Mechanical

HOLE COVER REMOVAL/INSTALLATION


4.00 101.6

Wiring Rules
Do not remotely ground any part of the input sensor wiring.

Field Bus Connection


DISCONNECT SWITCH MAY BE

CAUTION

115VAC

Remote grounds connected to the return terminal could make the system operate incorrectly or damage the equipment.
RS485

MORE THAN Operation is subject to the following two conditions: ONE

,32VA,50/60HZ

.18 THRU 4.6 FOR #8 SCREW

The signal return is not true earth ground. It is an electronic reference point necessary to interpret the sensor properly.
2X 1.50 38.1 TO COVER

(1) This device may not cause harmful interference. (2) This device must accept any interference received, including interference that may cause undesired operation.

This equipment complies with part 15 of the FCC rules.

.91 23.0 TO COVER

3.46 87.9

6.92 175.8

For reliable input operation, follow these input wiring guidelines: Never lay wires across the surface of a printed circuit board. Wires should never be within 1 in. or 25 mm of any component on a printed circuit board. Use shielded input wire. Terminate the shield of the input wires at one end of the run onlypreferably at the end where your module is located. Be careful when stripping wire not to drop small pieces of wire onto the circuit board. Dont run your input wiring in the same conduit with AC power or the same conduit with your output wiring. Grounding the Controller This controller includes a screw terminal connection for earth ground. It is important that this connection be made as close to the module as possible.
RS485

WHITE
RS-485

BLACK SHIELD

SHLD RET IN1 IN2 RET IN3 IN4 SPWR 24VAC OUT1 OUT2 RET 24VAC OUT3 OUT4 RET UNIVERSAL INPUTS

TO REMOVE: Gently lift inside tab and pull hole cover outward. TO INSTALL: Align hole cover with slot. Push hole cover inward until tab snaps into place. FOR PROPER VENTILATION, MOUNTED ORIENTATION MUST REMAIN VERTICAL AS SHOWN:
5.85 148.6 8.11 206.0

SMART SENSOR 24VAC ,750mA TOTAL MAX. LOAD


TRIAC OUTPUTS 24VAC ,0.3A

2.75 70.0

887-L-115-C 8

OUT5 RELAY OUTPUT 277VAC , 3A

USE COPPER CONDUCTORS ONLY

!
CAUTION

Caution: Earth ground ( ) must be connected to avoid module damage.

b3

887-L-C Installation
30-3001-888 Rev E

AC Power Connection
GREEN COLORED HEX NUT EARTH GROUND

Smart Sensor Bus Interface (IN4 & SPWR)


DISCONNECT SWITCH MAY BE

CAUTION

115VAC
N

MORE THAN Operation is subject to the following two conditions: ONE

,32VA,50/60HZ

EARTH GROUND

(IN3) (SPWR)

(RET)

INF +

(1) This device may not cause harmful interference. (2) This device must accept any interference received, including interference that may cause undesired operation.

This equipment complies with part 15 of the FCC rules.

AC SUPPLY

RS-485
SHLD

RS-485 + RS-485 -

(L) (N)

AC POWER SPECIFICATIONS
MODEL
i2/b3 887-L-115-C i2/b3 887-L-230-C

RET IN1 IN2 RET IN3 IN4 SPWR 24VAC OUT1 OUT2 RET 24VAC OUT3 OUT4 RET

UNIVERSAL INPUTS

POWER
115VAC, 32VA, 50/60Hz 230VAC, 32VA, 50/60Hz

RET IN4

SMART SENSOR 24VAC ,750mA TOTAL MAX. LOAD

SPWR

CAUTION

SMART SENSOR

TRIAC OUTPUTS 24VAC ,0.3A

Use care when attaching power wiring to these connectors. They are not to be used as a strain relief. The connectors cannot withstand excessive bending or flexing.

887-L-115-C 8

OUT5 RELAY OUTPUT 277VAC , 3A

USE COPPER CONDUCTORS ONLY

Inputs
Contact and Thermistor Sensing DC Voltage Sensing Digital Logic Signal Sensing

IN x
+

IN x DC Voltage RET

Digital logic Signal

IN x

IN y
V

Contact Closure

Thermistor RET

GND

Max DC Input Voltage = 5.12V Input Impedance = 10KW referenced to 5.12 VDC

Outputs
Digital Triac Output
Internally Powered
Output Rating*: 24 VAC, 300mA (Cannot switch DC loads) Minimum Load: 30mA * The total allowable current sourced by the internal power source for all external loads is 750mA.
24VAC
FORM A

Tristate from 2 Triac Outputs


LOAD OUT x
+ ON

Digital Form A Relay Output

LOAD

OUT x

GND
GND

Common
24VAC INTERNAL 24VAC

Note: One side of Triac is internally grounded


GND

OUT 5

Note: One side of Triac is internally grounded

Externally Powered
Output Rating: 24 VAC, 300mA (Cannot switch DC loads) Minimum Load: 30mA

OUT y LOAD
ON

Output Rating:
Adjacent output pairs:

277 VAC @ 3 A 30 VDC @ 3A

24 VAC Step-Down Transformer

OUT1 and OUT2 OUT3 and OUT4

DETAILED PROGRAMMING & TECHNICAL INFORMATION Refer to the following documents: i2 Controller Technical Reference, 30-3001-861 b3 and b4920 Controller Technical Reference, 30-3001-862
2011 Schneider Electric All Rights Reserved. Schneider Electric - One High Street - North Andover MA USA 01845

X1

FORM A

AC Line Power

Black

LOAD

OUT x

can be combined to form a standard Tri-state output. The outputs are electrically connected as shown in the schematic for the built-in Tri-state output. Configure the output point of the first point of a pair (OUT1 of the pair OUT1 and OUT2) with an Electrical Type of Tri-state.

GND

X2

White or Green

Note: One side of Triac is internally grounded