380.7 446.0 495.7 563.9 669.0 760.0 879.3 1017.1

Cap.

Input kW
99.5 109.7 125.0 130.1 153.1 173.5 193.9 229.7 255.2 293.4 339.4 99.8 110.0 125.3 130.4 153.5 173.9 194.4 230.2 255.8 294.1 340.2

Cooler Flow Rate (gpm)


252.0 273.6 323.3 341.1 399.6 444.2 505.2 599.4 680.9 787.8 911.2 262.1 284.6 336.3 354.8 415.7 462.0 525.6 623.5 708.3 819.5 947.9

Cond Flow Rate (gpm)


319.3 347.8 407.8 429.1 503.1 561.5 636.4 754.7 853.4 986.2 1140.7 329.6 359.0 421.0 443.0 519.5 579.6 657.0 779.2 881.2 1018.3 1177.9

48

50

121.6 132.1 156.0 164.6 192.9 214.4 243.9 289.3 328.6 380.2 439.8 126.3 137.2 162.1 171.0 200.4 222.7 253.3 300.5 341.4 395.0 456.9

113.8 123.6 146.0 154.0 180.5 200.6 228.2 270.7 307.5 355.8 411.5 118.3 128.4 151.7 160.1 187.6 208.5 237.2 281.4 319.6 369.8 427.8

106.0 115.1 136.0 143.4 168.1 186.8 212.5 252.1 286.4 331.3 383.2 110.2 119.7 141.4 149.2 174.8 194.3 221.0 262.2 297.9 344.7 398.7

LEGEND

Cap. Capacity, Tons of Refrigeration Cond Condenser

kW Compressor Motor Input Power at Rated Voltage LCWT Leaving Chilled-Water Temperature (F)

28 _ CHILLER 60Hz/R134a

Water-Cooled Screw

12. Pressure Drop


Condenser water pressure drop (SI Unit)
1 Compressor

180 160

60

Pressure Drop [kPa]

140 120 100 80 60 40

11

13

15

17

Water Flow [l/s]

Condenser water pressure drop (English Unit)


60

60 Pressure Drop [ftwg]


45

30

15

100

150

200

250

300

Water Flow [gpm]

Note: For flow out of this range, consult LG.

CHILLER 60Hz/R134a _ 29

Water-Cooled Screw

12. Pressure Drop


Condenser water pressure drop (SI Unit)
1 Compressor

40 35

70

80

90

100

Pressure Drop [kPa]

30 25 20 15 10 5 5

10

15

20

25

30

Water Flow [l/s]

Condenser water pressure drop (English Unit)


15 12 9 6 3 0 100

70

80

90

100

Pressure Drop [ftwg]

200

300

400

500

Water Flow [gpm]

Note: For flow out of this range, consult LG.

30 _ CHILLER 60Hz/R134a

Water-Cooled Screw

12. Pressure Drop


Condenser water pressure drop (SI Unit)
100 80

2 Compressor

260 220 140 180 200

Pressure Drop [kPa]

60 40 20 0

110 120

150

10

20

30

40

50

60

70

80

Water Flow [l/s]

Condenser water pressure drop (English Unit)


35 30

260 220 140 180 200

Pressure Drop [ftwg]

25 20 15 10 5 0 200

110 120

150

400

600

800

1000

1200

Water Flow [gpm]

Note: For flow out of this range, consult LG.

CHILLER 60Hz/R134a _ 31

Water-Cooled Screw

12. Pressure Drop


Condenser water pressure drop (SI Unit)
200

2 Compressor

400

Pressure Drop [kPa]

160

300

350

120

80

40 40

50

60

70

80

90

100

110

Water Flow [l/s]

Condenser water pressure drop (English Unit)


70

400
60

Pressure Drop [ftwg]

50 40 30 20 10 0 500

300

350

700

900

1100

1300

1500

1700

1900

Water Flow [gpm]

Note: For flow out of this range, consult LG.

32 _ CHILLER 60Hz/R134a

Water-Cooled Screw

12. Pressure Drop


Chilled water pressure drop (SI Unit)
150

1 Compressor

60
120

Pressure Drop [kPa]

90

60

30

10

12

14

16

Water Flow [l/s]

Chilled water pressure drop (English Unit)

50

60 Pressure Drop [ftwg]


40

30

20

10

100

120

140

160

180

200

220

Water Flow [gpm]

Note: For flow out of this range, consult LG.

CHILLER 60Hz/R134a _ 33

Water-Cooled Screw

12. Pressure Drop


Chilled water pressure drop (SI Unit)
250

1 Compressor
80 70 90 100

Pressure Drop [kPa]

200

150

100

50

10

15

20

25

Water Flow [l/s]

Chilled water pressure drop (English Unit)


90

80 Pressure Drop [ftwg]


70

90

100

70

50

30

10 100

150

200

250

300

350

Water Flow [gpm]

Note: For flow out of this range, consult LG.

34 _ CHILLER 60Hz/R134a

Water-Cooled Screw

12. Pressure Drop


Chilled water pressure drop (SI Unit)
160 140

2 Compressor

220 140 110120 150 180 200

260

Pressure Drop [kPa]

120 100 80 60 40 20 0 10 20 30

40

50

60

Water Flow [l/s]

Chilled water pressure drop (English Unit)

50

220
40

260

Pressure Drop [ftwg]

140
30

180 200

110120

150

20

10

200

400

600

800

1000

Wate Flow [gpm]

Note: For flow out of this range, consult LG.

CHILLER 60Hz/R134a _ 35

Water-Cooled Screw

12. Pressure Drop


Chilled water pressure drop (SI Unit)
300

2 Compressor

400
250

300

350

Pressure Drop [kPa]

200

150

100

50

30

45

60

75

90

Water Flow [l/s]

Chilled water pressure drop (English Unit)


100

400 300 350

80

Pressure Drop [ftwg]

60

40

20

0 400

600

800

1000

1200

1400

1600

Wate Flow [gpm]

Note: For flow out of this range, consult LG.

36 _ CHILLER 60Hz/R134a

NO 1 Compressor Condenser Expansion Device Oil Filter Oil separater Expansion Devices Filter Drier Evaporator Ejector for Oil Return Economizer (Flash gas tank) 2 3 4 5

1 Compressor Type

DESCRIPTION

DP 6,7 8

1
9 10 11 M

Water-Cooled Screw

LEGEND
SYMBOL OH LP LP T WF T WF HP LP DP OF HP HP T DESCRIPTION Oil heater High pressure switch Low pressure switch Diffenent pressure switch Oil flow switch WF AF T T AF T OL Water flow switch Anti-freezing switch Temperature sensor Oil level sensor Relief valve Insulation

13. Piping Diagrams

2 9

10 5 11 8
S OL OH

Sight glass Solenoid valve

7
HP

Check valve Shut-off valve(Angle valve) High Pressure Gauge LP M Low Pressure Gauge Muffler

OF

4 3

CHILLER 60Hz/R134a _ 37

LG Electronics

DWG NAME : Water cooled Screw Chiller's Piping Diagram 76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea MODEL NAME : DATE : -

NO 1 Compressor Condenser Expansion Device Oil Filter Oil separater Expansion Devices Filter Drier Evaporator Ejector for Oil Return 10 11 Economizer (Flash gas tank) 2 3

2 Compressors Type
HP LP
5 4

DESCRIPTION

1
DP
8 9 6,7

38 _ CHILLER 60Hz/R134a
M HP LP

Water-Cooled Screw

1
LEGEND
M LP OF S S OF T WF
SYMBOL OH HP LP DP DESCRIPTION Oil heater High pressure switch Low pressure switch Diffenent pressure switch OF WF Oil flow switch Water flow switch AF Anti-freezing switch

13. Piping Diagrams

T WF

2
HP T

T AF T

T OL

Temperature sensor Oil level sensor Relief valve

5 11
S S

8 10 6
S
S

Insulation Sight glass

10
OL OH

7
S

Solenoid valve Check valve Shut-off valve(Angle valve) HP LP M High Pressure Gauge Low Pressure Gauge Muffler

4 3
S

LG Electronics

DWG NAME : Water cooled Screw Chiller's Piping Diagram 76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea MODEL NAME : DATE : -

1 Compressor Type

R
Sign F1-F6 CCH1 NFB L0 R1,2
8 1 26 38

EXTERNAL EQUIPMENTS

Instruction Fuse Oil Heater No Fuse Switch Power Indicator Lamp Assist Relay Power Switch Model Option Switch Inner Temperature Controller C/Box Heat Dissipation Fan Power Box Heat Dissipation Fan Temperature Sensor Current Transducer PLC Controller

S
COW PUMP
P1 P2 ALM

P1

P2

REMOTE RUN TOWER FAN

CHW PUMP

ALARM

FN

T N
111 1
F3 F4 F5

FG
SMPS SW1 THC1

43
112 2 5 6 8 2 5 6 7

47

49

47

83

84

101

86

CT N2 L4 VOLTAGE MONITORING 7 4 (5E)


R S T

L1 L2 24 25 4 2 L3 L2 L3

L1

220VAC

DRY CONTACT

DRY CONTACT

220VAC POWERED

220VAC POWERED

220VAC POWERED

220VAC POWERED

380VAC 3P 4W

CF1
NFB 2

M5

M4

TO MAIN CONTROL UNIT

CF2 S1-S5 CT1,2 SC80-FX

Water-Cooled Screw

M6 T1
L0

T2

T3

T1 T2 T3

1 FR2
F1 SW1
REMOTE

F2 29 5

M1

CCH1

HMI unit
3 R1 R1 4 THC1 9 CF1

Pro-face Touch Screen HP1 LP1 FR OH DT High Voltage Switch Low Voltage Switch Comp. Over Load Protector Comp. Inner Temperature Protector Comp. Discharge Temperature Sensor INT69 M1 Comp. Internal Protector Main Contactor M2 M3 Contactor Y Contactor ENRG FU FW1 Emergency Button Freezing Switch Water Flow Switch FW2 RC MV1 MV2 Hot Water Flow Switch Remote Switch Comp. Loading Valve Comp. Unloading Valve

STOP

30

MANUAL

14. Wiring Diagrams

X Y COMP2 OH Z 604

U V W

603 1 DT 11 14 EMRG 102 R3 N L 605 2

INTERNAL PROTECTOR (INT69)

37 26 2 4 TO MAIN CONTROL UNIT

26 27
L

4 2
P2 EMRG FW2 REMOTE RUN

+V

-V

220V
N

SMPS

LPD

OIL FLOW-1

OIL LEVEL

INT69-1

5E-1

HP LP

ANTI-FREEZE

M1

M2

FROM CT1 TRANSMITTER

M3

S3: EVAP OUT WATER TEMP

S4: EVAP IN WATER TEMP

S1: COMD OUT WATER TEMP

S2: COND IN WATER TEMP

S5: COMP1 DISCHARGE TEMP

FR1

P1

49
FW1 R1

SV COMP OS1

Oil Separator Solenoid Valve Compressor Oil Level Switch

24VDC-P

24VDC-G

26 27 10 11 12 13 1415 16 17 18 19
AI1+ AI1AI2+ AI2AI6+ AI8+ AI3+ AI3+ AI4+ AI4AI5+ AI5IO1 IO2 IO3 IO4 IO5 IO6 AI6AI7+ AI7AI8IO7 IO8

27 26 22 23
F.G 3 2 5 O01 O02 O03 O04 O05 O06 O07 O08 COM O09 O10 O11 O12 O13 O14 O15 GND DD+ 24G 24+

31 32 33 34 35 36 37 38 39 40 41 42 43 44 45
IO9 I10 I11 I12 I13 I14 I15

46 26
I16 24V 24G

OS2 LPD P1, P2

Oil Flow Switch High-Low Pressure Gradient Switch Water Pump Contactor

SC80-FX: MAIN CONTROL UNIT


O16 COM

5E EXT

Converse Phase Protector Outer Alarm Connector

HMI UNIT
71 75 76 84
M3 M2

72

73 74

78 7 83

85
R3

86

7
EMRG

4
R3

TRANS FN

380/220 Transformer Cooling Tower Fan Connector

87

88

101

SV2

M1

M2

M3

MV1 SV1

MV2 MV3

FN

P1

P2

ALM

Note:

CHILLER 60Hz/R134a _ 39

1. Field modifications or additions must be in compliance with national electrical code as well as all applicable codes and specifications. 2. Refer to certified dimension drawing for exact locations of the main power and control power entrance locations.

2 Compressors Type
Dual point power connection
R S T FG
F6 F7 F8

N2
2 1 26 7 38

R 5

S 6

T 8

220VAC

L4

VOLTAGE MONITORING 4 (5E-1)

R S T N

111 1 1
F3 F4 F5

113

FG
1 26 58

220VAC

220V

P2

FW2

EMRG

LPD

5E-1

HP

LP

REMOTE RUN

INT69-1

OIL FLOW-1

OIL LEVEL

ANTI-FREEZE

M2

M1

M3

M4

M5

FROM CT1 TRANSMITTER

FROM CT2 TRANSMITTER

FR1

M6

S3: EVAP OUT WATER TEMP

S4: EVAP IN WATER TEMP

S1: COMD OUT WATER TEMP

S2: COND IN WATER TEMP

S5: COMP1 DISCHARGE TEMP

S6: COMP2 DISCHARGE TEMP

P1

FW1

24VDC-P

24VDC-G

26 10 11 12 13 1415 16 17 18 19
AI1+ AI1AI6+ AI8+ AI8AI2+ AI2AI3+ AI3+ AI4+ AI4AI5+ AI5AI6AI7+ AI7IO1 IO2 IO3 IO4 IO5 IO6 IO7 IO8 IO9 I10 I11 I12 I13 I14 I15 I16 24V 24G I17 I18 I19 I20 I21 I22 I23 I24 I25 I26 I27 I28 I29 I30 I31

27 22 23 24 25 26 27 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 51 52 53 54 57 58 59 46 26
F.G D+ DGND O01 O02 O03 O04 O05 O06 O07 O08 COM O09 O10 O11 O12 O13 O14 O15 O16 COM O17 O18 O19 O20 O21 O22 O23 O24 COM O17 O18 O19 O20 O21 O22 O23 O24 24G 24+

27 26

R1

FR2

49

OIL FLOW-2

INT69-2

5E-2

40 _ CHILLER 60Hz/R134a
112 2 2 5 6 8 2 7 8 7 6 7 5

CT1
114

CT2 N2 L4 VOLTAGE MONITORING 4 (5E-2)


R 5 S 6 T 8

380VAC 3P 4W

380VAC 3P 3W

Water-Cooled Screw

L1 L3 24 25 4 2 4 2 26 27 L2 L3 L2 L3

L2

L3

L1

L2

L1

L1

M2
T3

M1 M6 T1
L0 T2 T3 T1 T2 T3

TO MAIN CONTROL UNIT M5 M4

TO MAIN CONTROL UNIT

M3 T1 1 FR1
F1 SW1
REMOTE

T2 F2 29 5 6 M1 M4 CCH1

T3

T1

T2

NFB 2

FR2

3 R1 R1 4 THC1 CF1

14. Wiring Diagrams

STOP

30

MANUAL

U V W

600 1
Y COMP2 OH Z 604 X W

INTERNAL PROTECTOR (INT69-1)


U V

603 1 DT 11 14 9 CF2 N L THC2 605 2

INTERNAL PROTECTOR (INT69-2)

Y COMP1 OH Z 601

DT 11 14 N L

602 2

CF3 37 26 2 4 102 TO MAIN CONTROL UNIT 4 EMRG 2 TO MAIN CONTROL UNIT 57 26

R3

26 27

26 27

SMPS

+V

-V

I32

24V

24G

SC80-FX: MAIN CONTROL UNIT


COM

HMI UNIT
71 75 76 79 84 93 94
M6 R3 M5 R3

72 7 80 85 86 81 82 95 96 7 82
M3 M2

73 74

78 83 7 91 92

98

7
EMRG

4
P1 P2

EXTERNAL EQUIPMENTS REMOTE RUN TOWER FAN


FN

COW PUMP
P1

CHW PUMP
P2

ALARM
ALM

87 101 107 108

88

SV2 ALM

M1

M2

M3

MV1 SV1 FN SV5 M4 M5 M6 SV4 P1 P2

MV2 MV3 SV3 MV4 SV6 MV6

MV5

43 DRY CONTACT

47

49 DRY CONTACT

47

83

2 220VAC POWERED

84

2 220VAC POWERED

101

2 220VAC POWERED

86

2 220VAC POWERED

F1 ~ F3
CF1 CF2 R1
CCH1

Fuse C/Box Heat dissipation fan P/Box Heat dissipation fan Assist relay Oil heater
THC

FN1A ~ FN3A FN1B ~ FN3B OLF1A ~OLF3A OLF1B ~ OLF3B OLC1 Inner temperature controller
SV1 SV2
MV1 MV2 MV3

Fan1A~Fan3A magnet contactors Fan1B~Fan3B magnet contactors Fan1A~Fan3A over current relays Fan1B~Fan3B over current relays Comp over current relay Emergency switch Oil seperator solenoid v/v Mid pressure air charging solenoid v/v Comp. capacity control v/v(25%, 50%, 75%) M1 M2 M3 Comp. magnetic switch 1 Comp. magnetic switch 2 ( connection) Comp. magnetic switch 3 ( Y connection) SW1 HP LP 5E
L0

Power indicator lamp Mold option switch High pressure switch Low pressure switch Converse phase protector

Note:

1. Field modifications or additions must be in compliance with national electrical code as well as all applicable codes and specifications. 2. Refer to certified dimension drawing for exact locations of the main power and control power entrance locations.

Water-Cooled Screw

15. Electrical Data


1 Compressor Type
Unit Voltage Unit (1Comp. Type) RCWW0609AAA RCWW0709AAA RCWW0809AAA RCWW0909AAA RCWW1009AAA V-HzPhase Supplied Min. Max. 1 1 1 1 1 No. Compressor LRA Amp. 200 245 265 270 283 RLA Amp. 73 83 95 102 115 Start Current Amp. 195 219 251 275 306 73 83 95 102 115 Total RLA Minimun Circuit Amps. (MCA) 91 104 119 128 144

MOCP

REC Fuse Size 150 175 175 200 225

380-60-3

342

418

150 175 200 225 250

Symbols: LRA: Locked Rotor Amps. RLA: Rated Load Amps. MCA : Minimum Circuit Amps. (for wire sizing) MOCP : Maximum Over Current Protection REC Fuse Size: Recommended Fuse Size Notes: 1. 380V-60Hz-3 rating voltage, voltage maximum tolerance 10%. 2. Electrical source must be 3phase 4wire for security. Neutral line and earth line must be separately connected. 3. Ground wire must be installed. 4. Use cable applicable to current more than MCA. 5. Use ring type terminal cable. 6. Have all electric work done by a licensed electrician according to "Electrical facility engineering standard" and "Interior wire regulations."

CHILLER 60Hz/R134a _ 41

Water-Cooled Screw

15. Electrical Data


Single point power connection
Unit Voltage Unit (2Comp. Type) RCWW1109AAB RCWW1209AAB RCWW1409AAB RCWW1509AAB RCWW1809AAB RCWW2009AAB RCWW2209AAB RCWW2609AAB RCWW3009AAB RCWW3409AAB RCWW4009AAB 380-60-3 342 418 V-HzPhase Supplied Min. Max. 2 2 2 2 2 2 2 2 2 2 2 No. Compressor LRA Amp. 200 200 245 245 270 283 328 372 381 445 486 RLA Amp. 65 73 83 92 102 115 129 153 170 203 217 Start Current Amp. 169 190 216 239 265 299 335 398 442 527 564 130 146 166 184 204 230 258 306 340 405 434 Total RLA

2 Compressors Type

Minimun Circuit Amps. (MCA) 182 204 232 257 285 321 360 427 475 566 606

MOCP

REC Fuse Size 225 250 300 300 350 400 450 500 600 700 700

250 300 300 350 400 450 500 600 600 800 800

Symbols: LRA: Locked Rotor Amps. RLA: Rated Load Amps. MCA : Minimum Circuit Amps. (for wire sizing) MOCP : Maximum Over Current Protection REC Fuse Size: Recommended Fuse Size Notes: 1. 380V-60Hz-3 rating voltage, voltage maximum tolerance 10%. 2. Electrical source must be 3phase 4wire for security. Neutral line and earth line must be separately connected. 3. Ground wire must be installed. 4. Use cable applicable to current more than MCA. 5. Use ring type terminal cable. 6. Have all electric work done by a licensed electrician according to "Electrical facility engineering standard" and "Interior wire regulations."

42 _ CHILLER 60Hz/R134a

Water-Cooled Screw

15. Electrical Data


Dual point power connection
Unit Voltage Unit (2Comp. Type) RCWW1109AAB RCWW1209AAB RCWW1409AAB RCWW1509AAB RCWW1809AAB RCWW2009AAB RCWW2209AAB RCWW2609AAB RCWW3009AAB RCWW3409AAB RCWW4009AAB 380-60-3 342 418 V-HzPhase Supplied Min. Max 2 2 2 2 2 2 2 2 2 2 2 No. Compressor LRA Amp. 200 200 245 245 270 273 328 372 482 583 643 RLA Amp. 65 73 83 92 102 115 129 153 170 203 217 Start Current Amp. 169 190 216 239 265 299 335 398 442 527 564 130 146 166 184 204 230 258 306 340 405 434 Total RLA

2 Compressors Type

Minimun Circuit Amps. (MCA) 81 / 81 91 / 91 104 / 104 115 / 115 128 / 128 144 / 144 161 / 161 191 / 191 213 / 213 253 / 253 271 / 271

MOCP

REC Fuse Size 125 / 125 150 / 150 175 / 175 175 / 175 200 / 200 225 / 225 250 / 250 300 / 300 350 / 350 400 / 400 450 / 450

175 / 175 200 / 200 225 / 225 250 / 250 250 / 250 300 / 300 350 / 350 400 / 400 450 / 450 500 / 500 600 / 600

Symbols: LRA: Locked Rotor Amps. RLA: Rated Load Amps. MCA : Minimum Circuit Amps. (for wire sizing) MOCP : Maximum Over Current Protection REC Fuse Size: Recommended Fuse Size Notes: 1. 380V-60Hz-3 rating voltage, voltage maximum tolerance 10%. 2. Electrical source must be 3phase 4wire for security. Neutral line and earth line must be separately connected. 3. Ground wire must be installed. 4. Use cable applicable to current more than MCA. 5. Use ring type terminal cable. 6. Have all electric work done by a licensed electrician according to "Electrical facility engineering standard" and "Interior wire regulations."

CHILLER 60Hz/R134a _ 43

Water-Cooled Screw

16. Installation
Instruction about space for chiller maintenance

900(35.43)

900(35.43)

Unit

Control Box

In & Out water pipe side

D
"D" refer to Dimension Data

1200(47.24)

[Unit : mm (inch)]

Foundation bolt install instruction


1 2 3

Flange Dimension

D
5 6 7

C G f

150(5.91)

[Unit : mm] No. 1 2 3 4 5 6 7 Name Foot Bolt(field supplied) Cap Nut(field supplied) Spring Washer(field supplied) Flat Washer(field supplied) Base Unit Damping Rubber Pad Foundation Place [Unit : mm (inch)] DN 80 100 220 20 156 2 108 180 18 8-M16 150 200

D 200 t 20 G 132 f 2 d (O.D. of Pipe) 89 C 160 Bolting Dia. of Holes 18 No.-Size 8-M16 Slip on welding - RF Type

285 340 22 26 211 266 3 3 156 219 240 295 22 22 8-M20 12-M20

44 _ CHILLER 60Hz/R134a

Water-Cooled Screw

16. Installation
Foundation
250(9.84)

Ground

4-M24(1") Anchor Bolt

E+600(23.62)

Electric cable reservation hole 150(6)

1200(47.24) D D+720(28.35)

250(9.84)

[Unit : mm (inch)] Unit : RCWW Series 0609AAA 0709AAA 0809AAA 0909AAA 1009AAA inch mm inch mm inch mm inch mm inch mm D 73.15 1,858 88.90 2,258 92.83 2,358 92.83 2,358 92.83 2,358 Outline Dimension E 19.09 485 19.09 485 19.09 485 19.09 485 21.06 535

Explain : 1. Ensure base has sufficient strength which can be produced by steel concrete and can also be produced by profiled bar. 2. Level deviation of base should not be more than 0.1%. 3. Rubber damping pad can be used during installation.

CHILLER 60Hz/R134a _ 45

Water-Cooled Screw

16. Installation
Foundation
250(9.84)

600(23.62)

600(23.62) Ground

Drain 4-M24(1") Anchor Bolt

E+600(23.62)

Electric cable reservation hole 150(6)

250(9.84)

900(35.43)

1,000(39.37) D D+720(28.35)

250(9.84)

600(23.62)

600(23.62)

[Unit : mm (inch)] Unit : RCWW Series inch mm inch mm inch mm D 104.65 2,658 104.65 2,658 104.65 2,658 Outline Dimension E 44.09 1,120 45.28 1,150 49.21 1,250

1109AAB 1209AAB 1409AAB

Explain : 1. Ensure base has sufficient strength which can be produced by steel concrete and can also be produced by profiled bar. 2. Level deviation of base should not be more than 0.1%. 3. Rubber damping pad can be used during installation.

46 _ CHILLER 60Hz/R134a

Water-Cooled Screw

16. Installation
Foundation
250(9.84)

600(23.62)

600(23.62) Ground

Drain 4-M24(1") Anchor Bolt

E+600(23.62)

Electric cable reservation hole 150(6)

250(9.84)

900(35.43)

1,200(47.24) D D+720(28.35)

250(9.84)

600(23.62)

600(23.62)

[Unit : mm (inch)] Unit : RCWW Series 1509AAB 1809AAB 2009AAB 2209AAB 2609AAB 3009AAB 3409AAB 4009AAB Explain : 1. Ensure base has sufficient strength which can be produced by steel concrete and can also be produced by profiled bar. 2. Level deviation of base should not be more than 0.1%. 3. Rubber damping pad can be used during installation. inch mm inch mm inch mm inch mm inch mm inch mm inch mm inch mm D 112.52 2,858 112.52 2,858 112.52 2,858 120.39 3,058 128.27 3,258 151.89 3,858 151.73 3,854 159.61 4,054 Outline Dimension E 49.21 1,250 53.54 1,360 53.54 1,360 57.09 1,450 59.06 1,500 61.02 1,550 66.93 1,700 66.93 1,700

CHILLER 60Hz/R134a _ 47

Water-Cooled Screw

17. Guide Specifications


1. General
LG RCWW series are microprocessor controlled, twin-screw compressor, water-cooled, liquid chillers. Each RCWW series chiller is factory-assembled including compressor, evaporator, condenser, and control box. The initial charge of refrigerant HFC-134a and oil will be supplied for all units. Chillers shall be rated in accordance with ARI Standard 550/590. Chillers shall be evacuated and fully charged with refrigerant and oil, and shall be factory operational run tested.

2. Equipment
2.01 Application range
This specification is applied to all the models of water cooled screw chillers RCWW which is made and sold by LG Electronics Co.

2.02 General structure


Chiller is all in one and is made with convenient structure for installation, operation and maintenance management and also compact to minimize the installation area.

2.03 Screw compressor


Semi-hermetic screw compressor uses environment friendly refrigerant,R134a (HFC series). Motor is 3 phase and semi-hermetic type. Apparatus for supplying oil is operated by the pressure difference of high and low pressure, it has oil filter and oil heater in it to minimize oil dilution. It has the structure to recover oil from discharged gas by built in oil separator. Capacity control is stepless control by slide valve operation through electric valve open-close which senses chilled water outlet temperature. For protecting compressor, PTC sensor is installed which is able to sense motor temperature. Check valve is installed at refrigerant discharge outlet to prevent the compressor from the backward flow of refrigerant gas when chiller stops. Compressor has a built-in motor to prevent refrigerant leakage. The rotor housing is made of high strength gray cast iron FC-25.

2.04 Evaporator
Evaporator is (flooded) shell & tube type and made with carbon steel. Also it has tube changeable structure. To increase the efficiency of evaporator, it has the structure to spray refrigerant liquid on heat exchanger tube surface. It has the structure which is easy to be disassembled, because water box cover is attached and fixed with bolt & nut for maintenance and washing of inner tube. Safety valve which spouts refrigerant of evaporator is installed to protect chiller in case when temperature increases too much because of fire. Tube is phosphorus deoxidization bronze pipe which has over 99.9% purity and no joint, outside of it is attached to special shape fin, inside of it has inner grooved tube or equivalent product. Anti-freezing switch is installed at chilled water outlet to prevent it from being frozen and burst by chilled water flow stopping, chilled water temperature decreasing, and drain plug, air bent plug are at body.

48 _ CHILLER 60Hz/R134a

Water-Cooled Screw

17. Guide Specifications


Evaporator is covered with thermal insulation materials for dew condensation prevention and thermal insulation. Design pressure for shell is 300psig(2.1MPa). Design working pressure for tube line is 150psig(1.0MPa) or 300psig(optional). The evaporator and economizer are insulated with 3/4inch(19mm) insulation(K=0.26).

2.05 Condenser
High efficiency heat exchanger of Horizontal shell & tube type is used. It has structure which is easy to be disassembled, because water box cover is attached and fixed with Bolt & Nut for maintenance and washing of inner Tube after condenser installation. Condenser inner pressure test is done at 3.3MPa pressure and there should not be any leakage, change or any malfunction. Tube is phosphorus deoxidization bronze pipe which has over 99.9% purity and no joint, outside of it is attached to special shape fin, inside of it has inner grooved tube or equivalent product. Safety valve is installed to protect the chiller by spurting the refrigerant of condenser when the temperature increases too much because of fire and outlet stop valve for Pump- Down the refrigerant when operation stop.

2.06 Expansion device


Expansion devices are installed between compressor and evaporator to enable refrigerant to be evaporated in cooler by reducing pressure (throttling). Ejector type is applied to increase the durability of product.

2.07 Oil separator


Oil heater is installed inside of oil separator to maintain proper oil temperature, at the same time to separate refrigerant from oil. Oil which is supplied to compressor is operated by the difference of high and low pressure without extra oil pump. Oil separator has a sight glass to enable operator to check the oil level.

2.08 Economizer, Flash gas tank


Economizer is installed to increase efficiency of refrigeration cycle. Refrigerant passed through the condenser is separated to refrigerant liquid and flash gas in the economizer. Refrigerant liquid is sent to evaporator and flash gas is sent to compressor inlet to enhance the chiller performance. Economizer does not have any driving part; it has the structure to increase the chiller performance

2.09 Safety devices


Proper oil circulation Triple protection of oil flow switch, oil level switch and differential pressure switch. Normal refrigerant pressure switch High pressure switch and low pressure switch. Temperature check Sensing overheat of compressor discharge temperature, sensing overheat of compressor motor wire, and anti-freezing switch. Chilled water flow Chilled water flow switch. Voltage and current Voltage monitoring system, compressor over-current breaker (compressor OCR).

CHILLER 60Hz/R134a _ 49

Water-Cooled Screw

17. Guide Specifications


2.10 Spray ejector for oil return
Spray ejector which does not really need extra energy for consumption, recovers the oil mixed with refrigerant for supplying to the compressor.

2.11 Auto controls


Chiller has its own auto control function; also component parts for auto control shall be installed in an extra control panel and power panel. Control panel and power panel shall be designed to satisfy waterproof class IP54. Component parts for auto control are installed in the control panel and power panel, controller and power supply device are in the control panel and fan, electric contactor for controlling compressor and 3 phase power related device are in the power panel. Indicator which indicates supply of control power, stop switch for emergency and the control powers ON/OFF switch shall be installed in the control panel. The PLC (Programmable Logic Controller) is applied to control the chiller enhances the chiller performance and through HMI (Human Machine Interface) that has touch screen LCD, it aids user interface and the function of it contains these below. - Chiller ON/OFF - Detect the sensor of chiller and indicate operation information - Indicate malfunction occurrence and history - Input and indicate the set temperature and user setting value - Input and indicate control setting and service setting value Temperature sensor information of chiller is provided through HMI, which contains the following: - Chilled water inlet temperature - Chilled water outlet temperature - Compressor outlet refrigerant temperature - Condenser water inlet temperature - Condenser water outlet refrigerant temperature PLC provides MODBUS RTU communication function; especially Lon Works or BACnet can be applied to the system on the request of customer by installing exterior type translator. Power panel contains electric contactor for compressor and over load relay. Electric contactor for compressor is made to minimize the running current of compressor through Y-start. Power panel contains electric contactor and over-load relay for each condenser fan. Power panel contains power monitoring device to detect power supply condition, and power monitoring device has over 5 detecting function including reverse voltage, over voltage, low voltage, open-phase, and no voltage. Auto control system of chiller contains the following functions: - It performs fan and compressor ON/OFF function and several solenoid valve controlling. - It provides interlock point of contact for controlling chilled water pump. - It controls refrigerant volume through the condition of compressor operation and slide valve of compressor for achieving chilled water outlet setting temperature. - When chilled water outlet temperature and condenser outlet refrigerant temperature is high, limit the compressor operation to prevent malfunction. - Keep proper pressure of condenser through fan control by condenser outlet temperature.

50 _ CHILLER 60Hz/R134a

Water-Cooled Screw

17. Guide Specifications


2.12 Refrigerant piping
Ref. piping is made with phosphorus deoxidization bronze pipe which has no joint and its purity over 99.9%, and is installed to for smooth flow of refrigerant between each component. Install check valve at compressor discharge side not to reverse the discharged refrigerant. Install filter dryer at pipe to absorb the moisture from inner side of pipe and filter the alien substance. From expansion valve to evaporator pipe has insulation to prevent flash gas occurrence, also to prevent dew condensation on pipe surface. When discharged gas temperature is abnormal, electric valve is operated and protect a compressor by connecting the liquid refrigerant to suction pipe of compressor (liquid injection pipe). After test, vacuum is done so that there shall be no moisture inside.

3. Other
Chiller is made after getting approval on everything about production from ordering company. About thing that is not in this specification, discuss it with ordering company and get approval.

CHILLER 60Hz/R134a _ 51

Water-Cooled Screw

Appendix
Unit Conversion Cooling Capacity
RT 1 Btu/h 12,000 kcal/h 3024.2 W 3516.8

Volume
CMM 1 CFM 35.3 gpm 264.2 l/s 16.67

Length
m 1 cm 100 mm 1,000 inch 39.37

Power
HP 1 W 746 kW 0.746

Pressure
bar 1 kPa 100 ft wg 33.455 psi 14.5 kg / cm2 1.0198

Temperature
5 C = (F - 32) 9 Where, C is Temperature in C F is Temperature in F

52 _ CHILLER 60Hz/R134a

CHILLER 60Hz/R134a _ 53

54 _ CHILLER 60Hz/R134a

CHILLER 60Hz/R134a _ 55

P/No.: MFL61764715

Air Conditioner 20 Yeouido-dong, Yeongdeungpo-gu, Yeouido P.O.Box 335 Seoul, 150-721, Korea. http://www.lgeaircon.com

All rights reserved Printed in Korea September/2010 The specifications, designs, and information in this brochure are subject to change without notice.

The air conditioners manufactured by LG have received ISO9001 certificate for quality assurance and ISO14001 certificate for environmental management system.

You might also like