59 Bus communication with ABB circuit-breakers
E.2 Stored energy motor operator MOE-E
Tmax moulded-case circuit-breakers series T4, T5 and
T6 can carry out opening and closing commands from
remote control when they are equipped with MOE-E
motor operator and AUX-E auxiliary contacts in elec-
tronic version (provided by default together with MOE-E).
MOE-E motor operator is constituted, besides the real
motor operating mechanism, by an electronic actuation
unit, which converts the digital signals coming from the
remote supervision system into their equivalent power
signals necessary to perform the mechanical opening
and closing operations of the circuit-breaker. The digital
signals coming from the supervision system are acquired
by the trip unit and sent to the motor operator according
to the scheme of Figure E.3.
AUX-E auxiliary contacts communicate to the trip unit the
circuit-breaker state (open/closed/tripped) and according
to this information, the trip unit shall carry out or not the
opening, closing and reset commands it receives by the
supervision system.
In this way, the trip unit consents only to the actuation of
the commands which are compatible with the real state
of the circuit-breaker (for instance it shall not consent
to a closing command when the circuit-breaker is in the
tripped state).
Figure E.3: Operating principle of MOE-E and AUX-E modules
A
n
n
e
x
E
:
A
U
X
-
E
a
u
x
i
l
i
a
r
y
c
o
n
t
a
c
t
s
a
n
d
M
O
E
-
E
m
o
t
o
r
o
p
e
r
a
t
o
r
MOE-E
MOE-E
Circuit-breaker
Modbus
AUX-E
AUX-E
Trip-unit
Trip-unit