You are on page 1of 21

ANACOSTIA LOCATION

PROJECT DIRECTORY
Building Address Architect
1801 Good Hope Road SE CORE
Washington, DC 20020 1010 Wisconsin Avenue, NW
Suite 405
Washington, D.C. 20007
Owner Contact: David Cheney
DC Public Library drc@COREdc.com
Martin Luther King , Jr. Memorial Library    Sabrina Cheung
901 G Street NW sbc@COREdc.com
Washington, DC 20001-4599 202.466.6116
Contact: Jeff Bonvechio 202.466.6235 fax
jeffrey.bonvechio@dc.gov
Telephone: 202.442.6070 MEP Engineer
Fax: 202.727.4792 Allen and Shariff
7061 Deepage Drive
2nd Floor
Columbia, MD 21045
fbeam@allenshariff.com
Contact: Fred Beam

Telephone: 410.381.7100
Fax: 410.381.7110

BID SET 6/15/06


DC Public Library
1010 wisconsin avenue, nw
suite 405
washington, dc 20007
1801 Good Hope Road SE
Washington, DC 20020
T 202.466.6116
F 202.466.6235
E GEN@COREdc.com
© core group, pc 2006
DC Public Library - Anacostia
1801 Good Hope Road SE
Washington, DC, 20020
2. Remove and replace defective work. 09250 GYPSUM BOARD
4. Millwork covered in wood veneer or plastic laminate shall be fabricated and assembled by skilled workmen to the complete satisfaction
of the Architect. Reinforcing as required to ensure a rigid and secure assembly shall be provided, even if not detailed on the drawings. SECTION 08450 - ALL-GLASS ENTRANCES A. General
Exposed surfaces shall be free from dents, tool marks, warpage, buckle, glue and open joints. All joint corners and miter connections
shall be made tightly so that threads are entirely concealed. All exposed laminate joints shall be shown on shop drawings and reviewed A. SUBMITTALS 1. The Contractor shall notify Architect of date for partition layout. Layout shall be reviewed by Architect prior to construction.
by the Architect.
1. Product Data: 2. All gypsum board installation shall be done by a qualified installer with experience in commercial applications similar in scope to this
5. For millwork indicating plastic laminate exterior finished surfaces, provide white melamine as the interior cabinet and drawer surface a. Submit manufacturer's literature describing products to be provided. project.
finish (unless otherwise noted in the Drawings and details).
2. Shop Drawings: 3. Gypsum board installation shall conform to ASTM C840, the recommendations of the Gypsum Association, the specific
6. Install millwork to be plumb, level, true and straight with no distortions. Shim as required using concealed shims. a. Submit shop drawings for systems. Show anchorage, field connections, and glazing for component parts and prepare coordination recommendations of the manufacturer, and the requirements of the UL Fire Resistance Directory (at fire rated partitions)
details for entire system including framing and bracing to structure.
7. Scribe and cut Work to fit adjoining Work and refinish cut surfaces or repair damaged finish at cuts. Provide clear sealant at all joints. b. Shop drawings shall show scale elevations and sections. Full size sections shall be shown only when needed for clarity. 4. At areas where existing partitions are indicated to remain, repair and prepare existing gypsum board surface to accept new finish.
Quality of repaired and prepared surface of existing partition shall be equal to that of newly constructed partitions.
8. Anchor millwork to built-in blocking or directly attach to substrate. Secure to grounds, strapping and blocking with counter-sunk, 3. Samples:
concealed fasteners and blind nailing as required for a complete installation. a. Submit 2 samples of finished metal materials: B. Metal Framing
i. Extrusions: 12" lengths
9. The Contractor shall be responsible for making certain that millwork items are not delivered until areas are sufficiently dry so that the ii. Sheet or Plate Materials: 6" squares 1. Installation of metal framing for interior gypsum board shall conform to ASTM C754.
millwork will not be damaged by excessive changes in moisture content. All delivered units shall match the final approved shop b. Submit 2 samples of glass.
drawings and samples. Units which are marred, chipped or otherwise damaged shall be repaired or replaced as determined by the i. Sample Size: 12" x 12" 2. Metal stud gauge for partitions shall be 25 gauge minimum unless noted otherwise. Metal studs at fire rated partitions shall be 20 gauge
Architect. Units shall be protected during shipment and installation. After installation of units in their proper location, all protection shall minimum.
be removed and all surfaces thoroughly cleaned to the complete satisfaction of the Architect. Surfaces shall then be recovered and 4. Quality Assurance Submittals:
protected. a. Certificates: 3. Metal stud framing shall conform to ASTM C754.
i. Provide certification by Safety Glazing Certification Council that safety glazing materials meet specified requirements.
10. Repair or replace damaged or defective millwork wherever deemed necessary. If millwork cannot be adequately repaired, it shall be ii. Provide certification of Heat Checking of tempered glass.
replaced to the satisfaction of the Architect.
5. Contract Close-out Submittals:
11. All standing and running trim pieces shall be plain sawn hardwood Grade I lumber to meet AWI requirements for Premium Grade. a. Submit instructions to be followed in cleaning and maintaining components of system. Include a copy of instruction in Operation and
Maintenance Data Manual.
DIVISION 8 — DOORS AND WINDOWS B. QUALITY ASSURANCE
08100 STEEL DOORS AND FRAMES 1. Regulatory Requirements:
a. Provide glazing at Hazardous Locations as determined by CPSC 16 CFR 1201. Glazing shall be in compliance with Consumer
A. Submittals Product Safety Act and shall have been tested and labeled.
b. Safety glazing shall conform to requirements of ANSI Z97.1.
1. Shop Drawings:
a. Submit shop drawings that show elevations of each door design, door construction details, and methods of assembling sections, C. MATERIALS
hardware locations, and installation methods, dimensions, and shapes of materials, anchorage and fastening methods, door frame
types and details, wall opening construction details, and finish requirements. 1. Glass: Tempered; ASTM C1048
b. Indicate location of each unit in Project. 3
a. Classifications: ASTM C1036; Type 1, class 1, quality q
c. Shop drawings submittal shall be coordinated with shop drawings submission of related portions of Work, such as:

1010 wisconsin avenue, nw


i.) Wood Doors b. Thickness: 1/2"
ii.) Hardware c. Color: Clear

E GEN@COREdc.com
washington, dc 20007
B. Quality Assurance 3. Glazing Channels:
a. Top Channel: 1" x 2" no minal

F 202.466.6235
T 202.466.6116
1. Qualifications: b. Bottom Channel: 1" x 1" nominal
a. Single Source Responsibility: c. Finish: [Stainless Steel #4 , satin brushed ] [Match BHMA #62 5 (US26)]
i.) To greatest extent possible, frames, anchors, etc. shall be products of a single manufacturer or items standard with
manufacturer of hollow metal products.

suite 405
ii.) Provide secondary materials which are produced or are specifically recommended by hollow metal products manufacturer to D. DOOR HARDWARE
ensure compatibility.
1. Overhead Closers:
2. Certifications: a.Concealed overhead closers s hall be hea vy duty, fully hydraulic, full rack and pinion action with
a. Fire doors shall bear labels approved by Underwriters Laboratories, Inc or Warnock Hersey International. Provide fire rated doors
with a label permanently attached to either hinge stile or to top rail, showing testing agency approval for classification scheduled. adjustable sprin g power. Closers s hall be sized in compliance with re quireme nts for accessibility for
ha ndicapped a nd recommendations of ma nufacturer.
C. Hollow Metal Doors b. Acceptable Products:
1. Non-Rated Doors: Seamless hollow steel doors i. Dorma - RTS88
a. Grade: SDI Grade II, Heavy Duty; Model 2 ii. LCN - 6030 Series w/CP 150 pivot
b. Gauge: 18 gauge iii. Norton - 4900 Series w/490 pivot
c. Core Material: Acoustical insulation at interior applications, thermal insulation at exterior applications.
2. Fire Rated Doors: Seamless hollow steel doors
a. Grade: SDI Grade II, Heavy Duty; Model 2 2. Push/Pull Bars: Horizontal push bar/offset pull bar combinati on
b. Gauge: 18 gauge a. Size: 1" diameter
c. Core Material: Acoustical insulation b. Projection: 2 1/2" nominal
d. Label: As indicated on Drawings. c. Offset: 2 1/4" (nominal
d. Mounting:
D. Hollow Metal Frames
i. Pull Bar: 12" center to center
1. Non-Rated Frames: ii. Push Bar: 33" center to center
Printed Date: 6/15/06 at 12:54 PM

a. Gauge: 16 gauge e. Finish: [BHMA #630 (US32D)] [BHMA #625 (US26)]


b. Frames over 4'-0" (1200 mm) wide: 14 gauge f. Acceptable Products:
2. Fire Rated Frames: i. Builders Brass Works - 2960
a. Rated hollow metal frames shall follow same general criteria as indicated for non-rated units. ii. Hiawatha - 658B x 1081 LBP
b. Provide rated units in compliance with ASTM E152. iii. Rockwood - 15847
c. Rated units shall bear UL label certificate indicated on Drawings.
E. INSTALLATION
E. Finishes
1. All-Glass E ntrance System:
1. Shop Priming:
a. Doors and frames shall be chemically treated to ensure maximum paint adhesion and coated, on exposed surfaces, with a rust- a. Install all-glass entrance system in compliance with manufacturer's instructions.
inhibitive primer suitable as a base for finish paints. b. Use a method of attachment to structure to perm it sufficient adjustment to accommodate construction
b. Apply primer of even consistency to provide a uniform finished surface. Allow to fully cure before shipment. tolerances and irregularities.
c. Fit, a lign, and adjust door assemblies plumb and level, to pro vide a smooth operation.
F. Frame Tolerances: ii. Door Sills: 1/4"
iii. Butt Glazing Joints: 3/8", except between sidelights and glass transoms, which shall be 1/8"
1. Squareness: +/- 1/16" (1.5 mm)

DB

CB
Layout: A0.2 Specifications

a. Measured on a line 90 degrees from one jamb, at upper corner of frame at other jamb. 08700 HARDWARE

PERMIT SET
2. Alignment: +/- 1/16" (1.5 mm) A. Product Data:
a. Measured on jambs on a horizontal line parallel to plane of wall.
1. Submit manufacturer's literature describing products to be provided.
3. Twist: +/- 1/16" (1.5 mm)
a. Measured at face corners of jambs on parallel lines perpendicular to plane of wall. B. Shop Drawings:
4. Plumbness: +/- 1/16" (1.5 mm) 1. Submit a minimum of 3 copies of hardware schedule. Indicate location of hardware set, cross-referenced to indications on Drawings,
a.) Measured on jambs at floor. manufacturer's name and product number, finish, and other similar information describing hardware to be provided.

PN 06015.00

ISSUED FOR
DT 6/15/06
G. Door Clearances Subject to +/- 1/32" (.08 mm) tolerance: C. Regulatory Requirements:
1. Head and Jambs: 1/8" (3 mm) 1. Federal Accessibility Regulations:
a. Americans with Disabilities Act - ADA
2. Undercut doors sufficiently to allow clearance above finish floors and where indicated on Drawings to allow for adequate air transfer.
File Name: "PROJECTS:06004 DC Lib - 4200 Wisconsin:06004 DCPL dwgs:3 sheet layouts (.lbks):06004 Modular CD.lbk:06004 Modular CD.lbk"

b. Uniform Federal Accessibility Standards - UFAS


a. Where scheduled floor finish material is less than 1/2" (12 mm) thick, allow not more than 5/8" (16 mm) above top of substrate to
which it is applied. 2. National Fire Protection Association: I CERTIFY THAT THESE DOCUMENTS
b. Where scheduled floor finish material is more than 1/2" (21 mm) thick, allow not more than 1/4" (6mm) above finish material. a. NFPA 80 Standard for Fire Doors and Windows WERE PREPARED OR APPROVED BY ME,
c. Where a threshold is used, allow not more than 1/4" (6mm) above threshold. b. NFPA 101 Life Safety Code AND THAT I AM A DULY LICENSED
c. NFPA 105 Smoke- and Draft-Control Door Assemblies ARCHITECT UNDER THE LAWS OF
H. Adjustments
THE DISTRICT OF COLUMBIA
D. General Requirements:
1. Prime Coat Touch-up:
a. Sand smooth all rusted or damaged areas of prime coat and touch-up with compatible air-drying primer 1. Items of hardware not definitely specified, but needed for satisfactory installation of hardware shall be provided. Such items shall be of
b. Touch-up areas shall not be obvious. type and quality suitable for service needed and comparable to adjacent hardware.
2. Final Adjustments: 2. Doors with locksets shall be furnished with non-removable pins hinges.
a. Check and re-adjust operating finish hardware just prior to final inspection and after painting hinges if hinges are indicated to be
painted. 3. Securely install finish hardware items in compliance with accepted schedule and templates furnished with hardware.
b. Remove and replace defective work.
4. Install locksets, surface mounted closers, and trim after finishing of doors and frames is complete.
08120 ALUMINUM DOOR FRAMES 5. Verify keying requirements with Owner. Furnish 2 keys per lock with a maximum of 8 keys per keyed alike set.
A. Submittals
6. Before final completion, adjust hardware so that doors operate in perfect order. Test and adjust hardware for quiet, smooth operation, free
1. Shop Drawings: of sticking, binding, or rattling. Adjust closers for proper, smooth operation.
a. Submit shop drawings that show elevations of frames, construction details, and methods of assembling sections, hardware
locations, and installation methods, dimensions, and shapes of materials, anchorage and fastening methods, wall opening 7. At final completion, properly tag and identify keys and deliver to Owner.
construction details, and finish requirements.
b. Indicate location of each unit in Project.
c. Shop drawings submittal shall be coordinated with shop drawings submission of related portions of Work, such as: DIVISION 9 — FINISHES
i.) Wood Doors
ii.) Hardware 09000 GENERAL FINISH NOTES
B. Extruded Aluminum Frames A. Submittals:
1. 1. The Contractor shall submit a minimum of three (3) 12" x 12" square samples of each scheduled finish for review by the Architect. The
Architect shall retain two (2) samples of finishes for record and return a minimum of one sample to Contractor.
Finish:
Clear anodized
2. The Contractor shall advise the Architect of locations of changes in dye lots, batches or similar color shifts.
2. Products:
a. Ragland Manufacturing Company, Inc. - RACO Classic Freestanding Series B. Quality Assurance:
b. Avalon Dual Lock Partition System, Inc. - Eagle
1. Before proceeding with procurement of finishes, the Contractor shall field verify dimensions to assure that sufficient quantities of
C. Tolerances: materials are ordered to complete the work.

Specifications
1. Squareness: +/- 1/16" (1.5 mm) 2. The Contractor shall refer to the Drawings for specific locations of finishes. Should the Contractor find any discrepancies, omissions,
a. Measured on a line 90 degrees from one jamb, at upper corner of frame at other jamb. ambiguities or conflicts on the plans, the Contractor shall bring the item(s) to the attention of the Architect for direction, before ordering
materials or proceeding with any work in question.
2. Alignment: +/- 1/16" (1.5 mm)
a. Measured on jambs on a horizontal line parallel to plane of wall. 3. Finishes to be installed in strict accordance with the manufacturer's specifications and instructions and in a manner consistent with the
highest quality standards of workmanship.
3. Twist: +/- 1/16" (1.5 mm)
a. Measured at face corners of jambs on parallel lines perpendicular to plane of wall. 4. Where there is a question as to the acceptable level of quality for the installation of any materials, the Architect shall act as mediator.
4. Plumbness: +/- 1/16" (1.5 mm) 5. Upon receipt from the manufacturer, inspect materials for defects, flaws, shipping damage, correct color and pattern. Prior to beginning
a.) Measured on jambs at floor. work, damaged or wrong materials shall be returned to the manufacturer for immediate replacement to prevent delays in the completion
of the work.
D. Adjustments
6. Compliance with the manufacturer's requirements for handling, storage, installation and protection is the exclusive responsibility of the
1. Check and re-adjust operating finish hardware just prior to final inspection. Contractor.

7. Finishes shall extend over, under and/or behind any item of built-in millwork, equipment, mirrors, etc., as indicated on the drawings.

A0.2
© core group, pc 2006
DC Public Library - Anacostia
1801 Good Hope Road SE
Washington, DC, 20020
SPECIFICATION NOTES 01060 REGULATORY REQUIREMENTS intent of the Contract. No payment whether partial or final, shall be construed as an acceptance of defective Work or improper materials

DIVISION 1 — GENERAL REQUIREMENTS A. The Work shall comply with applicable codes, amendments, rules, regulations, ordinances, laws, orders, approvals, etc., that are
required by public authorities. In the event of conflict, the most stringent requirements shall govern. Requirements include, but are 01500
01010 not necessarily limited to, the currently applicable editions or publications of the following: CONSTRUCTION FACILITIES AND TEMPORARY CONTROLS
SUMMARY OF WORK
1. International Building Code 2000 A. The Contractor is responsible for and shall provide protection for any existing finishes including elevators, lobbies, stairs, and corridors of the
A. Unless otherwise noted, "The Owner" refers to the persons, organization and/or business entering into an agreement with the 2. DC Construction Code Supplement of 2003 base building.
Contractor to execute the Work indicated in the Contract Documents. "The Landlord" refers to the person, organization and/ or 3. International Mechanical Code 2000 B. The Contractor shall protect existing base building window coverings.
business that owns or is responsible for managing the property on which the Work is to be executed. The Contractor's 4. International Plumbing Code 2000
responsibilities to each party are described in the specifications and documents below. 5. International Fire Code 2000 C. The Contractor shall patch and repair fireproofing damaged or removed during performance of the Work. Fireproof new penetrations
6. NFPA National Electrical Code 1996 required by the Work.
B. The "Work" includes Owner improvements to an existing tenant space and includes new partitions, finishes and modifications to
HVAC, plumbing, electrical, and fire protection systems. D. Debris shall be removed from the site on a daily basis. Upon completion of the Work, remove debris from the site created by the Work
B. Install building standard fire extinguishers and cabinets where required by applicable codes as directed by the Architect (Provide and provided under the Contract and leave areas clean.
C. Owner-supplied items include: install any additional code-required fire extinguishers and cabinets where directed by code officials and/or the Architect).
E. The Contractor shall be required to maintain a job site telephone and fax machine.
1. Furniture 01300 SUBMITTALS
2. Appliances
3. Equipment A. Within seven (7) days of the contract award, the Contractor shall submit to the Architect a schedule of all submittals identifying 01700
4. Data and telephone cabling and equipment estimated date of submission. Submittals shall include but are not limited to: CONTRACT CLOSEOUT
5. Security system and equipment
6. Computer cabling and equipment 1. Finishes A. When the Contractor considers that the Work is substantially complete, the Contractor shall prepare and submit to the Architect a list of items
2. Carpet seaming diagram to be completed or corrected. The Architect shall visit the site to determine the status of completion and amend the Contractor's list as
D. Permits and Inspections 3. Doors, frames, and hardware required. Upon the Contractor’s stated completion of the items listed to be completed or corrected, and prior to final payment, the Architect
shall perform a final inspection of all items listed. Failure to complete listed items, as determined by the Architect, shall require additional site
4. Glass visits as needed by the Architect to determine final completion. The cost of any additional site visits shall be billed hourly based on the
1. The Contractor is responsible for obtaining all necessary permits required to perform the Work. 5. Metals Architects published hourly rates and shall be deducted from the Contractor's final payment.
6. Millwork
2. The Contractor is responsible for inspections required for the jurisdiction in which the Work is performed. Verify with local 7. Equipment B. The following items shall be submitted to the Owner by the Contractor before requesting final payment:
regulatory agency exact number, type and schedule of inspections required for the Work prior to commencing with the Work. 8. Appliances
9. Mechanical equipment, diffusers, grilles, devices, etc. 1. Complete release or waiver of liens — documentation shall be notarized and signed.
3. The Contractor shall provide the Owner with documentation and scheduling necessary for Occupancy Permit. 10. Electrical equipment, light fixtures, controls, devices, etc.
11. Plumbing equipment, fixtures, devices, etc. 2. Certificates of inspection approvals for required occupancy permit and similar approvals or certifications by governing authorities,
4. The Building Permit will be obtained by an agent of the Owner. 12. Sprinkler plan assuring the Owner's full access and use of completed Work.

E. Contract Documents B. Preparation of submittals shall be as follows: 3. A notebook containing warranties, bonds, guarantees, affidavits and certificates required by the Contract Documents. Include any
operating and cleaning instructions for appliances, materials, finishes, systems and equipment installed as part of the Work.
1. The AIA “General Conditions of the Contract for Construction” AIA Document A201, 1997 edition, published by the American 1. Submit one (1) reproducible copy and two (2) prints of each shop drawing.
Institute of Architects, hereinafter referred to as “General Conditions”, is hereby made part of the Contract Documents, the same C. Final Cleaning: Remove protective coatings, coverings, any tags, labels or other markings from materials fixtures and equipment. Clean
wall, floor and ceiling surfaces including trim, outlet and switch plates, windows, window sills, and window treatments. Clean plumbing

1010 wisconsin avenue, nw


as if bound herein. 2. For catalog cuts, brochures, and other standard printed or published product data, submit number of copies needed by
Contractor, plus two (2) copies to be retained by Architect. fixtures to a sanitary condition.

E GEN@COREdc.com
2. The Contract Documents consist of the following:

washington, dc 20007
3. The Contractor shall submit a minimum of three (3) samples of finishes. The Architect shall retain two (2) samples of finishes for DIVISION 2 — SITEWORK
a. Owner-Contractor Agreement ("The Contract") record and return a minimum of one sample to Contractor.
b. General Conditions

F 202.466.6235
T 202.466.6116
02070
c. Drawings as dated in agreement ("The Drawings") C. The Contractor shall provide manufacturer's specifications, installation instructions, shop drawings and samples for review and SELECTIVE DEMOLITION
d. Addenda approval prior to ordering or proceeding with the Work. No construction shall proceed until submittals are approved.
e. Modifications A. Extent of demolition is indicated in the Drawings.

suite 405
D. Contractor shall allow five (10) working days for the Architect and Consultants to the Architect to review submittals. All submittals not
3. The Contract Documents are instruments of service and shall remain the property of the Architect whether the project for which reviewed directly by the Architect, but rather Consultants to the Architect, shall be submitted simultaneously to both the Architect and B. Protect finishes indicated to remain during demolition.
they are prepared is executed or not. The Contract Documents are not to be used by the Owner, Landlord or Tenant for other the Consultant and shall be noted as such. The Contractor shall not proceed with work until both Architect and Consultant have
projects or extensions to the project nor are they to be modified in any manner whatsoever except by agreement in writing and approved the submittal. No extension of the contract time will be granted because of failure to provide submittals for the Architect's C. Following demolition, base building partitions should be cleaned and prepared for proposed tenant construction per review of Architect and
with appropriate compensation to the Architect. review or coordination in a timely fashion. the Contractor. Surfaces indicated as existing to remain shall be restored to like-new condition. Surfaces indicated as existing to remain and
to receive new finishes shall be properly prepared to receive indicated finishes.
01025 MEASUREMENT AND PAYMENT E. The Architect reserves the right to reject any and all items installed without prior review and approval by the Architect.
D. Prior to demolition, the Contractor shall schedule a meeting with the Owner and the Architect to review all items to be salvaged. Salvaged
A. Prior to commencing with the Work, the Contractor shall submit to the Architect the following information: F. Refer to specified items for specific submittal requirements. items may not necessarily be indicated for reuse. Salvaged items may include:

1. A Schedule of Values indicating the components of Work listed in sufficient detail to the satisfaction of the Architect and the • Millwork
• Doors, frames, and hardware.
Owner to serve as a basis for computing values for Applications for Payments during construction. 01400 QUALITY CONTROL • Lay-in ceiling panels and ceiling grid.
• All glass entrance system components.
2. A construction schedule for the Work in bar chart form. This schedule will be used as the basis for evaluating progress of the A. Dimensions and Tolerances: • HVAC diffusers, grilles, equipment and controls
Work and Applications for Payments. • Electrical equipment, lighting fixtures and controls
1. Do not scale drawings; dimensions govern. Verify dimensions with field conditions. If discrepancies are discovered between
B. The above schedule will be used as the basis for evaluating progress of the Work and Applications for Payments. field conditions and drawings or between drawings, contact the Architect for resolution before proceeding. E. Extent of items to be reused is indicated in the Contract Documents. Dispose of remaining items determined not to be salvaged in a safe,
clean, manner and in accordance with local, state and federal regulations.
C. Applications for Payment shall use AIA Document G702. Applications are to be notarized and bear the signature of an authorized 2. Horizontal dimensions indicated are to/from finished face of construction, except as noted.
officer. F. Make safe abandoned electrical conduits.
3. Vertical dimensions are from top of floor slab, except where noted to be from above finished floor (AFF), as measured from the
D. Only approved Change Orders are to be indicated on Applications for Payment. high point of the slab. Contractor to notify the Architect when deviation is greater than allowed in note 4 below. G. Terminate abandoned plumbing at entry to tenant space.
Printed Date: 6/15/06 at 12:54 PM

4. Floor Tolerance: The Contractor is to immediately verify slope and report any deviation over a 1/4 inch slope in 10 feet to the H. G.C. to prepare site grading and improvements required for building foundation, utilities, stairs and ramps to meet finish grade.
01030 ALTERNATES AND UNIT PRICES Architect prior to commencing Work. The Contractor shall be responsible for leveling all areas to achieve a slope deviation of
less than 1/4 inch slope in 10 feet. The Contractor shall ensure an absolute level floor under all swinging and sliding doors.
A. The Contractor shall provide pricing for all alternates indicated in the bid form.
5. Dimensions are not adjustable without approval of the Architect unless noted (±).
DIVISION 3 — CONCRETE
B. The Owner reserves the right to reduce or increase the total Scope of Work by accepting any of the Alternates or added/deleted Unit
Price items. 6. Dimensions indicated to be "clear' or "clr" shall be maintained. Any discrepancies or variations in these dimensions shall be FOUNDATIONS AND FOOTINGS
reviewed with the Architect before beginning construction.
A. G.C. to provide structural design drawings of foundation and footings with soils report documents soil type bearing capacity and water
01035 SUBSTITUTIONS 7. Any dimension noted "Verify" or "VIF" must be reviewed with the Architect before beginning construction. table elevation.
A. The Contractor's bid shall be based on providing all specified items. Substitutions shall be considered only under the following 8. The Contractor shall continuously check Architectural and structural clearances for accessibility of equipment and mechanical
circumstances: and electrical systems. No allowance of any kind will be made for the Contractor's failure to foresee means of installing DIVISION 5 — METALS
equipment into position inside structures.
1. The specified item is accompanied by the words "equal to". References to makes, brands, models, etc., is to establish type and 05500
quality desired. B. Observation of Work: METAL FABRICATIONS

DB

CB
Layout: A0.1 Specifications

2. The item is shown to have a prohibitively long lead time. 1. The Architect, acting as the Owner's designated agent for design of this project, will exercise sole authority for determining A. Submittals: Minimum of three (3) 3 1/2" x 12" samples of metals indicated in the finish schedule.

PERMIT SET
conformance of materials, equipment and systems with the intent of the design. Review and acceptance of items proposed by
3. An item of equal appearance and equal or greater quality to the specified item can be provided at substantial savings to the Contractor for incorporation into the Work will be by the Architect. This function of the Architect will apply both to Contract as B. All cold rolled steel shall match Architects sample and be prepared in the following manner (this metal is highly reactive and
Owner. initially signed, and to the changes to Contract by modification during progress of Work. must be carefully cleaned and sealed. All work is to be performed while wearing rubber gloves or white cotton gloves to keep
oils from hands away from metal):
B. Substitutions shall be considered by the Architect for acceptance under the following procedure. 2. If at any time before commencement of Work, or during progress thereof, the Contractor's methods, equipment or appliances are 1. Prepare surface with a light brushing to remove loose surface scale (leave most of scale on metal).
inefficient or inappropriate for securing quality of Work, or rate of progress intended by Contract Documents, the Owner may
1. The Contractor shall make all requests for substitutions within seven (7) days of contract award. order the Contractor to improve their quality or increase their efficiency. This will not relieve the Contractor of his sureties from 2. Clean carefully with an automotive metal conditioner (a degreasing agent). A clean rag must be used and changed

PN 06015.00
their obligations to secure quality of Work and rate of progress specified in contract.

ISSUED FOR
frequently to avoid accumulation of oil and grease on rag.

DT 6/15/06
2. The Architect requires seven (7) days for review of the Contractor's request for substitution.
C. Reference to Standards: 3. Seal the metal with one mm thick of an matte finish automotive clear coat acrylic lacquer enamel.
3. The Contractor's request for substitution shall include product information and samples as deemed necessary by the Architect of
both the specified item and proposed substitution. Characteristics of both products shall be clearly identified for the Architect's 1. Materials and workmanship specified by reference to number symbol, to title of a specification such as commercial standards, 4. All materials used must be approved by Architect prior to construction.
evaluation. federal specification, trade association standard, or other similar standard, shall comply with requirements in latest edition or
File Name: "PROJECTS:06004 DC Lib - 4200 Wisconsin:06004 DCPL dwgs:3 sheet layouts (.lbks):06004 Modular CD.lbk:06004 Modular CD.lbk"

revision thereof and with any amendment or supplement thereto in effect on date of origin of this project's Contract Documents.
Such standard, except as modified herein, shall have full force and effects as though printed in Contract Documents. DIVISION 6 - WOODS AND PLASTICS I CERTIFY THAT THESE DOCUMENTS
01040 COORDINATION WERE PREPARED OR APPROVED BY ME,
2. The Contractor shall waive "Common Practice" and "Common Usage" as construction criteria wherever details and Contract 06200
AND THAT I AM A DULY LICENSED
A. Coordination with Base Building and other Building Tenants: Documents or governing codes, ordinances, etc., require greater quantity or better quality than common practice or common FINISH CARPENTRY
ARCHITECT UNDER THE LAWS OF
usage would require.
A. Submittals: THE DISTRICT OF COLUMBIA
1. Exercise extreme care and precaution during construction of the Work. Schedule Work to minimize disturbances to
D. Existing Conditions:
adjacent spaces and/or structures and their occupants, property, public thoroughfares, etc. 1. Submit shop drawings and hardware catalog cuts of all millwork hardware for review by the Architect in accordance with the
1. The Contractor shall be responsible for checking Contract Documents, field conditions, and dimensions for accuracy and requirements of the Contract Documents. Shop drawings shall show the design and dimensions, and clearly indicate in large scale the
construction of the various components, reinforcements, and all other pertinent data and information as required for construction. Any
The Contractor shall take precautions and be responsible for the safety of building occupants from construction procedures. The confirming that Work is buildable as shown before proceeding with construction. Clarification regarding any conflicts shall be variation from the drawings must be clearly noted as a variation from the requirements. Fabrication of millwork shall not proceed until
Contractor shall be responsible for any overtime costs incurred thereby. received prior to related Work being started. A complete site survey is required by G.C. location all existing utilities and services shop drawings have been reviewed by the Architect.
as well as topographic informatiion prior to starting work.
2. The Contractor shall be required to meet all Landlord requirements for construction. 2. The contractor shall submit a minimum of three (3) 12" x 12" samples of all millwork finishes (including stone and metal) for approval.
2. The Contractor shall notify the Owner in writing of any deficiencies in base building construction prior to the commencement of The Architect shall retain two (2) samples of finishes for record and return a minimum of one sample to Contractor. In circumstances as
3. The Contractor shall coordinate with Landlord all Work required by the Tenant that occurs outside the Tenant space and is on or this Work. Any unreported deficiencies will become the responsibility of the Contractor to correct. appropriate, size of samples may be reduced if requested in writing by Contractor and approved by Architect prior to submission.
within the base building. The contractor is responsible for the installation and integrity of all penetrations required to the existing Finishing of millwork shall not proceed until samples have been reviewed.
roof and for meeting all Landlord requirements. E. In the event of conflict between the Drawings and the Specifications, the Specifications shall govern. Detail drawings take
precedence over drawings of larger scope. Should the Contractor at any time discover an error in a drawing or specification, or a 3. The Contractor shall provide the Architect with anticipated delivery date for all millwork. The Contractor shall continue to monitor in
4. The Contractor shall review the base building Contract Documents and shall comply with base building requirements and design discrepancy or variation between drawings, or a discrepancy or variation between dimensions and measurements at site, or lack of writing the anticipated delivery dates until all finish materials have been received.
criteria. dimensions or other information, the Contractor shall not proceed with the Work affected until clarification has been made.
B. Verification of Existing Conditions:
5. Prior to drilling slab penetrations, the Contractor shall do the following: F. The Contractor shall coordinate and review the layout and exact location of the items listed below in the field prior to construction.
a. Clearly identify location of slab penetrations for Architect's review. Any conflicts that arise shall be brought to the Architects attention in writing for resolution prior to proceeding with construction: 1. Before proceeding with the millwork, the Contractor is to obtain field measurements, verify dimensions, and provide shop drawings and
b. Coordinate with existing conditions below slab to insure no conflicts with existing ductwork, sprinkler piping, ceiling 1. Partitions details to ensure an accurate fit. Any variance found in the field must be brought to the attention of the Architect prior to fabrication. It is
conditions, etc. 2. Doors the responsibility of the Contractor to coordinate with the millwork subcontractor any revisions or clarifications issued by the Architect.
b. X-ray proposed slab penetration locations to identify structural conflicts as required by Landlord. 3. Core drill locations
2. The Contractor shall provide field layout of all work and report any discrepancies to the Architect.
4. Electrical/telephone outlets
B. Coordination with Owner- Supplied items: 5. Thermostats C. Execution of the Work:
6. Light switches
1. Make necessary provisions for items to be furnished or installed by Owner as indicated on the drawings. Such provisions 7. Light fixtures 1. The method of manufacturing, fabricating and installing millwork and equipment and its structural components defined in the Contract
include, but are not limited to, plumbing & electrical requirements. 8. Changes in ceiling plane, and other ceiling features Documents is representative and indicates design intent only. If the materials, details or dimensional properties are at variance with the
9. VAV boxes, supplemental AC units and other mechanical, electrical, or plumbing items requiring ceiling access or affecting Contractor's or manufacturer's recommendations, alternate details will be considered for review when shop drawings are submitted in
2. Provide protection for Owner-supplied items until completion of the project. ceiling height accordance with the Contract Documents. It shall be the responsibility of the Contractor to guarantee that the millwork and equipment
will have proper support, stability, and fault-free performance. All work shall conform to Architectural Woodwork Institute (AWI)
3. The Contractor is to include the installation cost of Owner-supplied items unless otherwise noted. G. The Contractor shall follow manufacturer's recommended specification & installation procedures. If these are contrary to the standards for premium construction.
Contract Documents, the Contractor shall notify the Architect, in writing, immediately, to resolve discrepancies prior to proceeding.
4. Any ambiguity or need for clarification regarding scope of Work related to Owner-supplied items is to be reviewed with the 2. It is the intent of the Architect that the hardware represent the highest quality and lasting durability for its specific function. If, in the
Architect prior to commencing with the Work. H. Only new items of recent manufacture, of the highest quality, free from defects, will be permitted on the Work. Rejected items shall opinion of the Contractor, the hardware indicated on the drawings does not represent the above-stated intent, the Contractor shall notify
be removed immediately from the Work and replaced with items of the quality specified. Failure to remove rejected materials and the Architect in writing with stated reasons and proposed substitutions.

Specifications
5. Telephone and data work shall be coordinated by the Contractor with Owner's representative. equipment shall not relieve the Contractor from the responsibility for quality and character of items used nor from any other obligation
imposed by the Contract. 3. Millwork indicated to have transparent finishes shall be constructed according to AWI standards for premium grade construction.
6. Security system work shall be coordinated by the Contractor with Owner's representative.
I. The finished Work shall be firm, well anchored, in true alignment, plumb, level, with smooth, clean, uniform appearance without
C. Cut and fit components for alteration of existing work and installation of new work. Patch disturbed areas to match adjacent waves, distortions, holes, marks, cracks, stains, or discoloration. Jointings shall be close fitting, neat and well scribed. The finish
materials and finishes. work shall have no exposed unsightly anchors or fasteners and shall not present hazardous, unsafe corners. Work shall have the
provision for expansion, contraction, and shrinkage as necessary to prevent cracks, buckling and warping due to temperature and
D. Prior to construction, the Contractor shall verify that no conflicts exist in locations of any mechanical, telephone, electrical, plumbing humidity conditions.
and sprinkler equipment (to include piping, duct work, structural members and conduit) and that required clearances for installation
and maintenance of above equipment are provided. Elements in conflict shall be determined and reviewed with Architect for J. Attachments, connections, or fastenings of any nature are to be properly and permanently secured in conformance with best practice
resolution prior to construction. and the Contractor is responsible for improving them accordingly. The drawings show only special conditions to assist the
Contractor. They do not illustrate every such detail.
E. Contractor shall order and schedule delivery of materials in ample time to avoid delays in construction. If an item is found to be
unavailable or have a long lead time, the Contractor shall notify Architect within seven (7) days of contract award. K. No Work defective in construction or quality or deficient in any requirements of drawings and specifications will be acceptable in
consequence of the Owner's or Architect's failure to discover or to point out defects or deficiencies during construction; nor will presence
of inspectors on Work relieve the Contractor from responsibility for securing quality and progress of Work as required by the Contract.
Defective Work revealed within required time guarantees, as specified in the Contract, shall be replaced by Work conforming with the

A0.1
© core group, pc 2006
DC Public Library - Anacostia
1801 Good Hope Road SE
Washington, DC, 20020
4. Metal runners shall correspond in size and gauge to metal studs. Metal runners shall be continuous and attachment shall be at 24" on B. Prepare the existing, base building slab prior to installation of the scheduled flooring. All surfaces shall be sealed, sized or properly prepared FABRICATION
center unless noted otherwise. per manufacturer's specifications and recommendations. The Contractor shall flash patch all uneven floor slab surfaces in order to provide a
flat, smooth and continuous floor surface. A. General Requirements:
5. Metal furring shall be spaced at 24" on center unless noted otherwise.
C. VCT shall be laid in straight grid (not basket weave) direction. Refer to drawings for color patterns and direction. 1. Shading system components shall be manufactured and assembled to allow for custom installation techniques to suit Project conditions.
C. Fire Rated Gypsum Board Partitions
D. 2 1/2" cove base shall be used at all VCT locations. 2 1/2" straight base shall be used at carpet locations unless noted otherwise. The 2. Finished assemblies shall be, square, true to size and free from distortion, twist, or other defects that could effect their strength,
1. Fire rated partitions shall conform to UL design number indicated. Refer to UL Fire Resistance Directory - Volume I (latest edition) for Contractor shall use inside and outside corners and end stops for all areas specified. Use roll goods only. No seam shall occur within 6" of operation or appearance.
additional information. an outside corner.
3. Fabric shall be colorfast , and retain its shape, and shall not be affected by moisture or heat. Cut fabric to eliminate glare and
2. All Mechanical, Electrical, and Plumbing penetrations in fire rated partitions shall be sealed at their perimeter with approved fire rated E. Install black resilient transition/reducer strip between VCT and other floor finishes. reverberation from shining surfaces maintaining exterior view. Top of fabric shall be retained in recessed spline of shade roller; bottom
sealer. of fabric shall be retained in extruded hem bar.
D. Sound Rated Partitions 09680 CARPET 4. Fasteners shall be non-corrosive type, suitable for intended application.
1. Sound rated partitions shall conform to ASTM E497, Standard Practice for Installing Sound-Isolating Lightweight Partitions. A. Submittals B. Aluminum Fascia:
2. All Mechanical, Electrical, and Plumbing penetrations in sound rated partitions shall be sealed at their perimeter with approved 1. Shop Drawings: 1. Fascias shall be custom designed closures to fit onto premoulded end mounting brackets without exposed fasteners.
acoustical sealer. a. Clearly indicate locations of seams, methods of joining seams, direction of carpet, type of adhesive to be used, method of
integrating resilient trim with carpet, and installation procedures. D. Shade Fabric:
E. Gypsum Board Finish Notes
2. Samples: 1. Top of fabric shall be retained in recessed spline of shade roller; bottom of fabric shall be retained in extruded hem bar, without exposed
1. Gypsum board shall be installed and finished to within 1/4" of floor slab. a Submit a minimum of three samples of each carpet to be used, sufficiently sized to clearly indicate construction, but not less than fasteners.
12" x 12".
2. All Gypsum board panel joints, joints to existing construction, edge trim, corner beads, and pre-formed reveals shall be tapped, bedded b. Submit samples, 12" long, of moldings and trims. E. Hem Bar:
in joint compound, and sanded smooth with no visible joints. Provide proper backing for all reveals as recommended by manufacturer.
B. Project Conditions 1. Bar shall be shaped steel profile, engineered to weight requirements, insert in welded hem bar pocket and closed ends, to maintain
3. Outside corners of gypsum board shall have metal corner beads (screwed type), unless noted otherwise. bottom of shade fabric straight and flat.
1. Field measurements:
4. Metal edge trim shall match USG #200B series and shall be in sizes corresponding to gypsum board thickness. a. Verify dimensions in field that may affect installation. Installer shall be responsible for accuracy of measurements of total yardage, INSTALLATION
individual floor yardage requirements, dye lot yardage placement, extra yardage for pattern matching, and roll length requirements.
5. Alignment of door heads and other critical horizontal elements shall be maintained at a constant level relative to the ceiling plane, and A. General requirements:
shall not follow variations in floor plane. 2. Surface Preparation:
a. Clean floors of dust, dirt, solvents, oil, grease, paint, plaster, and other substances which could be detrimental to proper 1. Make accurate measurements of site conditions before fabrication. Check layout of glazing framing sections, spans, and loading
6. Partition types above door are to be same as the adjacent partitions unless noted otherwise. performance of adhesive and carpet. Allow floors to thoroughly dry. capabilities.
b. Remove sub-floor ridges and bumps. Fill low spots, cracks, joints, holes, and other defects, using subfloor filler compatible with
7. Align face of partitions with face of adjacent column unless noted otherwise. carpet and adhesives. 2. Shades shall be install by manufacturers' skilled installers in strict compliance with manufacturers' recommendations.
c. Use an approved cementitious filler to patch cracks, small holes, and for leveling. Do not use gypsum-based leveling and patching
8. Provide additional studs as required to achieve outlet groupings. Coordinate with engineering drawings. materials. 3. Shades shall be installed plumb, square, and rigidly coupled, adequately anchored. Maintain uniform clearances, accurate alignment
levels and parallel installation with window plane.
F. Blocking C. Installation

1010 wisconsin avenue, nw


4. Install tube with shade fabric already attached. Shade fabric shall be pre-measured and manufactured off-site.
1. Wood blocking shall be fire retardant treated (FRT). Install wood blocking as required in partitions at wall hung shelving, cabinets, 1. General Requirements:
artwork, toilet partitions and accessories, etc. Verify blocking requirements with millwork subcontractor and review with the Architect for a. Check matching of carpet before installing and ensure there is no visible variation between dye lots.

E GEN@COREdc.com
5. Adjust shades and operating components as needed to ensure smooth and trouble free operation without binding. Fabric shall hang flat

washington, dc 20007
acceptance prior to installation. b. Do not place heavy objects such as furniture on carpeted surfaces for a minimum of 24 hours or until adhesive has set. without buckling or distortion. Replace units or components which cannot be adjusted to hang properly or operate smoothly.
c. Entire carpet installation is to be laid tight and flat to subfloor, well fastened at edges, and present a uniform pleasing appearance.
09300 TILE Ensure a monolithic color, pattern and texture match within area.

F 202.466.6235
T 202.466.6116
DIVISION 15 - MECHANICAL
A. Submittals 2. Layout:
a. Lay carpet on floors with pile in same direction of anticipated traffic. Do not change run of pile in one room. A. G.C. to provide mechanical plan showing all diffusers and duct layouts. Where ceiling is open and return air duct is required undercut doors
1. Tile samples indicating all sizes, shapes, and colors. b. Fit carpet neatly and snugly around projections through floor and to walls and other vertical surfaces with no gaps.

suite 405
in rooms with finished ceilings. Exhaust all bathrooms to exterior.
2. Grout color 3. Transitional Moldings and Trim:
DIVISION 16 — ELECTRICAL
B. Installation method a. Install resilient trim where carpet terminates at other floor coverings, or at carpet termination that does not abut a vertical surface. (Note: Refer to engineering drawings for complete electrical specifications.)
Use full length pieces only. Butt tight to vertical surfaces. Where splicing cannot be avoided, butt ends tight and flush.
1. Floor surfaces: Tile Council of America installation # F113-96, dry-set mortar or latex-Portland cement mortar. 16050 BASIC MATERIALS
D. Protection
2. Vertical surfaces: Tile Council of America installation # W242-96, thin set organic adhesive. A. Electrical receptacles shall be Decora by Leviton (800-323-8920). Color shall be black except for receptacles on dedicated circuits which
1. If needed to protect finished installation from dirt or paint, or if additional work is to be done after installation, cover carpet with a non- shall be gray and isolated ground receptacles which shall be orange. Receptacle faceplates shall be stainless steel with a satin or brushed
C. Prepare the existing base building slab prior to installation of tile. All surfaces shall be sealed, sized or properly prepared per manufacturer's staining building material paper. Plastic sheeting shall not be used over carpet installation. finish.
specifications and recommendations. The Contractor shall flash patch all uneven floor slab surfaces in order to provide a flat, smooth and
continuous floor surface. 2. Protect installation from rolling traffic by using sheets of hardboard or plywood in affected areas. B. Switches shall be Decora by Leviton (800-323-8920). Color shall be black. Switch faceplates shall be stainless steel with a satin or brushed
finish.
D. Install white marble threshold at doors that define transitions between ceramic tile and other floor finishes. Threshold shall be shaped to 3. Traffic over adhesive applications shall be restricted for a minimum of 24 to 48 hours to allow proper adhesive cure.
meet ADA requirements. C. Dimmers shall be Decora by Leviton (800-323-8920) or visually match Decora style. Dimmers shall be compatible with light fixtures and
4. Temperature of carpeted areas shall not fall below 50 degrees F, regardless of age of installation. ballasts. Color shall be black. Faceplates shall be stainless steel with a satin or brushed finish where possible - faceplates shall match
09900 PAINTING dimmer at other locations.
09510 ACOUSTICAL CEILINGS

A. Submittals A. Submittals

1. Submit a minimum of three samples of the following: 1. Provide a minimum of three 12” x 12” samples for each color and each finish indicated in the finish schedule.
a. Acoustical ceiling panels: 6" x 6" minimum
Printed Date: 6/15/06 at 12:54 PM

b. Suspension system components: 12" in length B. Products

B. Quality Assurance 1. See finish schedule for manufacturers, colors and finishes.

1. To the greatest extent possible, materials, including exposed wall moldings, suspensions systems, and accessories, shall be products of C. Execution
a single manufacturer or items standard with manufacturer of acoustical ceiling panel units.
1. General:
C. Materials a. Prior to paint application, the Contractor shall schedule a review of final paint color locations with the Architect in the field.
b. See finish plan and interior elevations for specific locations of paint colors and finishes.
1. Suspension system: ASTM C635 c. Where paints of two different types or colors abut, the seam shall be on an inside corner only.
a. Grid Components: d. Final coat of paint shall be roll applied at all GWB surfaces.
i.) Exposed Tee: Die cut and interlocking
ii.) Wall Moldings: Hemmed angle 2. Preparation:
iii.) Face dimension: 15/16" a. Remove blistered, peeling and scaling paint or chalk deposits to sound substrates.
iv.) Finish: Baked polyester paint b. Completely remove sealants or caulking.
v.) Color: c. Dull glossy surfaces.
1.) White at locations with acoustical ceiling panels d. At metal surfaces, remove rust, oil, grease and other contaminants harmful to painting. Sand clean and spot prime.
2.) Black at locations with open grid e. At GWB surfaces; repair surface defects with joint compound, fill flush and sand smooth. Clean surfaces of dust, grease and dirt.

DB

CB
f. At wood surfaces; sand smooth and remove dust. Countersink nails and fill nail holes, cracks and open joints with putty or wood
Layout: A0.3 Specifications

b. Acceptable Products:
i.) Armstrong - Prelude XL Exposed Tee System filler.

PERMIT SET
ii.) USG Interiors - DX Grid System
3. Application (unless noted otherwise):
2. Acoustical Ceiling Panels: ASTM E1264 a. At GWB surfaces:
a. Size: 24" x 24" One (1) primer coat: Vinyl acrylic primer sealer.
b. Thickness: 3/4” Two (2) finish coats: Vinyl acrylic latex; eggshell finish @ walls, flat @ ceilings.
c. Edge: Beveled tegular lay-in
d. Color: White b. At interior wood surfaces to be painted:
e. Acceptable Products: One (1) primer coat: Alkyd enamel underbody.

PN 06015.00

ISSUED FOR
Two (2) finish coats: Vinyl acrylic latex semi-gloss enamel.

DT 6/15/06
i.) Armstrong - Angled Tegular Cirrus c. At interior metal surfaces to be painted:
ii.) USG Interiors - Eclipse Tapered One (1) primer coat: Rust-inhibiting alkyd primer.
Two (2) finish coats: Alkyd gloss enamel.
D. Installation
File Name: "PROJECTS:06004 DC Lib - 4200 Wisconsin:06004 DCPL dwgs:3 sheet layouts (.lbks):06004 Modular CD.lbk:06004 Modular CD.lbk"

4. Clean-up:
1. Grid System: a. The Contractor shall provide one final touch-up of paint surfaces after the Owner has moved into the space.
I CERTIFY THAT THESE DOCUMENTS
a. Install grid system in compliance with ASTM C636, manufacturer's instructions, and as supplemented in this section. WERE PREPARED OR APPROVED BY ME,
b. Install grid system in a true, even plane and in straight courses as indicated on Drawings and accepted shop drawings.
c. Coordinate and fit ceiling components to grilles, lighting fixtures, and other related items. In determining location and spacing of DIVISION 12 - FURNISHINGS AND THAT I AM A DULY LICENSED
hangers and primary runners, take into consideration weight of grilles, light fixtures, etc., that are to be installed in conjunction with ARCHITECT UNDER THE LAWS OF
acoustical ceilings. 12490 - WINDOW SHADES THE DISTRICT OF COLUMBIA
d. Provide stabilizer bars, clips, splices, and edge moldings needed for a complete installation.
e. Hang grid system independent of walls, columns, ducts, pipes and conduit. Where carrying members are spliced, avoid visible SUBMITTALS
displacement of face plane of adjacent members.
f. Where ducts or other equipment prevent regular spacing of hangers, reinforce nearest affected hangers and related carrying A. Product Data:
channels to span extra distance.
g. Do not support components on main runners or cross runners if weight causes total dead load to exceed maximum deflection 1. Submit manufacturer's literature describing products to be provided.
limitations. Support fixture loads by supplementary hangers located within 6" (150 mm) of each corner; or support components
independently. B. Samples:
h. Do not eccentrically load system, or produce rotation of runners.
1. Submit minimum of 3 samples of each shade fabric. Sample Size: 6" x 6"
2. Moldings and Trim
a. Install wall moldings at intersection of suspended ceiling and vertical surfaces, using longest practical lengths. Provide moldings at
junctions with other interruptions and as needed to cover edges of acoustical ceiling panels. MANUAL CHAIN SHADES
b. Attach moldings and trims with screws spaced not more than 16" (400 mm) on center and within 3" (75 mm) of ends of each piece A. Acceptable Manufacturers:
being installed.
c. Moldings and trim shall be level with suspension system and within tolerances specified for suspension system. 1. Direct Path Corp. - Nysan Shading Systems
d. Miter corners and align butt joints where wall moldings intersect to form tight, hairline joints.
e. Face riveting of moldings and trim shall not be acceptable. 2. MechoShade Systems Inc.

3. Tolerances B. Manual Chain Operator: Unitized premoulded construction


a. Deflection of grid components shall not exceed 1/360 of span.
b. Variation from Flat and Level Surface: 1/8" (3 mm) in 10 feet (3000 mm) maximum. 1. Mounting Brackets: L shaped steel
c. Variation from Plumb of Grid Members: 2 degrees maximum; caused by eccentric loads. a. Size: 2 7/8" x 3"

E. Adjusting and Cleaning 2. Drive Chain: #10 stainless steel


a. Strength: 90 lbs. test
1. Follow grid system manufacturer's recommendations for methods and materials to clean and touch-up exposed components.
C. Shade Tube Assembly: Extruded aluminum tube
2. Replace components which are discolored or damaged in any way, in a manner which results in grid system showing no evidence of
replacement work. 1. Size: 1 3/8" diameter
2. Finish: Anodized; clear
09650 RESILIENT FLOORING
D. Aluminum Fascia: Extruded aluminum; 6063-T5 alloy
A. Submittals:

Specifications
1. Size: 3" x 2" nominal
1. Vinyl composition tile sample.
2. Thickness: 1/16"
2. Black resilient transition/reducer strip (provided at changes in flooring).
3. Finish: Match adjacent window framing
3. Vinyl cove and straight base.
F. Shade Fabric: PVC coated fiberglass fabric
1. Selections: Refer to Schedule of Finishes

2. Fire Performance Characteristics: NFPA 701; pass

D. Manual Chain Operator:

1. Unitized premoulded construction, shipped completely assembled from factory requiring only a few on-site adjustments to install.

2. Chain operator assembly shall be set for travel length of shade, on-site without disassembly of hardware.

3. Drive chain shall be #10 stainless steel, strength for 41 kg (90 lb.) test; Manufactured with precise automatic braking system, to
eliminate breakage of chain under normal usage.

A0.3
4. Shade shall not be operable by pulling hem bar downward.

© core group, pc 2006


SYMBOL LEGEND ABBREVIATIONS VICINITY MAP PROJECT INFORMATION

DC Public Library - Anacostia


1801 Good Hope Road SE
Washington, DC, 20020
1X One-inch nominal thickness JAN Janitor
Office Room Name 2X Two-inch nominal thickness JST Joist Project Name: DC Public Library - 1801 Good Hope Road SE, 20020
001 Room Number Project Number: 6015
@ At JT Joint
ABV Above KIT Kitchen
Project Description: New retail space
Detail Number AC Air Conditioning LAV Lavatory
2 Detail-Section ACOUS Acoustical LEV Level
A0.3 ACT Acoustical Ceiling Tile LH Left Hand Governing Code: International Building Code 2000
Sheet Number ADJ Adjacent, Adjustable LT Light DC Construction Code Supplement 0f 2003
AFF Above Finish Floor LTG Lighting International Mechanical Code 2000
International Plumbing Code 2000
Detail Number ALT Alternate MAS Masonry
International Fire Code 2000
2 ALUM Aluminum MATL Material NFPA National electrical Code 1996
Detail-Plan
A2.0 ANCH Anchor MAX Maximum International Energy Conservation Code 2000
Sheet Number ANOD Anodized MDO Medium Density Overlay International Fuel Code 2000
APPROX Approximate MECH Mechanical
Type of Construction: IIIB
ASSY Assembly MEMB Membrane
Section Number
2 AVG Average MEZZ Mezzanine
A2.0 Building Section BD Board (or Bead, if applicable) MFR Manufacturer('s)
Sheet Number BTWN Between MIN Minimum
BLDG Building MISC Miscellaneous Use Group: Assembly Group M
Business Group B
BLKG Blocking MLDG Molding
Elevation Number BLT Bolt MO Masonry Opening Building Stories: 1
2
BM Beam MTL Metal Project Stories: 1
A2.0 Exterior Building Elevation
BOT Bottom MTD Mounted Area: project gross square feet: occupancy:
Sheet Number Ground Floor Library (M): 3,828 64
BRG Bearing MTG Mounting
Ground Floor Office (B): 200 2
BRK Brick MW Microwave Oven Total Project Gross Area: 4,028 66
BSMT Basement N North occy by sf
1 Elevation Number BYD Beyond NIC Not in Contract Area of Work:
4 2
Interior Elevation-Plan CAB Cabinet NO Number
3 Exits Required: 2 stairway .2"
A2.1 Sheet Number CEM Cement # Number
egress width required: 13.16
CER Ceramic NTS Not to Scale egress width is compliant
CJ Control Joint OA Overall

1010 wisconsin avenue, nw


Exits Provided: 2
1 Window Designation CLO Closet OD Outside Diameter

E GEN@COREdc.com
No

washington, dc 20007
CLAD'G Cladding OC On Center Sprinklered:

Equipment Designation CLG Ceiling OFF Office


1 Fire Alarm: No

F 202.466.6235
T 202.466.6116
CLR Clear OPNG Opening
CMU Concrete Masonry Unit OPP Opposite Accessibility: New layout is accessible with handrails and ADA compliant fixtures
COL Column P Pole

suite 405
1 Sheet or Work Note CONC Concrete PART Partition 1801 Good Hope Road SE Plumbing Fixture Requirement: 1 toilet for 500 occupants required required WC: required Lav:
1/2 men = 0.07 0.04
CONST Construction PERIM Perimeter
1/2 women = 0.07 0.04
CONT Continuous PG Paint Grade total : 0 0.1
C
L Centerline CONT'R Contractor PL Plate EGRESS DIAGRAM
CPR Copper PLAM Plastic Laminate bathroom fixtures per floor: Provided WC: Provided Lav:
CPT Carpet PLAS Plaster Ground Floor 2 2
Alignment with Established Element 33
CORR Corridor PLEX Plexiglass 170
CS Cast Stone PLMB Plumbing
CSK Countersink PLYWD Plywood Service Sink Provided @ Ground Flr: 1 New
Elevation above grade – Building CT Ceramic Tile PMVT Pavement Drinking Fountain @ Ground Flr: 1 New
+ 32.16'
Section or Building Elevation CTR Center POLY Polyethylene
Printed Date: 6/15/06 at 12:54 PM

CTRD Centered PR Pair

8'-6" Elevation above finished floor –


CW
DBL
Cold Water
Double
PSF
PSI
Pound Per Square Foot
Pound Per Square Inch
DRAWING INDEX
Plans DEMO Demolish, Demolition PT Pressure Treated
DET Detail PTD Painted ARCHITECTURAL
DF Drinking Fountain PVC Polyvinyl Chloride
DG Double Glazed QT Quarry Tile A0.1 SPECIFICATIONS
Revision Cloud and Marker DIA Diameter A0.2 SPECIFICATIONS
QTY Quantity
DIM Dimension R Riser(s);Radius A0.3 SPECIFICATIONS
1 DN Down RO Rough Opening A0.4 PROJECT INFO, DRAWING INDEX
DS Downspout R= Radius A0.5 DOOR TYPES / HARDWARE SCHEDULE
DW Dishwaher RAD Radius A0.6 PARTITION TYPES
E Existing to remain DWG Drawing RDG Removable Double Glazing
Layout: A0.4 Project Info, Drawing Index

E East RECPT Receptacle A1.1 CONSTRUCTION PLAN


R Existing relocated EA Each REF Refigerator
A1.2 FIXTURE / MILLWORK PLAN
EJ Expansion Joint REG Register
A1.3 REFLECTED CEILING PLAN
ELEC Electric(al) REINF Reinforcing
A1.4 FINISH PLAN

DB

CB
ELEV Elevation REPL Replace(ment)
EMER Emergency REQ;REQ'D Required

PERMIT SET
1 Partition type A2.1 ELEVATIONS
EP Energy Panel RESIL Resilient
EQ Equal REV Revision A2.2 ELEVATIONS
EQUIP Equipment RM Room
1 Door type 33
ETR Existing to Remain RL Ridge Line A4.1 DETAILS
340
A Hardware set EWC Electric Water Cooler S Shelf;Shelves A4.2 DETAILS
S4S Surface Four Sides

PN 06015.00

ISSUED FOR
EXIST Existing A4.3 DETAILS

DT 6/15/06
EXH Exhaust SC Solid Core Actual
xx
EXP Expansion, Exposed SCHED Schedule(d) EGRESS LEGEND xx Capacity
EXT Exterior SDG Siding
Earth
File Name: "PROJECTS:06004 DC Lib - 4200 Wisconsin:06004 DCPL dwgs:3 sheet layouts (.lbks):06004 Modular CD.lbk:06004 Modular CD.lbk"

FA Fire Alarm SECT Section


FBO Furnished by Owner SG
SHT
Single Glazed
Sheet
MECHANICAL / ELECTRICAL I CERTIFY THAT THESE DOCUMENTS
FD Floor Drain WERE PREPARED OR APPROVED BY ME,
FDTN Foundation SHTG Sheathing P100 PLUMBING DATA SHEET AND THAT I AM A DULY LICENSED
Gravel ARCHITECT UNDER THE LAWS OF
FE Fire Extinguisher Cabinet SIM Similar P200 PLUMBING FLOOR PLAN
THE DISTRICT OF COLUMBIA
FF Finish Floor SM Smooth Lumber Molding Desig. E100 ELECTRICAL DATA SHEET
FGLAS Fiberglass SPEC Specification E200 ELECTRICAL POWER PLAN
FIN Finish SQ Square E300 ELECTRICAL LIGHTING PLAN
Concrete
FIX Fixture S. STL Stainless Steel
FLASH Flashing ST Street
FLR Floor STD Standard
Brick FLUOR Fluorescent STL Steel
FOM Face of Masonry STOR Storage
FOS Face of Structure(or Face of Stud, STRUC Structure
where applicable) SUBFL Subfloor
Concrete Masonry Unit FRT Fire Retardant Treated SURF Surface

Project Info, Drawing Index


FRMG Framing SUSP Suspend
FT Feet T Tread(s)
FTG Footing T&G Tongue and Groove
Cut Stone
FURN Furniture TBS To Be Specified
FURR Furring TEL Telephone
GA Gauge TEMP Temperature
Metal (See material designation & GALV Galvanized THK Thick
schedule for type)
GB Grab Bar TLT Toilet
GC General Contractor TO_ Top of (----)
Glass TRTD Treated
GFI Ground Fault Interrupter
GL Glass TYP Typical
GWB (Large scale) GWB Gypsum Wall Board UL Underwriters Laboratories, Inc.
GYP Gypsum UNO Unless Noted Otherwise
HB Hose Bib UON Unless Otherwise Noted
Medium Denisty Overlay (MDO) Board/
Oriented Strand Board (OSB) HC Hollow Core UTIL Utility
HD Head V Volt
Plywood HDBD Hardboard VL Valley Line
HDR Header VB Vapor Barrier
HDWR Hardware VCT Vinyl Composition Tile
Lay-in Ceiling Tile (Acoutical Panels) VENT Ventilate(-or)
HDWD Hardwood
HORIZ Horizontal VIF Verify in Field
HT Height W West
Insulation (Loose or Batt) WC Water Closet
HTR Heater
HVAC Heating/Ventilation/Air-Conditioning WD Wood
Insulation (Rigid) HW Hot Water WDW Window
IG Isolated Ground WF Wide Flange
IN Inch WH Water Heater
Wood Blocking/ Shim
INCL Include(d) WP Waterproofing

A0.4
INSUL Insulation WS Weather Stripping
Wood Blocking – Continuous
INT Interior W/ With
Wood – Finished W/O Without
WT Weight
Carpet WWM Welded Wire Mesh
© core group, pc 2006
DC Public Library - Anacostia
1801 Good Hope Road SE
Washington, DC, 20020
6"

6"
DOOR AND FRAME SCHEDULE

2"

2"
DOOR FRAME

SEE SCHEDULE
SIZE DETAIL FIRE RATING SET NO NOTES
MARK MATL MATL TYPE
TYPE WD HGT HEAD JAMB
D01 E1 3' 7' metal metal E2 H1/A0.4 J1/A0.4 C
D02 E1 3' 7' metal metal E2 H1/A0.4 J1/A0.4 B
D03 E1 3' 7' metal metal E2 H1/A0.4 J1/A0.4 A
D04 E3 6' 7' metal/glass metal E2 H1/A0.4 J1/A0.4 E

GLASS FOR D04 TO BE G1 (1" INSULATED LOW-E GLASS)

2" 6" 6" 6" 6" 2"

10"
2"

2"
3' SEE SCHEDULE 3'

HARDWARE SCHEDULE
ALL EGRESS DOORS SHALL BE OPERABLE IN THE DIRECTION OF TRAVEL WITHOUT THE USE OF A KEY OR SPECIAL KNOWLEDGE.
Glass Door Type
HARDWARE ITEM A B C D E F DESCRIPTION E3 SCALE: 3/8'' = 1'-0''
LATCH/LOCK SCHLAGE AL SERIES, CYLINDRICAL LATCH AND LOCKSETS. OR APPROVED EQUAL BY SEARGENT, OR BEST
AND LEVER SET LOCK, OR YALE.

FRONT ENTRY SET

REAR ENTRY SET


OFFICE LOCKSET

PASSAGE SET
STORE ROOM

RESTROOM
SEE SCHEDULE

2"

1010 wisconsin avenue, nw

E GEN@COREdc.com
washington, dc 20007
LEVER LOCKSET X X X X X SCHLAGE SATURN LEVER 626

F 202.466.6235
T 202.466.6116
HINGES X X X X X X BOMMER #5000 - 5 KNUCKLE, FULLY MORTISED BUTT HINGE (QTY. 3)
OR EQUAL BY HAGER.

suite 405
DOOR STOP X X X IVES #WS401CVX / WS402 CVX GRAY RUBBER STOPPER

SILENCERS X X X X IVES SR66 OR EQUIVALENT

COAT HOOK X X IVES 405 COMMERCIAL/PUBLIC GRADE ALUM CAST COAT/HAT HOOK
2" 2"

CLOSER X X X IVES 405


Printed Date: 6/15/06 at 12:54 PM

X X
KICK PLATE 24" HIGH METAL FULL WIDTH OF DOOR
Frame Type
HOLD OPEN X IVES PLUNGER TYPE FS1153 E2 SCALE: 3/8'' = 1'-0''
CRASH BAR X X

CONTRACTOR TO COORDINATE SECURITY REQUIREMENTS WITH OWNER.

DOOR AND HARDWARE NOTES:


Layout: A0.5 Door Types / Hardware Schedule

1. G.C. to provide full submittal package of all Doors and Hardware prior to proceeding with work.

2. See Architectural Plans A1.1 for symbol locations.

SEE SCHEDULE
3. All hardware finishes to be US26D UON.

DB

CB
4. G.C. to coordinate and provide all necessary cut-outs in door and millwork frames for security cabling, locking
devices, and accessories. G.C. to coordinate work between trades. Procure template from owners' security

PERMIT SET
vendor and coordinate as required.

5. All egress doors shall be operable in the direction of travel without the use of a key or special knowledge.

6. All hardware requirements indicated in plans and specifications shall be coordinated with Owner for all items
prior to placement of materials order.

PN 06015.00
SEE SCHEDULE

ISSUED FOR
DT 6/15/06
7. All lockes to be Sergeant master-keyed; confirm with Owner.

8. Hardware specified for each leaf unless otherwise noted.


Door Type
File Name: "PROJECTS:06004 DC Lib - 4200 Wisconsin:06004 DCPL dwgs:3 sheet layouts (.lbks):06004 Modular CD.lbk:06004 Modular CD.lbk"

9. Clean and adjust existing hardware to remain.


E1 SCALE: 3/8'' = 1'-0''
I CERTIFY THAT THESE DOCUMENTS
WERE PREPARED OR APPROVED BY ME,
AND THAT I AM A DULY LICENSED
ARCHITECT UNDER THE LAWS OF
THE DISTRICT OF COLUMBIA

Door Types / Hardware Schedule


A0.5
© core group, pc 2006
DC Public Library - Anacostia
1801 Good Hope Road SE
Washington, DC, 20020
UNDERSIDE OF STRUCTURE

HEAD
UNDERSIDE OF STRUCTURE

FACE OF EXISTING PARTITION

3/4"
OR STRUCTURE TOP TRACK

HEAD
ACOUSTICAL SEALANT

1/2" SHIM SPACE

PLAN
1/2" GWB.

SCHED PARTITION 1/2" GWB., BOTH SIDES, TYP.


METAL STUD

PLAN
ADJACENT PARTITION
(WHERE OCCURS) 3 5/8" METAL STUD
@ 16" O.C.

6"
1/2" 7/16"
SOUND ATTENUATION BLANKET (STC-50)

BASE

BASE
HOLLOW METAL FRAME

2"
- GROUT SOLID AT WALL BASE AS SCHEDULED
RATED DOORS
WALL BASE AS SCHEDULED

1010 wisconsin avenue, nw


CONT MTL RUNNER ANCHORED
TO SLAB

E GEN@COREdc.com
CONT MTL RUNNER ANCHORED

washington, dc 20007
TO SLAB ACCOUSTICAL SEALANT
SCHED DOOR
FINISHED FLR'G FINISHED FLR'G

F 202.466.6235
T 202.466.6116
ACCOUSTICAL SEALANT

1/4"

suite 405
TOP OF FILL SLAB

STUD LIMITING PARTITION SOUND FIRE STC STUD LIMITING PARTITION SOUND FIRE STC
NO. SIZE GAUGE SPACING HEIGHTS WIDTH BATTS RATING RATING REMARKS NO. SIZE GAUGE SPACING HEIGHTS WIDTH BATTS RATING RATING REMARKS
HM Door Head
H1 SCALE: 3'' = 1'-0''
002A 2 1/2" 25 16" 11'-3" 3 5/8" 3" non rated STC-50 001A 3 5/8" 25 16" 14'-4" 4 7/8" 3" non rated STC-50

002B 3 5/8" 25 16" 14'-4" 4 7/8" 3" non rated STC-50 001B 6" 25 16" 19'-9" 7 1/8" 3" non rated STC-50
HM Door Jamb
J1
Printed Date: 6/15/06 at 12:54 PM

SCALE: 3'' = 1'-0''

Partion Type Partion Type


002 SCALE: 3'' = 1'-0''
001 SCALE: 3'' = 1'-0''
Layout: A0.6 Partition Types / Schedule

DB

CB

PERMIT SET
PN 06015.00

ISSUED FOR
DT 6/15/06
File Name: "PROJECTS:06004 DC Lib - 4200 Wisconsin:06004 DCPL dwgs:3 sheet layouts (.lbks):06004 Modular CD.lbk:06004 Modular CD.lbk"

I CERTIFY THAT THESE DOCUMENTS


WERE PREPARED OR APPROVED BY ME,
AND THAT I AM A DULY LICENSED
ARCHITECT UNDER THE LAWS OF
THE DISTRICT OF COLUMBIA

GENERAL NOTES
1. ALL STUDS SHALL BE 25 GAGE, 16" O.C. UNLESS NOTED OTHERWISE

2. GYPSUM WALL BOARD SHALL BE TYPE "X" FIRE RATED AT FIRE RATED PARTITIONS

3. MOISTURE RESISTANT GYPSUM WALL BOARD SHALL BE USED AT ALL PARTITIONS

Partition Types / Schedule


SCHEDULED TO RECEIVE CERAMIC TILE.

4. REFER TO FINISH SCHEDULE FOR WALL, FLOOR, BASE AND CEILING FINISHES.

5. FIRE RATED PARTITIONS SHALL CONFORM TO THE REQUIREMENTS OF THE


REFERENCED TESTING AGENCY DESIGN NUMBER. ASSEMBLIES CONFORMING TO
EQUIVALENT REQUIREMENTS BY OTHER TESTING AGENCIES ARE ACCEPTABLE IF
APPROVED BY THE LOCAL CODE COMPLIANCE DEPARTMENT.
6. LIMITING HEIGHTS FOR GYPSUM WALL BOARD PARTITIONS ARE BASED ON A
LATERAL LOAD OF 5 PSF AND A DEFLECTION CRITERIA OF L/240 FOR PRODUCTS OF THE
NATIONAL GYPSUM COMPANY. CONTRACTOR SHALL VERIFY THAT APPROVED PRODUCTS
FROM OTHER MANUFACTURERS MEET L/240 DEFLECTION CRITERIA. IF REQUIRED TO
MEET CRITERIA, STUD GAGE AND/OR SPACING SHALL BE DECREASED, OR BRACING
SHALL BE ADDED ABOVE THE CEILING.
7. AT PARTITIONS SCHEDULED TO RECEIVE CERAMIC TILE FINISH, CONTRACTOR
SHALL PROVIDE ASSEMBLIES MEETING L/360 DEFLECTION CRITERIA.
8. PARTITION TYPES ARE CONTINUOUS AROUND CORNERS AND ACROSS DOOR AND
WINDOW OPENINGS, UNLESS NOTED OTHERWISE.

A0.6
© core group, pc 2006
DC Public Library - Anacostia
1801 Good Hope Road SE
Washington, DC, 20020
1010 wisconsin avenue, nw

E GEN@COREdc.com
washington, dc 20007
DN

F 202.466.6235
T 202.466.6116
2
CONSTRUCTION GENERAL NOTES CONSTRUCTION LEGEND

suite 405
A. Refer to A0.4 for partition types and details. Existing Perimeter Wall
D05

3'CLR
D02 D02 01B
New Interior Full-Height Wall 02A 02A
B. All dimensions shown are from finished faces of partitions. 5'CLR 18'-6"CLR 2'-11" 15'-4"CLR
1 Partition Type - Refer to Sheet A0.4 01A
01A 01A
1' 1'
C. Base building partitions should be clean and prepared for proposed tenant construction per review of 01A SEE FIXTURE PLAN

ALIGN
Architect and G.C. Areas that are scheduled originally or currently with gyp. bd. should be paint ready. New Interior Low -Height Wall

7'-6"CLR
01B
1 Partition Type - Refer to Sheet A0.4 02A
CL

5'CLR
D01
D. Alignment of door heads and other critical horizontal elements shall be maintained at a constant level D03

relative to the ceiling plane, and shall not follow variations in the floor plane. New Door
E. All architectural, electrical, and non-structural systems, components attached to existing structure shall 1 Door Type - Refer to Sheet A0.4
01A D01
comply with all applicable code. 02B 01A 02B

8'CLR
CLR
2'-9" 18'-4" 2'-9"
F. Dimensions indicated to be "clear" or "hold" shall be maintained. Any discrepancies or variations in these 01A
EQ EQ
8'-6"CLR
dimensions shall be reviewed with the Architect before beginning construction.

G. Any dimension noted "VIF" must be reviewed with the Architect before beginning construction.
Printed Date: 6/15/06 at 12:54 PM

01A
02A 02B
H. Provide and install fire retardant wood blocking in partitions at wall hung shelving, cabinets, etc. Verify 12'-4"CLR
shop standard with millwork subconstractor and review with the Architect for acceptance prior to CONSTRUCTION WORK NOTES
installation. Coordinate blocking requirements for millwork with plans and details. 5
1 MODULAR WINDOW CENTERED ON STANDARD MODULAR BAY.
I. Provide bracing to deck above at door jambs, windows, and millwork that goes to ceiling. 2 PAINTED PRESSURE TREATED WOOD LANDINGS, STAIRS, AND RAMPS. EXTENT
BASED ON SITED CONDITIONS. DESIGN BY ARCHITECT.
J. Provide additional studs as required to achieve outlet groupings. Coordinate with engineering drawings.
3 CHAINLINK FENCE WITH VINYL GRAPHIC BANNER. GRAPHIC TBD.
K. Contractor to examine extent of existing partitions and report any discrepancies to Architect prior to the 4 PAINTED PRESSURE TREATED WOOD CANOPY DESIGN BY ARCHITECT
start of construction. COORDINATES WITH STAIR LANDING AND RAMP.
6

67'-4"CLR
L Dashed lines indicate lines of ceiling overhead. 5 MODULAR HVAC UNIT
6 STRUCTURE ABOVE, TYP
M. Locate typical door opening 4" away from adjacent wall corner. Keep minimum 18" clearance from latch to
Layout: A1.1 Construction Plan

3
wall on pull side of all doors per ADA guidelines. 7 SECURITY NIC - BY OWNER

DB

CB
1

PERMIT SET
N. G.C. to replace any removed or damaged existing fireproofing material at deck, beams, or existing
partitions.

48'-4"CLR

ALIGN
O. Partition types above door are to be same as the adjacent partitions unless noted otherwise.

P. Coordinate all elevations and detail information with plans.

PN 06015.00

ISSUED FOR
DT 6/15/06
Q. Provide glavanized metal corner beads and/or trim for all exposed gypsum board edges and corners,
spackle and sand smooth.
File Name: "PROJECTS:06004 DC Lib - 4200 Wisconsin:06004 DCPL dwgs:3 sheet layouts (.lbks):06004 Modular CD.lbk:06004 Modular CD.lbk"

I CERTIFY THAT THESE DOCUMENTS


WERE PREPARED OR APPROVED BY ME,
AND THAT I AM A DULY LICENSED
ARCHITECT UNDER THE LAWS OF
THE DISTRICT OF COLUMBIA

01A

02A 02A
7

2'-8"CLR
D04
1' 12'-4"CLR 3'

RAMP
2 DN DN

CL

Construction Plan
A1.1
© core group, pc 2006
DC Public Library - Anacostia
1801 Good Hope Road SE
Washington, DC, 20020
1010 wisconsin avenue, nw

E GEN@COREdc.com
washington, dc 20007

F 202.466.6235
T 202.466.6116
JANITORS CLOSET STORAGE OFFICE
FIXTURE SCHEDULE FIXTURE WORK NOTES
TYPE SPECIFICATION NOTES

suite 405
12 13 12
1. ALL PERIMETER SHELVING TO BE RE-USED EXISTING SHELVING PROVIDED
F1 CIRCULATION DESK BY OWNER AND MODIFIED ACCORDING TO SPECIFICATIONS BY ARCHITECT. 15
G.C. TO COORDINATE WITH OWNER ON QTY AND FINISH. E6
F2 BOOK DROP 2. SEE A2.1-A2.2 FOR INTERIOR ELEVATIONS 9
3. SEE A1.4 AND A2.1 FOR FINISH INFORMATION E1
MENS
F3 ROTATING DIPLAY GONDOLAS 4. ALL FURNITURE NIC 6
8
7 E2
E11
F4 TOUCHDOWN DESK 18
YOUNG ADULT
E12 7 READING
F5 READING DESK

F6 AUTOCHECKOUT STATION E12

F7 COMPUTER DESK E11


4
WOMENS
F8 TASK CHAIR FIXTURE WORK NOTES E3
Printed Date: 6/15/06 at 12:54 PM

1 BOOK DROP
F9 COFFE TABLE
2 WINDOW DISPLAY AREA
F10 LOUNGE CHAIR
3 POS PROVIDED BY OWNER
4 NOT USED
F11 CHILDREN'S READING TABLE 5 WORK COUNTER
6 AUTO CHECKOUT PROVIDED BY OWNER ADULT
F12 CHILDREN'S COMPUTER TABLE
7 VEN MACHINE PROVIDED BY OWNER COMPUTERS
ADULT
F13 CHILDREN'S CHAIR
8 COPIER PROVIDED BY OWNER LOUNGE
9 TRASH CANS PROVIDED BY OWNER
F14 COMPUTER STATION 10 NOT USED
1 3
11 SORTING DESK
F15 BAR HEIGHT STOOLS
COMPUTER TOWER AND SCREEN PROVIDED BY OWNER
Layout: A1.2 Fixture/Millwork Plan

12

F16 LOUNGE CHAIRS


13 PRINTER PROVIDED BY OWNER
ADULT

DB

CB
14 SEE 4/A4.3 AND 5/A4.3 5 READING
F17 SIDE TABLE 15 SEE 1/A4.3

PERMIT SET
16 SEE 6/A4.3
F18 TASK CHAIR CHILDRENS
17 SEE 3/A4.3 COMPUTERS
18 SEE 2/A4.3
F19 BOOK CART CIRCULATION
14
DESK
F20 OFFICE DESK ADULT

PN 06015.00
COMPUTERS

ISSUED FOR
FIXTURE LEGEND

DT 6/15/06
16
F21 OFFICE DESK
3
NEW MILLWORK
F22A BOOKSHELF
File Name: "PROJECTS:06004 DC Lib - 4200 Wisconsin:06004 DCPL dwgs:3 sheet layouts (.lbks):06004 Modular CD.lbk:06004 Modular CD.lbk"

F22B BOOKSHELF
I CERTIFY THAT THESE DOCUMENTS
CHILDRENS WERE PREPARED OR APPROVED BY ME,
F22C BOOKSHELF
READING AND THAT I AM A DULY LICENSED
ARCHITECT UNDER THE LAWS OF
F23 BOOK DROP THE DISTRICT OF COLUMBIA

2
EQUIPMENT SCHEDULE
TYPE SPECIFICATION MANUFACTURER NOTES 2 2

EX
EXISITNG FIXTURES 17 17
/ EQUIPMENT
HOT F23
REFRIGERATOR SUMMIT APPLIANCES SUMMIT ALB-751/3
E1
718-893-3900 32" H, 23 5/8" W, 23 1/2" D TOPICS

E2 SINK ELKAY ELKAY BLR150C


630-574-84848 15"X15"

E3 ADA DRINKING ELKAY ELKAY SOFT SIDE


FOUNTAIN 630-574-84848 BARRIER FREE ECDFPW314C

E4
MIRROR BOBRICK BOBRICK B-165 1624
518-877-7444
TOILET PAPER BOBRICK BOBRICK B-4288
E5
DISPENSER 518-877-7444
PAPER TOWEL BOBRICK BOBRICK B-4262
E6
DISPENSER 518-877-7444

Fixture/Millwork Plan
A1.2
© core group, pc 2006
DC Public Library - Anacostia
1801 Good Hope Road SE
Washington, DC, 20020
1010 wisconsin avenue, nw

E GEN@COREdc.com
washington, dc 20007

F 202.466.6235
T 202.466.6116
RCP GENERAL NOTES RCP WORK NOTES

suite 405
A. All lighting dimensions are from the center of the fixtures to finish face of partitions and from center of the
1
DEDUCT ALTERNATE 1:
fixtures to center of the fixtures. IF BOTTOM OF STRUCTURE 7'-10" AFF BOTTOM

A.2
OF LIGHTING FOR TYPES H.1-H.3 TO BE 7'-0" AFF AND CEILING PLANES K
B. Ceiling details are provided to illustrate design intent. General contractor to advise any alternative
FOR TYPE CC TO BE CONVERTED AS FOLLOWS: F

A.3
construction details which may expedite construction schedule, pending Architect's approval.
K TYPE
9'9" AFF TO 7'9" AFF +10'-0" F CB A.3

B
C. Refer to electrical dwgs for the following information: specification, power requirements, circuitry, switching, 9'6" AFF TO 7'8" AFF
AFF

emergency lighting, location & type of exit sign, strobe & pulls. 9'3" AFF TO 7'7" AFF +10'-0"
AFF F H +10'-0"
G

A.2
D. Refer to mechanical drawings for air diffusers, returns, and tranfer ducts. 2 EXPOSED CEILING, TYP. NO EXPOSED INSULATION - TO BE COVER ED WITH
AFF

E. Any discrepancies with light fixtures, switches, thermostats, diffusers as to location between Architectural PAINTED PLYWOOD.
and Engineering drawings or between the drawings and existing field conditions shall be clarified with the
Architect before proceeding with installation. +10'-0" A.3 A.1
AFF
F.

A.2
All multiple switch locations are to be ganged and installed with a single face plate. Cover plates shall not
be cut and butted together. G
Printed Date: 6/15/06 at 12:54 PM

J J J
G. Thermostats and strobes to be centered above light switch UNO
H. The GC shall be responsible for electrical work to be done in strict accordance with applicable codes,
regulations and requirements for the governing body having jurisdiction. A.2 A.4 A.1

I. All exposed ceiling area to be clean and prepare to be painted. Remove protrusions and unidentified debris TYPE
as required. Existing devices that can easily be relocated are to be relocated. Abandoned devices to be CB
removed in exposed area. H
H A.2 A.2
J. Fixtures shown suspended from structure are to be supported independently from mechanical or electrical
+10'-0"
devices. AFF
J J J
K. Ceiling open to exposed structure UNO, paint P4 +10'-0"
AFF

A.3
L. Paint all existing exposed ductwork and mechanical P4
Layout: A1.3 Reflected Ceiling Plan

TYPE

A.2
CB A.3
M. See A4.1 and A4.2 for ceiling type details and lighting fixture assignments for ceiling type CC.

A.4
2

DB

CB

PERMIT SET
+9'-3"
J J J

A.4
AFF
A.3
LIGHT FIXTURE LEGEND RCP LEGEND A.4

A.2
TYPE TYPE
LSI SINGLE CIRCUIT PENDANT MOUNTED CC
A.1 Existing ceiling to remain. CB
DIMMABLE TRACK (120V) +9'-6"
AFF
4' LENGTH
+9'-9"

PN 06015.00
+10'-0"

ISSUED FOR
AFF
LSI SINGLE CIRCUIT PENDANT MOUNTED

DT 6/15/06
A.2 New GWB Ceiling AFF

DIMMABLE TRACK (120V) +9'-3" 1 J J J


AFF
8' LENGTH
Ceiling tile to be ACT-1 per finish schedule
File Name: "PROJECTS:06004 DC Lib - 4200 Wisconsin:06004 DCPL dwgs:3 sheet layouts (.lbks):06004 Modular CD.lbk:06004 Modular CD.lbk"

LSI SINGLE CIRCUIT PENDANT MOUNTED A.4 A.4


A.3
A.3 DIMMABLE TRACK (120V) I CERTIFY THAT THESE DOCUMENTS
12' LENGTH +9'-6" A.1 WERE PREPARED OR APPROVED BY ME,
Patch existing GWB Ceiling AFF
+9'-3" AND THAT I AM A DULY LICENSED
LSI SINGLE CIRCUIT PENDANT MOUNTED AFF ARCHITECT UNDER THE LAWS OF
A.4 DIMMABLE TRACK (120V) THE DISTRICT OF COLUMBIA
J J J
FIELD CUT TO FIT SPECIFIED LENGTH

A.3

A.3
Items on finish floor below
+9'-3"
AFF
LIGHTOLIER 2X4 RECESSED FLUORESCENT A.4 A.1 A.1 A.1 A.1 A.4
B Suspended and stained MDF
(2) 54W T5 HO 3500K
QHE 2 G PF OP 2 54 120 PI
LSI WALLWASHER
C PAR38 HALOGEN (250W MAX)
120V DIMMABLE
239-00 S WL W/ C995
LSI ACCENT LIGHT
D PAR38 HALOGEN (250W MAX)
120V DIMMABLE
238-00 S WL W/ C998
EPI DOWNLIGHT
E 100W 120V
A19 INCANDESCENT
A19/4 COL
EPI WALLWASHER

Reflected Ceiling Plan


F 100W 120V
A19 INCANDESCENT
A19/4 WW COL
G LIGHTOLIER VANITY LIGHT - WALL MOUNTED
(2) T8 120V 3500K
BCW6X48 SW4S232HPFUNVHI

H.1 ARTEMIDE CASTORE (SUSPENDED FIXTURE)


H.2 (VARIOUS DIAM) H.1=6" , H.2=10", H.3 = 14"
H.3 DIMMABLE 100W INCANDESCENT

H ZUMTOBEL 8' LINEAR PENDENT


(4) 54W T5 HO 3500K
ETHOS EE45458T305

I ADA COMPLIENT
WALL SCONCE (TBD)
100W INCANDESCENT

J LIGHTOLIER PENDANT
CFL MULTI TRIPLE TUBE
4 X 26/32/42 W 120V
DIMMABLE

K 4' UTILITY STRIP FLUORESCENT


SURFACE MOUNT W/ LENS
32W T8 120V 3500K

A1.3
© core group, pc 2006
DC Public Library - Anacostia
1801 Good Hope Road SE
Washington, DC, 20020
1010 wisconsin avenue, nw

E GEN@COREdc.com
washington, dc 20007

F 202.466.6235
T 202.466.6116
FINISH GENERAL NOTES FINISH WORK NOTES

suite 405
1. Refer to A0.2 and A0.3 or additional notes and specificications.
2. Refer to elevations and details for specific locations of all finishes. Any discrepancies, omissions,
ambiguities, or conflicts between the drawings should be brought ot the attention of the Architect for
direction before proceeding with the work in question. P2
3. G.G. shall provided one final touch-up of painted surfaces after the tenant has moved into the space.
4. Ceiling registers, vents, grills, diffusers, speakers, etc. shall be painted in flat finish to match ceiling. P2
5. Finishes called for shall extend over, under, and/or behind any item of built-in millowrk, equipment, mirrors, P6 T1 VCT1
etc. as indicated on drawings.
6. Paint door frames to match adjacent partitions in semi-gloss finish u.o.n.
7. Locate floor finish transitions below centerline of doors, u.o.n.
8. Transitions between dissimilar floor finishes are to align. P3
9. Where floor finishes appear to align with partitions, align all edges and widths.
10. Partitions concealed with millwork are to be taped, mudded, sanded smooth, primed, and painted with one T1
coat of finish paint. P3 P3
11. Flooring material to be installed under all millwork. P6
12. Paint all access panels to match adjacent painted surface.
13. G.C. to provide Architect with submittals of all finish materials for review and approval prior to ordering and
installation.
14. Floor finishes inside closets are to be the same as that of the space into which the closet door opens.
15. All wood base splices shall be puttied and sanded smooth prior to painting for invisible seam.
Printed Date: 6/15/06 at 12:55 PM

16. All finishes are to be installed in strict accordance with the manufacturer's specifications and instructions.
17. G.C. to provide blocking in partitions as required to secure millwork as shown. C1
18. All walls to be P1 unless otherwise noted.
19. See elevations for additional finish information

FINISH SCHEDULE
TYPE SPECIFICATION MANUFACTURER / SPECIFICATION

CLG1 Ceilng deck painted P4

DB

CB
2x2 Armstrong Optima Open Plan ceiling tile with
CLG2 Ceiling tile Benjamin Moore grid and 4" inverted axiom perimeter trim
Layout: A1.4 Finish Plan

PERMIT SET
Gray
P1 Wall paint Benjamin Moore
2122-40 smoke, eggshell
Yellow
P2 Accent wall paint 1 Benjamin Moore 2023 sunburst, flat
Orange

PN 06015.00

ISSUED FOR
P3 Accent wall paint 2 Benjamin Moore

DT 6/15/06
2014-30 tangy orange, flat C1
Gray
P4 Ceiling paint Benjamin Moore C2
2122-40 smoke, flat
File Name: "PROJECTS:06004 DC Lib - 4200 Wisconsin:06004 DCPL dwgs:3 sheet layouts (.lbks):06004 Modular CD.lbk:06004 Modular CD.lbk"

White
P5 Ceiling paint Benjamin Moore
2122-60 palest pistachio, flat I CERTIFY THAT THESE DOCUMENTS
WERE PREPARED OR APPROVED BY ME,
P6 Wall paint White
Benjamin Moore AND THAT I AM A DULY LICENSED
int Ready Miix super white, semi-gloss ARCHITECT UNDER THE LAWS OF
THE DISTRICT OF COLUMBIA
P7 Wall paint Benjamin Moore 2122-60 palest pistachio, eggshell

B1 2 1/2" grey vinyl base Jonsonite 2 1/2" grey vinyl base, 38 Pewter

B2 Millwork base - matches millwork finish Formica 1-800-FORMICA 605 Brushed aluminum

Shaw
C1 General field carpet 24square EW24, style 59490, color four sided - 07, 90585
contact Kelli Seidell 410-908-9320
Shaw Color Chinese Peridot
C2 Accent at children's area
contact Kelli Seidell 410-908-9320

VCT1 At office and closed storage areas Armstrong Stonetex excelon, 52125 Granite gray, 12x12

T1 Ceramic tile at restroom floors

WD1 Wood - flat cut premium maple

WD2 MDF Stained to match architect's sample

WD3 MDF painted P_

PL1 White melamine

White
PL2 Laminate - color or metallic Formica 1-800-FORMICA
933C-58 Mission White, matte finish, color core
Red
PL3 Laminate - color or metallic Abet Laminati

Finish Plan
823 SEI

PL3 Laminate - color or metallic Formica 1-800-FORMICA 605 Brushed aluminum

GC1 Film graphic 1 Komatex White with orange/red background with black letters

GC2 Film graphic 2

A1.4
© core group, pc 2006
File Name: "PROJECTS:06004 DC Lib - 4200 Wisconsin:06004 DCPL dwgs:3 sheet layouts (.lbks):06004 Modular CD.lbk:06004 Modular CD.lbk" Layout: A2.1 Elevations Printed Date: 6/15/06 at 12:55 PM

5
4
3
2
1

DEDUCT ALTERNATE 2:
DEDUCT ALTERNATE 2:

WINDOWS TO BE STANDARD WINDOWS


WINDOWS TO BE STANDARD WINDOWS
P7
P1

TYP
TYP

P3
P1

1
FINISH WORK NOTES
7

DT 6/15/06 DB 1010 wisconsin avenue, nw


suite 405 DC Public Library - Anacostia
Elevations PN 06015.00 CB washington, dc 20007

ISSUED FOR PERMIT SET 1801 Good Hope Road SE


T 202.466.6116
© core group, pc 2006

F 202.466.6235 Washington, DC, 20020


E GEN@COREdc.com
A2.1
THE DISTRICT OF COLUMBIA
AND THAT I AM A DULY LICENSED
ARCHITECT UNDER THE LAWS OF
I CERTIFY THAT THESE DOCUMENTS
WERE PREPARED OR APPROVED BY ME,
File Name: "PROJECTS:06004 DC Lib - 4200 Wisconsin:06004 DCPL dwgs:3 sheet layouts (.lbks):06004 Modular CD.lbk:06004 Modular CD.lbk" Layout: A2.2 Elevations Printed Date: 6/15/06 at 1:18 PM

1
1

5
4

DT 6/15/06 DB 1010 wisconsin avenue, nw


suite 405 DC Public Library - Anacostia
Elevations PN 06015.00 CB washington, dc 20007

ISSUED FOR PERMIT SET 1801 Good Hope Road SE


T 202.466.6116
© core group, pc 2006

F 202.466.6235 Washington, DC, 20020


E GEN@COREdc.com
A2.2
THE DISTRICT OF COLUMBIA
AND THAT I AM A DULY LICENSED
ARCHITECT UNDER THE LAWS OF
I CERTIFY THAT THESE DOCUMENTS
WERE PREPARED OR APPROVED BY ME,
DC Public Library - Anacostia
1801 Good Hope Road SE
Washington, DC, 20020
AREA FOR SELF CHECK,

7/A4.3

8/A4.3

6/A4.3

7/A4.3

8/A4.3

6/A4.3
GROMMET PROVIDED BY OWNER GROMMET
PL1
OC OC OC
1'-6" PL1 WD1 1'-6" 1'-6" POS WD1 3' 2"

2"

2"

2"

2"
PL3

2'

2'

2'
3" 9' 5'-9" 3" 5'-9 3/4" 2'-10 1/2" 3 3/4" 5'-9"

2"
EQ EQ

7/A4.3

8/A4.3

6/A4.3

7/A4.3

8/A4.3

6/A4.3
CONTINUOUS WIRE CONTINUOUS WIRE
MANAGEMENT CHANNEL 1/2" DIAM SS PIPE MANAGEMENT CHANNEL
PL1 PL1
STANDOFF, TYP

1"

1"
WD1 WD1 WD1 WD1

1/2" DIAM SS PIPE

1"

1"
WD1
STANDOFF, TYP

2"

2"
END CORNER

5"

5"
20 degree 20 degree slide TOP RAIL BEYOND
(2) 3/4" LAMINATED MDF locking (2) 3/4" LAMINATED MDF OR POST
WITH PL2, TYP tilt tilt slide slide out WITH PL2, TYP

1/2"

1/2"
drawers open open VINYL BANNER MATERIAL
PL1, TYP shelves shelves out out shelves PL1, TYP

4"
2"
shelf shelf

2'-10"

2'-10"
trash WD1, TYPICAL WD1, TYPICAL trash
slide slide PL3

2'

2'
cpu END FINISH END FINISH cpu
out sheves out sheves

2'
book

1'-3"

1'-3"
locking locking VINYL SPECIFICATION BY
printer printer drop

1/2"

1/2"
drawer drawer GRAPHIC DESIGNER POST

2"

2"
1/2" 1/2" 1/2" 1/2"

2"

2"
NO WIRE MANAGEMENT
2" 2'-9 1/4" 1 1/2" 2'-10 1/2" 1 1/2" 1'-5" 1/2" 1'-5" 1 1/2" 1'-1/2" 1' 9 1/4" 1" 2'-9 1/2" 2" 2" 2'-9 1/2" 1" 9 1/4" 1' 1'-1/2" 1 1/2" 1'-5" 1/2" 1'-5" 1 1/2" 2'-10 1/2" 1 1/2" 2'-9 1/4" 2" AT BOOKDROP
15' 15'

1'-6"

2"

2"
PL1, TYP WD1, TYP WD1, TYP PL1, TYP

4"

1010 wisconsin avenue, nw


EQ EQ

E GEN@COREdc.com
13'-0"

washington, dc 20007
2'-10"
3'
PL3

2'-4"

F 202.466.6235
T 202.466.6116
suite 405
3" 9' 9' 3"
TRUSS ROD BEYOND

TENSION WIRE BEYOND


FENCE DESIGN BY CHAIN LINK
BOTTOM RAIL BEYOND FENCE MANUFACTURER

1'-0"CLR
REAR RECEPTION DESK DETAILS FRONT RECEPTION DESK DETAILS
6 SCALE: 1/2'' = 1'-0''
5 SCALE: 1/2'' = 1'-0'' GRADE

H.1

R 3"
6'-0"O.C.
H.3
R 7"

H.3
R 7"
Printed Date: 6/15/06 at 12:55 PM

H.3
R 7"

BANNER DETAIL
4 SCALE: 1/2'' = 1'-0''

DB

CB
R 5"
H.2 H.2
R 5"

PERMIT SET
Layout: A3.1 Details

R 3"
H.1

FIXTURE DESIGNATION, TYP

CIRCULAR CUTOUTS, TYP


H.2

PN 06015.00

ISSUED FOR
DT 6/15/06
R 5" CONNECTION
H.1 LOCATIONS.
R 3"
4 CONNECTION
POINTS PER CEILNG
PIECE MINIMUM. 12' 12'
File Name: "PROJECTS:06004 DC Lib - 4200 Wisconsin:06004 DCPL dwgs:3 sheet layouts (.lbks):06004 Modular CD.lbk:06004 Modular CD.lbk"

R 5"
H.3 SEE DETAIL 2/A4.2 5'-9" 6" 5'-9" 8' 6" 3'-6"
TO RESOLVE I CERTIFY THAT THESE DOCUMENTS
R 8 1/2" CONNECTION CONNECTION
H.2 CEILING OBSTACLES
6"MIN TYP
LOCATIONS. LOCATIONS. WERE PREPARED OR APPROVED BY ME,
4 CONNECTION 4 CONNECTION AND THAT I AM A DULY LICENSED
POINTS PER CEILNG POINTS PER CEILNG
ARCHITECT UNDER THE LAWS OF
PIECE MINIMUM. PIECE MINIMUM.
H.1 THE DISTRICT OF COLUMBIA
SEE DETAIL 2/A4.2 SEE DETAIL 2/A4.2
R 3" TO RESOLVE TO RESOLVE
CEILING OBSTACLES CEILING OBSTACLES
ALIGN TYP ALIGN TYP
3'-9"

3'-9"
ALL TO BE PAINTED P5

R 3" H.1

H.3
R 7"
6"

6"
R 5"

R 5"
H.2
H.2
ALIGN TYP

ALIGN TYP
LIGHT HUNG 8'0" AFF, TYP LIGHT HUNG 8'0" AFF, TYP
12'-3"

12'-3"
3'-9"

3'-9"
H.3
R 8 1/2"

R 5"

H.2
6"

6"
R 3"
H.1

H.1
3'-9"

3'-9"
R 3" ALL TO BE PAINTED P5 ALL TO BE PAINTED P5
1'OC TYP

1'OC TYP

1'OC TYP

1'OC TYP

Details
1'OC TYP 1'OC TYP 1'OC TYP 1'OC TYP

CEILING FRAMING - TYPE CC CEILING FRAMING - TYPE CB CEILING FRAMING - TYPE CA


3 SCALE: 1/2'' = 1'-0''
2 SCALE: 1/2'' = 1'-0''
1 SCALE: 1/2'' = 1'-0''

A3.1
© core group, pc 2006
DC Public Library - Anacostia
1801 Good Hope Road SE
Washington, DC, 20020
STRUCTURE

CEILING OBSTACLE BEYOND

STEEL THREADED ROD


STRUCTURE
TIED TO STRUCTURE
ABOVE WITH
BOLT AND WASHER

1 5/8" UNISTRUT CHANNEL


STEEL THREADED ROD CHANNEL NUT
TIED TO STRUCTURE W/ BOLT AND WASHER
ABOVE WITH
BOLT AND WASHER

SCHEDULED CEILING CONNECTOR

SCHEDULED CEILING
RACEWAY HANGER

BOLT W/ WASHER

EXPOSED FACE OF
MDF NOT HAVE

1010 wisconsin avenue, nw


EXPOSED CONNECTIONS

E GEN@COREdc.com
washington, dc 20007
1/2" STAINED MDF

F 202.466.6235
T 202.466.6116
suite 405
CEILING TYPE CC - HANGER DETAIL CEILING TYPE CA & CB - HANGER DETAIL
2 SCALE: 6'' = 1'-0''
1 SCALE: 6'' = 1'-0''

LOOP CAP

BRACE RAIL

BRACE RAIL
Printed Date: 6/15/06 at 12:55 PM

BOLT WITH
HEX NUT

BOLT AND NUT

DB

CB

PERMIT SET
Layout: A3.2 Details

BRACE BAND

RAIL END WITH OFFSET LUG


BRACE RAIL
BRACE RAIL
RAIL END
WITH OFFSET LUG

PN 06015.00

ISSUED FOR
DT 6/15/06
REINFORCED EDGES
WITH METAL EYELETS

TENSION OR BRACE BAND


File Name: "PROJECTS:06004 DC Lib - 4200 Wisconsin:06004 DCPL dwgs:3 sheet layouts (.lbks):06004 Modular CD.lbk:06004 Modular CD.lbk"

FABRIC BAND

I CERTIFY THAT THESE DOCUMENTS


VINYL SIGNAGE
WERE PREPARED OR APPROVED BY ME,
,MATERIAL SPECIFIED
BY GRAPHIC DESIGNER AND THAT I AM A DULY LICENSED
ARCHITECT UNDER THE LAWS OF
THE DISTRICT OF COLUMBIA

TENSION BAR TRUSS ROD

ROUND LINE POST

TURNBUCKLE POST DESIGNED


BY FENCE MANUFACTURER

CORNER OR END POST

POST DESIGNED
BY FENCE MANUFACTURER

END OR CORNER POST ROUND TERMINAL POSTS


4 SCALE: 3'' = 1'-0''
3 SCALE: 3'' = 1'-0''

Details
A3.2
© core group, pc 2006
DC Public Library - Anacostia
1801 Good Hope Road SE
Washington, DC, 20020
2 3/4"

2"

ALIGN
CUSTOM CORE P.LAM COUNTERTOP
WD1 W/MITERED SELF EDGE,
FORMICA COLOR: "MISSION WHITE"

GROMMET LOCATIONS
WHERE SPECIFIED

10"
3/4" WD1

3"
WD1, SOLID LUMBER EDGE
6"OC

CHANNEL FOR WIRE MANAGEMENT


2X3X1/16" MTL
3/4" WD1

1'-4" OR 1'-7"

1010 wisconsin avenue, nw


2'

E GEN@COREdc.com
washington, dc 20007

F 202.466.6235
T 202.466.6116
CHILDREN'S COMPUTER TABLE

suite 405
5

1"
SCALE: 1 1/2'' = 1'-0''
SEE DETAIL 5/A4.3 FOR TYPICAL DETAILS

RECEPTION DESK DETAIL

1'-6"
8 SCALE: 1 1/2'' = 1'-0''
P-LAM COUNTERTOP (PL-2)

COUNTERTOP ABOVE

GROMMET LOCATIONS PL-2


WHERE SPECIFIED

6"OC

1"
WOOD CLEAT
COUNTERTOP SUPPORT, TYP.

1"
3" DIA. GROMMET

P.LAM W/MITERED SELF EDGE,


Printed Date: 6/15/06 at 12:55 PM

MDF FIN FORMICA COLOR: "MISSION WHITE"


4" OFF SIDES, TYP

2'-8"
3'

2'-10"
PL-1

DB

CB
5/A4.3 5/A4.3

PERMIT SET
Layout: A3.3 Details

BLACK MELAMINE INTERIOR

PN 06015.00

ISSUED FOR
DT 6/15/06
VINYL BASE @ TOE KICK

4"
3"
File Name: "PROJECTS:06004 DC Lib - 4200 Wisconsin:06004 DCPL dwgs:3 sheet layouts (.lbks):06004 Modular CD.lbk:06004 Modular CD.lbk"

1" 1" 2"

SEE DETAIL 5/A4.3 FOR TYPICAL DETAILS I CERTIFY THAT THESE DOCUMENTS
WERE PREPARED OR APPROVED BY ME,

RECEPTION DESK DETAIL CHILDREN'S COMPUTER TABLE COUNTER W/SINK AND THAT I AM A DULY LICENSED
ARCHITECT UNDER THE LAWS OF

7 SCALE: 1 1/2'' = 1'-0''


4 SCALE: 1 1/2'' = 1'-0''
2 SCALE: 1 1/2'' = 1'-0''
THE DISTRICT OF COLUMBIA

GROMMET LOCATIONS
WHERE SPECIFIED
3/4" WD1
EXISTING STOREFRONT
WD1, SOLID LUMBER EDGE SYSTEM
6"OC SEE PLAN
2"H BACKSPLASH
CHANNEL (2X3X1/16" MTL)
FOR WIRE MANAGEMENT P.LAM COLOR CORE
WITH NOTCH OUT IN PANEL FOR COUNTERTOP
CONTINUOUS RUN FORMICA COLOR: "MISSION
WHITE"

2"
3/4" WD1
COLOR CORE P.LAM COUNTERTOP

4"
W/MITERED JOINTS AND SELF EDGE
FORMICA COLOR: "MISSION WHITE"
4"
CONTINUOUS ALUM SUPPORT

3"
ANGLE – PROVIDE BLKNG AT
WALL
ADJUSTABLE SHELF
1/2" MDF WITH PL1, TYP
P-LAM COLOR CORE SUPPORT
2'-10"

LEGS
FORMICA COLOR: "MISSION

2'-6"
WHITE"
(2) LAMINATED 3/4" MDF W/ PL1, TYP
5/8" GWB

END PANEL CONDITIONS TO BE 2" WD1


VINYL BASE

V.I.F.
VINYL BASE 8" PROVIDE 2 LEVELING FEET PER
SUPPORT
2 LEVELERS, TYP
FOR EACH SUPPORT

Details
(CHROME) SCHEDULED FLOORING SCHEDULED FLOORING
1"

RECEPTION DESK DETAIL WINDOW DISPLAY WORK COUNTERTOP


6 SCALE: 1 1/2'' = 1'-0''
3 SCALE: 1 1/2'' = 1'-0''
1 SCALE: 1 1/2'' = 1'-0''
A3.3
© core group, pc 2006
PLUMBING SPECIFICATIONS

Washington, DC, 20020


DC Public Library - Anacostia
1801 Good Hope Road SE
PIPING LEGEND
1. ALL WORK AND EQUIPMENT SHALL COMPLY WITH ALL APPLICABLE LAWS, CODES, ETC., OF ALL AUTHORITIES 23. ALL NEW SANITARY, SOIL, WASTE, AND VENT SHALL BE SERVICE WEIGHT CAST IRON, BELL AND SPIGOT, PIPE
AND FITTINGS, ANSI A.112.5.1 AS MANUFACTURED BY TYLER PIPE AND FOUNDRY CO., U.S. PIPE AND FOUNDRY CO., SYMBOL ABRV. DESCRIPTION
HAVING JURISDICTION, INCLUDING BUT NOT LIMITED TO : THE INTERNATIONAL PLUMBING CODE, THE LOCAL FIRE
MARSHAL, UNDERWRITERS LABORATORY (UL), IRI, FM, OSHA, AND THE NATIONAL ELECTRICAL CODE (NEC). CENTRAL FOUNDRY OR APPROVED EQUAL. TYLER "TY-SEAL" OR APPROVED EQUAL, NEOPRENE POSITIVE SEAL SAN.,W. SOIL, WASTE OR SANITARY SEWER PIPING
WHERE CONTRACT DOCUMENT REQUIREMENTS ARE IN EXCESS OF CODE REQUIREMENTS, THE CONTRACT ELASTOMERIC COMPRESSION TYPE GASKETS SHALL BE USED AT ALL JOINTS. AS AN OPTION, ALL NEW PLUMBING FIXTURE SCHEDULE
DOCUMENT SHALL GOVERN. DEVIATIONS FROM THE CONTRACT DOCUMENTS REQUIRED BY THE ABOVE SANITARY, SOIL, WASTE, AND VENT PIPING 4 INCHES AND SMALLER MAY USE HUBLESS SERVICE WEIGHT CAST CW COLD WATER PIPING
AUTHORITIES SHALL BE SUBMITTED TO THE ENGINEER FOR REVIEW. MODIFICATIONS REQUIRED BY THE ABOVE IRON PIPE, FITTINGS AND JOINTS WITH TYLER "NO-HUB" STAINLESS STEEL CONNECTORS. IN ADDITION, ALL VENT DESIG. FIXTURE TYPE C.W. H.W. WASTE VENT MANUFACTURER MODEL NO. TRIM REMARKS
SAID AUTHORITIES TO BRING THE SPACE UNDER CONTRACT UP TO CODE SHALL BE MADE WITHOUT ADDITIONAL PIPING MAY BE DWV COPPER PIPE AND FITTINGS WITH SOLDERED JOINTS. GASKETS, JOINTS, CONNECTORS, ADA FLOOR MOUNTED FLUSH HW HOT WATER PIPING
CHARGE. CONTRACTOR IS RESPONSIBLE FOR ALL ROUGH-IN, FINAL CONNECTIONS, AND PROPER INSTALLATION OF SPECIALTIES AND PIPE SHALL BE MANUFACTURED AND PROVIDED BY THE SAME MANUFACTURER. WASTE LINES P-1 TANK WATER CLOSET 1/2" --- 4" 2" KOHLER K-3485 --- 1,2,9
FIXTURES AND ASSOCIATED PIPING MOUNT FAUCETS, AND TO SUPPLY ANY TRAPS, VALVE FITTINGS, VACUUM FROM DRINKING WATER FOUNTAINS SHALL BE INSULATED WITH 1/2 INCH THICK HEAVY DUTY FIBERGLASS V VENT PIPING
P-2 ADA LAVATORY 1/2" 1/2" 1-1/2" 1-1/2" KOHLER K-2054 CHICAGO 1 THRU 9
BREAKERS, PRESSURE GAGES, OR PRESSURE REGULATORS REQUIRED FOR A COMPLETE INSTALLATION THAT MATERIAL WITH ALL PURPOSE NONCOMBUSTIBLE VAPOR BARRIER JACKET. INSULATION SHALL HAVE A MAXIMUM 2200-4E2805
MEETS CODE. THERMAL CONDUCTIVITY (K) OF 0.23 BTU*IN/HR*FT2*°F AT 75°F. ADHESIVE SYSTEMS THAT EMPLOY RELEASE OF OVERFLOW PIPING
SERVICE SINK 3/4" 3/4" 3" 2" KOHLER K-6719 STERN 1,9
PAPER WILL NOT BE ACCEPTABLE. ALL DRAINAGE PIPE SHALL BE SUPPORTED DIRECTLY ON EACH SIDE OF A P-3 T-10-VB
G GAS PIPING
2. ALL SPECIFICATIONS AND DRAWINGS, I.E., ARCHITECTURAL, MECHANICAL, PLUMBING, AND ELECTRICAL ARE JOINT. ALL PIPING SUPPORTS AND RESTRAINTS SHALL BE IN STRICT ACCORDANCE WITH THE DRAINAGE PIPE PANTRY SINK 1/2" 1/2" 2" 1-1/2" SL-1921-A CHICAGO
P-4 JUST 1 THRU 9
COMPLIMENTARY AND MUST BE USED IN COMBINATION TO OBTAIN COMPLETE CONSTRUCTION INFORMATION. ANY MANUFACTURER'S RECOMMENDATIONS AND INSTALLATION GUIDELINES. -GR 2300-8
FLOOR SINK
INFORMATION CONFLICTS WITHIN THE SPECIFICATIONS AND DRAWINGS SHALL BE BROUGHT TO THE ENGINEER'S WATER FOUNTAIN 1/2" --- 1-1/2" DF-2611 --- 1,2,9
P-5 1-1/2" SUNROC
ATTENTION. 24. (OPTION) ALL NEW SANITARY, SOIL, WASTE, AND VENT, PIPING SHALL BE ABS OR PVC, DWV SCHEDULE 40 CLEAN OUT, EXPOSED
CO
OR HEAVIER. PLASTIC SANITARY SEWER PIPING BELOW GRADE SHALL BE PVC PIPE, ASTM D3034, SDR 35 OR
3. ALL PIPING SHALL RUN CONCEALED ABOVE CEILING OR IN WALL CHASE, UNLESS OTHERWISE NOTED. HEAVIER, WITH ELASTOMERIC GASKETS. SANITARY SEWER PIPING ABOVE GRADE SHALL BE ABS PIPE, ASTM NOTE: FLOOR CLEAN OUT
1. PROVIDE ALL REQUIRED COMPONENTS FOR COMPLETE FIXTURE ROUGH-IN I.E., SUPPLIES, STOPS, TRAPS AND PRIMERS, CARRIERS, GRID DRAINS, CO
EXPOSED PIPING SHALL BE 3/4 INCH MINIMUM FROM ANY WALL SURFACE. EXCEPT WHERE OTHERWISE INDICATED D2680 OR D2151 WITH SOLVENT WELD JOINTS, OR PVC PIPE, ASTM D2665 WITH SOLVENT WELD JOINTS. WASTE CO
ON THE DRAWINGS, PIPING IS SHOWN ON THE FLOOR WHERE IT ACTUALLY OCCURS IN THE BUILDING. LINES FROM DRINKING WATER FOUNTAINS SHALL BE INSULATED WITH 1/2 INCH THICK HEAVY-DUTY FIBERGLASS TAIL PIECES, ETC. NOT ALL REQUIRED COMPONENTS ARE SPECIFIED ABOVE. BACK FLOW PREVENTER
BFP
MATERIAL WITH ALL PURPOSE NONCOMBUSTIBLE VAPOR BARRIER JACKET. INSULATION SHALL HAVE A MAXIMUM 2. FIXTURE SHALL BE ADA COMPLIANT. PROVIDED WITH ADA COMPLIANT ACCESSORIES. MOUNT ADA COMPLIANT. SEE ARCHITECTURAL PLAN FOR
4. CONTRACTOR SHALL VERIFY ALL POINTS OF CONNECTION BEFORE COMMENCING WORK. CONTRACTOR SHALL THERMAL CONDUCTIVITY FACTOR (K) OF 0.23 BTU*IN/HR8FT2*°F AT 75°F. ADHESIVE SYSTEMS THAT EMPLOY ELEVATIONS. TRAP PRIMER LINE
COORDINATE WORK WITH EXISTING WORK AND OTHER TRADES. CONTRACTOR SHALL REMOVE ALL WASTE RELEASE PAPER WILL NOT BE ACCEPTABLE. ALL DRAINAGE PIPE SHALL BE SUPPORTED DIRECTLY ON EACH SIDE 3. PROVIDE SKAL + GUARD INSULATING DEVICES ON EXPOSED UNDERCOUNTER PLUMBING. TPL
MATERIALS, DEBRIS, AND RUBBISH FROM SITE AND LEGALLY DISPOSE OF IT. ALL UNUSED EQUIPMENT SERVING OF A JOINT. ALL PIPING SUPPORTS AND RESTRAINTS SHALL BE IN STRICT ACCORDANCE WITH THE DRAINAGE PIPE 4. PROVIDE GOOSENECK FAUCETS WITH ADA WRIST BLADE HANDLES.
THIS AREA SHALL BE REMOVED AND RETURNED TO THE OWNER. MANUFACTURER'S RECOMMENDATIONS AND INSTALLATION GUIDELINES. 5. PROVIDE FIXTURE TYPES PER MANUFACTURER OR APPROVED EQUAL. CV CHECK VALVE
6. COORDINATE FIXTURE TYPES AND SPECIFICATIONS W/ ARCHITECTURAL PLANS.
5. CONTRACTOR SHALL CONFIRM THE REQUIREMENTS FOR PREMIUM TIME OR SPECIAL PROCEDURES WITH THE 25. EXCEPT WHERE OTHERWISE INDICATED, HORIZONTAL SANITARY, SEWAGE AND WASTE PIPING SHALL SLOPE 7. SEE PLANS & RISERS FOR VENT SIZES AND CONNECTIONS.
AT 1/4 INCH PER FOOT FOR PIPES 2 INCHES AND SMALLER, PIPES 3 INCHES AND LARGER SHALL SLOPE AT 1/8 INCH 8. PROVIDE THERMOSTATIC MIXING VALVE BY WATTS SERIES L111 OR APPROVED EQUAL. CONNECT TO EXISTING
OWNER AND INCLUDE THE COST IN HIS BID PROPOSAL. THE CONTRACTOR, BY SUBMITTING HIS BID PROPOSAL
AGREES TO ACCEPT ALL EXISTING SITE CONDITIONS NOT SPECIFICALLY EXCEPTED. ALL EXCEPTIONS SHALL BE PER FOOT. ALL VERTICAL SANITARY SEWER WHICH TURN 90° AFTER PASSING THROUGH A FLOOR, SHALL BE 9. PROVIDE HEAT-TRACING PIPING BELOW FLOOR.
PROVIDED IN WRITING TO THE ARCHITECT AND ENGINEER. INSTALLED AS TIGHT AS POSSIBLE TO THE UNDERSIDE OF THE STRUCTURE. FLOOR DRAIN

1010 wisconsin avenue, nw


FD

washington, dc 20007
6. CONTRACTOR SHALL COORDINATE, PREPARE AND SUBMIT SHOP DRAWINGS TO THE ARCHITECT AND ENGINEER 26. CLEAN-OUTS SHALL BE PROVIDED IN PIPING AS REQUIRED BY CODE AND AT ALL OTHER LOCATIONS AS HW SUPPLY SHUT OFF VALVE
A.S.M.E. COMBINATION

E GEN@COREdc.com
FOR THEIR APPROVAL. SHOP DRAWINGS TO BE SUBMITTED INCLUDE: FIXTURES, VALVES, PUMPS, WATER NOTED ON THE DRAWINGS. ALL CLEAN-OUTS SHALL BE THE SAME SIZE AS THE PIPE DIAMETER UP TO AND CW SUPPLY TEMPERATURE AND

T 202.466.6116
F 202.466.6235
HEATERS, PIPING MATERIALS AND INSULATION, DRAINS, CLEANOUTS AND ALL EQUIPMENT SPECIFIED ON THESE INCLUDING PIPE 4 INCHES IN DIAMETER. FOUR INCH CLEAN-OUTS SHALL BE USED FOR ALL PIPE LARGER THAN 4 PRESSURE RELIEF VALVE GATE VALVE
CONTRACT DRAWINGS. INCHES, UNLESS NOTED OTHERWISE. ALL CLEAN-OUT LOCATIONS SHALL BE NO MORE THAN 5 FEET ABOVE THE EXTEND PIPE TO SPILL
BASE OF THE HORIZONTAL OFFSET AND BE APPROVED BY THE ARCHITECT. FOR CARPETED AREAS, PROVIDE A OVER SAFE PAN BALL VALVE OR SHUTOFF VALVE

suite 405
7. A SET OF MEP RECORD/COORDINATION DRAWINGS SHALL BE MAINTAINED IN THE GENERAL CONTRACTORS PERMANENT IDENTIFYING MARK IN THE CARPET DIRECTLY ABOVE THE CLEAN-OUT. THE CLEAN-OUT SHALL HAVE A
OFFICE AT THE JOB SITE. ACTUAL LOCATIONS OF ALL EQUIPMENT, PIPING, DUCTWORK, ETC., AND ALL DEVIATIONS SMOOTH POLISHED BRONZE FINISH WITH THE LETTERS "C.O." CAST IN THE COVER. FOR WALLS, PROVIDE AN UNION (TYP) GAS COCK/GAS STOP
OF THE WORK FROM THAT SHOWN ON THE CONTRACT DOCUMENTS SHALL BE MARKED ON THE ACCESS PANEL WITH CLEARANCE FOR RODDING. THE FLOOR CLEAN-OUTS SHALL BE ZURN MODEL ZN-1400-T OR DOMESTIC ELECTRIC
RECORD/COORDINATION DRAWINGS. EACH TRADE SHALL REVIEW THE COORDINATION DRAWINGS AND RESOLVE APPROVED EQUAL WITH BRONZE PLUG, SQUARE NICKEL BRONZE FRAME AND COVER. THE WALL CLEAN-OUTS GATE VALVE (TYP.) WATER HEATER WATER HAMMER ARRESTER/SHOCK ABSORBER
ANY POTENTIAL CONFLICTS WITH OTHER TRADES PRIOR TO INSTALLING ANY PORTION OF THEIR WORK. SHALL BE ZURN MODEL ZN-1443-BP OR APPROVED EQUAL WITH BRONZE PLUG AND 7 INCHES X 7 INCHES NICKEL DRAIN VALVE
TOP CONNECTION
CONTRACTOR SHALL NOT CORE, DRILL, OR CUT CONCRETE SLABS FOR ANY REASON WITHOUT THE KNOWLEDGE BRONZE COVER. NO SANITARY, SOIL OR WASTE PIPE SHALL EXTEND GREATER THAN 2'-0" TO A DEAD-END. SHELF WITH SAFE PAN.
AND WRITTEN CONSENT OF THE STRUCTURAL ENGINEER AND THE OWNER. WATER HEATER
27. ALL PIPING SYSTEMS, VALVES, AND EQUIPMENT SHALL BE PROPERLY IDENTIFIED. ALL VALVES SHALL HAVE SUPPORTED BY PIPE UP
THREADED RODS 1" DRAIN PIPE FROM SAFE
8. WORK SHALL BE EXECUTED IN A GOOD WORKMANLIKE MANNER USING MECHANICS SKILLED IN THEIR THEIR NORMAL (IN OPERATION) POSITION IDENTIFIED, SUCH AS "NORMALLY OPEN" OR "NORMALLY CLOSED". PAN TO EXTEND AND
(TYP OF 4) PIPE DOWN
RESPECTIVE TRADES. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR ALL CONSTRUCTION MEANS, METHODS, CONNECT TO SINK TRAP
SUSPEND RODS FROM
TECHNIQUES, SEQUENCES AND PROCEDURES FOR COORDINATING THE WORK UNDER THIS CONTRACT. MAINTAIN 28. ALL PACKAGED EQUIPMENT SHALL BE INDEPENDENTLY THIRD PARTY LABELED AS A SYSTEM FOR ITS CAPPED PIPE
STRUCTURE ABOVE.
THE CONSTRUCTION PREMISES IN A NEAT AND ORDERLY CONDITION AT THE END OF EACH WORKING DAY. INTENDED USE BY A NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL) IN ACCORDANCE WITH OSHA ARCHITECT IS RESPONSIBLE
FEDERAL REGULATIONS 29CFR1910.303 AND .399, AS WELL AS NFPA PAMPHLET NO. 70, NATIONAL ELECTRIC FOR PROVIDING STRUCTURAL PIPE UNION
9. IN CASES OF DOUBT AS TO THE WORK INTENDED, OR IN THE EVENT OF NEED FOR EXPLANATION THEREOF, THE CODE (NEC), ARTICLE 90-7. SUPPORT.
CONTRACTOR SHALL REQUEST SUPPLEMENTARY INSTRUCTIONS FROM THE ENGINEER. NO CHANGES ARE TO BE NOTES:
MADE TO THE WORK OF THIS CONTRACT WITHOUT PRIOR KNOWLEDGE AND APPROVAL OF THE ENGINEER. THE 29. THE CONTRACTOR SHALL MAKE ALL FINAL EQUIPMENT AND FIXTURE CONNECTIONS AND PROVIDE THE 1. NOT ALL SYMBOLS AND ABBREVIATIONS ARE IN USE FOR THIS PROJECT.
CONTRACTOR SHALL HOLD THE OWNER AND ITS CONSULTANTS HARMLESS AGAINST ALL CLAIMS AND NECESSARY ADAPTERS, FITTINGS, VALVES, DEVICES, ETC. FOR A COMPLETE AND OPERABLE SYSTEM. PROVIDE SCHEDULE OF CAPACITIES
JUDGMENTS ARISING OUT OF THE CONTRACTORS PERFORMANCE OF THE WORK OF THIS CONTRACT. THE VALVES AND UNIONS WHERE NEEDED TO PERMIT DISCONNECTIONS OF EACH PIECE OF EQUIPMENT FOR REPAIRS. W.H. STORAGE G.P.H. RECOVERY ELECTRIC BASIS OF DESIGN
CONTRACTOR SHALL NOT PROCEED WITH ANY WORK, WHICH HE EXPECTS ADDITIONAL COMPENSATION BEYOND PLUMBING CONNECTIONS SHOWN ARE NOMINAL. VERIFY EXACT CONNECTION SIZE WITH EACH PIECE OF NO GALLONS @90° TEMP. RISE KW VOLTS PH
THE CONTRACT AMOUNT, WITHOUT WRITTEN AUTHORIZATION FROM THE APPROPRIATE AUTHORITY. FAILURE TO EQUIPMENT SUPPLIED. FOLLOW FIXTURE MANUFACTURER'S RECOMMENDED INSTALLATION INSTRUCTIONS, AND WH 20 18 4.0 208 V. 1Ø A.O. SMITH #DEL-20
OBTAIN SUCH AUTHORIZATION SHALL INVALIDATE ANY CLAIM FOR EXTRA COMPENSATION. ROUGH-IN DIMENSIONS. REFER TO CONSULTANT AND ARCHITECTURAL DOCUMENTS FOR ADDITIONAL
INFORMATION. COORDINATE WITH THE EQUIPMENT SUPPLIER FOR ADDITIONAL INFORMATION.
10. WHEREVER FIRE RATED PARTITIONS ARE PENETRATED FOR WIRE, DUCT, OR PIPE PASSAGE, SEAL PASSAGES ELECTRIC WATER HEATER DETAIL
WITH CODE APPROVED, LABORATORY TESTED AND LABELED SEALANT OF FIRE RESISTANCE RATING NOT LESS NO SCALE
THAN THAT OF PENETRATED ASSEMBLY THAT WILL PREVENT PASSAGE OF FIRE AND SMOKE.
2"VTR
ROOF 2"V 3/4"CW 2"V ROOF
11. ALL CUTTING, DRILLING, AND PATCHING OF WALLS, FLOORS, AND/OR STRUCTURAL MEMBERS FOR THE
INSTALLATION OF THE PLUMBING SYSTEMS SHALL BE PROVIDED. STRUCTURAL COMPONENTS SHALL NOT BE CUT,

DB

CB
DRILLED, OR MODIFIED IN ANY WAY WITHOUT THE STRUCTURAL ENGINEER'S REVIEW AND APPROVAL PRIOR.
3/4"HW

Permit - SET
12. SUPPORT ALL PIPING FROM STRUCTURE WITH UL LISTED HANGERS AND SUPPORTS SUITABLE FOR THE CLG. 3/4"CW CLG.
INTENDED INSTALLATION. DESIGN, SELECTION, SPACING, AND APPLICATION OF HANGERS AND SUPPORTS SHALL 1 1/2"V 1 1/2"V 1 1/2"V (E) SHUT-OFF
COMPLY WITH ANSI B31.1 AND MSS SP-69. 1/2"CW&HW WH VALVE
1/2"CW
13. CONNECTIONS BETWEEN DISSIMILAR PIPING MATERIALS SHALL BE MADE WITH SUITABLE DIELECTRIC 1/2"CW 2"V 1 1/2"V 1/2"CW&HW 2"V
CONTRACTOR TO

06016.00
INSULATING UNIONS. ISOLATE COPPER PIPING FROM DISSIMILAR METALS, SUCH AS METAL STUDS AND VENT 1/2"CW&HW WATER METER IN
PROVIDE DRAIN PAN

ISSUED FOR
PIPING. P-2 P-4 P-2 VAULT BELOW GRADE

DATE
W/ DRAIN PIPE. TO
P-5 3/4"CW&HW P-3 MOP SINK
14. ALL PRODUCTS LOCATED WITHIN PLENUM AREAS, INCLUDING BUT NOT LIMITED TO INSULATION AND ADHESIVE
FCO

DT

PN
SYSTEMS, SHALL HAVE A COMPOSITE FIRE HAZARD RATING NOT TO EXCEED 25 FLAME SPREAD AND 50 SMOKE FLOOR. P-1 P-1 FLOOR.
DEVELOPED AS DETERMINED BY THE APPLICABLE UL OR ASTM STANDARD. 3"SAN.
I CERTIFY THAT THESE DOCUMENTS
3"SAN. 2"SAN. 2"SAN. 2"SAN. 3"SAN. M WERE PREPARED OR APPROVED BY ME,
2"SAN. AND THAT I AM A DULY LICENSED
15. ALL NEW DOMESTIC WATER PIPING SHALL BE TYPE L HARD DRAWN SEAMLESS COPPER WATER TUBE OR CPVC ARCHITECT UNDER THE LAWS OF
PIPE (ASTM D2846) WITH CPVC FITTINGS AND SOLVENT WELD JOINTS. COPPER TUBE FITTINGS SHALL BE CONNECT NEW 1"CW TO EXISTING THE DISTRICT OF COLUMBIA
4"SAN. 4"SAN. CITY WATER SUPPLY. COORDINATE WITH
WROUGHT COPPER JOINT FITTINGS CONFORMING TO ANSI 316.22. SOLDERED COPPER JOINTS SHALL BE SEE PLAN FOR CONTINUATION
SOLDERED WITH LEAD FREE ASTM B32 GRADE 95T TIN-ANTIMONY SOLDER. CONNECT NEW 4"SAN TO EXISTING CIVIL ENGINEER FOR EXACT LOCATION.
CITY SANITARY MAIN. COORDINATE WITH
16. PIPING SYSTEM SHALL BE INSULATED WITH 1/2 INCH THICK HEAVY-DUTY FIBERGLASS MATERIAL WITH ALL CIVIL ENGINEER FOR EXACT LOCATION.
PURPOSE NONCOMBUSTIBLE VAPOR BARRIER JACKET. INSULATION SHALL HAVE A MAXIMUM THERMAL
CONDUCTIVITY FACTOR (K) OF 0.23 BTU*IN/HR*FT2*°F AT 75°F. ADHESIVE SYSTEMS THAT EMPLOY RELEASE PAPER WATER AND SANITARY RISER
WILL NOT BE ACCEPTABLE. AS AN ACCEPTABLE ALTERNATE TO THE ABOVE INSULATION, THE CONTRACTOR MAY NOT TO SCALE
PROVIDE OWENS-CORNING "SSL-II" DOUBLESURE PIPE INSULATION.

17. ALL NEW DOMESTIC WATER PIPING SHALL BE INSULATED WITH 3/4 INCH THICK ARMSTRONG FLEXIBLE
ELASTOMERIC CLOSED CELL PIPE INSULATION OR APPROVED EQUAL. THE INSULATION SHALL HAVE A MAXIMUM
THERMAL CONDUCTIVITY FACTOR (K) OF 0.28 BTU*IN/HR*FT2*°F AT 75°F AND A MAXIMUM WATER PERMEABILITY OF
0.15 PERM-INCH. THE PIPE INSULATION BUTT JOINTS AND LONGITUDINAL JOINTS SHALL BE SEALED WITH
ARMSTRONG 520 ADHESIVE AND THE ENTIRE INSULATION INSTALLATION SHALL BE IN ACCORDANCE WITH THE
MANUFACTURER'S RECOMMENDATIONS. ADHESIVE SYSTEMS THAT EMPLOY RELEASE PAPER WILL NOT BE
ACCEPTABLE. 7061 Deepage Dr
Columbia, MD 21045
18. FITTINGS, VALVES, AND FLANGES SHALL BE INSULATED WITH THE SAME MATERIALS AND OF THE SAME 410-381-7100 Fax: 410-381-7110
1-800-ASC-4-MEP
THICKNESS AS THE ADJOINING PIPE. (1-800-272-4637)

19. DOMESTIC WATER SHUT-OFF VALVES SHALL BE TWO PIECE, FULL PORT, TRUE UNION TYPE, WITH PLASTIC
BODY, BLOW-OUT PROOF STEM DESIGN AND O-RING STEM SEAL. PLASTIC PARTS SHALL BE CPVC. VALVES
SHALL BE NIBCO DUO-BLOC, OR EQUAL.

20. PROVIDE STOP VALVES AT ALL FIXTURE AND EQUIPMENT SUPPLIES. ALL EXPOSED FIXTURE CONNECTIONS

DATA SHEET
SHALL BE CHROME PLATED, STAINLESS STEEL OR FITTED WITH CHROME PLATED SLEEVES. PROVIDE VACUUM
BREAKERS WHERE REQUIRED BY CODE.

PLUMBING
21. ALL DOMESTIC WATER PIPING SYSTEMS SHALL BE DISINFECTED IN ACCORDANCE WITH THE APPLICABLE

Anacostia
CODES AND AWWA C651.

22. PERFORM A HYDROSTATIC PRESSURE TEST ON ALL PIPING, AT THE PIPING SYSTEM WORKING PRESSURE, FOR
A MINIMUM PERIOD OF 24-HOURS. REPAIR ANY LEAKS AND RETEST TO DEMONSTRATE TIGHTNESS. STOP-LEAK
COMPOUNDS WILL NOT BE ALLOWED. ALL PIPING FOR PRESSURIZED WATER SYSTEMS SHALL HAVE A MINIMUM
PRESSURE RATING OF 150 PSI.

P100
© core group, pc 2006

ASC PROJECT #0611138


JANITORS CLOSET STORAGE OFFICE

Washington, DC, 20020


DC Public Library - Anacostia
1801 Good Hope Road SE
DOMESTIC WATER METER IN VAULT
BOX W/ READING IN CUBIC FEET.
GENERAL NOTES
1. REFER TO DRAWING P100 FOR PLUMBING SYMBOLS AND ABBREVIATIONS. EXTEND 1"CW PIPE BELOW GRADE AND
2. REFER TO SANITARY AND DOMESTIC WATER RISERS ON DRAWING P100 FOR CONNECTION TO EXISTING CITY MAIN SUPPLY
ADDITIONAL PIPE SIZES. PIPE. COORDINATE W/ LOCAL JURISDICTION WH
3. PROVIDE UNDER ALL SINKS AND LAVATORIES A POINT OF USE THERMOSTATIC CIVIL ENGINEER FOR EXACT LOCATION.
MIXING VALVE. REFER TO DATA SHEET P100 FOR MAKE AND MODEL. P-3
4. HEAT TRACE ALL PIPING & TRAPS BELOW FLOOR AND DOMESTIC WATER PIPE
3/4" CW ABV. CLG.
FROM BELOW GRADE TO PIPING LEADING INTO BUILDING.
MENS P-1
P-4

1/2" CW&HW ABV. CLG.

3/4" HW ABV. CLG. YOUNG ADULT


P-2 READING

WOMENS P-2

P-5
P-1

1010 wisconsin avenue, nw

washington, dc 20007

E GEN@COREdc.com
T 202.466.6116
F 202.466.6235
suite 405
ADULT
COMPUTERS
ADULT
LOUNGE

NEW PLUMBING PLAN - DOMESTIC WATER SUPPLY


SCALE: 1/4" = 1'-0"

JANITORS CLOSET STORAGE OFFICE

DB

CB

Permit - SET
FCO

P-3

06016.00
1 1/2"V ABV. CLG.
2"VTR

ISSUED FOR
DATE
MENS P-1

DT

PN
P-4
I CERTIFY THAT THESE DOCUMENTS
WERE PREPARED OR APPROVED BY ME,
AND THAT I AM A DULY LICENSED
4" SAN. BELOW FLOOR W/ ARCHITECT UNDER THE LAWS OF
HEAT-TRACING. 2" SAN. BELOW FLOOR W/
YOUNG ADULT
THE DISTRICT OF COLUMBIA
HEAT-TRACING.
P-2 READING

WOMENS P-2

2"V ABV. CLG.

P-5
P-1
EXTEND 4" SAN. PIPE BELOW GRADE AND
CONNECTION TO EXISTING CITY MAIN SAN.
PIPE. COORDINATE W/ LOCAL JURISDICTION 7061 Deepage Dr
CIVIL ENGINEER FOR EXACT LOCATION. Columbia, MD 21045
410-381-7100 Fax: 410-381-7110
1-800-ASC-4-MEP
(1-800-272-4637)

FLOOR PLAN
ADULT
COMPUTERS

PLUMBING
Anacostia
ADULT
LOUNGE

NEW PLUMBING PLAN - SANITARY & VENT


SCALE: 1/4" = 1'-0"

1' 0 2' 4' 6' 8' P200


© core group, pc 2006
GRAPHIC SCALE 1/4" = 1'-0"
ASC PROJECT #0611138
23. FIRE ALARM AND DETECTION SYSTEM
ELECTRICAL SPECIFICATIONS – NEW WORK 13. PANELBOARDS: ALL PANELBOARDS SHALL BE EQUAL IN MANUFACTURER TO “SQUARE D ELECTRICAL SYMBOLS

Washington, DC, 20020


DC Public Library - Anacostia
1801 Good Hope Road SE
COMPANY” TYPE NQOD. THE PANELBOARDS SHALL BE PROVIDED WITH THE FOLLOWING
GENERAL: PROVIDE A COMPLETELY ADDRESSABLE, ELECTRICALLY SUPERVISED, CENTRALLY
ELECTRICAL ABBREVIATIONS
SYMBOL DESCRIPTION
STANDARD FEATURES:
1. SCOPE OF WORK: MONITORED (VIA AUTOMATIC DIALER), POWER-LIMITED, CLASS ‘B” FIRE ALARM AND DETECTION EMERGENCY BATTERY BACK-UP TYPE FIXTURE WITH MINIMUM 90 MINUTES % PERCENT KCMIL THOUSAND CIRCULAR MILS
SYSTEM. THE BASIS OF DESIGN FOR THIS SYSTEM SHALL BE "SIMPLEX", WITH ACCEPTABLE OF RUN TIME. NUMBER OF FIXTURE HEADS AS SHOWN. REFER TO LIGHTING
A. COPPER BUSSING
A. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL LABOR AND MATERIAL, STORAGE, ALTERNATE MANUFACTURERS, EDWARDS SYSTEM TECHNOLOGIES AND NOTIFIED. FIXTURE SCHEDULE. (E) EXISTING TO REMAIN KV KILOVOLTS
B. BOLT-ON MOLDED CASE, THERMAL MAGNETIC CIRCUIT BREAKERS.
UNPACKING AND PLACEMENT TO INCLUDE, BUT NOT LIMITED TO THE FOLLOWING ITEMS: KVA KILOVOLT AMPERES
C. BUSSING AND BREAKERS SHALL MAKE A FULLY RATED (KAIC) SYSTEM. SERIES RATED EXIT LIGHTING FIXTURE, SINGLE OR DOUBLE FACE, CONNECTED TO (D) EXISTING TO BE DEMOLISHED
A. ALL DEVICES, COMBINATIONS OF DEVICES, APPLIANCES AND EQUIPMENT SHALL BE UL LISTED
EQUIPMENT IS NOT ACCEPTABLE. EMERGENCY POWER SOURCE OR PROVIDED WITH BATTERY POWER UNIT.
1. A COMPLETE POWER AND LIGHTING DISTRIBUTION SYSTEM, WHICH INCLUDES ALL PANELS, FOR THE PURPOSE, WHICH THEY ARE USED AND SHALL BE INSTALLED IN ACCORDANCE WITH (N) NEW KW KILOWATT
D. PROVIDE PANEL WITH SEPARATE EQUIPMENT GROUND BUS TERMINAL BLOCK.
FEEDERS, BRANCH CIRCUITS, SAFETY SWITCHES, TRANSFORMERS AND CONNECTIONS THERETO. NFPA 72, AS WELL AS ALL APPLICABLE LOCAL CODES, AUTHORITIES HAVING JURISDICTION AND
E. PROVIDE TYPED PANEL DIRECTORIES. EXIT LIGHTING FIXTURE-SINGLE OR DOUBLE FACE WITH DIRECTIONAL ARROWS (R) RELOCATED EXISTING LTG LIGHTING
2. COMPLETE BRANCH CIRCUIT SYSTEM. MANUFACTURER’S REQUIREMENTS.
F. PROVIDE DEAD FRONT CONSTRUCTION AND HINGED FRONT DOORS WITH A SPRING-LOADED, AS INDICATED. CONNECT TO EMERGENCY POWER SOURCE OR PROVIDED (RL) EXISTING TO BE RELOCATED MANUF MANUFACTURER
3. COMPLETE LIGHTING FIXTURE INSTALLATION, INCLUDING LAMPS. B. THE INSTALLATION OF THIS SYSTEM SHALL BE BY A COMPANY THAT SPECIALIZES IN
KEY LOCKABLE LATCH. WITH BATTERY POWER UNIT.
4. COMPLETE TELEPHONE AND COMMUNICATION RACEWAY SYSTEM, WHICH INCLUDES BOXES, INSTALLATION OF THIS EQUIPMENT AND HAS A SUCCESSFUL RECORD OF SYSTEM MAX MAXIMUM
G. OTHER FEATURES SHALL BE AS INDICATED ON THE PANEL SCHEDULES. LIGHTING CONTROL TOGGLE SWITCHES, SINGLE POLE, THREE-WAY OR (RR) REMOVE AND RELOCATE
PLASTER RINGS, CONDUITS, AND PULL WIRES. CONDUITS AND/OR PULL STRINGS SHALL BE INSTALLATIONS DATING BACK A MINIMUM OF 5 YEARS ON SIMILAR TYPES OF INSTALLATIONS. Sa S 3a S 4a
PROVIDED TO ACCESSIBLE CEILING SPACE OR COMMUNICATION CLOSET. C. THE CONTRACTOR SHALL MAINTAIN AN UP-TO-DATE SET OF DESIGN DOCUMENTS, APPROVED FOUR-WAY, 20AMP RATED, 2-POLE, 3-WIRE. MOUNT +48" AFF UNO. LETTER A AMPS OR AMPERES MCA MINIMUM CIRCUIT AMPACITY
14. CONDUCTORS: ALL CONDUCTORS SHALL BE COPPER UNLESS NOTED OTHERWISE. ALL ADJACENT SWITCH INDICATES FIXTURE GROUP CONTROLLED.
5. COMPLETE EMERGENCY LIGHTING AND POWER SYSTEM, WHICH IS CONSISTENT WITH THE PERMIT DOCUMENTS AND SHOP DRAWINGS ON-SITE AND SHALL TURN THESE DOCUMENTS OVER ABV ABOVE MCB MAIN CIRCUIT BREAKER
CONDUCTORS SHOWN ON THE DOCUMENTS SHALL BE RATED A MINIMUM OF 75 DEG C TYPE THW LINEAR SLIDE TYPE DIMMER SWITCH, SINGLE POLE OR THREE-WAY TYPE.
BASE BUILDING. TO THE OWNER UPON PROJECT COMPLETION AND APPROVAL BY THE LOCAL AUTHORITY.
600 VOLT INSULATION. SD S3D DIMMER SWITCH RATED FOR LOAD CONTROLLED (INCAND, FLUOR AND LV). MECH MECHANICAL
6. TEMPORARY ELECTRICAL POWER AND LIGHTING AS REQUIRED FOR CONSTRUCTION. D. RECORD DRAWINGS SHALL INCLUDE A CAD GENERATED SET OF DOCUMENTS, WHICH AMERICANS W/ DISABLITIES ACT
7. TESTING OF ALL CABLES AND CIRCUIT WIRING FOR CONTINUITY OF POWER AND FOR INTEGRITY INDICATE LOCATION OF ALL DEVICES, CONTROL PANELS, ANNUNCIATORS, INTERFACE MOUNT +48" AFF UNO. ADA
A. CONDUCTORS #10AWG AND SMALLER SHALL BE SOLID TYPE CONDUCTORS. CONDUCTORS COMPLIANCE MEP MECHANICAL, ELECTRICAL, PLUMBING
OF THE GROUNDING SYSTEM. ADDRESSABLE MODULES, AND END-OF-LINE DEVICES. DUPLEX RECEPTACLE, 20AMP, NEMA 5-20R. MOUNT +18" AFF UNO.
#8AWG AND LARGER SHALL BE STRANDED TYPE. MFS MAXIMUM FUSE SIZE
8. WIRING DEVICES AND FLOOR BOXES. E. CONTROL PANEL SHALL BE SINGLE LOOP ADDRESSABLE FIRE ALARM CONTROL PANEL. ARCHITECTURAL AND ENGINEERING;
B. MINIMUM CONDUCTOR SIZE TO BE #12AWG UNLESS NOTED OTHERWISE. AE
9. LIGHTING CONTROLS CONTROL PANEL SHALL BE CAPABLE OF REPORTING SUPERVISORY, TROUBLE AND ALARM OR ARCHITECT AND ENGINEER MH MOUNTING HEIGHT
C. ALL CONDUCTORS MUST BE INSTALLED IN CONDUIT, UNLESS NOTED OTHERWISE.
10. GROUNDING OF THE ELECTRICAL SYSTEM. CONDITIONS TO CENTRAL STATION VIA FLOOR, ZONE AND TYPE OF DEVICE. POWER SUPPLY DUPLEX RECEPTACLE, GROUND FAULT CIRCUIT INTERRUPTER TYPE (GFCI),
D. ALL BRANCH CIRCUITS INSTALLED IN CONDUIT SHALL BE PROVIDED WITH A SEPARATE GREEN 20AMP RATED. MOUNT +6" ABOVE COUNTER OR BACKSPLASH. AF AMPERES FRAME MIN MINIMUM
11. FIRE ALARM SYSTEM RELOCATION AND ADDITION OF NEW DEVICES AS SHOWN. SHALL BE ADEQUATE TO SERVE PANEL MODULES, RELAYS AND ALARM INDICATING AND
INSULATED GROUND CONDUCTOR.
INITIATING DEVICES. PANEL SHALL BE PROVIDED WITH A SECONDARY EMERGENCY POWER AFF ABOVE FINISHED FLOOR MLO MAIN LUG ONLY
2. WORK AND EQUIPMENT SHALL COMPLY WITH THE LATEST AND APPLICABLE ADOPTED SUPPLY WITH CAPACITY FOR OPERATING SYSTEM IN STAND-ALONE MODE FOR 24-HOURS DOUBLE DUPLEX RECEPTACLE (QUAD). PROVIDE TWO (2) 20AMP, NEMA
15. CABLES: METAL CLAD CABLE (MC) WITH AN INSULATED GREEN GROUND CONDUCTOR SHALL AFG ABOVE FINISHED GRADE MO MOTOR OPERATOR
NATIONAL BUILDING CODES (INTERNATIONAL BUILDING CODE (IBC), NATIONAL ELECTRIC CODE FOLLOWED BY ALARM MODE FOR 10 MINUTES. 5-20R IN A COMMON BACKBOX. MOUNT +18" AFF.
BE USED IN ALL CONCEALED BRANCH WIRING APPLICATIONS UNLESS OTHERWISE NOTED. TYPE
(NEC), NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) AND ALL LOCAL AMENDMENTS TO THE AHU AIR HANDLING UNIT MOCP MAXIMUM OVERCURRENT PROTECTION
ARMOR CLAD CABLE (AC) OR BX CABLE IS NOT PERMITTED.
NATIONAL CODES, AS WELL AS ALL AUTHORITIES HAVING JURISDICTION. THE ESTABLISHED 1. SUBMIT BATTERY CALCULATIONS TO SUBSTANTIATE COMPLIANCE WITH REQUIREMENTS. JUNCTION BOX
NATIONAL STANDARDS SHALL BEAR THEIR LABEL ON ALL NEW EQUIPMENT (UNDERWRITER’S 2. PROVIDE PANEL MOUNTED ANNUNCIATOR AND AUDIBLE TROUBLE ALARM ON CONTROL PANEL J J AIC AMPERES INTERRUPTING CAPACITY MTD MOUNTED
16. INSTALLATION OF CONDUIT AND CABLE:
LABORATORY-UL), FACTORY MUTUAL-FM AND ALL WORK SHALL BE IN COMPLIANCE WITH THE COVER. APPROX APPROXIMATE MTG MOUNTING
OCCUPATIONAL AND SAFETY ADMINISTRATION (OSHA). MODIFICATIONS REQUIRED BY THE ABOVE 3. PROVIDE AUTO-DIALER OR DACT TECHNOLOGY FOR COMMUNICATING ALARMS TO CENTRAL BRANCH CIRCUIT HOMERUN. NUMBER OF ARROWHEADS INDICATE NUMBER

1010 wisconsin avenue, nw


A. CABLE AND CONDUIT SHALL BE INSTALLED CONCEALED IN FINISHED AREAS. BRANCH ARCH ARCHITECT, ARCHITECTURAL N NEUTRAL
SAID AUTHORITIES TO BRING THE PROJECT SPACE UNDER CONTRACT UP TO CODE SHALL BE STATION CONNECTION, WHICH WILL BE COORDINATE WITH OWNER. PROVIDE 3/4” E.C. TO OF CIRCUITS. NUMBER OF SLASHES INDICATES NUMBER OF CONDUCTORS IF
CIRCUITS INSTALLED IN UNFINISHED AREAS SHALL BE INSTALLED IN CONDUIT.

washington, dc 20007
MADE WITHOUT ADDITIONAL CHARGE. WHERE CONTRACT DOCUMENT REQUIREMENTS ARE IN TELEPHONE BACKBOARD AND PROVIDE DEDICATED PHONE LINE FOR FIRE ALARM MORE THAN 2#12, 1#12G - 3/4" CONDUIT MINIMUM. AT AMPERES TRIP N/A NOT APPLICABLE
B. ALL EMPTY CONDUITS SHALL BE INSTALLED WITH PULL LINES.

E GEN@COREdc.com
EXCESS OF CODE REQUIREMENTS, THE CONTRACT DOCUMENTS SHALL GOVERN. DEVIATIONS COMMUNICATION USE. BRANCH CIRCUIT CONCEALED IN CEILING OR WALL.
C. CONDUITS INSTALLED INDOORS SHALL BE EMT. ATC AUTOMATIC TEMPERATURE CONTROL NC NURSE CALL

T 202.466.6116
F 202.466.6235
FROM THE CONTRACT DOCUMENTS REQUIRED BY THE ABOVE AUTHORITIES SHALL BE SUBMITTED
D. CONDUITS SERVING MOTORS, TRANSFORMERS OR VIBRATING EQUIPMENT INSTALLED IN
TO THE ARCHITECT AND ENGINEER FOR REVIEW. ATS AUTOMATIC TRANSFER SWITCH NEC NATIONAL ELECTRICAL CODE
INDOOR DRY LOCATIONS SHALL BE FLEXIBLE METALLIC CONDUIT (FMC)
F. DEVICES TO BE PROVIDED FOR THIS PROJECT INCLUDE; NFPA 72 AND ADA COMPLIANT BRANCH CIRCUIT OR FEEDER INSTALLED IN CONCRETE
E. CONDUITS INSTALLED OUTDOORS OR EXPOSED TO DAMP OR MOIST ENVIRONMENTS SHALL BE

suite 405
3. CONTRACTOR SHALL ARRANGE FOR THE PAYMENT OF ALL NECESSARY PERMITTING AND FLASHING STROBE LIGHTS (MINIMUM 15/75 CANDELA, UNO) AND COMBINATION STROBE / HORNS, AV AUDIO VISUAL NATIONAL ELECTRICAL
INSTALLED IN IMC. SLAB OR INSTALLED BELOW GRADE. NEMA
INSPECTION FEES. THIS CONTRACTOR SHALL SCHEDULE ALL REQUIRED INSPECTIONS OF THE WALL AND CEILING MOUNT TYPE AS INDICATED; PHOTOELECTRIC SMOKE DETECTORS, HEAT AVG AVERAGE MANUFACTURER'S ASSOC.
F. CONDUITS SERVING MOTORS, TRANSFORMERS OR VIBRATING EQUIPMENT INSTALLED IN
PROJECTS WITH THE LOCAL JURISDICTION AT THE REQUIRED STAGES OF COMPLETION. DETECTORS, FLOW AND TAMPER ALARMS, AND DUCT MOUNTED SMOKE DETECTORS. DUCT
OUTDOORS OR IN DAMP OR MOIST LOCATIONS SHALL BE LIQUIDTITE FLEXIBLE METAL CONDUIT CONDUIT TURNED UP AWG AMERICAN WIRE GAUGE NFSS NON-FUSED SAFETY SWITCH
DETECTORS SHALL HAVE A BASE WITH AN AUXILIARY RELAY (FOR HVAC UNIT SHUTDOWN) AND A
FLEXIBLE METALLIC CONDUIT (LFMC).
4. MEP DOCUMENTS ARE DIAGRAMMATIC AND INDICATE MAJOR COMPONENTS, GENERAL PHOTOELECTRIC DETECTOR WITH SAMPLING TUBE (LENGTH AS REQUIRED. BLDG BUILDING NIC NOT IN CONTRACT
G. ALL CONNECTORS FOR SOLID CONDUIT (EMT AND IMC) SHALL BE COMPRESSION TYPE
LOCATION OF WORK AND SYSTEMS. COORDINATE ALL TRADES AND BE FAMILIAR WITH G. WATERFLOW AND TAMPER SWITCHES SHALL BE FURNISHED AND INSTALLED BY THE
FITTINGS. ALL CONNECTORS FOR FLEXIBLE CONDUIT AND CABLE SHALL BE UL LISTED FOR USE CONDUIT TURNED DOWN BLW BELOW NO.; # NUMBER
CONDITIONS, NEW AND EXISTING, WHICH MAY AFFECT THE WORK. VERIFY AND FIELD CHECK SPRINKLER CONTRACTOR. THE ELECTRICAL CONTRACTOR SHALL CONNECT EACH DEVICE TO THE
WITH THAT EQUIPMENT.
DIMENSIONS AND CONDITIONS PRIOR TO THE START OF ANY WORK AND REVIEW THE FIRE ALARM SYSTEM. C CONDUIT NOM. NOMINAL
H. ALL CABLE AND CONDUIT SHALL BE INSTALLED PARALLEL AND PERPENDICULAR TO BUILDING
DOCUMENTS FOR ANY CONDITIONS WHICH AFFECT THIS WORK. EQUIPMENT LOCATIONS H. WHERE MULTIPLE STROBE DEVICES ARE INSTALLED IN A COMMON AREA, PROVIDE
LINES AND SHALL BE PROPERLY SUPPORTED AS RECOMMENDED BY THE NEC. THE ABOVE SHALL COMBINATION TELEPHONE/DATA OUTLET. PROVIDE PLASTER CAD COMPUTER-AIDED DESIGN NTS NOT TO SCALE
INDICATED ARE APPROXIMATE AND SHALL BE FIELD VERIFIED. THIS CONTRACTOR SHALL REVIEW SYNCHRONIZED STROBES TO ALLOW FLASH TO OCCUR SIMULTANEOUSLY.
NOT BE SUPPORTED BY MECHANICAL PIPING OR TIED TO DUCTWORK HANGERS. CABLES SHALL RING & PULL CORD TO CEILING SPACE. MOUNT +18" AFF UNO.
ALL SUPPORTING AND COMPLIMENTARY DOCUMENTS, WHICH ARE CONSIDERED A PART OF THE I. WIRING: CATV CABLE TELEVISION P PUMP; POLES
NOT BE SUPPORTED BY OTHER ELECTRICAL CONDUIT.
CONTRACT DOCUMENT PACKAGE. THESE DOCUMENTS INCLUDE; ARCHITECTURAL, STRUCTURAL,
I. WHERE BRANCH CIRCUIT CABLE ENTERS AN ELECTRICAL CLOSET, THE CABLES SHALL NOT BE FLUSH FLOOR BOX WITH DUPLEX RECEPTACLE AND CKT CIRCUIT PB PUSHBUTTON
MECHANICAL, PLUMBING AND ELECTRICAL DOCUMENTS AND SPECIFICATIONS. THESE 1. ALL FIRE ALARM WIRING SHALL BE INSTALLED IN MINIMUM OF 3/4" CONDUIT, EXCEPT USE UL
INSTALLED BUNDLED TOGETHER. RATHER THE CABLES SHALL BE PULLED INTO THE ROOM, TELE/DATA OUTLET. PROVIDE BARRIER BETWEEN DEVICE
DOCUMENTS COMPLIMENT EACH OTHER AND MUST BE UTILIZED BY ALL CONTRACTORS IN ORDER RATED "MC" FIRE ALARM CABLE FROM JUNCTION BOX LOCATED ABOVE CEILING SPACE OVER THE CLG CEILING PC PHOTOCELL
DRESSED AND TRAINED INTO SINGLE AND DOUBLE ROWS, WHICH ARE NEATLY FASTENED TO GANGS.
TO OBTAIN COMPLETE CONSTRUCTION INFORMATION. ANY INFORMATION, WHICH CONFLICTS STROBE, DOWN INSIDE THE WALL TO STROBE JUNCTION BOX. WHERE ACCEPTABLE TO THE
KINDORF RACK VIA THE PROPER TYPE OF CABLE PRESSURE CONNECTORS. THE CABLE SHALL BE COMM COMMUNICATION PH; Ø PHASE
WITHIN THESE DOCUMENTS AND SPECIFICATIONS, SHALL BE BROUGHT TO THE ARCHITECTS AND AUTHORITY HAVING JURISDICTION (AHJ), THE CONTRACTOR MAY USE UL LISTED, MC FIRE ALARM CATV (CABLE TELEVISION) OUTLET. PROVIDE PLASTER RING
SUPPORTED AND SMOOTHLY TRANSITIONED INTO THE INDICATED BRANCH CIRCUIT PANELBOARD. TV
ENGINEERS ATTENTION. CABLE. AND PULL CORD TO THE CEILING UNO. MOUNT +18" AFF UNO. CONN CONNECTION, CONNECT PLBG PLUMBING
J. COORDINATE ALL CONDUITS, AND CABLE RUNS WITH MECHANICAL PIPING AND DUCTWORK TO
2. ALL WIRING TO DEVICES SHALL BE SIZED AND INSTALLED PER MANUFACTURERS
AVOID CONFLICTS. CONT CONTINUATION PNL PANELBOARD
5. MAKE ARRANGEMENTS FOR, AND PAY ALL COSTS, AS APPLICABLE FOR TEMPORARY WATER, REQUIREMENTS. ELECTRICAL PANELBOARD, SURFACE OR
K. CONDUITS SHALL NOT BE USED AS EQUIPMENT GROUND RETURN PATHS. SEE 18. D. ABOVE
PLUMBING, POWER, LIGHTING AND HVAC AS REQUIRED TO PROPERLY CONDUCT THE WORK 3. FIRE ALARM WIRING SHALL NOT BE INSTALLED IN THE SAME CONDUIT OR JUNCTION BOXES AS RECESSED MOUNTED 208Y/120V. DD DUCT SMOKE DETECTOR PS PRESSURE SWITCH
SPECIFIED IN THIS CONTRACT AND MAINTAIN ALL EXISTING SERVICES. PROVIDE AND MAINTAIN POWER AND LIGHTING WIRING.
17. TRANSFORMERS: TRANSFORMERS, UNLESS NOTED OTHERWISE SHALL BE DRY TYPE GENERAL DIA DIAMETER QTY QUANTITY
FOR THE ENTIRE LENGTH OF THIS CONTRACT; EXITS, EXIT AND EMERGENCY LIGHTING, FIRE 4. ALL WIRE SPLICING SHALL BE PERFORMED IN JUNCTION BOXES SIZED TO ACCOMMODATE MOTOR CONNECTION
PURPOSE TYPE , EQUAL TO SQUARE D COMPANY TYPE NL, RATED 150 DEG C RISE OVER 40 DEG
PROTECTION AND ALARM DEVICES TO CONFORM TO THE REQUIREMENTS OF THE LOCAL BUILDING TERMINAL BLOCKS (NUMBER AS REQUIRED). ALL CONNECTIONS SHALL BE MADE WITH DISC DISCONNECT QUAD QUADRAPLEX
C AMBIENT WITH CLASS 220 INSULATION.
CODES. APPROVED CRIMP-ON TERMINAL SPADE LUGS, PRESSURE-TYPE TERMINAL BLOCKS OR PLUG
CONNECTORS. CABLE TAPS OR T-TAPS WILL NOT BE PERMITTED. DISP DISPOSAL RCPT RECEPTACLE
A. ALL TRANSFORMER WINDINGS SHALL BE COPPER. DISCONNECT SWITCH, NFSS OR FSS.
6. VERIFY POINTS OF CONNECTION BEFORE COMMENCING WORK. CONFIRM THE REQUIREMENTS F DN DOWN REF REFRIGERATOR
B. KVA RATING AND VOLTAGE SYSTEM CONFIGURATION ARE AS SHOWN ON THE DOCUMENTS
FOR PREMIUM TIME OR SPECIAL PROCEDURES WITH THE OWNER AND INCLUDE THE COST IN THE 2. FIELD QUALITY CONTROL AND TESTING: ALL TESTING SHALL BE PERFORMED IN THE
C. PROVIDE 4” CONCRETE HOUSEKEEPING PAD WITH A 3” REVEAL AROUND ALL SIDES. DW DISHWASHER REQD REQUIRED
BID PROPOSAL. BY SUBMITTING A BID PROPOSAL, THE CONTRACTOR AGREES TO ACCEPT PRESENCE OF A REPRESENTATIVE OF THE BUILDING MANAGEMENT. MANUAL MOTOR STARTER (TOGGLE SWITCH TYPE) WITH THERMAL
D. ALL FLOOR MOUNTED TRANSFORMERS SHALL BE INSTALLED A MINIMUM OF 3” FROM ANY
EXISTING SITE CONDITIONS NOT SPECIFICALLY EXCLUDED. EXCLUSIONS SHALL BE PROVIDED IN DWG DRAWING RES RESISTANCE

DB
SM

CB
WALL SURFACE. OVERLOAD PROTECTION.
WRITING AS A SEPARATE DOCUMENT TO THE ARCHITECT AND ENGINEER. A. THE COMPLETED FIRE ALARM SYSTEM SHALL BE FULLY TESTED IN ACCORDANCE WITH NFPA
EDH ELECTRIC DUCT HEATER RLA RUNNING LOAD AMPERES

Permit - SET
72H, AND LOCAL FIRE DEPARTMENT REQUIREMENTS, BY THE INSTALLER, AND IN THE PRESENCE
18. OUTLET BOXES FIRE ALARM MANUAL STATION.
7. ALL MATERIALS SHALL BE NEW, FREE FROM DEFECTS AND LISTED BY THE UNDERWRITERS OF THE OWNERS REPRESENTATIVE AND THE LOCAL FIRE MARSHALL. UPON COMPLETION OF A F EF EXHAUST FAN RM ROOM
MOUNT +48" AFF UNO.
LABORATORIES, INC (UL) BEFORE PROCURING MATERIALS OR EQUIPMENT. SUBMIT ENGINEERING SUCCESSFUL TEST, THE INSTALLER SHALL SO CERTIFY IN WRITING TO THE OWNER AND GENERAL
A. USE SHEET STEEL, ZINC COATED OR CADMIUM PLATED OUTLET BOXES CONCEALED FOR EL ELEVATION RTU ROOF TOP UNIT
DATA FOR MATERIAL AND EQUIPMENT PROPOSED FOR USE. VERIFY EQUIPMENT DIMENSIONS FOR CONTRACTOR. WALL MOUNTED VISUAL ALARM (OR FLASHING STROBE), CANDELA RATING
INTERIOR WORK. 15
ADEQUATE SPACE ALLOTMENT ON THE PROJECT. THE PRODUCT MANUFACTURERS AND B. TEST CONDUCTORS FOR SHORT CIRCUITS USING AN INSULATION-TESTING DEVICE. ELEC ELECTRICAL S/N SOLID NEUTRAL
B. USE CAST BOXES, ZINC-CADMIUM FINISH MALLEABLE IRON, FOR EXPOSED EXTERIOR WORK V AS SHOWN. MOUNT +80" AFF OR 6" BELOW CEILING, WHICHEVER IS LOWER.

06016.00
COMPONENT MODEL NUMBERS ARE GIVEN TO ESTABLISH A LEVEL OF QUALITY AND C. TEST INDICATING AND INITIATING CIRCUITS FOR PROPER SIGNAL TRANSMISSION UNDER OPEN
AND FOR EXPOSED CONCEALED WORK IN WET, DAMP OR EXTERIOR LOCATIONS. ELEV ELEVATOR SCH SCHEDULE

ISSUED FOR
PERFORMANCE, AND ARE NOT INTENDED TO EXCLUDE EQUIVALENT PRODUCTS OF ALTERNATE CIRCUIT CONDITIONS.

DATE
C. WALL BOXES SHALL BE 4’ SQUARE X 2 1/2” DEEP WHERE WALL CONSTRUCTION PERMITS. 110 WALL MOUNTED COMBINATION AUDIBLE/VISUAL ALARM, CANDELA RATING AS
MANUFACTURERS. ALTERNATE MANUFACTURERS OF EQUIVALENT PRODUCTS WILL BE D. TESTING INDICATING AND INITIATING CIRCUITS FOR PROPER ALARM OPERATION AND EM EMERGENCY SD SMOKE DAMPER; SMOKE DETECTOR
D. GANG BOXES SHALL BE ONE PIECE. AV SHOWN. MOUNT +80" AFF OR 6" BELOW CEILING, WHICHEVER IS LOWER.
CONSIDERED. COORDINATE, PREPARE AND SUBMIT SHOP DRAWINGS TO THE ARCHITECT AND RESPONSE AND ANNUNCIATION AT THE MAIN FIRE ALARM CONTROL PANEL.
E. FLUSH MOUNT BOXES IN ALL FINISHED WALLS, INSTALL PLASTERRINGS IN DRYWALLED OR EMS ENERGY MANAGEMENT SYSTEM SEF SMOKE EXHAUST FAN

DT
ENGINEER FOR REVIEW AND APPROVAL. SHOP DRAWINGS TO BE SUBMITTED SHALL INCLUDE, E. TEST NEW SYSTEMS FOR SPECIFIED FUNCTIONS ACCORDING TO THIS SPECIFICATION AND THE

PN
PLASTERED WALLS AND RAISED COVERTS AS REQUIRED IN WALLS WITH OTHER FINISHES SO FIRE ALARM CONTROL PANEL.
BUT NOT BE LIMITED TO: LIGHTING FIXTURES, CONTROL DEVICES, WIRING DEVICES (SWITCHES FIRE ALARM MATRIX INDICATED ON THE DRAWINGS. ENCL ENCLOSURE SF SUPPLY FAN
COVER PLATES WILL FIT TIGHT AGAINST WALL SURFACE. FACP I CERTIFY THAT THESE DOCUMENTS
AND RECEPTACLES), POWER DISTRIBUTION EQUIPMENT, PANELBOARDS, CIRCUIT BREAKERS, F. RETESTING: CORRECT DEFICIENCIES INDICATED BY TESTING AND COMPLETELY RETEST WORK WERE PREPARED OR APPROVED BY ME,
F. PROPERLY SUPPORT ALL BOXES PER THE NEC TO ALLOW FOR A RIGID HOLD AND PROPER EX EXISTING SHT SHEET
SAFETY SWITCHES, TRANSFORMERS, FIRE DETECTION AND ALARM EQUIPMENT. AFFECTED BY SUCH DEFICIENCIES. VERIFY BY THE SYSTEM TEST THAT THE TOTAL SYSTEM AND THAT I AM A DULY LICENSED
ALIGNMENT. SPEC SPECIFICATION ARCHITECT UNDER THE LAWS OF
MEETS THE EXISTING BASE BUILDING SYSTEM OPERATION STANDARD. EXH EXHAUST THE DISTRICT OF COLUMBIA
8. MAINTAIN A SET OF MEP RECORD DRAWINGS IN THE GENERAL CONTRACTORS OFFICE, AT THE G. PROVIDE INTERFACE WITH SECURITY SYSTEM TO UNLOCK ALL EGRESS DOORS IN THE EVENT
19. WIRING DEVICES: FA FIRE ALARM STD STANDARD
PROJECT SITE OFFICE. INDICATE ACTUAL LOCATIONS OF ALL EQUIPMENT, CONDUIT AND ETC., AS OF AN ALARM BY AN INITIATING DEVICE.
WELL AS DEVIATIONS OF WORK FROM THAT SHOWN ON THE CONTRACT DOCUMENTS. WHERE H. UPON ACTIVATION OF FLOOR FIRE ALARM PULL STATION, SMOKE DETECTORS, HEAT FAAP FIRE ALARM ANNUNCIATOR PANEL SWBD SWITCHBOARD
A. ALL LIGHTING SWITCHES SHALL BE RATED 20 AMPERE 120/277 VOLT AC QUIET TYPE SNAP
CONFLICTS EXIST BETWEEN EQUIPMENT OF MULTIPLE DISCIPLINES, THIS CONTRACTOR SHALL DETECTORS AND WATERFLOW SWITCH AND ETC., SHALL CAUSE THE RELEASE OF ALL SECURITY
SWITCHES. FACP FIRE ALARM CONTROL PANEL SWGR SWITCHGEAR
DEVELOP FIELD COORDINATION DRAWINGS TO ASSIST IN THE INSTALLATION AS WELL AS A DOOR LOCKS/ELECTRIC DOOR STRIKE.
B. PROVIDE NEMA 5-20R DUPLEX 125 VOLT GROUNDING TYPE RECEPTACLES UNLESS OTHERWISE FATP FIRE ALARM TERMINAL PANEL
RECORD TO INDICATE THESE ISSUES TO THE ARCHITECT AND ENGINEER. I. INCLUDE ON-SITE SERVICES OF A CERTIFIED FACTORY TECHNICIAN TO PROVIDE TECHNICAL SYM SYMBOL
NOTED.
INSTALLATION SUPPORTER FOR PANEL START UP, PROGRAMMING AND PROGRAM EDITING BASED
C. RECEPTACLES REQUIRING AMPERAGES, VOLTAGES OR CONFIGURATIONS DIFFERENT FROM FCU FAN COIL UNIT TC TIME CLOCK
9. GUARANTEE EQUIPMENT AND WORKMANSHIP FOR A PERIOD OF ONE YEAR BEGINNING FROM ON LOCAL AUTHORITY COMMENTS, ASSIST CONTRACTORS WITH TROUBLESHOOTING AND ASSIST
DUPLEX RECEPTACLES ABOVE SHALL BE AS INDICATED ON THE DRAWINGS.
THE DAY OF FINAL ACCEPTANCE OF THE WORK OR BENEFICIAL OCCUPANCY BY THE OWNER, INSTALLER FOR ONE COMPLETE FINAL SYSTEM CHECKOUT. FLA FULL LOAD AMPS TELE TELEPHONE
D. ALL WIRING DEVICES, SHALL BE IVORY IN COLOR AND MANUFACTURED BY HUBBELL, P& S OR
WHICHEVER COMES FIRST. GUARANTEE WORK SHALL BE PERFORMED PROMPTLY AND AT NO
LEVITON. FLR FLOOR TS TAMPER SWITCH
ADDITIONAL COST TO THE OWNER. GUARANTEE SHALL APPLY TO MATERIALS, EQUIPMENT AND 2. WARRANTY
E. PROVIDE DEVICE PLATES FOR OUTLET BOXES AS FOLLOWS UNLESS NOTED OTHERWISE:
SERVICES. WORK SHALL BE PERFORMED USING MECHANICS SKILLED IN THEIR RESPECTIVE FS FLOAT SWITCH TRANSSENT VOLTAGE SURGE
TRADES. THE CONTRACTOR SHALL WARRANTY THE INSTALLATION OF THIS SYSTEM FOR A PERIOD OF NOT TVSS
1. FINISHED AREAS: PRIME PAINTED STEEL IN THE COLOR OF THE DEVICE. FSS FUSED SAFETY SWITCH SUPPRESION
LESS THAN 18 MONTHS, AND THAT SHALL INCLUDE ALL DEFECTIVE PARTS, TROUBLESHOOTING
2. UNFINISHED AREAS: ZINC COATED SHEET METAL, ALUMINUM, OR CAST METAL AS TYP TYPICAL
10. INSTALL WORK IN A NEAT AND WORKMANLIKE MANNER. THE CONTRACTOR IS SOLELY OF NUISANCE ALARMS DUE TO SHORTS OR OTHER ANOMALIES. THE STANDARD MANUFACTURER FT FOOT OR FEET
APPROPRIATE FOR THE TYPE OF BOX.
RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS TECHNIQUES, SEQUENCES AND WARRANTY SHALL APPLY TO ALL DEVICES, POWER SUPPLIES AND EQUIPMENT. UG UNDERGROUND
3. WHERE MORE THAN ONE DEVICE IS INDICATED, PROVIDE A MULTI-GANG BOX AND A COMMON FVNR FULL VOLTAGE NON REVERSING 7061 Deepage Dr
PROCEDURES FOR COORDINATING WORK UNDER THIS CONTRACT.
GANG DEVICE PLATE. UH UNIT HEATER
Columbia, MD 21045
G; GRD GROUND 410-381-7100 Fax: 410-381-7110
11. MAINTAIN THE CONSTRUCTION PREMISES IN A NEAT AND ORDERLY CONDITION AND CLEAN UL UNDERWRITERS LABORATORY 1-800-ASC-4-MEP
20. TELEPHONE AND DATA OUTLETS: GEN GENERATOR (1-800-272-4637)
DEBRIS FROM THE SITE AT THE END OF EACH WORKING DAY.
GFCI GROUND FAULT CIRCUIT INTERRUPTER UNO UNLESS NOTED OTHERWISE
A. PROVIDE PLASTER RING AND PULL WIRE TO ACCESSIBLE CEILING SPACE. INSTALL PLASTIC
12. IN CASES OF DOUBT AS TO THE WORK INTENDED, OR IN THE EVENT OF NEED FOR UPS UNINTERRUPTABLE POWER SUPPLY
BUSHING IN METAL STUD TOP PLATE OR STUD OPENINGS TO AVOID CONDUCTOR DAMAGE. H; HGT HEIGHT DOOR HOLDER
EXPLANATION THEREOF, REQUEST SUPPLEMENTARY INSTRUCTIONS FROM THE ENGINEER. NO
B. PROVIDE AN OUTLET BOX AND 1” EMPTY CONDUIT WITH PULL STRING WHERE LOCATION IS IN V VOLTS
CHANGES ARE TO BE MADE TO THE WORK OF THIS CONTRACT WITHOUT PRIOR KNOWLEDGE AND HD HEAT DETECTOR
AN INSULATED WALL PARTITION OR DOES NOT HAVE A CLOSE ACCESSIBLE CEILING.
APPROVAL OF THE ARCHITECT AND ENGINEER. HOLD THE OWNER AND ITS CONSULTANTS HORIZ HORIZONTAL VA VOLT AMPERE
HARMLESS AGAINST CLAIMS AND JUDGEMENTS ARISING OUT OF THE CONTRACTOR’S

DATA SHEET
ELECTRICAL
21. PROVIDE CUTTING AND PATCHING AS REQUIRED TO ACCOMPLISH THE ELECTRICAL WORK
PERFORMANCE OF THE WORK OF THIS CONTRACT. DO NOT PROCEED WITH ANY WORK, FOR HP HORSEPOWER VFD VARIABLE FREQUENCY DRIVE
PORTRAYED ON THE DRAWINGS.
WHICH ADDITIONAL COMPENSATION IS EXPECTED BEYOND THE CONTRACT AMOUNT, WITHOUT W WATT(S); WIRE
HTR HEATER
AUTHORIZATION FROM THE APPROPRIATE AUTHORITY. FAILURE TO OBTAIN SUCH AUTHORIZATION

Anacostia
22. DISCONNECT SWITCHES: PROVIDE FUSED OR NON-FUSED GENERAL DUTY DISCONNECT IG ISOLATED GROUND W/ WITH
SHALL INVALIDATE ANY CLAIM FOR EXTRA COMPENSATION.
SWITCHES. SIZE AND RATING AS INDICATED ON THE DRAWINGS. ALL DISCONNECTS SHALL HAVE
HANDLE LOCKING PROVISIONS IN THE ON AND OFF POSITIONS. IN INCHES W/O WITHOUT
IS INFORMATION SYSTEMS WH WATER HEATER
IT INFORMATION TECHNOLOGY WF WATER FLOW SWITCH
J, JB JUNCTION BOX WP WEATHERPROOF
THOUSAND AMPERES INTERRUPTING XFMR TRANSFORMER
KAIC
CAPACITY

E100
© core group, pc 2006

ASC PROJECT #0611138


PANEL 'L' (SECT 1)

Washington, DC, 20020


DC Public Library - Anacostia
1801 Good Hope Road SE
LOCATION: 120/208V, 3Ø, 4W MOUNTING RECESSED
JANITORS CLOSET STORAGE OFFICE OFFICE 400 AMP MCB KAIC 10
CONDUCTOR CKT BKR LOAD CONDUCTOR CKT BKR
CKT EQUIPMENT C WIRE PH. AMP VOLT KVA KVA CKT EQUIPMENT C WIRE PH. AMP VOLT
METER Ø
C/T CABINET 1 LTG - TRACK 3/4" 2#12, 1#12G 1 20 120 1.3 A 1.3 2 LTG - TRACK 3/4" 2#12, 1#12G 1 20 120
3 LTG - TRACK 3/4" 2#12, 1#12G 1 20 120 1.8 B 1.8 4 LTG - TRACK 3/4" 2#12, 1#12G 1 20 120
F
2 5 LTG - GENERAL 3/4" 2#12, 1#12G 1 20 120 0.9 C 1.5 6 LTG - TRACK 3/4" 2#12, 1#12G 1 20 120
L-42,44 7 LTG - TRACK 3/4" 2#12, 1#12G 1 20 120 1.5 A 1.5 8 LTG - TRACK 3/4" 2#12, 1#12G 1 20 120
L-40 9 LTG - TRACK 3/4" 2#12, 1#12G 1 20 120 1.5 B 0.8 10 LTG - GENERAL 3/4" 2#12, 1#12G 1 20 120
L-38
11 LTG - TRACK 3/4" 2#12, 1#12G 1 20 120 1.8 C 1.2 12 LTG - GENERAL 3/4" 2#12, 1#12G 1 20 120
PNL 'L' L-32 L-41 13 LTG - TRACK 3/4" 2#12, 1#12G 1 20 120 1.0 A 1.4 14 LTG - GENERAL 3/4" 2#12, 1#12G 1 20 120

S
MENS L-34
J
15 LTG - TRACK 3/4" 2#12, 1#12G 1 20 120 1.8 B 1.5 16 LTG - TRACK 3/4" 2#12, 1#12G 1 20 120
17 LTG - TRACK 3/4" 2#12, 1#12G 1 20 120 1.3 C 1.5 18 LTG - TRACK 3/4" 2#12, 1#12G 1 20 120
L-30
19 LTG - TRACK 3/4" 2#12, 1#12G 1 20 120 1.8 A 1.0 20 LTG - TRACK 3/4" 2#12, 1#12G 1 20 120

FACP
V AV
15 15 21 LTG - TRACK 3/4" 2#12, 1#12G 1 20 120 1.3 B 1.0 22 LTG - TRACK 3/4" 2#12, 1#12G 1 20 120
L-26
L-36 23 LTG - GENERAL 3/4" 2#12, 1#12G 1 20 120 1.0 C 0.8 24 LTG - GENERAL 3/4" 2#12, 1#12G 1 20 120
L-25 YOUNG ADULT 25 GFI RCPT - BATHRM 3/4" 2#12, 1#12G 1 20 120 0.4 A 0.8 26 RCPT - GENERAL 3/4" 2#12, 1#12G 1 20 120
V
15
+40" GFI
L-28
L-39 READING 27 RCPT - ADULT LOUNGE 3/4" 2#12, 1#12G 1 20 120 1.2 B 1.0 28 VENDING MACHINE 3/4" 2#12, 1#12G 1 20 120
29 RCPT - CHILDEN'S PC 3/4" 2#12, 1#12G 1 20 120 0.8 C 1.5 30 COPIER 3/4" 2#12, 1#12G 1 20 120
REMARKS:
WOMENS

V
15 PHASE A LOAD 12.0

1010 wisconsin avenue, nw


PHASE B LOAD 13.7
PHASE C LOAD 12.3

washington, dc 20007

E GEN@COREdc.com
AV

T 202.466.6116
F 202.466.6235
75 TOTAL KVA 53.1

TOTAL CONNECTED AMP: 147.5

suite 405
PANEL 'L' (SECT 2)
LOCATION: 120/208V, 3Ø, 4W MOUNTING RECESSED
OFFICE 400 AMP MLO KAIC 10
CONDUCTOR CKT BKR LOAD CONDUCTOR CKT BKR
CKT EQUIPMENT C WIRE PH. AMP VOLT KVA KVA CKT EQUIPMENT C WIRE PH. AMP VOLT
L-27
ADULT 31 RCPT - HOT TOPICS 3/4" 2#12, 1#12G 1
Ø
20 120 1.2 A 0.8 32 RCPT - OFFICE COMP'S 3/4" 2#12, 1#12G 1 20 120
COMPUTERS 33 RCPT - CIRCULATION DESK 3/4" 2#12, 1#12G 1 20 120 0.8 B 0.7 34 DISPOSAL 3/4" 2#12, 1#12G 1 20 120
ADULT 35 RCPT - ADULT READING 3/4" 2#12, 1#12G 1 20 120 0.8 C 0.4 36 RCPT - OFFICE 3/4" 2#12, 1#12G 1 20 120
L-35
LOUNGE 37 RCPT - ADULT'S COMP'S 3/4" 2#12, 1#12G 1 20 120 0.8 A 0.2 38 RCPT - OFFICE 3/4" 2#12, 1#12G 1 20 120
39 RCPT - YOUNG ADULT READIN 3/4" 2#12, 1#12G 1 20 120 1.2 B 0.4 40 RCPT - YOUNG ADULT READING 3/4" 2#12, 1#12G 1 20 120
41 RCPT - GENERAL 3/4" 2#12, 1#12G 1 20 120 1.2 C 2.0 42 WH-1 3/4" 2#10, 1#10G 2 30 208
43 SPACE A 2.0 44 - - - - - -
45 SPACE B 0.6 46 NIGHT LIGHTS 3/4" 2#12, 1#12G 1 20 120
47 SPACE C 1.0 48 HEAT TRACING 3/4" 2#10, 1#10G 1 20 120
49 SPACE A 1.0 50 HEAT TRACING 3/4" 2#10, 1#10G 1 20 120
51 SPACE B 52 SPARE 1 20 120
53 SPACE C 54 SPARE 1 20 120
L-37 55 SPACE A 56 SPARE 1 20 120
ADULT 57 SPACE B 58 SPARE 1 20 120
READING 59 SPACE C 60 SPARE 1 20 120
REMARKS:

DB

CB

Permit - SET
CHILDRENS
COMPUTERS L-29
PHASE A LOAD 6.0
CIRCULATION PHASE B LOAD 3.7

06016.00
PHASE C LOAD 5.4
DESK

ISSUED FOR
DATE
1 (TYP)
ADULT
COMPUTERS

DT

PN
I CERTIFY THAT THESE DOCUMENTS
WERE PREPARED OR APPROVED BY ME,
AND THAT I AM A DULY LICENSED
C/T ARCHITECT UNDER THE LAWS OF
400A THE DISTRICT OF COLUMBIA
PNL 'L' PNL 'L'
FACP 120/208V
L-33 400A 400A R1 METER
3Ø, 4W
(SECT 2) (SECT 1)
120/208V 120/208V
3Ø, 4W 3Ø, 4W

CHILDRENS
READING
2 SETS (4#3/0+1#2G - 2 1/2"C)
RISER NOTES: R# INCOMING SERVICE
FROM BGE (BY OWNER)
1. PROVIDE A NEMA 3R 3P+S/N, 400A - ELECTRICAL RISER DIAGRAM
250V FUSED SAFETY SWITCH @ 400A. NOT TO SCALE 7061 Deepage Dr
L-31 Columbia, MD 21045
410-381-7100 Fax: 410-381-7110
1-800-ASC-4-MEP
110 (1-800-272-4637)
AV
EXOTHERMIC WELD
F

GROUNDING GROUNDING
EXOTHERMIC WELD ELECTRODE ELECTRODE #1/0 COLD WATER SYS
CONDUCTOR #1/0 CONDUCTOR #1/0

POWER PLAN
HOT

ELECTRICAL
GROUNDING
MAIN SERVICE GROUND
TOPICS ELECTRODE NON-METALLIC
PROTECTIVE CONTINUOUS

Anacostia
SLEEVE
ELECTRICAL POWER PLAN SUPPLEMENTAL GROUND ROD
SCALE: 1/8" = 1'-0"
CONCRETE FOUNDATION
GROUNDING NOTES:
GENERAL NOTES POWER NOTES: # #2 AWG BARE COPPER 1. GROUND PER NATIONAL ELECTRICAL CODE (NEC) SECTION 250 PART H.
CONDUCTOR 2. GROUND SYSTEM TO INCLUDE FOUNDATION GROUND AND METAL WATER
1. CONTRACTOR TO VERIFY EXACT LOCATION AND MOUNTING HEIGHTS OF ALL 1. FLOOR MOUNTED FLUSH POKE-THRU BY WIREMOLD: CATALOG #RC4ATCBK OR BONDED TOGETHER PER NEC.
REBAR 3. TEST GROUND SYSTEM RESISTANCE & VERIFY LESS THAN 5 OHMS.
RECEPTACLES, COMMUNICATION DEVICES AND JUNCTION BOXES WITH APPROVED EQUIVALENT. PROVIDE COM50 COMMUNICATION ADAPTER AS NECESSARY. 2" MIN 4. ALL GROUNDING WIRES SHALL BE COPPER.
ARCHITECT PRIOR TO INSTALLATION. COORDINATE CORE DRILL WITH ARCHITECT PRIOR TO INSTALLATION.

2. REFER TO DWG E-1 FOR SPECIFICATIONS. 2. WH-1, 4KW, 208V, 1Ø. PROVIDE A NFSS 30A - 250V, 2P SAFETY SWITCH. DIRECT CONTACT
DIRECT CONTACT
30 FEET MINIMUM WITH EARTH
WITH EARTH
E200
GROUNDING DETAIL © core group, pc 2006

NO SCALE ASC PROJECT #0611138


Washington, DC, 20020
DC Public Library - Anacostia
1801 Good Hope Road SE
JANITORS CLOSET STORAGE OFFICE

TYPE B (TYP) TYPE F (TYP) TYPE C (TYP)

S S LIGHTING FIXTURE SCHEDULE


K L-21
TYPE DESCRIPTION MANUFACTURER CATALOG LAMPS MOUNTING VOLTAGE REMARKS
K NUMBER QTY TYPE
J LSI SINGLE CIRCUIT PENDANT MOUNTED
A DIMMABLE TRACK LSI - - - TRACK 120
MENS NL L-5 SDt
2' X 4' RECESSED FLUORESCENT
G
B LIGHTING FIXTURE LIGHTOLIER QHE2GPFOP228227PG 2 54W T5 HO 3500K RECESSED 120
SDu
2 H

S
L-23
L-24 YOUNG ADULT C LSI DIMMABLE WALL WASHER LSI 239-00-S-WL W/ C995 1 50PAR TRACK 120

S
READING
SDw D LSI DIMMABLE ACCENT LIGHT LSI 238-00-S-WL W/ C998 1 50PAR TRACK 120

WOMENS SDv
G E EPI DOWNLIGHT EPL A19/4 COL 1 90W A19 RECESSED 120
J

L-19
S

L-17 F EPI WALL WASHER EPL A19/4 WW COL 1 90W A19 RECESSED 120

1010 wisconsin avenue, nw


J

washington, dc 20007
SDs G WALL MOUNTED VANITY LIGHT LIGHTOLIER BCW6X48 SW4S32HPFUNVHI 2 32W T8 SURFACE 120

E GEN@COREdc.com
T 202.466.6116
F 202.466.6235
L-22
H DIMMABLE BALL PENDANT GLO - 1 100W PENDANT 120
TYPE J (TYP)

suite 405
J 8' LINEAR PENDANT FIXTURE
I W/ DIMMING BALLAST ZUMTOBEL EE45458T305 4 54W T5 PENDANT 120
SDr CEILING PAD
W/ LIGHTING
H H J PENDANT LIGHTOLIER - 4 26/32/42W PENDANT 120

ADULT K 4' UTILITY STRIP FLUORESCENT LIGHT - - 1 32W T8 SURFACE 120


NL SDq COMPUTERS
ADULT L-20 SDp

LOUNGE J J
L-13 EXIT SIGN LIGHTOLIER LLC2-U-R-W - LED SURFACE 120

REMARKS:

1. ALL CEILING TYPES SHALL BE VERIFIED PRIOR TO FIXTURES BEING ORDERED.

2. ALL FLUORESCENT FIXTURES SHALL BE PROVIDED WITH HIGH POWER FACTOR ELECTRONIC BALLASTS. ALL HID FIXTURES SHALL BE PROVIDED WITH HIGH POWER FACTOR BALLASTS.
SDl L-15
L-14 3. REFER TO ARCHITECTURAL PLANS FOR ADDITIONAL INFORMATION ON LIGHT FIXTURES SELECTED.
J L-18 J

SDo ADULT SDn 4. ALL FIXTURES SHOWN ESTABLISH THE BASIS OF DESIGN OR LEVEL OF QUALITY EXPECTED, IF ALTERNATE FIXTURES ARE SUBSTITUTED DURING THE SUBMITTAL PROCESS, THE ENGINEER
SDk
READING ARCHITECT RESERVE THE RIGHT TO REJECT THE SUBSTITUTED FIXTURE BASED UPON OUR PROFESSIONAL JUDGEMENT.
J L-16
5. ALL FIXTURES PROVIDED ARE EXPECTED TO HAVE ALL APPURTENANCES, MOUNTING HARDWARE AND ETC. PROVIDED IN ORDER TO PROVIDE A PROPER INSTALLATION.
SPECIAL SDj

DB

CB
CEILING PAD
CHILDRENS
L-12

Permit - SET
COMPUTERS
FOR CHILDREN
CIRCULATION H

06016.00
DESK

ISSUED FOR
DATE
ADULT SDa SDb SDc SDd SDe SDf SDg SDh SDi SDj SDk SDl
COMPUTERS

DT

PN
I CERTIFY THAT THESE DOCUMENTS
WERE PREPARED OR APPROVED BY ME,
SDm SDn SDo SDp SDq SDr SDs SDt SDu SDv SDw AND THAT I AM A DULY LICENSED
ARCHITECT UNDER THE LAWS OF
L-10 THE DISTRICT OF COLUMBIA
L-6 L-9 L-7
L-8
SDi TRACK SWITCH BANK DETAIL
SDe SDg
SDf
SDh LIGHTING NO SCALE

J J J J
SDm

CHILDRENS L-11 J

READING

L-3
L-4
NL
SDc SDd 7061 Deepage Dr
Columbia, MD 21045
J L-2 L-1 J
410-381-7100 Fax: 410-381-7110
1-800-ASC-4-MEP
(1-800-272-4637)
SDa SDb

J J

LIGHTING PLAN
1
HOT (TYP) TYPE D (TYP)

ELECTRICAL
TOPICS
ELECTRICAL LIGHTING PLAN

Anacostia
SCALE: 1/8" = 1'-0"

GENERAL NOTES LIGHTING NOTES: #

1. CONTRACTOR TO WIRE ALL EXIT SIGNS, BATTERY PACKS AND


1. CONTRACTOR TO COORDINATE EXACT LOCATION OF ALL LIGHTING
FIXTURES AND CONTROLS WITH ARCHITECT PRIOR TO INSTALLATION NIGHT LIGHTS TO CKT 46 IN PANEL 'L'.

2. SWITCH BANK, SEE DETAIL THIS SHEET.

E300
© core group, pc 2006

ASC PROJECT #0611138