31,25 Kbit/s
32 Address
FF Power Supply 12 dev. @ 1s scan
CONTROL ROOM
Trunk
FIELD
Min. 9V Tx @ 14 mA
Min. 10mA Pos @ 22mA
Typical 12-16
devices.
Special
Bulk power ? protection
for fieldbus
power
Hazardous Area supply?
protection?
CONTROL ROOM
What FIELD
approvals
for wiring
hub and What
Field Wiring
junction approvals
Hub
box? for Fieldbus
devices?
Hazardous area
FOUNDATION Fieldbus Devices
Ex i/Intrinsically Safe
ENTITY or FISCO
CONTROL ROOM
Ex-e FIELD
No live Field Wiring
maintenance! Hub
Ex-d / Ex-e
Instruments
Hazardous area
FOUNDATION Fieldbus Devices
CONTROL ROOM
Hazardous area
FOUNDATION Fieldbus Devices
24Vdc
24Vdc FISCO power supply
(IIB / IIC)
CONTROL ROOM
Live
Maintenance FIELD
!
Intrinsically Safe
Field wiring hub
Zone 1
Intrinsically safe FISCO Fieldbus devices Division 1
24Vdc
24Vdc
Trunk #2 Trunk #3
Zone 1
Intrinsically safe FISCO Fieldbus devices Division 1
Redundant FISCO
Bulk power input 24Vdc
24Vdc power supply
CONTROL ROOM
Intrinsically FIELD
Safe trunk Zone 1
and spurs
Intrinsically Safe
Field wiring hub
265mA available,
(280 mA)
typically 14-16 devices
Power supply
Singel or Redundant
Up to 8 channel
modules available
Increased safety
(Ex e) trunk CONTROL ROOM
FIELD
Fieldbus
Barriers
IS spurs
HOST / LAS
POWER SUPPLIES
Power
Supply
Entity IS FISCO
Intrinsically safe trunk and
spurs?
„Live-working „ permitted in any
part of field network?
Simple safety documentation?
Eliminate cable parameter
calculations?
Gas Group IIB option?
Max output current 80mA 265mA
FISCO Fieldbus
Barrier
IS Spur? Live Maintenance?
IS Trunk? Live Maintenance?
Simple documentation?
Redundant Power
Redundant Field Wiring Hub
Compatible with FISCO field
devices?
Compatible with Entity field
devices? Only with spur
connector!
24Vdc
24Vdc FNICO power supply
CONTROL ROOM
FIELD
Live-workable Ex n or Intrinsically
Non-incendive Safe Field wiring
trunk and spurs hub
Division 2
Non-incendive or Intrinsically safe Fieldbus devices
Zone 2
265mA available,
typically 14-16
devices
FISCO, IIB Gas Groups
Host
Diagnostic modules
Fieldbus testers
Devices on net
# transmissions
# failed transmissions
Retransmisson rate
Average noise in diff.bandwidth
Peak noise in diff.bandwidth
Voltage level of all devices
Signal level of all devices
Short Circuit of all dev.
8 DI / 4 DO (low power)
ATEX certified zone 1 & 2
8 ch Temp. Multiplekser
RTD and THC
Panel Mounting