Electrical Saf ety Standards f or LV/MV/HV (on photo Indonesia's state energy giant - High Voltage Switchyard)
Content
1. St andard: West ern Power Company Water Safely Clearance on Electrical Fires Minimum Approach Distance for Authorized Person Minimum Approach Distance for Ordinary Person
Minimum Approach Distance for Vehicle and Plant for Ordinary Person . 2. St andard: New Zealand Elect rical Code Min. Safe Distance between Buildings and Overhead Line Min. Safe Distance for excavation near Overhead Line Min. Safe Distance for Tower Carin near Electrical Tower Min. Safe Vertical Distance above Railway Track Min. Distance between two Conductors on Same Supports Min. Distance between two Conductors on Different Supports Min. Safety Distance from Electrical Apparatuses Min. Approach Distance for Non-Competent Person near exposed Live Parts Min. Approach Distance for Competent Person near exposed Live Parts . 3. St andard: ETSA Ut ilit ies Vertical Clearances between Services Horizontal Clearances between Services . 4. St andard: UK Power Net works EI 02-0019 Cable Installation Depths Minimum Approach Distance of Crane or Moving Part from Live Conductor Minimum Fixed Clearances for Electrical Apparatus (Isolation Points)
4.0 Meter
5.0 Meter
Go to Content
3.0 Meter 3.0 Meter 3.0 Meter 3.0 Meter 4.5 Meter 6.0 Meter
Minimum Approach Distance for Vehicle and Plant for Ordinary Person
Volt age Dist ance (min) Mobile Plant Up to 1 KV 1 V to 6.6 KV 6.6 KV to 11 KV 11 KV to 22 KV 22 KV to 33 KV 33 KV to 66 KV 66 KV to 132 KV 132 KV to 220 KV 220 KV to 330 KV 3.0 Meter 3.0 Meter 3.0 Meter 3.0 Meter 3.0 Meter 3.0 Meter 3.0 Meter 3.0 Meter 6.0 Meter Vehicle 0.6 Meter 0.9 Meter 0.9 Meter 0.9 Meter 0.9 Meter 2.1 Meter 2.1 Meter 2.9 Meter 3.4 Meter
Go to Content
Excavation in land more than 750mm depth Excavation in land up to750mm depth
8 Meter 2.2 to 5 Meter 2.2 Meter 2.2 Meter 6 Meter 8 Meter 2.2 Meter 5 Meter
Excavation in land up to 300mm depth Construction near 11KV to 33KV Line Construction near 33KV to 66KV Line Construction near 66KV and more Wire Fence near 1KV to 66KV Line Wire Fence near 66KV and more Go to Content
Circuit
Up to 33 KV Up to 33 KV
33 KV to 110 KV 33 KV to 110 KV
2.5 Meter
0.6 Meter 1.2 Meter 1.8 Meter 2.4 Meter 2.8 Meter
1.0 Meter wide 2.5 Height 1.0 Meter wide 2.2 Height 0.8 Meter wide 2.2 Height
Passage at any side of Metal-Clad Switch gear containing Bare conductor (UP to HV) Go to Content
Min. Approach Distance for Non-Competent Person near exposed Live Parts
Volt age Below 110 kV 220 kV and above Go to Content Dist ance (min) 4.0 Meter 6.0 Meter
Min. Approach Distance for Competent Person near exposed Live Parts
Volt age Below 1 kV 11 kV 22 kV 33 kV 66 kV 110 kV Dist ance (min) 0.5 Meter 1.5 Meter 2.0 Meter 2.5 Meter 3.0 Meter 4.0 Meter
6.0 Meter
Low Voltage
Footways, grass verges or private property Carriageways (including road crossings) Normal agricultural land (not deep ploughing) Agricultural land subject to deep ploughing
0.450 Meter
1.2 Meter
11 KV to 20 KV
Footways, grass verges or private property Carriageways (including road crossings) Normal agricultural land (not deep ploughing) Agricultural land subject to deep ploughing
0.600 Meter
1.2 Meter
33 KV to 132 KV
Footways, grass verges or private property Carriageways (including road crossings) Normal agricultural land (not deep ploughing) Agricultural land subject to deep ploughing
0.9 Meter
1.2 Meter
Footways, grass verges or private property Carriageways (including road crossings) Normal agricultural land (not deep ploughing) Agricultural land subject to deep ploughing
0.450 Meter
1.2 Meter
The clearance from a supporting wall The vertical clearance between cables is greater If the number of cables > 4, they are to be installed in a horizontal Go to Content