You are on page 1of 12

PPMV Product Management

GSec
SF6 load-break switch-disconnector

GSec
Three position switch disconnector

Upper terminal
SF6 line disconnector

SF6 earthing switch

Insulate busbar from cables

Grounds cable side

Lower terminal
Capacitive dividers intergrated

ABB Group
Month DD, Year

| Slide 2

GSec
Compact and safe structure

Upper part in epoxy resin and filled with SF6:

long-term protection against external environment

Sealed for life: 30 years

Lower part in stainless steel

Metallic partition (PM) between busbar and cable compartments

Safety for operators during maintenance activities

Lower bushings with integrated capacitive dividers:

ABB Group
Month DD, Year

| Slide 3

compact design

Direct cable connection

GSec
Actuators
Line actuators:

Single spring mechanism


(1S dead centre)

Double spring mechanism


(2S stored energy)
Earth actuator:

Single spring mechanism


(1S dead centre)

1.
2.
3.
4.
5.
6.
7.

ABB Group
Month DD, Year

| Slide 4

Line operating slot


Earth operating slot
Line diagram with indicators
Pushbuttons (for 2S actuator)
Voltage indicators
Spring charged signal
Fuse blown signal

GSec
Actuators diagrams
1S Single Spring

2S Double Spring

time

Actuation speed is independent from operator


ABB Group
Month DD, Year

| Slide 5

time

GSec
Typical units

ABB Group
Month DD, Year

| Slide 6

GSec/T1

GSec/T2

1S Single spring mechanism

2S Double spring mechanism


(stored energy)

GSec
Typical units

GSec/IB

1S Single spring mechanism

2S Double spring mechanism

For panels with removable


circuit breakers

Fuse tripping system

Fuse base

Fuse blown indicator

Downstream earthing switch


(interlocked)

ABB Group
Month DD, Year

| Slide 7

GSec/T2F

Downstream earthing switch


(interlocked)

GSec
Mechanical interlocks for safety

| Slide 8

(3)

Closed

Open - Isolated

Earth

It is possible to close the earthing switch only if the line switchdisconnector is open

Earthing switch Panel door

ABB Group
Month DD, Year

(2)

Line disconnector - Earthing switch

(1)

It is possible to open the door only if the earthing switch is closed

GSec
Wide range of accessories

ABB Group
Month DD, Year

| Slide 9

GSec
Safety and Compactness

ABB Group
Month DD, Year

| Slide 10

GSec
SF6 three-positions LBS
Three positions load-break
switch disconnector:
SF6 Load break switch

SF6 Disconnector

SF6 Earthing switch


(cable side)

Rated Voltage [kV]

12
(1S / 2S)

17.5
(1S / 2S)

24
(1S / 2S)

Rated Current [A]

630 / 800

630 / 800

630

16(3s) / 25(2s)

16(3s) / 20(3s)

16(3s) / 20(2s)

Short time current [kA]


Mechanical class
Electrical class
ABB Group
Month DD, Year

| Slide 11

Line: M1 / M2 Earth: M0
Line: E3 Earth: E2