Professional Documents
Culture Documents
Power System
Support Components
Measurement & Monitoring System Protection System
Generation
Transmission
Distribution
Load
Main Components
AROUND TOWN & RESIDENTIAL AREA Underground distribution to individual premises is at 400V and 230 V
SMALL INDUSTRY Most small factories receive their electricity at 11kV HEAVY INDUSTRY - Some have direct connections to the transmission at 132kV
POWER STATION- Generator output at
11kV/20kV is stepped up by transformer to 220kV and 500kV for transmission.
Importance of Protection
Reliability
Operate dependably and in healthy operating condition when fault conditions occur, even after remaining idle for months or years. Clearly discriminate between normal and abnormal system condition to avoid unnecessary, false trips. Ability to distinguish the fault condition, although the difference between fault and normal condition is small.
Selectivity
Sensitivity
Design Criteria/Characteristics
Speed
Fault at any point in the system must be detected and isolated rapidly to minimize fault duration and equipment damage. Any intentional time delays should be precise. Provide maximum protection at minimum cost Minimize protection equipment and circuitry
Economy
Simplicity
Protection Zones
Zones of Protection
Zones of Protection
Zones of Protection
Characteristics:
Zones are overlapped.
Primary protection
Primary protection is the first line of defence. The protection provided to protect a specific device or equipment or instrument immediately is called primary protection. It may fail due to the failure of CT, PT, relay or circuit breaker.
Back up protection
Back up protection is second line of defence. Back-up protection is provided which take over only in the event of primary protection failure. The back up protection must wait for the primary protection to operate. So, the operating time of back up protection must be delayed by an appropriate amount over the primary protection.
Fault types
faults faults
Types of faults
Shunt Faults
Fault L-G L-L L-L-G L-L-L Total Probability 85% 8% 5% 2% 100% Severity Least severe severe severe Most severe
Series Faults
Series faults are nothing but a break in the path of current. It is observed in practice that most of the open conductor faults sooner or later develop into some of the other short circuit faults
Faults involving only one of the phase conductors and ground, are called ground faults.
Ground faults:-
Phase faults:
Faults involving two or more phase conductors, with or without ground, are called phase faults.
9 10
7 12
CT, PT, relays, control 12 Faults statistics with reference to equipments, etc
100%
Magnitude & phase angle of current Directional fault protection Magnitude & phase angle of current in earth or neutral Directional Earth Fault Protection V/I ratio Impedance protection Difference between 2 or more currents Differential protection Difference between phase angles of 2 currents phase comparison protection
Apparatus
Principal
Nondirectional Over-current
Directional over-current
Differential
Distance
Alternator
Primary protection Primary protection Primary protection Primary protection Primary protection
Busbar
Transformer
Protection Components
Protection Components
Fault Occur
Transducer
Relay
Circuit Breaker
Fault Clear
Instrument Transformers
Instrument Transformer
Use to reduce abnormal current & voltage levels Transmit input signals to the relays of a protection system.
The lower level input to the relays ensures that the physical hardware used to construct the relays will be small & cheap The personnel who work with the relays will be working in a safe environment.
Potential Transformers
Current Transformers
CT is an instrument transformer that is used to supply a reduced value of current to meters, protective relays, and other instruments.
The primary winding consist of a single turn which is the power conductor itself.
CT secondary is connected to a currentsensing device.
Types of current transformers:There are two types of current transformers: 1. Wound primary type 2. Bar primary type
CT & PT Protection
AS A SAFETY PRECAUTION, NEVER OPENCIRCUIT CURRENT TRANSFORMER ON LOAD! AS A SAFETY PRECAUTION, NEVER SHORTCIRCUIT VOLTAGE TRANSFORMER ON LOAD!
A transformer is a device that changes AC electrical power at one voltage level to ac electrical power at another voltage level through the action of a magnetic field.
It consists of two of more coils of wire wrapped around a common ferromagnetic core. These coils are usually not directly connected.
HV and LV bushing flashovers (external to the tank) HV winding earth fault LV winding earth fault Inter-turn fault Core fault Tank fault
Inter-turn faults
Insulation between turns can break down due to electromagnetic or mechanical forces on the winding causing chafing or cracking. Ingress of moisture into the oil can also be a contributing factor..
Tank faults:
Loss of oil through a leak in the tank can cause a reduction of insulation and possibly overheating on normal load due to the loss of effective cooling.
e.g.,
Failure of the winding insulation Localized heating can also precipitate a breakdown of oil into gas. Severe arcing Oil surge from the tank to the conservator.
Differential protection
Differential protection compares currents entering and leaving the protected zone and operates when the differential current between these currents exceed a pre-determined level.
Also called the current balance or circulating current scheme.
Buchholz Protection
The Buchholz relay can detect both gas and oil surges as it is mounted in the pipe to the conservator.
The unit contains two mercury switches.
Description
This is widely used for transformers between 30MVA to 60MVA
Oil Natural Air Neutral This is widely used for transformers up to 30MVA
O.F.A.F
O.F.W.F
A.N
Air Natural
Faults
Phase faults Ground faults
Buchholz relay Buchholz relay OC relay with thermal image of protected unit Over-fluxing relay with measures (V/f) ratio
Relay Function
Relay Type
51GP, 51GS, 51N
Protection Type
Back-Up Protection
Function
Ground Over Current Detection
Over Current Detection Ground Over Voltage Detection Differential Current Detection Internal Fault Detection
51P, 51S, 50/51T Back-Up Protection 64 87T 87N Back-Up Protection Primary Protection Primary Protection
Name 2008-EE-
Relays
A device that detects the fault and initiates the operation of the circuit breaker to isolate the defective element from the system. Relay types
Magnitude or Over-current Relay Directional Relay Distance or Ratio or Impedance Relay Differential Relay
Magnitude Relays
If it is less than the set point value, the relay remains open, blocking the trip coil.
Directional Relays
Responds to fault only in one direction. Operation depends upon the direction (lead or lag) of the fault current with respect to a reference voltage. The directional element of these relays checks the phase angle between the current and voltage of one phase, and allows the over-current unit to operate if this phase angle indicates current in the reverse direction.
Ratio Relays
Also called impedance or distance relay Operate for certain relations between the magnitudes of voltage, current and the phase angle between them. Measures the distance between the relay location and the point of fault, in term of impedance, reactance and admittance. Respond to the ratio of two phasor quantities.
Differential Relays
Respond to the vector difference between two current. Not suitable for transmission-line protection. Used for the protection of generators, transformers and busbars.
i.
ii.
iii.
The primary winding of a current transformer which is connected in series with the line to be processed. Secondary winding of C.T and the relay operating coil. The tripping circuit which consist of a source of supply, the trip coil of the circuit breaker and the relay stationary contacts.
C.B
C.T
Relay coil
Bus-Bar
Electrical
In electrical power distribution busbars refers to thick strips of copper or aluminium that conduct electricity within a switchboard.
An electrically conductive bar connecting two or more electrical circuits.
Circuit Breakers
A circuit breaker is an equipment that breaks a circuit either manually or automatically under all conditions at no load, full load or short circuit.
TYPES OF CIRCUIT BREAKER
Sulphur Hexafluoride (SF6) gas is used as an arc quenching medium. SF6 is an electro-negative gas. It has strong tendency to absorb electrons.
Advantages
Simple construction. Less cost. Non flammable, non toxic & chemical inert gas. Maintenance free C.B. Ability to interrupt low and high fault current. Excellent Arc extinction.
ISOLATORS
Mechanical switch use to isolate the transmission line or other equipment from the source of energy.
Operates at no load.
INSULATORS
Insulator provides necessary insulation between the line conductors and supports and stop any kind of leakage current towards the earth from conductor. PROPERTIES Rigidity High resistance Greater dielectric strength. Non porous. WHAT IS INSULATOR ?
Name 2008-EE-
transmission line is the material,medium or structure that forms path from one place to another for directing the transmission of energy.
Phase comparison Step Distance Inverse time over current Current Differential
Fault Calculation
Fault Current is approximately 10 to 20 times normal full load current. To understand the relay performance, we must know how severe is the fault. The voltage at relaying point and current passing through relay, tells the nature of fault.
Introduction
The most obvious effect of shunt fault is a sudden build up of current therefore the over current protection is the most widely used form of protection
AC Bus
Protected Line
AC Elementary Diagram
a b c Phase sequence a-b-c CT c 52 b a 51-C 51-B 51-A 51-N AC Bus
Over current relays 51-A, 51-B, and 51-C should send trip signal to breaker 52
Protected Line
Drawbacks of OCRs
The operating time of over current relay depends upon, The type of fault Source impedence
Distance protection
The reach of over-current relay depends on the type of fault as well as on the source impedance thus the relay may under reach or over reach depending upon the type of fault . We must therefore look for relay whose reach does not depend on the actual magnitude of the fault current, Search for such relaying principle has led to distance relay whose reach depend on the ratio of voltage at relay location and the fault current
INTRODUCTION
Reactance relay
Mho relay
Current
Directional element
Restraining quantity
Directional property Effect of fault resistance Area occupied on R-X plane Effect of power swing
Voltage
Directional element
NO
Voltage
NO
Yes
Under reach
Moderate
Maloperates
Maloperates
Maloperates <SIR
First step
It is not advisable to set the reach of the distance protection to 100% So set to reach up to 80 to 90% of the length of line section
Z1 Remot e
Third step
The 3rd step is provided with an intention to give full back up to the adjoining line section. It covers the line section under consideration 100% of the next line section and reaches further into the system.
Purpose
Reach
Operating time
1St step
80-90% of line section 100% of line under consideration + 50% of the shortest adjoining line
Instantaneous
2nd step
3rd step
Backup protection
100% of line under consideration +100% longest adjoining line +10-20% extra
110