You are on page 1of 40

ENGLISH

Wall-hung gas boilers

CITY 1.24 and 2.24 GN CITY 1.24 and 2.24 B/P

Installation and commissioning manual


11/00 - 94858165 - 8666-4118A

CONTENTS
1. GENERAL . . . . . . . . . . . . . 1.1 Description . . . . . . . . 1.2 Approvals . . . . . . . . . . 1.3 Technical specifications 2. MAIN DIMENSIONS . . 2.1 Packages . . . . . . . 2.2 Mounting backplate 2.3 Installed boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 3 3 4 5 5 5 6

3. SCHEMATICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 4. CONTROL PANEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8 5. HYDRAULIC SPECIFICATIONS . . . . . . 5.1 Circulator . . . . . . . . . . . . . . . . . . . 5.2 8 litre expansion tank . . . . . . . . . . . 5.3 12 litre expansion tank (option) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9 .9 .9 .9

6. INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9 6.1 Regulations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9 6.2 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11 6.2.1 Installing the backplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11 6.2.2 Water and gas connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11 6.2.3 Water drainage connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12 6.2.4 Installing the boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12 6.2.5 230 V electrical power supply connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12 6.2.6 Connection of the Easymatic control or a room thermostat (option) . . . . . . . . . . . . . . . . . . .13 6.3 Pump logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14 6.4 Fitting the boiler casing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15 7. PRESSURE SETTING AND CALIBRATED INJECTOR AND DIAPHRAGM MARKINGS 8. COMMISSIONING . . . . . . . . . . . . . . . . . . . . . . . . . . 8.1 Pre-commissioning checks . . . . . . . . . . . . . . . . 8.2 Switching on the boiler . . . . . . . . . . . . . . . . . . . 8.3 Filling the installation with water . . . . . . . . . . . . 8.4 Igniting the boiler . . . . . . . . . . . . . . . . . . . . . . . 8.5 Air bleed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.6 Adjusting the domestic hot water flow rate . . . . 8.7 Adjustment of the maximum holding temperature 8.8 Checks and adjustments in service . . . . . . . . . . 8.8.1 Burner pressure check . . . . . . . . . . . . . . 8.8.2 Burner safety check . . . . . . . . . . . . . . . . 8.8.3 Safety thermostat check . . . . . . . . . . . . . 8.8.4 Switching off the boiler . . . . . . . . . . . . . . 8.8.5 Anti-overflow safety check . . . . . . . . . . . 9.1 9.2 9.3 9.4 9.5 9.6 9.7 Removing the burner . . . . . . . . . . . . . Replacing the injectors . . . . . . . . . . . . Replacing the diaphragm . . . . . . . . . . Replacing the gas assembly modulator Reassembling . . . . . . . . . . . . . . . . . . Adjusting the minimum pressure . . . . . Gas type label . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. .. .. .. .. .. .. of .. .. .. .. .. .. . . . . . . . . . . . . . . . . . . . . . . . . ................ ................ ................ ................ ................ ................ ................ the DHW exchanger ................ ................ ................ ................ ................ ................ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16 .16 .16 .16 .16 .17 .17 .17 .18 .18 .19 .19 .20 .20 .21 .22 .22 .22 .22 .23 .23 .24 .24 .24 .25 .25

9. MODIFICATION TO USE DIFFERENT GAS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21

10. MAINTENANCE . . . . . . . . . . . . . . 10.1 Main heat exchanger . . . . . . . 10.2 Burner . . . . . . . . . . . . . . . . . . 10.3 Domestic hot water . . . . . . . . 10.4 Cleaning the cold water filter 11. DRAINING DOWN

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26

12. ELECTRICAL CIRCUIT DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27 13. FAULT CODES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29 14. LIST OF SPARES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29 15 WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37

1. GENERAL
1.1 Description
CITY 1.24 wall hung gas boilers are for central heating only. They can be associated with 50, 80 or 150 litre storage tanks to produce domestic hot water. CITY 2.24 boilers provide central heating and instantaneous domestic hot water. They use natural gas or butane/propane. CITY 1.24 GN and CITY 2.24 GN boilers are factory set for use with natural gas. CITY 1.24 B/P and CITY 2.24 B/P boilers are factory set for use with butane/propane. The boiler output can be varied between 10 and 24 kW for central heating and 8 and 24 kW for domestic hot water. These boilers are supplied in 2 packs: - backplate pack: water, gas and drain connections (safety valve, disconnector and domestic hot water pot bleeder on the 2.24 model). - boiler pack. Note: An extended height backplate must be used for boilers associated with an 80 litre tank.

Boiler CE No. Category Type Combustion product removal Ignition Gas

2.24 GN

2.24 B/P 1.24 GN CE-0085 AT 0282 II


2E+ 3+

1.24 B/P

B 11 BS Flue liner Automatic Natural gas Butane/Propane Natural gas Butane/Propane

1.2 Approvals
CITY boilers conform to the following European directives and standards: 90/396 EEC 73/23 EEC 89/336 EEC Gas appliance directives Applicable standards: EN 297 and EN 625. Low voltage directives Applicable standards: EN 60.335.1 EMC directives Applicable standards: EN 50.081.1/ EN 50.082.1./EN 55.014 Efficiency directives ## CE

92/42 EEC

1.3 Technical specifications


BOILER Nominal usable output (central heating and hot water modes) Nominal rated output (central heating and hot water modes) Combustion efficiency Minimum usable output (central heating mode) Minimum rated output (central heating mode) Minimum usable output (domestic hot water mode) Minimum rated output (domestic hot water mode) Maximum temperature (safety thermostat trips out) Weight of boiler without water, backplate, casing Weight of boiler without water, with backplate and casing Shipping weight Central heating circuit Nominal water flowrate (T = 20 K) Available head Outlet temperature Maximum pressure Expansion tank Initial tank pressure Minimum working pressure Gas flowrate at nominal output Natural gas H (G20) Natural gas L (G25) Butane (G30) Propane (G31) Domestic hot water Specific hot water flow rate (T = 30 K) Setpoint temperature Maximum cold water pressure Minimum operating pressure Minimum pressure for 11 l/min Combustion product circuit Connection Minimum draw Combustion product flowrate (nominal output) Combustion product temperature (nominal output) Electrical circuit Supply voltage (50 Hz) Output consumption 1 mbar = 100 Pa 1 daPa ~ 1mm H2O kW kW % kW kW kW kW C kg kg kg l/h bar C bar l bar bar m3/h m3/h kg/h kg/h l/mn C bar bar bar mm mbar kg/h C V W 1.24 24 26.4 > 92 10 11.5 105 30 42 47 1034 0.1 40 - 90 3 8 0.75 0.3 2.79 2.97 2.08 2.05 125 0.035 69.5 114 230 80 2.24 24 26.4 > 92 10 11.5 8 9.5 105 35 47 52 1034 0.1 40 - 90 3 8 0.75 0.3 2.79 2.97 2.08 2.05 11.2 40 - 60 10 0.1 1.3 125 0,035 69.5 114 230 80

Serial No.
The serial number is on the information plates on the boiler.

mini information plate

information plate
8666N175

2. MAIN DIMENSIONS
2.1 Packages
Pack Number Boiler CITY 2.24 GN CITY 2.24 B/P CITY 1.24 GN (50)* CITY 1.24 B/P (50)* CITY 1.24 GN (80)* CITY 1.24 B/P (80)* Pack dimensions Backplate pack
A C

Backplate pack HA 10 HA 10 HA 9 HA 9 HA 11 HA 11

Boiler pack HA 3 HA 4 HA 1 HA 2 HA 1 HA 2

* CITY 1.24 GN and CITY 1.24 B/P central heating boilers can be used in conjunction with a 50 or 80 litre storage tank. If they are associated with an 80 litre storage tank they can be mounted on an HA 11 increased height backplate so that the front panel of the boiler can be lined up with that of the storage tank.

Boiler pack 1000

B
8666N073

540

Pack HA 9 HA 10 HA 11

A 860 890

B 375 389

C 95 139 570
8666N074

2.2 Mounting backplate


Standard backplate for 1.24 and 2.24
332

Increased height backplate for 1.24 / 80L


332

630

173

55 55 55 55 153 20

55 55 55 55 153 20

27,5

8666N075

97,5

173

630

8666N076

2.3 Installed boiler


CITY 1.24 and 2.24 CITY 1.24 with increased height backplate (for lining up with 80 litre domestic hot water storage tank)
380 230
450 = =
Coupling ring internal diameter 125 mm

450 = =
Coupling ring internal diameter 125 mm

450 300

880

880

8666N077

8666N078

3. SCHEMATICS
CITY 2.24

2.24 and 1.24 boilers


1. 2. 3. 4. Central heating outlet valve Domestic hot water outlet valve Gas inlet valve Cold water inlet valve: - water flow open / close - flowrate adjustment - filter (removable from below) 5. Central heating return valve 6. Drain screw 7. Water flowrate sensor 8. Domestic hot water outlet sensor 9. Domestic hot water heat exchanger drain screw 10. Domestic hot water heat exchanger maintain temperature sensor 11. Domestic hot water heat exchanger air bleed screw 12. Central heating / domestic hot water changeover valve drive motor 13. Central heating / domestic hot water changeover valve 14. Electronic pressure gauge 15. Degassing chamber 16. Circulator motor 17. Burner pressure offtake 18. Ionisation sensor 19. Expansion tank 20. Expansion tank inflation valve 21. Automatic bleeder 22. Anti-backflow draw cup-out 23. Combustion product connector 24. Combustion product anti-overflow sensor 25. Main heat exchanger 26. Central heating outlet temperature sensor 27. Safety thermostat 28. Combustion chamber 29. Burner 30. Igniter electrodes 31. Gas valve modulator 32. Gas valve safety valves 33. Gas supply pressure offtake 34. Modulator gas valve 35. Domestic hot water heat exchanger (2.24 only) 36. Central heating circuit safety valve 37. Central heating circuit by-pass pipe 38. Disconnector 42. Igniter 43. Domestic hot water flow rate controller (10 l/min) 44. Non return valve * If boiler is connected to domestic hot water storage tank
24 25 26
TS S1 TAF

23 22 21 20

27 28 29 30 31 32 42 33 34 35 44 36
S2

19

18 17 16
M 2 1

15 14 13 12 11 10 9 43 8 7

S3

37 38 6
Central heating outlet D.H.W.

6
Gas inlet D.C.W.

6
Central heating return

CITY 1.24

M 2 1

Central heating outlet

Domestic* hot water storage tank primary outlet

gas inlet

Domestic* hot water storage tank primary return

Central heating return 8666N016F

4. CONTROL PANEL

B 1 B2

L
F. Installer button G. 3-position switch - off/anti-freeze

8666N020

A. Temperature display - displays the temperature at the central heating outlet or the domestic hot water outlet when water is drawn off. B. Domestic hot water heat exchanger temperature button (CITY 2.24 only). This function is factory set to the activated position. This provides maximum user comfort. When the boiler is switched on, indicator B2 is on to show that this function is activated. The function can be deactivated, for example in the event of prolonged absence, by pressing button B (indicator B2 turns off). Disconnection of the output supply does not modify the selected operating mode. Note: - if indicators B1 and B2 are both turned on, the burner has been ignited to heat the domestic hot water supply. - B2 flashes when the holding position is activated by bypassing the Easymatic control. C. Safety indicator D. Unlocking button - used to reset the boiler from failsafe mode E. clean button - forces operation of the boiler press and hold for 5 seconds (display shows to force the burner to the P min position )

- central heating and domestic hot water (winter) - domestic hot water (summer) H. Central heating on indicator - on when the boiler is ignited to heat the water in the central heating circuit I. Central heating temperature control - range from 40 to 90C (click stop at 75C) J. Flame present indicator - on when the burner is ignited K. Domestic hot water temperature control - range from 40 to 60C (click stop at 55C) L. Domestic hot water on indicator - on when the burner is ignited to heat the domestic hot water supply M. Pressure indicator - indicates the pressure in the central heating circuit (0.5 to 2.5 bars)

press again (display shows ) to force the burner to the P max (24 kW) position
8

5. HYDRAULIC SPECIFICATIONS
5.1 Circulator
The circulator incorporated in the boiler is equipped with a 3-speed motor with a output consumption of 80 W supply. It is factory-set on high. Remark For boilers also producing domestic hot water (City 2.24 or 1.24 plus storage cylinder), the circulator can if required be set on intermediate. It is nevertheless recommended, for reasons of comfort, to leave it on high. For installations requiring greater hydraulic performance it is possible to replace the motor with a more outputful one (pack HA 209) with a output consumption of 93 W.
6

GV
5

GV
Head (mcE)
4

MV

MV PV

PV
1

200

400

600

800

1000

1200
8666N079

Flowrate (l/h)

1. PV : low speed 2. MV : medium speed 3. GV : high speed

80 W motor 93 W motor (option)

5.2

8 litre expansion tank


Static head in metres up to Total water volume 5 6 7 8 9 10

CITY boilers are equipped as standard with an 8 litre tank (initial pressure 0.75 bar). The total water volume is determined in accordance with the static head of the installation and for an average water temperature of 80C (flow: 90/return:70).

138 129 120 111 102 92

5.3

12 litre expansion tank

CITY boilers can optionally be fitted with a 12 litre expansion tank (initial pressure 0.75 bar) (pack HA 208).

Static head in metres up to Total water volume

10

213 204 195 186 177 167

6. INSTALLATION
6.1 Regulations
Installation and maintenance regulations The appliance must be installed and maintained by a qualified professional in accordance with statutory requirements. Establishments receiving the public Installation regulations: The appliance must be installed and maintained in accordance with statutory requirements.

48 cm mini

55 cm mini

S1

15 mm mini

15 mm mini 10 cm mini *

S2

5 cm either side of the boiler

- The connection to the flue must be as short and direct as possible. - Do not install the boiler over a cooker.
8666N089

S1 and S2 : Minimum 600 cm2 unimpeded area 10 cm min * : Distance between front of boiler and inside of closure panel

30 cm mini
8666N090

- The boiler must be fixed to a solid wall capable of supporting the weight of the appliance when filled with water and associated equipments. - A 15 mm gap on either side of the boiler is sufficient for removing and replacing the casing. However, a 50 mm gap is recommended to facilitate maintenance.

The installation must comply with applicable regulations. Thermostatic radiator valves must not be used on all radiators. The CITY boiler incorporates a by-pass assuring a minimum flow of 200 l/h. Radiators in rooms containing a room thermostat must not be fitted with thermostatic valves.

- The boiler must not be installed above a heat source or a cooker. - The IPX4D protection index authorises installation in bathrooms, but outside protection level 1 and 2 volumes.
Ventilation of the room in which the boiler is installed Fresh air supply In the case of direct fresh air entry, the minimum area required is 50 cm2. Vitiated air extraction If the boiler is installed in a kitchen, for example, vitiated air from appliances not connected to an extractor pipe (gas cooker, etc.) can be extracted via the draw cup of the boiler. For this it is sufficient for the top of the boiler casing to be at least 1.8 m above the floor.

Note: We would draw your attention to the risk of corrosion of boilers installed or near rooms in which the atmosphere may be polluted by substances containing chlorine or fluorine. Examples are: hairdressing salons, industrial premises (solvents), refrigeration plants, etc. The warranty does not cover such installations.

10

6.2 Connections
Important notes:
Before connecting the boiler to an existing installation, the installation must be thoroughly rinsed out using an appropriate product to prevent sludge reaching the heater body of the new boiler. If different metals are used, such as copper and aluminium, a corrosion inhibitor must be used.

6.2.1 Installing the backplate See the installation instruction sheet supplied in the backplate pack. 6.2.2 Water and gas connections With 8 or 12 litre expansion tanks, the connections can be made from below, from above or from the rear. Tube-cutter Connections From the rear

From above

From below

8666N130

Central heating connection Copper bush for connection to 16/18 mm dia. indoor tube or 20/22 mm dia. outdoor tube. Domestic hot water connection Copper bush for connection to 14/16 mm dia. indoor tube or 18/20 mm dia. outdoor tube. In hard water areas (hardness >25) we recommend a water softener upstream of the boiler. Gas connection Conform to the applicable provisions and in particular gas installation specification. A shut-off valve must always be installed as close as possible to the boiler. The copper bush is for 16/18 mm dia. indoor copper tube. Operating pressure 20 mbar for H natural gas H 25 mbar for H natural gas L 29 mbar for butane 37 mbar for propane (G20) (G25) (G30) (G31)

Central heating outlet 18

D.H.W 16

Gas inlet 18

D.C.W 16

Central heating return 18

18 od

16 od

18 od

16 od

18 od

20 id

18 id

18 id

20 id

All nested connections to the gas tube must be made using sleeves purchased off the shelf.
8666N081

11

6.2.3 Water drain connection The 32 mm diameter waste water drainage connection supplied with the backplate must be fitted only after brazing the copper tubes. It is P19 to the left-hand upright of the fixed backplate using a 12 mm long 4 mm diameter screw. Evacuation to a drain is by means of a syphon.
8666N088 B

6.2.4 Installing the boiler

Remove the plastic plugs from the boiler pipes.

2 Offer up the boiler above the valve bracket so that it backs onto the backplate. 3 Lower the boiler gently. Fit the 5 seals supplied in the sachet with the manual. 4 Remove the retaining pins and tighten the nuts.

8666N087

6.2.5 230 V electrical main supply connection CITY boilers are fitted with a 3-core main supply cable approximately 1.5 m long. For correct electrical installation, the appliance must be connected to a socket outlet or a circuit including a 2-pole switch with an open contact spacing greater than 3 mm. Electrical connections must be made by a qualified professional. Note: When connecting to the mains electrical main supply, connect the brown wire to live and the blue wire to neutral. If these connections are reversed the ionisation type flame detector will not operate. The boiler will then go to the fail-safe mode.
12

brown to live blue to neutral grenn/yellow to earth

mar ron sur pha se

8666N091 A

6.2.6 Connection of the Easymatic control or a room thermostat (option) The options are to be connected at the back of the control panel under the small flap. - Pivot the panel forwards after unscrewing the 2 fastening side screws. - Pull the small flap towards you and ensure that the connections are in accordance with the selected options. Easymatic communicative remote control (box AD 136) - see the instructions delivered with the Easymatic remote control. Programmable room thermostat (box AD 137) - remove the resistance from the Room Thermostat connector - connect, in any order, terminals 1 and 3 of the thermostat to the terminals of the Room Thermostat connector. - see also the instructions delivered with the thermostat. Non-programmable room thermostat (box AD 140) - remove the resistance from the Room Thermostat connector - connect, in any order, terminals 1 and 4 of the thermostat to the terminals of the Room Thermostat connector. - see also the instructions delivered with the thermostat. Note : If a room thermostat with 2 dry-contact wires has been installed, it may be used. For this: - remove the resistance from the Room Thermostat connector - connect, in any order, the 2 thermostat wires to the terminals of the Room Thermostat connector. Remark: Connections can be with either a 2 wire telephone cable or an electrical section cable of up to 2 x 1,5 mm2.
BU S

TA M

SB
BU S TA M SB 12 3

8666N094

13

6.3 Pump Logic


1. In mode (domestic hot water) or in Easymatic

mode (summer), the pump works when domestic hot water is produced (d.h.w), and cuts off 30 seconds after the d.h.w has been produced; the inversion valve will remain in the d.h.w. position. 2. In mode (heating + d.h.w.)

A. Without a Room Thermostat or Easymatic The pump will work continuously. B. With a Room Thermostat Switch in position 1: Continuous operation of the pump. Switch in position 2: - The pump cuts off 15 minutes after starting the Room Thermostat. - After production of d.h.w., if the Room Thermostat is started up, the pump cuts off after 30 seconds and the inversion valve remains in the d.h.w. position. Switch in position 3: - The pump cuts off 30 seconds after starting the Room Thermostat - After production of d.h.w., if the room thermostat is started up, the pump cuts off after 30 seconds and the inversion valve remains in the d.h.w. position. C. With an Easymatic: Switch in position 1 or 2: Continuous operation of the pump. Switch in position 3: - When the room temperature is correct, the pump remains in continuous operation. - When the room temperature is too high, the pump cuts off after 15 minutes. - After the production of d.h.w., if the room temperature is too high the pump cuts off after 30 seconds and the inversion valve remains in the d.h.w. position 3. In mode
12

BU

ST AM

SB 12 3

8666N124A

The pump is stopped. If need be, when the room temperature falls below 10 C, the pump will start up to prevent the boiler from freezing.

14

6.4 Fitting the boiler casing

Note : fit the front panel after commissioning the boiler.


8666N092 8666N093

7. PRESSURE SETTING AND CALIBRATED INJECTOR AND DIAPHRAGM MARKINGS


Equipment
mm 1.35 0.8 5.2 4.2

CITY 1.24 and 2.24 Burner injectors Diaphragm Natural gas H and L Butane / Propane Natural gas H and L Butane / Propane

Burner pressure and gas flow rate

CITY 1.24 and 2.24 Output Burner pressure Nat. gas H Nat. gas L Butane Propane Nat. gas H Nat. gas L Butane Propane mbar mbar mbar mbar m3/h m3/h kg/h kg/h nominal 6.5 7.9 19.1 24.1 2.79 2.97 2.08 2.05
15

minimum 1.0 1.4 2.5 3.4 1.01 1.07 0.75 0.74

Flow rate*

* 1013 mbar at 15C

8. COMMISSIONING
Commissioning must be carried out by a qualified professional

8.1 Pre-commissioning checks


- Check on the boiler label that it is set up for the gas in use. - If not, see chapter 9 Modification to use a different gas. - Open the gas valve 3. - Take out the 2 fixing screws at the sides and swing the control panel forward. - Check the pressure of the gas supply to the boiler at the pressure offtake on the gas valve (33) against the information plate. - Close the gas pressure offtake screw. - Check for gas and water leaks. Return the control panel to its original position and replace the 2 fixing screws at the sides.
8666N180

33

8.2 Switching on the boiler


Check the 3-position switch G is set to off/anti-freeze and then switch on the boiler by plugging in the plug or operating the isolating switch.

8666N096

8.3 Filling the installation with water


- Open valves 1-2*-4* and 5. - Check that the automatic bleeder 21 at the top of the expansion tank is open. - Fill the installation to a pressure of 1.5 to 2 bars via valves 38.1 and 38.2. - Close valves 38.1 and 38.2 when the installation has been filled with water. * CITY with domestic hot water production.

38.2 38.1

1 2* 4* 5
8666N098 B

8.4 Igniting the boiler


- Set the switch to the position marked
.

- If there is a room thermostat or a communicating remote controller, set it to call for heat.

8666N097

16

8.5 Air bleed


1 Open the stopper of the automatic bleeder in the top rear corner of the boiler. Domestic hot water heat exchanger (CITY 2.24 only) 2 - Bleed the domestic hot water heat exchanger by unscrewing the bleeder slightly. - To accelerate bleeding, alternate between calling for heat and hot water. - Tighten the bleeder after bleeding the air. Central heating installation - Check that all of the installation has been bled correctly.

8666N106 B

8.6 Adjusting the domestic hot water flow rate


(CITY 2.24 only) The maximum domestic hot water flow rate is limited to 10 l/min by the flow rate controller which is mounted on the flow rate detector (item 43 3). This maximum flow rate can be reduced in 2 ways: - 1. by adjusting the screw 4.1 (8 mm Allen key), - 2. by replacing the 10 l/min controller with an 8 l/min controller. The 8 l/min controller (package HA 218) is supplied with fitting instructions.

4.1
8666N105 A

8.7 Adjustment of the maximum temperature position of the DHW exchanger : TMM
(CITY 2.24 only) The DHW exchanger, when activated, is maintained at the projected holding temperature DHW - 5 C or at the maximum TMM. Adjustment - Press the button for 5 seconds Display (55C)

- Press repeatedly to select the desired maximum temperature position TMM

To exit the display, wait 5 minutes without pressing anything


17

8.8. Checks and adjustments in service


8.8.1 Burner pressure check - Unscrew the screw inside the burner pressure offtake 17 a few turns. - Connect a pressure gauge to the pressure offtake and verify that the pressure corresponds to that indicated in chapter 7.

17

8666N104 A

Checking the burner pressure at nominal (max) output: Force the burner to operate at maximum output by pressing the button marked E:

- Press and hold down the clean button E for 5 seconds. The display A indicates . .

- Press button E briefly. The display A indicates

8666N107A

Check that the measured pressure corresponds to that indicated in chapter 7. If there is any significant difference, check that the boiler is equipped for the gas supplied as indicated in the table in chapter 7. To revert to normal operation press button E briefly. - Remember to close the pressure offtake screw 17 after measuring the pressure. - Check the pressure offtake 17 for gas leaks.

18

8.8.2 Burner safety check - With the burner lit, cut off the gas supply by closing the shut-off valve. - Check the reaction of the safety system: the alarm indicator C should turn on and the display A should alternately indicate and .

CD

- Open the gas valve and press the reset button D.


8666N108 B

8.8.3 Safety thermostat check The safety thermostat should shut down the boiler if the temperature at the central heating outlet exceeds 105C. - Press the clean button E for 5 seconds. The display A shows . .

- Press button E briefly. The display A shows

- Press button E a third time for 5 seconds. This forces the burner to minimum output and the display A indicates alternately rature. and the original tempe8666N111 A

- Close the central heating flow and return valves 1 and 5 using an 8 mm wrench. The outlet temperature is no longer limited by the control system and the safety thermostat should shut down the burner. When the temperature exceeds 100C and the safety thermostat has not yet tripped, the display indicates alternately and

8666N218

If the burner is turned off, the boiler cools and shortly afterwards the burner is ignited again and the rise in temperature continues: - when the burner is shut off by the safety thermostat: indicator C turns on the display alternately indicates and

If the boiler has not shut down 2 minutes after shutting the valves, disconnect the boiler from the mains electrical output supply.

C D

- To restart the burner: open central heating flow and return valves 1 and 5 press button D.

8666N219

19

8.8.4 Switching off the boiler Set switch G to off/anti-freeze: The boiler goes to the standby mode and the display indicates Note: In this operating mode only the boiler is protected against freezing.

8666N096

8.8.5 Anti-overflow safety check If fumes overflow through the anti-backflow device, the anti-overflow safety device 24 disconnects the electrical output supply to the valve and the boiler goes to its fail-safe mode. The anti-overflow device must be checked on commissioning the boiler and during annual maintenance.

Check procedure: - Turn off the boiler by setting the 3-position switch G to off/anti-freeze. - Remove the pipe connecting the boiler to the flue. - Using a sheet of metal (or any other heat-resistant material), block the combustion product outlet of the boiler. - Start the boiler; combustion products are evacuated in the upper part of the boiler via the openings in the anti-backflow device. - The anti-overflow sensor disconnects the electrical output supply from the gas valve within 2 minutes. The burner is turned off. - After completing the check, replace the pipe connecting the boiler to the flue. The boiler restarts automatically after about 10 minutes.

24

8666N118

Note: To avoid this time delay it is sufficient to switch off the mains electrical output supply and switch it on again.

20

9. MODIFICATION TO USE DIFFERENT GAS


CITY 2.24 GN and 1.24 GN boilers are equipped to use natural gas. CITY 2.24 B/P and 1.24 B/P boilers are equipped to use butane/propane. The procedure from changing from one gas to the other is as follows: 9.1 Removing the burner 9.2 Replacing the injectors 9.3 Replacing the diaphragm 9.4 Replacing the gas assembly modulator 9.5 Reassembling 9.6 Adjusting the minimum pressure 9.7 Gas type label

The operations described below must be carried out by a qualified professional.

9.1 Removing the burner


Disconnect the electrical output supply and the gas supply from the boiler.
1
1

Remove the front panel from the boiler casing (2 screws at the top). Remove the front plate from the combustion chamber (2 screws at the top + 2 wing-nuts).
2

Disconnect the 2 igniter electrodes.

Disconnect the wire from the ionisation sensor.

8666N177

Remove the anti-radiation plate by pulling it forwards. Unscrew the 3/4 nut at the top of the gas valve. Unscrew the 4 screws fixing the burner to the manifold. Use a magnetic screwdriver if possible. Remove the burner, the diaphragm and the 2 seals.

8666N178

21

9.2 Replacing the injectors

9.3 Replacing the diaphragm

8666N201

8666N179

Replace the injectors and the seals (see chapter 7).

When replacing the burner, fit the new diaphragm to the gas assembly between 2 new seals. See chapter 7.

9.4 Replacing the gas assembly modulator


1 2 Disconnect the two wires from the modulator. Unscrew the 2 screws retaining the modulator using a Torx No. 20 wrench. Replace the modulator and the seal, checking that the seal and the spacer seat correctly. G Modulator with grey cap = natural gas, modulator mark: 1.5 - 20 mbar. G Modulator with yellow cap = butane/propane, modulator mark: 3 - 37 mbar. Reconnect the 2 wires to the modulator.

2 3

8666N184

9.5 Reassembling
Reassembly is the reverse procedure to disassembly. - Connect the igniter electrode. - Connect the ionisation sensor. - Replace the anti-radiation plate. - Replace the combustion chamber side and front plates. - Switch on and open the gas supply. Check for gas leaks.

22

9.6 Adjusting the minimum pressure


Natural gas H and L, butane and propane. Adjust the pressure at the burner downstream of the gas assembly. The values to set are indicated in chapter 7. Measure the pressure at the boiler by connecting a pressure gauge to pressure offtake 17, as follows:

17

8666N104 A

1 2 3

Remove the screw retaining the plastic cover. Remove the cover. Verify that the maximum flowrate plastic nut is screwed fully home. Force operation of the boiler at the minimum output setting by pressing the clean button E and holding it down for 5 seconds (see section 4). Adjust the minimum pressure with the brass nut. - Turning the nut clockwise increases the pressure. - Turning the nut anti-clockwise reduces the pressure. After completing the adjustment, replace the cap.

5 3

To revert to normal operation, press button E briefly. Disconnect the pressure gauge. Screw in the screw of the pressure offtake. Check for gas leaks.

1
8666N183

9.7 Gas type label


Affix the label indicating the type of gas for which the boiler is equipped and set up.

8666N122

23

10. MAINTENANCE
Maintenance operations must be carried out by a qualified professional.

10.1 Main heat exchanger


Periodically check the main heat exchanger for soiling. If necessary remove the heat exchanger and wash it with very hot water containing a detergent. Disconnect the electrical output supply and the gas supply from the boiler. Close the boiler isolating valves and open the drain screws.

Remove the boiler casing front panel (2 screws at the top). Remove the front plate from the combustion chamber (2 screws at the top + 2 wing nuts).

3 4

Remove the anti-radiation plate. Remove the side plates of the combustion chamber. Unscrew the 3/4" nuts of the heat exchanger (30 mm wrench). Remove the main heat exchanger by pulling it towards you.

8666N176

30 5 6 4 3 5

Note: When refitting the main exchanger: - grease the threads of the connectors - replace the seals - tighten the nuts moderately

4
8666N119 A

10.2 Burner
Check the condition of the burner annually. Use a dry soft brush to clean the burner, or wash it with hot water containing a detergent. Rinse thoroughly. For instructions on removing the burner, see section 9.1.
24

10.3 Domestic hot water


If the domestic hot water heat exchanger is affected by limescale, clean it by connecting a descaling pump to the two domestic water connectors Use only products suitable for this purpose.

3
Disconnect the electrical output supply and the gas supply from the boiler. Close the domestic water inlet and outlet valves and open the drain screws.

7 5

To obtain access to the domestic water connectors: 1 2 Tilt the control panel forward after removing the 2 fixing screws at the sides. Protect the control panel from being splashed with descaling product. Unscrew the two 1/2nuts on the domestic water heat exchanger (24 mm wrench). Unscrew slightly the 3/4 nut on the domestic hot water outlet (30 mm wrench). Pivot the domestic hot water outlet tube towards the front. Unscrew the 3/4" nut on the domestic cold water inlet pipe (30 mm wrench). Remove the domestic cold water inlet pipe. Connect the descaling device to the two 1/2" exchanger connectors.

3 4 5

8666N182

7 8

After descaling, reassembly is the reverse of the above procedure. Replace the seals with new seals.

10.4 Cleaning the cold water filter


(CITY 2.24 only) 1 Turn the tap off (6mm spanner) to avoid any drawing off from the domestic circuit (kitchen, bathroom, etc.) and major discharge when the filter is dismantled. Unscrew the drain cock after connecting a hose (dimension: 8 mm). Unscrew the adjustment door-filter-tap with a 17mm spanner. If required, remove the filter and clean it with a soft brush - replace the filter on the filter-door and screw it into the tap (17mm spanner) - turn off the drain cock - turn on the tap (6mm spanner).
25

" !

2 3 4


8666N293

11. DRAINING DOWN


To drain down the boiler: - Close gas valve 3, water valves 1, 2, 5 (8 mm wrench) and 4 (6 mm wrench). - Connect an 8 mm internal diameter hose to drain screw 6. - Unscrew the drain screw.

1 2* 3

6 6* 4* 6* 6

8666N117 B

Boiler prepared for domestic hot water supply.

26

CITY 2.24 with flue liner


8806-5112

10

14

J15 J13 8806-5111 J8 J10 J2 J7 J8 J11


1 2 3 4 5 6

J18 J6

1 2 3

1 2 3

J1

1 2

J17

SCH

J12

SECS

SECSM

1 2 3 4 5 6

MNM

12. ELECTRICAL CIRCUIT DIAGRAMS

27
TEMPO
2 1 3 2 1 2 1 2 1

TAF J4 J1 LN
ALI. 230V / 50Hz

DBM J3 J2
SB TAM

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

J5

J3

J4

J5

65 43 21

CDC

TS

SI VGM TA
5 6 8666N110 E based on 8666.4074 C

M VINV P

ALI CDC DBM EXT J.. MNM P

Output supply Communicating remote controller Flowrate detector External Printed circuit connector Pressure gauge Pump

SB SCH SECS SECSM SI TA TAF

Tank sensor Boiler sensor Domestic hot water sensor Domestic hot water maintain temp. sensor Ionisation sensor Igniter transformer Anti-backflow thermostat

TAM TEMPO TS VGM VINV

Room thermostat Time-delay adjustment Safety thermostat Modulating gas valve Inverter valve

CITY 1.24 with flue liner


8806-5112

10

14

J15 J13

J18 J6 J8 J10 J2 J7

1 2 3

1 2 3

J1

1 2

J17

8806-5111

SCH

J12

J11
1 2 3 4 5 6

J8

1 2 3 4 5 6

MNM

28
J5
6 5 4 3 2 1 TEMPO
SB TAM 2 1 3 2 1 2 1 2 1

TAF

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

J3 J4 J1 LN
ALI. 230V / 50Hz

J4

J5

J3

J2

CDC

TS

SI VGM TA
5 6 8666N109 E based on 8666.4078 C

M VINV P

ALI CDC DBM EXT J.. MNM P

Output supply Communicating remote controller Flowrate detector External Printed circuit connector Pressure gauge Pump

SB SCH SECS SECSM SI TA TAF

Tank sensor Boiler sensor Domestic hot water sensor Domestic hot water maintain temp. sensor Ionisation sensor Igniter transformer Anti-backflow thermostat

TAM TEMPO TS VGM VINV

Room thermostat Time-delay adjustment Safety thermostat Modulating gas valve Inverter valve

13. FAULT CODES


In the event of a fault, the display indicates an alarm message by alternately showing and a code from which the type of fault can be determined. There are two alarm categories:

1. Safety alarms
Alarm code Meaning Igniter fault Ionisation fault Spurious flame Overheating alarm No water Combustion product overflow. Display shows combustion product temperature at time of overflow Card fault Safety fault display interrupted

8666N121

2. SENSOR alarms
Alarm code ou ou Meaning Central heating outlet temperature sensor fault Anti-overflow sensor fault Domestic hot water outlet (CITY 2.24) storage tank (CITY 1.24) sensor fault Domestic hot water maintain temperature function sensor fault Storage tank sensor connection on CITY 2.24 (incoherent) Electronic pressure gauge fault

ou
8666N121

14. LIST OF SPARES


See following pages

29

8666-4140 A

Spares
Note: to order a spare part it is essential to give the code number in the list opposite the item number of the part required.

CITY 1.24 and 2.24

FRAME
2 1

7 6
8666N133

ANTI-BACKFLOW DEVICE + COMBUSTION CHAMBER


9

66

8 10

13 11

14 12

11
8666N134

DE DIETRICH THERMIQUE BP 30 57, rue de la Gare F-67580 MERTZWILLER Tl. : +33 3 88 80 27 00 Fax : +33 3 88 80 27 99 N IRC : 347 555 559 RCS STRASBOURG Spare Part Centre 4, rue d'Oberbronn F-67110 REICHSHOFFEN Tel. :+33 3 88 80 26 50 Fax : +33 3 88 80 26 98

CITY 1.24 and 2.24


PIPES 1 SERVICE

26

26

25

25A

19

15 19A

17

18

16

8666N135B

PIPES 2 SERVICES
21 25A 26 26

25 19 24

23

22

19A

20 17

16

8666N136 B

2/7

CITY 1.24 and 2.24


BURNER
34 / 35 64 65

14x 42

2x

30 / 31 32 33 91 92 38 39 / 40
4x

38a

36 93 37

41
8666N137A

DOMESTIC HOT WATER HEAT EXCHANGER AND 3-WAY VALVE ASSEMBLY


50

CITY 2.24 ET 2.24 FF

Montage
Colis HA 218
Blanc : 8 l/mn

Kit rgulateur de dbit d'eau sanitaire

Bleu : 10 l/mn

Assembly
- Fermer les vannes dpart de sanitaire 4 .

8666N191

Pour monter un rgulateur de dbit 8 l/mn ou 10 l/mn sur une chaudire CITY 2.24 ou 2.24 FF, procder comme suit :

Couper l'alimentation lectrique et l'alimentation en gaz de la chaudire 3 .

2 3

6
2 et entre eau froi-

4 6

- raccord un tuyau flexible intrieur 8 mm sur les vis de vidange 6 , puis les desserrer.

8666N192

03/99 - 948.58.118 - 8666-4106

69 51

45 59 48 46 65 46
From 14/01/99

56

49 54 47

Until 13/01/99

57

61

52

63

68

67
3/7

62

55

60
8666N138 C

CITY 1.24 and 2.24


BOILER CASING
70 102

71

73 72

101

8666N140

CONTROL PANEL
86

79

80

76

88

87 83 78 85 75

77

82

81
8666N139

4/7

CITY 1.24 and 2.24


BRACKET - 1 SERVICE
122 124

128 126 107 106 112

113

108

109 108 111

110

129 105

114

8666N141C

BRACKET 2 SERVICES
122 124 116

128

118 117 126 127

123 125 119 121 121a 120 115

8666N142 A

5/7

CITY 1.24 and 2.24


Ref. Code No.
FRAME 1 2 3 4 5 6 7 8666-8500 8666-5500 8666-5501 8666-5502 8666-5503 8666-5504 8666-5505 COMPLETE (CPL) FRAME COMPLETE LEFT UPRIGHT COMPLETE RIGHT UPRIGHT COMPLETE CHASSIS SUPPORT COMPLETE TANK SUPPORT COMPLETE PIPE SUPPORT COMPLETE CABLE-CLAMP 34 35 ANTI-BACKFLOW DEVICE 8 9 8666-5569 8666-5506 COMPLETE ANTI-BACKFLOW DEVICE COMPLETE NOZZLE 36 36 COMBUSTION CHAMBER 10 11 12 13 14 8666-5507 8666-8544 8666-8545 8666-5508 8666-5509 COMPLETE COMBUSTION CHAMBER BACK INSULATED COMBUSTION CHAMBER SIDE PLATE INSULATED COMBUSTION CHAMBER FRONT PLATE COMBUSTION CHAMBER INSULATION KIT FRONT PLATE FIXING ROD KIT 37 38 38a 39 40 41 42 PIPES 1 SERVICE 15 16 17 18 19 19a 25 25a 8666-5510 8666-5511 8666-5512 8666-5513 8666-5514 8666-5578 9758-1257 8666-5579 COMPLETE CENTRAL HEATING OUTLET PIPE COMPLETE PRIMARY RETURN PIPE CPL CENTRAL HEATING EXCHANGER RETURN PIPE CPL DOMESTIC HOT WATER PRIMARY RETURN PIPE COMPLETE EXPANSION TANK PIPE COMPLETE EXPANSION TANK PIPE 8 LITRE EXPANSION TANK COMPLETE EXPANSION TANK 45 46 47 48 49 50 51 52 8666-5527 9490-2000 9491-8134 9491-4277 8666-5528 8666-5529 8666-5530 8666-5531 2 SERVICES ONLY COMPLETE DOMESTIC HOT WATER EXCHANGER DRAIN VALVE BLEED SCREW NON-RETURN VALVE DOMESTIC HOT WATER EXCHANGER FIXING KIT CPL DOMESTIC HOT WATER EXCHANGER BASE DOMESTIC HOT WATER EXCHANGER INSULATING KIT DRAIN PIPE 8666-5522 8666-5580 8666-5523 8666-5524 8666-5581 8666-5525 8666-5526 8666-8019 8666-5577 GAS VALVE COMPLETE NG VALVE COMPLETE B/P VALVE COMPLETE GAS PIPE COMPLETE VALVE GAS/MANIFOLD PIPE COMPLETE FLANGE COMPLETE NG DIAPHRAGM COMPLETE BP DIAPHRAGM ANTI-RADIATION PLATE COMPLETE CENTRAL HEATING EXCHANGER 8666-7212 8666-7213 CONVERSION KIT NG CONVERSION KIT BP CONVERSION KIT 30 31 32 33 9758-0051 9758-0052 8666-5520 8666-5521

DESCRIPTION

Ref. Code No.


BURNER

DESCRIPTION

WORGAS NG BURNER WORGAS BP BURNER COMPLETE IGNITER SPARK PLUG SET COMPLETE IONISATION SENSOR

2 SERVICES 16 17 19 19a 20 21 22 23 24 25 25a 26 8666-5511 8666-5512 8666-5514 8666-5578 8666-5515 8666-5516 8666-5517 8666-5518 8666-5519 9758-1257 8666-5579 9491-8141 COMPLETE PRIMARY RETURN PIPE CPL CENTRAL HEATING EXCHANGER RETURN PIPE COMPLETE EXPANSION TANK PIPE COMPLETE EXPANSION TANK PIPE COMPLETE PRIMARY OUTLET PIPE CPL CENTRAL HEATING EXCHANGER OUTLET PIPE COMPLETE LOOP TUBE COMPLETE DOMESTIC COLD WATER PIPE COMPLETE DOMESTIC HOT WATER PIPE 8 LITRE EXPANSION TANK COMPLETE EXPANSION TANK AUTOMATIC AIR BLEEDER + SEAL 62 63 64 65 9536-5107 8666-5533 8666-5534 9536-2442 54 55 56 57 59 60 61 9513-2296 9510-0502 8666-5541 8666-5576 8666-5571 9750-9052 8666-5532

COMPLETE 3-WAY VALVE COMPLETE CIRCULATOR COMPLETE STEPPER MOTOR COMPLETE CIRCULATOR BASE CIRCULATOR SEAL SUB-ASSEMBLY COMPLETE VALVE BODY COMPLETE VALVE COMPLETE 3-WAY VALVE FLANGE

CONTROL AND SAFETY SYSTEM ELECTRONIC PRESSURE GAUGE COMPLETE SAFETY VALVE COMPLETE SAFETY THERMOSTAT SCREW-IN TEMPERATURE SENSOR

6/7

CITY 1.24 and 2.24


Ref. Code No.
66 9536-2443

DESCRIPTION
FUMES SENSOR

Ref. Code No.


8666-4932 8666-4934

DESCRIPTION
1.24 BASIC HARNESS CH.HO HONEYWELL CABLE CONNECTOR

2 SERVICES ONLY 67 68 69 8666-5535 9536-2440 8666-7218 COMPLETE FLOWRATE DETECTOR CLIP-ON DOMESTIC HOT WATER OUTLET SENSOR KIT DOMESTIC HOT WATER FLOW RATE CONTROLLER (10 L/MN) 1 SERVICE BOILER CASING 70 71 72 73 8666-8540 8666-8549 8666-8550 8666-8551 8666-5536 CASING ASSEMBLY FLUE-LINER COMPLETE LEFT SIDE PANEL COMPLETE RIGHT SIDE PANEL FRONT PANEL ASSEMBLY FLUE LINER BOILER SCREW FASTENERS PACK 105 106 107 108 109 110 111 CONTROL PANEL 75 75 75 75 76 77 78 79 80 81 82 83 8666-8564 8666-8565 8666-8566 8666-8567 9752-5362 9655-9151 8666-5544 8666-5545 9752-5312 8666-5546 9655-9150 8666-5547 8666-5548 85 86 87 88 91 92 93 8806-5512 8806-5511 8666-5549 9654-7000 8666-5582 8666-5583 8666-5584 8666-4926 COMPLETE 1.24 NG CONTROL PANEL HO COMPLETE 1.24 B/P CONTROL PANEL HO COMPLETE 2.24 NG CONTROL PANEL HO COMPLETE 2.24 B/P CONTROL PANEL HO PRE-ASSEMBLED PANEL FRONT PANEL PLATE COMPLETE CARD SUPPORT COMPLETE REAR COVER CONNECTOR COVER COMPLETE PRE-ASSEMBLED FLAP FLAP PLATE CONTROL BUTTON KIT PANEL ACCESSORY KIT COMPLETE DISPLAY CARD CPL WALL-MOUNT CENTRAL UNIT CARD COMPLETE CHEM SAFETY CARD 4 A FUSE COMPLETE ANSTOSS IGNITER COMPLETE IGNITER SUPPORT COMPLETE IGNITER COVER ASSEMBLED 2-PIN CONNECTOR 115 116 117 118 119 120 121 8666-8507 8666-5551 8666-5552 8666-5553 8666-5554 8666-5555 8666-5556 2 SERVICES COMPLETE 2.24 CONNECTOR PANEL UNEQUIPPED CONNECTOR PANEL PLUS FIXINGS CPL CENTRAL HEATING OUTLET VALVE CPL DOMESTIC HOT WATER OUTLET VALVE COMPLETE GAS VALVE COMPLETE CENTRAL HEATING RETURN VALVE COMPLETE COLD WATER INLET VALVE D. C. W. ADJUSTER SCREW + VALVE FILTER COMPLETE DISCONNECTOR COMPLETE BYPASS CONNECTING PIPE CPL DISCONNECTOR DOWNSTREAM CON. PIPE CPL DISCONNECTOR UPSTREAM CONNECTOR PIPE COMPLETE DISCONNECTOR FLOW PIPE COMPLETE 2.24 CONNECTOR PIPE KIT COMPLETE EVACUATION CONNECTOR 112 113 114 128 129 8666-8506 8666-5551 8666-5552 8666-5553 8666-5554 8666-5555 8666-5558 8666-5562 8666-5575 8666-5574 8666-5564 8666-5587 COMPLETE 1.24 CONNECTOR PANEL UNEQUIPPED CONNECTOR PANEL PLUS FIXINGS COMPLETE CENTRAL HEATING OUTLET VALVE COMPLETE DOMESTIC HOT WATER OUTLET VALVE COMPLETE GAS VALVE CPL CENTRAL HEATING RETURN VALVE COMPLETE BYPASS CONNECTING PIPE 161 MM CONNECTING PIPE KIT 231 MM CONNECTING PIPE KIT COMPLETE FILLER TUBE COMPLETE EVACUATION CONNECTOR PIECES FOR CONNECTION 101 102 8666-1517 8666-0543 BACKPLATE ASSEMBLE BACKPLATE BACKPLATE HEIGHT EXTENSION

121a 8666-5570 122 123 124 125 126 127 128 8666-5557 8666-5558 8666-5559 8666-5560 8666-5561 8666-5563 8666-5564

WIRING HARNESSES 8666-4922 8666-4923 8666-4925 8666-4924 8666-4929 8666-4930 MAIN SUPPLY CABLE PUMP CABLE IONISATION SENSOR CABLE UC-CS BUS CONNECTION CABLE EARTH WIRE 2.24 BASIC HARNESS CH.HO 8666-5565 8666-5566 8666-5567 9731-0700

SUNDRY PANEL SEAL PACK BACKPLATE FIXINGS PACK BOILER SEALS PACK O-RING GREASE

11/00

7/7

15. WARRANTY
Thank you for purchasing a DE DIETRICH appliance, and for the confidence in us that your purchase demonstrates. We would like to point out to you that the device will retain its original qualities only if it checked and maintained regularly. Your installer and the entire DE DIETRICH network are naturally ready, willing and able to assist you. Warranty conditions Your device is warranted against all manufacturing defects from the date of purchase for a period of 2 years. We shall not be liable as manufacturer in the event of incorrect use of the device, lack of or insufficient maintenance of the device or incorrect installation of the device (you are responsible for assuring that the boiler is installed by a professional installer). In particular we shall not be liable for damage, losses or injury consequent upon installation that does not conform to: - applicable laws and regulations, - specific requirements relating to the installation, - our manuals and instructions. Our warranty is limited to exchange or repair of parts agreed to be defective by our technical department and excludes labour, travel and transportation costs. Our warranty does not cover replacement or repair of parts required because of normal wear and tear, incorrect use, work carried out by unqualified third parties, lack of or insufficient supervision or maintenance, non-standard electrical output supply and use of inappropriate or poor quality fuel. The warranty covers sub-assemblies such as motors, pumps, solenoid valves, etc. only if they have never been removed from the boiler.

37

Notes

38

Notes

39

Fitter :

Servicing company :

BP 30 - 57, rue de la Gare F-67580 MERTZWILLER + 33/3 88 80 27 00 - Fax : + 33/3 88 80 27 99


N IRC : 347 555 559 RCS STRASBOURG

In the interest of customers, DE DIETRICH THERMIQUE are continuously endeavouring to make improvements in product quality. All the specifications stated in this document are therefore subject to change without notice.

AD 14 b

You might also like