Compact & Powerful Inverter

STARVERT iG5A

0.4~1.5kW 1phase 200~230Volts 0.4~22kW 3Phase 200~230Volts 0.4~22kW 3Phase 380~480Volts

Inverter

STARVERT iG5A
LS Starvert iG5A is very competitive in its price and shows an upgraded functional strength. User-friendly interface, extended inverter ranges up to 22kW, superb torque competence and small size of iG5A provides an optimum use environment.

Standard compliance Compactness

iG5A
High performance Userfriendliness & Easy maintenance

Compact & Powerful Inverter iG5A

Contents

4 8 9 11 13 15 16 18 20 23 25 42 43

Overview Model & Type Standard Specifications Wiring Terminal Configurations Keypad Features Parameter Setting Trial Run Dimensions Braking Resistors and Peripheral Devices Function List Protective Functions Fault Remedy

iG5A

Powerful & Upgraded Performance


iG5A provides sensorless vector control, PID control, and ground-fault protection through powerful built-in functions.

Sensorless vector control


The built-in sensorless vector control provides the superb speed control and powerful high torque.
Torque (%)

Speed vs Torque Characteristics

The ground-fault protection of output terminal is possible during running.

Mode: Auto tuning Measure Condition: Sensorless Vector Control(1/5/10/20/30/40/50/60Hz) maximum torque (%) at each speed

Analog control from -10V to 10V


Inputting analog signals from -10V to 10V provides user-friendly operation.
+10 -10
Forward Reverse

Built-in PID control


The built-in PID function enables to control flow-rate, oil-pressure, temperature, etc without any extra controller.

PID control PID control PID control PID control

PI control PI control PI control PI control

Built-in dynamic braking circuit


The built-in dynamic braking circuit minimizes deceleration time via braking resistors.

Speed

With braking resistor Normal state

Built-in 485 communication The built-in RS-485 communication supports remote control and monitoring between iG5A and other equipment. Wide product range
iG5A consists of the product range from 0.4 to 22KW. 4

Reducing deceleration time

Time

Speed (Hz)

Ground-fault protection during running

Compact & Powerful Inverter iG5A

RS-485 communication
Connected to PC

RS-485 - 232C converter

Monitoring Checking operation status (Voltage, Current, Frequency, etc) Checking modified parameters Windows support Remote Control Convenient remote control to modify operation status (Forward/Reverse operation, Frequency, etc) Easy parameter setting Available to control up to 31 Inverters RS-485, Modbus communication Connected to XGT panel

Monitoring Checking operation time Automatic list-up of trip record Language support (Korean, English, Chinese) Remote Control Convenient remote control to modify operation status (Forward/Reverse operation, Frequency, etc) Easy parameter setting Available to control up to 31 Inverters RS-485, Modbus communication

iG5A

User-friendly Interface & Easy Maintenance


The parameter setting becomes easier by adopting the 4 directions key. And iG5A supports easy maintenance via diagnosis and fan changeable structure.
Diagnosis of output module Through easy parameter setting, iG5A can diagnose the status of output module. Easy change of fan iG5A is designed to be the fan changeable structure in preparation for a fan breakdown.

Cooling fan control By controlling the cooling fan, iG5A provides a virtually quiet environment according to the status of operation. User-friendly interface The 4 directions key provides easy handling and monitoring. External loader (Optional) The external loader away from a panel enables to control and monitor conveniently. And the parameters made by external loader can be copied and applicable to other Inverters.
Loader type + External type (Optional)

Model name INV, REMOTE KPD 2M (SV-iG5A) INV, REMOTE KPD 3M (SV-iG5A) INV, REMOTE KPD 5M (SV-iG5A)

Remarks 2m 3m 5m

Compact & Powerful Inverter iG5A

Compact Size
The compact size achieves cost-efficiency and various applications.

Same height from 0.4 to 4.0kW (128mm)

Global standard compliance CE UL


Global standard iG5A series complies with CE and UL standards. PNP/NPN input Both PNP and NPN inputs become possible and these enable to use the outer power. To do so, users will be given wider choices of selecting the controller.

iG5A

Model & Type


1 Phase 200V
SV004iG5A-1 SV008iG5A-1 SV015iG5A-1

Applicable motor ranges


0.4kW (0.5HP) 0.75kW (1HP) 1.5kW (2HP) 2.2kW (3HP) 3.7kW (5HP) 4.0kW (5.4HP) 5.5kW (7.5HP) 7.5kW (10HP) 11.0kW (15HP) 15.0kW (20HP) 18.5kW (25HP) 22.0kW (30HP)

3 Phase 200V
SV004iG5A-2 SV008iG5A-2 SV015iG5A-2 SV022iG5A-2 SV037iG5A-2 SV040iG5A-2 SV055iG5A-2 SV075iG5A-2 SV110iG5A-2 SV150iG5A-2 SV185iG5A-2 SV220iG5A-2

3 Phase 400V
SV004iG5A-4 SV008iG5A-4 SV015iG5A-4 SV022iG5A-4 SV037iG5A-4 SV040iG5A-4 SV055iG5A-4 SV075iG5A-4 SV110iG5A-4 SV150iG5A-4 SV185iG5A-4 SV220iG5A-4

SV

015

iG5A

STARVERT Motor rating (kW) (004: 0.4kW~220: 22kW) iG5A series Input voltage (1: 1 phase 200~230[V], 2: 3 phase 200~230[V], 4: 3 phase 380~480[V])

Compact & Powerful Inverter iG5A

Standard Specifications
1 Phase 200V
SV iG5A-1
Max. capacity 1) Output rating Input rating Weight (kg) (HP) (kW) Capacity (kVA) 2) FLA (A) 3) Max frequency Max voltage Rated voltage Rated frequency 0.76

004
0.5 0.4 0.95 2.5

008
1 0.75 1.9 5 400 [Hz] 4) 3 phase 200~230V 5) 1phase 200~230 VAC (+10%, -15%) 50~60 [Hz] (5%) Forced air cooling 1.12

015
2 1.5 3.0 8

Cooling method

1.84

3 Phase 200V
SV iG5A-2
Max. capacity 1) Output rating Input rating Weight (kg) (HP) (kW) Capacity (kVA) FLA (A) 3) Max frequency Max voltage Rated voltage Rated frequency N/C 6) 0.76 0.77 1.12 1.84 1.89 1.89
2)

004
0.5 0.4 0.95 2.5

008
1 0.75 1.9 5

015
2 1.5 3.0 8

022
3 2.2 4.5 12

037
5 3.7 6.1 16

040
5.4 4.0 6.5 17

055
7.5 5.5 9.1 24
4)

075
10 7.5 12.2 32

110
15 11 17.5 46

150
20 15 22.9 60

185
25 18.5 28.2 74

220
30 22 33.5 88

400 [Hz] 3 phase 200~230V 5) 3 phase 200~230 (+10%, -15%) 50~60 [Hz] (5%) Forced air cooling 3.66 3.66 9.0 9.0 13.3 13.3

Cooling method

3 Phase 400V
SV iG5A-4
Max. capacity 1) Output rating Input rating Weight (kg) (HP) (kW) Capacity (kVA) 2) FLA (A) 3) Max frequency Max voltage Rated voltage Rated frequency N/C 6) 0.76 0.77 1.12 1.84 1.89 1.89

004
0.5 0.4 0.95 1.25

008
1 0.75 1.9 2.5

015
2 1.5 3.0 4

022
3 2.2 4.5 6

037
5 3.7 6.1 8

040
5.4 4.0 6.5 9

055
7.5 5.5 9.1

075
10 7.5 12.2 16

110
15 11 18.3 24

150
20 15 22.9 30

185
25 18.5 29.7 39

220
30 22 34.3 45

12 400 [Hz] 4)

3 phase 380~480V 5) 3 phase 380~480 VAC (+10%, -15%) 50~60 [Hz] (5%) Forced air cooling 3.66 3.66 9.0 9.0 13.3 13.3

Cooling method

1) Indicate the maximum applicable motor capacity when using 4 pole LS standard motor. 2) Rated capacity is based on 220V for 200V series and 440V for 400V series. 3) Refer to 15-3 of users manual when carrier frequency setting (39) is above 3kHz. 4) Max. frequency setting range is extended to 300Hz when H40 (Control mode select) is set to 3 (Sensorless vector control). 5) Max. output voltage cannot be higher than the input voltage. It can be programmable below input voltage. 6) Self-Cooling

iG5A

Standard Specifications
Control method Frequency setting resolution Frequency accuracy V/F, Sensorless vector control Digital command: 0.01Hz Analog command: 0.06Hz (Max. freq.: 60Hz) Digital command: 0.01% of Max. output frequency Analog command: 0.1% of Max. output frequency Linear, Squared, User V/F 150% per 1 min. Manual/Auto torque boost Max. braking torque Max. Duty Operation mode Frequency setting Operation features 20% 1) 150% when using optional DB resistor 2) Keypad/ Terminal/ Communication option/ Remote keypad selectable Analog: 0~10V, -10~10V, 0~20mA Digital: Keypad PID, Up-down, 3-wire NPN/PNP selectable Multi-function terminal P1~P8 FWD/REV RUN, Emergency stop, Fault reset, Jog operation, Multi-step Frequency-High, Mid, Low, Multi-step Accel/Decel-High, Mid, Low, DC braking at stop, 2nd motor select, Frequency UP/Down, 3-wire operation, External trip A, B, PID-Inverter (V/F) operation bypass, Option-inverter (V/F) operation bypass, Analog Hold, Accel/Decel stop

Control

V/F pattern Overload capacity Torque boost Dynamic braking

Operation

Input

Open collector terminal Output Multi-function relay Analog output (AM) Trip Protective function Alarm Momentary power loss Protection degree Ambient temp Environ ment Storage temp Humidity Altitude/Vibration Atmospheric pressure Location

Fault output and inverter status output

Less than DC 24V, 50mA (N.O., N.C.) Less than AC 250V, 1A; Less than DC 30V, 1A

0~10Vdc (less than 10mA): Output freq, Output current, Output voltage, DC link selectable Over voltage, Under voltage, Over current, Ground fault current detection, Inverter overheat, Motor overheat, Output phase open, Overload protection, Communication error, Loss of speed command, Hardware fault, Fan trip Stall prevention, Overload Below 15 msec.: Continuous operation (Should be within rated input voltage, rated output power.) Above 15 msec.: Auto restart enable IP 20, NEMA1 (Optional) -10~50 -20~65 Below 90% RH (No condensation) Below 1,000m, 5.9m/sec 2 (0.6G) 70~106 kPa Protected from corrosive gas, Combustible gas, Oil mist or dust

1) Means average braking torque during Decel to stop of a motor. 2) Refer to Chapter 16 of users manual for DB resistor specification.

10

Compact & Powerful Inverter iG5A

Wiring
0.4~7.5kW

DB resistor (Optional)
3 phase AC input (Rated input voltage)

B1 R S T G
Ground

B2 U V W

24 24V output
P1 FX (Forward run) P2 RX (Reverse run) CM Input signal common P3 BX (Emergency stop) P4 RST (Trip reset) P5 JOG (Jog operation) CM Input signal common P6 Multi-step freq. - Low P7 Multi-step freq. - Middle P8 Multi-step freq. - High

AM CM

Multi-function analog output signal: 0~10V

3A A contact output 3C A/B contact common 3B B contact output

Potentiometer (1kohm, 1/2W) VR 10V power supply for potentiometer V1 Freq. Setting Voltage signal input: -10~10V I Freq. Current signal input: 0~20mA

MO Multi-function open collector output MG MO Common

S+ RS-485 communication terminal S-

CM Input signal common

11

iG5A

Wiring

11.0~22.0kW
DB resistor (Optional)

DC reactor

3 phase AC input (Rated input voltage)

P1(+) R S T G

B1 B2

N(-) U V W

Ground

24 24V output
P1 FX (Forward run) P2 RX (Reverse run) CM Input signal common P3 BX (Emergency stop) P4 RST (Trip reset) P5 JOG (Jog operation) CM Input signal common P6 Multi-step freq. - Low P7 Multi-step freq. - Middle P8 Multi-step freq. - High

AM CM

Multi-function analog output signal: 0~10V

3A A contact output 3C A/B contact common 3B B contact output

Potentiometer (1kohm, 1/2W) VR 10V power supply for potentiometer V1 Freq. Setting Voltage signal input: -10~10V I Freq. Current signal input: 0~20mA

MO Multi-function open collector output MG MO Common

S+ RS-485 communication terminal S-

CM Input signal common

12

Compact & Powerful Inverter iG5A

Terminal Configuration
Specifications for power terminal block wiring
0.4kW~0.75kW (1 phase)
R T B1 B2 W

0.4kW~1.5kW (3 phase)
R S T B1 U B2 V W

1.5kW (1 phase)
B1 R T 2.2~4.0kW (3 phase) T B1 B2 U V W

U V 5.5kW~7.5kW (3 phase) B1 R S B2 T U V

R S 11~22kW (3 phase) W R(L1)


R, S, T wire U, V, W wire mm2 2 2 2 2 2 2 2 3.5 3.5 5.5 8 14 22 30 30 2 2 2 2 2 2 2 3.5 5.5 8 8 14 AWG 14 14 14 14 14 14 14 12 12 10 8 6 4 2 2 14 14 14 14 14 14 14 12 10 8 8 6

B2

S(L2)

T(L3) P1(+)

B1

B2

N(-)

Ground wire mm2 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 5.5 5.5 14 14 22 22 2 2 2 2 2 2 3.5 3.5 8 8 14 14 AWG 12 12 12 12 12 12 12 12 12 10 10 6 6 4 4 14 14 14 14 14 14 12 12 8 8 6 6

mm2 SV004iG5A-1 SV008iG5A-1 SV015iG5A-1 SV004iG5A-2 SV008iG5A-2 SV015iG5A-2 SV022iG5A-2 SV037iG5A-2 SV040iG5A-2 SV055iG5A-2 SV075iG5A-2 SV110iG5A-2 SV150iG5A-2 SV185iG5A-2 SV220iG5A-2 SV004iG5A-4 SV008iG5A-4 SV015iG5A-4 SV022iG5A-4 SV037iG5A-4 SV040iG5A-4 SV055iG5A-4 SV075iG5A-4 SV110iG5A-4 SV150iG5A-4 SV185iG5A-4 SV220iG5A-4 2 2 2 2 2 2 2 3.5 3.5 5.5 8 14 22 30 38 2 2 2 2 2 2 3.5 3.5 5.5 14 14 22

AWG 14 14 14 14 14 14 14 12 12 10 8 6 4 2 2 14 14 14 14 14 14 12 12 10 6 6 4

Terminal Screw Size M3.5 M3.5 M4 M3.5 M3.5 M3.5 M4 M4 M4 M5 M5 M6 M6 M8 M8 M3.5 M3.5 M4 M4 M4 M4 M5 M5 M5 M5 M6 M6

Screw Torque (kgf.cm) / lb-in 10/8.7 10/8.7 15/13 10/8.7 10/8.7 10/8.7 15/13 15/13 15/13 32/28 32/28 30.7/26.6 30.7/26.6 30.5/26.5 30.5/26.5 10/8.7 10/8.7 15/13 15/13 15/13 15/13 32/28 32/28 30.7/26.6 30.7/26.6 30.5/26.5 30.5/26.5

13

iG5A

Terminal Configuration

Control terminal specifications

MO MG 3A 3B 3C P5

24 CM

P1 P6

P2 P7

CM P8

P3 VR

P4 V1

SI

S+ AM

Terminal P1~P8 CM VR V1 I AM MO MG 24 3A 3B 3C

Description Multi-function input T/M 1-8 Common terminal Power supply for external potentiometer Input terminal for voltage operation Input terminal for current operation Multi-function analog output terminal Multi-function terminal for open collector Ground terminal for external power supply 24V external power supply Multi-function relay output A contact Multi-function relay output B contact Common for multi-function relays

Wire size (mm2) Single wire 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 Stranded 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5

Screw size M2.6 M2.6 M2.6 M2.6 M2.6 M2.6 M2.6 M2.6 M2.6 M2.6 M2.6 M2.6

Torque (Nm) 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4

1)

Specification

Output voltage: 12V Max. output current: 100mA Potentiometer: 1~5kohm Max. input voltage: -12V~+12V input 0~20mA input Internal resistor: 500ohm Max. output voltage: 11V Max. output current: 100mA Below DC 26V,100mA Max. output current: 100mA Below AC 250V, 1A Below DC 30V, 1A

1) Use the recommended tightening torque when securing terminal screws. When you use external power supply (24V) for multi-function input terminal (P1~P8), apply voltage higher than 12V to activate. Tie the control wires more than 15cm away from the control terminals. Otherwise, it interferes front cover reinstallation.

14

Compact & Powerful Inverter iG5A

Keypad Features

Display RUN STOP/RESET KEY FWD LED


1)

Term Run key STOP/RESET key Up key Down key Right key Left key Enter key Forward run Reverse run Run key Setting Run command

Description STOP: Stop command during operation, RESET: Reset command when a fault occurs. Used to scroll through codes or increase parameter value Used to scroll through codes or decrease parameter value Used to jump to other parameter groups or move a cursor to the right to change the parameter value Used to jump to other parameter groups or move a cursor to the left to change the parameter value Used to set the parameter value or save the changed parameter value Lit during forward run Lit during reverse run Lit during operation Lit during parameter setting

REV RUN SET

1) 4 LEDs above are set to blink when a fault occurs.

Dimensions

36.2

SET RUN

FWD REV

72.4

RUN

2-4.5

STOP RESET ENT

65.6 5 2.1 13.9 23.1

3.4

95 83 70 C L

15

iG5A

Moving to Other Groups

Parameter groups
There are 4 different parameter groups in iG5A series as shown below.

Parameter group Drive group Function group 1 Function group 2 I/O (Input/Output) group

Description Basic parameters necessary for the inverter to run. Parameters such as Target frequency, Accel/Decel time settable. Basic function parameters to adjust output frequency and voltage. Advanced function parameters to set parameters for such as PID Operation and second motor operation. Parameters necessary to make up a sequence using multi-function input/output terminal.

Moving to other groups


Moving to other groups using the Right () key
1)

Moving to other groups using the Left () key


1)

1) Target frequency can be set at 0.0 (the 1st code of drive group). Even though the preset value is 0.0, it is user-settable. The changed frequency will be displayed after it is changed.

16

Compact & Powerful Inverter iG5A

When changing ACC time from 5.0 sec to 16.0 sec

1 2 3 4 5 6

In the first code 0.00press the Up () key once to go to the second code. , ACC [Accel time] is displayed. Press the Ent () key once. Preset value is 5.0, and the cursor is in the digit 0. Press the Left () key once to move the cursor to the left. The digit 5 in 5.0 is active. Then press the Up () key once. The value is increased to 6.0 Press the Left () key to move the cursor to the left. 0.60 is displayed. The first 0 in 0.60 is active. Press the Up () key once. 16.0 is set. Press the Ent () key once. 16.0 is blinking. 1) Press the Ent () key once again to return to the parameter name. ACC is displayed. Accel time is changed from 5.0 to 16.0 sec.

1) Pressing the Left ()/Right ()/Up ()/Down () key while a cursor is blinking will cancel the parameter value change. Pressing the Ent () key in this status will enter the value into memory. In step 7, pressing the Left () or Right () key while 16.0 is blinking will disable the setting.

Code change in Drive group 1 2 3 4 5 In the 1st code in Drive group 0.00 , press the Up () key once. The 2nd code in Drive group ACC displayed. is Press the Up () key once. The 3rd code dEC Drive group is displayed. in Keep pressing the Up () key until the last code appears. The last code in Drive group "drC displayed. is Press the Up () key again. Return to the first code of Drive group.

Use Down () key for the opposite order.

17

iG5A

Trial Run

Multi-step operation + Run/Stop via FX/RX + Max. frequency change Operation condition
Operation command: Run/Stop via FX/RX Frequency command: Multi-step operation [Low (20), Middle (30), High (80)] Max. frequency change: From 60Hz to 80Hz

Wiring
S1 P1 (Forward)

S2

P2 (Reverse) 3 phase AC input P6 (Low)

R S T G

U V W

S3

S4

P7 (Middle) S/W

S5

P8 (High)

P1 (Forward) P2 (Reverse)

CM P6 (Low) P7 (Middle) P8 (High) CM 1. Please make sure that R, S, T are connected to 3 phase AC input, and U, V, W are also motor connection terminals. 2. After supplying the power, please set the frequency of multi-step among Low, Middle, and High. 3. If P1 (FX) turns on, the motor operates in forward. And after turning off, it stops according to the deceleration time. 4. If P2 (RX) turns on, the motor operates in reverse. And after turning off, it stops according to the deceleration time. VR V1 CM

Parameter setting
Step 1 2 3 4 5 6 Command Max. frequency change (FU1) Multi-step frequency (DRV) Multi-step frequency (DRV) Multi-step frequency (I/O) Forward run (P1: FX) Reverse run (P2: RX) Code F21 st1 st2 I30 I17 I18 Set Low step. Set Middle step. Set High step. The default is FX. This value may change. The default is RX. This value may change. Description Change Max. frequency. Default 60Hz 10Hz 20Hz 30Hz FX RX After change 80Hz 20Hz 30Hz 80Hz FX RX

18

Compact & Powerful Inverter iG5A

Potentiometer (Volume) + Run/Stop via FX/RX + Accel/Decel time change Operation condition
Operation command: Run/Stop via FX/RX Frequency command: 0~60Hz analog input via potentiometer Accel/Decel time: Accel-10sec, Decel-20sec

Wiring
Potentiometer 1~5kohm, 1/2W 3 VR 1 V1 CM 0~60Hz P1 (FX) Forward P2 (RX) Reverse Motor 3 phase AC input R S T G U V W

CM

1. Please make sure that R, S, T are connected to 3 phase AC input, and U, V, W are also motor connection terminals. 2. After supplying the power, please set the frequency of multi-step among Low, Middle, and High. 3. If P1 (FX) turns on, the motor operates in forward. And after turning off, it stops according to the deceleration time. 4. If P2 (RX) turns on, the motor operates in reverse. And after turning off, it stops according to the deceleration time. 5. Control the motors speed via potentiometer. VR V1 CM Potentiometer 1~5kohm, 1/2W

Parameter setting
Step 1 2 3 4 5 Command Operation command (DRV group) Analog input (DRV group) Accel/Decel time (DRV group) Forward run (P1: FX) Reverse run (P2: RX) Code Drv Frq ACC dEC I17 I18 Description Turn on/off motor via terminal. Change keypad command to analog voltage command. Set Accel time to 10sec in ACC Set Decel time to 20sec in dEC. The default is FX. This value may change The default is RX. This value may change. Default 1 (FX/RX-1) 0 (Keypad-1) 5sec (Accel) 10sec (Decel) FX RX After change 1 (FX/RX-1) 3 (V1: 0~10V) 10sec (Accel) 20sec (Decel) FX RX

19

iG5A

Dimensions
W W1 A A H D B W1 H1

SV004iG5A-2 / SV008iG5A-2, SV004iG5A-4 / SV008iG5A-4

mm (inches) Inverter model SV004IG5A-2 SV008IG5A-2 SV004IG5A-4 SV008IG5A-4 (kW) 0.4 0.75 0.4 0.75 W (mm) 70 70 70 70 W1 (mm) 65.5 65.5 65.5 65.5 H (mm) 128 128 128 128 H1 (mm) 119 119 119 119 D (mm) 130 130 130 130 4.0 4.0 4.0 4.0 A (mm) 4.5 4.5 4.5 4.5 B (mm) 4.0 4.0 4.0 4.0 (kg) 0.76 0.77 0.76 0.77

SV015iG5A-2 / SV015iG5A-4
W W1 A A1 H D B W1 H1

mm (inches) Inverter model SV015IG5A-2 SV015IG5A-4 (kW) 1.5 1.5 W (mm) 100 100 W1 (mm) 95.5 95.5 H (mm) 128 128 H1 (mm) 120 120 D (mm) 130 130 4.5 4.5 A (mm) 4.5 4.5 B (mm) 4.5 4.5 (kg) 1.12 1.12

20

Compact & Powerful Inverter iG5A

SV022iG5A-2 / SV037iG5A-2 / SV040iG5A-2, SV022iG5A-4 / SV037iG5A-4 / SV040iG5A-4


W C L A B H1 D H B W1

mm (inches) Inverter model SV022IG5A-2 SV037IG5A-2 SV040IG5A-2 SV022IG5A-4 SV037IG5A-4 SV040IG5A-4 (kW) 2.2 3.7 4.0 2.2 3.7 4.0 W (mm) 140 140 140 140 140 140 W1 (mm) 132 132 132 132 132 132 H (mm) 128 128 128 128 128 128 H1 (mm) 120.5 120.5 120.5 120.5 120.5 120.5 D (mm) 155 155 155 155 155 155 4.5 4.5 4.5 4.5 4.5 4.5 A (mm) 4.5 4.5 4.5 4.5 4.5 4.5 B (mm) 4.5 4.5 4.5 4.5 4.5 4.5 (kg) 1.84 1.89 1.89 1.84 1.89 1.89

SV055iG5A-2 / SV075iG5A-2, SV055iG5A-4 / SV075iG5A-4


W A W A

H1

H D

mm (inches) Inverter model SV055IG5A-2 SV075IG5A-2 SV055IG5A-4 SV075IG5A-4 (kW) 5.5 7.5 5.5 7.5 W (mm) 180 180 180 180 W1 (mm) 170 170 170 170 H (mm) 220 220 220 220 H1 (mm) 210 210 210 210 D (mm) 170 170 170 170 4.5 4.5 4.5 4.5 A (mm) 5 5 5 5 B (mm) 4.5 4.5 4.5 4.5 (kg) 3.66 3.66 3.66 3.66

21

iG5A

Dimensions

SV110iG5A-2 / SV150iG5A-2 / SV110iG5A-4 / SV150iG5A-4

W A W1 A

H1

D B W1 B

mm (inches) Inverter model SV110iG5A-2 SV150iG5A-2 SV110iG5A-4 SV150iG5A-4 (kW) 11.0 15.0 11.0 15.0 W (mm) 235 235 235 235 W1 (mm) 219 219 219 219 H (mm) 320 320 320 320 H1 (mm) 304 304 304 304 D (mm) 189.5 189.5 189.5 189.5 7.0 7.0 7.0 7.0 A (mm) 8.0 8.0 8.0 8.0 B (mm) 7.0 7.0 7.0 7.0 (kg) 9.00 9.00 9.00 9.00

SV185iG5A-2 / SV220iG5A-2 / SV185iG5A-4 / SV220iG5A-4


W

W1 A

H1

D B W1 B

mm (inches) Inverter model SV185iG5A-2 SV220iG5A-2 SV185iG5A-4 SV220iG5A-4 (kW) 18.5 22.0 18.5 22.0 W (mm) 260 260 260 260 W1 (mm) 240 240 240 240 H (mm) 410 410 410 410 H1 (mm) 392 392 392 392 D (mm) 208.5 208.5 208.5 208.5 10.0 10.0 10.0 10.0 A (mm) 10.0 10.0 10.0 10.0 B (mm) 10.0 10.0 10.0 10.0 (kg) 13.3 13.3 10.0 10.0

22

Compact & Powerful Inverter iG5A

Braking Resistors and Peripheral Devices


Braking resistors
Voltage Inverter 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11.0 15.0 18.5 22.0 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11.0 15.0 18.5 22.0 100% braking Resistor [] 400 200 100 60 40 30 20 15 11 9 8 1,800 900 450 300 200 120 90 60 45 35 30 Watt [W]1) 50 100 200 300 500 700 1,000 1,400 2,000 2,400 2,800 50 100 200 300 500 700 1,000 1,400 2,000 2,400 2,800 150% braking Resistor [] 300 150 60 50 33 20 15 10 8 5 5 1,200 600 300 200 130 85 60 40 30 20 20 Watt [W] 1) 100 150 300 400 600 800 1,200 2,400 2,400 3,600 3,600 100 150 300 400 600 1,000 1,200 2,000 2,400 3,600 3,600

200V Series

400V Series

1) The wattage is based on Enable Duty (%ED) with continuous braking time 15sec.

Breakers
Model 004iG5A-1 008iG5A-1 015iG5A-1 004iG5A-2 008iG5A-2 015iG5A-2 022iG5A-2 037iG5A-2 040iG5A-2 055iG5A-2 075iG5A-2 110iG5A-2 150iG5A-2 185iG5A-2 MCCB, ELCB (LS) TD125U,EBs33 TD125U,EBs33 TD125U,EBs33 TD125U,EBs33 TD125U,EBs33 TD125U,EBs33 TD125U,EBs33 TD125U,EBs33 TD125U,EBs33 TD125U,EBs53 TD125U,EBs53 TD125U,EBs53 TD125U,EBs53 TD250U,EBs53 MC GMC-9 GMC-9 GMC-12 GMC-9 GMC-9 GMC-12 GMC-18 GMC-32 GMC-32 GMC-40 GMC-50 GMC-65 GMC-100 GMC-100 Model 220iG5A-2 004iG5A-4 008iG5A-4 015iG5A-4 022iG5A-4 037iG5A-4 040iG5A-4 055iG5A-4 075iG5A-4 110iG5A-4 150iG5A-4 185iG5A-4 220iG5A-4 MCCB, ELCB (LS) TS250U,EBs53 TD125U,EBs33 TD125U,EBs33 TD125U,EBs33 TD125U,EBs33 TD125U,EBs33 TD125U,EBs33 TD125U,EBs33 TD125U,EBs33 TD125U,EBs53 TD125U,EBs53 TD125U,EBs53 TD125U,EBs53 MC GMC-125 GMC-9 GMC-9 GMC-9 GMC-12 GMC-18 GMC-18 GMC-32 GMC-32 GMC-40 GMC-50 GMC-65 GMC-65

23

iG5A

Braking Resistors and Peripheral Devices


Model 004iG5A-1 008iG5A-1 015iG5A-1 004iG5A-2 008iG5A-2 015iG5A-2 022iG5A-2 037iG5A-2 040iG5A-2 055iG5A-2 075iG5A-2 110iG5A-2 150iG5A-2 185iG5A-2 220iG5A-2 004iG5A-4 008iG5A-4 015iG5A-4 022iG5A-4 037iG5A-4 040iG5A-4 055iG5A-4 075iG5A-4 110iG5A-4 150iG5A-4 185iG5A-4 220iG5A-4 AC external fuse Current [A] 10 A 10 A 15 A 10 A 10 A 15 A 25 A 30 A 30 A 30 A 50 A 70 A 100 A 100 A 125 A 5A 10 A 10 A 10 A 20 A 20 A 20 A 30 A 35 A 45 A 60 A 70 A Voltage [V] 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V AC reactor 4.20 mH, 3.5 A 2.13 mH, 5.7 A 1.20 mH, 10 A 4.20 mH, 3.5 A 2.13 mH, 5.7 A 1.20 mH, 10 A 0.88 mH, 14 A 0.56 mH, 20 A 0.56 mH, 20 A 0.39 mH, 30 A 0.28 mH, 40 A 0.20 mH, 59 A 0.15 mH, 75 A 0.12 mH, 96 A 0.10 mH, 112 A 18.0 mH, 1.3 A 8.63 mH, 2.8 A 4.81 mH, 4.8 A 3.23 mH, 7.5 A 2.34 mH, 10 A 2.34 mH, 10 A 1.22 mH, 15 A 1.14 mH, 20 A 0.81 mH, 30 A 0.61 mH, 38 A 0.45 mH, 50 A 0.39 mH, 58 A DC reactor 0.74 mH, 56 A 0.57 mH, 71 A 0.49 mH, 91 A 0.42 mH, 107 A 2.76 mH, 29 A 2.18 mH, 36 A 1.79 mH, 48 A 1.54 mH, 55 A

Fuses & AC reactors

24

Compact & Powerful Inverter iG5A

Function List
Drive Group
LED display Address for communication Parameter name Min/Max range commanded to output. 0.00 A100 [Frequency command] 0 ~ 400 [Hz] During Stop: Frequency Command During Run: Output Frequency During Multi-step operation: Multi-step frequency 0. It cannot be set greater than F21- [Max frequency]. ACC dEC A101 A102 [Accel time] [Decel time] 0 ~ 6000 [Sec] During Multi-Accel/Decel operation, this parameter serves as Accel/Decel time 0. 0 1 drv A103 [Drive mode] 0~3 Terminal operation 2 3 4 0 1 2 3 Frq A104 [Frequency setting method] 0~7 4 5 6 7 8 9 St1 St2 St3 CUr rPM dCL A105 A106 A107 A108 A109 A10A [Multi-Step frequency 1] [Multi-Step frequency 2] [Multi-Step frequency 3] [Output current] [Motor RPM] [Inverter DC link voltage] [User display select] 0 ~ 400 [Hz] Digital Volume Set to Field Bus communication 1) 10.00 20.00 30.00 O O O Analog Run/Stop via Run/Stop key on the keypad FX: Motor forward run RX: Motor reverse run FX: Run/Stop enable RX: Reverse rotation select RS485 communication Set to Field Bus communication Digital
1)

Description This parameter sets the frequency that the inverter is

Factory defaults

Adj. during run

0.00

5.0 10.0

O O

Keypad setting 1 Keypad setting 2 V1 1: -10 ~ +10 [V] V1 2: 0 ~ +10 [V] Terminal I: 0 ~ 20 [mA] Terminal V1 setting 1 + Terminal I Terminal V1 setting 2+ Terminal I 0

RS485 communication

Sets Multi-Step frequency 1 during Multi-step operation. Sets Multi-Step frequency 2 during Multi-step operation. Sets Multi-Step frequency 3 during Multi-step operation. Displays the output current to the motor. Displays the number of Motor RPM. Displays DC link voltage inside the inverter. This parameter displays the item selected at H73- [Monitoring item select]. vOL POr tOr Output voltage Output power Torque

vOL

A10B

vOL

1) This function can be available with iG5A Communication Option Module.

25

iG5A

Function List
Address for communication A10C Parameter name [Fault Display] [Direction of Min/Max range time of the fault Sets the direction of motor rotation when drv - [Drive mode] is set F, r to either 0 or 1. F r 0 1 Forward Reverse Run/Stop via Run/Stop key on the keypad FX: Motor forward run Terminal operation 2 3 4 0 1 2 3 0~7 4 5 6 7 8 9 PID control 0~400[Hz] 0~100 [%] Digital Volume Set to Filed Bus Communication 3) 0.00 0 Analog RX: Motor reverse run FX: Run/Stop enable RX: Reverse rotation select RS-485 communication Set to Filed Bus Communication 3) Digital Keypad setting 1 Keypad setting 2 V1 1: -10 ~ +10 [V] V1 2: 0 ~ +10 [V] Terminal I: 0 ~ 20 [mA] Terminal V1 setting 1 + Terminal I Terminal V1 setting 2+ Terminal I RS485 communication 0 1 F O Description Displays the types of faults, frequency and operating status at the Factory defaults Adj. during run -

Drive Group
LED display nOn

drC

A10D

motor rotation select]

drv2

A10E

[Drive mode 2]

0~3

Frq2

1)

[Frequency A10F setting method 2]

If H58 is 0, it is expressed as a [Hz] unit. If H58 is 1, it is expressed as a [%] unit. In [Hz] unit, you cant set Max. frequency more than (F21). In [%] unit, 100% means Max. frequency. It indicates a feedback amount in PID control. If H58 is 0, it is expressed as a [Hz] unit. If H58 is 1, it is expressed as a [%] unit. -

rEF 2)

A110

standard or value setting PID control

Fbk

2)

A111

feedback amount

1) Only displayed when one of the Multi-function input terminals 1-8 [I17~I24] is set to 22. 2) It is indicated when H49(PID control selection) is 1. 3) This function can be available with iG5A Communication Option Module.

Function group 1
LED display F0 F1 F2 F3 Address for communication A200 A201 A202 A203 Parameter name [Jump code] [Forward/ Reverse run disable] [Accel pattern] 0~1 [Decel pattern] 1 S-curve 0~2 Min/Max range 0 ~ 71 Description Sets the parameter code number to jump. 0 1 2 0 Fwd and rev run enable Forward run disable Reverse run disable Linear 0 0 Factory defaults 1 Adj. during run O

26

Compact & Powerful Inverter iG5A

Function group 1
LED display Address for communication Parameter name [Stop mode select] [DC Brake start frequency] [DC Brake wait time] [DC Brake voltage] [DC Brake time] [DC Brake start voltage] [DC Brake start time] [Time for F14 F20 A20E A214 magnetizing a motor] [Jog frequency] Min/Max range 0 F4 A204 0~3 0.1 ~ 60 [Hz] 0 ~ 60 [sec] 0 ~ 200 [%] 0 ~ 60 [sec] 0 ~ 200 [%] 0 ~ 60 [sec] 0 ~ 60 [sec] 0 ~ 400 [Hz] 1 2 3 F 8 1) F9 F10 F11 F12 F13 A208 A209 A20A A20B A20C A20D Decelerate to stop DC brake to stop Free run to stop Power Braking stop 5.00 0.1 50 1.0 50 0 0.1 10.00 0 Description Factory defaults Adj. during run

This parameter sets DC brake start frequency. It cannot be set below F23 - [Start frequency]. When DC brake frequency is reached, the inverter holds the output for the setting time before starting DC brake. This parameter sets the amount of DC voltage applied to a motor. It is set in percent of H33 - [Motor rated current]. This parameter sets the time taken to apply DC current to a motor while motor is at a stop. This parameter sets the amount of DC voltage before a motor starts to run. It is set in percent of H33 - [Motor rated current]. DC voltage is applied to the motor for DC Brake start time before motor accelerates. This parameter applies the current to a motor for the set time before motor accelerates during Sensorless vector control. This parameter sets the frequency for Jog operation. It cannot be set above F21 - [Max frequency]. This parameter sets the highest frequency the inverter can output. It is frequency reference for Accel/Decel (See H70)

F21 2)

A215

[Max frequency]

40 ~ 400 [Hz] frequency

Caution Any frequency cannot be set above Max frequency except Base

60.00

F22 F23 F24 F25 3) F26 F27 F28 F29

A216 A217 A218 A219 A21A A21B A21C A21D

[Base frequency] [Start frequency] [Frequency high /low limit select] [Frequency high limit] [Frequency low limit] [Torque Boost select] [Torque boost in forward direction] [Torque boost in reverse direction]

30 ~ 400 [Hz] 0.1 ~ 10 [Hz] 0~1 0 ~ 400 [Hz] 0.1 ~ 400 [Hz] 0~1 0 ~ 15 [%]

The inverter outputs its rated voltage to the motor at this frequency (see motor nameplate). The inverter starts to output its voltage at this frequency. It is the frequency low limit. This parameter sets high and low limit of run frequency. This parameter sets high limit of the run frequency. It cannot be set above F21 - [Max frequency]. This parameter sets low limit of the run frequency. It cannot be set above F25 - [Frequency high limit] and below F23 - [Start frequency]. 0 1 Manual torque boost Auto torque boost

60.00 0.50 0 60.00 0.50 0 2 2

This parameter sets the amount of torque boost applied to a motor during forward run. It is set in percent of Max output voltage. This parameter sets the amount of torque boost applied to a motor during reverse run. It is set as a percent of Max output voltage.

1) Only displayed when F 4 is set to 1 (DC brake to stop). 2) If H40 is set to 3 (Sensorless vector), Max. frequency is settable up to 300Hz. 3) Only displayed when F24 (Frequency high/low limit select) is set to 1.

27

iG5A

Function List
Address for communication A21E A21F A220 A221 A222 A223 A224 A225 A226 A227 A228 A232 Parameter name [V/F pattern] [User V/F frequency 1] [User V/F ] voltage 1 [User V/F frequency 2] [User V/F voltage 2] [User V/F frequency 3] [User V/F voltage 3] [User V/F frequency 4] [User V/F voltage 4] [Output voltage adjustment] [Energy-saving level] [Electronic thermal select] [Electronic Min/Max range 0 {Linear} {Square} {User V/F} 15.00 25 30.00 50 45.00 75 60.00 100 This parameter adjusts the amount of output voltage. The set value is the percentage of input voltage. This parameter decreases output voltage according to load status. This parameter is activated when the motor is overheated (timeinverse). This parameter sets max current capable of flowing to the motor continuously for 1 minute. The set value is the percentage of H33 - [Motor rated current]. It cannot be set below F52 - [Electronic thermal level for continuous]. [Electronic This parameter sets the amount of current to keep the motor 50 ~ 150 [%] running continuously. It cannot be set higher than F51 - [Electronic thermal level for 1 minute]. 0 0~1 1 30 ~ 150 [%] 0 ~ 30 [Sec] Standard motor having cooling fan directly connected to the shaft A motor using a separate motor to power a cooling fan. 150 0 0 0 100 0 150 0 100 0 0 0 0 0 0~2 0 ~ 400 [Hz] 0 ~ 100 [%] 0 ~ 400 [Hz] 0 ~ 100 [%] 0 ~ 400 [Hz] 0 ~ 100 [%] 0 ~ 400 [Hz] 0 ~ 100 [%] 40 ~ 110 [%] 0 ~ 30 [%] 0~1 The value of voltage is set in percent of H70 - [Motor rated voltage]. The values of the lower-numbered parameters cannot be set above those of higher-numbered. 1 2 Description Factory defaults Adj. during run

Function group 1
LED display F30 F31 1) F32 F33 F34 F35 F36 F37 F38 F39 F40 F50

It is used only when V/F pattern is set to 2(User V/F) It cannot be set above F21 - [Max frequency].

F51 2)

A233

thermal level for 1 minute]

50 ~ 200 [%]

F52

A234

thermal level for continuous] [Motor cooling method] [Overload warning level] [Overload warning time]

F53

A235

This parameter sets the amount of current to issue an alarm signal at a relay or multi-function output terminal (see I54, I55). The set value is the percentage of H33- [Motor rated current]. This parameter issues an alarm signal when the current greater than F54- [Overload warning level] flows to the motor for F55[Overload warning time]. 10 0

F54

A236

F55

A237

1) Set F30 to 2(User V/F) to display this parameter. 2) Set F50 to 1 to display this parameter.

28

Compact & Powerful Inverter iG5A

Function group 1
LED display F56 F57 F58 Address for communication A238 A239 A23A Parameter name [Overload trip select] [Overload trip level] [Overload trip time] Min/Max range 0~1 30 ~ 200 [%] 0 ~ 60 [Sec] overloaded. This parameter sets the amount of overload current. The value is the percentage of H33- [Motor rated current]. This parameter turns off the inverter output when the F57[Overload trip level] of current flows to the motor for F58[Overload trip time]. This parameter stops accelerating during acceleration, decelerating during constant speed run and stops decelerating during deceleration. During Decel Bit 2 F59 A23B [Stall prevention select] 0 0~7 1 2 3 4 5 6 7 F60 A23C [Stall prevention level] [When Stall F61 1) A23D prevention during deceleration, voltage limit select F63 F64 2) A23F A240 [Save up/down frequency select] [Save up/down frequency] [Up-down mode select] [Up-down step frequency] [Draw run mode select] [Draw rate] This parameter decides whether to save the specified frequency 0~1 during up/down operation. When 1 is selected, the up/down frequency is saved in F64. If Save up/down frequency is selected at F63, this parameter saves the frequency before the inverter stops or decelerated. We can select up-down mode among three thing F65 A241 0~2 0 1 2 F66 A242 0~400 [Hz] 0~3 Increases goal frequency as a standard of Max. frequency/Min. frequency Increases as many as step frequency according to edge input Available to combine 1 and 2 0.00 0 0.00 0 0~1 In Stall prevention run during deceleration, if you want to limit output voltage, select 1 30 ~ 200 [%] This parameter sets the amount of current to activate stall prevention function during Accel, Constant or Decel run. The set value is the percentage of the H33- [Motor rated current]. 150 During constant run During Accel Bit 1 Bit 0 0 60 0 Description This parameter turns off the inverter output when motor is Factory defaults 1 180 Adj. during run 0 0

In case of choosing F65 as a 1 or 2, it means increase or decrease of frequency according to up-down input 0 Inverter doesnt run as a draw mode V1(0~10V) input draw run I(0~20mA) input draw run V1(-10~10V) input draw run 1 2 3

F70

A246

F71

A247

0~100[%]

Sets rate of draw

0.00

1) It is indicated when setting bit 2 of F59 as 1 2) Set F63 to 1 to display this parameter.

29

iG5A

Function List
Address for communication A300 A301 A302 A303 A304 A305 A306 Parameter name [Jump code] [Fault history 1] [Fault history 2] [Fault history 3] [Fault history 4] [Fault history 5] [Reset fault history] [Dwell frequency] Min/Max range 0~95 0~1 0.1~400 [Hz] 0~10 [sec] 0~1 Clears the fault history saved in H 1-5. When run frequency is issued, motor starts to accelerate after dwell frequency is applied to the motor during H8- [Dwell time]. [Dwell frequency] can be set within the range of F21- [Max frequency] and F23- [Start frequency]. Sets the time for dwell operation. Sets the frequency range to skip to prevent undesirable resonance and vibration on the structure of the machine. Stores information on the types of faults, the frequency, the current and the Accel/Decel condition at the time of fault. The latest fault is automatically stored in the H 1- [Fault history 1]. Description Sets the code number to jump. Factory defaults 1 nOn nOn nOn nOn nOn 0 Adj. during run O O

Function group 2
LED display H0 H1 H2 H3 H4 H5 H6

H7

A307

5.00

H8 H10 H11 1) H12 H13 H14 H15 H16 H17 H18 H19

A308 A30A A30B A30C A30D A30E A30F A310 A311 A312 A313

[Dwell time] [Skip frequency select] [Skip frequency low limit 1] [Skip frequency high limit 1] [Skip frequency low limit 2] [Skip frequency high limit 2] [Skip frequency low limit 3] [Skip frequency high limit 3] [S-Curve accel/ decel start side] [S-Curve accel/ decel end side] [Input/output phase loss protection select]

0.0 0 10.00 15.00

Run frequency cannot be set within the range of H11 thru H16. 0.1~400 [Hz] The frequency values of the low numbered parameters cannot be set above those of the high numbered ones. Settable within the range of F21 and F23.

20.00 25.00 30.00 35.00

1~100 [%] 1~100 [%] 0~3

Set the speed reference value to form a curve at the start during accel/decel. If it is set higher, linear zone gets smaller. Set the speed reference value to form a curve at the end during accel/decel. If it is set higher, linear zone gets smaller. 0 Disabled 1 Output phase protection 2 Input phase protection 3 Input/output phase protection

40 40 0

This parameter is activated when drv is set to 1 or 2 (Run/Stop H20 A314 [Power On Start select] [Restart after H21 A315 fault reset selection] 0 ~1 0~1 via Control terminal). Motor starts acceleration after AC power is applied while FX or RX terminal is ON. This parameter is activated when drv is set to 1 or 2 (Run/Stop via Control terminal). Motor accelerates after the fault condition is reset while the FX or RX terminal is ON. 0 O 0 O

1) only displayed when H10 is set to 1. # H17, H18 are used when F2, F3 are set to 1 (S-curve)

30

Compact & Powerful Inverter iG5A

Function group 2
LED display Address for communication Parameter name Min/Max range Description This parameter is active to prevent any possible fault when the inverter outputs its voltage to the running motor. 1. H202. Restart 3. Operation [Power On start] 0 1 2 3 4 1. H20[Power H22 1) A316 [Speed Search Select] 0 ~ 15 5 6 7 8 9 10 11 12 13 14 15 [Current level H23 H24 H25 A317 A318 A319 during Speed search] [P gain during Speed search] [I gain during speed search] [Number of Auto Restart try] [Auto Restart time] [Motor type select] [Number of motor poles] 80~200 [%] 0~9999 0~9999 This parameter limits the amount of current during speed search. The set value is the percentage of the H33- [Motor rated current]. It is the Proportional gain used for Speed Search PI controller. It is the Integral gain used for Speed search PI controller. This parameter sets the number of restart tries after a fault occurs. Auto Restart is deactivated if the fault outnumbers the 0 ~10 restart tries. This function is active when [drv] is set to 1 or 2 {Run/Stop via control terminal}. Deactivated during active protection function (OHT, LVT, EXT, HWT etc.). H27 H30 H31 A31B A31E A31F 0~60 [sec] 0.2~ 22.0 2 ~ 12 This parameter sets the time between restart tries. 0.2 ~ 22.0 0.2kW ~ 22.0kW 4 7.5 2) 1.0 O 0 O H26 A31A 100 100 200 O O O On start] Bit 3 2. Restart after instant power failure Bit 2 Bit 1 Bit 0 3. Operation after fault 4. Normal accel after instant power failure after fault 4. Normal accel Factory defaults 0 Adj. during run O

This setting is displayed via rPM in drive group.

1) Normal acceleration has first priority. Even though #4 is selected along with other bits, Inverter performs Speed search #4. 2) H30 is preset based on inverter rating.

31

iG5A

Function List
Address for communication Parameter name Min/Max range fs = fr Description Factory defaults Adj. during run

Function group 2
LED display

[ rpm p ] 120
2.33 1)

H32

A320

[Rated slip frequency]

0 ~ 10 [Hz]

Where, fs = Rated slip frequency fr = Rated frequency rpm = Motor nameplate RPM p = Number of Motor poles

H33

A321

[Motor rated current] [No Load Motor Current] [Motor efficiency]

0.5~150 [A] 0.1~ 50 [A] 50~100 [%] 0~2

Enter motor rated current on the nameplate. Enter the current value detected when the motor is rotating in rated rpm after the load connected to the motor shaft is removed. Enter the 50% of the rated current value when it is difficult to measure H34 - [No Load Motor Current]. Enter the motor efficiency (see motor nameplate). Select one of the following according to motor inertia. 0 1 2 Less than 10 times About 10 times More than 10 times

26.3

H34

A322

11

H36

A324

87

H37

A325

[Load inertia rate]

[Carrier H39 A327 frequency select] H40 H41 H42 H44 H45 2) H46 H47 A328 A329 A32A A32C A32D A32E A32F [Control mode select] [Auto tuning] [Stator resistance (Rs)] [Leakage inductance (L )] [Sensorless P gain] [Sensorless I gain]

This parameter affects the audible sound of the motor, noise 1 ~ 15 [kHz] emission from the inverter, inverter temp, and leakage current. If the set value is higher, the inverter sound is quieter but the noise from the inverter and leakage current will become greater. 0 0~3 0~1 0 ~ 28 [] 0~ 300.0 [mH] 0~ 32767 I gain for Sensorless control Limits output torque in sensorless mode. If you want to limit a inverter leakage current, select 2 phase [%] PWM mode. 0~1 It has more noise in comparison to Normal PWM mode. 0 1 0~1 Normal PWM mode 2 phase PWM mode 0 0 100 180.0 O 1 3 {Volts/frequency Control} {Slip compensation control} {Sensorless vector control} 0 1000 O 0 3 O

If this parameter is set to 1, it automatically measures parameters of the H42 and H44. This is the value of the motor stator resistance. This is leakage inductance of the stator and rotor of the motor. P gain for Sensorless control

[Sensorless 100~220 torque limit] PWM mode select PID select

H48

A330

H49

A331

Selects whether using PID control or not

1) H32 ~ H36 factory default values are set based on OTIS-LG motor. 2) Set H40 to 3 (Sensorless vector control) to display this parameter.

32

Compact & Powerful Inverter iG5A

Function group 2
LED display H50 1) H51 H52 H53 H54 Address for communication A332 A333 A334 A335 A336 Parameter name [PID F/B select] [P gain for PID] [Integral time for PID [Differential time for PID (D gain)] [PID control mode select] [PID output H55 A337 frequency high limit] [PID output H56 A338 frequency low limit] Min/Max range 0~1 0~ 999.9 [%] 0.1~32.0 [sec] 0 ~ 30.0 [sec] Selects PID control mode 0~1 0.1 ~ 400 [Hz] 0.1 ~ 400 [Hz] 0 1 Normal PID control Process PID control 60.00 O 0 This parameter sets the gains for the PID controller. 0 1 Description Terminal I input (0 ~ 20 mA) Terminal V1 input (0 ~ 10 V) Factory defaults 0 300.0 1.0 0.0 Adj. during run O O O

This parameter limits the amount of the output frequency through the PID control. The value is settable within the range of F21 ? [Max frequency] and F23 - [Start frequency]. Selects PID standard value. Standard value is indicated in rEF of Drive group.

0.50

H57

A339

[PID standard value select]

0 0~4 1 2 3 4

Loader digital setting 1 Loader digital setting 2 V1 terminal setting 2: 0~10V I terminal setting: 0~20mA Setting as a RS-485 communication Frequency[Hz] Percentage[%] Self-diagnostic disabled IGBT fault/Ground fault Output phase short & open/ Ground fault Ground fault (This setting is unable when more than 11kW) 60.0 0.00 35.0 0 125.0 130.0 1000 0 O O 0 0 0

H58

A33A

PID control unit select [Self-diagnostic select]

Selects a unit of the standard value or feedback amount. 0~1 0 1 0 0~3 1 2 3

H60 H61 2) H62 H63 H64 H65 H66 H67 H70

A33C A33D A33E A33F A340 A341 A342 A343 A346

[Sleep delay time] 0~2000[s] Sets a sleep delay time in PID drive. Sets a sleep frequency when executing a sleep function in PID [Sleep frequency] 0~400[Hz] control drive. You cant set more than Max. frequency(F21) [Wake up level] [KEB drive select] [KEB action start level] [KEB action stop level] [KEB action gain] [Frequency Reference for Accel/Decel] 0~1 0~100[%] Sets a wake up level in PID control drive. 0~1 110~140 [%] 110~145 [%] 1~20000 Sets KEB drive. Sets KEB action start level according to level. Sets KEB action stop level according to level. Sets KEB action gain. 0 1 Based on Max freq (F21) Based on Delta freq.

1) Set H49 to 1 (PID control) to display this parameter. 2) Set H49 as a 1 3): it is indicated when setting H64(KEB drive select) as a 1 (KEB does not operate when cut power after loading ting input (about 10%).

33

iG5A

Function List
Address for communication A347 Parameter name [Accel/Decel time scale] Min/Max range 0 0~2 1 2 Description Settable unit: 0.01 second. Settable unit: 0.1 second. Settable unit: 1 second. 1 O Factory defaults Adj. during run

Function group 2
LED display H71

This parameter selects the parameter to be displayed on the keypad when the input power is first applied. 0 1 2 3 4 5 6 H72 A348 [Power on display] 0 ~ 15 7 8 9 10 11 12 13 14 15 16 17 Frequency command Accel time Decel time Drive mode Frequency mode Multi-Step frequency 1 Multi-Step frequency 2 Multi-Step frequency 3 Output current Motor rpm Inverter DC link voltage User display select (H73) Fault display Direction of motor rotation select Output current 2 Motor rpm 2 Inverter DC link voltage 2 User display select 2 0 O

One of the following can be monitored via vOL - [User display H73 A349 [Monitoring item select] [Gain for Motor rpm display] [DB resistor H75 H76 A34B A34C operating rate limit select] [DB resistor operating rate] [Cooling fan control] [Operating H78 H79 A34E A34F method select when cooling fan malfunctions] [S/W version] 0 ~ 10.0 0~1 1 Operation stopped when cooling fan malfunctions. 1.0 This parameter displays the inverter software version. 0 ~ 30 [%] 0~1 0~1 select]. 0~2 0 1 2 H74 A34A 1 ~ 1000 [%] Output voltage [V] Output power [kW] Torque [kgfm] 100 1 10 O O O 0 O

This parameter is used to change the motor rotating speed (r/min) to mechanical speed (m/mi) and display it. 0 1 Unlimited Use DB resistor for the H76 set time.

Set the percent of DB resistor operating rate to be activated during one sequence of operation. 0 Always ON Keeps ON when its temp is higher than inverter protection 1 0 limit temp. Activated only during operation when its temp is below that of inverter protection limit. Continuous operation when cooling fan malfunctions.

H77 1)

A34D

1) Exception: Since SV004iG5A-2/SV004iG5A-4 is Natural convection type, this code is hidden.

34

Compact & Powerful Inverter iG5A

Function group 2
LED display H81 1) H82 H83 H84 H85 H86 H87 H88 Address for communication A351 A352 A353 A354 A355 A356 A347 A358 Parameter name [2nd motor Accel time] [2nd motor [sec] Decel time] [2nd motor base frequency] [2nd motor V/F pattern] [2nd motor forward torque boost] [2nd motor reverse torque boost] [2nd motor stall prevention level] [2nd motor Electronic thermal level for 1 min] [2nd motor H89 A359 Electronic thermal level for continuous] H90 H91 2) H92 A35A A35B A35C [2nd motor 0.1~100 rated current] [Parameter read] [Parameter write] [A] 0~1 0~1 Copy the parameters from inverter and save them into remote loader. Copy the parameters from remote loader and save them into inverter. This parameter is used to initialize parameters back to the factory default value. 0 H93 A35D [Parameter initialize] 0~5 1 2 3 4 5 H94 A35E [Password register] [Parameter lock] 0 ~ FFFF All parameter groups are initialized to factory default value. Only Drive group is initialized. Only Function group 1 is initialized. Only Function group 2 is initialized. Only I/O group is initialized. 0 O 0 26.3 0 0 50~150 [%] 100 O 30~150 [%] 50~200 [%] 0 ~ 15 [%] This parameter actives when the selected terminal is ON after I17-I24 is set to 12 {2 motor select}.
nd

Min/Max range 0 ~ 6000

Description

Factory defaults 5.0 10.0

Adj. during run O O

30 ~ 400 [Hz] 0~2

60.00 0 5 5 150 150

Password for H95-[Parameter lock]. Set as Hexa value. This parameter is able to lock or unlock parameters by typing password registered in H94. UL (Unlock) L (Lock) Parameter change enable Parameter change disable

H95

A35F

0 ~ FFFF

1) It is indicated when choosing I17~I24 as a 12 (2nd motor select). 2) H91,H92 parameters are displayed when Remote option is installed.

35

iG5A

Function List
Address for communication A400 A402 A403 A404 A405 A406 A407 A408 A409 A40A A40B A40C A40D A40E A40F A410 Parameter name [Jump code] [NV input Min voltage] [Frequency corresponding to I 2] [NV input Max voltage] [Frequency corresponding to I 4] for V1 input] [V1 input Min voltage] [Frequency corresponding to I 7] [V1 input Max voltage] [Frequency corresponding to I 9] [Filter time constant for I input] [I input Min current] [Frequency corresponding to I 12] [I input Max current] [Frequency corresponding to I 14] [Criteria for Analog Input Signal loss] [Multi-function 0 ~ 9999 0 ~ 20 [mA] 0 ~ 400 [Hz] 0 ~ 20 [mA] 0 ~ 400 [Hz] 0~2 Sets the inverter output maximum frequency at maximum current of I input. 0 1 2 0 1 2 0 ~ 27 3 4 5 6 7 Disabled activated below half of set value. activated below set value. Forward run command Reverse run command Emergency Stop Trip Reset when a fault occurs {RST} Jog operation command Multi-Step freq - Low Multi-Step freq - Mid Multi-Step freq - High 0 O 0 O Sets the inverter output minimum frequency at minimum current of I input. Sets the Maximum current of I input. Sets the minimum current of I input. 0 ~ 10 [V] 0 ~ 400 [Hz] 0 ~ 10 [V] 0 ~ 400 [Hz] Sets the inverter output maximum frequency at maximum voltage of the V1 input. Sets the input sections internal filter constant for I input. Sets the inverter output minimum frequency at minimum voltage of the V1 input. Sets the maximum voltage of the V1 input. Sets the minimum voltage of the V1 input. Min/Max range 0 ~ 87 0 ~ -10 [V] 0 ~ 400 [Hz] 0 ~ -10 [V] 0 ~ 400 [Hz] Sets the inverter output maximum frequency at maximum voltage of the NV input. Sets the inverter output minimum frequency at minimum voltage of the NV input. Sets the maximum voltage of the NV input. Description Sets the code number to jump. Sets the minimum voltage of the NV (-10V~0V) input. Factory defaults 1 0.00 0.00 10.0 60.00 10 0 0.00 10 60.00 10 4.00 0.00 20.00 60.00 Adj. during run O O O O O O O O O O O O O O O

Input/output group
LED display I0 I2 I3 I4 I5 I6 I7 I8 I9 I10 I11 I12 I13 I14 I15 I16

[Filter time constant 0 ~ 9999 Adjusts the responsiveness of V1 input (0 ~ +10V).

I17

A411

input terminal P1 define] [Multi-function

I18

A412

input terminal P2 define] [Multi-function

I19

A413

input terminal P3 define] [Multi-function

I20

A414

input terminal P4 define]

* See Chapter 14 Troubleshooting and maintenance for External trip A/B contact. * Each multi-function input terminal must be set differently.

36

Compact & Powerful Inverter iG5A

Input/output group
LED display I21 Address for communication A415 Parameter name [Multi-function input terminal P5 define] [Multi-function I22 A416 input terminal P6 define] [Multi-function I23 A417 input terminal P7 define] Min/Max range 8 9 10 11 12 13 14 15 0 ~ 27 16 17 18 [Multi-function I24 A418 input terminal P8 define] 19 20 21 22 23 24 25 26 27 I25 I26 A419 A41A [Input terminal status display] [Output terminal status display] [Filtering time I27 A41B constant for Multi-function Input terminal] I30 I31 I32 I33 I34 I35 I36 A41E A41F A420 A421 A422 A423 A424 [Multi-Step frequency 4] [Multi-Step frequency 5] [Multi-Step [Hz] frequency 6] [Multi-Step frequency 7] [Multi-Accel time 1] [Multi-Decel 0~ time 1] [Multi-Accel time 2] 6000 [sec] 0 ~ 400 It cannot be set greater than F21 - [Max frequency]. 20.00 15.00 3.0 3.0 4.0 O O O 30.00 25.00 O O 1 ~ 15 If the value is set higher, the responsiveness of the Input terminal is getting slower. 4 O BIT7 P8 Description Multi Accel/Decel - Low Multi Accel/Decel - Mid Multi Accel/Decel - High DC brake during stop 2nd motor select -Reserved-ReservedUp-down 3-wire operation External trip: A Contact (EtA) External trip: B Contact (EtB) Self-diagnostic function Change from PID operation to V/F operation 2nd Source Analog Hold Accel/Decel Disable Up/Down Save Freq. Initialization JOG-FX JOG-RX BIT6 P7 BIT1 3AC BIT5 P6 BIT4 P5 BIT3 P4 BIT2 P3 MO BIT1 P2 BIT0 BIT0 P1 0 0 O O 7 O Frequency increase (UP) command Frequency decrease command (DOWN) Factory defaults 4 Adj. during run O

37

iG5A

Function List
Address for communication A425 A426 A427 A428 A429 A42A A42B A42C A42D A42E A42F Parameter name [Multi-Decel time 2] [Multi-Accel time 3] [Multi-Decel time 3] [Multi-Accel time 4] [Multi-Decel time 4] [Multi-Accel 0~ time 5] [Multi-Decel time 5] [Multi-Accel time 6] [Multi-Decel time 6] [Multi-Accel time 7] [Multi-Decel time 7] Output item Output to 10[V] 200V 400V Max frequency 150 % AC 282V DC 400V AC 564V DC 800V 100 30.00 0 ~ 400 [Hz] Used when I54 or I55 is set to 0-4. Cannot be set higher than F21. 0 1 2 3 0 ~ 19 4 5 6 7 8 9 [Multi-function relay select] FDT-1 FDT-2 FDT-3 FDT-4 FDT-5 Overload (OLt) Inverter Overload (IOLt) Motor stall (STALL) Over voltage trip (Ovt) Low voltage trip (Lvt) 17 O 10.00 12 O O O 0 O 6000 [sec] Min/Max range Description Factory defaults 4.0 5.0 5.0 6.0 6.0 7.0 7.0 8.0 8.0 9.0 9.0 Adj. during run

Input/output group
LED display I37 I38 I39 I40 I41 I42 I43 I44 I45 I46 I47

I50

A432

[Analog output item select]

0~3

0 1 2 3

Output freq. Output current Output voltage Inverter DC link voltage

I51 I52 I53

A433 A434 A435

[Analog output level adjustment] [Frequency detection level] [Frequency detection bandwidth] [Multi-function

10~200 [%]

Based on 10V.

I54

A436

output terminal select]

I55

A437

38

Compact & Powerful Inverter iG5A

Input/output group
LED display Address for communication Parameter name Min/Max range 10 11 12 13 I55 A437 [Multi-function relay select] 0 ~ 19 14 15 16 17 18 19 Command loss During Run During Stop During constant run During speed searching Wait time for run signal input Multi-function relay select Warning for cooling fan trip Brake signal select When setting the auto restart try] Bit 2 0 I56 A438 [Fault relay output] 0~7 1 2 3 4 5 6 7 Multi-function relay [Output terminal I57 A439 select when communication error occurs] 0~3 0 1 2 3 Set communication protocol. I59 I60 A43B A43C [Communication protocol select] [Inverter number] 1 ~ 250 0 ~1 0 1 Modbus RTU LS BUS 1 O 0 Bit 1 Multi-function output terminal Bit 0 0 O When the trip voltage trip occurs Bit 1 Bit 0 2 O When the low voltage trip occurs H26 - [Number of other than low 17 O Description Inverter Overheat (OHt) Factory defaults Adj. during run

Set for RS485 communication Select the Baud rate of the RS485. 0 1200 [bps] 2400 [bps] 4800 [bps] 9600 [bps] 19200 [bps]

I61

A43D

[Baud rate]

0~4

1 2 3 4

It is used when freq command is given via V1 /I terminal or [Drive mode I62 A43E select after loss of frequency command] 0~2 RS485. 0 1 2 Continuous operation at the frequency before its command is lost. Free Run stop (Output cut-off) Decel to stop 0 O

39

iG5A

Function List
Address for communication Parameter name [Wait time after Min/Max range Description This is the time inverter determines whether there is the input 0.1 ~ 120 frequency command or not. If there is no frequency command [sec] 2 ~ 100 [ms] input during this time, inverter starts operation via the mode selected at I62. Frame communication time When the protocol is set, the communication format can be set. 0 0~3 1 2 3 Parity: None, Stop Bit: 1 Parity: None, Stop Bit: 2 Parity: Even, Stop Bit: 1 Parity: Odd, Stop Bit: 1 5 6 7 The user can register up to 8 discontinuous addresses and read them all with one Read command. 8 O 9 10 11 12 5 6 7 The user can register up to 8 discontinuous addresses and write them all with one Write command 8 O 5 6 7 8 0~180 [%] Sets current level to open the brake. It is set according to H33s (motor rated current) size 50.0 O O O 5 O 1.0 O Factory defaults Adj. during run

Input/output group
LED display

I63

A43F

loss of frequency command] [Communication time setting] [Parity/stop bit setting] [Read address register 1] [Read address register 2] [Read address register 3] [Read address register 4] [Read address register 5] [Read address register 6] [Read address register 7] [Read address register 8] [Write address register 1] [Write address register 2] [Write address register 3] [Write address register 4] [Write address register 5] [Write address register 6] [Write address register 7] [Write address register 8] [Brake open current]

I64

A440

I65

A441

I66 I67 I68 I69 I70 I71 I72 I73 I74 I75 I76 I77 I78 I79 I80 I81 182 1)

A442 A443 A444 A445 A446 A447 A448 A449 A44A A44B A44C A44D A44E A44F A450 A451 A452

0~42239

0~42239

1)

1) It is indicated when choosing I54~I55 as a 19 (Brake signal).

40

Compact & Powerful Inverter iG5A

Input/output group
LED display 183 184 185 186 187 Address for communication A453 A454 A455 ` A456 A457 Parameter name [Brake open delay time] [Brake open FX frequency] [Brake open RX frequency] [Brake close delay time] [Brake close frequency Min/Max range 0~10 [s] 0~400 [Hz] 0~400 [Hz] 0~19 [s] 0~400 [Hz] Description Sets Brake open dely time. Sets FX frequency to open the brake Sets RX frequency to open the brake Sets delay time to close the brake Sets frequency to close the brake Factory defaults 1.00 1.00 1.00 1.00 2.00 Adj. during run

41

iG5A

Protective Functions
Protective functions Overcurrent Ground fault current Inverter Overload Overload trip Heat sink overheat Output Phase loss Over voltage Low voltage Electronic Thermal Input phase loss Self-diagnostic malfunction Parameter save error Inverter hardware fault Communication Error Remote keypad communication error Keypad error Cooling fan fault Instant cut off External fault A contact input External fault B contact input Operating method when the frequency command is lost Descriptions The inverter turns off its output when the output current of the inverter flows more than 200% of the inverter rated current. The inverter turns off its output when a ground fault occurs and the ground fault current is more than the internal setting value of the inverter. The inverter turns off its output when the output current of the inverter flows more than the rated level (150% for 1 minute). The inverter turns off its output if the output current of the inverter flows at 150% of the inverter rated current for more than the current limit time (1min). The inverter turns off its output if the heat sink overheats due to a damaged cooling fan or an alien substance in the cooling fan by detecting the temperature of the heat sink. The inverter turns off its output when the one or more of the output (U, V, W) phase is open. The inverter detects the output current to check the phase loss of the output. The inverter turns off its output if the DC voltage of the main circuit increases higher than 400V when the motor decelerates. This fault can also occur due to a surge voltage generated at the power supply system. The inverter turns off its output if the DC voltage is below 180V because insufficient torque or overheating of the motor can occur when the input voltage of the inverter drops. The internal electronic thermal of the inverter determines the overheating of the motor. If the motor is overloaded, the inverter turns off the output. The inverter cannot protect the motor when driving a motor having more than 4 poles or multi motors. Inverter output is blocked when one of R, S, T is open or the electrolytic capacitor needs to be replaced. Displayed when IGBT damage, output phase short, output phase ground fault or output phase open occurs. Displayed when user-setting parameters fails to be entered into memory. Displayed when an error occurs in the control circuitry of the inverter. Displayed when the inverter cannot communicate with the keypad. Displayed when the inverter and the remote keypad do not communicate with each other. It does not stop inverter operation. Displayed after the inverter resets the keypad when a keypad error occurs and this .... Displayed when a fault condition occurs in the inverter cooling fan. Used for the emergency stop of the inverter. The inverter instantly turns off the output when the EST terminal is turned on. Caution: The inverter starts to regular operation when turning off the EST terminal while FX or RX terminal is ON. When multi-function input terminal (I20-I24) is set to 19 {External fault signal input A: (Normal Open Contact)}, the inverter turns off the output. When multi-function input terminal (I20-I24) is set to 19 {External fault signal input B: (Normal Close Contact)}, the inverter turns off the output. When inverter operation is set via analog input (0-10V or 0-20mA input) or option (RS-485) and no signal is applied, operation is done according to the method set in I62 (Operating method when the frequency reference is lost).

Keypad display

42

Compact & Powerful Inverter iG5A

Fault Remedy
Keypad display Cause Remedy Caution: When an overcurrent fault occurs, operation must be started after the cause is removed to avoid damage to IGBT inside the inverter. Overcurrent Accel/Decel time is too short compared to the GD2 of the load. Load is greater than the inverter rating. Inverter output is issued when the motor is free running. Output short circuit or ground fault has occurred. Mechanical brake of the motor is operating too fast. Ground fault has occurred at the output wiring of the inverter. The insulation of the motor is damaged due to heat. Load is greater than the inverter rating. Torque boost scale is set too large. Cooling system has faults. An old cooling fan is not replaced with a new one. Ambient temperature is too high. Faulty contact of magnetic switch at output. Faulty output wiring. An alien substance is clogged in a ventilating slot. Inverter has been in use without changing a cooling fan. Decel time is too short compared to the GD2 of the load. Regenerative load is at the inverter output. Line voltage is too high. Line voltage is low. Load larger than line capacity is connected to line (ex: welding machine, motor with high starting current connected to the commercial line). Faulty magnetic switch at the input side of the inverter. Motor has overheated. Load is greater than inverter rating. ETH level is set too low. Inverter capacity is incorrectly selected. Inverter has been operated at low speed for too long. External fault A contact input External fault B contact input Operating method when the frequency command is lost Remote keypad communication error The terminal set to 18 (External fault- A) or 19 (External fault-B) I20-I24 in I/O group is ON. in Increase the Accel/Decel time. Replace the inverter with appropriate capacity. Resume operation after stopping the motor or use H22 (Speed search). Check output wiring. Check the mechanical brake. Check the wiring of the output terminal. Replace the motor. Upgrade the capacity of motor and inverter or reduce the load weight. Reduce torque boost scale. Check for alien substances clogged in the heat sink. Replace the old cooling fan with a new one. Keep ambient temperature under 50 C. Make connection of magnetic switch at output of the inverter securely. Check output wiring. Check the ventilating slot and remove the clogged substances. Replace the cooling fan. Increase the Decel time. Use Dynamic Brake Unit. Check whether line voltage exceeds its rating. Check whether line voltage is below its rating. Check the incoming AC line. Adjust the line capacity corresponding to the load. Change a magnetic switch. Reduce load weight and operating duty. Change inverter with higher capacity. Adjust ETH level to an appropriate level. Select correct inverter capacity. Install a cooling fan with a separate power supply.

Ground fault current Inverter overload Overload trip Heat sink overheat

Output Phase loss Cooling fan fault

Over voltage

Low voltage

Electronic thermal

Eliminate the cause of fault at circuit connected to external fault terminal or cause of external fault input. Check the wiring of V1 and I and frequency reference level. Check for connection of communication line and connector.

No frequency command is applied to V1 and I. Communication error between inverter keypad and remote keypad. - EEP: Parameter save error - HWT: Hardware fault - Err: Communication Error - COM: Keypad error

Contact your LSIS sales distributor.

43

For your safety, please read user's manual thoroughly before operating. Contact the nearest authorized service facility for examination, repair, or adjustment. Please contact a qualified service technician when you need maintenance. Do not disassemble or repair by yourself!

Safety Instructions

Any maintenance and inspection shall be performed by the personnel having expertise concerned.

2005.5 LSIS Co.,Ltd. All rights reserved.

www.lsis.biz

HEAD OFFICE

LS Tower, 127, LS-ro, Hogye-dong, Dongan-gu, Anyang-si, Gyeonggi-do 431-848, Korea


+82-2-2034-4901 / bonseongk@lsis.biz +82-2-2034-4620 / mswoo@lsis.biz

Global Network LSIS (Middle East) FZE Dalian LSIS Co., Ltd.

Address: LOB 19 JAFZA VIEW TOWER Room 205, Jebel Ali Freezone P.O. Box 114216, Dubai, United Arab Emirates Tel: 971-4-886 5360 Fax: 971-4-886-5361 e-mail: jungyongl@lsis.biz Address: No.15, Liaohexi 3-Road, Economic and Technical Development zone, Dalian 116600, China Tel: 86-411-8273-7777 Fax: 86-411-8730-7560 e-mail: lixk@lsis.com.cn Address: 102-A , National High & New Tech Industrial Development Area, Wuxi, Jiangsu, 214028, P.R.China Tel: 86-510-8534-6666 Fax: 86-510-522-4078 e-mail: xuhg@lsis.com.cn Address: Nguyen Khe - Dong Anh - Ha Noi - Viet Nam Tel: 84-4-882-0222 Fax: 84-4-882-0220 e-mail: srjo@lsisvina.com Address: 41 Nguyen Thi Minh Khai Str. Yoco Bldg 4th Floor, Hochiminh City, Vietnam Tel: 84-8-3822-7941 Fax: 84-8-3822-7942 e-mail: sbpark@lsisvina.com Address : 16th, Higashi-Kan, Akasaka Twin Tower, 2-17-22, Akasaka, Minato-ku, Tokyo, Japan Tel: 81-3-3582-9128 Fax: 81-3-3582-2667 e-mail: jschuna@lsis.biz Address: Room E-G, 12th Floor Huamin Empire Plaza, No.726, West Yan'an Road Shanghai 200050, P.R. China Tel: 86-21-5237-9977 (609) Fax: 89-21-5237-7191 e-mail: jinhk@lsis.com.cn

Dubai, U.A.E.

Dalian, China Wuxi, China

EMEA Asia Pacific

LSIS (Wuxi) Co., Ltd. LSIS-VINA Co., Ltd. LSIS-VINA Co., Ltd. LSIS Tokyo Office

Hanoi, Vietnam

Hochiminh , Vietnam

Tokyo, Japan

LSIS Shanghai Office

Shanghai, China

LSIS Beijing Office Beijing, China Address: B-Tower 17FL.Beijing Global Trade Center B/D. No.36, BeiSanHuanDong-Lu, DongCheng-District,
Beijing 100013, P.R. China Tel: 86-10-5825-6025,7 Fax: 86-10-5825-6026 e-mail: cuixiaorong@lsis.com.cn

LSIS Guangzhou Office LSIS Chengdu Office LSIS Qingdao Office

Address: Room 1403,14F,New Poly Tower,2 Zhongshan Liu Road,Guangzhou, P.R. China Tel: 86-20-8326-6764 Fax: 86-20-8326-6287 e-mail: linsz@lsis.biz Address: Room 1701 17Floor, huanminhanjun internationnal Building, No1 Fuxing Road Chengdu, 610041, P.R. China Tel: 86-28-8670-3101 Fax: 86-28-8670-3203 e-mail: yangcf@lsis.com.cn Address: 7B40,Haixin Guangchang Shenye Building B, No.9, Shandong Road Qingdao 26600, P.R. China Tel: 86-532-8501-6568 Fax: 86-532-583-3793 e-mail: lirj@lsis.com.cn

Guangzhou, China

Chengdu, China

Specifications in this catalog are subject to change without notice due to continuous product development and improvement.

Qingdao, China

2012. 01

STARVERT iG5A(E)2005.05/(14)2012.01 Printed in Korea Pacomkorea