July 2009
x AMI Head-End application software and related services (the City will provide
the hardware, operating system, and database software); the application software
will need to immediately be able to support the numbers of meters, devices, etc.
as identified in RFP Section 6.1.0
x Network that would initially provide the ability to connect to various IP-based
endpoints including 5,170 electric meters and 528 water meters (these numbers
include replacing specific electric meters currently connected via telephone to
MV-90 and the water meters associated with those customer accounts; the totals
also include ); the network will need to be capable of expanding to support the
numbers of meters, devices, etc. as identified in RFP Section 6.1.0
x Meters, including the 5,170 electric meters identified above, plus 14 spares (5,184
total) and the 528 water meters as identified above, plus 12 spares (540 total) –
please see RFP Section 6.1.0 for specific types and quantities
x Project Plan and Project Schedule
x AMI Solution Implementation – Phase 1 estimated at one (1) year, including:
x Implementation Plan
x System and network documentation
x System and network installation
x Lab Proof of Concept – to include set up and testing of electric and water
meters under various scripts to test end-to-end functionality on all specified
head-end system, communication system and meter-based functions.
x Field Proof of Concept – to include 500 electric meters (30 of which would be
industrial meters) and 50 water meters (the type and location of these to be
identified by the City); this shall include testing from end-to-end on all
specified Head-End System (HES), communication system and meter-based
functions
x Final Roll-out of the remaining electric meters (4,770) and water meters (478)
The City’s goal is to select a comprehensive solution that will enable Santa Clara to meet
the business needs of both their internal and external customers (City employees and
citizens).
The City is currently organized into 15 departments consisting of the City Manager’s
Office, City Clerk, City Attorney, Information Technology, Human Resources, Finance,
Police, Fire, Electric Utility (Silicon Valley Power), Water and Sewer Utilities, Public
Works and Engineering, Street Maintenance and Automotive Services, Parks and
Recreation, Planning and Inspection, and Library. The City departments are described at
www.santaclaraca.gov.
This RFP is sponsored by the City’s municipal electric utility - Silicon Valley Power
(SVP). The name Silicon Valley Power came into being in March 1998. The name
change was in recognition of the vital role the utility plays in serving a growing
community, as well as powering some of the world's largest high-tech, bio-tech, and info-
tech companies, and has a vibrant start-up community.
Other City project stakeholders and their roles associated with this procurement are as
follows:
1. Customer Service - customers call Customer Service to start or stop service,
report service issues, make billing inquiries, make payments, obtain bill payment
information, make general inquiries, make complaints, and check on account
status.
2. Finance and Billing - manages, administers, and maintains on-line computerized
systems for Utility Billing (the Harris Public Utility Billing System (PUBS);
generates monthly utility bills for all City of Santa Clara residential, commercial,
and industrial customers; and investigates researches, prepares findings, and
works with customers to resolve their concerns, complaints, and/or suggestions.
3. Electric Metering - manages field and office personnel who provide customer
assistance regarding utilities (electric, water, sewer, refuse, etc.); support meter
reading and utility field services.
Joe Blackwell
AMI Project Coordinator
City of Santa Clara
Silicon Valley Power
1601 Civic Center Drive
Santa Clara, CA 95050
Email: jblackwell@santaclaraca.gov
In addition, the City will make additional project related documents available via a
Responder’s Library. Access to this library will be provided only to those Responder’s
who submit a Registered Responder Information/Intent to Bid Form and a Confidentiality
Statement. Once the Key Contact identified in Section 1.4 above receives these
documents, the City will email each Responder a user ID, Responders Library website
address, and a telephone number to call to receive a password. Once each Responder has
a user ID and password, they will be able to access the Responder’s Library website.
Responders will be notified of any additions to the public site or Responder’s Library via
an email notification.
Activity Date
Issue RFP 7/21/09
Registered Responder Information/Intent to Bid 8/7/09 (5:00 p.m. PT)
Form and Confidentiality Statement Due
Responder’s Conference 8/19/09 (1:00 p.m. PT)
Deadline for Final Responder Questions to the City 8/28/09 (5:00 p.m. PT)
City’s Responses to Responder Questions Sent 9/4/09
Proposals Due 9/24/09 (5:00 p.m. PT)
Contract Execution (targeted) 12/1/09
All Key Action Dates are subject to change. The City will notify registered Responders
of any changes in the Key Action Dates via RFP addenda.
x Enter into an agreement with another Responder in the event the originally
selected Responder defaults or fails to execute an agreement with the City
An agreement shall not be binding or valid with the City unless and until it is reviewed
and approved by the City Attorney’s Office, approved by the City Council, if so required,
and executed by authorized representatives of the City and of the Responder.
The City shall not be responsible for nor be bound by any oral instructions,
interpretations or explanations issued by the City or its representatives. Questions
received after the date and time stated above will not be accepted.
A Responder who desires clarification or further information on the content of the RFP,
but whose questions relate to the proprietary aspect of that Responder’s proposal and
which, if disclosed to other Responders, would expose that Responder’s proposal, may
mark such questions “CONFIDENTIAL” and submit them in the same manner as above
no later than the scheduled date specified in Section 1.8 to ensure a response. The
Responder must explain why such questions are sensitive in nature. If the City concurs
that the disclosure of the question or answer would expose the proprietary nature of the
proposal, the question will be answered and both the question and answer will be kept in
confidence. If the City does not concur with the proprietary aspect of the question, the
question will not be answered in this manner and the Responder will be so notified.
While Responders will be able to ask questions at the conference, the City encourages
responders to submit their questions (which must be done in accordance with RFP
Section 2.1) prior to the conference. For any questions submitted prior to the conference,
the City will develop written answers and make every attempt to have them available at
the conference. The Q&A’s will be assembled so as to not divulge the source of the
query.
The City may modify the RFP prior to the date that proposals are due by issuance of an
addendum (or addenda). Addenda will be numbered consecutively. Responders will be
given the opportunity to ask questions pertaining specifically to each addendum by
following the question submission process detailed in RFP Section 2.1, but must do so
within five (5) working days of the release of the addendum.
2.5 Subcontractors
Responders may utilize Subcontractors as part of their solution. If Responders plan to
utilize Subcontractors, Responders must identify the Subcontractors and summarize their
In no event shall the City of Santa Clara, or any of its agents, representatives, consultants,
directors, officers or employees be liable to a Responder or Responder’s team member
for the disclosure of all or a portion of a Respondent’s proposal submitted under this
RFP.
Responses to this RFP become the exclusive property of the City. At such time the City
recommends a Responder to the City Council, all proposals received in response to this
RFP become a matter of public record and shall be regarded as public records, with the
exception of those elements in each proposal which are defined by the Responder as
business or trade secrets and plainly marked as "Confidential," “Trade Secret," or
"Proprietary."
The City shall not in any way be liable or responsible for the disclosure of any such
proposal or portions thereof, if they are not plainly marked as "Confidential," Trade
Secret," or "Proprietary" or if disclosure is required under the Public Records Act. Any
proposal which contains language purporting to render all or significant portions of the
proposal "Confidential," "Trade Secret," or "Proprietary," may be regarded as
nonresponsive.
Although the California Public Records Act recognizes that certain confidential trade
secret information may be protected from disclosure, the City of Santa Clara may not be
in a position to establish that the information a Responder submits is a trade secret. If the
City of Santa Clara receives a request for public disclosure of all or any portion of a
Responder’s proposal that the submitting firm has designated as a trade secret,
proprietary information, or other confidential information exempted from disclosure, the
City of Santa Clara will use reasonable efforts to notify the applicable Responder of the
request and give such respondent an opportunity to assert, in writing and at its sole
expense, a claimed exception under the California Public Records Act or other applicable
law within the time period specified in the notice issued by the City of Santa Clara and
allowed under the California Public Records Act.
All policies, endorsements, certificates and/or binders shall be subject to the approval of
the City of Santa Clara as to form and content. The selected Responder agrees to provide
the City with a copy of said policies, certificates and/or endorsement upon award of
contract through the City’s insurance database.
2.9 Collusion
By submitting a proposal, each Responder represents and warrants that its proposal is
genuine and made in the interest of or on behalf of any person not named therein, that the
Responder has not directly induced or solicited any other person to submit a sham
proposal or any other person to refrain from submitting a proposal, and that the
Responder has not in any manner sought collusion to secure any improper advantage over
any other person submitting a proposal.
The City reserves the right to accept or reject any proposal. The City also reserves the
right to waive any minor informality or irregularity in any proposal.
x Any of the RFP forms are left blank or are materially altered; or
x Any document or item necessary to the proposal is incomplete, improperly
executed, indefinite, ambiguous, or is missing.
Additionally, factors such as, but not limited to the following may also disqualify a
Responder without further consideration:
2.12 Gratuities
No person shall offer, give or agree to give any City employee any gratuity, discount or
offer of employment in connection with the award of contract by the City. No City
employee shall solicit, demand, accept or agree to accept from any other person a
gratuity, discount or offer of employment in connection with a City contract.
x The consultant or other entity who works on the procurement will be precluded
from submitting proposals or bids as a prime Responder or Subcontractor.
x The consultant or any other entity who participated in the procurement shall not
have a financial, ownership or other interest in any potential Responder.
2.15 Pricing
Responders must submit pricing according to: 1) the instructions in RFP Section 8.0; 2)
the format identified in RFP Section 9.3; and 3) within the sheets provided in Attachment
D – Price Worksheets.
NOTE: The total of the Implementation Phase plus the Operations and Maintenance
Phase will constitute a “not-to-exceed” price. Please note that the City’s goal is to
provide the best service possible and that cost will be only one of the factors considered
in the evaluation of the proposals.
Proposals may not be altered or enhanced during the demonstration. The City reserves
the right to determine whether or not a demonstration has been successfully passed.
3.1 Overview
SVP’s electric utility infrastructure consists of 450 circuit miles of a 12kV radial
distribution system. The system is 60% underground and 40% overhead, and includes a
number of customer distribution transformers. There are 24 substations and
approximately 10,000 utility poles and 8,000 street light poles in the City of Santa Clara.
Although the majority of poles are owned and maintained by the City, some are jointly
owned by the county or other carriers.
Today, there are 51,000 electric and 27,000 water meters located in the City. Most
residential and commercial electric meters are read via a walk-by process involving the
monthly visitation and inspection of every meter to obtain consumption data.
Approximately 6,000 of the 51,000 electric meters and 200 of the 27,000 water meters
are radio-based residential meters.
The City’s Municipal Services Department is responsible for all utility billing. Municipal
Services employs a staff of meter readers to conduct the walk-by meter reading process.
Once collected, the readings are entered in the Harris Public Utility Billing System
(PUBS) and invoices are generated from the consumption data based upon a council
approved rate structure. Currently, customer invoice services are outsourced to Regulus
Group, LLC and cash receipts processing is outsourced to San Jose Water Company.
The maps on the following pages illustrate the electric and water meters (by density) that
are included in this project. Additionally, the maps illustrate SVP’s total service area.
GREAT
ND
S MA
TA
LA
FA
YE
TTE
ST
PY
EX
UE
AG
NT
MO
MISSION CO
LLEGE BL
VD
US
HW
Y1
01
RD
E
BOWERS AVE
BL
IM
TR
CENTRAL EXPY
SCOTT BLVD
MONROE ST
DE LA CRUZ BLVD
SAN TOMAS EXPY
EL CAMINO REAL
LAWRENCE
EXPY
BENTON ST
T
OY AVE
TS
KE
KIELY BLVD
LAWRENCE EXPY
R
MA ST
M Y
LO
POMER
B EL
PA
R
WA
K
A
S
HIN
GT
ON
ST
HOMESTEAD RD
VI
IN
TA
UN
MO
LA
FA
YE
TTE
ST
Y
XP
U EE
AG
NT
MO
MISSION CO
LLEGE BL
VD
US
H WY
101
RD
E
BOWERS AVE
BL
IM
TR
CENTRAL EXPY
SCOTT BLVD
MONROE ST
DE LA CRUZ BLVD
SAN TOMAS EXPY
EL CAMINO REAL
LAWRENCE
EXPY
BENTON ST
ST
OY AVE
ET
KIELY BLVD
LAWRENCE EXPY
RK
MA ST
MY
LLO
POMER
BE
PA
RK
WA
AV
SH
E
IN
GT
ON
ST
HOMESTEAD RD
3.2 Existing Technical Architecture
The following diagram illustrates what the meter reading and billing process will look
like after the implementation of the Meter Data Management System (MDMS), which is
scheduled to begin on 9/1/09 and be completed by 6/1/10. Following the diagram, we
define all the components within it.
Public Switched
Telephone Network
(PSTN) Lines
Itron MV-90
Data Collector
Database
Itron
MV-RS Finance
Data Department Harris
Collector PUBS
Itron MV-RS
Handhelds City Data Center
Water
Meters Electric Meters
Of the 51,000 electric meters, approximately 300 industrial meters are capable of being
read via remote, telephony-based interrogation systems for interval consumption and
demand measurement. Approximately 6,000 residential meters are capable of short-
distance, walk-by radio-based interrogation for consumption measurement.
Water Meters
All of the existing 27,000 water meters are read manually, with the exception of
approximately 200 radio walk-by enabled meters. The MDMS will support water meter
reads, associated data, and provisioning.
Large industrial electric meters are connected to the MV-90 Data Collector through
Public Switched Telephone Network (PSTN) Lines. Initially, the MDMS will interface
with the Itron MV-90 Data Collector. When the AMI Solution is fully deployed
throughout the entire city, a communications platform will replace the Itron MV-90 Data
Collector. That platform will allow the MDMS to poll the large industrial electric meters
directly.
The Itron MV-RS Data Collector is a Windows-based system housed in the City’s
Finance Department. The MV-RS application provides an interface to the MV-RS
handhelds and administers meter reading routes and the collection of daily meter reads
for electric and water accounts. The MV-RS Data Collector communicates with the MV-
RS handhelds when the units are inserted in cradles connected to the data collector. The
MV-RS Data Collector interfaces with the Harris Public Utility Billing System (PUBS)
via a custom, file transfer interface that delivers meter reading route detail and daily
meter reads which the PUBS uses to generate customer invoices. The existing data from
the MV-RS data collector will be migrated to the MDMS. After full MDMS
implementation, the MV-RS Data Collector will continue to operate to support the use of
the Itron MV-RS Handhelds. The City anticipates that the MV-RS Data Collector and
the MV-RS Handhelds will be retired upon roll-out of the complete AMI solution.
The Itron MV-RS Handhelds are carried by the meter reading staff employed by the City
and are used to collect all water and electric meter reads. The MV-RS handhelds are
equipped to automatically read electric and water meters that utilize radio transmitters
known as ERT’s. Additionally, the MV-RS handhelds can accept meter reads that are
manually input by the meter reading staff based upon visual inspection of the meters.
The MV-RS handhelds communicate with the MV-RS Data Collector when the units are
inserted into cradle devices connected to the data collector. Once inserted into the
cradles, the meter reads, whether manually or automatically collected, are uploaded to the
MV-RS Data Collector and meter reading route information is downloaded for
The MDMS (eMeter’s EnergyIP) will collect and store meter data. The MDMS will act
as the core part of the system and will be the central repository for all meter related data.
Interfaces to other systems should be based upon open standards and common data
models. The MDMS will be housed in the SVP Data Center.
MDMS Database
The MDMS Database (Oracle) will process, archive and reroute large volumes of
operational data. This database will manage the large number of meter event data and
play a significant role in supporting metering reports, customer service activities, and
outage management. The MDMS Database will also be used by analytical applications,
data mining, decision support, and other user queries. The MDMS Database will be
housed in the SVP Data Center.
The MDMS Test and Control Workstation will be housed in the SVP Data Center. This
workstation will be provided by SVP.
Harris PUBS
The Harris PUBS is located within the City’s Data Center. The PUBS interfaces with the
Itron MV-90 via a CMEP interface, and with the Itron MV-RS, located in the City’s
Finance Department via a custom interface. The Finance Department’s Municipal
Services Division Customer Service staff is responsible for handling all utility billing.
Staff deal with customer calls either directly, by phone, or through a web portal.
Customer Service is responsible for adding new customers; adding, changing, or
terminating services; handle billing inquiries; and troubleshooting problems (i.e. no
power). Customer Service must be able to perform a number of functions including
obtain instantaneous meter reads, access Customer usage profile, usage by time-of-day,
season, identify what causes high bill, enter customer preference for meter read/bill due
date flexibility, request remote meter connect/disconnect, perform meter health checks,
and check for unauthorized usage.
SVP has fiber backbone deployed throughout its service territory. It connects all
substations with operation centers. Currently, 28 substations serving 106 distribution
feeders are connected with two additional substations in design. There are 144 fibers in
each fiber ring. Traffic is provisioned over an OC-3 fiber ring currently, but it is being
upgraded to OC-48. SVP has deployed the GE JungleMux Ethernet over fiber to support
SCADA data. Currently SVP keeps track of how much fiber is lit, and leases out dark
fiber to companies located in Santa Clara. Bandwidth utilization is estimated by
application demand. The GE JungleMux does not support traffic management.
SVP will make the document “SVP Fiber Optic Backbone Route” available via a
Responder’s Library for those Responders who submit Appendix A1 - Registered
Responder Information/Intent to Bid Form and Appendix A2 – Confidentiality Statement.
In August of 2008, Silicon Valley Power (SVP) purchased a privately held wireless
network. The network is in service today and SVP continues to make ongoing
performance improvements to the network resulting in a high quality, consistent
performing and highly available Metro Wi-Fi network. In the remainder of this section,
we provide additional information pertaining to this network.
3.3.2.3 Coverage
x The network covers 7.4 square miles of the 18.3 square miles in Santa Clara, which is
approximately 40% of the city.
x The network is estimated to cover 30,000 of the 43,000 residential meters (70%),
3,000 of the 6,000 commercial meters, (60%) and 25 of the 1,800 industrial meters
(1%) in Santa Clara.
SVP will make the documents “Metro Wi-Fi Density Map” and “Metro Wi-fi Access
Point Data Sheet” available via a Responder’s Library for those Responders who
submit Appendix A1 - Registered Responder Information/Intent to Bid Form and
Appendix A2 – Confidentiality Statement.
Outage
Management System
Public Switched
Telephone Network
(PSTN) Lines Work Management
System
Enterprise
Service
Itron MV-90 Bus Asset Management
Data Collector System
PI Historian
Itron
MV-RS Finance
Data Department Harris
Collector PUBS
Itron MV-RS
Handhelds City Data Center
= Internal SVP
Systems
Water
Meters Electric Meters
The Enterprise Service Bus will provide an open network messaging approach that uses a
common method to expose sources of information across many applications. Data
requestors and users will access data using the same method, and this will prevent the
need to build customized point-to-point interfaces whenever an application is
changed/added. The Enterprise Service Bus will be housed in the SVP Data Center.
x GIS - Currently, the City utilizes GIS (ESRI) capabilities within several
departments. At present, these interests are not coordinated and no central GIS
facility exists. SVP recognizes the value of GIS in leveraging the benefits of an
AMI/UCI infrastructure for benefits such as outage management and asset
control. The likelihood of a coordinated GIS initiative to fully realize these
benefits for Santa Clara is uncertain, but must be supported in the future.
x PI Historian - The OSISoft PI Historian is a utility data storage application that
provides SVP with access to real-time or historical role-based data.
Fan
Collector
(Radio- Mobile Workforce
Based)
SVP
Data
Center
AMI Head-End
Backhaul System
or Wide (HES)
Area
Network
(WAN)
Home Area
Network (HAN)
Future Network
In the AMI Solution, the electric meters will be enabled to serve as a premise gateway
between the utility, customer site, and customer’s load controllers over a Home Area
Network (HAN) – note that the HAN is part of the future solution. In addition, the 300
MV-90 meters will be replaced.
Water Meters
The solution will need to support water meter reads, associated data, and provisioning.
Any water meters associated with the 300 MV-90 electric meter accounts will be
replaced as part of this solution.
The distribution meters, grid sensors, and controllers will be placed on feeders, circuits,
and branches to gather real-time operational data and the health and performance of the
distribution circuits. For advanced distribution automation activities, these devices can
act as capacitor bank controllers, voltage regulators, and/or remote circuit switches.
FAN Controller
The FAN Controller (radio-based collectors) will manage communications over the FAN
to the electric meters; distribution meters, grid sensors, and controllers; and eventually to
the HAN. Each collector will support a portion of the utility service territory, and as
such, multiple collectors will be required to communicate to all field devices across the
entire utility service territory.
The Backhaul or WAN will provide data connectivity across the utility service area. This
network must provide adequate bandwidth to support all existing and forecasted devices,
employ redundancy, and have a very high availability. Today, there is a significant
amount of existing fiber optic communications infrastructure interconnecting SVP
distribution facilities within the City. As mentioned in RFP Section 3.3, the Backhaul
Network may make use of the City’s existing core network, which includes fiber optic
and Wi-Fi components.
These may be any form of wireless, IP-based device used by the general public or City
staff to perform a variety of value added functions. Examples include mobile computers,
mobile communication devices, and personal digital assistants.
The mobile workforce is expected to encompass City employees working in the field
performing a variety of functions. Their activities can be coordinated via applications
and tools that communicate over a broadband wireless network.
A PHEV is a hybrid electric vehicle with batteries that can be recharged by attaching to a
power service.
The AMI Head-End System (HES) will manage the communications, operations, and
diagnostic monitoring of the electric meters and field devices. The HES will perform
load balancing on the communications network resulting from scheduled meter reads,
support meter read retries when communications fail, and provide clients with meter
diagnostic information.
The future HAN will include the utility-owned premise gateway, as well as customer-
owned and operated devices and systems that broker messaging between the customer's
HAN-attached devices and the utility's premise gateway. HANs can be either wire or
wireless-based. Devices may include in-home displays (IHDs), PCs with a HAN
interface, thermostats, pool pumps, building automation systems, customer energy
management systems (EMS), sub-meters, field tools, etc.
Water
Meters Work Management
Plug-In Hybrid System
Enterprise
Electric Vehicle
Service
(PHEV) Asset Management
Bus
System
Fan
SVP Data Center Test & Control
Collector
Workstation GIS
(Radio-
Based) Meter Data
Mobile Management System
Workforce (MDMS)
Firewall
PI Historian
AMI Head-End
Backhaul System Database Other Existing Systems
or Wide (HES)
Area
Network
(WAN) Itron
MV-RS Finance
Other IP- Data Department Harris
Electric Collector
Based PUBS
Meters
Devices
Itron MV-RS
Home Area Handhelds City Data Center
Network (HAN)
= Internal SVP
Systems
Water
Meters Electric Meters
Future Network
Overall, it is the desire of the City to procure products and services which help minimize
the environmental impact resulting from the use and disposal of these products. This
includes products that can be recycled, as well as those that can be disposed of as non-
hazardous waste. Such products, referred to as "Environmentally Preferable Products"
(EPPs), include, but are not limited to, those that contain post-consumer recycled content,
Responders are required to meet or exceed all local, State, and Federal requirements and
guidelines for recycling and disposing of electric and water meters, and related packaging
materials, including those requirements identified by the:
x California EPA - The California Environmental Protection Agency is charged
with developing, implementing and enforcing the state's environmental protection
laws that ensure clean air, clean water, clean soil, safe pesticides and waste
recycling and reduction.
x California Integrated Waste Management Board - The California Integrated
Waste Management Board's mandated responsibility is to reduce waste, promote
the management of all materials to their highest and best use, and protect public
health and safety and the environment. The Board promotes a Zero Waste
California in partnership with local government, industry, and the public. This
means managing about 93 million tons of waste generated each year by reducing
waste whenever possible, promoting the management of all materials to their
highest and best use, regulating the handling, processing and disposal of solid
waste, and protecting public health and safety and the environment.
The best way to keep electronic equipment (including metering equipment) out of
landfills is to design them with consideration for ease of recycling in mind. For example,
make certain components easily removable, avoid toxic paint, use bromine-free plastics,
mark any potentially hazardous components clearly, and publish disassembly information
for many products in order to maximize their ability to be disassembled and recycled.
5.1.1 Background
5.1.2 Experience
c.) Tax returns for the Responder are acceptable in lieu of audited, reviewed, or
certified financial statements or annual reports. If a 10-K is not provided by an
applicant other than an individual, there shall be a statement of ownership for
Responder’s business entity.
Responders must provide three (3) references for similar projects that have been
completed in the last five years. For each project, Responders must include a completed
Attachment E – Customer Reference Form.
The City may, at its discretion, contact any or all of the references provided.
5.2 Staffing
Responders must address all the staffing-related requirements in this section.
Additionally, if a Responder plans to utilize the services of one or more Subcontractors to
meet any of the RFP requirements, the Responder must provide responses to all the
staffing requirements identified in this section for each Subcontractor.
Key staff includes, but is not limited to a Project Manager and Technical Lead (for the
Implementation Phase), an Operations Manager for the Operations and Maintenance
Phase, and any other implementation and/or ongoing operations staff identified by the
Responder.
The job descriptions must identify the key staff member’s responsibilities and the
qualifications needed for one to fill the position.
The resumes must include a summary of the person’s experience (especially that which is
specific to this RFP), a chronological, detailed account of their experience, education
information, and identification of any certifications.
Responders must provide three (3) references for each key staff person proposed by using
Attachment F – Key Personnel Reference Form. The references provided for each
individual must be for projects of similar size and scope (or larger) to the AMI project.
In support of this project, Responders will be required to develop a detailed Project Plan
and Schedule. The Project Plan and Schedule must include the following sections:
x Project Plan
x General Project Information
x Stakeholder and Participant Information
As described in RFP Section 5.3.3.1, there are two phases to this project: Implementation
and Operations and Maintenance. Both the Project Plan and Schedule will primarily be
used for the Implementation Phase. However, Responders should plan to continue to
utilize (and therefore keep updated) the components relevant to the management of the
Operations and Maintenance Phase.
In response to the RFP requirements above, Responders shall provide a draft Project Plan
and a draft Project Schedule (the schedule must be in MS Project format). The schedule
must identify the relevant project phases, tasks, milestones, and deliverables (as defined
in the following section), with associated timeframes and resource assignments. In their
response, Responders must also identify the need for any specific information, materials,
and/or decisions necessary from the City.
NOTE: RFP Section 5.3.3 includes an extensive amount of information and project
related requirements. While these requirements are in the Administrative Requirements
section, there are a number of them that are more technical in nature, and as such, are to
be addressed in response to RFP Section 6.0. These items include deliverables that are
identified with an “*”.
The key project phases include Implementation, as well as Operations and Maintenance.
The City will pay Responders for both phases as discussed later in RFP Section 5.3.3.4.
For purposes of this RFP, “System” is the same as “Solution” which is defined to include
AMI Head-End application software, data, communications network, meters, and related
devices all integrated and functioning together, as well as the services provided to
perform as described in the RFP and resulting contract. AMI Head-End hardware and
operating system software, as well as database software, are not included as those items
will be provided by the City.
Please note that Responders will need to specify their required AMI Head-End hardware,
operating system software, and database software specifications in response to RFP
Section 6.0. As identified in RFP Section 6.3 – Mandatory Technical Requirements,
acceptable database software includes Oracle or SQL Server.
Phase 1 - Implementation
The Implementation Phase is expected to last approximately one (1) year. It consists of
Phase 1A – Foundation Tasks, Phase 1B - Lab Proof of Concept, Phase 1C – Field Proof
of Concept, and Phase 1D - Final Roll-out in which the remainder of the electric and
water meters will be rolled-out and tested.
The City provides additional information pertaining to the requirements of Phase 1 later
in this section and in RFP Sections 6.0, 6.1, 6.2, 6.3, and 6.4.
At the end of the Phase 1D - Final Roll-out, the system will need to operate successfully
(three months/billing cycles) before the Implementation Phase will be considered
complete.
The Operations and Maintenance Phase will last approximately two (2) years. We
provide additional information pertaining to the requirements of Phase 2 later in this
section and in RFP Section 6.5.
Implementation Phase
x Begin Implementation
x Begin Solution Component Installation (includes):
Implementation Phase
Deliverable Set 1
x Project Plan (updated – first draft is due with proposal response) – must
include the following high-level documents:
x Risk Management Plan
x Communication Management Plan
x Issue Tracking Plan
x Change Control Plan
x Quality Management Plan
x Problem Resolution Plan
x Project Schedule (updated – first draft is due with proposal response)
Deliverable Set 2
x Technical Architecture Diagram (updated – first draft is due with proposal
response – see RFP Section 6.0)*
x Network Architecture Diagram (updated – first draft is due with proposal
response – see RFP Section 6.0)*
x Data Flow Diagram (updated – first draft is due with proposal response – see
RFP Section 6.0)*
x Application and Third Party Software List (updated – first draft is due with
proposal response – see RFP Section 6.0)*
x Implementation Plan (updated – first draft is due with proposal response)
x Meter Installation Plan (must include installation process for electric and
water meters, and list of meters to be replaced)*
x Electric and Water Meter Recycling Plan (updated – first draft is due with
proposal response)
x The Electric and Water Meter Recycling Plan shall meet all state and
federal requirements (please see RFP Section 4.3 for more information)
Deliverable Set 3
x User/Training Documentation (including Training Manual, Training
Materials, Help Guide, etc.)
x Training Plan (updated - first draft is due with proposal response)
x Test Plan (updated - first draft is due with proposal response)
x System Turnover/Transition Plan (updated - first draft is due with proposal
response )
All of the key phases, milestones, and deliverables are required. Regarding the
Implementation Phase, progress payments will be tied to the deliverables and milestones.
As part of their offer, Responders must provide a comprehensive system warranty (less
hardware) for the first three (3) months of the Operations Phase. Regarding the
Operations and Maintenance Phase, Responders will bill the City on a quarterly basis.
The following table illustrates how the project phases, milestones, deliverables, and
payments will be tied together.
All dates identified in the table are estimates and are subject to change. Responders may
add any additional milestones and/or deliverables they believe are necessary for
successful project completion. All project phases, milestones, and/or deliverables, and
related payments and dates agreed upon by the City and Responders will be reflected in
the final contract.
In response to the RFP Section 5.3.3, Responders shall provide the following:
a. Project Plan
b. Project Schedule
c. Implementation Plan
e. Training Plan
f. Test Plan
In response to the RFP, Responders must acknowledge and state their compliance with
the information in this section. The City will accept the system as fully implemented
when the following criteria have been met (this criteria will be finalized and jointly
agreed to during contract negotiations):
x The City will assign resources to work with the Responder. This will include
project management related resources, testing resources, and documentation
review resources.
x The City will provide workspace for two (2) individuals, including telephone and
VPN connection for Responder personnel working on-site. The provision of these
items shall not change or alter, in any way, the status of Responder personnel as
independent contractors, not employees, of the City. The VPN Policy is provided
in RFP Attachment J.
x The City will provide all AMI Head-End hardware and operating system
software. This hardware and software is for AMI project use only, and will
remain property of the City and SVP, and will be used according to City
information technology use policy.
x The City will provide all required source data and related materials. However, the
City will maintain ownership of this data and materials.
x The City will provide all required information pertaining to interfaces including
the Harris PUBS and MDMS data structures and process flows.
x The City will provide formal acceptance of each DED in writing when complete.
x The City will provide formal acceptance of each deliverable in writing when
complete.
For purposes of this RFP, “System” equals “Solution,” which is defined to include AMI
Head-End application software, data, communications network, meters, and related
devices all integrated and functioning together, as well as the services provided to
perform as described in the RFP and resulting contract. AMI Head-End hardware and
operating system software, as well as database software, are not included in this
definition, as those items will be provided by the City. Responders will need to specify
their required AMI Head-End hardware, operating system software, and database
software specifications in response to this section (see item #7 on the following page).
As identified in RFP Section 6.3 – Mandatory Technical Requirements, acceptable
database software includes Oracle or SQL Server.
Responders must meet and adhere to all of the System Requirements. Failure to
positively identify the Responder’s intention to fulfill these requirements may, at the
discretion of the City, result in a determination of material defect and result in
disqualification of the Responder’s response. These requirements are broken into three
areas: Functional Requirements (Mandatory and Optional/Future), Technical
Requirements (Mandatory and Optional/Future), and Operations and Maintenance
Requirements.
Please note that Responders are to provide estimated pricing for the Optional/Future
requirements, but are NOT to include these costs in their Implementation or Operations
and Maintenance costs. Please see RFP Section 8.0 for additional information pertaining
to pricing.
To address the System Requirements, Responders should repeat the headings from this
section in their proposal and then provide full written responses to the requirements under
each heading (the requirements pertaining to RFP Sections 6.1 6.2, 6.3, and 6.4 are
contained in Word tables). Regarding the repeated heading, Responders should number
their proposals according to the instructions in RFP Section 9.0 – Response Format,
Submission, and Delivery Instructions. Please do not attach company brochures in lieu
of providing written responses.
If a Responder plans to utilize the services of one or more Subcontractors to meet any of
the RFP System Requirements, Responders must identify any tasks and/or deliverables to
be completed by Subcontractors and describe their role in accordance with the
requirements.
Prior to addressing the System Requirements, Responder’s must address each of the
following requirements:
5) Provide a Data Flow Diagram (this should include identification of the data
elements the Head-End System will collect, and those that it expects it will
transmit to and receive from the eMeter EnergyIP MDMS)
8) Provide a discussion of how the software will be configured to meet the City’s
needs, without source code changes and how those configurations will be retained
through software version upgrades
9) The City intends to complete a full roll-out of the AMI network and associated
meters (see related device counts in RFP Section 6.0.1) by 2013. At the City’s
option, based on the success of the original implementation, we may choose to
amend the contract resulting from this RFP to include the full roll-out. As such,
Responders should describe how they would expand the AMI Solution to be
completed by 2013, including specific, scheduled checkpoints for new technology
assessment. Please also discuss other solution functions and/or approaches the
City might want to consider in the future.
Each requirement has an associated Requirement Type. The Requirement Types are
defined as follows:
FR = Functional Requirement
PR = Performance Requirement
NOTE: While there are PR requirements throughout the spreadsheet, there are also a
number of PR requirements that have been collected in Section 6.1.4.17. These PR
requirements will help form the basis of the Service Level Agreements (SLAs) to be
developed with the successful Responder as part of contract negotiations. For more
information on SLAs, please see Section 6.5.
6.1.1 Meters
6.1.1.1 Meters – Electric, General
6.1.1.1.1 Comply with applicable U.S. meter standard for induction and solid state watt-hour meters and FR
communication standards including:
1. ANSI C12.1-2001
2. ANSI C12.20 (Class 0.2) – 2002
3. ANSI/IEEE C37.90.1 - 2002
4. ANSI/IEEE 62.45 – 2002
5. ANSI C12.10 – 2004
6. ANSI C12.18 – 1996
7. ANSI C12.19 – 1997
8. ANSI C12.21
9. ANSI C12.22
10. IEC 61000-4-4 – 2004-07
11. IEC 61000-4-2 – 2001-04
12. IETF IPv4
13. Support for latest revision of above standards where applicable.
14. Comply with FCC regulations (provide documentation of compliance with proposal response)
15. FCC Part 15 Class B
16. FCC Part 15, sub-paragraph 247
6.1.4.10 Sub-metering
6.1.4.10.1 HES shall be capable of supporting Sub-Metering for up to ten (10) Sub-Meters via grouping of meter reads. FR
6.1.4.16.4 Confidentiality - Provide assurance that information is not disclosed to unauthorized persons, processes, or FR
devices.
6.1.4.16.5 Data Integrity - Provide assurance that data is unchanged from its source and has not been accidentally or FR
maliciously modified, altered, or destroyed.
6.3.0.2 Responders are to indicate their support/implementation plans for adopted NIST Interoperability Standards including: FR
Standard Application
AMI-SEC System Security Advanced metering infrastructure (AMI) and Smart
Requirements Grid end-to-end security
ANSI C12.19/MC1219 Revenue metering information model
BACnet ANSI ASHRAE 135- Building automation
2008/ISO 16484-5
DNP3 Substation and feeder device automation
IEC 60870-6 / TASE.2 Inter-control center communications
IEC 61850 Substation automation and protection
IEC 61968/61970 Application level energy management system
interfaces
IEC 62351 Parts 1-8 Information security for power system control
operations
IEEE C37.118 Phasor measurement unit (PMU) communications
IEEE 1547 Physical and electrical interconnections between
utility and distributed generation (DG)
IEEE 1686-2007 Security for intelligent electronic devices (IEDs)
NERC CIP 002-009 Cyber security standards for the bulk power system
NIST Special Publication (SP) Cyber security standards and guidelines for federal
800-53, NIST SP 800-82 information systems, including those for the bulk
power system
Open Automated Demand Price responsive and direct load control
Response (Open ADR)
OpenHAN Home Area Network device communication,
measurement, and control
ZigBee/HomePlug Smart Home Area Network (HAN) Device Communications
Energy Profile and Information Model
6.3.4 Database
6.3.4.1 Application software shall be compatible with Oracle or SQL Server. FR
6.3.7.3 Provide SVP with ad-hoc reports as needed (describe ability to do so and typical report types). FR
6.3.7.4 Allow SVP to configure the report recipient groups and send the system generated reports to predetermined email FR
addresses and predetermined storage file locations.
6.3.7.5 Allow SVP to set up or change the report deliveries without modifying source program code and without any FR
proprietary language skills.
6.3.7.6 Allow reports to be generated on demand and/or via a scheduled process. FR
6.3.7.7 Provide SVP operating personnel with performance and health reports on demand or via a scheduled process. FR
6.3.7.8 List all supported or provided industry standard reporting tools (i.e. Hyperion, Crystal, Cognos, Obvient, etc.). FR
6.3.7.9 Conduct analysis to identify assets, service points, and applications that have chronic or excessive problems, report FR
them, and support problem resolution efforts to address problems.
During the Operations and Maintenance Phase, the selected Responder must sustain the
services already implemented, and work to continuously improve and optimize those
services.
As mentioned in RFP Section 1.0, the first part of the City’s AMI procurement included a
Meter Data Management System (MDMS). As shown in the figure below, the
implementation and operation of that system is going to overlap with the implementation
and operation of the Head-End System (please note that the dates shown are estimates).
MDMS
MDMSOperations
Implementation
AMI
AMIOperations
Implementation
In the remainder of this section, the City identifies the Operations and Maintenance
requirements specific to this procurement. Please note that the City realizes that some of
these requirements, and the selected AMI Solution Responder tasks, may need to be
revised during contract negotiations. This is due to the fact that the MDMS operations
will have begun before the AMI Solution operations, and because the selected Responder
will need to work with both the City and the MDMS vendor (Siemens/eMeter) in
supporting project operations.
For the purposes of this RFP, Responders should keep the above in mind as they respond
to the following operations and maintenance requirements:
1) Software Licensing – describe the application software licenses and any third-
party software licenses required for the two (2) year Operations and Maintenance
period. Please also describe the licensing that would be applicable for such
software licenses over the following eight (8) years.
3) Support for Software Changes based on Operating System Patches – describe how
Responder will handle changes to application and any third-party software that
are necessary based on operating system patches; critical operating system
patches must be compatibility certified within 30 days of release and supported
thereafter.
4) System Operations – describe how Responder will operate the system (solution).
Responders will work with the City and the MDMS vendor to provide
comprehensive and collaborative system operations. Describe support to be
provided based on best practices regarding system operations support in a multi-
vendor environment, including lines of responsibility demarcation.
5) Network Operations – describe how Responder would operate and monitor the
network.
7) Help Desk Support – describe any Help Desk support that would be required over
the two (2) year Operations and Maintenance period. Include answers to the
following:
d. How is the Help Desk staffed? Are the various types (levels) or support
provided?
e. How are Help Desk tickets tracked? How are issues escalated?
h. Responders will work with the City and the MDMS vendor to provide
comprehensive and collaborative Help Desk support. Describe support to be
provided based on best practices regarding Help Desk operations support in a
multi-vendor environment, including lines of responsibility demarcation.
9) Replacement and Installation of Faulty Meters – Provide meter failure rate and
describe how Responder will work with the City to identify and replace failed
meters.
10) Service Level Agreements – in RFP Section 6.1.4.17, there are a number of
Performance Requirements. These requirements will help form the basis of the
Service Level Agreements (SLAs) to be developed with the successful Responder
as part of contract negotiations. These service levels would also include, but not
be limited to, the following:
11) Comprehensive System Warranty – Responders must warrant that the goods sold
constitute a system suitable for the purposes articulated in the contract. For this
project, the warranty will begin the first day of the Operations and Maintenance
Phase and conclude 90 days later (at a minimum). Responder shall be responsible
for any and all necessary additions, modifications, repair or replacement of all
elements of the solution (minus Head-End hardware, operating system, and
database software) to ensure satisfactory operation and subsequent expansion of
the system. SVP will notify Responder promptly of any failure of the system to
12) Turnover/Transition Plan – Responders must provide a plan that describes how
they will turnover/transition the AMI Solution (meters, communication network,
AMI Head-End application, and all related hardware, software, data and
documents) to SVP. Please note that at the City’s option, we may choose to
amend the contract to continue to provide operations and maintenance support, for
all or part of the solution, for any number of reasons including a delay in the
transition.
Please review the contract in its entirety. If Responder desires to take any exception to
the Agreement, Responder shall provide the following information in response to RFP
Section 9.2.6:
x Responder shall identify the contract item number (and page number) at issue.
NOTE: The above factors will be taken into account in evaluating proposals. Proposals
that take exceptions to the proposed agreement may be determined by the City, at its sole
discretion, to be unacceptable and no longer considered for award.
1. Implementation
b) Responders must provide firm, fixed prices, not price estimates, for
Implementation (Sheet 1), as well as the Operations and Maintenance(Sheet 2).
NOTE: The City acknowledges that the Travel and Expenses items in both these
sheets are estimates, but expect Responders to make their best effort in estimating
these costs.
c) Responders are to provide price estimates for the Optional/Future Items, Optional
Network Expansion and Meter Installations, and Out-Year Software Licensing
and Maintenance (Sheets 3 through 5 respectively).
d) Do not leave pricing cells blank. Enter "0" if there are no costs involved and
insert "Not Applicable" or "Included in Item #" in the Comment column.
f) Please list any assumptions made by Responder as they pertain to each item on
the sheets; insert assumptions in the “Comment” column. Responders may attach
an additional sheet for these assumptions if necessary (if so, please ensure to
reference each assumption to specific items in the pricing sheets).
g) In addition to the Pricing Worksheets, please provide an additional sheet that lists
hourly rates specific to the various job titles (labor categories) proposed on this
project. If any offshore labor is proposed, please use a separate sheet for it and
estimate the percentage of expected utilization in each labor category.
h) All pricing must be valid for 90 days from the date of proposal submittal. Hourly
rates pertaining to labor categories must be valid through the end of the
Operations and Maintenance period.
j) List any additional cost items not already identified in the price sheets in the
appropriate “Other” sections and explain what they are and why they would be
necessary.
1. Implementation
iii. If applicable, please provide pricing for any product and system
configurations, customizations, and/or enhancements. Please itemize
these items and use the “Comment” column to tie them directly to the
specific RFP requirements that will be supported by the
enhancement/customization.
iii. Provide pricing for application and any third-party software licensing
fees (consider the three required environments – development/test,
training, and production). Be sure to itemize.
3. Optional/Future Items
i. Please identify the staff required (by title), and the hours and rates for
each. Please also identify the network devices (by type, number, and
unit cost), and the meters (by type, number, and unit cost).
i. Please list software licensing fees (itemize both application and third-
party software) for years four (4) through ten (10)
ii. Please list software maintenance and upgrade fees (itemize both
application and third-party software) for years four (4) through ten
(10)
9.1 Overview
All RFP requirements must be answered and all requested information must be provided.
All pages in the proposal must be standard 8.5" x 11" paper, except charts, diagrams, etc.,
which may be foldouts. If foldouts are used, the folded size must fit within the 8.5" x 11"
format. All charts and diagrams must be sized so they are readable. Proposals must be
provided in an appropriately sized three-ring binder.
Page numbers must be located in the same page position throughout the proposal.
Figures, tables, charts, etc. must be assigned their own numbers and must be referenced
by these numbers in the proposal text and in the proposal Table of Contents. Figures,
tables, charts, etc. must be placed as close to text references as possible.
x Cover Letter
x Table of Contents
x Executive Summary
x Administrative Requirements Response
x Technical Requirements Response
x Contract Terms and Conditions
The City provides additional instructions pertaining to these items in the following
sections.
The proposal must contain a Cover Letter on letterhead, signed by an individual who is
authorized to contractually bind the Responder, and indicating the title that person holds
The proposal must contain a Table of Contents. Figures, tables, charts, etc. must be
assigned index numbers and must be identified in the Table of Contents.
The proposal must contain the Executive Summary that describes the salient features of
the proposal. It must condense and highlight the contents of the proposal and include
conclusions and recommendations. The Executive Summary must list each
Subcontractor and explain each Subcontractor’s role in relation to meeting the RFP
requirements. RFP Attachment B – List of Subcontractors – must be included at the end
of the Executive Summary.
In responding to the System Requirements, Responders should repeat the heading names
from the System Requirements section and address each of the requirements under those
headings.
Please note that there are nine (9) separate requirements within Section 6.0 that must be
addressed prior to addressing the Functional and Technical requirements in the Word
tables.
Responders must also provide responses to each of the items in RFP Section 6.5.
Responders must include a statement of compliance with all contract terms and
conditions as identified in the City’s Standard Service Agreement – Attachment C.
1) Cover Letter
2) Table of Contents
Failure to provide the appropriate number of copies in the correct format may be grounds
for immediate disqualification.
x Name of Responder
x Address of Responder
x RFP Number
x Proposal Name (Administrative/Technical OR Price)
x Proposal Due Date and Time
x Number of Copies Provided
Proposals must be delivered to the following address by the date and time identified in
Section 1.8 – Key Action Dates (or indicated in any RFP addenda that changes the Key
Action Dates):
Joe Blackwell
AMI Project Coordinator
City of Santa Clara
Silicon Valley Power
1601 Civic Center Drive
Santa Clara, CA 95050
o Degree to which the proposed solution has been proven (in use) in other cities,
counties and/or electric and water utilities for the relevant functions
o Project timing
The evaluation process may involve contacting any or all of the customer references.
The City may interview these customers so it can confirm the information submitted.
Customers must respond positively in order for the Responder to be successful in this
portion of the evaluation.
The City will evaluate the Responder’s proposed organization and staff in terms of their
organization, skills, knowledge, references, and experience as described in the narrative
response and in their resumes. Scoring of these responses will be based on the consensus
of the Evaluation Team.
The City will evaluate the project management approach based on the Responder’s
description. Scoring of these responses will be based on the consensus of the Evaluation
Team.
The City will evaluate the proposed Project Plan and Schedule, including the proposed
milestones, deliverables, resources, and timeframes. Scoring of these responses will be
based on the consensus of the Evaluation Team.
Joe Blackwell
AMI Project Coordinator
City of Santa Clara
Silicon Valley Power
Fax: 408-244-2990
Date: _____________________________________________
_____________________________________________
_____________________________________________
Phone: _____________________________________________
Fax: _____________________________________________
Email: _____________________________________________
Signature: _____________________________________________
I agree to advise the City of Santa Clara, SVP immediately in the event that I either learn
or have reason to believe that any person who has access to project confidential
information has or intends to disclose that information in violation of this agreement.
Date:_____________________________________________________________
Signature:_________________________________________________________
Printed Name:______________________________________________________
Title:_____________________________________________________________
Organization:_______________________________________________________
Telephone
Number:___________________________________________________________
Fax Number:________________________________________________________
PREAMBLE
This agreement for the performance of services (“Agreement”) is made and entered into on
this______ day of __________, 200__, (“Effective Date”) by and between _________________,
[choose one: corporation/partnership/individual], with its principal place of business located at
____________________________ (“Contractor”), and the City of Santa Clara, California, a
chartered California municipal corporation with its primary business address at 1500 Warburton
Avenue, Santa Clara, California 95050 (“City”). City and Contractor may be referred to
individually as a “Party” or collectively as the “Parties” or the “Parties to this Agreement.”
RECITALS
A. City desires to secure professional services more fully described in this Agreement, at
Exhibit A, entitled “Scope of Service”; and
B. Contractor represents that it, and its subcontractors, if any, have the professional
qualifications, expertise, necessary licenses and desire to provide certain goods and/or
required services of the quality and type which meet objectives and requirements of City;
and,
C. The Parties have specified herein the terms and conditions under which such services will
be provided and paid for.
AGREEMENT PROVISIONS
1. SERVICES TO BE PROVIDED.
Except as specified in this Agreement, Contractor shall furnish all technical and
professional services, including labor, material, equipment, transportation, supervision
and expertise (collectively referred to as “Services”) to satisfactorily complete the work
required by City at his/her own risk and expense. Services to be provided to City are
more fully described in Exhibit A entitled “SCOPE OF SERVICES.” All of the exhibits
referenced in this Agreement are attached and are incorporated by this reference.
Contractor acknowledges that the execution of this Agreement by City is predicated upon
representations made by Contractor in that certain document entitled
“__________________________” dated ________________, 20___, (“Proposal”) set
forth in Exhibit A, which constitutes the basis for this Agreement.
Unless otherwise set forth in this Agreement or unless this paragraph is subsequently
modified by a written amendment to this Agreement, the term of this Agreement shall
begin on the Effective Date of this Agreement and terminate on ______________, 20__.
A. All reports, costs estimates, plans and other documentation which may be
submitted or furnished by Contractor shall be approved and signed by a qualified
licensed professional in the State of California.
B. The title sheet for specifications and reports, and each sheet of plans, shall bear
the professional seal, certificate number, registration classification, expiration
date of certificate and signature of the professional responsible for their
preparation.
Contractor represents and maintains that it has the necessary expertise in the professional
calling necessary to perform services, and its duties and obligations, expressed and
implied, contained herein, and City expressly relies upon Contractor’s representations
regarding its skills and knowledge. Contractor shall perform such services and duties in
conformance to and consistent with the professional standards of a specialist in the same
discipline in the State of California.
The plans, designs, specifications, estimates, calculations, reports and other documents
furnished under Exhibit A shall be of a quality acceptable to City. The criteria for
acceptance of the work provided under this Agreement shall be a product of neat
appearance, well organized, that is technically and grammatically correct, checked and
having the maker and checker identified. The minimum standard of appearance,
organization and content of the drawings shall be that used by City for similar projects.
5. MONITORING OF SERVICES.
City may monitor the Services performed under this Agreement to determine whether
Contractor’s operation conforms to City policy and to the terms of this Agreement. City
may also monitor the Services to be performed to determine whether financial operations
are conducted in accord with applicable City, county, state, and federal requirements. If
any action of Contractor constitutes a breach, City may terminate this Agreement
pursuant to the provisions described herein.
6. WARRANTY.
Contractor expressly warrants that all materials and services covered by this Agreement
shall be fit for the purpose intended, shall be free from defect, and shall conform to the
specifications, requirements, and instructions upon which this Agreement is based.
Contractor agrees to promptly replace or correct any incomplete, inaccurate, or defective
7. PERFORMANCE OF SERVICES.
Contractor shall perform all requested services in an efficient and expeditious manner and
shall work closely with and be guided by City. Contractor shall be as fully responsible to
City for the acts and omissions of its subcontractors, and of persons either directly or
indirectly employed by them, as Contractor is for the acts and omissions of persons
directly employed by it. Contractor will perform all Services in a safe manner and in
accordance with all federal, state and local operation and safety regulations.
8. RESPONSIBILITY OF CONTRACTOR.
Contractor shall be responsible for the professional quality, technical accuracy and
coordination of the Services furnished by it under this Agreement. Neither City’s review,
acceptance, nor payments for any of the Services required under this Agreement shall be
construed to operate as a waiver of any rights under this Agreement or of any cause of
action arising out of the performance of this Agreement and Contractor shall be and
remain liable to City in accordance with applicable law for all damages to City caused by
Contractor’s negligent performance of any of the Services furnished under this
Agreement.
Contractor will bill City on a monthly basis for Services provided by Contractor during
the preceding month, subject to verification by City. City will pay Contractor within
thirty (30) days of City’s receipt of invoice.
The Progress Schedule will be as set forth in the attached Exhibit F, entitled
“MILESTONE SCHEDULE” if applicable.
Either Party may terminate this Agreement without cause by giving the other Party
written notice (“Notice of Termination”) which clearly expresses that Party’s intent to
terminate the Agreement. Notice of Termination shall become effective no less than
thirty (30) calendar days after a Party receives such notice. After either Party terminates
the Agreement, Contractor shall discontinue further services as of the effective date of
termination, and City shall pay Contractor for all Services satisfactorily performed up to
such date.
City and Contractor bind themselves, their successors and assigns to all covenants of this
Agreement. This Agreement shall not be assigned or transferred without the prior written
approval of City. Contractor shall not hire subcontractors without express written
permission from City.
This Agreement shall not be construed to be an agreement for the benefit of any third
party or parties and no third party or parties shall have any claim or right of action under
this Agreement for any cause whatsoever.
Contractor and all person(s) employed by or contracted with Contractor to furnish labor
and/or materials under this Agreement are independent contractors and do not act as
agent(s) or employee(s) of City. Contractor has full rights, however, to manage its
employees in their performance of Services under this Agreement. Contractor is not
authorized to bind City to any contracts or other obligations.
Under no circumstances shall Contractor have the authority or power to pledge the credit
of City or incur any obligation in the name of City. Contractor shall save and hold
harmless the City, its City Council, its officers, employees, boards and commissions for
expenses arising out of any unauthorized pledges of City’s credit by Contractor under this
Agreement.
Contractor shall not use City’s name, insignia, or emblem, or distribute any information
related to services under this Agreement in any magazine, trade paper, newspaper or
other medium without express written consent of City.
All material, including information developed on computer(s), which shall include, but
not be limited to, data, sketches, tracings, drawings, plans, diagrams, quantities,
estimates, specifications, proposals, tests, maps, calculations, photographs, reports and
other material developed, collected, prepared or caused to be prepared under this
Agreement shall be the property of City but Contractor may retain and use copies thereof.
City shall not be limited in any way or at any time in its use of said material. However,
Contractor shall not be responsible for damages resulting from the use of said material for
work other than Project, including, but not limited to, the release of this material to third
parties.
City, through its authorized employees, representatives or agents shall have the right
during the term of this Agreement and for three (3) years from the date of final payment
for goods or services provided under this Agreement, to audit the books and records of
Contractor for the purpose of verifying any and all charges made by Contractor in
connection with Contractor compensation under this Agreement, including termination of
Contractor. Contractor agrees to maintain sufficient books and records in accordance with
generally accepted accounting principles to establish the correctness of all charges
submitted to City. Any expenses not so recorded shall be disallowed by City.
Contractor shall submit to City any and all reports concerning its performance under this
Agreement that may be requested by City in writing. Contractor agrees to assist City in
meeting City’s reporting requirements to the State and other agencies with respect to
Contractor’s Services hereunder.
Contractor shall not discriminate against any employee or applicant for employment
because of race, color, creed, national origin, gender, sexual orientation, age, disability,
religion, ethnic background, or marital status, in violation of state or federal law.
To the extent permitted by law, Contractor agrees to protect, defend, hold harmless and
indemnify City, its City Council, commissions, officers, employees, volunteers and
agents from and against any claim, injury, liability, loss, cost, and/or expense or damage,
including all costs and reasonable attorney’s fees in providing a defense to any claim
arising therefrom, for which City shall become liable arising from Contractor’s negligent,
reckless or wrongful acts, errors, or omissions with respect to or in any way connected
with the Services performed by Contractor pursuant to this Agreement.
During the term of this Agreement, and for any time period set forth in Exhibit C,
Contractor shall purchase and maintain in full force and effect, at no cost to City
insurance policies with respect to employees and vehicles assigned to the Performance of
Services under this Agreement with coverage amounts, required endorsements,
certificates of insurance, and coverage verifications as defined in Exhibit C.
24. AMENDMENTS.
This Agreement may be amended only with the written consent of both Parties.
This Agreement represents the entire agreement between City and Contractor. No other
understanding, agreements, conversations, or otherwise, with any representative of City
prior to execution of this Agreement shall affect or modify any of the terms or obligations
of this Agreement. Any verbal agreement shall be considered unofficial information and
is not binding upon City.
In case any one or more of the provisions in this Agreement shall, for any reason, be held
invalid, illegal or unenforceable in any respect, it shall not affect the validity of the other
provisions, which shall remain in full force and effect.
27. WAIVER.
Contractor agrees that waiver by City of any one or more of the conditions of
performance under this Agreement shall not be construed as waiver(s) of any other
condition of performance under this Agreement.
All notices to the Parties shall, unless otherwise requested in writing, be sent to City
addressed as follows:
If notice is sent via facsimile, a signed, hard copy of the material shall also be mailed.
The workday the facsimile was sent shall control the date notice was deemed given if
there is a facsimile machine generated document on the date of transmission. A facsimile
transmitted after 1:00 p.m. on a Friday shall be deemed to have been transmitted on the
following Monday.
29. CAPTIONS.
The captions of the various sections, paragraphs and subparagraphs of this Agreement are
for convenience only and shall not be considered or referred to in resolving questions of
interpretation.
This Agreement shall be governed and construed in accordance with the statutes and laws
of the State of California. The venue of any suit filed by either Party shall be vested in the
state courts of the County of Santa Clara, or if appropriate, in the United States District
Court, Northern District of California, San Jose, California.
B. The Parties may agree on one mediator. If they cannot agree on one mediator, the
Party demanding mediation shall request the Superior Court of Santa Clara
County to appoint a mediator. The mediation meeting shall not exceed one day
D. For any contract dispute, mediation under this section is a condition precedent to
filing an action in any court. In the event of mediation which arises out of any
dispute related to this Agreement, the Parties shall each pay their respective
attorney’s fees, expert witness costs and cost of suit, through mediation only. In
the event of litigation, the prevailing party shall recover its reasonable costs of
suit, expert’s fees and attorney’s fees.
Contractor shall:
This Agreement does not prevent either Party from entering into similar agreements with
other parties. To prevent a conflict of interest, Contractor certifies that to the best of its
knowledge, no City officer, employee or authorized representative has any financial
interest in the business of Contractor and that no person associated with Contractor has
any interest, direct or indirect, which could conflict with the faithful performance of this
Agreement. Contractor is familiar with the provisions of California Government Code
Section 87100 and following, and certifies that it does not know of any facts which would
violate these code provisions. Contractor will advise City if a conflict arises.
The Parties acknowledge and accept the terms and conditions of this Agreement as evidenced by
the following signatures of their duly authorized representatives. It is the intent of the Parties that
this Agreement shall become operative on the Effective Date.
[*CONTRACTOR]
[CHOOSE ONE: CORPORATION/PARTNERSHIP/INDIVIDUAL]
By:
(Signature of Person executing the Agreement on behalf of Contractor)
Name:
Title:
Local Address:
Telephone ( )
Fax: ( )
EXHIBIT A
SCOPE OF SERVICES
The Services to be performed for the City by the Contractor under this Agreement are more fully
described in the Contractor’s proposal entitled, “[*insert name of proposal]” dated [*insert date
of proposal], which is attached to this Exhibit A.
EXHIBIT B
FEE SCHEDULE
Consultant shall provide a schedule of rates and fees which includes all billing amounts and costs
as follows (if applicable), such as:
[NOTE TO CITY DEPARTMENTS: This Exhibit “B” should contain a schedule of rates
and fees which includes all billing amounts and costs as follows (if applicable), such as:
-Fee Schedule Effective Date;
-Hourly Billing Rates for Each Staff Position/level;
-Minimum Billing Hours;
-Charges for Equipment by Day/week/month;
-Travel Time and Costs;
-Per Diem Expenses;
-Expendable Material or New Parts Costs;
-Outside Services Costs; and,
-Overtime Costs.]
In no event shall the amount billed to City by Contractor for services under this Agreement
exceed $ _______________, subject to budget appropriations.
EXHIBIT C
INSURANCE REQUIREMENTS
Without limiting the Contractor’s indemnification of the City, and prior to commencing any of
the Services required under this Agreement, the Contractor shall purchase and maintain in full
force and effect, at its sole cost and expense, the following insurance policies with at least the
indicated coverages, provisions and endorsements:
2. Exact structure and layering of the coverage shall be left to the discretion of
Contractor; however, any excess or umbrella policies used to meet the required
limits shall be at least as broad as the underlying coverage and shall otherwise
follow form.
3. The following provisions shall apply to the Commercial Liability policy as well as
any umbrella policy maintained by the Contractor to comply with the insurance
requirements of this Agreement:
Business automobile liability insurance policy which provides coverage at least as broad
as ISO form CA 00 01 with policy limits a minimum limit of not less than one million
dollars ($1,000,000) each accident using, or providing coverage at least as broad as,
Insurance Services Office form CA 00 01. Liability coverage shall apply to all owned,
non-owned and hired autos.
In the event that the Work being performed under this Agreement involves transporting
of hazardous or regulated substances, hazardous or regulated wastes and/or hazardous or
regulated materials, Contractor and/or its subcontractors involved in such activities shall
provide coverage with a limit of two million dollars ($2,000,000) per accident covering
transportation of such materials by the addition to the Business Auto Coverage Policy of
Environmental Impairment Endorsement MCS90 or Insurance Services Office
endorsement form CA 99 48, which amends the pollution exclusion in the standard
Business Automobile Policy to cover pollutants that are in or upon, being transported or
towed by, being loaded onto, or being unloaded from a covered auto.
C. WORKERS’ COMPENSATION
3. This policy must include a Waiver of Subrogation in favor of the City of Santa
Clara, its City Council, commissions, officers, employees, volunteers and agents.
All of the following clauses and/or endorsements, or similar provisions, must be part of
each commercial general liability policy, and each umbrella or excess policy.
1. Additional Insureds. City of Santa Clara, its City Council, commissions, officers,
employees, volunteers and agents are hereby added as additional insureds in
respect to liability arising out of Contractor’s work for City, using Insurance
Services Office (ISO) Endorsement CG 20 10 11 85 or the combination of CG 20
10 03 97 and CG 20 37 10 01, or its equivalent.
4. Cancellation.
5. Other Endorsements. Other endorsements may be required for policies other than
the commercial general liability policy if specified in the description of required
insurance set forth in Sections A through D of this Exhibit C, above.
1. Contractor agrees to ensure that subcontractors, and any other party involved with
the Services who is brought onto or involved in the performance of the Services
by Contractor, provide the same minimum insurance coverage required of
Contractor, except as with respect to limits. Contractor agrees to monitor and
review all such coverage and assumes all responsibility for ensuring that such
coverage is provided in conformity with the requirements of this Agreement.
Contractor agrees that upon request by City, all agreements with, and insurance
compliance documents provided by, such subcontractors and others engaged in
the project will be submitted to City for review.
3. The City reserves the right to withhold payments from the Contractor in the event
of material noncompliance with the insurance requirements set forth in this
Agreement.
F. EVIDENCE OF COVERAGE
Prior to commencement of any Services under this Agreement, Contractor, and each and
every subcontractor (of every tier) shall, at its sole cost and expense, purchase and
maintain not less than the minimum insurance coverage with the endorsements and
deductibles indicated in this Agreement. Such insurance coverage shall be maintained
with insurers, and under forms of policies, satisfactory to City and as described in this
Agreement. Contractor shall file with the City all certificates and endorsements for the
required insurance policies for City’s approval as to adequacy of the insurance protection.
G. EVIDENCE OF COMPLIANCE
Contractor or its insurance broker shall provide the required proof of insurance
compliance, consisting of Insurance Services Office (ISO) endorsement forms or their
equivalent and the ACORD form 25-S certificate of insurance (or its equivalent),
evidencing all required coverage shall be delivered to City, or its representative as set
forth below, at or prior to execution of this Agreement. Upon City’s request, Contractor
shall submit to City copies of the actual insurance policies or renewals or replacements.
Unless otherwise required by the terms of this Agreement, all certificates, endorsements,
coverage verifications and other items required to be delivered to City pursuant to this
Agreement shall be mailed to:
City of Santa Clara [insert City department name here]
c/o Insurance Data Services - Insurance Compliance
P.O. 12010-S2 or 151 North Lyon Avenue
Hemet, CA 92546-8010 Hemet, CA 92543
Telephone: (951) 766-2280; or
Fax: (951) 766-2299
H. QUALIFYING INSURERS
All of the insurance companies providing insurance for Contractor shall have, and
provide written proof of, an A. M. Best rating of at least A minus 6 (A- VI) or shall be an
insurance company of equal financial stability that is approved by the City or its
insurance compliance representatives.
EXHIBIT D
I. The City may, at its sole discretion, terminate this Agreement in the event any one or
more of the following occurs:
1
For purposes of this Agreement, the word “Consultant” (whether a person or a legal entity) also refers to
“Contractor” and means any of the following: an owner or co-owner of a sole proprietorship; a person who controls
or who has the power to control a business entity; a general partner of a partnership; a principal in a joint venture; or
a primary corporate stockholder [i.e., a person who owns more than ten percent (10%) of the outstanding stock of a
corporation] and who is active in the day to day operations of that corporation.
2
For purposes of this Agreement, the words “convicted” or “conviction” mean a judgment or conviction of a
criminal offense by any court of competent jurisdiction, whether entered upon a verdict or a plea, and includes a
conviction entered upon a plea of nolo contendere within the past five (5) years.
3
As used herein, “dishonesty” includes, but is not limited to, embezzlement, theft, forgery, bribery,
falsification or destruction of records, making false statements, failure to pay tax obligations, receiving stolen
property, collusion or conspiracy.
J. The City may also terminate this Agreement in the event any one or more of the
following occurs:
1. The City determines that Contractor no longer has the financial capability4 or
business experience5 to perform the terms of, or operate under, this Agreement;
or,
2. If City determines that the Contractor fails to submit information, or submits false
information, which is required to perform or be awarded a contract with City,
including, but not limited to, Contractor’s failure to maintain a required State
issued license, failure to obtain a City business license (if applicable) or failure to
purchase and maintain bonds and/or insurance policies required under this
Agreement.
4
Contractor becomes insolvent, transfers assets in fraud of creditors, makes an assignment for the benefit of
creditors, files a petition under any section or chapter of the federal Bankruptcy Code (11 U.S.C.), as amended, or
under any similar law or statute of the United States or any state thereof, is adjudged bankrupt or insolvent in
proceedings under such laws, or a receiver or trustee is appointed for all or substantially all of the assets of
Contractor.
5
Loss of personnel deemed essential by the City for the successful performance of the obligations of the
Contractor to the City.
EXHIBIT E
Based on my review of the appropriate documents and my good-faith review of the necessary
inquiry responses, I hereby state that neither the business entity nor any individual(s) belonging
to said “Contractor” category [i.e., owner or co-owner of a sole proprietorship, general partner,
person who controls or has power to control a business entity, etc.] has been convicted of any
one or more of the crimes identified in the Ethical Standards within the past five (5) years.
The above assertions are true and correct and are made under penalty of perjury under the laws
of the State of California.
[*Contractor]
By:
Signature of Authorized Person or Representative
Name:
Title:
EXHIBIT F
MILESTONE SCHEDULE
(If Applicable)
mentation Phase
ct Management Support *Deliverable Set 1 - Project N $ - $ - F $ - $ -
Plan (updated) and Project
Schedule (updated)
*Deliverable Set 2 - N $ - $ - F $ - $ -
Technical Architecture
Diagram (updated), Network
Architecture Diagram
(updated), Data Flow
Diagram (updated),
Application and Third Party
Software List (updated),
(updated)
Implementation Plan
(updated), Meter Installation
Plan (updated), Electric and
Water Meter Recycling Plan
(updated), System and
Network Documentation
*Deliverable Set 3 - N $ - $ - F $ - $ -
User/Training
Documentation, Training Plan
(updated), Test Plan
(updated), System
Turnover/Transition Plan
(updated)
irements Verification N $ - $ - F $ - $ -
ct & System Configurations
ze)
$ - $ - F $ - $ -
$ - $ - F $ - $ -
$ - $ - F $ - $ -
$ - $ - F $ - $ -
ct Customizations (Itemize)
$ - $ - F $ - $ -
$ - $ - F $ - $ -
$ - $ - F $ - $ -
$ - $ - F $ - $ -
$ - $ - F $ - $ -
ct Enhancements (Itemize)
$ - $ - F $ - $ -
$ - $ - F $ - $ -
$ - $ - F $ - $ -
$ - $ - F $ - $ -
$ - $ - F $ - $ -
-End Software Installation N $ - $ - F $ - $ -
S Interface Support N $ - $ - F $ - $ -
rk Installation N $ - $ - F $ - $ -
Installation N $ - $ - F $ - $ -
m Operations N $ - $ - F $ - $ -
rk Operations N $ - $ - F $ - $ -
ng Training Results N $ - $ - F $ - $ -
roof of Concept Testing Lab Proof of Concept Test N $ - $ - F $ - $ -
Results
Proof of Concept Testing Field Proof of Concept Test N $ - $ - F $ - $ -
Results
Testing Final Test Results N $ - $ - F $ - $ -
l and Expenses N $ - $ - B $ - $ -
$ - $ - F $ - $ -
$ - $ - F $ - $ -
$ - $ - F $ - $ -
al Implementation Cost 0 $ - $ - $ -
ns and Maintenance
d Expenses N $ - $ - B $ - $ -
k Support N $ - $ - F $ - $ -
anagement Operations Reports, Quarterly Invoices N $ - $ - F $ - $ -
pport
Licensing (Itemize N
n and Third-Party)
$ - $ - F $ - $ -
$ - $ - F $ - $ -
$ - $ - F $ - $ -
$ - $ - F $ - $ -
$ - $ - F $ - $ -
Maintenance and N
(Itemize Application and
ty)
$ - $ - F $ - $ -
$ - $ - F $ - $ -
$ - $ - F $ - $ -
$ - $ - F $ - $ -
$ - $ - F $ - $ -
perations N
$ - $ - F $ - $ -
Operations N
$ - $ - F $ - $ -
Hardware Maintenance N
ades
$ - $ - F $ - $ -
ent/Installation of Faulty N
$ - $ - F $ - $ -
$ - $ - F $ - $ -
.4.0 Recommended N $ - $ - B $ - $ -
ractices
N $ - $ - B $ - $ -
N $ - $ - B $ - $ -
N $ - $ - B $ - $ -
N $ - $ - B $ - $ -
N $ - $ - B $ - $ -
N $ - $ - B $ - $ -
N $ - $ - B $ - $ -
N $ - $ - B $ - $ -
N $ - $ - B $ - $ -
4
are Licensing (Itemize
ation and Third Party)
N $ - B $ - $ -
N $ - B $ - $ -
N $ - B $ - $ -
N $ - B $ - $ -
are Maintenance and
des (Itemize Application and
Party)
N $ - B $ - $ -
N $ - B $ - $ -
N $ - B $ - $ -
N $ - B $ - $ -
5
are Licensing (Itemize
ation and Third Party)
N $ - B $ - $ -
N $ - B $ - $ -
N $ - B $ - $ -
N $ - B $ - $ -
are Maintenance and
des (Itemize Application and
Party)
N $ - B $ - $ -
N $ - B $ - $ -
N $ - B $ - $ -
N $ - B $ - $ -
6
are Licensing (Itemize
ation and Third Party)
N $ - B $ - $ -
N $ - B $ - $ -
N $ - B $ - $ -
N $ - B $ - $ -
are Maintenance and
des (Itemize Application and
Party)
N $ - B $ - $ -
N $ - B $ - $ -
N $ - B $ - $ -
N $ - B $ - $ -
7
are Licensing (Itemize
ation and Third Party)
N $ - B $ - $ -
N $ - B $ - $ -
N $ - B $ - $ -
N $ - B $ - $ -
are Maintenance and
des (Itemize Application and
Party)
N $ - B $ - $ -
N $ - B $ - $ -
N $ - B $ - $ -
N $ - B $ - $ -
8
are Licensing (Itemize
ation and Third Party)
N $ - B $ - $ -
N $ - B $ - $ -
N $ - B $ - $ -
N $ - B $ - $ -
are Maintenance and
des (Itemize Application and
Party)
N $ - B $ - $ -
N $ - B $ - $ -
N $ - B $ - $ -
N $ - B $ - $ -
9
are Licensing (Itemize
ation and Third Party)
N $ - B $ - $ -
N $ - B $ - $ -
N $ - B $ - $ -
N $ - B $ - $ -
are Maintenance and
des (Itemize Application and
Party)
N $ - B $ - $ -
N $ - B $ - $ -
N $ - B $ - $ -
N $ - B $ - $ -
10
are Licensing (Itemize
ation and Third Party)
N $ - B $ - $ -
N $ - B $ - $ -
N $ - B $ - $ -
N $ - B $ - $ -
are Maintenance and
des (Itemize Application and
Party)
N $ - B $ - $ -
N $ - B $ - $ -
N $ - B $ - $ -
N $ - B $ - $ -
l Out Year Licensing and 0 $ - $ - $ -
tenance/Upgrades
mates)
Company (Customer)
Name
Project Name
Customer Contact Name,
Title, Address, Phone, Fax,
and E-mail
Summary Project
Description (Scope of
Work)
Summary of Responder’s
Involvement (Specific
Tasks Completed by
Responder vs.
Subcontractors)
Summary of Installation
Services Provided
Summary of
Implementation Services
Provided
Summary of On-Going
Services Provided
Number and Type of
Meters Supported
Interfaces Supported
Deliverables Completed,
Submitted, and
Approved/Accepted by
Customer
Current Status of Project
Project Start and End
Dates
Original Cost Estimate
Actual Cost
Telephone:
FAX:
Contact person, title, telephone number, email address and fax number:
ADDENDA
To assure that all Responders have received each addendum, check the appropriate
box(es) below. Failure to acknowledge receipt of an addendum/addenda may be
considered an irregularity in the Proposal:
Addendum number(s) received:
1
2
3
4
5
Or,
_____No Addendum/Addenda Were Received (check and initial).
Responder’s Signature
(type or print)
Date:
Date:
By:
Title:
Dated:
By:
Title:
Dated:
Responder’s Signature
(type or print)
Date:
Date:
By:
Title:
Dated:
By:
Title:
Dated:
This policy outlines the requirements for Remote Access via VPN
connections to SVP Networks and ensures that each entity,
including contracting agencies, understands that they must
establish, enforce and continuously improve an Information
Technology (IT) Security Program.
REGULATORY With the passage of the Energy Policy Act of 2005 (ACT), the
PROVISIONS: United States Congress entrusted the Federal Energy Regulatory
Commission (FERC) with the authority to approve and enforce
rules to assure reliability of the Nation’s Bulk-Power System. The
ACT mandates that all users, owners, and operators of the Bulk-
Power System in the United States will be subject to the
Commission-approved Reliability Standards. The Critical
Infrastructure Protection group of reliability standards, as filed,
consists of standards aimed at establishing security for critical cyber
assets which addresses the cyber security of bulk electric system
assets. This group of standards applies to the SVP Network.
SVP Network VPN User A VPN User of the SVP Network is either, 1) an individual who is
DEFINITION a member of the Electric Department Active Directory Domain
(SVP User); or 2) an individual or entity that has been identified as
requiring network access to specific SVP systems for the purpose of
regulatory or contractual business activities (Non-SVP User).
Each individual that will use the requested access must be uniquely
identified and the associated business requirements specified prior
to granting access. The VPN Access will be strictly limited to the
services required and all network related activity will be monitored
and recorded. There is no warranty of privacy or confidentiality
other than that specifically provided for by contract.
An SVP Network
VPN User May Not: 1. Attempt any access to SVP Network or other electronic
facilities without specific prior written authorization.
4. Use any authorized SVP Network access for any purpose other
than what has been identified by the specified contract and this
policy.
Individuals Authorized to
Grant Network Access 1. SVP Cyber Security Officer
2. SVP Management
Network Security
Measures: 1. All External User Interfaces and Ports are specifically
identified and allowed as per contract requirements and are
continuously scanned and monitored for compliance.
RESPONSIBILITY : ACTION