Specialists in the design and manufacturing of innovative solutions. With its Epoxy Vacuum Impregnation

E.V.I. process, it provides


superior quality products.

Synonymous with Quality

www.delta.xfo.com

2-2

2- CHARGES NON LINAIRES

1 800 663-3582

Back to table of contents


Synonymous of Quality

DELTA TRANSFORMERS INC.


Founded in 1983, Delta Transformers Inc. has developed considerable expertise in the development of power, distribution and non linear load transformers over the years. With the contibution of its qualied employees, Delta Transformers Inc. has become a leader in the industry. The values of Delta Transformers Inc. are conveyed through its Delta Touch Philosophy. Synonymous with quality, Delta Touch Philosophy guides the Delta Transformers Inc. performance: Customers First ... Quality always Innovative quality Products delivered on time A long-term partnership with our customers and suppliers

Power Transformer
Up to 35 000 V Up to 15 000 kVA Up to 150 kV BIL

GENERAL INFORMATIONS

Non Linear Load Transformer


Drive Isolation Transformer - Optimal design - Oversized neutral conductor - Electrostatic Shield K-Factor Transformer Isolated Transformer Super Isolated Transformer - K-Factor (4, 9, 13, etc.) - Economic solution in high harmonic environments - High quality manufacturing - TVSS - Electrostatic Shield Computer Power Center - Compact - Proximity to load - Solution to harmonics mitigation Mitigator Series Transformer - Harmonic currents mitigation at low impedance - Field adjustable phase shift - Single or double output

INTRODUCTION

Its vision: to be recognized as the best in the eld of electrical energy transformation in Canada.

Performance Products
Exceeding customers needs, the Research & Development team is characterized by its innovative solutions, Today, Delta Transformers Inc. offers the following product lines from its plant in Granby:

Distribution Transformers
General Purpose Transformer - Copper or Aluminium - Single phase or Three phase Commercial Series Transformer - Institutional or Commercial Application - No option available - Economic solution Epoxy-potted Transformer - humid or corrosive environments Mini Power Center - Compact solution - Proximity to load - Temporary or permanent installation Autotransformer - Common primary and secondary winding - Light and compact - More cost effective

1 www.delta.xfo.com

MANUFACTURING STANDARD
Delta Transformers Inc. uses the highest quality materials available in the manufacturing of all its transformers such as copper, aluminium, magnetic steel and various insulators. In addition to being ISO 9001 : 2000 certied, Delta Transformers Inc. also tests and certies its products based on recognized international standards. Delta Transformers Inc. also offers high quality with its Epoxy Vacuum Impregnation (E.V.I.) process. A manufacturing standard for over 20 years, it affords better mechanical strength, environmental protection and heat dissipation, while reducing the noise level of its transformers. All of Deltas dry-type transformers are environmentally friendly. Some of its products also stand out for their energy efciency, which meets the requirements of the National Resources Canada (RNCan) Ofce of Energy Efciency program, which is aimed at protecting the environment and saving energy.

FULL BREADTH OF BUSINESS OPPORTUNITIES WITH DELTA TRANSFORMERS


Including the benets of Epoxy Vacuum Impregnation Process... E.V.I. ... a standard feature with all our products!!!

GENERAL INFORMATIONS

With a wide range of applications such as:


New Installation Equipment Modernization Equipment Replacement Coordination with other Manufacturers Equipment Harmonics Mitigation Harsh Environmental conditions

A STEP AHEAD OF THE COMPETITION !


In order to compare expected theoretical outcomes, Delta Transformers Inc. is one of a few Canadian manufacturers to have developed a non-linear test bench, The Engineering Department not only ensures that the products meet customers expectations and needs, but also focuses its efforts on the continuous development of high-performance products. For more information, you can contact us by one of the following options; Our local Manufacturers Representative. refer to Delta Transformers Inc. Web Site for complete info. Our local Authorized Distributors Web Site: www.delta.xfo.com Email at: info@delta.xfo.com Our Customer Service at: Phone: Fax: 1-800-663-3582 1-877-449-9115

Delt Transformers Inc. provides the best solutions! Technical expertise available...
Project Specications Joint Calls Plant Tours Presentations Training Sessions Table Top Events On Site Surveys Engineering Services

To satisfy your customers expectations!

2 1-800-663-3582

Back to table of contents


Synonymous of Quality

ALL YOUR NEEDS FULFILLED FROM A SINGLE TRANSFORMER MANUFACTURER


GENERAL INFORMATIONS
Including the benefits of Epoxy Vacuum Impregnation process... E.V.I.
Distribution Transformers
Industrial Applications Economic and Compact Solutions Harsh Environmental Conditions Temporary or Permanent Commercial and Institutional Applications Harsh environment requirements and Stringent Industrial standards Delta Transformers Inc. General Purpose Transformers Autotransformers Epoxy Potted Transformers Mini Power Centres Commercial
C802-Series

Enviro-Guard

Non Linear Loads Transformers


Predonimant Non Linear Loads Triplen Harmonics 5th, 7th, etc. Harmonics Field Adjustable Phase Shift Computer Applications Critical problems with noise and transients Motor Controls Multi Pulses (6,12,18) Drives Soft Starters K-Rated Transformers Zero Sequence Transformers Transformers with double outputs, special phase shifting Mitigator Computer Grade Isolated Transformers Super Isolated Transformers Variable Speed Drive Transformers

Power Transformers
Medium Voltage Applications Up to15 000 kVA,35kV,150kV BIL Nominal kVA Upgrade Stand Alone Unit Substation Transformers Core and Coil Only Consult with our technical sales representative K-Rated Load Profile Harmonics Miligation M.V. Motor Control Other Manufacturers Replacement / Spare Unit PCB Replacement

3 www.delta.xfo.com

TABLE OF CONTENTS
Introduction .............................................................................................................................................................. 1 4

GENERAL INFORMATIONS

Table of contents ......................................................................................................................................................

SECTION 1 - DISTRIBUTION ...................................................................................................................................... General Purpose Transformers Copper or Aluminum Winding ............................................................................................................................... Line Current ......................................................................................................................................................... Enclosure Configuration ....................................................................................................................................... General Purpose Transformers Copper winding - CDSC, CDTC, CD3C and CD1C Series........................................................................................ Aluminum winding - CD1A and CD3A Series ........................................................................................................ Autotransformers CATC Series ......................................................................................................................................................... Commercial - C802-Series DC1, DC3, DA1 and DA3............................................................................................ Enviro-Guard - C802-Series XD3C and XK3C ....................................................................................................... Epoxy-Potted Transformers for harsh environments CESC and CETC Series ......................................................................................................................................... Mini Power Center CCSC and CCTC Series ......................................................................................................................................... SECTION 2 - NON LINEAR LOAD ............................................................................................................................... Power Quality Problems and their Solutions ............................................................................................................................... K-Rated Transformers Single and Three-Phase - VKSC, VKTC, VK3C and VK3A Series ............................................................................. Zero Sequence Filters VFTC Series.......................................................................................................................................................... Computer Application Isolated Transformers Single and Three-Phase - VCSC, VCTC, VC1C and VC3C Series............................................................................. Super Isolated Transformers Single and Three-Phase - VSSC, VSTC, VS1C and VS3C Series ............................................................................. Transformers for Variable Speed Drives CITC, CI3C, CITA and CI3A Series ......................................................................................................................... Mitigator E-Series ............................................................................................................................................... Mitigator E-Silver (technical specification) ...........................................................................................................

1-1 1-3 1-5 1-6 1-7 1-14 1-19 1-23 1-29 1-34 1-36 2-1 2-3 2-6 2-13 2-15 2-18 2-21 2-27 2-31

4 1-800-663-3582

TABLE OF CONTENTS

Back to table of contents


Synonymous of Quality

TABLE OF CONTENTS
Mitigator E-Gold (technical specification) ............................................................................................................. Mitigator E-Platinum (technical specification) ...................................................................................................... SECTION 3 - POWER .................................................................................................................................................. Power your Future ............................................................................................................................................... Advantages of Dry Type Transformers, BPC transformer replacement ................................................................... Advantages of the E.V.I. Process .......................................................................................................................... Dry-Type Transformers ....................................................................................................................................... Arrangement Layout . ........................................................................................................................................... SECTION 4 - ORION CONTROL TRANSFORMERS ...................................................................................................... Features and Benefits ......................................................................................................................................... Dimensional Drawings and Accessories .............................................................................................................. SECTION 5 - MISCELLANEOUS INFORMATIONS ...................................................................................................... Technical data sheet for Power Dry-Type Transformer ........................................................................................ Distribution Nomenclature System ....................................................................................................................... K-Rated Transformers ......................................................................................................................................... Variable Speed Drive Transformers ...................................................................................................................... Medical Equipement Transformers ...................................................................................................................... Electrostatic Shield............................................................................................................................................... Noise Level Analysis ............................................................................................................................................. Temperature Level Analysis ................................................................................................................................. Dripshields for General Purpose Transformers ...................................................................................................... 2-33

GENERAL INFORMATIONS

2-36 3-1 3-3 3-4 3-5 3-7 3-12 4-1 4-3 4-9 5-1 5-3 5-4 5-5 5-6 5-7 5-8 5-9 5-13 5-16

TABLE OF CONTENTS

Sprinkler Hoods for Commercial Series.................................................................................................................. 5-17 Wall mounting brackets ........................................................................................................................................ Anti-vibration Pads ............................................................................................................................................... Transformer Handling........................................................................................................................................... Cast Coil advantages ........................................................................................................................................... Electrical Schematics Diagrams .......................................................................................................................... Warranties reference list...................................................................................................................................... 5-18 5-19 5-20 5-21 5-24 5-25

Terms and Condition ............................................................................................................................................. 5-26

5 www.delta.xfo.com

2-2

2- CHARGES NON LINAIRES

1 800 663-3582

Back to table of contents


Synonymous of Quality

DISTRIBUTION
General Purpose Transformers Copper or Aluminum Winding General Purpose Transformers Copper winding CDSC, CDTC, CD1C and CD3C Series Aluminum winding CD1A and CD3A Series Auto-Transformers - CATC Series

SECTION 1

Line Current

Commercial - C802-Series DC1, DC3, DA1 and DA3 Series

Enviro-Guard - C802-Series XD3C and XK3C Series 1-1 www.delta.xfo.com

Epoxy-Potted Transformers for harsh environments CESC and CETC Series

Mini Power Center CCSC and CCTC Series

Back to table of contents


Synonymous of Quality

GENERAL PURPOSE TRANSFORMERS


Copper and Aluminum Winding
All Delta general purpose transformers meet the most stringent industrial standards on account of their optimal design, superior quality and ease of installation.

Features :
Copper : Aluminum : 3 - 333 KVA - single-phase 6 - 1000 KVA - three-phase 15 - 333 KVA - single-phase 30 - 600 KVA - three-phase

Quality Assurance
The Quality Assurance Department is separate from Production and Engineering in order to guarantee the independence required for maintaining strict quality control. Our quality assurance program complies with ISO standards and is available on all our transformers. Electrical tests are performed in accordance with the latest specifications, and they include: Voltage ratio Dielectric tests No load and full load losses Resistance measurement Excitation current Heat run tests Noise level Polarity

3 coil delta-wye (three-phase) or 2 coil (single-phase) E.V.I. process (epoxy vacuum impregnation) at no additional cost High-quality grain-oriented steel laminations Insulation class 220 Compact and easy-to-install enclosure Quiet operation Adequate ventilation Manufactured to ISO standards upon request

1- DISTRIBUTION

Connections
The three-phase delta-wye (three coil) connection is a standard feature on all three-phase general purpose transformers. The delta primary connection was designed to eliminate third homopolar harmonics (triplets) of a balanced load, which can be damaging to equipment connected upstream, Given an unbalanced load, the delta-wye connection will not create a noticeable voltage variation between phases, which means an ease in load combinations. Consequently, lighting and motor loads may be hooked up on a single unit without risk. The terminal layout was designed to allow simple and quick connections to the transformer. All connections are located on the front of the transformer and are easily indentified. Three-phase DELTA transformers are available in delta-wye, delta-delta, wye-wye or wye-delta configurations.

In addition to electrical tests, mechanical inspections are carried out throughout the manufacturing process in order to maintain the dependability and quality of our products.

Computer-Aided Design (CAD)


DELTA Transformers are designed and produced with a specialized software developed by DELTA engineers and technicians. This software enables us to execute the necessary mathematical operations and to design premium transformers, which will meet the requirements and specifications of industrial and institutional applications. The software also allows us to anticipate potential production problems and to find suitable solutions prior to the manufacturing process, thus avoiding numerous delays. They are also used for the analysis of test results, in order to maintain a constant level of quality.

1-3 www.delta.xfo.com

Enclosures
DELTA transformers are the most compact copper or aluminum wound product available on the market today. The transformers are available in types 1, 2, 3R, 4 and sprinkler proof enclosures. Constructed of heavy-gauge steel, treated with a phosphate conversion coating, and then painted with an electrostatically applied baked paint (ASA 61 grey), transformers will be well protected against rust and corrosion. Our standard enclosures were designed specically to save oor space, and they include features such as :

Why Epoxy rather than any other material ?


Although epoxy is popular because of its high resistance to adverse environmental conditions, it has many other less well-known and interesting characteristics, such as excellent dielectric insulation properties and lower temperature sensitivity since it can resist a temperature of 220C without undergoing any changes in property. This resin-based product is ideal as a coating agent. In addition to their superior quality, transformers with E.V.I. have a longer life. Why settle for less when you know that for the same price, you can have the DELTA E.V.I. DELTA uses an epoxy resin that has been manufactured and tested for several years by Riply Resin Engineering, a Division of EPOXYLITE CORP.

1- DISTRIBUTION

Base forklift points for easier handling Lifting eyes for easier installation (on small units) Sturdy support system available for wall-mounted units

E.V.I. Process (epoxy vacuum impregnation) at no additional cost


Delta Transformers has set a new standard of excellence for transformer manufacturers across North America by treating all DELTA Transformers with epoxy vacuum impregnation.

Benets of E.V.I.
Increased mechanical strength Improved long-term stability of core loss Improved heat dissipation Reduced noise Improved winding insulation Elimination of air bubbles
Vacuum Tank Epoxy Transformer

1-4 1-800-663-3582

Back to table of contents


Synonymous of Quality

LINE CURRENT
(Amps)

1- DISTRIBUTION

1 PHASE
Line voltage (volts) KVA
3 5 7,5 10 15 25 37,5 50 75 100 150 200 250 333

3 PHASES
Line voltage (volts) 480
6,25 10,4 15,6 20,8 31,3 52,1 78,1 104 156 208 313 417 521 694

120
25,0 41,7 62,5 83,3 125 208 313 417 625 833 1250 1667 2083 2775

240
12,5 20,8 31,3 41,7 62,5 104 156 208 313 417 625 833 1042 1388

600
5,00 8,33 12,5 16,7 25,0 41,7 62,5 83,3 125 167 250 333 417 555

2400
1,25 2,08 3,13 4,17 6,25 10,4 15,6 20,8 31,3 41,7 62,5 83,3 104 139

4160
0,72 1,20 1,80 2,40 3,61 6,01 9,01 12,0 18,0 24,0 36,1 48,1 60,1 80,0

KVA
6 10 15 30 45 50 75 112,5 150 225 300 450 500 600 750 1000 1500 2000

208
16,7 27,8 41,6 83,3 125 139 208 312 416 625 833 1249 1388 1665 2082 2776 4164 5551

240
14,4 24,1 36,1 72,2 108 120 180 271 361 541 722 1083 1203 1443 1804 2406 3608 4811

480
7,22 12,0 18,0 36,1 54,1 60,1 90,2 135 180 271 361 541 601 722 902 1203 1804 2406

600
5,77 9,62 14,4 28,9 43,3 48,1 72,2 108 144 217 289 433 481 577 722 962 1443 1925

2400
1,44 2,41 3,61 7,22 10,8 12,0 18,0 27,1 36,1 54,1 72,2 108 120 144 180 241 361 481

4160
0,83 1,39 2,08 4,16 6,25 6,94 10,4 15,6 20,8 31,2 41,6 62,5 69,4 83,3 104 139 208 278

KVA (1 phase) = Amps =

volts X amps _____________ 1 000 KVA (1 phase) X 1 000 __________________ volts

KVA (3 phases) = ________________ 1,732 X volts X amps 1 000 Amps = KVA (3 phases) X 1 000 __________________ 1,732 X volts

1-5 www.delta.xfo.com

GENERAL PURPOSE TRANSFORMERS


Enclosure Configuration CSA type 1
(ventilated)

1- DISTRIBUTION

(indoor use)

CSA type 2
(ventilated)

Drip-proof enclosure
(indoor use) Commercial General Purpose

CSA type 3R
(venitlated)

Weather proof and sprinkler proof enclosure


(indoor and outdoor use)

CSA type 4
(non ventilated)

Weather tight and sprinkler proof enclosure


(indoor and outdoor use)

1-6 1-800-663-3582

Back to table of contents


Synonymous of Quality

GENERAL PURPOSE TRANSFORMERS


Copper winding - CDSC, CDTC, CD1C and CD3C Series The Ultimate in Durability and Dependability
General Purpose Transformers (distribution)
The DELTA general purpose transformers CDSC, CDTC, CD1C and CD3C Series of copper wound are superior quality products designed for the ultimate in dependability. Designed by DELTA engineers through their specialized software, the compact DELTA CDSC, CDTC, CD1C and CD3C Series transformer are ideal for industrial, institutional or commercial applications where performance and reliability are essential. Our single-phase and three-phase CDSC, CDTC, CD1C and CD3C transformers are manufactured to exacting standards, and a quality program complying with ISO standards is available upon request. The electrolytic copper coils are wound in a circular conguration to allow a uniform circulation of air for superior cooling and efcient operation. The high quality grainoriented steel laminations ensure reliable noise levels. The CDSC, CDTC, CD1C and CD3C Series transformers employ the E.V.I. process which ensures structural mechanical strength, a better heat dissipation, improved resistance to humid, salty and corrosive environments, improved dielectric properties and lower noise levels.

Features :
3 - 333 KVA - single-phase 6 - 1000 KVA - three-phase Copper winding (standard 3 coil delta-wye 3 phases) E.V.I. process (epoxy vacuum impregnation) at no additional cost High-quality grain-oriented steel laminations Insulation class 220 Compact and easy-to-install enclosure Quiet operation and adequate ventilation Manufactured to ISO standards upon request

1- DISTRIBUTION

LIFETIMEoriginal manufacturer warranty WARRANTY Consult


1-7 www.delta.xfo.com

GENERAL PURPOSE TRANSFORMERS


Single-phase - Copper winding - CDSC Series
Copper Series CDSC, Single-phase, Type 1, Primary 600 V or 480 V, Secondary 120 / 240 V, 150 C
kVA Mounting Taps Height 3 5 7.5 W/F W/F W/F % 2 x 4.5 2 x 4.5 2 x 4.5
F = Floor mount 3 - 7.5kVA 1 x FCAN, 1 x FCBN For the electical schematics diagrams see Section 5, page 5-24

Dimensions Width mm 457 457 533 po 12 12 15 mm 305 305 381 po 9 9 11 Depth mm 229 229 279 lb 71 82 110 po 18 18 21

Weight kg 32 37 50

Noise Level dB 45 45 45

1- DISTRIBUTION

(1) W = Wall mount (2) Taps : SINGLE-PHASE :

(3) No correspondence between approved type 2, 3R and 4.enclosure All weights and dimensions are approximate and subject to change without notice.

Copper Series CDSC, single-phase, Type 3R, Primary 600 V or 480 V, Secondary 120 / 240 V, 150 C
kVA Mounting Taps Height 3 5 7.5 W/F W/F W/F % 2 x 4.5 2 x 4.5 2 x 4.5
3 - 10 kVA

Dimensions Width mm 635 635 635


1 x FCAN, 1 x FCBN

Weight Depth po 13 13 13 mm 324 324 324 lb 92 103 121 kg 42 47 55

Noise Level dB 45 45 45

po 25 25 25

po 15 15 15

mm 381 381 381

(1) W = Wall mount (2) Taps : SINGLE-PHASE :

F = Floor mount

(3) No correspondence between approved enclosure type 1, 2 and 4. All weights and dimensions are approximate and subject to change without notice.

For the electical schematics diagrams see Section 5, page 5-24

1-8 1-800-663-3582

Back to table of contents


Synonymous of Quality

GENERAL PURPOSE TRANSFORMERS


Three-phase - Copper winding - CDTC Series
Copper Series CDTC, Three-phase, Type 1, Primary 600 V or 480 V, Secondary 208Y / 120 V, 150 C
kVA Mounting Taps Height 6 10 W/F W/F % 2 x 4.5 2 x 4.5
6 - 10 kVA

Dimensions Width mm 483 483


1 x FCAN, 1 x FCBN

Weight Depth po 10 10 mm 254 254 lb 112 130 kg 51 59

Noise Level dB 40 45

po 19 19

po 18 18

mm 457 457

(1) W = Wall mount (2) Taps : THREE-PHASE :

F = Floor mount

1- DISTRIBUTION

(3) No correspondence between approved enclosure type 2, 3R and 4. All weights and dimensions are approximate and subject to change without notice.

For the electical schematics diagrams see Section 5, page 5-24

Copper Series CDTC, Three-phase, Type 3R, Primary 600 V or 480 V, Secondary 208Y / 120 V, 150 C
kVA Mounting Taps Height 6 10 W/F W/F % 2 x 4.5 2 x 4.5
6 - 10 kVA

Dimensions Width mm 635 635


1 x FCAN, 1 x FCBN

Weight Depth po 13 13 mm 324 324 lb 141 158 kg 64 72

Noise Level dB 40 45

po 25 25

po 21 21

mm 533 533

(1) W = Wall mount (2) Taps : THREE-PHASE :

F = Floor mount

(3) No correspondence between approved enclosure type 1, 2 and 4. All weights and dimensions are approximate and subject to change without notice.

For the electical schematics diagrams see Section 5, page 5-24

1-9 www.delta.xfo.com

GENERAL PURPOSE TRANSFORMERS, C802.2


Single-phase - Copper winding - CD1C Series

Copper Series CD1C, Single-phase, Type 1, Primary 600 V or 480 V, Secondary 120 / 240 V, 150 C
kVA Mounting Taps Height 15 25 37.5 50 75 100 150 200 250 W/F W/F W/F F F F F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po 23 23 29 29 37 37 46 54 54 mm 584 584 737 737 940 940 1168 1372 1372 po 17 17 20 20 22 22 26 31 31 Dimensions Width mm 432 432 508 508 559 559 660 787 787 po 12 12 14 14 18 18 21 23 23 Depth mm 305 305 356 356 457 457 533 584 584 lb 165 196 301 334 480 614 803 1087 1269 kg 75 89 137 152 218 279 365 494 577 dB 50 50 50 50 55 55 60 65 65 Weight Noise Level

1- DISTRIBUTION

(1) W = Wall mount F = Floor mount (2) Taps : SINGLE-PHASE : 15 - 250 kVA 2 x FCAN, 2 x FCBN THREE-PHASE : 15 - 250 kVA 2 x FCAN, 2 x FCBN (3) No correspondence between approved enclosure type 2, 3R and 4. All weights and dimensions are approximate and subject to change without notice.

For the electical schematics diagrams see Section 5, page 5-24

Copper Series CD1C, Single-phase, Type 1, Primary 600 V or 480 V, Secondary 120 / 240 V, 150 C
kVA Mounting Taps Height 15 25 37.5 50 75 100 150 200 250 W/F W/F W/F F F F F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po 30 30 33 33 33 47 51 51 58 mm 762 762 838 838 838 1194 1295 1295 1473 po 18 18 21 21 21 25 28 28 32 Dimensions Width mm 457 457 533 533 533 616 718 718 820 po 14 14 16 16 16 23 27 27 30 Depth mm 349 349 400 400 400 583 685 685 761 lb 185 227 321 352 453 631 805 1043 1342 kg 84 103 146 160 206 287 366 474 610 dB 50 50 50 50 55 55 60 65 65 Weight Noise Level

(1) W = Wall mount F = Floor mount (2) Taps : SINGLE-PHASE : 15 - 250 kVA 2 x FCAN, 2 x FCBN THREE-PHASE : 15 - 250 kVA 2 x FCAN, 2 x FCBN (3) No correspondence between approved enclosure type 2, 3R and 4. All weights and dimensions are approximate and subject to change without notice.

For the electical schematics diagrams see Section 5, page 5-24

1-10 1-800-663-3582

Back to table of contents


Synonymous of Quality

GENERAL PURPOSE TRANSFORMERS, C802.2


Three-phase - Copper winding - CD3C Series

Copper Series CD3C, Three-phase, Type 1, Primary 600 V or 480 V, Secondary 208Y /120 V, 150 C
kVA Mounting Taps Height 15 30 45 50 75 112.5 150 225 300 W/F W/F W/F W/F W/F F F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po 21 27 28 28 28 37 37 46 46 mm 533 686 711 711 711 940 940 1168 1168 po 20 23 29 29 29 35 35 38 44 Dimensions Width mm 508 584 737 737 737 889 889 965 1118 po 12 13 14 14 14 18 18 21 23 Depth mm 305 330 356 356 356 457 457 533 584 lb 174 264 341 387 506 710 849 1214 1580 kg 79 120 155 176 230 323 386 552 718 dB 45 45 45 45 50 50 50 55 55 Weight Noise Level

1- DISTRIBUTION

(1) W = Wall mount F = Floor mount (2) Taps : SINGLE-PHASE : 15 - 250 kVA 2 x FCAN, 2 x FCBN THREE-PHASE : 15 - 250 kVA 2 x FCAN, 2 x FCBN (3) No correspondence between approved enclosure type 2, 3R and 4. All weights and dimensions are approximate and subject to change without notice.

For the electical schematics diagrams see Section 5, page 5-24

Copper Series CD3C, Three-phase, Type 3R, Primary 600 V or 480 V, Secondary 208Y /120 V, 150 C
kVA Mounting Taps Height 15 30 45 50 75 112.5 150 225 300 W/F W/F W/F W/F W/F F F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po 25 30 30 33 33 47 47 51 58 mm 635 762 762 838 838 1194 1194 1295 1473 po 21 25 25 29 29 33 33 40 46 Dimensions Width mm 533 635 635 737 737 845 845 1023 1176 po 13 14 14 16 16 23 23 27 30 Depth mm 324 349 349 400 400 583 583 685 761 lb 194 277 326 381 513 717 854 1188 1663 kg 88 126 148 173 233 326 388 540 756 dB 45 45 45 45 50 50 50 55 55 Weight Noise Level

(1) W = Wall mount F = Floor mount (2) Taps : SINGLE-PHASE : 15 - 250 kVA 2 x FCAN, 2 x FCBN THREE-PHASE : 15 - 250 kVA 2 x FCAN, 2 x FCBN (3) No correspondence between approved enclosure type 1, 2 and 4. All weights and dimensions are approximate and subject to change without notice.

For the electical schematics diagrams see Section 5, page 5-24

1-11 www.delta.xfo.com

GENERAL PURPOSE TRANSFORMERS, C802.2


Three-phase - Copper winding - CD3C Series
Copper Series CD3C, Three-phase, Type 1, Primary 600 V or 480 V, Secondary 208Y / 120 V, 115 C
kVA Mounting Taps Height 15 30 45 50 75 112.5 150 225 300 W/F W/F W/F W/F F F F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po 27 27 28 28 30 37 37 44 44 mm 686 686 711 711 762 940 940 1168 1168 po 23 23 29 29 30 35 35 44 44 Dimensions Width mm 584 584 737 737 762 889 889 1118 1118 po 13 13 14 14 14 18 18 23 23 Depth mm 330 330 356 356 356 457 457 584 584 lb 229 290 398 482 576 812 1005 1520 1811 kg 104 132 181 219 262 369 457 691 823 dB 45 45 45 45 50 50 50 55 55 Weight Noise Level

1- DISTRIBUTION

(1) W = Wall mount F = Floor mount (2) Taps : SINGLE-PHASE : 15 - 250 kVA 2 x FCAN, 2 x FCBN THREE-PHASE : 15 - 250 kVA 2 x FCAN, 2 x FCBN (3) No correspondence between approved enclosure type 2, 3R and 4. All weights and dimensions are approximate and subject to change without notice.

For the electical schematics diagrams see Section 5, page 5-24

Copper Series CD3C, Three-phase, Type 3R, Primary 600 V or 480 V, Secondary 208Y / 120 V, 115 C
kVA Mounting Taps Height 15 30 45 50 75 112.5 150 225 300 W/F W/F W/F W/F F F F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po mm po Dimensions Width Depth mm po mm Consult our Customer Service Consult our Customer Service Consult our Customer Service Consult our Customer Service Consult our Customer Service Consult our Customer Service Consult our Customer Service Consult our Customer Service Consult our Customer Service lb Weight kg Noise Level dB

(1) W = Wall mount F = Floor mount (2) Taps : SINGLE-PHASE : 15 - 250 kVA 2 x FCAN, 2 x FCBN THREE-PHASE : 15 - 250 kVA 2 x FCAN, 2 x FCBN (3) No correspondence between approved enclosure type 1, 2 and 4. All weights and dimensions are approximate and subject to change without notice.

For the electical schematics diagrams see Section 5, page 5-24

1-12 1-800-663-3582

Back to table of contents


Synonymous of Quality

GENERAL PURPOSE TRANSFORMERS, C802.2


Three-phase - Copper winding - CD3C Series
Copper Series CD3C, Three-phase, Type 1, Primary 600 V or 480 V, Secondary 208Y / 120 V, 80 C
kVA Mounting Taps Height 15 30 45 50 75 112.5 150 225 300 W/F W/F W/F W/F F F F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po 27 28 28 28 37 37 46 46 58 mm 686 711 711 711 940 940 1168 1168 1473 po 23 29 29 29 35 35 38 44 50 Dimensions Width mm 584 737 737 737 889 889 965 1118 1270 po 13 14 14 14 18 18 21 23 26 Depth mm 330 356 356 356 457 457 533 584 660 lb 264 341 506 506 711 1005 1214 1811 2526 kg 120 155 230 230 323 457 552 823 1148 dB 45 45 45 45 50 50 50 55 55 Weight Noise Level

1- DISTRIBUTION

(1) W = Wall mount F = Floor mount (2) Taps : SINGLE-PHASE : 15 - 250 kVA 2 x FCAN, 2 x FCBN THREE-PHASE : 15 - 250 kVA 2 x FCAN, 2 x FCBN (3) No correspondence between approved enclosure type 2, 3R and 4. All weights and dimensions are approximate and subject to change without notice.

For the electical schematics diagrams see Section 5, page 5-24

Copper Series CD3C, Three-phase, Type 3R, Primary 600 V or 480 V, Secondary 208Y / 120 V, 80 C
kVA Mounting Taps Height 15 30 45 50 75 112.5 150 225 300 W/F W/F W/F W/F F F F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po mm po Dimensions Width Depth mm po mm Consult our Customer Service Consult our Customer Service Consult our Customer Service Consult our Customer Service Consult our Customer Service Consult our Customer Service Consult our Customer Service Consult our Customer Service Consult our Customer Service lb Weight kg Noise Level dB

(1) W = Wall mount F = Floor mount (2) Taps : SINGLE-PHASE : 15 - 250 kVA 2 x FCAN, 2 x FCBN THREE-PHASE : 15 - 250 kVA 2 x FCAN, 2 x FCBN (3) No correspondence between approved enclosure type 1, 2 and 4. All weights and dimensions are approximate and subject to change without notice.

For the electical schematics diagrams see Section 5, page 5-24

1-13 www.delta.xfo.com

GENERAL PURPOSE TRANSFORMERS, C802.2


Aluminum Winding - CD1A and CD3A Series The Cost-Effective Alternative
Delta general purpose transformers CDSA, CDTA, CD1A and CD3A. Series of aluminum wound transformers offer an economical alternative to copper wound transformers. Designed by Delta engineers through their specialized software, the compact Delta CDSA, CDTA, CD1A and CD3A Series aluminum transformer design require virtually the same floor space as comparable copper units and substantially less space than other manufacturers aluminum products. Our single-phase and three-phase CDSA, CDTA, CD1A and CD3A series transformers are manufactured to exacting standards, and our quality assurance program complies with ISO standards and is available upon request. The electrolytic coils are wound in a circular configuration to allow a uniform circulation of air for superior cooling and efficient operation. The high quality grain-oriented steel laminations ensure reliable sound levels. The CDSA, CDTA, CD1A and CD3A series transformers employ the E.V.I. process which ensures structural mechanical strength, a better heat dissipation, improved resistance to humid, salty and corrosive environments, improved dielectric properties, and lower noise levels.

Features :
15 - 333 KVA single-phase; 15 - 600 KVA three-phase Aluminum winding (standard 3 coils delta-wye three-phase) E.V.I. process (epoxy vacuum impregnation) at no additional cost High-quality grain-oriented steel laminations Insulation class 220 Compact and easy-to-install enclosure Quiet operation and adequate ventilation Economical alternative Manufactured to ISO standards upon request

1- DISTRIBUTION

LIFETIME WARRANTY
1-14 1-800-663-3582

Consult orignal manufacturer warranty

Back to table of contents


Synonymous of Quality

GENERAL PURPOSE TRANSFORMERS, C802.2


Single-phase - Aluminum winding - CD1A Series
Aluminum Series CD1A, Single-phase, Type 1, Primary 600 V or 480 V, Secondary 120 / 240 V, 150 C
kVA Mounting Taps Height 15 25 37.5 50 75 100 150 200 250 W/F W/F W/F F F F F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po 23 29 29 29 37 46 46 54 54 mm 584 737 737 737 940 1168 1168 1372 1372 po 17 20 20 20 22 26 26 31 31 Dimensions Width mm 432 508 508 508 559 660 660 787 787 po 12 14 14 14 18 21 21 23 23 Depth mm 305 356 356 356 457 533 533 584 584 lb 150 211 266 337 471 612 812 1036 1192 kg 68 96 121 153 214 278 369 471 542 dB 50 50 50 50 55 55 60 65 65 Weight Noise Level

1- DISTRIBUTION

(1) W = Wall mount F = Floor mount (2) Taps : SINGLE-PHASE : 15 - 333 kVA 2 x FCAN, 2 x FCBN THREE-PHASE : 15 - 1 000 kVA 2 x FCAN, 2 x FCBN (3) No correspondence between approved enclosure type 2, 3R and 4. All weights and dimensions are approximate and subject to change without notice.

For the electical schematics diagrams see Section 5, page 5-24

Aluminum Series CD1A, Single-phase, Type 3R, Primary 600 V or 480 V, Secondary 120 / 240 V, 150 C
kVA Mounting Taps Height 15 25 37.5 50 75 100 150 200 250 W/F W/F W/F F F F F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po 30 33 33 33 47 47 51 58 58 mm 762 838 838 838 1194 1194 1295 1473 1473 po 18 21 21 21 24 24 28 32 32 Dimensions Width mm 457 533 533 533 616 616 718 820 820 po 14 16 16 16 23 23 27 30 30 Depth mm 349 400 400 400 583 583 685 761 761 lb 169 227 277 350 486 572 814 1109 1265 kg 77 103 126 159 221 260 370 504 575 dB 50 50 50 50 55 55 60 65 65 Weight Noise Level

(1) W = Wall mount F = Floor mount (2) Taps : SINGLE-PHASE : 15 - 333 kVA 2 x FCAN, 2 x FCBN THREE-PHASE : 15 - 1 000 kVA 2 x FCAN, 2 x FCBN (3) No correspondence between approved enclosure type 1, 2 and 4. All weights and dimensions are approximate and subject to change without notice.

For the electical schematics diagrams see Section 5, page 5-24

1-15 www.delta.xfo.com

GENERAL PURPOSE TRANSFORMERS, C802.2


Three-phase - Aluminum winding- CD3A Series
Aluminum Series CD3A, Three-phase, Type 1, Primary 600 V or 480 V, Secondary 208Y / 120 V, 150 C
kVA Mounting Taps Height 15 30 45 50 75 112.5 150 225 300 W/F W/F W/F W/F W/F F F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po 21 27 28 28 30 37 37 46 46 mm 533 686 711 711 762 940 940 1168 1168 po 20 23 29 29 30 35 35 44 44 Dimensions Width mm 508 584 737 737 762 889 889 1118 1118 po 12 13 14 14 14 18 18 23 23 Depth mm 305 330 356 356 356 457 457 584 584 lb 172 249 334 356 482 671 794 1175 1456 kg 78 113 152 162 219 305 361 534 662 dB 45 45 45 45 50 50 50 55 55 Weight Noise Level

1- DISTRIBUTION

(1) W = Wall mount F = Floor mount (2) Taps : SINGLE-PHASE : 15 - 333 kVA 2 x FCAN, 2 x FCBN THREE-PHASE : 15 - 1 000 kVA 2 x FCAN, 2 x FCBN (3) No correspondence between approved enclosure type 2, 3R and 4. All weights and dimensions are approximate and subject to change without notice.

For the electical schematics diagrams see Section 5, page 5-24

Aluminum Series CD3A, Three-phase, Type 3R, Primary 600 V or 480 V, Secondary 208Y / 120 V, 150 C
kVA Mounting Taps Height 15 30 45 50 75 112.5 150 225 300 W/F W/F W/F W/F W/F F F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po 30 30 33 33 47 47 51 51 58 mm 762 762 838 838 1194 1194 1295 1295 1473 po 25 25 29 29 33 33 40 40 46 Dimensions Width mm 635 635 737 737 845 845 1023 1023 1167 po 14 14 16 16 23 23 27 27 30 Depth mm 349 349 400 400 583 583 685 685 761 lb 207 317 385 365 623 746 1036 1058 1547 kg 94 144 175 166 283 339 471 481 703 dB 45 45 45 45 50 50 50 55 55 Weight Noise Level

(1) W = Wall mount F = Floor mount (2) Taps : SINGLE-PHASE : 15 - 333 kVA 2 x FCAN, 2 x FCBN THREE-PHASE : 15 - 1 000 kVA 2 x FCAN, 2 x FCBN (3) No correspondence between approved enclosure type 1, 2, and 4. All weights and dimensions are approximate and subject to change without notice.

For the electical schematics diagrams see Section 5, page 5-24

1-16 1-800-663-3582

Back to table of contents


Synonymous of Quality

GENERAL PURPOSE TRANSFORMERS, C802.2


Three-phase - Aluminum winding - CD3A Series
Aluminum Series CD3A, Three-phase, Type 1, Primary 600 V or 480 V, Secondary 208Y / 120 V, 115 C
kVA Mounting Taps Height 15 30 45 50 75 112.5 150 225 300 W/F W/F W/F W/F F F F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po 27 28 28 30 37 37 46 46 46 mm 686 711 711 762 940 940 1168 1168 1168 po 23 29 29 30 35 35 38 44 44 Dimensions Width mm 586 737 737 762 889 889 965 1118 1118 po 13 14 14 14 18 18 21 23 23 Depth mm 330 356 356 356 457 457 533 584 584 lb 216 297 370 436 598 763 981 1384 1685 kg 98 135 168 198 272 347 446 629 766 dB 45 45 45 45 50 50 50 55 55 Weight Noise Level

1- DISTRIBUTION

(1) W = Wall mount F = Floor mount (2) Taps : SINGLE-PHASE : 15 - 333 kVA 2 x FCAN, 2 x FCBN THREE-PHASE : 15 - 1 000 kVA 2 x FCAN, 2 x FCBN (3) No correspondense between approved enclosure type 2, 3R and 4. All weights and dimensions are approximate and subject to change without notiice.

For the electical schematics diagrams see Section 5, page 5-24

Aluminum Series CD3A, Three-phase, Type 3R, Primary 600 V or 480 V, Secondary 208Y / 120 V, 115 C
kVA Mounting Taps Height 15 30 45 50 75 112.5 150 225 300 W/F W/F W/F W/F F F F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po mm po Dimensions Width Depth mm po mm Consult our Customer Service Consult our Customer Service Consult our Customer Service Consult our Customer Service Consult our Customer Service Consult our Customer Service Consult our Customer Service Consult our Customer Service Consult our Customer Service lb Weight kg Noise Level dB

(1) W = Wall mount F = Floor mount (2) Taps : SINGLE-PHASE : 15 - 333 kVA 2 x FCAN, 2 x FCBN THREE-PHASE : 15 - 1 000 kVA 2 x FCAN, 2 x FCBN (3) No correspondense between approved enclosure type 1, 2, and 4. All weights and dimensions are approximate and subject to change without notiice.

For the electical schematics diagrams see Section 5, page 5-24

1-17 www.delta.xfo.com

GENERAL PURPOSE TRANSFORMERS, C802.2


Three-phase - Aluminum winding - CD3A Series
Aluminum Series CD3A, Three-phase, Type 1, Primary 600 V or 480 V, Secondary 208Y /120 V, 80 C
kVA Mounting Taps Height 15 30 45 50 75 112.5 150 225 300 W/F W/F W/F W/F F F F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po 27 28 30 30 37 46 46 46 58 mm 686 711 762 762 940 1168 1168 1168 1473 po 23 29 30 30 35 38 44 44 50 Dimensions Width mm 584 737 762 762 889 965 1118 1118 1270 po 13 14 14 14 18 21 23 23 26 Depth mm 330 356 356 356 457 533 584 584 660 lb 249 334 482 482 671 981 1175 1685 2444 kg 113 152 219 219 305 446 534 766 1111 dB 45 45 45 45 50 50 50 55 55 Weight Noise Level

1- DISTRIBUTION

(1) W = Wall mount F = Floor mount (2) Taps : SINGLE-PHASE : 15 - 333 kVA 2 x FCAN, 2 x FCBN THREE-PHASE : 15 - 1 000 kVA 2 x FCAN, 2 x FCBN (3) No correspondense between approved enclosure type 2, 3R and 4. All weights and dimensions are approximate and subject to change without notiice.

For the electical schematics diagrams see Section 5, page 5-24

Aluminum Series CD3A, Three-phase, Type 3R, Primary 600 V or 480 V, Secondary 208Y /120 V, 80 C
kVA Mounting Taps Height 15 30 45 50 75 112.5 150 225 300 W/F W/F W/F W/F F F F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po mm po Dimensions Width Depth mm po mm Consult our Customer Service Consult our Customer Service Consult our Customer Service Consult our Customer Service Consult our Customer Service Consult our Customer Service Consult our Customer Service Consult our Customer Service Consult our Customer Service lb Weight kg Noise Level dB

(1) W = Wall mount F = Floor mount (2) Taps : SINGLE-PHASE : 15 - 333 kVA 2 x FCAN, 2 x FCBN THREE-PHASE : 15 - 1 000 kVA 2 x FCAN, 2 x FCBN (3) No correspondense between approved enclosure type 1, 2 and 4. All weights and dimensions are approximate and subject to change without notiice.

For the electical schematics diagrams see Section 5, page 5-24

1-18 1-800-663-3582

Back to table of contents


Synonymous of Quality

AUTO-TRANSFORMERS
CATC Series The Economical Solution
The Auto-transformer is a transformer with a common primary and secondary winding. Therefore, the secondary winding of auto-transformers is not electrically isolated from the primary. They are usually lighter and less bulky than their isolated counterpart (particularly if the transformation ratio is less than 2:1), and they are therefore, less costly.

Features :
600 V - 480 V 10 to 1000 KVA 600 V - 240 V 10 to 1000 KVA 3 coils, three-phases Isulation class 220 E.V.I. process (epoxy vacuum impregnation) at no additional cost High-quality steel laminations Compact enclosure Silent operation

1- DISTRIBUTION

CAD Computer-aided Design


Copper winding Compact design High efficiency Enclosure 2, 3R, 4 and sprinkler proof

Options and Accessories :


Special paint (other than ASA61 grey) 115C and 80C temperature rise Operating frequencies other than 60 Hz Special voltage (for domestic or export applications) Type 2, 3R, 4 and sprinklerproof enclosure Quality assurance program to ISO available upon request

1-19 www.delta.xfo.com

AUTO-TRANSFORMERS
Three-phase - CATC Series
Copper Series CATC, Three-phase, Type 1, Primary 600Y / 347 V, Secondary 480Y / 277 V, 150 C
kVA Mounting Taps Height 10 15 30 45 75 112.5 150 225 300 450 500 600 750 1000 W/F W/F W/F W/F W/F W/F W/F W/F W/F F F F F F % 2 x 4.5 2 x 4.5 2 x 4.5 2 x 4.5 2 x 4.5 2 x 4.5 2 x 4.5 2 x 4.5 2 x 4.5 2 x 4.5 2 x 4.5 2 x 4.5 2 x 4.5 2 x 4.5 po 19 19 19 21 27 27 27 28 28 37 37 46 46 58 mm 483 483 483 533 686 686 686 711 711 940 940 1168 1168 1473 po 18 18 18 20 23 23 23 29 29 35 35 38 38 50 Dimensions Width mm 457 457 457 508 584 584 584 737 737 889 889 965 965 1270 po 10 10 10 12 13 13 13 14 14 18 18 21 21 26 Depth mm 254 254 254 305 330 330 330 356 356 457 457 533 533 660 lb 106 108 128 163 218 267 304 355 503 772 859 1054 1237 1973 kg 48 49 58 74 99 121 138 161 228 350 390 478 561 895 dB 45 45 45 45 50 50 50 55 55 60 60 62 64 64 Weight Noise Level

1- DISTRIBUTION

(1) W = Wall mount (2) Taps : THREE-PHASE :

F = Floor mount 10 - 1000 kVA 1 x FCAN, 1 x FCBN For the electical schematics diagrams see Section 5, page 5-24

(3) No correspondense between approved enclosure type 2, 3R and 4. All weights and dimensions are approximate and subject to change without notiice.

1-20 1-800-663-3582

Back to table of contents


Synonymous of Quality

AUTO-TRANSFORMERS
Three-phase - CATC Series
Copper Series CATC, Type 1,Three-phase, Primary 600 Y / 347V, Secondary 380Y / 220 V, 150 C
kVA Mounting Taps Height 10 15 30 45 75 112.5 150 225 300 450 500 600 750 1000 W/F W/F W/F W/F W/F W/F W/F F F % 2 x 4.5 2 x 4.5 2 x 4.5 2 x 4.5 2 x 4.5 2 x 4.5 2 x 4.5 2 x 4.5 2 x 4.5 po 19 19 21 27 27 28 28 37 37 mm 483 483 533 686 686 711 711 940 940 Dimensions Width Depth po mm po mm 18 457 10 254 18 457 10 254 20 508 12 305 23 584 13 330 23 584 13 330 29 737 14 356 29 737 14 356 35 889 18 457 35 889 18 457 Consult our Customer Service Consult our Customer Service Consult our Customer Service Consult our Customer Service Consult our Customer Service lb 110 115 165 223 273 390 485 697 730 Weight kg 50 52 75 101 124 177 220 316 331 Noise Level dB 45 45 45 45 50 50 50 55 55

1- DISTRIBUTION

1) W = Wall mount 2) Taps :

F = Floor mount

THREE-PHASE : 10 - 300 kVA 1 x FCAN, 1 x FCBN (3) No correspondense between approved enclosure type 2, 3R and 4. All weights and dimensions are approximate and subject to change without notiice.

For the electical schematics diagrams see Section 5, page 5-24

1-21 www.delta.xfo.com

AUTO-TRANSFORMERS
Three-phase - CATC Series

Copper Series CATC, Type 1, Three-phase, Primary 600 Y / 347V, Secondary 240Y / 139 V, 150 C
kVA Mounting Taps Height 10 15 30 45 75 112.5 150 225 300 450 500 600 750 1000 W/F W/F W/F W/F W/F W/F F F F % 2 x 4.5 2 x 4.5 2 x 4.5 2 x 4.5 2 x 4.5 2 x 4.5 2 x 4.5 2 x 4.5 2 x 4.5 po 19 21 27 27 28 28 37 37 46 mm 483 533 686 686 711 711 940 940 1168 Dimensions Width Depth po mm po mm 18 457 10 254 20 508 12 305 23 584 13 330 23 584 13 330 29 737 14 356 29 737 14 356 35 889 18 457 35 889 18 457 38 965 21 533 Consult our Customer Service Consult our Customer Service Consult our Customer Service Consult our Customer Service Consult our Customer Service Weight lb 115 165 220 267 355 494 701 851 1301 kg 52 75 100 121 161 224 318 386 590 Noise Level dB 45 45 45 45 50 50 50 55 55

1- DISTRIBUTION

(1) W = Wall mount (2) Taps : THREE-PHASE :

F = Floor mount

10 - 300 kVA

1 x FCAN, 1 x FCBN For the electical schematics diagrams see Section 5, page 5-24

(3) No correspondense between approved enclosure type 2, 3R and 4. All weights and dimensions are approximate and subject to change without notiice.

1-22 1-800-663-3582

Back to table of contents


Synonymous of Quality

COMMERCIAL - C802-SERIES
Copper or Aluminum - DC1, DC3, DA1 and DA3 Series
Delta Transformers Inc. presents the Commercial C802Series of Distribution Transformers. Building on our years of experience in engineering and designing of transformers we have created a product that is guaranteed to provide high efciency in an economical package. These units are designed to the latest Industry Standards and are CSA Certied. Transformers need to qualify to High Efciency Values for Dry-Type Transformers as per CSA C802.2-06. These attributes coupled with its efciency in design make this product attractive to stock and economically placed to meet your budget. The transformers are manufactured in a state of the art facility by associates who are committed to quality and rst class workmanship. The warranty provided with these products offers our guarantee against defects and workmanship for up to 12 months after receipt of the product. All our transformers are manufactured utilizing the E.V.I. process (Epoxy Vacuum Impregnated) ensuring: Structural and mechanical strength Superior heat dissipation Improved resistance to environments containing salt humidity and corrosive agents Improved dielectric properties and lower noise levels

Features
The available transformer sizes are: - Single-phase: 25, 37,5, 50, 75, 100, 150 and 200 kVA. - Three-phase: 15, 30, 45, 75, 112,5 and 150 kVA. The primary windings shall be 600 volts, three-phase, delta connected or 600 volts, single-phase, c/w four full capacity 2,5 % adjustement taps, 2 below (FCBN) and 2 above (FCAN) the rated voltage. Secondary winding shall be 208Y/120 volts (threephase), wye connected, with an angular 30 displacement, lagging with respect to the primary winding or 120/240 volts, single-phase. All winding conductors are of copper or aluminum. Temperature rise at full load shall not exceed 150C , with class 220 insulation system. High efciency as per CSA C802.2-06. Standard impedance at 60 Hz. Standard audible sound level. Windings are wound with secondary nearest to the core. The core is made of high grade silicon steel laminations. The impregnation process for the core and coil assembly includes a period under vacuum, followed by pressure impregnation using epoxy resin (E.V.I. Process), for 220 isolation class. The core and coils are isolated from the enclosure by anti-vibration pads. The transformers enclosure is fabricated from sheet metal and comes complete with drip hood construction making it suitable for sprinklered environments (threephase). The coating of the enclosure is ASA 61 Grey and suitable for indoor use.

1- DISTRIBUTION

1-23 www.delta.xfo.com

COMMERCIAL - C802-SERIES
Single-phase - Copper - DC1 Series

Copper Series DC1, Single-phase, Primary 600 V or 480 V, Secondary 120 / 240 V, 130 C
kVA Mounting Taps Height 15 W/F % 4 x 2.5 po 18 mm 457 po 21 Dimensions Width mm 533 Depth Type 1 po mm 17 432 Depth Type 2 po mm 22 550 Weight Noise Level

lb 200

kg 440

dB 50

1- DISTRIBUTION

(1) W = Wall mount F = Floor mount (2) Taps : SINGLE-PHASE : 15 kVA 2 x FCAN, 2 x FCBN THREE-PHASE : 15 kVA 2 x FCAN, 2 x FCBN (3) The dimensions are applicable for type 1 enclosure and type 2 All weigths and dimensions are approximate and subject to change without notice.

For the electical schematics diagrams see Section 5, page 5-24

Copper Series DC1, Single-phase, Primary 600 V, Secondary 120 / 240 V, 150 C
kVA Mounting Taps Height % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po 24 26 26 29 31 46 46 mm 610 660 660 737 787 1168 1168 po 22 24 24 26 31 33 33 Dimensions Width mm 559 610 610 660 787 838 838 Depth Type 1 po mm 17 432 21 533 21 533 21 533 23 584 27 686 27 686 Depth Type 2 po mm 22 559 26 660 26 660 26 660 27 673 27 775 27 775 Weight Noise Level

25 37.5 50 75 100 150 200

W/F W/F W/F F F F F

lb 275 360 395 535 609 765 1013

kg 605 792 869 1177 1340 1683 2229

dB 50 50 50 55 55 60 65

(1) W = Wall mount (2) Taps : SINGLE-PHASE : THREE-PHASE :

F = Floor mount

25 - 200 2 x FCAN, 2 x FCBN kVA 15 - 300 2 x FCAN, 2 x FCBN kVA (3) The dimensions are applicable for type 1 enclosure and type 2 All weigths and dimensions are approximate and subject to change without notice.

For the electical schematics diagrams see Section 5, page 5-24

1-24 1-800-663-3582

Back to table of contents


Synonymous of Quality

COMMERCIAL - C802-SERIES
Three-phase - Copper - DC3 Series

Copper Series DC3, Three-phase, Primary 600 V or 480 V, Secondary 208Y / 120 V, 130 C
kVA Mounting Taps Height 15 30 45 W/F W/F W/F % 4 x 2.5 4 x 2.5 4 x 2.5
F = Floor mount

Dimensions Width po 19 21 22 mm 483 533 559 Depth Type 1 po mm 13 330 17 432 17 432 Depth Type 2 po mm 18 457 22 559 22 559

Weight

Noise Level

po 16 18 24

mm 406 457 610

lb 175 295 385

kg 385 649 847

dB 45 45 45

1- DISTRIBUTION

15 - 45 2 x FCAN, 2 x FCBN kVA THREE-PHASE : 15 - 45 2 x FCAN, 2 x FCBN kVA (3) The dimensions are applicable for type 1 enclosure and type 2 All weigths and dimensions are approximate and subject to change without notice.

(1) W = Wall Mount (2) Taps : SINGLE-PHASE :

For the electical schematics diagrams see Section 5, page 5-24

Copper Series DC3, Three-phase, Primary 600 V or 480 V, Secondary 208Y / 120 V, 150 C
kVA Mounting Taps Height 75 112.5 150 225 300 W/F F F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po 26 29 31 41 46 mm 660 737 787 1041 1168 po 24 26 31 31 33 Dimensions Width mm 610 660 787 787 838 Depth Type 1 po mm 21 533 21 533 23 584 24 610 27 686 Depth Type 2 po mm 26 660 26 660 27 673 28 699 31 775 Weight Noise Level

lb 530 655 855 1500 1800

kg 1166 1441 1881 3300 3960

dB 50 50 50 55 55

(1) W = Wall Mount (2) Taps : SINGLE-PHASE :

F = Floor mount

75 - 200 2 x FCAN, 2 x FCBN kVA THREE-PHASE : 75 - 300 2 x FCAN, 2 x FCBN kVA (3) The dimensions are applicable for type 1 enclosure and type 2 All weigths and dimensions are approximate and subject to change without notice.

For the electical schematics diagrams see Section 5, page 5-24

1-25 www.delta.xfo.com

COMMERCIAL - C802-SERIES
Single-phase and Three-phase - Aluminum - DA1 and DA3 Series
Aluminum Series DA1, Single-phase, Primary 600 V, Secondary 120 / 240 V, 150 C
kVA Mounting Taps Height 15 25 37.5 50 75 100 150 200 W/F W/F W/F W/F F F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5
F = Floor mount

Dimensions Width po 21 22 24 24 24 31 33 33 mm 533 559 610 610 610 787 838 838 Depth Type 1 po mm 17 432 17 432 21 533 21 533 21 533 24 610 27 686 27 686 Depth Type 2 po mm 22 559 22 559 26 660 26 660 26 660 28 699 31 775 31 775

Weight

Noise Level

1- DISTRIBUTION

po 18 24 26 26 26 41 46 46

mm 457 610 660 660 660 1041 1168 1168

lb 175 260 310 350 505 578 772 964

kg 385 572 682 770 1111 1272 1698 2121

dB 50 50 50 50 55 55 60 65

15 - 200 2 x FCAN, 2 x FCBN kVA THREE-PHASE : 15 - 300 2 x FCAN, 2 x FCBN kVA (3) The dimensions are applicable for type 1 enclosure and type 2 All weigths and dimensions are approximate and subject to change without notice.

(1) W = Wall mount (2) Taps : SINGLE-PHASE :

For the electical schematics diagrams see Section 5, page 5-24

Aluminum Series DA3, Three-phase, Primary 600 V or 480 V, Secondary 208Y / 120V, 150 C
kVA Mounting Taps Height 15 30 45 75 112.5 150 225 300 W/F W/F W/F W/F F F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5
F = Floor mount

Dimensions Width po 19 21 22 24 26 31 31 33 mm 483 533 559 610 660 787 787 838 Depth Type 1 po mm 13 330 17 431 17 431 21 533 21 533 23 584 24 610 27 686 Depth Type 2 po mm 18 457 22 558 22 558 26 680 26 680 27 673 28 699 31 775

Weight

Noise Level

po 16 18 24 26 29 31 41 46

mm 406 457 610 660 737 787 1041 1168

lb 145 222 290 409 587 803 292 320

kg 66 101 132 186 267 365 522 703

dB 45 45 45 50 50 50 55 55

15 - 200 2 x FCAN, 2 x FCBN kVA THREE-PHASE : 15 - 300 2 x FCAN, 2 x FCBN kVA (3) The dimensions are applicable for type 1 enclosure and type 2 All weigths and dimensions are approximate and subject to change without notice.

(1) W = Wall mount (2) Taps : SINGLE-PHASE :

For the electical schematics diagrams see Section 5, page 5-24

1-26 1-800-663-3582

Back to table of contents


Synonymous of Quality

COMMERCIAL - C802-SERIES
Copper or Aluminum

GUIDE SPECIFICATION STANDARD FORMAT


PART 1 - GENERAL
1.1 SECTIONS
A. This section includes Dry Type Distribution Transformers.

1.5 DELIVERY, STORAGE AND HANDLING


A. Section 01600, Material and equipement will address, transport, handling, storage and protection of products. B. Deliver transformers individually wrapped for protection. C. Store in a clean, dry space. Maintain factory wrapping or provide an additional heavy canvas or plastic cover to protect units from dirt, water, construction debris and trafc. D. Do not stack transformers.

1- DISTRIBUTION

1.2 REFERENCES
A. CSA C22.2 N 47 B. CSA C802.2-06

E. Temporary Heating: If transformer cannot be stored in a space that is continously under normal control of temperature and humidity, apply temporary heat according to manufacturers written instructions until evidence of condensation is no longer visible.

1.3 SUBMITTALS
A. Products Data: Include data on features, components, ratings and performance for each type of transformer specied. Include dimensioned plans, sections, elevation and side views. B. Wiring diagrams will identify, detail wiring and terminals for tap changing and connecting eld-installed wiring.

1.6 WARRANTY
A. Provide a 12 month warranty against defects in materials and workmanship.

1.4 STANDARDS
A. Listing and Labeling: Transformers specied in the section are certied by CSA. B. Transformers shall meet relevant CSA standards.

1-27 www.delta.xfo.com

COMMERCIAL - C802-SERIES
Copper or Aluminum PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Acceptable Manufacturer : Delta Transformers. B. Alternative manufacturer and product are subject to full compliance with this specification and must be approved by engineer at least 10 days prior to bid closing. C. The transformers must be a standard item in manufacturers published catalog. A custom product, one that requires design and/or packaging modifications to meet this specification, is not acceptable. D. All transformers in the project must be provided by the same manufacturer. I. Windings shall be wound with the secondary winding nearest to the core. J. The core shall be constructed of high grade, silicon steel laminations. K. The impregnation process for the core-and-coil assembly shall include a period under vacuum, followed by pressure impregnation using epoxy resin (E.V.I. Process) for 220 isolation class. L. The transformer shall be isolated from the enclosure to reduce noise and vibration by means of anti-vibration pads. M. The transformer enclosure shall be fabricated from sheet steel and shall be of Type 2 (three-phase) or Type 2 (singlephase). N. The enclosure coating shall be grey ASA 61, and suitable for indoor use.

1- DISTRIBUTION

2.2 CONSTRUCTION THREE-PHASE AND SINGLE-PHASE TRANSFORMERS


A. Transformer shall be [15, 30, 45, 75, 112,5, 150] kVA, three-phase, 3 coils or [25, 37,5, 50, 75, 100, 150, 200] kVA, single-phase, 2 coils with a common core constructions, 60 Hz. B. Primary winding shall be 600 volts, three-phase, delta connected, or 600 volts, single-phase, complete with 4 full capacity 2,5% adjustment taps, 2 below (FCBN) and 2 above (FCAN) the rated voltage. C. Secondary winding shall be 208Y/120 volts, threephases, wye connected, with a 30 angular displacement (lagging) with respect to the primary winding or 120/240 volts, single-phase. D. All winding conductors shall be of copper or aluminum. E. Temperature rise at full load shall not exceed 150C, with a class 220 insulation system. F. Transformers to qualify to High Efficiency Values for drytype transformers per CSA C802.2-06. G. Standard impedance at 60 Hz. H. Standard audible sound level.

1-28 1-800-663-3582

Back to table of contents


Synonymous of Quality

ENVIRO-GUARD - C802-SERIES
Copper - XD3C and XK3C Series
A complete and versatile transformer line that meets harsh environment requirements, stringent industrial standards and eases your installation. BENEFITS
Enhanced electrical and mechanical protection Lighter unit Lower transportation cost Ease of manipulation Lighter structural support

ENVIRO GUARD

Optimized epoxy vacuum impregnation for harsh environment.


Maximize sealing of windings and conductor leads Improved resistance to shrinking and cracking during lifetime operation Provides hydrolytic stability under electrical stress, environmental contamination or abrupt temperature variation

1- DISTRIBUTION

Flexibility to any electrical requirements Available at any kVA or voltage ratings

CHARACTERISTICS
Low viscosity resins Flexible coating Excellent peel strength High dielectric withstand Excellent noise reduction properties Superior heat transfer capabilities

FEATURES
High Efficiency compliant per CSA C802-2 UL-1446 recognized class 220 insulation systems Superior thermal endurance UL mil-spec qualified fungus resistance Chemical resistance: H2S, H2S + salt and more Other data available upon request Approved for installation in hazardous locations Class 1, Zone 2, Groups A, B, C and D temperature code (T4A to T2C)

APPLICATION
Next generation of epoxy-potted transformer for needs beyond 75 kVA applications Indoor and outdoor applications: mining, petrochemical, pulp & paper...

1-29 www.delta.xfo.com

ENVIRO-GUARD - C802-SERIES
Copper - XD3C and XK3C Series
Series XD3C (T2C), Three-phase, Primary 600 V or 480 V, Secondary 208Y / 120 V, 150
kVA Mounting Taps Height 15 30 45 50 75 112.5 150 225 300 % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po mm po Dimensions Width Depth mm po mm Consult our Customer Service Consult our Customer Service Consult our Customer Service Consult our Customer Service Consult our Customer Service Consult our Customer Service Consult our Customer Service Consult our Customer Service Consult our Customer Service lb Weight kg Noise Level dB

1- DISTRIBUTION

(1) W = Wall mount F = Floor mount (2) Taps : THREE-PHASE : 15 - 300 kVA (3) The dimensions are applicable for type 3R enclosure only.

2 x FCAN, 2 x FCBN Approved for installation in hazardous locations Class 1, Zone 2, Groups A, B C and D temperature code T2C. For the electical schematics diagrams see Section 5, page 5-24

All weights and dimensions are approximate and subject to change without notice.

Series XK3C (T2C), Three-phase K Factor, Primary 600 V or 480 V, Secondary 208Y /120 V, 150 C
kVA Mounting Taps Height 15 30 45 50 75 112.5 150 225 300 % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po mm po Dimensions Width Depth mm po mm Consult our Customer Service Consult our Customer Service Consult our Customer Service Consult our Customer Service Consult our Customer Service Consult our Customer Service Consult our Customer Service Consult our Customer Service Consult our Customer Service lb Weight kg Noise Level dB

(1) W = Wall mount F = Floor mount (2) Taps : THREE-PHASE : 15 - 300 kVA (3) The dimensions are applicable for type 3R enclosure only.

2 x FCAN, 2 x FCBN Approved for installation in hazardous locations Class 1, Zone 2, Groups A, B C and D temperature code T2C. For the electical schematics diagrams see Section 5, page 5-24

All weights and dimensions are approximate and subject to change without notice.

1-30 1-800-663-3582

Back to table of contents


Synonymous of Quality

ENVIRO-GUARD - C802-SERIES
Copper - XD3C and XK3C Series
Series XD3C (T3), Three-phase, Primary 600 V or 480 V, Secondary 208Y / 120 V, 115 C
kVA Mounting (1) Taps (2) Height 15 30 45 75 112.5 150 225 300 W/F W/F W/F W/F W/F W/F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po 30 30 33 33 47 47 58 58 mm 762 762 838 838 1194 1194 1473 1473
2 x FCAN, 2 x FCBN Approved for installation in hazardous locations class 1, Zone 2, Groups A, B, C and D temperature code T3 For the electical schematics diagrams see Section 5, page 5-24

Dimensions (3) Width po mm 25 635 25 635 29 737 29 737 33 845 33 845 46 1176 46 1176

Weight Depth po 14 14 16 16 23 23 30 30 mm 349 349 400 400 583 583 761 761 lb 50 66 84 123 171 207 331 395 kg 111 146 185 270 376 457 728 869

Noise level dB 45 45 45 50 50 50 55 55

1- DISTRIBUTION

(1) W = Wall mount F = Floor mount (2) Taps : THREE-PHASE : 15 - 300 kVA (3) The dimensions are applicable for type 3R enclosure only.

All weights and dimensions are approximate and subject to change without notice.

1-31 www.delta.xfo.com

ENVIRO-GUARD - C802-SERIES
SPECIFICATION GUIDE PART 1 - GENERAL
1.1 PRODUCT DATA
A. Read and be governed by Section 16010. Submit product data in accordance with Section 16010. Q. R. O. P. Ventilated, 3-R weatherproof enclosure with grey nish. Anti-vibration pads shall be used between the core and the enclosure. Lifetime warranty at standard voltage applications. The impregnation process for the whole core-andcoil and connecting leads assembly shall meet Enviro-Guard process consisting of optimized EPOXY Vacuum Pressure Impregnation. Impregnation processes with periods under vacuum, followed by pressure impregnations using epoxy resin part of a class 220 UL-1446 Recognized Insulation Systems. Transformers shall have nameplate indicating, but not restricted to the following : - KVA rating - Voltage rating - Impedance - Type - Insulation Class - Temperature rise - Connection diagram - Serial number

1- DISTRIBUTION

1.2 STANDARDS
A. Design, manufacture and test the dry-type transformers in accordance with industry-standard practices and in accordance with the following standards: - CSA C22.2 No. 47 Air-cooled Transformers - CSA C802-2 Minimum efciency values for dry-type transformers.

S.

PART 2 - PRODUCTS
2.1 TRANSFORMERS
A. B. C. D. E. F. G. H. I. J. K. L. Transformers shall have the following characteristics. Type : ANN. KVA, primary and secondary voltage as indicated. Single or Three phase, as indicated. Delta connected primary for three-phase transformers. Secondary winding shall be wye connected. 4 full capacity 2,5 %, adjustment taps, 2 below (FCBN) and 2 above (FCAN). Scott T connected three-phase windings are not acceptable. Copper windings, 3 coil construction. 220C insulation class. Transformers to pass continous nominal voltage and induced voltage tests immersed into tap water tank. 115 C temperature rise (80 C available upon request). Sound level : max. 45 dB up to 45 kVA, 50 dB from 75 to 150 kVA and 55 dB from 150 to 300 kVA. Other kVA per applicable standards. B.

2.2 OPTIONAL FEATURES


A. Transformers suitable for hazardous location Class 1, Zone 2, groups A, B, C, D, temperature code (T2C or T3), per Canadian Electrical Code CSA C22.1-02, at maximun nameplate KVA rating. K-rated as indicated with electrostatic shield.

2.3 MANUFACTURERS
A. All transformers shall be of one manufacturer. Acceptable manufactuers are: - Enviro-Guard by Delta Transformers Inc. - Or approved equivalent with Recognized UL-1446 class 220 epoxy resin impregnation process.

M. Standard impedance. N.

1-32 1-800-663-3582

Back to table of contents


Synonymous of Quality

ENVIRO-GUARD - C802-SERIES
SPECIFICATION GUIDE PART 3 - EXECUTION
3.1 MOUNTING
A. B. C. D. E. F. G. H. I. Floor or wall mount the dry-type transformers up to 75 kVA as indicated. Mount transformers 75 kVA and above, on oor. Ensure adequate clearance around transformer for ventilation. Install transformers in level upright position. Remove shipping supports only after transformer is installed and just before putting into service. Loosen isolation pad bolts until no compression is visible. Supply and install anti-vibration dampers for wall or ceiling mounted transformers. Make primary and secondary connections with exible metal conduits. Energize transformers as soon as possible after installation is completed.

1- DISTRIBUTION

3.2 EQUIPMENT IDENTIFICATION


A. Provide equipment identication nameplates in accordance with section 16104.

1-33 www.delta.xfo.com

EPOXY-POTTED TRANSFORMERS
Series CESC and CETC The solution to Extreme Applications
Delta Epoxy-Potted Transformers
Delta transformers are manufactured to the most exacting standards. These epoxy-potted transformers provide excellent protection against dusty, damp, humid or corrosive environments. This enhanced protection is obtained through the use of epoxy resins and materials cured and hardened to form a protective coating around the core and the winding.

Features :
3 - 50 KVA - single-phase 3 - 75 KVA - three-phase 600 V or 480 V primary 3R and sprinkler proof enclosure suitable for outdoor applications Copper winding Easy-to-install Wall mounting up to 50 KVA, single-phase and 30 KVA, three-phases Floor mounting 45 and 75 KVA, three-phases Sturdy and reliable Insulation class 185 115C temperature rise

1- DISTRIBUTION
1-34

1-800-663-3582

Back to table of contents


Synonymous of Quality

EPOXY-POTTED TRANSFORMER
Single-phase and Three-phase - Series CESC and CETC

Copper Series CESC, Single-phase, Primary 600 V or 480 V, Secondary 120 / 240 V, 115 C
kVA Mounting Taps % 2 x 4.5 2 x 4.5 2 x 4.5 2 x 4.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5
F = Floor mount

Dimensions po 13 13 14 14 15 18 22 23 Height mm 324 324 356 356 387 451 559 578 po 9 10 10 12 13 16 16 18 Width mm 229 254 254 292 330 394 394 445 po 8 8 9 10 11 12 12 13 Depth mm 191 210 229 260 267 298 298 337 Wall mount po mm 6 156 6 156 6 156 6 156 6 156 10 244 10 244 10 244

Weight lb 99 128 161 192 240 381 511 650 kg 45 58 73 87 109 173 232 295

Noise level dB 45 45 45 50 50 50 50 50

3 5 7.5 10 15 25 37.5 50

W W W W W W W W

1- DISTRIBUTION

(1) W = Wall mount (2) Taps : SINGLE-PHASE :

3 - 10 kVA 1 x FCAN, 1 x FCBN 15 - 50 kVA 2 x FCAN, 2 x FCBN THREE-PHASE : 3 - 9 kVA 1 x FCAN, 1 x FCBN 15 - 76 kVA 2 x FCAN, 2 x FCBN (3) The dimensions are applicable for type 3R enclosure only. All weights and dimensions are approximate and subject to change without notice.

For the electical schematics diagrams see Section 5, page 5-24

Copper Series CETC, Three-phase, Primary 600 V or 480 V, Secondary 208Y / 120 V, 115 C
kVA Mounting Taps % 2 x 4.5 2 x 4.5 2 x 4.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5
F = Floor mount

Dimensions po 14 14 14 14 18 18 23 30 Height mm 356 356 356 356 445 445 591 762 po 14 14 14 17 21 21 12 15 Width mm 356 356 356 438 533 533 311 375 po 8 8 9 10 11 11 24 27 Depth mm 197 197 229 260 286 286 616 692 Wall mount po mm 6 156 6 156 6 156 6 156 10 244 10 244 10 244 10 244

Weight lb 146 174 209 302 459 500 750 1343 kg 66 79 95 137 208 227 340 609

Noise level dB 45 45 45 50 50 50 50 55

3 6 9 15 22.5 30 45 75

W W W W W W F F

3 - 10 kVA 1 x FCAN, 1 x FCBN 15 - 50 kVA 2 x FCAN, 2 x FCBN THREE-PHASE : 3 - 9 kVA 1 x FCAN, 1 x FCBN 15 - 76 kVA 2 x FCAN, 2 x FCBN (3) The dimensions are applicable for type 3R enclosure only. All weights and dimensions are approximate and subject to change without notice.

(1) W = Wall mount (2) Taps : SINGLE-PHASE :

For the electical schematics diagrams see Section 5, page 5-24

1-35 www.delta.xfo.com

MINI-POWER CENTER
Series CCSC and CCTC Look for further for quality, savings, flexibility and reliability
The DELTA mini power center (CCSC/CCTC) is a small substation housed in a 3R and sprinklerproof enclosure which porvides quality, savings and flexibility. It comprises an epoxy-potted transformer with a distribution panel equipped with the necessary circuit breakers for the primary and secondary. The Delta mini power center is supplied with pre-installed components, including cables, which provides 30% to 40% savings in equipment and installation time. The compact design requires substantially less floor space than the conventional panel & transformer. The CCSC/CCTC Series transformers meet CSA standards and the Electrical Code Service entrance requirements, and may also serve as a temporary indoor or outdoor installation. The two-component construction enables the dismantling of the transformer without having to move the panel cables.

Features:
5 - 25 KVA single-phase, 9 - 30 KVA three-phase 600 V or 480 V primary 3R and sprinkler proof enclosure - compact and adapted to outdoor applications Epoxy-potted and copper-wound Choice of panels from different manufacturers Pre-installed and pre-wired primary and secondary circuts Removable transformer Approved for service entrances

1- DISTRIBUTION

Quality, Savings, Flexibility and Reliability


The mini power center is designed and constructed according to the same standards as any other Delta product with regard to accuracy, dependability and quality. The transformer is designed by means of specialized software, and manufactured under a strict quality assurance program in order to guarantee optimum service.

1-36 1-800-663-3582

Back to table of contents


Synonymous of Quality

MINI-POWER CENTER
Single-phase and Three-phase - CCSC and CCTC Series

Copper Cutler-Hammer Series CCSC, Single-phase, Primary 600 V or 480 V, Secondary 120 /240 V, 115 C
kVA Mounting Taps
% 2 x 4.5 2 x 4.5 4 x 2.5 4 x 2.5
F = Floor mount

Secondary circuts
Disjonc. 120 V 22 22 22 22 1 po. 240 V 11 11 11 11

Circuit Breaker Capacity


Primary Second. Branch. Max.

Dimensions
Height po mm 44 1127 46 1159 47 1191 49 1254 Width po mm 24 610 24 610 24 610 24 610 Depth po mm 14 356 14 356 14 356 14 356

Weight
lb 262 331 377 528 kg 119 150 171 235

Noise level
dB 45 50 50 50

5 10 15 25

W W W W

15 20 30 50

25 50 70 125

20 40 60 100

1- DISTRIBUTION

5 - 10 kVA 1 x FCAN, 1 x FCBN 15 - 25 kVA 2 x FCAN, 2 x FCBN THREE-PHASE : 9 kVA 1 x FCAN, 1 x FCBN 15 - 30 kVA 2 x FCAN, 2 x FCBN (3) The dimensions are applicable for type 3R.enclosure only. All weights and dimensions are approximate and subject to change without notice.

(1) W = Wall mount (2) Taps : SINGLE-PHASE :

For the electical schematics diagrams see Section 5, page 5-24

Copper Cutler-Hammer Series CCTC, Three-phase, Primary 600 V or 480 V, Secondary 208Y /120 V, 115 C
kVA Mounting Taps
% 2 x 4.5 4 x 2.5 4 x 2.5 4 x 2.5
F = Floor mount

Secondary circuts
Disjonc. 120 V 21 21 21 21 1 po. 208 V 7 7 7 7

Circuit Breaker Capacity


Primary Second. Branch Max.

Dimensions
Height po mm 46 1159 46 1159 49 1248 49 1248 Width po mm 24 610 24 610 24 610 24 610 Depth po mm 14 356 14 356 14 356 14 356

Weight
lb 355 452 595 637 kg 161 205 270 289

Noise level
dB 45 50 50 50

9 15 22.5 30

W W W W

15 20 30 40

30 50 70 125

20 40 60 80

(1) W = Wall mount (2) Taps : SINGLE-PHASE :

5 - 10 kVA 1 x FCAN, 1 x FCBN 15 - 25 kVA 2 x FCAN, 2 x FCBN THREE-PHASE : 9 kVA 1 x FCAN, 1 x FCBN 15 - 30 kVA 2 x FCAN, 2 x FCBN (3) The dimensions are applicable for type 3R.enclosure only. All weights and dimensions are approximate and subject to change without notice.

For the electical schematics diagrams see Section 5, page 5-24

1-37 www.delta.xfo.com

MINI-POWER CENTER
Single-phase and Three-phase - CCSC and CCTC Series
Copper Square D Series CCSC, Single-phase, Primary 600 V or 480 V, Secondary 120 / 240 V, 115 C
kVA Mounting Taps
% 2 x 4.5 2 x 4.5 4 x 2.5 4 x 2.5
F = Floor mount

Secondary circuts
Disjonc. 120 V 28 28 28 28 1 po. 240 V 14 14 14 14

Circuit Breaker Capacity


Primary Second. Branch. Max.

Dimensions
Height po mm 44 1127 46 1159 47 1191 49 1254 Width po mm 24 610 24 610 24 610 24 610 Depth po mm 14 356 14 356 14 356 14 356

Weight
lb 262 331 377 518 kg 119 150 171 235

Noise level
dB 45 50 50 50

5 10 15 25

W W W W

15 20 30 50

25 45 70 110

20 40 60 100

1- DISTRIBUTION

(1) W = Wall mount (2) Taps : SINGLE-PHASE :

5 - 10 kVA 1 x FCAN, 1 x FCBN 15 - 25 kVA 2 x FCAN, 2 x FCBN THREE-PHASE : 9 kVA 1 x FCAN, 1 x FCBN 15 - 30 kVA 2 x FCAN, 2 x FCBN (3) The dimensions are applicable for type 3R.enclosure only. All weights and dimensions are approximate and subject to change without notice.

For the electical schematics diagrams see Section 5, page 5-24

Copper Square D Series CCTC, Three-phase, Primary 600 V or 480 V, Secondary 208Y / 120 V, 115 C
kVA Mounting Taps
% 2 x 4.5 4 x 2.5 4 x 2.5 4 x 2.5
F = Floor mount

Secondary circuts
Disjonc. 120 V 27 27 27 27 1 po. 208 V 9 9 9 9

Circuit Breaker Capacity


Primary Second. Branch. Max.

Dimensions
Height po mm 46 1159 46 1159 49 1248 49 1248 Width po mm 24 610 24 610 24 610 24 610 Depth po mm 14 356 14 356 14 356 14 356

Weight
lb 355 452 595 637 kg 161 205 270 289

Noise level
dB 45 50 50 50

9 15 22.5 30

W W W W

15 20 25 35

30 45 70 90

20 40 60 80

(1) W = Wall mount (2) Taps : SINGLE-PHASE :

5 - 10 kVA 1 x FCAN, 1 x FCBN 15 - 25 kVA 2 x FCAN, 2 x FCBN THREE-PHASE : 9 kVA 1 x FCAN, 1 x FCBN 15 - 30 kVA 2 x FCAN, 2 x FCBN (3) The dimensions are applicable for type 3R.enclosure only. All weights and dimensions are approximate and subject to change without notice.

For the electical schematics diagrams see Section 5, page 5-24

1-38 1-800-663-3582

Back to table of contents


Synonymous of Quality

NON LINEAR LOAD


Power Quality Modern Quality Problems and their Solutions K-Rated Transformers Single-Phase and Three-Phase Series VKSC, VKTC, VK3C and VK3A Zero Sequence Filters Serie VFTC Computer Application Isolated Transformers Single-Phase and Three-Phase Series VCSC, VCTC, VC1C and VC3C Super Isolated Transformers Single-Phase and Three-Phase Series VSSC, VSTC, VS1C and VS3C Transformers for Variable Speed Drives Series CITC, CI3C, CITA and CI3A

SECTION 2

Mitigator E-Series Mitigator E-Silver (Technical specification) Mitigator E-Gold (Technical specification) Mitigator E-Platinum (Technical specification)

2-1 www.delta.xfo.com

2-2

2- NON LINEAR LOAD

1-800-663-3582

Back to table of contents


Synonymous of Quality

POWER QUALITY
Modern Quality Problems and their Solutions
Many surveys have been performed and reported about sensitive electronic equipment and power quality. These surveys are difcult to compare because of different thresholds for data recording. It is possible to summarize the main problems encountered as follows :

HARMONIC
Representation of a nonsinusoidal periodic wave by the sum of many sinusoidal waves that are integer multiples of the fundamental frequency (60 Hz). Equipment using DC voltage such as personal computers, ofce equipment, semiconductor converters and other non linear loads.. The gure (reverse side) illustrates the voltage limits and zones which are considered capable of causing computer problems such as errors, loss of memory or software, and programmable equipment or process control failures.

Categories of Power Quality Problems


TRANSIENT
High amplitude and short duration over voltage superimposed on the normal voltage. Transients vary widely in waveforms; amplitude varying from a few hundreds to many thousands of volts, duration varying from 1 microsecond to 10 millseconds, and may be classied as impulse or oscillatory type. Lightning and switching of power circuits.

2- NON LINEAR LOAD

SAG and SWELL


Variation of about 20 % (sag) or +10 % (swell) of the AC voltage at power frequency and a duration from a half cycle to a few seconds. Starting (sag) or de-energizing (swell) of heavy loads or sudden increase (sag) or decrease (swell) of loads.

UNDER and OVER VOLTAGE


Variation in the range of 13 % to +6 % of the AC voltage at the power frequency and lasting more than a few seconds. Circuit overloads or poor voltage regulation.

POWER OUTAGE
Complete loss of power for many missiseconds to many hours. Operation of protective equipment, power equipment failures, accidents involving power transmission lines.

NOISE
Unwanted signals superimposed on a normal sine wave of many sinusoidal waves as small repetitive voltage or frequency transients. Power electronic circuits, arc welding, switching power supplies, electromagnetic and radio frequency interference.

2-3 www.delta.xfo.com

POWER QUALITY
Modern Quality Problems and their Solutions

GENERAL RECOMMENDATIONS
The rst thing you need to know is the correct value of your loads (true RMS values). Therefore, True RMS instrumentation is important. Proper grounding and bonding conditions are essential to ensure the proper function of all equipment and their protection devices. All protection devices and transformers should be as close as possible to loads. With TVSS, make sure that you have added a surge protection at the distribution panel or transformer, Transformers close to your loads will give low common mode voltage (neutral-ground) and many small transformers are better than a large one. Loads should be segregated as linear and non linear loads. Loads should be well balanced on each of your phases. Stop your third harmonic currents on the secondary side of transformers with secondary zigzag windings (at low zero sequence impedance), or by trapping them by the means of zero sequence harmonic lters close to your loads. Non linear load systems should be balanced and phase shifted between each other. By phase shifting your non linear loads by 30, 5th and 7th harmonic currents, instead of adding up on your main bus, will cancel each other. In the case of an isolated ground installation (orange receptacles) at the distribution panel, install a transformer having one or multiple electrostatic shields, which may be equipped with a high frequency lter and surge protection. Verify that there are no ground loops present in the system, such as two computers at two different ground potentials with a communication cable grounded at both ends. The potential difference between the two grounding points creates a circulation current in the communication cable.

NOTE
Impedance is very important with non linear loads. Because the impedance value (resistance and/or reactance) increases with frequency, harmonic load currents (current distortion THDi) will create undersirable harmonic voltages (voltage distortion THDv).

TRANSFORMERS
VKTC (-30)

2- NON LINEAR LOAD

VCTC (-30)

VSTC (-30)
F

VFTC Zero sequence lter

VZTC (-0)

VZTC (-30)

VZTC (0/-30)

2-4 1-800-663-3582

Back to table of contents


Synonymous of Quality

POWER QUALITY

Modern Quality Problems and their Solutions

TYPICAL APPLICATION
TRANSFORMER T2 25 KV - 600Y V

HYDRO

UTILITY

2 DRIVE 500 HP

TRANSFORMER T1 25 KV - 600 V

DRIVE 500 HP 2 DRIVE 500 HP DRIVE 500 HP VCTC - 30 600 - 208Y/120 V 3 OFFICE EQUIPMENT

MAIN TRANSFORMER 25 KV - 600Y/347 V

2- NON LINEAR LOAD

VOLTAGE REGULATOR 600 - 208Y/120 V VZTC 0 600 - 208Z/120 V 1 2 VSSC 600 - 120/240 V UPS F 3

HIGH TECH ELECTRONIC EQUIPMENT

VSTC - 30 600 - 208Y/120 V

3 COMPUTERS, ORANGE RECEPTACLES

F ELECTRONIC BALLASTS VZTC 0 600 - 208Z/120 V

3 COMPUTER ROOM

NETWORK SERVER

VZTC - 30 600 - 208Z/120 V

3 COMPUTER ROOM

MOTORS PUMPS AND VENTILATION

VZTC 0/-30 600 - DUAL 208Z/120 V VKTC -30 600 - 208Y/120 V

3 PANEL A ELECTRONIC BALLASTS 3 PANEL B ELECTRONIC BALLASTS

POWER FACTOR CORRECTION

3 PLC AND NONLINEAR LOADS

HYBRID FILTERS (Filters and Surge Suppressors (TVSS)) (Noise Rejection, Peak Transient Current)
1 2 3 iSE (up to 50 dB, 150 000 A / phase) iBP (up to 50 dB, 110 000 A / phase) OSW (up to 40 dB, 80 000 A / phase)

VFTC

NOTE: This diagram is an example for suggestion purpose only and is not representative of a particular situation.

2-5 www.delta.xfo.com

K-RATED TRANSFORMERS Single-Phase and Three-Phase - Series VKSC, VKTC, VK3C and VK3A
All VKSC, VKTC, VK3C and VK3A Series transformers meet the most stringent industrial standards on account of their optimal design, superior quality and ease of installation. The VKSC, VKTC, VK3C and VK3A transformers are manufactured for applications where non linear (nonsinusoidal) loads are predominant. The transformer construction minimizes losses associated with harmonic currents, and the impregnation process ensures a quiet operation.

Features and Option :


E.V.I. Process (epoxy vacuum impregnation) at no additional cost Copper winding Insulation class 220 80C, 115C or 150C temperature rise available Compact and easy-to-install enclosure Quiet operation Proper ventilation Neutral sized for twice the rated current Voltage of 600 V to 208Y/120 V, 60 Hz, delta-wye, for Three-phase transformers (3 coils) Voltage of 600 V to 120/240 V, 60 Hz, for single-phase transformers (2 coils) Electrostatic shield Special voltages available upon request

2- NON LINEAR LOAD

Examples of harmonic content with K-Factor : K=4 100 % 60 Hz 6 % of fundamental for 3rd 10 % of fundamental for 5th 7 % of fundamental for 7th 5,5 % of fundamental for 9th ... Up to 25th K = 13 100 % 60 Hz 33 % of fundamental for 3rd 20 % of fundamental for 5th 14 % of fundamental for 7th 11 % of fundamental for 9th ... Up to 25th

Applications :
Non linear loads Installations with isolated ground Industrial programmable controllers (PLC) Protected receptacles for hospitals Protected receptacles (orange)

2-6 1-800-663-3582

Back to table of contents


Synonymous of Quality

K-RATED TRANSFORMERS

Single-Phase - copper winding - Serie VKSC

Copper Series VKSC, Single-phase, Type 1, Primary 600 V, Secondary 120 / 240 V, K = 13, 150 C
kVA Mounting Taps Height 3 5 7.5 10 W/F W/F W/F W/F % 2 x 4.5 2 x 4.5 2 x 4.5 4 x 2.5 po 18 21 21 23 mm 457 533 533 584 po 12 15 15 17 Dimensions Width mm 305 381 381 432 po 9 11 11 12 Depth mm 229 279 279 305 lb 76 107 121 153 kg 34 49 55 69 dB 45 45 45 50 Weight Noise level

3 - 7.5 kVA 1 x FCAN, 1 x FCBN 10 kVA 2 x FCAN, 2 x FCBN THREE-PHASE : 6 kVA 1 x FCAN, 1 x FCBN 10 kVA 2 x FCAN, 2 x FCBN (3) Factors k=4 and k=9 dimensions and weights may be lower that data shown in the table. (4) For dimensions and weights of transformer with K-Factor higher than K=13, consult our customer service. (5) No correspondence between approved type 2, 3R and 4 enclosure All weights and dimensions are approximate and subject to change without notice.

(1) W = Wall mount (2) Taps : SINGLE-PHASE :

F = Floor mount

2- NON LINEAR LOAD

For the electical schematics diagrams see Section 5, page 5-24

Copper Series VKSC, single-phase, Type 3R, Primary 600 V, Secondary 120 / 240 V, K = 13, 150 C
kVA Mounting Taps Height 3 5 7.5 10 W/F W/F W/F W/F % 2 x 4.5 2 x 4.5 2 x 4.5 4 x 2.5 po mm po Dimensions Width Depth mm po mm Consult our Customer Service Consult our Customer Service Consult our Customer Service Consult our Customer Service lb Weight kg Noise level dB

3 - 7.5 kVA 1 x FCAN, 1 x FCBN 10 kVA 2 x FCAN, 2 x FCBN THREE-PHASE : 6 kVA 1 x FCAN, 1 x FCBN 10 kVA 2 x FCAN, 2 x FCBN (3) Factors k=4 and k=9 dimensions and weights may be lower that data shown in the table. (4) For dimensions and weights of transformer with K-Factor higher than K=13, consult our customer service. (5) No correspondence between approved type 1, 2 and 4 enclosure All weights and dimensions are approximate and subject to change without notice.

(1) W = Wall mount (2) Taps : SINGLE-PHASE :

F = Floor mount

For the electical schematics diagrams see Section 5, page 5-24

2-7 www.delta.xfo.com

K-RATED TRANSFORMERS Three-Phase - copper winding - Serie VKTC

Copper Series VKTC, Three-phase, Type 1, Primary 600 V, Secondary 208Y/120V, K = 13, 150 C
kVA Mounting Taps Height 6 10 W/F W/F % 2 x 4.5 4 x 2.5 po 19 21 mm 483 533 po 18 20 Dimensions Width mm 457 508 po 10 12 Depth mm 254 305 lb 119 165 kg 54 75 dB 40 45 Weight Noise level

2- NON LINEAR LOAD

10 kVA 2 x FCAN, 2 x FCBN 6 kVA 1 x FCAN, 1 x FCBN 10 kVA 2 x FCAN, 2 x FCBN (3) Factors k=4 and k=9 dimensions and weights may be lower that data shown in the table. (4) For dimensions and weights of transformer with K-Factor higher than K=13, consult our customer service. (5) No correspondence between approved type 2, 3R and 4 enclosure All weights and dimensions are approximate and subject to change without notice.

(1) W = Wall mount (2) Taps : SINGLE-PHASE : THREE-PHASE :

F = Floor mount

For the electical schematics diagrams see Section 5, page 5-24

Copper Series VKTC, Three-phase, Type 3R, Primary 600 V, Secondary 208Y/120V, K = 13, 150 C
kVA Mounting Taps Height 6 10 W/F W/F % 2 x 4.5 4 x 2.5 po 25 25 mm 635 635 po 21 21 Dimensions Width mm 533 533 po 13 13 Depth mm 324 324 lb 147 180 kg 67 82 dB 40 45 Weight Noise level

10 kVA 2 x FCAN, 2 x FCBN 6 kVA 1 x FCAN, 1 x FCBN 10 kVA 2 x FCAN, 2 x FCBN (3) Factors k=4 and k=9 dimensions and weights may be lower that data shown in the table. (4) For dimensions and weights of transformer with K-Factor higher than K=13, consult our customer service. (5) No correspondence between approved type 1, 2 and 4 enclosure All weights and dimensions are approximate and subject to change without notice.

(1) W = Wall mount (2) Taps : SINGLE-PHASE : THREE-PHASE :

F = Floor mount

For the electical schematics diagrams see Section 5, page 5-24

2-8 1-800-663-3582

Back to table of contents


Synonymous of Quality

K-RATED TRANSFORMERS, C802.2 Three-Phase - copper winding - Serie VK3C

Copper Series VK3C, Three-phase, Type 1, Primary 600 V, Secondary 208Y / 120 V, ESS, K = 4, 150 C
kVA Mounting Taps Height 15 30 45 50 75 112.5 150 225 300 W/F W/F W/F W/F F F F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po 27 27 28 28 30 37 37 46 46 mm 686 686 711 711 762 940 940 1168 1168 po 23 23 29 29 30 35 35 44 44 Dimensions Width mm 584 584 737 737 762 889 889 1118 1118 po 13 13 14 14 14 18 18 23 23 Depth mm 330 330 356 356 356 457 457 584 584 lb 229 290 387 398 576 812 1005 1520 1811 kg 104 132 176 181 262 369 457 691 823 dB 45 45 45 45 50 50 50 55 55 Weight Noise level

2- NON LINEAR LOAD

(1) W = Wall mount F = Floor mount (2) Taps : SINGLE-PHASE : 15 - 300 kVA 2 x FCAN, 2 x FCBN THREE-PHASE : 15 - 300 kVA 2 x FCAN, 2 x FCBN (3) Factors k=4 and k=13 dimensions and weights may be lower that data shown in the table. (4) No correspondence between approved type 2, 3R and 4 enclosure. All weights and dimensions are approximate and subject to change without notice.

For the electical schematics diagrams see Section 5, page 5-24

Copper Series VK3C, Three-phase, Type 3R, Primary 600 V, Secondary 208Y / 120 V, ESS, K = 4, 150 C
kVA Mounting Taps Height 15 30 45 50 75 112.5 150 225 300 W/F W/F W/F W/F F F F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po 30 33 33 mm 762 838 838 po 25 29 29 Dimensions Width Depth mm po mm Consult our Customer Sevice 635 14 349 737 16 400 737 16 400 Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice lb 304 381 579 Weight kg 138 173 263 Noise level dB 45 45 50

(1) W = Wall mount F = Floor mount (2) Taps : SINGLE-PHASE : 15 - 300 kVA 2 x FCAN, 2 x FCBN THREE-PHASE : 15 - 300 kVA 2 x FCAN, 2 x FCBN (3) Factors k=4 and k=13 dimensions and weights may be lower that data shown in the table. (4) No correspondence between approved type 1, 2 and 4 enclosure. All weights and dimensions are approximate and subject to change without notice.

For the electical schematics diagrams see Section 5, page 5-24

2-9 www.delta.xfo.com

K-RATED TRANSFORMERS, C802.2 Three-Phase - aluminum winding - Serie VK3A

Aluminum Series VK3A, Three-phase,Type 1, Primary 600 V, Secondary 208Y/120 V, ESS, K = 13, 150 C
kVA Mounting Taps Height 15 30 45 50 75 112.5 150 225 300 W/F W/F W/F W/F F F F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po 27 27 28 28 30 37 37 46 46 mm 686 686 711 711 762 940 940 1168 1168 po 23 23 29 29 30 35 35 44 44 Dimensions Width mm 584 584 737 737 762 889 889 1118 1118 po 13 13 14 14 14 18 18 23 23 Depth mm 330 330 356 356 356 457 457 584 584 lb 229 290 387 398 576 812 1005 1520 1811 kg 104 132 162 168 262 369 457 691 823 dB 45 45 45 45 50 50 50 55 55 Weight Noise level

2- NON LINEAR LOAD

(1) W = Wall mount F = Floor mount (2) Taps : SINGLE-PHASE : 15 - 300 kVA 2 x FCAN, 2 x FCBN THREE-PHASE : 15 - 300 kVA 2 x FCAN, 2 x FCBN (3) Factors k=4 and k=9 dimensions and weights may be lower that data shown in the table. (4) For dimensions and weights of transformer with K-Factor higher than K=13, consult our customer service. (5) No correspondence between approved type 2, 3R and 4 enclosure. All weights and dimensions are approximate and subject to change without notice.

For the electical schematics diagrams see Section 5, page 5-24

Aluminium Series VK3A,Triphas,Type 3R,Primaire 600 V,Secondaire 208Y/120 V,ESS,Facteur K=13, 150 C
kVA Mounting Taps Height 15 30 45 50 75 112.5 150 225 300 W/F W/F W/F W/F F F F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po 30 30 33 33 33 47 47 58 58 mm 762 762 838 838 838 194 1194 1473 1473 po 25 25 29 29 29 33 33 46 46 Dimensions Width mm 635 635 737 737 737 845 845 1176 1176 po 14 14 16 16 16 23 23 30 30 Depth mm 349 349 400 400 400 583 583 761 761 lb 242 304 381 407 579 816 1003 1610 1901 kg 110 138 173 185 263 371 456 732 864 dB 45 45 45 45 50 50 50 55 55 Weight Noise level

(1) W = Wall mount F = Floor mount (2) Taps : SINGLE-PHASE : 15 - 300 kVA 2 x FCAN, 2 x FCBN THREE-PHASE : 15 - 300 kVA 2 x FCAN, 2 x FCBN (3) Factors k=4 and k=9 dimensions and weights may be lower that data shown in the table. (4) For dimensions and weights of transformer with K-Factor higher than K=13, consult our customer service. (5) No correspondence between approved type 1, 2 and 4 enclosure. All weights and dimensions are approximate and subject to change without notice.

For the electical schematics diagrams see Section 5, page 5-24

2-10 1-800-663-3582

Back to table of contents


Synonymous of Quality

K-RATED TRANSFORMERS, C802.2 Three-Phase - aluminum winding - Series VK3A

Aluminum Series VK3A, Three-phase, Type 1, Primary 600 V, Secondary 208Y / 120 V, ESS, K = 4, 150 C
kVA Mounting Taps Height 15 30 45 50 75 112.5 150 225 300 W/F W/F W/F W/F F F F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po 27 27 28 28 30 37 37 46 46 mm 686 686 711 711 762 940 940 1168 1168 po 23 23 29 29 30 35 35 44 44 Dimensions Width mm 584 584 737 737 762 889 889 1118 1118 po 13 13 14 14 14 18 18 23 23 Depth mm 330 330 356 356 356 457 457 584 584 lb 229 290 356 370 576 812 1005 1520 1811 kg 104 132 162 168 262 369 457 691 823 dB 45 45 45 45 50 50 50 55 55 Weight Noise level

2- NON LINEAR LOAD

(1) W = Wall mount F = Floor mount (2) Taps : SINGLE-PHASE : 15 - 300 kVA 2 x FCAN, 2 x FCBN THREE-PHASE : 15 - 300 kVA 2 x FCAN, 2 x FCBN (3) Factors k=4 and k=9 dimensions and weights may be lower that data shown in the table. (4) For dimensions and weights of transformer with K-Factor higher than K=13, consult our customer service. (5) No correspondence between approved type 2, 3R and 4 enclosure. All weights and dimensions are approximate and subject to change without notice.

For the electical schematics diagrams see Section 5, page 5-24

Aluminum Series VK3A, Three-phase, Type 3R, Primary 600 V, Secondary 208Y/120 V, ESS, K = 4, 150 C
kVA Mounting Taps Height 15 30 45 50 75 112.5 150 225 300 W/F W/F W/F W/F F F F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po mm po Dimensions Width Depth mm po mm Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice lb Weight kg Noise level dB

(1) W = Wall mount F = Floor mount (2) Taps : SINGLE-PHASE : 15 - 300 kVA 2 x FCAN, 2 x FCBN THREE-PHASE : 15 - 300 kVA 2 x FCAN, 2 x FCBN (3) Factors K=4 and k=9 dimensions and weights may be lower that data shown in the table. (4) For dimensions and weights of transformer with K-Factor higher than K=13, consult our customer service. (5) No correspondence between approved type 1, 2 and 4 enclosure. All weights and dimensions are approximate and subject to change without notice.

For the electical schematics diagrams see Section 5, page 5-24

2-11 www.delta.xfo.com

K-RATED TRANSFORMERS, C802.2 Three-Phase - copper winding - Series VK3C

Copper Series VK3C, Three-phase, Type 1, Primary 600 V, Secondary 208Y / 120 V, ESS, K = 13, 150 C
kVA kVA Prises Montage Mounting Taps dajustement (1) (2) % W/F 4 % 2.5 x W/F 44xx2.5 W/F 2.5 W/F 44xx2.5 W/F 2.5 W/F 44xx2.5 W/F 2.5 W/F 44xx2.5 F 2.5 F 44xx2.5 F 2.5 F 44xx2.5 F 2.5 F 44xx2.5 F 2.5 F 44xx2.5 F 2.5 F 4 x 2.5 Height poHauteur mm po mm 27 686 27 686 27 686 27 686 28 711 28 711 28 711 28 711 30 762 30 762 37 940 37 940 37 940 37 940 46 1168 46 1168 46 1168 46 1168 Dimensions Dimensions (3) Width poLargeur mm po mm 23 584 23 584 23 584 23 584 29 737 29 737 29 737 29 737 30 762 30 762 35 889 35 889 35 889 35 889 44 1118 44 1118 44 1118 44 1118 Weight Poids Depth Profondeur po mm po mm 13 330 13 330 13 330 13 330 14 356 14 356 14 356 14 356 14 356 14 356 18 457 18 457 18 457 18 457 23 584 23 584 23 584 23 584 lb lb 229 229 290 290 387 387 398 398 576 576 812 812 1005 1005 1520 1520 1811 1811 kg kg 104 104 132 132 176 176 181 181 262 262 369 369 457 457 691 691 823 823 Noise Niveau level de bruit dB dB 45 45 45 45 45 45 45 45 50 50 50 50 50 50 55 55 55 55

2- NON LINEAR LOAD

15 15 30 30 45 45 50 50 75 75 112.5 112.5 150 150 225 225 300 300

(1) W = Wall mount F F = mount (1) W = Montage au mur = FloorMontage au plancher (2) Taps : (2) Prises dajustement : SINGLE-PHASE : 15 300 kVA MONOPHAS : 15 - - 300 kVA 22 x FCAN, 2 x FCBN x FCAN, 2 x FCBN THREE-PHASE 15 300 kVA TRIPHAS : : 15 - - 300 kVA 22 x FCAN, 2 x FCBN x FCAN, 2 x FCBN (3) Les dimensions et poids de facteur k=4 et k=13 peuvent tre infrieurs aux donnes (3) tableau. k=4 and k=9 dimensions and weights may be lower that data shown in the table. Factors du (4) For dimensions and et poids des transformateurs suprieurs than consultez le service (4) Pour les dimensions weights of transformer with K-Factor higherk=13,K=13, consult our customer service. la clientle. (5) No dimensions ne between approved botiers de type 2, 3R et 4. (5) Lescorrespondencesappliquent pas auxtype 2, 3R and 4 enclosure. Tous les poids et dimensions sont approximatifs et peuvent changer sans pravis All weights and dimensions are approximate and subject to change without notice.

For the electical schematics diagrams see Section 5, page 5-24

Copper Series VK3C, Three-phase, Type 3R, Primary 600 V, Secondary 208Y / 120 V, ESS, K = 13, 150 C
kVA Mounting Taps Height 15 30 45 50 75 112.5 150 225 300 W/F W/F W/F W/F F F F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po 30 30 33 33 33 47 47 58 58 mm 762 762 838 838 838 1194 1194 1473 1473 po 25 25 29 29 29 33 33 46 46 Dimensions Width mm 635 635 737 737 737 845 845 1176 1176 po 14 14 16 16 16 23 23 30 30 Depth mm 349 349 400 400 400 583 583 761 761 lb 242 304 381 407 579 816 1003 1610 1901 kg 110 138 173 185 263 371 456 732 864 dB 45 45 45 45 50 50 50 55 55 Weight Noise level

(1) W = Wall mount F = Floor mount (2) Taps : SINGLE-PHASE : 15 - 300 kVA 2 x FCAN, 2 x FCBN THREE-PHASE : 15 - 300 kVA 2 x FCAN, 2 x FCBN (3) Factors k=4 and k=9 dimensions and weights may be lower that data shown in the table. (4) For dimensions and weights of transformer with K-Factor higher than K=13, consult our customer service. (5) No correspondence between approved type 1, 2 and 4 enclosure. All weights and dimensions are approximate and subject to change without notice.

For the electical schematics diagrams see Section 5, page 5-24

2-12 1-800-663-3582

Back to table of contents


Synonymous of Quality

ZERO SEQUENCE FILTERS Serie VFTC


The cost effective solution to zero sequence harmonic problems
The VFTC Series zero sequence filters are specifically designed to reduce third harmonic and zero sequence currents in the neutral of a three-phase four wire system. These filters are an alternative to the conventional solutions which consist in reducing the existing transformer capacity or in installing a K-rated transformer. They substantially reduce third harmonic currents in the system. Power quality is improved by a parallel installation as close as possible to non linear loads, thus reducing neutral current and common mode voltage.

Features and Option :


E.V.I. process (epoxy vacuum impregnation) at no additional cost Copper winding Insulation class 220 High- quality grain-oriented steel laminations Compact and easy-to-install enclosure Quiet operation Proper ventilation Neutral sized for three times the line current 208 V (3 coils) rated voltage Ammeter displaying the neutral current in option 80C and 115C temperature rise in option Special voltages available upon request

2- NON LINEAR LOAD

Applications :
Three-phase four wire electrical system with Single-phase non linear loads such as lighting Ballasts, computers, printers...

Benefits :
Reduced third harmonic and zero sequence currents in the neutral and the system Improved electrical system performance Improved power factor Improved electrical system capacity Reduced neutral-ground voltage Reduced main transformer load Reduced K-factor rating of load current at main transformer Reduced system losses Reduced total harmonic distortion (THD) Economical and stand-alone solution

2-13 www.delta.xfo.com

ZERO SEQUENCE FILTER Three-Phase - Serie VFTC

Series VFTC, Three-phase, Voltage 280 V, 150 C


Zero sequence neutral current A(ms) Mounting Height 100 175 250 350 450 600 800
(1) W = Wall mount F = Floor mount For the electical schematics diagrams see Section 5, page 5-24

Dimensions Width mm 533 533 711 711 762 762 940 po 20 20 29 29 30 30 35 mm 508 508 737 737 762 762 889 po 12 11 14 14 14 14 18 Depth mm 305 279 356 356 356 356 457 po 21 21 28 28 30 30 37

Weights lb 169 163 372 372 550 550 715 kg 77 74 169 169 250 250 325

Noise level dB 40 45 45 45 45 45 50

2- NON LINEAR LOAD

W/F W/F W/F W/F W/F W/F W/F

(2) No correspondence between approved type 2, 3R and 4 enclosure All weights and dimensions are approximate and subject to change without notice.

2-14 1-800-663-3582

Back to table of contents


Synonymous of Quality

COMPUTER APPLICATION ISOLATED TRANSFORMERS Single-Phase and Three-Phase - Series VCSC, VCTC, VC1C and VC3C
The cost effective solution for installations with isolated ground (orange receptacles)
All VCSC, VCTC, VC1C and VC3C Series isolated transformers meet the most stringent industrial standards on account of their optimal design, superior quality and ease of installation. The VCSC, VCTC, VC1C and VC3C transformers use a filtering method that minimizes the capacitance between input and ouput circuits.

Features and Options :


E.V.I. Process (epoxy vacuum impregnation) at no additional cost Copper windings Insulation class 220 High-quality grain-oriented steel laminations Compact and easy-to-install enclosure Quiet operation Proper ventilation Cost effective protection of sensitive electronic equipment Cost-effective protection of sensitive electronic equipment Electrostatic shield Common mode noise, attenuation of 60 db minimum K=13 Factor Neutral sized for twice the rated current Voltage of 600 V to 208Y/120 V, 60 Hz, delta-wye, for three-phase transformers (3 coils) Voltage of 600 V to 120/240 V, 60 Hz, for single-phase transformers (2 coils) Special voltages available upon request

2- NON LINEAR LOAD

Applications :
Non linear loads Installations with isolated ground Industrial programmable controllers (PLC) Protected receptables for hospitals Protected receptacles (orange) Installations where noise and transients are a problem

2-15 www.delta.xfo.com

COMPUTER APPLICATION ISOLATED TRANSFORMERS Single-Phase - Serie VCSC

Copper Series VCSC, Single-phase, Primary 600 V, Secondary 120 / 240 V, ESS, K = 13, 150 C
kVA Mounting Taps Height 3 5 7.5 10 W/F W/F W/F W/F
F = Floor mount

Dimensions Width mm 457 533 533 584 po 12 15 15 17 mm 305 381 381 432 po 9 11 11 12 Depth mm 229 279 279 305 lb 76 107 121 153 po 18 21 21 23

Weight kg 34 49 55 69

Noise level dB 45 45 45 50

% 2 x 4.5 2 x 4.5 2 x 4.5 4 x 2.5

2- NON LINEAR LOAD

3 - 7.5 kVA 1 x FCAN, 1 x FCBN 10 kVA 2 x FCAN, 2 x FCBN THREE-PHASE : 6 kVA 1 x FCAN, 1 x FCBN 10 kVA 2 x FCAN, 2 x FCBN (3) Factors k=4 and k=9 dimensions and weights may be lower that data shown in the table. (4) For dimensions and weights of transformer with K-Factor higher than K=13, consult our customer service. (5) No correspondence between approved type 2, 3R and 4 enclosure. All weights and dimensions are approximate and subject to change without notice.

(1) W = Wall mount (2) Taps : SINGLE-PHASE :

For the electical schematics diagrams see Section 5, page 5-24

COMPUTER APPLICATION ISOLATED TRANSFORMERS Three-Phase - Serie VCTC


Copper Series VCTC, Three-phase, Primary 600 V, Secondary 208Y /120 V, ESS, K = 13, 150 C
kVA Mounting Taps Heigth 6 10 W/F W/F % 2 x 4.5 4 x 2.5 po 19 21 mm 483 533 po 18 20 Dimensions Width mm 457 508 po 10 12 Depth mm 254 305 lb 119 165 kg 54 75 dB 40 45 Weight Noise level

(1) W = Wall mount (2) Taps : SINGLE-PHASE : THREE-PHASE :

F = Floor mount

10 kVA 2 x FCAN, 2 x FCBN 6 kVA 1 x FCAN, 1 x FCBN 10 kVA 2 x FCAN, 2 x FCBN (3) Factors k=4 and k=9 dimensions and weights may be lower that data shown in the table. (4) For dimensions and weights of transformer with K-Factor higher than K=13, consult our customer service. (5) No correspondence between approved type 1, 2 and 4 enclosure. All weights and dimensions are approximate and subject to change without notice.

For the electical schematics diagrams see Section 5, page 5-24

2-16 1-800-663-3582

Back to table of contents


Synonymous of Quality

COMPUTER APPLICATION ISOLATED TRANSFORMERS, C802.2 Single-Phase and Three-Phase - Serie VC1C and VC3C
Copper Series VC1C, Single-phase, Primary 600 V, Secondary 120 / 240 V, ESS, K = 13, 150 C
kVA Mounting Taps Height 15 25 37.5 50 75 100 150 200 W/F W/F W/F F F F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po 23 29 29 37 37 46 54 54 mm 584 737 737 940 940 1168 1372 1372 po 17 20 20 22 22 26 31 31 Dimensions Width mm 432 508 508 559 559 660 787 787 po 12 14 14 18 18 21 23 23 Depth mm 305 356 356 457 457 533 584 584 lb 177 265 312 479 565 820 1089 1215 kg 89 137 152 218 279 356 494 577 dB 50 50 50 50 55 55 60 65 Weight Noise level

2- NON LINEAR LOAD

(1) W = Wall mount F = Floor mount (2) Taps : SINGLE-PHASE : 15 - 200 kVA 2 x FCAN, 2 x FCBN THREE-PHASE : 15 - 300 kVA 2 x FCAN, 2 x FCBN (3) Factors k=4 and k=9 dimensions and weights may be lower that data shown in the table. (4) For dimensions and weights of transformer with K-Factor higher than K=13, consult our customer service. (5) No correspondence between approved type 2, 3R and 4 enclosure. All weights and dimensions are approximate and subject to change without notice.

For the electical schematics diagrams see Section 5, page 5-24

Copper Series VC3C, Three-phase, Primary 600 V, Secondary 208Y /120 V, ESS K = 13, 150 C
kVA Mounting Taps Height 15 30 45 50 75 112.5 150 225 300 W/F W/F W/F W/F F F F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po 27 27 28 28 30 37 37 46 46 mm 686 686 711 711 762 940 940 1168 1168 po 23 23 29 29 30 35 35 44 44 Dimensions Width mm 584 584 737 737 762 889 889 1118 1118 po 13 13 14 14 14 18 18 23 23 Depth mm 330 330 356 356 356 457 457 584 584 lb 229 291 388 399 578 813 1008 1523 1814 kg 104 132 176 181 262 369 457 691 823 dB 45 45 45 45 50 50 50 55 55 Weight Noise level

(1) W = Wall mount F = Floor mount (2) Taps : SINGLE-PHASE : 15 - 200 kVA 2 x FCAN, 2 x FCBN THREE-PHASE : 15 - 300 kVA 2 x FCAN, 2 x FCBN (3) Factors =4 and k=9 dimensions and weights may be lower that data shown in the table. (4) For dimensions and weights of transformer with K-Factor higher than K=13, consult our customer service. (5) No correspondence between approved type 2, 3R and 4 enclosure. All weights and dimensions are approximate and subject to change without notice.

For the electical schematics diagrams see Section 5, page 5-24

2-17 www.delta.xfo.com

SUPER ISOLATED TRANSFORMERS Single-Phase and Three-Phase - Series VSSC, VSTC, VS1C and VS3C
The super isolated solution
All VSSC, VSTC, VS1C and VS3C Series isolated transformers meet the most stringent industrial standards on account of their optimal design, superior quality and ease of installation. The VSSC, VSTC, VS1C and VS3C transformers have a hybrid design using an isolated transformer with a hybrid filter (filter and surge suppressor (TVSS)).

Features and Option :


E.V.I. Process (epoxy vacuum impregnation) at no additional cost Copper winding Insulation class 220 High-quality grain-oriented steel laminations Compact and easy-to-install enclosure Quiet operation Proper Ventilation Cost-effective protection of sensitive electronic equipment Multiple electrostatic shields Hybrid filter - filtering band of 10 kHz to 100 MHz - peak transient current of 80 000 A Common mode noise attenuation up to 100 dB K=13 Factor Neutral sized for twice the rated current Voltage of 600 V to 208Y/120 V, 60 Hz, delta-wye, for three-phase transformers (3 coils) Voltage of 600 V to 120/240 V, 60 Hz, for single-phase transformers (2 coils) Special voltages available upon request

2- NON LINEAR LOAD

Applications :
Non linear loads Installations with isolated ground Protected receptables for hospitals Protected receptables (orange) Installations where noise and transients are a critical problem.

2-18 1-800-663-3582

Back to table of contents


Synonymous of Quality

SUPER ISOLATED TRANSFORMERS Single-Phase - Series VSSC

Copper Series VSSC, Single-phase, Primary 600 V, Secondary 120 / 240 V, ESS, K = 13, 150 C
kVA Mounting Taps Height 5 7.5 10 W/F W/F W/F % 2 x 4.5 2 x 4.5 4 x 2.5 po 21 21 23 mm 533 533 584 po 15 15 17 Dimensions Width mm 381 381 432 po 11 11 12 Depth mm 279 279 305 lb 107 121 153 kg 49 55 69 dB 45 45 50 Weight Noise level

(1) W = Wall mount (2) Taps : SINGLE-PHASE :

F = Floor mount

5 - 7.5 kVA 1 x FCAN, 1 x FCBN 10 kVA 2 x FCAN, 2 x FCBN THREE-PHASE : 10 kVA 2 x FCAN, 2 x FCBN (3) Factors k=4 and k=9 dimensions and weights may be lower that data shown in the table. (4) For dimensions and weights of transformer with K-Factor higher than K=13, consult our customer service. (5) No correspondence between approved type 2, 3R and 4 enclosure. All weights and dimensions are approximate and subject to change without notice.

2- NON LINEAR LOAD

For the electical schematics diagrams see Section 5, page 5-24

SUPER ISOLATED TRANSFORMERS Three-Phase - Series VSTC


Copper Series VSTC, Three-phase, Primary 600 V, Secondary 208Y /120 V, ESS, K = 13, 150 C
kVA Mounting Taps Height 6 10 W/F W/F % 2 x 4.5 4 x 2.5 po 19 21 mm 483 533 po 18 20 Dimensions Width mm 457 508 po 10 12 Depth mm 254 305 lb 119 165 kg 54 75 dB 40 45 Weight Noise level

(1) W = Wall mount (2) Taps : THREE-PHASE :

F = Floor mount

6 kVA 1 x FCAN, 1 x FCBN 10 kVA 2 x FCAN, 2 x FCBN (3) Factors k=4 and k=9 dimensions and weights may be lower that data shown in the table. (4) For dimensions and weights of transformer with K-Factor higher than K=13, consult our customer service. (5) No correspondence between approved type 2, 3R and 4 enclosure. All weights and dimensions are approximate and subject to change without notice.

For the electical schematics diagrams see Section 5, page 5-24

2-19 www.delta.xfo.com

SUPER ISOLATED TRANSFORMERS, C802.2 Single-Phase - Series VS1C and VS3C

Copper Series VS1C, Single-Phase, Primary 600 V, Secondary 120 / 240 V, ESS, K = 13, 150 C
kVA Mounting Taps Height 15 25 37.5 50 75 100 150 200 W/F W/F W/F F F F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po 23 29 29 37 37 46 54 54 mm 584 737 737 940 940 1168 1372 1372 po 17 20 20 22 22 26 31 31 Dimensions Width mm 432 508 508 559 559 660 787 787 po 12 14 14 18 18 21 23 23 Depth mm 305 356 356 457 457 533 584 584 lb 177 265 312 479 565 820 1089 1215 kg 89 137 152 218 279 365 494 577 dB 50 50 50 50 55 55 60 65 Weight Noise level

2- NON LINEAR LOAD

(1) W = Wall mount F = Floor mount (2) Taps : SINGLE-PHASE : 15 - 200 kVA 2 x FCAN, 2 x FCBN THREE-PHASE : 15 - 300 kVA 2 x FCAN, 2 x FCBN (3) Factors k=4 and k=9 dimensions and weights may be lower that data shown in the table. (4) For dimensions and weights of transformer with K-Factor higher than K=13, consult our customer service. (5) No correspondence between approved type 2, 3R and 4 enclosure. All weights and dimensions are approximate and subject to change without notice.

For the electical schematics diagrams see Section 5, page 5-24

Copper Series VS3C, Three-Phase, Primary 600 V, Secondary 208Y / 120 V, ESS, K = 13, 150 C
kVA Mounting Taps Height 15 30 45 50 75 112 150 225 300 W/F W/F W/F W/F F F F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po 27 27 28 28 30 37 37 46 46 mm 686 686 711 711 762 940 940 1168 1168 po 23 23 29 29 30 35 35 44 44 Dimensions Width mm 584 584 737 737 762 889 889 1118 1118 po 13 13 14 14 14 18 18 23 23 Depth mm 330 330 356 356 356 457 457 584 584 lb 229 291 388 399 578 813 1008 1523 1814 kg 104 132 176 181 262 369 457 691 823 dB 45 45 45 45 50 50 50 55 55 Weight Noise level

(1) W = Wall mount F = Floor mount (2) Taps : SINGLE-PHASE : 15 - 300 kVA 2 x FCAN, 2 x FCBN THREE-PHASE : 15 - 300 kVA 2 x FCAN, 2 x FCBN (3) Factors k=4 and k=9 dimensions and weights may be lower that data shown in the table. (4) For dimensions and weights of transformer with K-Factor higher than K=13, consult our customer service. (5) No correspondence between approved type 2, 3R and 4 enclosure. All weights and dimensions are approximate and subject to change without notice.

For the electical schematics diagrams see Section 5, page 5-24

2-20 1-800-663-3582

Back to table of contents


Synonymous of Quality

TRANSFORMERS FOR VARIABLE SPEED DRIVES Series CITC, CI3C, CITA and CI3A
The superior protection for your variable speed drives and motors
All CITC, CI3C, CITA and CI3A Series transformers for variable speed drives meet the most stringent industrial standards on account of their optimal design, superior quality and easy installation.

Benefits and Options :


Special paint (other than ASA 61 grey) 115C and 80C temperature rise Special voltage Type 2, 3R, 4 and sprinklerproof enclosures Quality assurance programs to ISO available upon request

Features :
7,5 to 1 000 KVA Three-phase E.V.I. process (epoxy vacuum impregnation) at no additional cost Primary voltages available: delta 600, 575, 480, 460, 240, 230 Secondary voltages available: wye or delta 575, 480, 460, 240, 230 The three-phase transformers supplied by Delta are 3 coil type with delta-wye or delta-delta connections Copper winding High-quality grain-oriented steel laminations Insulation class 220 Quiet operation

2-21 www.delta.xfo.com

2- NON LINEAR LOAD

VARIABLE SPEED DRIVE TRANSFORMERS Three-Phase - Serie CITC

Copper Series CITC, Three-phase, Type 1, Primary 600 V, Secondary 480 V, ESS, 150 C
kVA Mounting Taps Height 7.5 11 14 W/F W/F W/F % 2 x 4.5 4 x 2.5 4 x 2.5 po 19 21 21 mm 483 533 533 po 18 20 20 Dimensions Width mm 457 508 508 po 10 12 12 Depth mm 254 305 305 lb 119 168 170 kg 54 76 77 dB 40 45 45 Weight Noise level

(1) W = Wall mount (2) Taps :

F = Floor mount

2- NON LINEAR LOAD

600 V PRIMARY ONLY 7.5 kVA 1 x FCAN, 1 x FCBN 11 - 14 kVA 2 x FCAN, 2 x FCBN (3) Taps other than 600V Primary, contact our customer service (4) No correspondence between approved type 2, 3R and 4 enclosure All weights and dimensions are approximate and subject to change without notice. THREE-PHASE :

For the electical schematics diagrams see Section 5, page 5-24

VARIABLE SPEED DRIVE TRANSFORMERS Three-Phase - Serie CITC


Copper Series CITC, Three-phase, Type 3R, Primary 600 V, Secondary 480 V, ESS, 150 C
kVA Mounting Taps Height 7.5 11 14 W/F W/F W/F % 2 x 4.5 4 x 2.5 4 x 2.5 po mm po Dimensions Width Depth mm po mm Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice lb Weight kg Noise level dB

(1) W = Wall mount (2) Taps : THREE-PHASE :

F = Floor mount

600 V PRIMARY ONLY 7.5 kVA 1 x FCAN, 1 x FCBN 11 - 14 kVA 2 x FCAN, 2 x FCBN (3) Taps other than 600V Primary, contact our customer service (4) No correspondence between approved type 1, 2R and 4 enclosure All weights and dimensions are approximate and subject to change without notice.

For the electical schematics diagrams see Section 5, page 5-24

2-22 1-800-663-3582

Back to table of contents


Synonymous of Quality

VARIABLE SPEED DRIVE TRANSFORMERS, C802.2 Three-Phase - Serie CI3C

Copper Series CI3C, Three-phase, Type 1, Primary 600 V, Secondary 480 V, ESS, 150 C
kVA Mounting Taps Height 20 27 34 40 51 63 75 93 118 145 175 220 275 330 W/F W/F W/F W/F W/F W/F W/F F F F F F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po 27 27 27 28 28 28 28 30 37 37 37 46 46 46 mm 686 686 686 711 711 711 711 762 940 940 940 1168 1168 1168 po 23 23 23 29 29 29 29 30 35 35 35 38 44 44 Dimensions Width mm 584 584 584 737 737 737 737 762 889 889 889 965 1118 1118 po 13 13 13 14 14 14 14 14 18 18 18 21 23 23 Depth mm 330 330 330 356 356 356 356 356 457 457 457 533 584 584 lb 229 264 290 341 399 482 506 577 812 850 1006 1215 1521 1811 kg 104 120 132 155 181 219 230 262 369 386 457 552 691 823 dB 45 45 45 45 50 50 50 50 50 50 55 55 55 60 Weight Noise level

2- NON LINEAR LOAD

(1) W = Wall mount (2) Taps :

F = Floor mount

600 V PRIMARY ONLY THREE-PHASE : 20 - 330 kVA 2 x FCAN, 2 x FCBN (3) Taps other than 600V Primary, contact our customer service (4) No correspondence between approved type 2, 3R and 4 enclosure All weights and dimensions are approximate and subject to change without notice.

For the electical schematics diagrams see Section 5, page 5-24

2-23 www.delta.xfo.com

VARIABLE SPEED DRIVE TRANSFORMERS, C802.2 Three-Phase - Serie CI3C


Copper Series CI3C, Three-phase, Type 3R, Primary 600 V, Secondary 480 V, ESS, 150 C
kVA Mounting Taps Height 20 27 34 40 51 63 75 93 118 145 175 220 275 330 W/F W/F W/F W/F W/F W/F W/F F F F F F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po mm po Dimensions Width Depth mm po mm Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice lb Weight kg Noise level dB

2- NON LINEAR LOAD

(1) W = Wall mount (2) Taps :

F = Floor mount

600 V PRIMARY ONLY THREE-PHASE : 20 - 330 kVA 2 x FCAN, 2 x FCBN (3) Taps other than 600V Primary, contact our customer service (4) No correspondence between approved type 1, 2 and 4 enclosure All weights and dimensions are approximate and subject to change without notice.

For the electical schematics diagrams see Section 5, page 5-24

2-24 1-800-663-3582

Back to table of contents


Synonymous of Quality

VARIABLE SPEED DRIVE TRANSFORMERS, C802.2 Three-Phase - Serie CI3A


Aluminum Series CI3A, Three-phase, Type 1, Primary 600 V, Secondary 480V, ESS, 150 C
kVA Mounting Taps Height 20 27 34 40 51 63 75 93 118 145 175 220 275 330 W/F W/F W/F W/F W/F W/F W/F F F F F F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po 27 27 27 28 28 28 28 30 37 37 37 46 46 46 mm 686 686 686 711 711 711 711 762 940 940 940 1168 1168 1168 po 23 23 23 29 29 29 29 30 35 35 35 38 44 44 Dimensions Width mm 584 584 584 737 737 737 737 762 889 889 889 965 1118 1118 po 13 13 13 14 14 14 14 18 18 18 18 21 23 23 Depth mm 330 330 330 356 356 356 356 457 457 457 457 533 584 584 lb 216 249 297 335 370 436 482 599 764 795 982 1175 1384 1686 kg 98 113 135 152 168 198 219 272 347 361 446 534 629 766 dB 45 45 45 45 50 50 50 50 50 50 55 55 55 60 Weight Noise level

2- NON LINEAR LOAD

(1) W = Wall mount (2) Taps :

F = Floor mount

600 V PRIMARY ONLY THREE-PHASE : 20 - 330 kVA 2 x FCAN, 2 x FCBN (3) Taps other than 600V Primary, contact our customer service (4) No correspondence between approved type 2, 3R and 4 enclosure All weights and dimensions are approximate and subject to change without notice.

For the electical schematics diagrams see Section 5, page 5-24

2-25 www.delta.xfo.com

VARIABLE SPEED DRIVE TRANSFORMER, C802.2 Three-Phase - Serie CI3A

Aluminum Series CI3A, Three-phase, Type 3R, Primary 600 V, Secondary 480V, ESS, 150 C
kVA Mounting Taps Height 20 27 34 40 51 63 75 93 118 145 175 220 275 330 W/F W/F W/F W/F W/F W/F W/F F F F F F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po mm po Dimensions Width Depth mm po mm Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice lb Weight kg Noise level dB

2- NON LINEAR LOAD

(1) W = Wall mount (2) Taps :

F = Floor mount

600 V PRIMARY ONLY THREE-PHASE : 20 - 330 kVA 2 x FCAN, 2 x FCBN (3) Taps other than 600V Primary, contact our customer service (4) No correspondence between approved type 2, 3R and 4 enclosure All weights and dimensions are approximate and subject to change without notice.

For the electical schematics diagrams see Section 5, page 5-24

2-26 1-800-663-3582

Back to table of contents


Synonymous of Quality

MITIGATOR E-SERIES, C802.2


Brevet US No. 6,930,578

Stable and reliable power certied high efciency transformers


Over the last 25 years, Delta Transformers has designed and manufactured apparatus using the technology of magnetics to reduce and eliminate harmonic currents in low voltage power distribution systems. With the introduction of the Mitigator e- Series the company has achieved a high efciency benchmark in transformer design and technology.

FIELD ADJUSTABLE PHASE SHIFT*


The Mitigator e-Series comes with optional eld adjustable phase shift on the primary winding, a design that allows selection of the desired primary to secondary phase shift while in the eld. This innovation gives customers maximum exibility to adjust each transformer to suit actual application situations.

CORE AND COIL DESIGN

2- NON LINEAR LOAD

THE DESIGN
The patented* design of the Mitigator e-Series results in a quality unit that is certiable and tested to meet international standards and users preferences. The eld adjustable phase shifting option is rst in its class for the industry, allowing increased exibility in the eld. The assurance of the Delta Quality process is enhanced by the application of an epoxy vacuum impregnation - E.V.I. process, which provides superior environmental protection for all units.

The Mitigator e- Series core is designed using non-aging silicon steel with a three leg common core topology. Its coils are built with electrolytic copper magnetic wire, geometrically designed to allow for uniform cooling. This combined design is such that transformer direct and zero sequence impedance are maintained at a level that reduces voltage distortion generated by harmonic currents.

EPOXY VACUUM IMPREGNATION E.V.I. PROCESS


An epoxy compound is applied to the Mitigator e- Series core and coil in a sealed vacuum pressure tank during production, impervious to cracking or peeling, this compound increases the mechanical strength of the unit and reduces noise emissions.The E.V.I. process enhances transformer performance by improving the winding insulation. The Mitigator e- Series with E.V.I. performs in protecting carefully the core and coil, particularly in heavily contaminated environments.

THE EXPERIENCE
With more than 25 years experience in transformers design and manufacturing, Delta Transformers has introduced the latest in its line of industry leading products: the Mitigator e-Series. This family of transformers, whose primary function is the mitigation of harmonics in typical low voltage power distribution systems, is available in : e-Platinum, e-Gold and e-Silver congurations. These variations give customers the exibility to choose the right product for each unique application.

THE QUALITY
The Mitigator e-Series provides the industry with a new standard for transformers designed to mitigate harmonics present in typical commercial, institutional and industrial environments. Firsts in its class, the Mitigator e-Series leads the industry in both price and performance.

2-27 www.delta.xfo.com

MITIGATOR E-SERIES, C802.2

TESTED AND CERTIFIED TO MEET HIGH EFFICIENCY STANDARDS PER CSA C802.2, NEMA TP-1 / Energy Star requirements
Designed to individual specifications, each unit in the Mitigator e- Series is also built to strict international standards, including CSA standards. Units are performance tested and certified at Delta Transformers state of the art certifying test facilities, where customers are invited to observe the process.

The Delta primary zigzag secondary transformer (-15, -45 or 0, -30 ) Double output three phase secondary Cancellation of the 3rd, 5th, 7th, 9th, 15th, 17th and 19th harmonics Elimination of the 11th and 13th harmonics (by utilizing the phase shift between the transformer windings so that these currents subtract at the common bus with 11th and 13th harmonic currents existing at the bus) Improved power factor

2- NON LINEAR LOAD

Three-Phase, 60 Hz systems display a characteristic 120 degrees shift between each phase. On systems with balanced loads, the neutral current is zero. Loads that result in the generation of harmonics and the distortion of current and voltage present different characteristics and require specific transformer configurations.

EXAMPLES
The Delta primary zigzag secondary (0 or -30) Single output three phase secondary 0 or -30 phase shift from primary to secondary The 3rd 9th and 15th harmonic currents are concelled by flux opposition at low impedance Reduction of current imbalance Less voltage distortion due to low zero-sequence impedance Improved power factor

The Mitigator e- Series offers three distinct models to address the full scope of harmonic mitigation applications. The patented* field adjustable phase shifting feature is available on each model. The enclosure is a Type 2, with options available for Type 1 and 3R enclosures. The Mitigator e-Series like all Delta Transformers products, are manufactured using the Epoxy Vacuum Impregnation E.V.I. Process. Benefits include : Increased mechanical strength Reduced noise Improved winding insulation Enhanced performance in heavily contaminated areas

Delta Transformers is truly a canadian success story. It has been in existence for over twenty five years and continues to be one of the leading canadian suppliers of transformers and associated magnetic products. Its commitment to the market has been demonstrated by its distribution products life time warranty and the high caliber of agents it has located across the continent, consistently responding to the needs of customers. Delta Transformers continues on the road of excellence with the introduction of the Mitigator e- Series.

2-28 1-800-663-3582

Back to table of contents


Synonymous of Quality

MITIGATOR E-SERIES, C802.2

Mitigator e-Platinum
K-factor profile of 20, suitable for health care environments (including operation rooms) and critical electronic applications such as radar and radio. High efficiency characteristics from 35% - 100% load requirements.

Mitigator e-Gold
K-factor profile of 20, suitable for data centers, computer services and critical loads high efficiency characteristics at 35% load requirements.

2- NON LINEAR LOAD

Mitigator e-Silver
K-factor profile of 13, suitable for most general-purpose applications. High efficiency characteristics at 35% load requirements.

NOTE
All Mitigator e-Series products are tested and certified to meet High Efficiency Standards per CSA C802.2-00, NEMA TP-1 requirements.

APPLICATIONS
Health care institutions Commercial office buildings Condominiums Airport transportation facilities Industrial applications

2-29 www.delta.xfo.com

MITIGATOR E-SERIES

MODEL
K Factor Load Profile Temperature Rise 13 150C Standard 4,0 - 6,5 % 20 130C IZo < 0,95 IXo < 0,30 Up to 75 kVA : 2,5 - 4,0 % 112,5 - 300 kVA : 5,0 % max. At 35 %
Loading

20 130C IZo < 0.95 IXo < 0.30


Up to 75 kVA : 2,5 - 4,0 % 112,5 - 300 kVA : 5,0 % max.

2- NON LINEAR LOAD

Zero Sequence Impedance Standard Impedance

Efficiency per C802.2-00 Electrostatic Shield Field Adjustable Phase Shift* Double output Enclosure Warranty

At 35 %
Loading

From 35 % to 100 %
Loading

Yes Optional Optional Type 2 10 years pro-rated

Yes Optional Optional Type 2 10 years pro-rated

Yes Optional Optional Type 2 10 years pro-rated

Trade Marks Certification

* Patent US No. 6,930,578

2-30 1-800-663-3582

Back to table of contents


Synonymous of Quality

MITIGATOR E-SERIES C802.2 HARMONIC MITIGATION TRANSFORMERS TECHNICAL SPECIFICATONS


Serie Mitigator e-Silver, single output
Energy savings : Harmonic Treatment : Load Compatibility : Load Imbalance : Windings : Secondary Windings : Phase Shift : Zero Sequence Data : Voltage Distortion : Certified Performance : Nameplate Impedance : Inslulation Class : Operating Temperature Rise : Efficiency : Electrostatic Shield: Impregnation Method : Construction Standards : Certification / Labeling : Neutral Rating : Frequency : Taps : Type : Sound Level : Enclosure : Warranty : OPTIONS 1. Dual Output : 2. Field Adjustable Phase Shifts* : 3. Operating Temperature Rise : 4. Enclosure : 5. Thermocouples : 6. Thermal Sensors : 7. TVSS : 8. Custom Color: Standard Product : Substitution : Acceptable Manufacturer : 0/-30 and -15/-45 mitigates 3rd, 5th, 7th, 9th, 15th, 17th, 19th... on the secondary and 11th,13th... with 15 phase shift on the primary common bus +15, -15, 0 supplementary phase shift 80 C, 115 C Open-type, Type 3R, Sprinkler-proof Type K, one per leg in the secondary winding NO or NC contact set at 200 C, one per leg in the secondary winding 80 000 Amps per mode surge surrent capacity, UL 1449 Approved. Specify Product must be standard item in manufacturers published catalog. Non linear test bench certified. Custom desigh and / or packaging to meet this specification are not acceptable. Alternate must be approved by the engineer 10 days prior to bid closing, subject to meeting all aspects of this specification. Delta Transformers Inc., MITIGATOR e-Silver series. Transformer must be certified and bear the CSA C802.2 3rd, 9th, 15th... on the secondary and 5th, 7th, 17th, 19th... with 30 phase shift on the primary common bus K-13 load profile, crest factor of 3 Reduction of fundamental current imbalance from secondary to primary of transformer Copper Wound to mitigate zero sequence current flux. These zero-sequence currents shall no be coupled into the primary winding of the transformer. Windings configured to provide primary-to-secondary phase shift of -30 or 0 (as specified on drawings) Standard Non Linear Loads test bench certified Non Linear Loads test bench cerfified 4.0 6.5% (up to 300 kVA) Class 220 150 C As per CSA C802.2 Program at 35% loading Single shield Epoxy Vacuum Impregnation Applicable NEMA, CSA and ANSI/IEEE standards CSA C22.2 No 47, CSA C802.2 200% of rated secondary phase current 60 Hz 4 x 2.5% full capacity taps (2-FCBN + 2-FCAN) Three-phase, common core, dry-type convection air cooled Per CSA C9, NEMA ST-20 Type 2, ASA #61 grey 10 years pro-rated with limited liabililty

2-31 www.delta.xfo.com

2- NON LINEAR LOAD

MITIGATOR E-SERIES C802.2 HARMONIC MITIGATION TRANSFORMERS TECHNICAL SPECIFICATONS

2- NON LINEAR LOAD

Copper e-Silver DZ(0) Serie VZ3C, Three-phase, Type 2, Primary 600 V, Secondary 208/120V, load profile K13, ESS, 150 C
kVA Mounting Taps Height 15 30 45 75 112.5 150 225 300 W/F W/F W/F F F F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po 27 28 28 37 37 37 46 46 mm 686 711 711 940 940 940 1168 1168 po 23 29 29 35 35 35 44 44 Dimensions Width mm 584 737 737 889 889 889 1118 1118 po 13 14 14 18 18 18 23 23 Depth mm 330 356 356 457 457 457 584 584 lb 227 345 444 660 873 1032 1531 1806 kg 103 157 202 300 397 469 696 821 dB 45 45 45 50 50 50 55 55 Weight Noise level

(1) W = Wall mount F = Floor mount (2) Taps : THREE-PHASE : 15 - 300 kVA 2 x FCAN, 2 x FCBN (3) All weights and dimensions are subject to change without notice.

Copper e-Silver DZ(0) Serie VZ3C, Three-phase, Type 3R, Primary 600 V, Secondary 208/120V, Load profile K13, ESS, 150 C
kVA Mounting Taps Height 15 30 45 75 112.5 150 225 300 W/F W/F W/F F F F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po mm po Dimensions Width Depth mm po mm Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice lb Weight kg Noise level dB

(1) W = Wall mount F = Floor mount (2) Taps : THREE-PHASE : 15 - 300 kVA 2 x FCAN, 2 x FCBN (3) All weights and dimensions are subject to change without notice.

2-32 1-800-663-3582

Back to table of contents


Synonymous of Quality

MITIGATOR E-SERIES C802.2 HARMONIC MITIGATION TRANSFORMERS TECHNICAL SPECIFICATONS


Serie Mitigator e-Gold, single output
Energy Savings : Harmonic Treatment : Load Compatibility : Load Imbalance : Windings : Secondary Windings : Phase Shift : Zero Sequence Data : Voltage Distortion : Certified Performance : Nameplate Impedance : Insulation Class : Operating Temperature Rise : Efficiency : Electrostatic Shield : Impregnation Method : Construction Standards : Certification / Labeling : Neutral Rating : Frequency : Taps : Type : Sound Level : Enclosure : Warranty : OPTIONS 1. Dual Output : 2. Field Adjustable Phase shift* : 3. Operating Temperature Rise : 4. Enclosure : 5. Thermocouples : 6. Thermal Sensors : 7. TVSS : 8. Custom Color : Standard Product : Substitution : Acceptable Manufacturer : 0/-30 and -15/-45 mitigates 3rd, 5th, 7th, 9th, 15th, 17th, 19th... on the secondary and 11th,13th... with 15 phase shift on the primary common bus +15, -15, 0 supplementary phase shift 80 C, 115 C Open-type, Type 3R, sprinkler-proof Type K, one per leg in the secondary winding NO and NF contact set at 200 C, one per leg in the secondary winding 80 000 Amps per mode surge current capacity, UL 1449 approved, EMI / RFI filtering Specify Product must be standard item in manufacturers published catalog. Non linear test bench certified. Custom design and / or packaging to meet this specification are not acceptable. Alternate must be approved by the engineer 10 days prior to bid closing, subject to meeting all aspects of this specification Delta Transformers Inc. MITIGATOR e-Gold Series Transformers must be certified and bear the CSA C802.2 3rd, 9th, 15th... on the secondary and 5th, 7th, 17tt, 19th... with 30 phase shift on the primary common bus K-20 load profile, crest factor of 5 Reduction of fundamental current imbalance from secondary to primary of transformer Copper Wound to mitigate zero sequence surrent flux. These zero-sequence currents shall not be coupled into the primary windings of the transformer. Windings configured to provide primary-to-secondary phase shift of -30 or 0 (as specified on drawings) Less than 0.95% ZS impedance, less than 0.3% ZS reactance Non linear load test bench certified Non linear load test bench certified 2.5 4.0% (up to 75 kVA), 5.0% max (112.5-300 kVA) Class 220 130 C As per CSA C802.2 program at 35% loading Single shield Epoxy vacuum impregnation Applicable NEMA, CSA, and ANSI/IEEE standards CSA C22.2 No 47, CSA C802.2 200% of rated secondary phase current 60 Hz 4 x 2.5% full capacity taps (2-FCBN + 2-FCAN) Three-phase, common core, dry-type, convection air cooled Per CSA C9, NEMA ST-20 Type 2, ASA #61 grey 10 years pro-rated, with limited liability

2-33 www.delta.xfo.com

2- NON LINEAR LOAD

MITIGATOR E-SERIES C802.2 HARMONIC MITIGATION TRANSFORMERS TECHNICAL SPECIFICATONS

Copper e-Gold DZ(0) Serie VZ3C, Three-phase, Type 2, Primary 600 V, Secondary 208/120V, Load profile K20, ESS, 130 C

2- NON LINEAR LOAD

kVA

Mounting

Taps Height % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po 27 28 28 37 46 46 46 46 mm 686 711 711 940 1168 1168 1168 1168

Dimensions Wiidth po 23 29 29 35 38 38 44 44 mm 584 737 737 889 965 965 1118 1118 po 12 14 14 18 21 21 23 23 Depth mm 305 356 356 457 533 533 584 584

Weight lb 277 1039 453 664 1005 1170 1635 1940 kg 126 195 206 302 457 532 743 882

Noise level dB 45 45 45 50 50 50 55 55

15 30 45 75 112.5 150 225 300

W/F W/F W/F F F F F F

(1) W = Wall mount F = Floor mount (2) Taps : THREE-PHASE : 15 - 300 kVA 2 x FCAN, 2 x FCBN (3) All weights and dimensions are subject to change without notice.

Copper e-Gold DZ(0) Serie VZ3C, Three-phase, Type 3R, Primary 600 V, Secondary 208/120V, Load profile K20, ESS, 130 C
kVA Mounting Taps Height 15 30 45 75 112.5 150 225 300 W/F W/F W/F F F F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po mm po Dimensions Wiidth Depth mm po mm Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice lb Weight kg Noise level dB

(1) W = Wall mount F = Floor mount (2) Taps : THREE-PHASE : 15 - 300 kVA 2 x FCAN, 2 x FCBN (3) All weights and dimensions are subject to change without notice.

2-34 1-800-663-3582

Back to table of contents


Synonymous of Quality

MITIGATOR E-SERIES C802.2 HARMONIC MITIGATION TRANSFORMERS TECHNICAL SPECIFICATONS

Copper e-Gold FAPST-Z(-15/0/+15) Serie VZ3C, Three-phase, Type 2, Primary 600 V, Secondary 208/120V, load profile K20, ESS, 130 C
kVA Mounting Taps Height 15 30 45 75 112.5 150 225 300 W/F W/F W/F F F F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po 28 28 28 37 46 46 46 46 mm 711 711 711 940 1168 1168 1168 1168 po 29 29 29 35 38 38 44 44 Dimensions Width mm 737 737 737 889 965 965 1118 1118 po 14 14 14 18 21 21 23 23 Depth mm 356 356 356 457 533 533 584 584 lb 328 442 508 766 1032 1239 1784 2171 kg 149 201 231 348 469 563 811 987 dB 45 45 45 50 50 50 55 55 Weight Noise level

2- NON LINEAR LOAD

(1) W = Wall mount F = Floor mount (2) Taps : THREE-PHASE : 15 - 300 kVA 2 x FCAN, 2 x FCBN (3) All weights and dimensions are subject to change without notice.

Copper e-Gold FAPST-Z(-15/0/+15) Serie VZ3C, Three-phase, Type 3R, Primary 600 V, Secondary 208/120V, load profile K20, ESS, 130 C
kVA Mounting Taps Height 15 30 45 75 112.5 150 225 300 W/F W/F W/F F F F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po mm po Dimensions Width Depth mm po mm Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice lb Weight kg Noise level dB

(1) W = Wall mount F = Floor mount (2) Taps : THREE-PHASE : 15 - 300 kVA 2 x FCAN, 2 x FCBN (3) All weights and dimensions are subject to change without notice.

2-35 www.delta.xfo.com

MITIGATOR E-SERIES C802.2 HARMONIC MITIGATION TRANSFORMERS TECHNICAL SPECIFICATONS


Serie Mitigator e-Platinum, single output
Energy Savings : Harmonic Treatment : Load Compatibility : Load Imbalance : Windings : Secondary Windings : Transformer must be certified and bear the CSA C802.2 3rd, 9th, 15th... on the secondary and 5th, 7th, 17th, 19th... with 30 phase shift on the primary common bus K-20 load profile, crest factor of 5 Reduction of fundamental current imbalance from secondary to primary of transformer Copper Wound to mitigate zero sequence current flux. These zero-sequence currents shall not be coupled into the primary winding of the transformer. Windings configuration to provide primary-to-secondary phase shift of -30 or 0 (as specified on drawings) Less than 0.95% ZS impedance, less that 0.3% ZS reactance Non linear loads test bench certified Non linear loads test bench certified 2.5 4.0% (up to 75 kVA), 5.0% (112.5-300 kVA) Class 220 130 C As per CSA C802.2 Program from 35% to 100% loading Single Shield Epoxy vacuum impregnation Applicable NEMA, CSA, and ANSI/IEEE standard CSA C22.2 No 47, CSA C802.2 200% of rated secondary phase current 60 Hz 4 x 2.5% Full capacity taps, (2-FCBN + 2-FCAN) Three-phase common core, dry-type, convection air cooled Per CSA C9, NEMA ST-20 Type 2, ASA #61 Grey 10 year pro-rated, with limited liability 0/-30 and -15/-45 mitigates 3rd, 5th, 7th, 9th, 15th, 17th, 19th... on the secondary and 11th,13th... with 15 phase shift on the primary common bus +15, -15, 0 supplementary phase shift 80 C, 115 C Open type, Type 3R, Sprinkler-proof Type K, one per leg in the secondary winding NO or NC, contact set at 200 C, one per leg in the secondary winding 80 000 Amps per mode surge current capacity, UL 1449 approved, EMI / RFI filtering Specify Product must be standard item in manufacturers published catalog. Non linear test bench certified. Custom design and / or packaging to meet this specification are not acceptable. Alternate must be approved by the engineer 10 days prior to bid closing. subject to meeting all aspects of this specification Delta Transformers Inc., Serie MITIGATOR e-Platinum

2- NON LINEAR LOAD

Phase shift Zero sequence Data : Voltage Distortion : Certified Performance : Nameplate Impedance: Insulation Class : Operation Temperature Rise : Efficiency : Electrostatic Shield : Impregnation Method : Construction Standards : Certification / Labeling : Neutral Rating : Frequency : Taps : Type : Sound Level : Enclosure : Warranty : OPTIONS 1. Dual Output : 2. Field Adjustable Phase Shifts* : 3. Operation Temperature Rise : 4. Enclosure : 5. Thermocouples : 6. Thermal Sensors : 7. TVSS : 8. Custom Color: Standard Product : Substitution :

2-36

Acceptable Maufacturer:

1-800-663-3582

Back to table of contents


Synonymous of Quality

MITIGATOR E-SERIES C802.2 HARMONIC MITIGATION TRANSFORMERS TECHNICAL SPECIFICATONS

Copper e-Platinum DZ(0) Serie VZ3C, Three-phase, Type 2, Primary 600 V, Secondary 208/120V, Load profile K20, ESS, 130 C
kVA Mounting Taps Height 15 30 45 75 112.5 150 225 300 W/F W/F W/F F F F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po 27 28 30 37 37 46 46 46 mm 686 711 762 940 940 1168 1168 1168 po 23 29 30 35 35 38 44 44 Dimensions Width mm 584 737 762 889 889 965 1118 1118 po 12 14 14 18 18 21 23 23 Depth mm 305 356 356 457 457 533 584 584 lb 277 451 557 829 1067 1393 2002 2636 kg 126 205 253 377 485 633 910 1198 dB 45 45 45 50 50 50 55 55 Weight Noise level

2- NON LINEAR LOAD

(1) W = Wall mount F = Floor mount (2) Taps : THREE-PHASE : 15 - 300 kVA 2 x FCAN, 2 x FCBN (3) All weights and dimensions are approximate and subject to change without notice.

Copper e-Platinum DZ(0) Serie VZ3C, Three-phase, Type 3R, Primary 600 V, Secondary 208/120V, Load profile K20, ESS, 130 C
kVA Mounting Taps Height 15 30 45 75 112.5 150 225 300 W/F W/F W/F F F F F F % 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 po mm po Dimensions Width Depth mm po mm Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice Consult our Customer Sevice lb Weight kg Noise level dB

(1) W = Wall mount F = Floor mount (2) Taps : THREE-PHASE : 15 - 300 kVA 2 x FCAN, 2 x FCBN (3) All weights and dimensions are approximate and subject to change without notice.

2-37 www.delta.xfo.com

3- POWER
3-2 1-800-663-3582

Back to table of contents


Synonymous of Quality

POWER

Power your future

Power Transformers Dry Type

SECTION 3

Advantages of the E.V.I. Process

E.V.I. Power Transformer 3-1 www.delta.xfo.com

3- POWER
3-2 1-800-663-3582

Back to table of contents


Synonymous of Quality

POWER TRANSFORMERS
Power your future
Delta Transformers specializes in the design and manufacture of Dry Type power transformers of up to 15 000 kVA and 34.5 kV class. With its modern plant and equipment, Delta Transformers caters to all your power transformer needs. Delta Transformers power transformers are ideal for industrial, institutional and commercial applications.

FACILITIES
Our manufacturing plant with power transformer building capacity, located in Granby, is fully integrated and equipped to handle special requirements and coordination from engineering to shipping.

SERVICE ADVANTAGES
Quick on-time delivery Troubleshooting, repair, eld support Service and retrot on all known brand names

Our Speciality, is Flexibility


Our manufacturing methods allow custom designs for special needs..

RNCan REGULATIONS
(Natural Resources Canada) Dry Type Transformers CSA C802.2

Performance and Value


Delta Transformers has the ability to generate new and creative solutions to meet the changing needs of the industry. With over 150 years experience in special application transformer design, our engineers can meet your most demanding application requirements. Quality material, safe construction, conservative designs backed by our quality assurance program ensure troublefree performance for the life of the transformer. Quality fabrication with proven insulation materials and testing with state-of-the-art equipment assures reliability and safety. Optimized computer design systems are used to analyse dielectric, magnetic and thermal effets to maximize the life of your transformers. Automated drafting is used for design accuracy. From design to approval for shipments, integrated MRP and scheduling systems coupled with our exibility, ensure ontime delivery.

Our Product Range


Dry Type Power Transformers up to 15 000 kVA and 34.5 kV class are offered with or without a wide range of enclosures suitable for indoor and outdoor installations. Our Dry Type transformer line manufactured in Granby Quebec facility complements the complete General Purpose transformer line offered by Delta Transformers. We can design to meet the most demanding space and performance criteria to the latest ANSI, IEEE and CSA standards.

3-3 www.delta.xfo.com

3- POWER

ADVANTAGES OF DRY TYPE TRANSFORMERS


BPC transformers replacement
1. 2. 3. 4. No oil as medium (other than air) for dielectric insulation; Proven for decades of interior installations across Canada; Solutions for more than 95 % of new installations following the regulations for the abolition of BPC; Liquid lled transformers for domestic use are no less expensive than dry type transformers ... Liguid for domesic use is much more expensive than oil for outdoor transformers not the same liquid is used; Delivery time usually longer for liquid lled transformers; Maintenance program is more expensive (periodic checks of oils by specialized external rm); Core and coils are much more accessible on a dry-type transformer; A retention basin is required with liquid lled transformer; Insurance for buildings is more expensive because of the liquid in a transformer : greater risks of loss and damage; 13. The transformer enclosure is of a knockdown construction allowing for easy assembly and disassembly at their nal locations on sites with restrictions; 14. In the majority of its projects, Delta was able to provide compact arrangements to meet the oor space available for these replacements; 15. Delta has achieved a high level of competence in the replacement of BPC transformers, including the site measurements and any technical assistance as needed.

5. 6. 7. 8. 9.

PERFORMANCE FIRST: E.V.I. AT NO ADDITIONAL COST


Every Delta Transformers is epoxy vacuum Impregnated (E.V.I.) at no additional cost. The E.V.I. process features the following benets : Increased mechanical strength; Reduced noise; Improved winding insulation; Superior partial discharge performance; Compatible with cast coil performance; Enhanced performance in heavily contaminated environments.

3- POWER

10. The concept of an oil lled transformer is not considered a solution in harmony with environmental protection; 11. The total cost of replacement of a BPC transformer by another liquid lled transformer is often more expensive if you consider all the extra infrastructure work (basin), insurance and maintenance costs; 12. Delta has successfully completed several projects to replace BPC lled transformers in recent years. Not too necessarily to compete head on with a liquid lled but on an environmental approach and long-term reliability, performance and lower maintenance costs;

This resin-based product is an ideal coating agent. In addition to their superior quality, transformers with E.V.I. have a longer life.

3-4 1-800-663-3582

Back to table of contents


Synonymous of Quality

( E.V.I. ) EPOXY VACUUM IMPREGNATION


The advantages of a cast coil without the inconveniences

E.V.I. Process
MECHANICAL

Advantages of the Delta Transformers

ELECTRICAL
With the Delta Transformers E.V.I design, as opposed to cast-coil, the epoxy resin is not part of the insulation system. Its function is purely mechanical: a great sealer to protect a great transformer. In fact, in the Delta Transformers E.V.I.: the insulation media are Nomex and air.

Both cast coil and Delta Transformers E.V.I. process make use of epoxy as an environmental protection.

EPOXY ENCAPSULATION VS. EPOXY CASTING


In a cast epoxy transformer, the resin is the major part of the insulation system. In the Delta Transformers E.V.I. Nomex and air are the insulation media; epoxy is used for its environmental protective properties only. The Delta Transformers E.V.I. gives improved performance since its encapsulation is not subject to cracking which is often related to solid epoxy casting.

THE DELTA TRANSFORMERS E.V.I. EPOXY


The Delta Transformers E.V.I. Power Transformers are recommended for use in very humid and hostile environments. Typical applications would be:

NO CRACKS
The Delta Transformers E.V.I. process has totally eliminated the cracking problems which could occur in a solid cast insulation, due to temperature differentials through the thickness of the resin and the thermal expansion of the coils. In the Delta Transformers E.V.I. design, the epoxy is thick enough to provide environmental protection but thin enough that internal stresses do not develop. Since the coils are self-supporting, it enables us to use a exible form of epoxy which will accommodate the expansion and contaction of the coil which it protects.

automotive industry; pulp and paper mills; stell mills; mines; water treatment plants; cement plants; chemical plants; and other industrial locations where the atmosphere is especially humid, dirty and/or corrosive, including outdoor and marine applications such as shipyards and offshore drillings rigs.

3- POWER

INHERENTLY STRONG
The Delta Transformers E.V.I design is inherently strong and self-supporting. The Delta Transformers E.V.I. epoxy being highly exible, it can endure thermal and mechanical stresses without cracking. In a solid cast epoxy transformers, it is usually necessary to incorporate spring type pressure blocks and berglass reinforcements to combat stresses between components in order to minimize cracking.

3-5 www.delta.xfo.com

WE BUILD FOR THE FUTURE

OUR PEOPLE : YOUR PARTNERS


All of our employees are committed to producing the highest quality Dry Type transformers. Well-trained tradespeople combine their skills with those of qualified and experienced engineers, technicians and drafting personnel to design and manufacture highly efficient products that consistently meet customer requirements. Our teams expertise in the design and manufacture of power transformers gives us the ability to create innovative solutions to application problems. Our success in the power transformer market confirms the ability of our people to deliver high-tech products on time. Our experienced customer service team can help you and your clients with any technical or logistic issue at all times. Our before and after-sale service is second to none.

RESEARCH AND DEVELOPMENT


Equipped with their own lab and specialized simulation software, our research and development engineers continously work at improving designs, methods and materials.

ENVIRO GUARD
OPTIMIZED EPOXY VACUUM IMPREGNATION FOR HARSH ENVIRONMENT

3- POWER

Maximize sealing of windings and conductor leads. Improved resistance to shrinking and cracking during lifetime operation. Provide hydrolytic stability under electrical stress, environmental contamination or abrupt temperature variatuion.

3-6 1-800-663-3582

Back to table of contents


Synonymous of Quality

POWER TRANSFORMERS
Dry-Type - Class 5 KV, 15 KV, 25 KV, and 34,5KV
Mechanical Characteristics Standard and options Cooling
Type ANN Possible combinations based on diagrams 1, 3, 9 (HT) and B, C, G (BT) with alternate outputs (left or right). Special dimensions for outputs and mounting holes on connections. Other connections may be available upon request and with specificaitons.

Options
AFN (fan-cooled) Provision for AFN

Options and Accessories


Temperature probes in windings Temperature indicators with 2 or 3 contacts Fans Control panel Terminals, flexible connectors and other types for outputs Provision for pads to facilitate moving Lighting arrester Grounding resistor Electrostatic shield Designed for use with rectifiers

Enclosures
Type 1, steel ASA 61 grey.

Options
Special color or finish Front or rear access only Doors with locks or mechanical interlocks

3- POWER

Connection Coordination
Position of LV and HV outlets, based on combination 1B opposite .

(1)

(B)

(3)

(C)

(9)
Vue de dessus Connexions HT Vue de droite

(G)
Vue de gauche Vue de dessus

Connexions BT

Options www.delta.xfo.com

3-7

POWER TRANSFORMERS C802.2


Dry-Type - Class 5 KV, 15 KV, 25 KV, and 34,5KV
Copper Class 5kV, Three-phase, Primary 4160 V, Secondary 600Y / 346 V, 150 C, BIL 30kV
kVA Mounting Impe(1) dance Taps (2) Dimensions Core & Coils (Figure 1) Weight Dimensions including enclosure (cable in / cable out) (Figure 2) Weight Noise level

150 225 300 450 500 600 750 1000 1250 1500 2000 2500

F F F F F F F F F F F F

5.5 6.7 4.5 5.5 5.5 6 6 6 6 6 6 6.5

% 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5

Height (A) po mm 34 864 36 42 46 50 49 54 59 58 59 67 66 914 1067 1168 1270 1245 1372 1499 1473 1499 1702 1676

Width (B) po mm 40 1016 46 46 48 48 56 56 56 64 66 66 74 1168 1168 1219 1219 1422 1422 1422 1626 1676 1676 1880

Depth (C) po mm 23 584 28 29 29 29 30 30 30 33 34 36 38 711 737 737 737 762 762 762 838 864 914 965

lb 1278 1566 1906 2423 2694 2955 3464 4210 5112 6056 7461 8902

kg 580 710 865 1099 1222 1340 1571 1910 2319 2747 3384 4038

Height (A) po mm 46 1168 46 58 60 60 80 80 80 80 80 90 90 1168 1473 1524 1524 2032 2032 2032 2032 2032 2286 2286

Width (B) po mm 44 1118 44 50 60 60 73 73 73 73 73 80 90 1118 1270 1524 1524 1854 1854 1854 1854 1854 2032 2286

Depth (C) po mm 23 584 23 26 33 33 45 45 45 45 45 54 54 584 660 838 838 1143 1143 1143 1143 1143 1372 1372

lb 1478 1816 2156 2873 3144 3455 3964 4710 5612 6556 8134 9630

kg 670 824 978 1303 1426 1567 1798 2136 2546 2974 3690 4368

dB 55 58 58 60 60 62 64 64 64 65 66 68

(1) F = Floor mount Winding terminals with connections above coils (no busbar coordination) (2) Taps : (3) No correspondence between approved type 2, 3R and 4 enclosures All weights and dimensions are approximate and subject to change without notice.

See page 3-9 for figure 1 and 2

Copper Class 15kV, Three-phase, Primary 12470 V or 13800 V, Secondary 600Y / 346 V, 150 C, BIL 95kV

3- POWER

kVA

Mounting Impe(1) dance

Taps (2)

Dimensions Core & Coils (Figure 1)

Weight

Dimensions including enclosure (cable in / cable out) (Figure 2)

Weight

Noise level

500 750 1000 1250 1500 2000 2500 3000 3750

F F F F F F F F F

5.5 6 6 6 6 6.5 6.5 7 7.5

% 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5

Height (A) po mm 59 1499 64 67 68 69 71 76 77 86 1626 1702 1727 1753 1803 1930 1956 2184

Width (B) po mm 60 1524 60 64 65 66 72 75 78 79 1524 1600 1651 1676 1829 1905 1981 2007

Depth (C) po mm 30 762 31 33 35 37 38 40 40 44 787 838 889 940 965 1016 1016 1118

lb 3537 4194 5106 5954 6741 8623 10245 11475 12855

kg 1604 1902 2316 2701 3058 3911 4647 5205 5831

Height (A) po mm 80 2032 90 90 90 90 90 100 100 100 2286 2286 2286 2286 2286 2540 2540 2540

Width (B) po mm 80 2032 80 80 90 90 90 90 100 100 2032 2032 2286 2286 2286 2286 2540 2540

Depth (C) po mm 54 1372 54 54 54 54 54 54 60 60 1372 1372 1372 1372 1372 1372 1524 1524

lb 4146 4867 5779 6882 7469 9351 11041 12374 13754

kg 1881 2208 2621 3031 3388 4242 5008 5613 6239

dB 60 64 64 65 65 66 68 68 71

(1) F = Floor mount Winding terminals with connections above coils (no busbar coordination) (2) Taps : (3) No correspondence between approved type 2, 3R and 4 enclosures All weights and dimensions are approximate and subject to change without notice.

See page 3-9 for figure 1 and 2

3-8 1-800-663-3582

Back to table of contents


Synonymous of Quality

POWER TRANSFORMERS C802.2


Type sec - Classes 5 KV, 15 KV, 25 KV, et 34,5KV
Copper Class 25kV, Three-phase, Primary 24940 V, Secondary 600Y / 346 V, 150 C, BIL 125kV
kVA Mounting Impe(1) dance Taps (2) Dimensions Core & Coils (Figure 1) Weight Dimensions including enclosure (cable in / cable out) (Figure 2) Weight Noise level

500 750 1000 1250 1500 2000 2500 3000 3750 5000

F F F F F F F F F F

6 6.5 6.5 6.5 6.5 7 7 7.5 8 8

% 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5

Height (A) po mm 63 1600 66 68 73 75 83 84 85 88 94 1676 1715 1854 1892 2086 2140 2165 2235 2381

Width (B) po mm 72 1829 74 75 75 75 81 82 84 88 100 1880 1905 1905 1905 2057 2083 2134 2235 2381

Depth (C) po mm 31 781 35 37 37 37 39 40 45 45 51 889 927 927 933 997 1010 1130 1137 1289

lb 4882 5797 6711 7333 7955 9918 11274 12602 14727 20251

kg 2214 2629 3044 3326 3608 4499 5114 5716 6680 9186

Height (A) po mm 90 2286 90 100 100 100 110 110 110 120 120 2286 2540 2540 2540 2794 2794 2794 3048 3048

Width (B) po mm 100 2540 100 100 100 100 110 110 110 110 120 2540 2540 2540 2540 2794 2794 2794 2794 3048

Depth (C) po mm 60 1524 60 66 66 66 66 66 66 66 72 1524 1676 1676 1676 1676 1676 1676 1676 1829

lb 5740 6655 7663 8285 7955 11037 12393 13721 15917 21568

kg 2604 3018 3476 3758 3608 5006 5621 6224 7220 9783

dB 63 67 67 68 68 69 71 71 74 76

(1) F = Floor mount Winding terminals with connections above coils (no busbar coordination) (2) Taps : (3) No correspondence between approved type 2, 3R and 4 enclosures All weights and dimensions are approximate and subject to change without notice.

Figure 1

Figure 2

3-9 www.delta.xfo.com

3- POWER

POWER TRANSFORMERS C802.2


Dry Type - Class 5 KV, 15 KV, 25 KV, and 34,5KV
Aluminum Class 5kV, Three-phase, Primary 4160 V, Secondary 600Y / 346 V, 150 C, BIL 30kV
kVA Mounting Impe(1) dance Taps (2) Dimensions Core & Coils (Figure 1) Weight Dimensions including enclosure (cable in / cable out) (Figure 2) Weight Noise level

150 225 300 450 500 600 750 1000 1250 1500 2000 2500

F F F F F F F F F F F F

5 5.5 5 6 5 6.2 6 6 6 6 6 6.5

% 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5

Height (A) po mm 35 889 43 47 49 52 48 52 60 65 60 67 66 1092 1194 1245 1321 1219 1321 1524 1651 1524 1702 1676

Width (B) po mm 40 1016 46 46 48 48 56 60 60 61 69 66 74 1168 1168 1219 1219 1422 1524 1524 1549 1753 1676 1880

Depth (C) po mm 23 584 23 29 29 29 30 33 33 33 34 36 38 584 737 737 737 762 838 838 838 864 914 965

lb 1249 1504 1766 2178 2444 2900 3345 4287 5025 6066 7461 8902

kg 567 682 801 988 1109 1315 1517 1945 2279 2752 3384 4038

Height (A) po mm 46 1168 58 58 60 60 80 80 80 80 80 90 90 1473 1473 1524 1524 2032 2032 2032 2032 2032 2286 2286

Width (B) po mm 44 1118 50 50 60 60 73 73 73 73 73 80 90 1270 1270 1524 1524 1854 1854 1854 1854 1854 2032 2286

Depth (C) po mm 23 584 26 26 33 33 45 45 45 45 45 54 54 660 660 838 838 1143 1143 1143 1143 1143 1372 1372

lb 1499 1754 2016 2628 2894 3400 3845 4787 5525 6566 8134 9630

kg 680 796 914 1192 1313 1542 1744 2171 2506 2978 3690 4368

dB 55 58 58 60 60 62 64 64 64 65 66 68

(1) F = Floor mount Winding terminals with connections above coils (no busbar coordination) (2) Taps : (3) No correspondence between approved type 2, 3R and 4 enclosures All weights and dimensions are approximate and subject to change without notice.

See page 3-11 for figure 1 and 2

3- POWER

Aliminum Class 15kV, Three-phase, Primary 12470 V or 13800 V, Secondary 600Y / 346 V, 150 C, BIL 95kV
kVA Mounting Impe(1) dance Taps (2) Dimensions Core & Coils (Figure 1) Weight Dimensions including enclosure (cable in / cable out) (Figure 2) Weight Noise level

500 750 1000 1250 1500 2000 2500 3000 3750

F F F F F F F F F

5.5 6 6 6 6 6.5 6.5 7 7.5

% 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5

Height (A) po mm 59 1499 64 67 68 69 71 76 77 86 1626 1702 1727 1753 1803 1930 1956 2184

Width (B) po mm 60 1524 60 63 65 66 72 75 78 79 1524 1600 1651 1676 1829 1905 1981 2007

Depth (C) po mm 30 762 31 33 35 37 38 40 40 44 787 838 889 940 965 1016 1016 1118

lb 3537 4194 5106 5954 6741 8623 10245 11475 12855

kg 1604 1902 2316 2701 3058 3911 4647 5205 5831

Height (A) po mm 80 2032 90 90 90 90 90 100 100 100 2286 2286 2286 2286 2286 2540 2540 2540

Width (B) po mm 80 2032 80 80 90 90 90 90 100 100 2032 2032 2286 2286 2286 2286 2540 2540

Depth (C) po mm 54 1372 54 54 54 54 54 54 60 60 1372 1372 1372 1372 1372 1372 1524 1524

lb 4146 4867 5779 6882 7469 9351 11041 12374 13754

kg 1881 2208 2621 3031 3388 4242 5008 5613 6239

dB 60 64 64 65 65 66 68 68 71

(1) F = Floor mount Winding terminals with connections above coils (no busbar coordination) (2) Taps : (3) No correspondence between approved type 2, 3R and 4 enclosures All weights and dimensions are approximate and subject to change without notice.

See page 3-11 for figure 1 and 2

3-10 1-800-663-3582

Back to table of contents


Synonymous of Quality

POWER TRANSFORMERS C802.2


Dry Type - Class 5 KV, 15 KV, 25 KV, and 34,5KV
Aluminum Class 25kV, Three-phase, Primary 24940 V, Secondary 600Y / 346 V, 150 C, BIL 125kV
kVA Mounting Impe(1) dance Taps (2) Dimensions Core & Coils (Figure 1) Weight Dimensions including enclosure (cable in / cable out) (Figure 2) Weight Noise level

500 750 1000 1250 1500 2000 2500 3000 3750

F F F F F F F F F

6 6.5 6.5 6.5 6.5 7 7 7.5 8

% 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5

Height (A) po mm 68 1727 71 71 77 80 82 85 87 89 1803 1803 1956 2032 2083 2159 2210 2261

Width (B) po mm 69 1753 71 72 72 72 79 79 81 85 1803 1829 1829 1829 2007 2007 2057 2159

Depth (C) po mm 30 762 31 34 35 36 40 40 40 45 787 864 889 914 1016 1016 1016 1143

lb 4471 5358 6155 6975 7910 9488 11060 12142 14409

kg 2028 2430 2792 3164 3588 4304 5017 5508 6536

Height (A) po mm 90 2286 90 90 100 100 100 110 110 110 2286 2286 2540 2540 2540 2794 2794 2794

Width (B) po mm 90 2286 90 90 90 90 100 100 100 110 2286 2286 2286 2286 2540 2540 2540 2794

Depth (C) po mm 60 1524 60 60 60 60 66 66 66 66 1524 1524 1524 1524 1676 1676 1676 1676

lb 5237 6124 6921 7812 8747 10429 12080 13162 15497

kg 2375 2778 3139 3543 3968 4731 5479 5479 7029

dB 63 67 67 68 68 69 71 71 74

(1) F = Floor mount Winding terminals with connections above coils (no busbar coordination) (2) Taps : (3) No correspondence between approved type 2, 3R and 4 enclosures All weights and dimensions are approximate and subject to change without notice.

See page 3-11 for figure 1 and 2

Figure 1

Figure 2

3-11 www.delta.xfo.com

3- POWER

POWER TRANSFORMERS E.V.I.


Arrangement layout with busbar coordination - for all types of installation
Figure 1

FRONT VIEW

FRONT VIEW

3- POWER

Figure 2

TOP VIEW

FRONT VIEW

3-12 1-800-663-3582

Back to table of contents


Synonymous of Quality

POWER TRANSFORMERS E.V.I.


Arrangement layout with busbar coordination - for all types of installation
Figure 3

TOP VIEW

FRONT VIEW

3- POWER

Figure 4

TOP VIEW

FRONT VIEW

3-13 www.delta.xfo.com

POWER TRANSFORMERS E.V.I.


Arrangement layout with busbar coordination - for all types of installation
Figure 5

FRONT VIEW

TOP VIEW

3- POWER

Figure 6

FRONT VIEW

TOP VIEW

3-14 1-800-663-3582

Back to table of contents


Synonymous of Quality

POWER TRANSFORMERS E.V.I.


Arrangement layout with busbar coordination - for all types of installation
Figure 7

TOP VIEW

FRONT VIEW

3- POWER

Figure 8

TOP VIEW

SIDE VIEW

3-15 www.delta.xfo.com

POWER TRANSFORMERS E.V.I.


Arrangement layout with busbar coordination - for all types of installation
Figure 9

TOP VIEW

SIDE VIEW

3- POWER

Figure 10

H.V. TROAT DRILLING PATTERN

L.V. TROAT DRILLING PATTERN

3-16 1-800-663-3582

Back to table of contents


Synonymous of Quality

ORION CONTROL TRANSFORMERS

Orion Features and Benefits Accessoires

SECTION 4
4-1 www.delta.xfo.com

4-2

4- ORION TRANSFORMER

1-800-663-3582

Back to table of contents


Synonymous of Quality Synonyme de qualit

ORION CONTROL TRANSFORMERS


Features and Benets
Molded terminal blocks for primary and secondary connections up to 3 000 VA and 30 Amps. Coil face termination over 3 000 VA and 30 Amps. All terminal blocks utilize a combination slot/Phillips #6 screw with a SEMS washer. Coil face terminations utilize a -20 UNC x 0,50 `` combination slot/Phillips screw and a spring lock washer. 50/60 Hz (60 Hz on UH*** and QC***). Copper wound coils with high dielectric strength insulation. CSA Certied (le LR 3902), UL listed with (le E50394), CE marked and RoHS Compliant. Meets NEMA standards. Superior insluation materials. The Delta Orion Controls offers the following insulation systems : Uo to 1 500 VA : 80 C rise 130 C temperature class (B) 2 000 to 5 000 VA : 115 C 180 C temperature class (F) Most Delta Orion Controls units incorporate Premium Packaging which feature: Premium uted cartons Custom molded foam inserts Easy removal and repacking Industrys best box label

All Delta Orion Controls units are supplied with trilingual installation and wiring instruction sheets. All units supplied with primary and secondary voltage links/jumpers. All Delta Orion Controls transformers are Vacuum Impregnated with polyester resin and oven cured. Bolted core construction. Bolt-on mounting brackets.

4- ORION TRANSFORMER

15 YEARS WARRANTY
4-3 www.delta.xfo.com

ORION CONTROL TRANSFORMERS

Serie-A Orion, Primary 600 /480V, Secondary 120/240V, 60 Hertz


VA Rating CE VA Rating Catalog Number Mig Fig. Output Amps Overall Dimensions Mounting Centers Mounting Slot Height with finger Guard Height with Fuse Block Adapter Approx. ship Weight Lbs.

50 100 150 250 350 500 750 1000 1500 2000 3000 5000

50 100 150 160 250 300 500 650 1000 1300 2000 3000

DC050UH DC0100UH DC0150UH DC0250UH DC0350UH DC0500UH DC0750UH DC01000UH DC01500UH DC02000UH DC03000UH DC05000UH

A A A A A A A A A A A C

0,42/0,21 0,83/0,42 1,25/0,63 2,08/1,04 2,92/1,04 4,17/2,08 6,25/3,13 8,33/4,17 12,5/6,25 16,7/8,33 25,0/12,5 40,7/20,8

*A 2,60 2,99 2,99 3,78 3,78 4,49 5,25 5,25 5,25 6,38 7,50 8,98

*B 3,82 3,74 4,29 4,09 4,49 4,69 5,08 5,47 6,85 5,87 7,50 9,88

*C 2,60 2,85 2,85 3,40 3,40 3,78 4,37 4,37 4,37 5,31 6,50 7,76

*D 2,13 2,52 2,52 3,31 3,31 3,78 4,50 4,50 4,50 5,75 6,30 7,40

*E 2,64 2,60 3,15 2,99 3,39 3,66 4,06 4,45 5,83 4,84 6,85 7,13

*G x *H 0,22 x 0,44 0,22 x 0,44 0,22 x 0,44 0,22 x 0,44 0,22 x 0,44 0,31 x 0,81 0,31 x 0,81 0,31 x 0,81 0,31 x 0,81 0,31 x 0,81 0,44 x 1,00 0,44 x 1,00

lb 2,98 3,23 3,23 3,78 3,78 4,16 4,75 4,75 4,56 5,69 6,50 N/D

kg 2,79 3,04 3,04 3,59 3,59 3,97 4,56 4,56 4,37 5,50 6,50 N/D

dB 2,2 3,3 4,4 6,4 7,5 11 18 21 28 34 60 93

4- ORION TRANSFORMER

Primary and Secondard voltage links/jumpers supplied standard with all transformers. Special voltages and VA sizes available upon request. Note: For 750 to 2 000 VA units actual overall depts is 0,24 in plus the value in column B. * For dimensional drawing see page 4-9 All dimensions are in inches 1 lb = 0,45kg

Ssrie-B Orion, Primary 600 V, Secondary 12/24V, 60 Hertz


VA Rating CE VA Rating Catalog Number Mig Fig. Output Amps Overall Dimensions Mounting Centers Mounting Slot Height with finger Guard Height with Fuse Block Adapter Approx. ship Weight Lbs.

50 100 150 250 350 500

50 100 150 160 250 300

DC050QC DC0100QC DC0150QC DC0250QC DC0350QC DC0500QC

A A A A A B

4,17/2,08 8,33/4,17 12,5/6,25 20,8/10,4 29,2/14,6 41,7/20,8

*A 2,60 2,99 2,99 3,78 3,78 4,49

*B 3,83 3,74 4,09 3,70 4,29 5,08

*C 2,60 2,85 2,85 3,40 3,40 3,78

*D 2,13 2,52 2,52 3,31 3,31 3,78

*E 2,05 2,60 2,95 2,60 3,19 3,27

*G x *H 0,22 x 0,44 0,22 x 0,44 0,22 x 0,44 0,22 x 0,44 0,22 x 0,44 0,31 x 0,81

lb 2,98 3,23 3,23 3,78 3,78 4,16

kg 2,79 3,04 3,04 3,59 3,59 3,97

dB 1,5 3,3 3,0 5,2 7,1 9,9

Primary and Secondard voltage links/jumpers supplied standard with all transformers. Special voltages and VA sizes available upon request. * For dimensional drawing see page 4-9 All dimensions are in inches 1 lb = 0,45kg

4-4 1-800-663-3582

Back to table of contents


Synonymous of Quality

ORION CONTROL TRANSFORMERS

Serie-C Orion, Primary 240 V / 480V, Secondary 120/240V, 50/60 Hertz


VA Rating CE VA Rating Catalog Number Mig Fig. Output Amps Overall Dimensions Mounting Centers Mounting Slot Height with finger Guard Height with Fuse Block Adapter Approx. ship Weight Lbs.

50 100 150 250 350 500 750 1000 1500 2000 3000 5000

50 100 150 160 250 300 500 650 1000 1300 2000 3000

DC050PH DC0100PH DC0150PH DC0250PH DC0350PH DC0500PH DC0750PH DC01000PH DC01500PH DC02000PH DC03000PH DC05000PH

A A A A A A A A A A A C

0,42/0,21 0,83/0,42 1,25/0,63 2,08/1,04 2,92/1,46 4,17/2,08 6,25/3,13 8,33/4,17 12,5/6,25 16,7/8,33 25,0/12,5 41,7/20,8

*A 2,60 2,99 2,99 3,78 3,78 4,49 5,25 5,25 5,25 6,38 7,50 8,98

*B 3,35 3,74 4,29 4,09 4,69 4,69 4,69 5,47 6,85 5,87 7,50 9,88

*C 2,60 2,85 2,85 3,40 3,40 3,78 4,37 4,37 4,37 5,31 6,50 7,76

*D 2,13 2,52 2,52 3,31 3,31 3,78 4,50 4,50 4,50 5,75 6,30 7,40

*E 2,17 2,60 3,15 2,99 3,58 3,66 3,66 4,45 5,83 4,84 7,28 7,28

*G x *H 0,22 x 0,44 0,22 x 0,44 0,22 x 0,44 0,22 x 0,44 0,22 x 0,44 0,31 x 0,81 0,31 x 0,81 0,31 x 0,81 0,31 x 0,81 0,31 x 0,81 0,44 x 1,00 0,44 x 1,00

lb 2,98 3,23 3,23 3,78 3,78 4,16 4,75 4,75 4,75 5,50 6,50 N/D

kg 2,79 3,04 3,04 3,59 3,59 3,97 4,56 4,56 4,56 5,31 6,50 N/D

dB 1,7 3 4,3 6,5 8,2 11 16 21 28 35 64 97

4- ORION TRANSFORMER

Primary and Secondard voltage links/jumpers supplied standard with all transformers. Special voltages and VA sizes available upon request. Note: For 750 to 2 000 VA units actual overall depts is 0,24 in plus the value in column B. * For dimensional drawing see page 4-9 All dimensions are in inches 1 lb = 0,45kg

Serie-D Orion, Primary 240 / 480V, Secondary 12/24V, 50/60 Hertz


VA Rating CE VA Rating Catalog Number Mig Fig. Output Amps Overall Dimensions Mounting Centers Mounting Slot Height with finger Guard Height with Fuse Block Adapter Approx. ship Weight Lbs.

50 100 150 250 350 500

50 100 150 160 250 300

DC050PC DC0100PC DC0150PC DC0250PC DC0350PC DC0500PC

A A A A A B

4,17/2,08 8,33/4,17 12,5/6,25 20,8/10,4 29,2/14,6 41,7/20,8

*A 2,60 2,99 2,99 3,78 3,78 4,49

*B 3,35 3,54 4,29 4,09 4,69 5,47

*C 2,60 2,85 2,85 3,40 3,40 3,78

*D 2,13 2,52 2,52 3,31 3,31 3,78

*E 2,17 2,40 3,15 2,99 3,58 3,66

*G x *H 0,22 x 0,44 0,22 x 0,44 0,22 x 0,44 0,22 x 0,44 0,22 x 0,44 0,31 x 0,81

lb 2,98 3,23 3,23 3,78 3,78 4,16

kg 2,79 3,04 3,04 3,59 3,59 3,97

dB 1,7 3 4,3 6,5 8,3 11

Primary and Secondard voltage links/jumpers supplied standard with all transformers. Special voltages and VA sizes available upon request. * For dimensional drawing see page 4-9 All dimensions are in inches 1 lb = 0,45kg

4-5 www.delta.xfo.com

ORION CONTROL TRANSFORMERS

Serie-E Orion, Primary 380 / 347, Secondary 120/240V, 50 / 60 Hertz


VA Rating CE VA Rating Catalog Number Mig Fig. Output Amps Overall Dimensions Mounting Centers Mounting Slot Height with finger Guard Height with Fuse Block Adapter Approx. ship Weight Lbs.

50 100 150 250 350 500 750 1000 1500

50 100 150 160 250 300 500 650 1000

DC050LH DC0100LH DC0150LH DC0250LH DC0350LH DC0500LH DC0750LH DC01000LH DC01500LH

A A A A A A A A A

0,42/0,21 0,83/0,42 1,25/0,63 2,08/1,04 2,92/1,04 4,17/2,08 6,25/3,13 8,33/4,17 12,5/6,25

*A 2,60 2,99 2,99 3,78 3,78 4,49 5,25 5,25 6,38

*B 3,35 3,74 4,29 4,09 4,69 4,69 4,69 5,47 4,88

*C 2,60 2,85 2,85 3,40 3,40 3,78 4,37 4,37 5,31

*D 2,13 2,52 2,52 3,31 3,31 3,78 4,50 4,50 5,75

*E 2,17 2,60 3,15 2,99 3,58 3,66 3,66 4,45 3,86

*G x *H 0,22 x 0,44 0,22 x 0,44 0,22 x 0,44 0,22 x 0,44 0,22 x 0,44 0,31 x 0,81 0,31 x 0,81 0,31 x 0,81 0,31 x 0,81

lb 2,98 3,23 3,23 3,78 3,78 4,16 4,75 4,75 5,50

kg 2,79 3,04 3,04 3,59 3,59 3,97 4,56 4,56 5,31

dB 1,7 3,4 4,4 6,7 8,4 12 17 21 29

Primary and Secondard voltage links/jumpers supplied standard with all transformers. Special voltages and VA sizes available upon request.

4- ORION TRANSFORMER

Note: For 750 to 2 000 VA units actual overall depts is 0,24 in plus the value in column B. * For dimensional drawing see page 4-9 All dimensions are in inches 1 lb = 0,45kg

Serie-F Orion, Primary 380 / 347, Secondary 12/24V, 50 / 60 Hertz


VA Rating CE VA Rating Catalog Number Mig Fig. Output Amps Overall Dimensions Mounting Centers Mounting Slot Height with finger Guard Height with Fuse Block Adapter Approx. ship Weight Lbs.

50 100 150 250 350 500

50 100 150 160 250 300

DC050LC DC0100LC DC0150LC DC0250LC DC0350LC DC0500LC

A A A A A B

4,17/2,08 8,33/4,17 12,5/6,25 20,8/10,4 29,2/14,6 41,7/20,8

*A 2,60 2,99 2,99 3,78 3,78 4,49

*B 3,35 3,74 4,29 4,09 4,69 5,47

*C 2,60 2,85 2,85 3,40 3,40 3,78

*D 2,13 2,52 2,52 3,31 3,31 3,78

*E 2,17 2,60 3,15 2,99 3,58 3,66

*G x *H 0,22 x 0,44 0,22 x 0,44 0,22 x 0,44 0,22 x 0,44 0,22 x 0,44 0,31 x 0,81

lb 2,98 3,23 3,23 3,78 3,78 4,16

kg 2,79 3,04 3,04 3,59 3,59 3,97

dB 1,7 3,3 4,4 6,4 8,1 11

Primary and Secondard voltage links/jumpers supplied standard with all transformers. Special voltages and VA sizes available upon request. * For dimensional drawing see page 4-9 All dimensions are in inches 1 lb = 0,45kg

4-6 1-800-663-3582

Back to table of contents


Synonymous of Quality

ORION CONTROL TRANSFORMERS

Serie-G Orion, Primary 277V, Secondary 120V, 50 / 60 Hertz


VA Rating CE VA Rating Catalog Number Mig Fig. Output Amps Overall Dimensions Mounting Centers Mounting Slot Height with finger Guard Height with Fuse Block Adapter Approx. ship Weight Lbs.

50 100 150 250 350 500 750 1000 1500

50 100 150 160 250 300 500 650 1000

DC050IE DC0100IE DC0150IE DC0250IE DC0350IE DC0500IE DC0750IE DC01000IE DC01500IE

A A A A A A A A A

0,42 0,83 1,25 2,08 2,92 4,17 6,25 8,33 12,50

*A 2,60 2,99 2,99 3,78 3,78 4,49 5,25 5,25 5,25

*B 3,35 3,54 4,29 4,09 4,49 4,69 5,08 5,47 6,85

*C 2,60 2,85 2,85 3,40 3,40 3,78 4,37 4,37 4,37

*D 2,13 2,52 2,52 3,31 3,31 3,78 4,50 4,50 4,50

*E 2,17 2,40 3,15 2,99 3,58 3,66 4,06 4,45 5,83

*G x *H 0,22 x 0,44 0,22 x 0,44 0,22 x 0,44 0,22 x 0,44 0,22 x 0,44 0,31 x 0,81 0,31 x 0,81 0,31 x 0,81 0,31 x 0,81

lb 2,98 3,23 3,23 3,78 3,78 4,16 4,75 4,75 4,75

kg 2,79 3,04 3,04 3,59 3,59 3,97 4,56 4,56 4,56

dB 1,6 3,2 4,3 6,4 8,1 11 18 20 29

Primary and Secondard voltage links/jumpers supplied standard with all transformers. Special voltages and VA sizes available upon request. Note: For 750 to 2 000 VA units actual overall depts is 0,24 in plus the value in column B. * For dimensional drawing see page 4-9 All dimensions are in inches 1 lb = 0,45kg

4- ORION TRANSFORMER

Serie-H Orion, Primary 120 / 240, Secondary 12/24V, 50 /60 Hertz


VA Rating CE VA Rating Catalog Number Mig Fig. Output Amps Overall Dimensions Mounting Centers Mounting Slot Height with finger Guard Height with Fuse Block Adapter Approx. ship Weight Lbs.

50 100 150 250 350 500

50 100 150 160 250 300

DC050HC DC0100HC DC0150HC DC0250HC DC0350HC DC0500HC

A A A A A B

4,17/2,08 8,33/4,17 12,5/6,25 20,8/10,4 29,2/14,6 41,7/20,8

*A 2,60 2,99 2,99 3,78 3,78 4,49

*B 3,35 3,74 4,29 3,90 4,69 5,47

*C 2,60 2,85 2,85 3,40 3,40 3,78

*D 2,13 2,52 2,52 3,31 3,31 3,78

*E 2,17 2,60 3,15 2,80 3,58 3,66

*G x *H 0,22 x 0,44 0,22 x 0,44 0,22 x 0,44 0,22 x 0,44 0,22 x 0,44 0,31 x 0,81

lb 2,98 3,23 3,23 3,78 3,78 4,16

kg 2,79 3,04 3,04 3,59 3,59 3,97

dB 1,7 3 4,3 5,9 8,2 11

Primary and Secondard voltage links/jumpers supplied standard with all transformers. Special voltages and VA sizes available upon request. * For dimensional drawing see page 4-9 All dimensions are in inches 1 lb = 0,45kg

4-7 www.delta.xfo.com

ORION CONTROL TRANSFORMERS

Serie-I Orion, Primary 208 /416, Secondary 120 X 240V, 50 / 60 Hertz


VA Rating CE VA Rating Catalog Number Mig Fig. Output Amps Overall Dimensions Mounting Centers Mounting Slot Height with finger Guard Height with Fuse Block Adapter Approx. ship Weight Lbs.

50 100 150 250 350 500 750 1000 1500

50 100 150 160 250 300 500 650 1000

DC050NH DC0100NH DC0150NH DC0250NH DC0350NH DC0500NH DC0750NH DC01000NH DC01500NH

A A A A A A A A A

0,42/0,21 0,83/0,42 1,25/0,63 2,08/1,04 2,92/1,04 4,17/2,08 6,25/3,13 8,33/4,17 12,5/6,25

*A 2,60 2,99 2,99 3,78 3,78 4,49 5,25 5,25 6,38

*B 3,35 3,54 4,29 4,09 4,69 4,69 4,69 5,47 4,88

*C 2,60 2,85 2,85 3,40 3,40 3,78 4,37 4,37 5,31

*D 2,13 2,52 2,52 3,31 3,31 3,78 4,50 4,50 5,75

*E 2,17 2,40 3,15 2,99 3,58 3,66 3,66 4,45 3,86

*G x *H 0,22 x 0,44 0,22 x 0,44 0,22 x 0,44 0,22 x 0,44 0,22 x 0,44 0,31 x 0,81 0,31 x 0,81 0,31 x 0,81 0,31 x 0,81

lb 1,6 3 4,3 6,5 8,3 11 16 20 27

kg 2,60 2,85 2,85 3,40 3,40 3,78 4,75 4,75 5,69

dB 1,6 3 4,3 6,5 8,3 11 16 20 27

Primary and Secondard voltage links/jumpers supplied standard with all transformers. Special voltages and VA sizes available upon request.

4- ORION TRANSFORMER

Note: For 750 to 2 000 VA units actual overall depts is 0,24 in plus the value in column B. * For dimensional drawing see page 4-9 All dimensions are in inches 1 lb = 0,45kg

Serie-J Orion, Primary 208 / 416, Secondary 12/24V, 50 /60 Hertz


VA Rating CE VA Rating Catalog Number Mig Fig. Output Amps Overall Dimensions Mounting Centers Mounting Slot Height with finger Guard Height with Fuse Block Adapter Approx. ship Weight Lbs.

50 100 150 250 350 500

50 100 150 160 250 300

DC050NC DC0100NC DC0150NC DC0250NC DC0350NC DC0500NC

A A A A A B

4,17/2,08 8,33/4,17 12,5/6,25 20,8/10,4 29,2/14,6 41,7/20,8

*A 2,60 2,99 2,99 3,78 3,78 4,49

*B 3,35 3,74 4,29 4,09 4,69 5,47

*C 2,60 2,85 2,85 3,40 3,40 3,78

*D 2,13 2,52 2,52 3,31 3,31 3,78

*E 2,17 2,40 3,15 2,99 3,58 3,66

*G x *H 0,22 x 0,44 0,22 x 0,44 0,22 x 0,44 0,22 x 0,44 0,22 x 0,44 0,31 x 0,81

lb 2,98 3,23 3,23 3,78 3,78 4,16

kg 2,79 3,04 3,04 3,59 3,59 3,97

dB 1,6 3,1 4,3 6,5 8,3 11

Primary and Secondard voltage links/jumpers supplied standard with all transformers. Special voltages and VA sizes available upon request. * For dimensional drawing see page 4-9 All dimensions are in inches 1 lb = 0,45kg

4-8 1-800-663-3582

Back to table of contents


Synonymous of Quality

ORION CONTROL TRANSFORMERS


Dimensional Drawings
Some actual transformer units may differ from dimensional drawings shown below.

Custom Control Capabilities


Delta is one of the industrys most technically capable manufacturers producting the broadest and most competitive range of custom dry-type transformers and related magnetic products in North America. Our designs are cost effective and our transformers are built with modern manufacturing techniques. We emphasize our Value Added Engineering whereby our design staff will interface with your team to produce the optimum transformer. Our 3-D modelling design and CAD facilities permits quick and effective communication when time is vital. Delta can provide custom control transformers to fit your design style requirements for most standard or specialty applications. From custom medium voltage to enclosed or even potted control, Delta has the engineering and manufacturing resources to deliver your custom control transformer how you want it and when you need it.

Figure A
B

C GxH

4- ORION TRANSFORMER

Figure B
B

C GxH E

Figure C
B

GxH

4-9 www.delta.xfo.com

ORION CONTROL TRANSFORMERS


Optional Accessories Finger Guard
Delta Control Transformers up to and including 3 000 VA or 30 Amps are available with optional finger guards.
Part Number FGO1 FGO1 FGO1 Applicable Transformer Part Number Suffics QC, PC, HC, LC, NC LH NH, IE UH, PH Applicable VA Sizes 50 500 50 1500 50 3000

Finger Guard
(optional)

Note:Eachfingerguardsupplieseithertheprimaryorsecondaryside.Fingerguardoptionnot availableonDCO5000UHandDCO5000PHstandardunits.Add0,38inperfingerguardto overall depth (column B) on units from 50 to 500 VA and 0,31 in to units from 750 to 2 000 VA whenfingerguardhasbeeninstalled.Forcustomunits,optionalfingerguardsarenotavailable on units up to 3 000 VA or 30 Amps.

4- ORION TRANSFORMER

Fuse Block Adapter kit


Delta Control Transformers up to and including 3 000 VA or 30 Amps are available with optional fuse block adapter kits. The Fuse Block Adapter Kit is designed to allow for the installation of any third party after market fuse block assembly onto the industrial control transformer. The transformer must be a unit that incorporates a molded terminal block on either the primary or secondary side.
Note : Delta does not provide any jumpers or appropriate fuses for any after market fuse block you install on the Delta control Transformers. The Delta Fuse Block Adapter Kit provides only the mechanical means of attaching a third party after market fuse block. Delta does not recommend anyspecificfuseblockorfusesupplier.

Sample Assembly Drawing For Optional Finger Guard Installation


(Only available for units supplied with either a primary or secondary molded terminal block)

Kit Part Number FBOAK1 FBOAK1 FBOAK1

Applicable Transformer Part Number suffixes QC, PC, HC, LC, NC LH NH, IE UH, PH

Applicable VA Sizes 50 500 50 1500 50 3000

Fuse Block Adapter Kit


(Optional)

Note : Only 1 fuse block adapter kit is required per transformer. Fuse block adapter kit not available on DCO5000UH and DCO5000PH standard units. Add 0,38 in per fuse block adapter to overall depth (colonne B) on units from 750 to 3 000 VA when optional fuse block adapter is installed. For custom units, optional fuse block adapter kit is only available on units up to 3 000 VA or 30 Amps.

Sample Assembly Drawing For Optional Fuse Block Adapter Installation

4-10 1-800-663-3582

Back to table of contents


Synonymous of Quality

MISCELLANEOUS INFORMATIONS
Technical data sheet for Power Transformers Nomenclature System for Products K-Rated Transformer Variable Speed Drive Transformers Medical Equipement Transformer Electrostatic Shield Noise Level Analysis Temperature Leve Analysis Dripshields Sprinkler Hood Kit Wall Mounting Brackets Anti-Vibration Pads Transformer Handling The advantages of Cast Coil Electrical Schematics Diagrams Reference List Warranties Terms and Conditions

SECTION 5
5-1

www.delta.xfo.com

5-2

5- MICELLANEOUS INFORMATIONS

1-800-663-3582

Back to table of contents


Synonymous of Quality

TECHNICAL DATA SHEET FOR POWER TRANSFORMER


Quantity : KVA / AA / Primary voltage : Secondary voltage : Impedance : K-Factor Load Profil : Primary Taps : Core & Coil only : Enclosure : OPTIONS Special Conditions Electro Static Shield Temperature Indicator Provision for Fan Cooling Fan Cooling Lighting Arresters Grounding Resistor Ground bus bar Special Paint Color Hinged Doors Mechanical Interlock Provision for Padlock Epoxy Vacuum Impregnation Primary Coordination Secondary Coordination Standard Production Test Heat Run Test Noise Level Test Basic Impulse Level Corona Test Witnessed Test Certified Test Report Instruction Manual Losses Evaluation (watts) Notes and Special features : Standard E.V.I. Provision for Incoming cables Provision for Outcoming cables Per IEEE / ANSI C57.12.91 / CSA C-9 Extra if required Extra if required Extra if required Extra if required Extra if required Copies Copies $ / No-Load Losses $ / Load Losses Volt. 4 x 2.5 % Taps, 2FCAN, 2FCBN (Off-load bolted links) Dimensions Max : Dimensions Max : Yes No Details Alt. : Std ft. Indoor Outdoor Amb. T C : 40 max H H W W D D Weight Max : Weight Max : Lbs Lbs BIL : kV BIL : kV Delta Delta Three-phase 60 Hz Wye Wye Temperature rise : 150 C Insulation Class : 220 C CO CO Noise Level dB

Al Al

% @ Temperature rise + 20 C

Between high and low voltage windings Dial Type Digital Type c/w 2 contacts 1 N.O. + 1 N.F.

Motor 120 volts a.c. (Fan kits not included) Motor 120 volts a.c. (120 volts a.c. source not included) kV Type Ohms. Distr. Amps. Interm. Station

5- MICELLANEOUS INFORMATIONS

Standard 10.25 x 2.0 cu

5-3 www.delta.xfo.com

5-4
IV V C 0030 IV V C 0030 IV V C 1A15
(**) When the transformer is special (i.e. different than the following standard designation described in position VI to all the alphanumeric described in position VII to XII are replaced by << SXXXXXX>> where <<X>> is a numeric betw

5- MICELLANEOUS INFORMATIONS

1-800-663-3582
VI VII VIII VH A 6 VI VII VIII S 9 VI VII VIII VH B 6 WINDING CONFIGURATION A - 3ph Delta - Delta B - 3ph Delta - Star C - 3ph Star - Star D - 3ph Star - Delta J - 1ph Prim. (Single) Second. (Single) K - 1ph Prim. (Double) Second. (Single) L - 1ph Prim. (Single) Second. (Double) M - 1ph Prim. (Double), Second. (Double) N - Zero-Sequence Filter IX X IX 9 IX X X X X 9 X X XI B XI 9 XI B XII A XII 9 XII R

CSA : DISTRIBUTION NOMENCLATURE SYSTEM

STANDARD ITEM CDTC0030VHA6XXBA NON STANDARD ITEM CDTC0030 Sxxxxxx MINI POWER CENTRE CCTC1A15VHB6XXBR

I C I C I C

II D II D II C

III T III T III T

CZVURX-

All devices are so designated. Non certified product Non Linear Load US Enclosed type US Open type Hazardeous Location

DISTRIBUTION NOMENCLATURE SYSTEM

PHASE S - Single 1 - Single C802 T - Three 3 - Three C802 IV C VH A 6 X V* V** VI VII VIII IX X X

WINDING A - Aluminum C - Copper

PRIMARY & SECONDARY TEMPERATURE RISE A =150 C N = 95 C VOLTAGE B =115C O = 90C A = 12 M = 347 Y = 2400 P = 85C C = 80C B = 16 N = 380 Z = 4160 D = 55 C Q = 75 C C = 24 O = 416 1 = 6900 E = 145C R = 70C D = 32 P = 440 2 = 7200 S = 65C F = 140C E = 110 Q = 460 3 = 8320 G = 135 C T = 60 C F = 115 R = 480 4 = 12470 H = 130 C U = 50 C G = 120 S = Spcl 5 = 13800 I = 125 C V = 45 C H = 208 T = 550 6 = 13860 J = 120 C W = 40 C I = 220 U = 575 7 = 14400 K = 110 C X = 35 C J = 230 V = 600 8 = 24940 L = 105 C Y = 30 C K =240 W = 2200 9 = 27600 C Z = 25 C L = 277 X = 2300 - = Not provided M = 100 XI B XII A

II

III

TYPE OF TRANSFORMER A - Autotransformer C - Mini - Power Centre D - Isolation transformer E - Epoxy Potted

V* & V** OTHER THAN (MPC) 0030 - kVA Rating ( 4 digits ) V* & V** MINI POWER CENTRE v* v** 15 kVA Rating ( 2 digits )
1A - Cutler Hammer 24 circuits 3B - Square D 30 circuits

FREQUENCY 5 = 50 / 60 Hz 6 = 60 Hz

ELECTROSATTIC SHIELD 1 - Qty of ESS X - Not provided K FACTOR A= 4 B= 9 C = 13 D = 20 E = 30 X = Not rated ENCLOSURE TYPE (COLOR ASA-61 GRAY) ABDEGHJR1 2 3R & Epoxy 4 Open Type (Without enclosure ) 4X (Stainless Steel, not Painted) 12 3R ( MINI POWER CENTRE)

IFZKLMNRTPXYS-

Drive Isolation Transformer Zero-Sequence Filter Interconnected Star xfo ( Mitigator) K - Factor 20 kv BIL Primary ( 2400V ) 30 kv BIL Primary ( 4160V ) 45 kv BIL Primary 60 kv BIL Primary ( layer ) 60 kv BIL Primary ( disk ) 95 kv BIL Primary 125 kv BIL Primary 150 kv BIL Primary Special Primary BIL ( 75, 110 kv )

Nomenclatur system 13 / 2006

Back to table of contents


Synonymous of Quality

K-RATED TRANSFORMERS

The Non Linear Load Low cost Solution


All K-Rated transformers meet the most stringent industrial standards due to their optimal design, superior quality and ease of installation.

Options
Single or Double Oversized Electrostatic Shield TVSS Special Voltage 115C and 80C Temperature Rise

Applications
Non Linear Loads Installation with dedicated ground Industrial Programmable Controllers (PLC) Protected Receptables for Hospitals Protected Receptables (orange)

Typical Application

5- MICELLANEOUS INFORMATIONS

Features
E.V.I. Process (Epoxy Vacuum Impregration) at no additional cost Copper Windings Insulation Class 220 150C Temperature Rise High Quality Grain Oriented Steel Laminations Compact and easy to install enclosure Quiet Operations Neutral sized for twice the rated current Voltage of 600V to 208Y/120 V, 60 Hz, -Y, 3P, 4W 3 Coil construction Electrostatic Shield

E.V.I. Plus-Value
Superior Bonding & Mechanical Strength Core Losses Stability Better Heat Dissipation Reduced Noise Improved Winding Insulation Enhanced Protection in Contaminated Environments Elimination of Air Pockets

5-5 www.delta.xfo.com

VARIABLE SPEED DRIVE TRANSFORMER

All variable speed drive transformers meet the most stringent industrial standards due to their optimal design, superior quality and ease of installation.

Typical Applications

Applications
AC and DC Variable Speed Drive Sillicon Controlled Rectifier Improved harmonic mitigation with multi-pulse configuration (6P, 18P, 24P, )

Features
E.V.I. Process (Epoxy Vacuum Impregration) Primary Voltages of 600, 575, 480, 460, 240 or 230V 6 Pulse Secondary Voltages of 600, 575, 480, 460, 240, 230V Y or 12 Pulse Secondary Voltages of 600, 575, 480, 460, 240 230V Y and Copper Windings Insulation Class 220 150C Temperature Rise High-Quality Grain-Oriented Steel Laminations Type 2 Enclosure Electrostatic Shield Double Neutral

5- MICELLANEOUS INFORMATIONS

E.V.I. Plus-Value
Superior Bonding & Mechanical Strength Core Losses Stability Better Heat Dissipation Reduced Noise Improved Winding Insulation Enhanced Protection in Contaiminated Environments Enhanced of Air Pockets

Options
115C and 80C Temperature Rise Thermal Switch with 1 or 2 N.C. contacts Open Type Core-Coil Construction Specific Phase Shirted Configuration for optimal harmonic mitigation Special Voltage Type 2, 3R and Sprinkleproof Enclosures

Quick Selector
Motor H.P.
6 7,5 10 15 20 25 30 40 50 60

Transformer kVA
7,5 11 14 20 27 34 40 51 63 75

Motor H.P.
75 100 125 150 200 250 300 400 500 600

Transformer kVA
93 118 145 176 220 276 330 440 550 660

5-6 1-800-663-3582

Back to table of contents


Synonymous de Quality Synonyme of qualit

MEDICAL EQUIPMENT TRANSFORMER

Medical imaging equipments are becoming more and more present in hospitals. To allow proper performance of this type of equipment. It is essential to provide a very low supply impedance, so low that even the transformer and equipment cable run makes a difference. Installation of a transformer with standard features would not be adequate. Therefore Delta Transformers has been developing specic solutions for hospitals and their critical equipments.

Options
80C and 115C Temperature Rise Electrostatic Shield

Typical Application

What is needed to choose the proper transformer


Capacity (kVA) Primary and Secondary Voltages required Maxinum line to line impedance required by medical imaging equipment. Cable length and size from the power source to the transformer. Cable length and size from the transformer to the medical imaging equipment.

E.V.I. Plus-Value
Superior Bonding & Mechanical Strength Core Losses Stability Better Heat Dissipation Reduced Noise Improved Winding Insulation Enhanced Protection in Contaiminated Environments Enhanced of Air Pockets

5- MICELLANEOUS INFORMATIONS

Features
E.V.I. Process (Epoxy Vacuum Impregnation) Copper Windings Insulation Class 200 150C Temperature Rise High Quality Grain Oriented Steel Laminations Compact and easy to install enclosure Quiet Operation

5-7 www.delta.xfo.com

ELECTROSTATIC SHIELD

All Transformers used with Non Linear Loads application such as drive transformers, K-Rated transformers, Harmonic mitigation transformers should come with an electrostatic shield.

How does it work


A transformer is a device that uses electromagnetic induction to convert energy from an input system to the desired output at the same frequency. The challenge with transients is that they do not need the transformer iron core path to travel from one side to the other. They travel using a path known as electrostatic action, using capacitive coupling between primary and secondary to ground.

But what exactly is an electrostatic shield ?


An Electrostatic Shield is a grounded metallic barrier provided between the primary and the secondary windings of an isolation transformer.

Shielded Transformers

Applications

5- MICELLANEOUS INFORMATIONS

Originaly used as an electrical barrier between primary and secondary windings of a power isolation transformer, so that the secondary side will be electrically isolated from fault occurring on the primary voltage system. These days, it will be commonly used to lter out, to very low values transient (High Frequency Common Mode Noise) present in distribution systems. Transients that are generated by contactors, High frequency variable speed drive, capacitor switching, H.I.D. lighting, computer power supply: basicaly all power electronic driven equipment.

Attenuation

* Level of attenuation usually obtained with 1-only standard electrostatic shield

Unshielded Transformer

5-8 1-800-663-3582

Back to table of contents


Synonymous of Quality

NOISE LEVEL ANALYSIS


Transformer installation and noise
Noise in a transformer is basically caused by magnetostriction. This translates into a hum of twice the applied frequency. This inherent characteristic of the transformer cannot be completely eliminated. It is not uncommon to observe an increase of 10 to 20 dBA in an installation, and very often it is a lot harder to correct the situation after the fact. Location, combined with good practice often makes the difference, included, you will find a table of noise level vs kVA, a list of recommended practices to help you choose the right location, and tips for prior to putting the transformer into service.
kVA Single-phase - Ventilated 1.2 kV 1.2 kV 15 kV 15 kV 25 kV 15 kV 0-9 45 50 54 50 55 59 55 60 64 60 65 69 65 68 72 68 68 72 Three-phase - Ventilated 1.2 kV 1.2 kV 15 kV 15 kV 25 kV 15 kV 0-9 40 45 49 45 50 54 50 55 58 55 58 61 60 60 63 62 62 65 64 64 67 65 65 68 66 66 69 68 68 71 71 71 74 73 73 76 Closed

Choice of location and recommendations


Avoid installations near sound reflecting surfaces. Avoid installations in narrow places or hallways. If possible, choose locations where sound would be least objectionable. If installation near sound reflecting surfaces cannot be avoided, be sure to use acoustic absorbing material between transformer and sound reflecting surface. Avoid any mechanical coupling to structure or equipment. Use of flexible conduct is highly recommended. Avoid installation on surfaces of relatively light mass like wood, tiles, masonry. Make sure the mass of installation surface is at least superior to the weight of the transformer.

10-50 51-100 101-167 168-333 334-1000 kVA

45 50 55 57 59 61 Closed

5- MICELLANEOUS INFORMATIONS

Install proper anti-vibration pads to avoid transmission of vibration to floor or mounting surface. Also refer to ANSI / IEEE C57.94-1982 : RECOMMENDED PRACTICE FOR INSTALLATION, APPLICATION, OPERATION, AND MAINTENANCE OF DRY-TYPE GENERAL PURPOSE DISTRIBUTION AND POWER TRANSFORMERS

10-50 51-150 151-300 301-500 501-700 701-1000 1001-1500 1501-2000 2001-3000 3001-3750 2751-5000

45 50 55 57 59 61 63 64 65 66 68 70

Prior to putting the transformer into service:


Remove all shipping brackets located at top of units (when present). Loosen anchoring bolts so that rubber pads between transformer and enclosure are no longer over compressed. Select proper voltage tap to help reduce emitted noise. Verity overall assembly and screw tightness. Make sure the installation is level.

These tables are based on CSA C9-02 standard. These values are used under maximun test conditions.

5-9 www.delta.xfo.com

NOISE LEVEL ANALYSIS

# Reference : SC # Order :

Project :

Date : Delivery Date :

CLIENT
Name and address

USER
Name and address

Contact
Tel. : Fax :

Contact
Tel. : Fax :

Characteristics
# Catalogue : # Model : # Serial: Sound level measurement at 12 inches from the unit, half height of the unit, from 4 faces of unit if possible Sound level measurement at 18 inches from the unit, half height of the unit, from 2 faces of unit if possible Any sound reflecting surface next to transformer? Describe type of sound reflecting surfaces Describe type of transformer mounting floor/pad/base. Is the unit sitting on anti-vibration pads? Is the unit sitting on a level floor/pad/base? What type of noise: Hum or Rattle? Feeling of any vibration on the enclosure or metallic parts? Is the vibration transferred to conduit or adjacent equipment? When applying pressure on any surface of enclosure does this change noise level? When applying pressure on any surface of conduit or adjacent equipment does this change noise level? Once front panel is removed, is the input voltage in accordance with selected voltage tap? Same voltage tap on each winding? What type of load is the unit feeding? Any excessive tension between cables and terminations? Shipping brackets located at the top of core & coil removed. Any change in noise? Anti-vibration pads located between transformer & enclosure must not be compressed, loosen up the four ancoring bolts until no visible excessive compression on the pads. Any change in noise? All screws, bolts, connectors and terminations of the assembly verifier for tightness. Any change in noise? KVA of the transformer : Primary : Secondary : KVA V V

5- MICELLANEOUS INFORMATIONS

Front Front

Left side Left side

Back Back

Right side Right side

Comments / Observations

5-10 1-800-663-3582

Back to table of contents


Synonymous of Quality

NOISE LEVEL ANALYSIS

5-11 www.delta.xfo.com

5- MICELLANEOUS INFORMATIONS

NOISE LEVEL ANALYSIS

5- MICELLANEOUS INFORMATIONS
5-12 1-800-663-3582

Back to table of contents


Synonymous of Quality

TEMPERATURE LEVEL ANALYSIS


Transformer installation and temperature
During transformer voltage and current conversions, losses (core, conductor and eddy current losses) generate heat. Therefore, it is possible to feel heat near transformers. For security reasons, standards have established maximum allowable temperature rises. The temperature rise of a transformer enclosure can reach 65 C maximum. Combined with a maximum ambient temperature of 40 C, enclosure surface temperature may attain 105 C. Hotspot temperature inside the transformer can reach 180 C at full load. Given ambient temperature, operating temperature can reach 220 C. Transformer insulation system is based on average temperature rise of conductors, ambient temperature and hotspot. At maximum temperatures, the system must be capable of withstanding 220 C. It is important to note that the core and the top of the enclosure can reach maximum allowable temperatures even at no load. This situation is completely normal and is caused by losses in the core due to the presence of magnetic field once the transformer is energized. Adequate ventilation is mandatory in order to control transformer temperature. When the transformer is installed in a confined area, proper ventilation will provide adequate ambient temperature. At all times, ambient temperature shall be less than 30 C nor exceed 40 C over a 24-hour period. Enclosure ventilation area is based on transformer KVA, heat losses in KW, height differential between inlet and outlet louvers and air temperature differential at inlet and outlet. Total area is designed to allow adequate ventilation of transformer and it must be kept free from any obstacles. No neaby object shall impede ventilation.

Recommendations on transformer location


Never locate transformer near a source of heat. Area shall be well ventilated. Clearances required by Electrical Code and applicable standards shall be met. Power and load cables shall not obstruct enclosure louvers. Ambient temperature shall never exceed 40 C during transformer operation nor 30 C over a 24-hour period. Ensure regular maintenance to prevent louvers and transformer from being covered with dust.

5-13 www.delta.xfo.com

5- MICELLANEOUS INFORMATIONS

TEMPERATURE LEVEL ANALYSIS


# Service Call : SC Project : Date :

# Order :

Delivery Date:

CLIENT
Name and address

USER
Name and address

Contact
Tel. : Fax :

Contact
Tel. : Fax :

Characteristics
# Catalogue : # Model : # Serial : KVA of the transformer : Primary : Secondary : KVA V V

5- MICELLANEOUS INFORMATIONS

Checking before panel removal


Does the transformer seem well ventilated? Do the cables obstruct the enclosure ventilations? Is there excessive dust in the ventilation and windings grids? Is the transformer close to equipment which generates heat? Yes Yes Yes Yes No No No No Load Characteristics : Space : Front Back

Checking after panel removal


Record the temperatures when energized (infrared) Verify all connection for tightness if hot spot(s) Position of cables vs coil air entrances / exits Fill in the table below In accordance In accordance Not in accordance Not in accordance Comments :

Monitored values (according to attached illustration)


Line 1 Primary tension Primary current Secondary tension Secondary current Primary neutral current Taps position Temperature (according to attached illustration) Ambiant Top (center) Other : C C C Top of the core right Top of the core center Top of the core left C C C Coil #1 Coil #2 Coil #3 C C C V A V A A K-Factor DHT (%) Line 2 V A V A Secondary neutral current K-Factor DHT (%) Line 3 V A V A A K-Factor DHT (%)

Comments / observations

5-14 1-800-663-3582

Back to table of contents


Synonymous of Quality

TEMPERATURE LEVEL ANALYSIS


Pictures

Top (center)

Left Top of the core

Center

Right

5- MICELLANEOUS INFORMATIONS

Coil (2 from the top)

5-15 www.delta.xfo.com

DRIPSHIELDS FOR GENERAL PURPOSE TRANSFORMERS


Dripshields installation
TYPICAL KIT
Dripshields kit DS2-12 DS4-18 DS4-15 DS4-20 DS4-17 DS4-27 DS4-23 DS4-30 DS4-20 DS6-30 DS8-22 DS8-35 DS5-26 DS4-38 DS4-44 DS6-31 DS7-50 DS8-60 DS12-73

Enclosure ENC 181209 ENC 191810

Tot. Reqd shields 2 x DS2-12 4 total 1 x DS4-18 4 total 1 x DS4-15 4 total 1 x DS4-20 4 total 1 x DS4-17 4 total 1 x DS4-27 4 total 1 x DS4-23 4 total 1 x DS4-30 4 total 2 x DS4-20 8 total 1 x DS6-30 6 total 1 x DS8-22 8 total 1 x DS8-35 8 total 2 x DS5-26 10 total 2 x DS4-38 8 total 2 x DS4-44 8 total 2 x DS8-31 12 total 2 x DS7-50 14 total 4 x DS8-60 36 total 4 x DS12-73 48 total 3 x DS2-12 6 total 2 x DS4-18 8 total 2 x DS4-15 8 total 2 x DS4-20 8 total 3 x DS4-17 12 total 3 x DS4-27 12 total 3 x DS4-23 12 total 3 x DS4-30 12 total 3 x DS4-20 12 total 2 x DS6-30 12 total 2 x DS8-22 16 total 2 x DS8-35 16 total 4 x DS5-26 20 total 5 x DS4-38 20 total 5 x DS4-44 20 total 4 x DS8-31 24 total 4 x DS7-50 28 total 8 x DS8-60 72 total 8 x DS12-73 96 total 1 x DS2-12 2 total 1 x DS4-18 4 total 1 x DS4-15 4 total 1 x DS4-20 4 total 2 x DS4-17 8 total 2 x DS4-27 8 total 2 x DS4-23 8 total 2 x DS4-30 8 total 1 x DS4-20 4 total 1 x DS6-30 6 total 1 x DS8-22 8 total 1 x DS8-35 8 total 2 x DS5-26 10 total 3 x DS4-38 12 total 3 x DS4-44 12 total 2 x DS8-31 12 total 2 x DS7-50 14 total 4 x DS8-60 36 total 4 x DS1273 48 total

This kit modies the enclosure. Beside is a table indicating the kit number necessary for each type. The enclosure number is on the transformer nameplate. On the right lower corner, beside the bar code. To obtain a Type 2 enclosure from a Type 1, install a dripshield so that there are a minimum of 2 series of ventilation holes, maximum 5, underneath the dripshield. (Fig. 2 : series A and C; Fig. 3 : serie A only). To obtain a Type 2 enclosure with additional shields, install a dripshield on evey set of holes. The enclosure is then protected by shields(Canadian Electrical Code, rule 26-008) from the direct spray, from sprinkler heads to live parts, when the angle between sprinkler heads and openings in the enclosure does not exceed 45 from the vertical. Using a screwdriver, x the dripshield from the center to the ends

ENC 211511 ENC 212012 ENC 231712 ENC 252718 ENC 272313 ENC 282914 ENC 292014 ENC 303014 ENC 372218 ENC 373518 ENC 462621 ENC 463821 ENC 464423 ENC 543123 ENC 585026 ENC 606033 ENC 807345

5- MICELLANEOUS INFORMATIONS

REF. :

ENC 181209 = 18 H x 12 L x 9 D 2 x DS2-12 : 2 = Qty, 12 = L

5-16 1-800-663-3582

Back to table of contents


Synonymous of Quality

OPTIONAL SPRINKLER HOOD FOR COMMERCIAL SERIES


Sprinkler hood kits for Commercial Series
Option sprinkler hood kit part number Code

kVA Single- phase

Enclosure

kVA Three-phase

Enclosure

15 25 37 50 75 100 150 200

CH2 CH3 CH4 CH4 CH4 CH7 CH7 CH7

15 30 45 75 112 150 225 300

CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8

SHCH1 SHCH2-3 SHCH2-3 SHCH4 SHCH5 SHCH6 SHCH7 SHCH8

*Please take note when you install sprinkler hood kits, the enclosure becomes a type 2.

5- MICELLANEOUS INFORMATIONS

Figure A

SHCH1 TO SHCH5

SHCH6 TO SHCH7-8

5-17 www.delta.xfo.com

WALL MOUNTING BRACKETS


Wall mounting brackets installation
TYPICAL KIT

5- MICELLANEOUS INFORMATIONS

This bracket kit is designed to install a transformer with type 1 or 2 enclosure on a wall. Beside is a table indicating the appropriate kit number for each enclosure. The enclosure number is on the transformer nameplate, on the right lower corner, beside the bar code. Important to remember: Each kits includes a right and a left support. To stabilize the installation, screws shall be used at the holes A and B.

# Enclosure
ENC 181209 ENC 191810 ENC 211511 ENC 212012 ENC 231712 ENC 252718 ENC 272313 ENC 282914 ENC 292014 ENC 303014

# Wall mounting brackets kits


SFM-P02 SFM-P02 SFM-P02 SFM-P02 SFM-P02 SFM-G02 SFM-G02 SFM-G02 SFM-G02 SFM-G02

REF. :

ENC 181209 = 18 H x 12 L x 9 D

5-18 1-800-663-3582

Back to table of contents


Synonymous of Quality

ANTI-VIBRATION PADS
Anti-vibration pads installation
TYPICAL KIT

5- MICELLANEOUS INFORMATIONS

This anti-vibration pads kit is designed to attenuate the noise transmitted by the transformer vibration. The type of foot base indicated the appropriate model. See figure beside.

5-19 www.delta.xfo.com

TRANSFORMER HANDLING
FORK LIFT

CRANE

5- MICELLANEOUS INFORMATIONS
5-20 1-800-663-3582

Back to table of contents


Synonymous de Quality Synonyme of qualit

THE ADVANTAGES OF A CAST COIL WITHOUT THE INCONVENIENCES


Advantages of the Delta Transformers E.V.I. Process
MECHANICAL
Both cast coil and Delta Transformers E.V.I. processes make use of epoxy as an environmental protection.

INHERENTLY STRONG
The Delta Transformers E.V.I. design is inherently strong and self-supporting. The Delta Transformers E.V.I. epoxy being highly exible, it can endure thermal and mechanical stresses without cracking. In solid cast epoxy transformers, it is usually necessary to incorporate spring type pressure blocks and berglass reinforcements to combat stresses between components in order to minimize cracking.

EPOXY ENCAPSULATION VS. EPOXY CASTING


In a cast epoxy transformer, the resin is the major part of the insulation system. In the Delta Transformers E.V.I. Nomex and air are the insulation media; epoxy is used for its environmental protective properties only. The Delta Transfomers E.V.I. gives improved performance since its encapsulation is not subject to cracking which is ofter related to solid epoxy casting.

ELECTRICAL
With the Delta Transformers E.V.I. design, as opposed to cast-coil, the epoxy resin is not part of the insulation system. Its function is purely mechanical: a great sealer to protect a great transformer. In fact, in the Delta Transformers E.V.I. the insulation media are Nomex and air.

NO CRACKS
The Delta Transformers E.V.I. process has totally eliminated the cracking problems which can occur in a solid cast insulation, due to temperature differentials through the thickness of Delta Transfomers E.V.I design, the epoxy is thick enough to provide environmental protection but thin enough that internal stresses do not develop. Since the coils are self-supporting, it enables us to use a exible form of epoxy which will accommodate the expansion and contraction of the coil which it protects.

5-21 www.delta.xfo.com

5- MICELLANEOUS INFORMATIONS

MULTIPLES ADVANTAGES

INSULATION STRESSED AT LESS THAN 1%


Low stress design at nominal voltage, the solid Nomex insulation is stressed at less than 1% of its surge rating. In the Delta E.V.I. insulation system, at nominal voltage, air provides insulation between sections, LV & HV windings and windings to ground. The Delta E.V.I. system relies on Nomex only as turn to turn insulation: which, at nominal voltage, is streessed 2030 volt per turn while its surge capacity is over 4000 volt per turn and is therefore only stressed under surge conditions. This conservative approach virtually eliminates dielectric aging thus guaranteeing longer life.

Air is the insulation between sections and between windings to ground.

QUALITY CONTROL
Since the Nomex insulation system is independent of the Delta E.V.I. process;insulation quality can be checked during the manufacturing process. Formal quality control procedures are used to monitor the physical dimensions and the electrical integrity of the insulation during construction of the transformer. Every turn-to-turn, section-to-section and high-to-low barrier can be scrutinized; our design does not have to rely on a perfect cast for insulation performance. All results are documented.

5- MICELLANEOUS INFORMATIONS

L.V. BARREL WOUND 100% NOMEX INSULATED (TURN TO TURN) H.V. TO L.V. NOMEX BARRIER H.V. DISK WOUND 100% NOMEX INSULATED (TURN TO TURN)

DELTA E.V.I. AN INSULATION BONUS


Unlike the cast coil a Delta E.V.I. core/coil assembly would withstand all IEEE tests, including the impulse test, prior to the E.V.I. process. The epoxy coating adds dielectric strenght, but it is used primarily to provide enhanced environmental protection to the coils.

5-22 1-800-663-3582

Back to table of contents


Synonymous of Quality

MULTIPLES AVANTAGES

THE DELTA E.V.I EPOXY


THE DELTA E.V.I power transformers are recommended for use in very humid and hostile environments. Typical applications would be : automotive industry, pulp and paper mills steel mills, water treatment plants, mines, chemical plants, cement plants, and other industrial locations where the atmosphere is especially humid, dirty and/or corrosive; including outdoor and marine applications such as shipyards and offshore drilling rigs. Delta Transformers. Inc. has been using this epoxy resin, for over 10 years, on both Power & Distribution Transformers. It has proven its value both in laboratory tests and in field experience. Seals, coils and enhances performances of the Nomex insulation by eliminating air pockets. Provides maxinum protection against moisture and contaminants. Adds high mechnical strength to the insulation by penetrating porous areas. Eliminates cracking because of its flexibility. Enables the basic design og the transformers to be easily modified to suit specific customers requirements. Eliminates need for coil maintenance. Imposes no storage time limit.

5- MICELLANEOUS INFORMATIONS

The resin used is suitable for most environments and is an excellent moisture sealer. The Delta E.V.I. insulation system is recognized for Acnor (CSA) and UL class 220 applications. When applied under vacuum, it offers the best possible combination of performance features.

5-23 www.delta.xfo.com

ELECTRICAL SCHEMATICS DIAGRAMS

SINGLE PHASE

5- MICELLANEOUS INFORMATIONS

THREE PHASE

5-24 1-800-663-3582

Back to table of contents


Synonymous of Quality

REFERENCE LIST WARRANTIES

Distribution Transformers
General Purpose Transformers
1 Phase 3-333 kVA, 150C 480 V and 600 V Primary 120/240 V Secondary. Enclosure Type 1 and Type 2 3 Phase 6-600 kVA, 150C 480 V and 600 V Primary 240Y/139 V or 208Y/120 V Secondary. Enclosure Type 1 and Type 2 All Others

Lifetime

12 / 18 Months* Lifetime 12 / 18 Months*

Enviro-Guard C802-Series
3 Phase 15-300 kVA, 115C 480 V and 600 V Primary 208Y/120 V or 480Y/277 V Secondary. Enclosure Type 3R All Others Commercial Series Transformers Auto Transformers Epoxy-Potted Transformers Mini Power Centers Special Transformers

12 / 18 Months*

5- MICELLANEOUS INFORMATIONS

Non Linear Loads Transformers


K-Rated Transformers Variable Speed Drive Transformers Computer Application Isolated Transformers Super Isolated Transformers Zero Sequence Filters Transformers

12 / 18 Months*

Mitigator Series Transformers Special Transformers

10 Years Pro-Rated 12 / 18 Months*

Power Transformers
Up to 15 MVA and 34.5 kv Class

12 / 18 Months*

* 12 / 18 Months Warranty: 12 months from energizing / 18 months after shipment whichever date comes first.

5-25 www.delta.xfo.com

TERMS & CONDITIONS

GENERAL
The acceptance of our tender includes the acceptance of the following terms and conditions.

PERFORMANCE
You assume responsibility for the capacity and the performance of the goods being sufcient and suitable for your purpose.

VALIDITY
Unless previously withdrawn, our tender is open for acceptance for the period stated, within thirty days only from the date hereof, and is subject to conrmation at time of such acceptance.

DELIVERY
Delivery promises are approximate only and are based on prompt receipt by us of all necessary information. We will use our best endeavours to ship on the date given but will accept no liability for failure to do so.

ACCEPTANCE
The acceptance of our tender must be accompanied by sufcient information to enable us to proceed with the order forthwith, Otherwise we are at liberty to amend the tender prices to cover any increase in cost for items and details not comtemplated by our tender.

SHIPMENT
Unless otherwise stated, all quotations are F.O.B. point of shipment. In case where freight is allowed beyond the F.O.B. point we will not accept liability or responsibility for any charges arising from the removal of the equipment from transport vehicles or equipment, nor for the setting up of the equipment at the site.

5- MICELLANEOUS INFORMATIONS

PACKING
Unless otherwise specied in our tender, packing in accordance with our standard practice is included.

TERMS OF PAYMENT
Unless otherwise specied, Net 30 days.

LIMITS OF CONTRACT
Our tender includes only such goods, accessories and word as are specied herein.

STORAGE
It is understood that you shall arrange to take delivery of the goods upon advised notice after notication that the goods are ready for shipment. In the event of your not taking delivery, we are prepared, if our storage facilities permit, to store the goods at negotiated extra charge, until such time as the goods are shipped, subject to our rights and your authorization to invoice the goods when they are ready to go for storage. Any charges for storage or demurrage after dispatch must be invoiced on a monthly basis.

DRAWINGS, ETC.
All descriptive and shipping specicaitons, drawings and particulars of weights and dimensions submitted with our tender are approximate only and the descriptions and illustrations contained in our catalogues, price lists and other advertisement matter are inteded merely to present a general idea of the goods described therein and none of these shall form art of the contract. After acceptance of our tender, a set of certied outline drawings will be supplied free of charge if desired.

DAMAGE IN TRANSIT
We will not be responsible for loss or damage to goods beyond the point of shipment, nor shall we be under any obligation to give to you further notice, statutory or other, that we accept no responsibility. When bills of Lading are taking out by us, we will on your instructions and at your expense, insure against loss or other risk, and will, on receipt of your indemnity, take all reasonable steps to recover from the underwriters any loss or damage for which they may be liable.

TESTS
Individual devices will receive standard insulation and other operation tests at point of manufacture. Any special test, or witness of tests required by you and which entails extra expenses to us shall be charged to you.

5-26 1-800-663-3582

Back to table of contents


Synonymous of Quality

TERMS & CONDITIONS

GENERAL LIABILITY AND WARRANTY


In lieu of any warranty, condition or liability implied by law, our liability in respect of any defect in or failure of the goods supplied, or for any loss, injury or damage attributable there to, is limited to making good by replacement or repair defects which under proper use appear therein to arise solely from our fault design, materials or workmanship within a period twelve calendar months after the original goods shall have been first dispatched, at the termination of which period all liability on our part ceases: provided always that such defective parts are promptly returned free to our place of manufacture unless otherwise arranged. The reparied or new parts will be delivered free of charge at our place of manufacture. In the case of goods not of our manufacture, you are entitled only to such benefits as we receive under any guarantee given to us in respect thereof. Save as in this clause herein before expressed, we shall be under no liability in contract, lost or otherwise for any person injury, howsoever caused by or resulting from anything done or omitted in connection with the goods or any work in connection therewith.

FORCE MAJEURE
We shall not be liable for any loss or damage resulting from causes beyond our reasonable control, including without limitation fire, strike civil or military authority, insurrection or riot, embargoes, car shortage, wrecks or delays in transportation, lack or failure of source of supply. Under reserve of the foregoing receipt of the apparatus by you shall constitute a waiver of all claims for loss or damage due to delay.

5-27 www.delta.xfo.com