38/66kV - 76/132kV Cables

Black HDPE outer sheath


Orange 5V-90PVC inner sheath

APL

sh e a h

Non-conductive water-blocking tapes


Copper wires and tape shiled
Semi-conductive water-blocking tapes
Extruded insulated semi-conductive XLPE
XLPE Insulation
Semi-conductive screen tape and
Extruded semi conductive XLPE
Aluminium circular compact stranded conductor

Apart from the cable construction above, cables can be fully customised to the clients specifications.
Aluminium cables up to 2500mm can be supplied.
Listed below are various alternative cable constructions:
Aluminium alloy wire armour(AWA).
Stainless steel wire armour(SSWA).
Fault current carrying capacity for 1 second, i.e. 5kA, 10kA or 13kA etc.
LLDPE, LDPE, MDPE, HDPE, PVC(Red/Blue/Black), LSOH, FR!PVC outer sheath.
Corrugated Aluminium and Corrugated Stainless Steel sheath.
Termite Protection/Repellent:
Double stainless steel tape(DSST).
Double brass tape(DBT).
Double copper tape(DCT).
Nylon jacket(NJ).
Additive into the outer sheath(Cypermethrin).

AUSSA Power Products PTY LTD PO Box 3132 Hendra Queensland 4011.
Phone: (07) 3868 2325 Mobile: 0420 610 557 Fax: (07) 3868 1340
Email: info@aussa.com.au Website: www.aussa.com.au

38/66kV Single Core


Al XLPE CWS(16.5kA/s) APL PVC HDPE
Conductor
nominal cross
sectional area

Conductor
diameter

Approx
insulation
thickness

Approx
diameter
over
insulation

Approx
screen
area on
each core

Number
and approx
diameter of
screen wires

Approx
diameter
over wire
screen

mm2

mm

mm

mm

mm2

no/mm

mm

mm

mm

mm

mm

kg/km

185

15.9

12.0

44.1

116.3

76/1.39

51.3

0.25

52.4

1.5/1.7

59.2

4041

240

18.1

12.0

46.1

116.3

76/1.39

53.3

0.25

54.4

1.6/1.8

61.5

4346

300

20.3

11.0

46.5

116.3

76/1.39

53.7

0.25

54.8

1.6/1.8

61.9

4495

400

23.0

11.0

49.3

116.3

76/1.39

56.5

0.25

57.6

1.6/1.8

64.8

4919

500

26.0

11.0

52.5

116.3

76/1.39

59.7

0.25

60.8

1.6/1.9

68.2

5436

630

30.0

11.0

56

116.3

76/1.39

63.2

0.25

64.3

1.7/2.0

72.0

6063

800

34.2

10.0

58.8

116.3

76/1.39

66

0.25

67.1

1.7/2.0

74.9

6708

1000

39.2

10.0

64

116.3

76/1.39

71.2

0.25

72.3

1.7/2.1

80.3

7758

1200

42.8

10.0

67.6

116.3

76/1.39

74.8

0.25

75.9

1.7/2.2

84.0

8562

Nominal
Approx Nominal Approx
thickness diameter thickness overall
of APL over APL of PVC
diameter
and HDPE

Current Ratings

Installation
Min.bending radius

Continuous current-carrying capacityA


Conductor
nominal cross
sectional area

Approx
mass

In air

Fault current
carrying capacity
for 1 second

in ground

Permissable pulling
During
force
installation

Set in
position

mm2

Solid
bond

Solid
bond

Solid
bond

Solid
bond

Cond.
kA

Scr.
kA

kN

mm

mm

185

375

390

324

312

17.5

16.5

5.6

1184

888

240

427

460

375

359

22.7

16.5

7.2

1230

923

300

500

531

421

414

28.4

16.5

1238

929

400

578

601

476

468

37.8

16.5

12

1296

972

500

656

695

539

546

47.3

16.5

12

1364

1023

630

757

796

601

625

59.6

16.5

12

1440

1080

800

859

906

664

695

75.7

16.5

12

1498

1124

1000

992

1046

757

796

94.6

16.5

12

1606

1205

1200

1085

1148

820

859

114

16.5

12

1680

1260

Electrical Parameters
Conductor
nominal cross
sectional area

Conductor DC
resistance at
20

Cond.AC
resistance at
50Hz and 90

Inductive
reactance at
50Hz and 90

Conductor to screen
capacitance

Screen DC
resistance at 20

Zero sequence
resistance at 20

Zero seq. react at


50Hz

mm2

Ohm/km

Ohm/km

Ohm/km

F/km

Ohm/km

Ohm/km

Ohm/km

185

0.164

0.211

0.155

0.129

0.162

0.197

0.085

0.162

0.167

0.082

240

0.125

0.161

0.151

0.135

300

0.1

0.129

0.139

0.164

0.162

0.158

0.079

400

0.0778

0.101

0.135

0.176

0.162

0.145

0.074

500

0.0605

0.079

0.131

0.201

0.162

0.139

0.07

630

0.0469

0.062

0.123

0.226

0.162

0.123

0.063

800

0.0367

0.0495

0.116

0.258

0.162

0.114

0.059

0.162

0.102

0.057

0.162

0.0976

0.055

1000

0.0298

0.0387

0.114

0.263

1200

0.0247

0.0323

0.113

0.287

AUSSA Power Products PTY LTD PO Box 3132 Hendra Queensland 4011.
Phone: (07) 3868 2325 Mobile: 0420 610 557 Fax: (07) 3868 1340
Email: info@aussa.com.au Website: www.aussa.com.au

76/132kV Single Core


Al XLPE CWS(16.5kA/s) APL PVC HDPE
Conductor
diameter

Approx
insulation
thickness

Approx
diameter
over
insulation

Approx
screen
area on
each core

Number
and approx
diameter of
screen wires

Approx
diameter
over wire
screen

mm2

mm

mm

mm

mm2

no/mm

mm

mm

mm

mm

mm

kg/km

185

15.9

22.0

64.5

116.3

76/1.39

72.1

0.25

73.2

1.7/2.2

81.2

4041

240

18.1

21.0

64.5

116.3

76/1.39

72.1

0.25

73.2

1.7/2.2

81.3

4346

300

20.3

21.0

66.9

116.3

76/1.39

74.5

0.25

75.6

1.7/2.2

83.8

4495

400

23.0

21.0

69.7

116.3

76/1.39

77.3

0.25

78.4

1.8/2.3

86.9

4919

500

26.0

21.0

72.9

116.3

76/1.39

80.5

0.25

81.6

1.8/2.3

90.3

5436

630

30.0

21.0

76.4

116.3

76/1.39

84.0

0.25

85.1

1.9/2.4

94

6063

800

34.2

20.0

79.2

116.3

76/1.39

86.8

0.25

87.9

1.9/2.5

97

6708

1000

39.2

20.0

84.4

116.3

76/1.39

92.0

0.25

93.1

2.0/2.5

102.5

7758

1200

42.8

20.0

88.0

116.3

76/1.39

95.6

0.25

96.7

2.0/2.6

106.3

8562

Conductor
nominal cross
sectional area

Approx Nominal
Nominal
Approx
thickness diameter thickness of overall
of APL over APL PVC and
diameter
HDPE

Current Ratings

Installation
Min.bending radius

Continuous current-carrying capacityA


Conductor
nominal cross
sectional area

Approx
mass

In air

Fault current
carrying capacity
for 1 second

In ground

Permissable pulling
force

During
installation

Set in
position

mm2

Solid
bond

Solid
bond

Solid
bond

Solid
bond

Cond.
kA

Scr.
kA

kN

mm

mm

185

383

391

332

336

17.5

16.5

5.6

1624

1218

240

453

461

383

391

22.7

16.5

7.2

1626

1220

300

500

516

438

430

28.4

16.5

1676

1257

400

578

602

492

484

37.8

16.5

12

1738

1304

500

672

680

555

531

47.3

16.5

12

1806

1355

630

773

797

633

609

59.6

16.5

12

1880

1410

800

859

922

711

680

75.7

16.5

12

1940

1455

1000

1023

1063

805

781

94.6

16.5

12

2050

1538

1200

1117

1164

867

969

114

16.5

12

2126

1595

Cond.AC
resistance at
50Hz and 90

Inductive
reactance at
50Hz and 90

Conductor to screen
capacitance

Screen DC
resistance at 20

Zero sequence
resistance at 20

Zero seq. react at


50Hz

F/km

Ohm/km

Ohm/km

Ohm/km

Electrical Parameters
Conductor
nominal cross
sectional area

Conductor DC
resistance at
20

mm2

Ohm/km

Ohm/km

Ohm/km

185

0.164

0.127

0.175

0.067

0.162

0.302

0.126

0.162

0.263

0.123

240

0.125

0.0973

0.169

0.072

300

0.100

0.0781

0.166

0.076

0.162

0.239

0.118

400

0.0778

0.0618

0.162

0.079

0.162

0.216

0.098

500

0.0605

0.0489

0.154

0.092

0.162

0.199

0.082

630

0.0469

0.039

0.146

0.099

0.162

0.185

0.076

800

0.0367

0.0318

0.137

0.107

0.162

0.175

0.073

0.162

0.167

0.071

0.162

0.164

0.064

1000

0.0298

0.0241

0.131

0.128

1200

0.0247

0.0202

0.127

0.136

AUSSA Power Products PTY LTD PO Box 3132 Hendra Queensland 4011.
Phone: (07) 3868 2325 Mobile: 0420 610 557 Fax: (07) 3868 1340
Email: info@aussa.com.au Website: www.aussa.com.au

You might also like