Panel de Incendio D7024

Ver. 2.02 y superiores

Instalacion
| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

3
Department

Panel de Incendio D7024

Propiedades Sistema
Teclado LCD incorporado Hasta 4 teclados adicionales Hasta 8 anunciadores remotos adicionales Comunicador Doble Linea Incorporado 4 Puntos On-Board (Expandible a 8) 247 Direcciones Off-Board (para entradas y/o salidas) 16 Codigos Usuario (Expandible a 100) Numeros PIN 4 Digitos Niveles Autoridad Programables Buffer de Memoria 99 Eventos (Expandible a 499) Programacion Libre Display Alfanumerico Programacion Dirigida a traves de Menus Programable con RAM IV Aprobaciones UL, CSFM, MEA
4

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

Panel de Incendio D7024

Especificaciones
Corriente Entrada Corriente: 120 V, 60 Hz, 1.5 A Corriente Notification Appliance Circuit (NAC): Cada NAC tiene 24 VDC nominal, corriente no filtrada con hasta 2.5 A capacidad (4.0 A max.) Corriente Auxiliar: 24 VDC nominal, no filtrada, 1.0 A Corriente Circuito Iniciacion (Humo): 24 VDC nominal, filtrada, 1.0 A. Corriente Bus Option: 12 VDC nominal, 500 mA Baterias Opcionales Standby: Dos 12 V (en serie), 7 40 Ah

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

Panel de Incendio D7024

Cont. Especificaciones
Notification Appliance Circuits (NACs) Dos circuitos notificacion on-board - NAC 1 y NAC 2. Cableado para estandares Class B, Estilo de operation Y (use modelo de convertidor NACD7015 Clase B a Clase A para convertir a Clase A, Estilo Z como se necesita).

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

7
Department

Panel de Incendio D7024

Modulos
D7014 Convertidor Zona Clase A
D7015 Convertidor NAC D7030 Anunciador Remoto LED D7031 Keyswitch Remoto D7033 Teclado LCD D7034 Expansor 4 Puntos D7035 Modulo Relevo Remoto

D7036 Teclado Anunciador Fuego


D7038 Fuente Poder Remota NAC D7039 Modulo Expansion Multiplex D7042 Modulo 8 Entradas
| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

Panel de Incendio D7024

ModulosConvertidor Zona Clase A D7014


Convertidor Zona Clase A Convierte un Clase B a Clase A

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

Panel de Incendio D7024

Modulos Convertidor NAC D7015


Convierte Circuito NAC Clase B a circuito Clase A. Compatible con circuitos NAC 24V

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

10

Panel de Incendio D7024

Modulos Anunciador Remoto D7030


8 LEDs Personalizables

Indica Sitios Alarma


LEDs Corriente y Fallo Cables cuatro hilos

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

11

Panel de Incendio D7024

Modulos Teclado LCD D7033


Display Alfa/Numerico

2 Lineas, 32 Caracteres
Sistema Control Remoto 4 LEDs de Estado Proteccion con clave

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

12

Panel de Incendio D7024

Modulos Expansor Puntos D7034


Expansor 4 Puntos

Usa dispositivos N/O o N/C


Detectores 2 o 4 hilos 20 circuitos 2 hilos

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

13

Panel de Incendio D7024

Modulos Modulo Relevo Remoto D7035


8 Salidas Forma C

Cada Relevo Programable


Hasta 2 Modulos/7024

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

14

Panel de Incendio D7024

Modulos Teclado Anunciador Fuego D7036


Teclado/Anunc LCD.

2 Lineas/16 Carac./linea
Buzzer incorporado Resetea Panel desp. Alarma

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

15

Panel de Incendio D7024

Modulos Expansor Multiplex D7039


Modulo Expansor Puntos

2 Buses Mux Clase B


o 1 Bus Mux Clase A Expande a 100 PINs Expande Memoria a 499

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

16

Panel de Incendio D7024

Dispositivos Puntos Off-Board


D7042 Modulo 8 Entradas D7044(M)-Entrada Sencilla Direccionable /M = mini D7050(TH)- Cabeza Humo Direccionable Photo-elect. D7050B Base 2 hilos 6 TH = 135f sensor seguro calor

D7045- Estacion Manual Direccionable


D7052- Entrada Doble Direccionable/Total 60 D7053- Entrada/Salida Direccionable [5a @ 28vdc] (Total 40 (20 en cada lazo aislado clase b SLC)

(Relevo usa funciones programable sistema)


D243P- Cabeza Detectora Direccionable para Ductos con/D7050DH Total 70 D344-RT Plato Remoto Pruebas Total 40 D344-RL Anunciador Remoto LED Total 50
Primeros 10 puntos perdidos anuncian individualmente si hay mas de 10 Common Bus Failure

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

17

Panel de Incendio D7024

Modulos Modulo 8 Entradas D7042


8 Entradas Remotas Modulo Mux 8 Circuitos Iniciacion Clase B
Tamper Bypass Tamper Address Sw.

Hasta 76 mt en Circuitos Iniciacion


Direccionable Dip Switch Tamper w/bypass para pruebas

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

18

Panel de Incendio D7024

Modules Fuente Poder Remota D7038


6 Amps de Corriente 4 Lazos Clase B Salida Regulada 24VDC Total/ Protegida/Supervisada

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

19

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

20
Department

Panel de Incendio D7024 / Communicator D7024 Fire Alarm Control

Instalacion y Puesta en Marcha


En la caja de envio, usted encontrara:

Un Control/Comunicador D7024 en paquete resistente estatica Una Caja con transformador Un paquete hardware Una cerradura, anillo sujeccion, y llaves Seis Resistencias Fin-de-Linea (EOL)

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

21

Panel de Incendio D7024 / Communicator D7024 Fire Alarm Control

Instalando la caja
Usando la base como plantilla, marque los hoyos de montaje Pre-fije los tornillos montaje para estos dos hoyos. Deslice la caja sobre estos tornillos Aprete los tornillos. Fije con dos tornillos los hoyos inferiores. Quite las entradas deseadas de cable

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

22

Panel de Incendio D7024 / Communicator D7024 Fire Alarm Control

Instalando el Control/Communicator
Inserte los 3 postes soporte en los hoyos retenedores Presione los soportes de nylon 1/8" dentro de los hoyos retenedores Deslice la parte superior de la caja en los tabs.

Asegure las dos esquinas inferiores a traves de los hoyos retenedores


Conecte el cable de tierra inserto Conecte la tierra de AC.

Asegurese de tocar tierra antes de manipular la tarjeta controladora


| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

23

Panel de Incendio D7024

Cableado
120VAC xfmr

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

24

Panel de Incendio D7024


Terminales 1 2 3 4 5 6 Funcion NAC 1 + +24V en alarma; tierra mientras en standby NAC 1 Tierra en alarma; voltaje supervisado en standby

NAC 2 + +24V en alarma; tierra mientras en standby NAC 2 Bateria Tierra en alarma; voltaje supervisado en standby

Requires 2 12 V batteries in series; combined Bateria + voltage 24 V; Charge Current 1.1 A max.

Todo el cableado exceptuando puntas bateria y entrada AC esta limitada por corriente. Separar estos de otros cables por lo menos 1/4, y asegurelos

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

25

Panel de Incendio D7024 D7024 Installation

Terminales 7

Funcion 12 V + Bus A Option

8
9 10 11 12 13 14

Com
Data Data

Bus A Option
Bus A Option Bus A Option [amarillo]

12 V + Bus B Option Com Data Data Bus B Option Bus B Option Bus B Option [amarillo]

*Puede usar solamente un bus option al tiempo


| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

26

Panel de Incendio D7024 D7024 Installation

Terminales 21

Funcion Earth Ground

20
19 18 17 16 15

Loop 4 Loop + Loop 3 Loop 2 Loop + Loop 1 All EOL resistors 2.21k-ohm Initiating Devices Class B, Style B 2-wire Compatibility Identifier A

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

27

Panel de Incendio D7024 D7024 Installation

Terminales 25

Funcion SMK + Corriente Humos 24 V, 1.0A max. [filtrada]

24
23 22

SMK - Switchada
AUX +

Supervisada

Corriente Auxiliar 24 V, 1.0A [sin filtrar] No Supervisada

AUX - No switchada

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

28

Panel de Incendio D7024 D7024 Installation

Terminales 31
Relay 2

Funcion NC 2

30
29

COM 2
NO 2 For connection to listed power limited Class 2 or Class 3 sources only. Contacts rated at 5.0A, 28 V.

28
Relay 1

NC 1 COM 1 NO 1

27 26

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

29

Panel de Incendio D7024 D7024 Installation

Terminales
Phone 2

Funcion R2

39

38
37 36

HR 2
HT 2 T2


30

Phone 1

35 34 33 32

R1 HR 1 HT 1 T1

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

Panel de Incendio D7024

Expansion

D7034 Expansor 4 Zonas Puntos On-Board

D7039 Expansor Multiplex 240 Puntos Off-Board Modulo I/O

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

31

Panel de Incendio D7024 / Communicator D7024 Fire Alarm Control

Instalacion Equipo Opcional


Hay tres opciones de expansion que pueden conectarse directamente al panel

Expansor D7034 Cuatro Entradas

Expansor Multiplex D7039

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

32

Panel de Incendio D7024 / Communicator D7024 Fire Alarm Control

Instalacion Equipo Opcional cont.


Cuando el panel es re-energizado, el panel mostrara lo siguiente:
y/o

y/o

Presione la tecla [Clear] para confirmar la instalacion de los dispositivos

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

33

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

34
Department

D7024 Programming Panel de Incendio D7024

Programacion
Teclas de Programacion Alfanumerica
1 4 7 2 5 8 0 3 6 9
# # Cmnd

Drill

Silence
Disable

Teclas Numero usadas para entrar valores alfanumericos

Test

Reset
Clear

Prog

History

Tecla Silence un espacio derecho Tecla Disable un espacio izquierda tecla #/Cmnd acepta datos cuando esta en modo programacion Tecla */Clear usada para: Salir programacion alpha Exit entra modo program

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

35

Panel de Incendio D7024

Programacion

RAMIV - Adiciona la habilidad para programar remotamente, diagnosticar remotamente, recuperar historico remotamente Programacion En sitio puede ser hecha usando un PC con RAMIV y un modem externo. Modem conexion Directa para deteccion tip/ring de lineas telefonicas entrantes en linea uno. Use RAMIV para conectar. Presione el boton Test en teclado D7024, presione 5 para Respuesta Remota, coloque nivel PIN maxima autoridad.
| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

36

D7024 Programming Panel de Incendio D7024

Programacion
Presione la 1 Programacion Alpha Desde Teclado tecla

Una
Dos Tres veces Cuatro veces

=
= = =

SPACE
1 ,

Cinco veces
Seis veces Siete veces Ocho veces

=
= = =

&
/ # !

Nueve veces

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

37

D7024 Programming Panel de Incendio D7024

Programacion
Programacion Alpha Desde Teclado
1ra vez 2da vez B E H K N R 3ra vez C F I L O S 4ta vez 2 3 4 5 6 7

2
3 4 5 6 7

A D G J M P

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

38

D7024 Programming Panel de Incendio D7024

Programacion
Programacion Alpha Desde Teclado 1ra vez 8 9 0 T W Q 2da vez U X Z 3ra vez V Y 0 4ta vez 8 9

Prog

#
Cmd

Entra descripcion & returna a menu programacion. Returna a menu programacion sin hacer cambios.

Clear Disable

Mueve cursor un espacio izquierda.


Mueve cursor un espacio derecha

Silence

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

39

Panel de Incendio D7024 Menu Tree D7024 Program

Programacion
Nivel 1 es Menu Principal. Seleccione Programar con Tecla.
Prog

Nivel 2
1- PROG TIME 2- SECURITY 3- PROG SYSTEM 4- PROG INPUTS 5- PROG OUTPUTS 6- PROG ACCNTS

7- PROG FORMATS
8- HISTORY DEFLTS 9- PROGRAM MUX
| ZVW2, 22.12.00 en teclado, excluyendo Nivel 2 item Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

Arbol Programacion RAMIV, tiene igual info al display navegacion 8.

40

Panel de Incendio D7024 / Communicator D7024 Fire Alarm Control

Arbol Menu Programacion

Program/ Hora
| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

41

Panel de Incendio D7024 / Communicator D7024 Fire Alarm Control

Arbol Menu Programacion

Seguridad
| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

42

Panel de Incendio D7024 / Communicator D7024 Fire Alarm Control

Arbol Menu Programacion

Program/ Sistema
| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

43

Panel de Incendio D7024 / Communicator D7024 Fire Alarm Control

Arbol Menu Programacion

Program/ Entradas
| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

44

Panel de Incendio D7024 / Communicator D7024 Fire Alarm Control

Arbol Menu Programacion

Programar Salidas
| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

45

Panel de Incendio D7024 / Communicator D7024 Fire Alarm Control

Arbol Menu Programacion

Programar Cuentas
| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

46

Panel de Incendio D7024 / Communicator D7024 Fire Alarm Control

Arbol Menu Programacion

Formatos Program/
| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

47

Panel de Incendio D7024 / Communicator D7024 Fire Alarm Control

Arbol Menu Programacion

Historicos/Deflts
| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

48

Panel de Incendio D7024 / Communicator D7024 Fire Alarm Control

Arbol Menu Programacion

Program Mux
| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

49

Panel de Incendio D7024 D7024 Programming

Programacion RAM IV
D7024s equipados con versiones software inferiores a 2.02 no pueden ser programados remotamente.

RAM IV Software Programacion Remota, Ver. 3.1.18 y superior, es el programador remoto para el D7024 [Ver. 2.02 y superior].

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

50

Panel de Incendio D7024 D7024 Programming

Programacion RAM IV
Programming Shortcuts Programacion Remota Sistema permanece Operacional Systema muestra SYSTEM TROUBLE RMT PRG ACTIVE

Sirenas no activan

Otras salidas programadas en Zona 62 se activaran Problemas no se anuncian hasta sesion de programacion finalice, pero apareceran en diagnosticos programador Nuevas Alarmas terminan sesiones programacion & reportan normalmente

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

51

Panel de Incendio D7024 D7024 Programming

D7024 Guia Rapida Programacion


Para preparar el panel y poder programar con RAM IV usted debe habilitar la opcion programacion remota: Presione 0 en el teclado Pulse 9876 # Seleccione opcion 3 Programar Sistema Pulse 7 para Programacion Remota Para Habilitar Presione 1 Presione la tecla * dos veces Presione 6 para Programar Cuentas Seleccione 4 para Conteo Rings

Colocar Auto Respuesta Conteo Rings 3 o 5

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

52

Panel de Incendio D7024 D7024 Programming

D7024 Guia Rapida Programacion cont.


Para responder la llamada entrante desde RAM IV Presione la tecla Test despues 5 Preguntara para entrar un codigo. Teclee 9876 Pantalla mostrara Remote Program Active

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

53

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

54
Department

Panel de Incendio D7024 / Communicator D7024 Fire Alarm Control

Modos de Operacion
Existen tres modos de operar el sistema en el Control/Comunicador D7024 : ALARM TROUBLE NORMAL

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

55

Panel de Incendio D7024 / Communicator D7024 Fire Alarm Control

Modos de Operacion - Alarma


ALARMA Cuando una alarma ocurre, la linea superior de la pantalla mostrara FIRE ALARM, o un mensaje similar.

La segunda linea de la pantalla mostrara el numero de el punto que esta en alarma, alternando con la descripcion programada en el punto afectado.
Si mas de una alarma esta activa, se mostrara en la segunda linea de la pantalla, una despues de otra. La sirena interna se activara con tono continuo, y las salidas programadas se activaran con la condicion de alarma actual que se active.
| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

56

Panel de Incendio D7024 / Communicator D7024 Fire Alarm Control

Modos de Operacion - Trouble


TROUBLE Cuando una condicion de trouble sucede, la sirena se activara con un beep cada 10 segundos.

El LED de Trouble iluminara y el LCD mostrara SYSTEM TROUBLE, seguido por una descripcion de la condicion de trouble.

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

57

Panel de Incendio D7024 / Communicator D7024 Fire Alarm Control

Modos de Operacion Seales Trouble


TROUBLE 1. FIRE ALARM: Uno o mas puntos estan en alarma. 2. SUP'VISORY ALARM: Una condicion supervisada existe 3. SYSTEM TROUBLE: Una condicion trouble existe 4. POINT TROUBLE: Uno de los puntos no responde 5. DISABLED DEVICE: Un dispositivo de entrada o salida fue desabilitado.

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

58

Panel de Incendio D7024 / Communicator D7024 Fire Alarm Control

Modos de Operacion - Normal


NORMAL Cuando el sistema esta operando normalmente, este mostrara SYSTEM NORMAL.

En la linea superior de la pantalla, el LED de corriente estara encendido, y no otros LEDs alumbraran.
Si la programacion requiere un PIN, la segunda linea de la pantalla LCD mostrara ENTER PIN:

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

59

Panel de Incendio D7024 D7024 Fuse re Alarm Control / Communicator

USO DEL SISTEMA NAVEGANDO MENUS

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

60

Panel de Incendio D7024 / Communicator D7024 Fire Alarm Control

USO DEL SISTEMA NAVEGANDO MENUS


Existen diferentes formas para seleccionar un item: 1. En el menu principal, TEST, HISTORY, DISABLE, y DRILL cada uno tiene un boton exclusivo en el teclado. 2. Las teclas PROG y CMND no son exclusivas, pero compartiran con otros caracteres. El caracter compartira la tecla correspondiente mostrada en la segunda linea seguida por un slash.

3. La tecla correspondiente al item sub-menu puede ser mostrada en la segunda linea precedido por un guion.

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

61

Panel de Incendio D7024 / Communicator D7024 Fire Alarm Control

OPERACION SISTEMA :
Una vez el Item Menu Principal Item fue seleccionado Cuando un item del Menu principal es seleccionado, el teclado podra preguntarle para entrar el PIN. Devolviendose a travez del Menu Para returnar a la pantalla previa en cualquier momento, presione la tecla [*/Clear]. Entrar Datos Cuando un item del submenu se muestra para entrar el dato, hacerlo seguido por la tecla [#]. Drill El comando drill activa todos los NACs y no los relays. Desabilitar El comando desabilitar se usa para desabilitar puntos entradas/salidas, o el discador Historia La opcion HISTORIA es una lista de eventos que han occurrido. | ZVW2, 22.12.00
Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

62

Panel de Incendio D7024 / Communicator D7024 Fire Alarm Control

HISTORIA ABREVIATURAS

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

63

Panel de Incendio D7024 / Communicator D7024 Fire Alarm Control

TECLADO INCORPORADO
LED Corriente LED Alarma LED Problema LED Silenciar

Tecla Drill Tecla Desabilitar Tecla Prueba Tecla Limpiar Tecla Programar Tecla Silenciar Tecla Reset Tecla Historia Tecla Comando
64

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

Panel de Incendio D7024 / Communicator D7024 Fire Alarm Control

TECLADO REMOTO

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

65

Panel de Incendio D7024 / Communicator D7024 Fire Alarm Control

PRUEBA
Para entrar en Modo Prueba presione la tecla Test Seleccione una de las siguientes funciones de prueba Test Caminado Test Comunicador Test Programacion Remota Test Circuito Batteria/NAC

Test Activacion Salidas Manuales


Test Nivel Entradas Zona Test Puntos Direccionables Para salir del modo test presione la Tecla Clear
| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

66

Panel de Incendio D7024 / Communicator D7024 Fire Alarm Control

Test Caminado
Cuando seleccione esta opcion, tres opciones seran ofrecidas para la activacion de las salidas. SHORT ACTIVE: 1 segundo activacion LONG ACTIVE: 5 segundos activacion NO ACTIVE: salidas no seran activadas

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

67

Panel de Incendio D7024 / Communicator D7024 Fire Alarm Control

Test Comunicador
El comunicador enviara un reporte de prueba.

El LED de corriente alumbrara durante la comunicacion.


Cuando la comunicacion se produce: un beep largo en el teclado se escuchara, el LED de Corriente retornara a normal, y la pantalla retornara a modo normal. Terminando la funcion de prueba del comunicador se reseteara el comunicador y se descartaran los reportes no enviados.

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

68

Panel de Incendio D7024 / Communicator D7024 Fire Alarm Control

Test Programador Remoto


El panel llamara al numero telefonico 3 e intentara conectarse para el downloading.

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

69

Panel de Incendio D7024 / Communicator D7024 Fire Alarm Control

Test Circuito Bateria/NAC


En este modo de prueba, el sistema operara los circuitos locales NAC y probara la bateria por dos segundos.

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

70

Panel de Incendio D7024 / Communicator D7024 Fire Alarm Control

Test Activacion Salidas Manuales


Permite seleccionar una salida para ser activada y desactivada manualmente.

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

71

Panel de Incendio D7024 / Communicator D7024 Fire Alarm Control

Test Nivel Entradas Zona


Muestra el estado de los puntos on-board seleccionados.

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

72

Panel de Incendio D7024 / Communicator D7024 Fire Alarm Control

Test Puntos Direccionables


El test de puntos direccionables, o modo test mux, permite activacion de los modos especiales de prueba para dispositivos direccionables, multiplex. Cuando este modo de prueba es seleccionado, el sistema pregunta cual bus es probado. El sistema entonces presenta 5 opciones: Lista Dispositivos Muestra Hoyos Muestra Extras Muestra Perdidos Muestra Estado

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

73

Panel de Incendio D7024 / Communicator D7024 Fire Alarm Control

Ejemplo: X0L0R0D0M0T0F0A0
traduccion = relay debe estar off relay is off no sucio no perdido
X: reservado para uso futuro L: estado relay comandado R: estado relevo actual D: detector sucio M: dispositivo perdido T: tamper F: falla loop A: loop de alarma

no tamper
no falla no alarma.

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

74

Panel de Incendio D7024 / Communicator D7024 Fire Alarm Control

MAPEO PUNTO/ZONA
El panel soporta un sist. Flex. para direccionar puntos entrada a puntos salida Dispositivos seran designados como: Puntos Entrada: Detectores Humo, estaciones manuales, etc.

Zona: Un grupo de puntos entrada (Zonas 1-50 son configurables, 52-63 son activadas automaticamente).
Puntos Salida : NACs (campanas, strobes, etc.) y relevos. Activacion zonas entrada Activacion salidas

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

75

Panel de Incendio D7024 / Communicator D7024 Fire Alarm Control

Ejemplo Mapeo

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

76

Panel de Incendio D7024 / Communicator D7024 Fire Alarm Control

Zonas Pre-asignadas

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

77

Panel de Incendio D7024 / Communicator D7024 Fire Alarm Control

NUMEROS PIN
El Numero de Identificacion Personal (PIN) es el codigo 4 digitos que el usuario entra en el teclado para ganar acceso al sistema

D7024 Panel Usuarios 00 a 15


D7039 Modulo Expansion Usuarios 16 a 99

| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

78

Panel de Incendio D7024 / Communicator D7024 Fire Alarm Control

OPERACION COMUNICADOR
D7024 contiene un comunicador integrado que puede ser habilitado para enviar reportes a una estacion de monitoreo. Alarmas de Fuego y flujo aguaseran enviadas primero, seguidas por: alarmas supervision y reportes prueba y finalmente todos los demas reportes.

Lineas telefonicas para controles/comunicadores de fuego no deben ser compartidas


| ZVW2, 22.12.00 Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as copying and passing on to third parties.

79

Panel de Incendio D7024 / Communicator D7024 Fire Alarm Control