You are on page 1of 3

TECHNICAL PAPER

POWER QUALITY BASIC


ENGR. ARSENIO A. ABELLANA-PEE,MScEE
1. Introduction
IEEE 1100 defines power quality as “the degree to which both the utilization and
delivery of electrical power affects the performance of electrical equipment”.Power
quality affects system performance and operating costs.

I had my first experience on the importance of power in the fundamental and various harmonics and so
quality during a consultancy project with a trip erroneously. Also,leakage currents may reach
European company more than a decade ago.The thresholds causing residual current devices to trip.
European engineer was complaining of poor power
quality that may result in equipment 2.2 Computer problems:lock up,damaged,loss of
malfunctioning.The said equipment required a very data
tight voltage regulation which the utility cannot A voltage drop between the equipment and true
meet.A generator has to be provided to solve the earth may be due to earth current from the
problem. equipment. Although small, this noise voltage may
be comparable with the signal voltages, on which
Another experience was the improper operation of IT equipment operates and creates disturbance.This
delicate testing equipment, of an electronic kind of disturbance cannot be eliminated
manufacturing company,due to transients.A entirely - and consequently reduces data
TVSS(Transient Voltage Surge Suppresor) network throughput. As a result, PCs will often slow down
was installed and a significant grounding or lock-up, a frequent phenomenon in today’s
improvement using chemical grounding was set-up offices.
to solve the problem.
Lightning and switching strikes occuring “close” to
We experienced a main distribution circuit breaker computers and other electronic equipment, may
overheating and tripping when the current was completely damage the equipment if surge
below rated value.We had to force air to cool the protection is insufficient.
contacts using a big industrial fan.We found out later
that harmonics was the culprit and the ammeters 2.3 Lights flickering
used were incapable to sense true RMS current.
Switching, short-circuits and load changing produce
A decade ago the above mentioned scenarios may short duration changes in voltage that can result in
seem to be ‘isolated cases’.Nowadays such light flicker.Voltage sags, which are the consequence
problems are common- with the proliferation of of large load fluctuation and too low local electrical
non-linear/electronic loads such as: computers system short circuit power, may also cause light
printers,copiers,fax machines,UPS,electronic control flicker.
of equipment,etc.

The following factors determine if you’re likely to 2.4 Synchronization problems of processing
suffer from power quality problems: equipment and malfunctioning of motors due to
* the quality of the utility supplied voltage harmonics
* the types of loads in your installation
* the sensitivity of your equipment to various kinds Additional zero-crossings within a cycle,caused by
of disturbances harmonic distortion, of the sine wave; can affect
sensitive measurement equipment. and cause
2. Power Quality Problems synchronisation problems of process control
equipment .PLC devices may lock up.
Power quality problems spread throughout the sys-
tem causing shutdowns,greater energy Voltage harmonics cause adverse effects in direct
losses,reduced equipment life;all costing a lot of line-connected induction motors. The 5th harmonic
money. creates a counter-rotating field which impedes
normal motor rotation. The 7th harmonic creates a
Some signs of power quality problems are the rotating field beyond the motor’s synchronous
following: speed. The resulting torque pulsing causes wear
and tear on couplings and bearings. Since the speed
2.1 Nuisance tripping of circuit breakers is fixed, the energy contained in these harmonics is
Due to limitations of current sensing devices, circuit dissipated as extra heat, resulting in premature
breakers may incorrectly sum the current contained ageing. Harmonic currents are also induced into the

THE ELECTRICAL ENGINEER FIRST QUARTER 2009 35


TECHNICAL PAPER

rotor causing further excess heating. The additional solutions can represent quite a challenge. In the
heat reduces the rotor/stator air gap, reducing future, engineers will be able to confidently predict
efficiency even further.Bottomline,there is a marked the likely scale of problems and have practical
power loss increase. experience of solving them. By then, perhaps
In extreme cases when the motor is operating in a building owners and operators will have realized
high harmonic content environment it may be that prevention is always cheaper than cure.
damaged because of overheating.
3.1 Surge protection
2.5 Noise interference to telecommunication lines TVSS which are properly sized and strategically/
The level of electrical noise may produce correctly placed effectively handles
interference signals, which exceed surges.Grounding improvements have to be done
telecommunication immunity level.This increases to ensure efficient bypassing of the surge.
the probability of transmission error rates.
. 3.2 UPS (un-interruptible power supply)
2.6 Transformers and cables overheating IT or process control equipment usually have some
Harmonics produce extra eddy current losses and kind of UPS to ensure voltage stability and quality.
skin effect losses due to its higher frequency. These This can range from simple low power units
losses lead to transformers and cables protecting individual server computers to a large
overheating. Additionally triple n harmonics add up central unit rated at up to 1 MVA or so. UPS
and flow in neutral conductors and delta windings strategy must be carefully thought out because UPS
of transformers creating additional extra heat. energy i is expensive and should be used selec-
tively. The most frugal approach is to use UPS power
only to maintain the server computers, process
control equipment and safety equipment long
3. PQ problems’Solutions enough to allow an orderly shutdown and/or
evacuation - this leaves all the client computers and
The list of possible solutions for power quality auxiliary plant without power. At the other end of
problems is long and non-complete. There is no the spectrum, the UPS may be dimensioned to
single solution to power quality problems. Each support virtually the whole operation for the time
problem type has a range of possible mitigation required to bring an auxiliary supply on-line. For
approaches applied. In the real world, it is likely most situations, the optimum will lie somewhere
that several problems will co-exist, and the between these two extremes. .
solutions adopted must be compatible with each 3.3 Back-up generator
other and with the loads that make up the Because of the start-up delay, the generator is the
installation. second line of defense against power blackouts.
One must beware of the so called wonder This device is able to provide power to a large
solutions that are sometimes heavily marketed as portion of loads over a longer period of time.
curing a particular problem in all circumstances . In
actual practice, such panacea does not exist! The 3.4 True RMS measurement
optimum mix of solutions must be seeked, for the Measuring is knowing. True RMS measured values
problems being experienced and expected to arise can be significantly higher than the incorrect
in the future in the context of the installation. values measured by average reading meters. To
be completely sure, all measurement instruments
Always note that the electrical load is not static. must be true RMS instruments.
Differences in equipments’ duty cycles and
variations in working patterns result to a constantly 3.5 Transformer derating
changing load pattern. A large office building, for Transformers are derated for harmonic loads . It
example, may have hundreds of mutations per year should be noted that the additional heat
so that the spectrum of aggregate harmonic generated by harmonics can lead to a significant
currents - in the installation changes constantly. decrease in equipment life. Use of a K-rated
The harmonic profiles from IT equipment do not transformer, specially designed to cope with
average out but, especially for the third and fifth harmonic loads, should be preferred over trans-
harmonics, add up. former derating because the K-rated transformer is
designed to have lower eddy current losses. A
Operation of short duty cycle equipment, such as derated transformer has larger losses - it is simply
lifts and metal working equipment causes local oversized so that the resultant heat can dissipate.
voltage variations to add to those that originate in On a practical level, it is difficult to maintain the
the distribution system. derating of a transformer over its lifetime - as the
The result is that power quality problems are often load grows, the derating tends to be overlooked
stochastic in nature and require careful monitoring and the transformer becomes seriously overloaded.
to define fully.

The cost of power quality problems, in terms of lost 3.6 Motor derating
output and disruption varies widely depending on Voltage unbalance and harmonic voltages result in
the type of industry. Unfortunately, for a building additional losses in electric motors, so that the
in design stage, the nature and size of the final motor cannot be fully loaded up to its rated power.
load is generally unknown so potential power qual- NEMA provides some guidance on how to derate
ity problems and their costs are difficult to quan- the motor in the presence of harmonic voltages.
tify. Building a business case for investment in PQ High efficiency motors (Eff1-class) not only save

36 THE ELECTRICAL ENGINEER FIRST QUARTER 2009


TECHNICAL PAPER

energy , but they are also more robust against


some of the problems mentioned earlier. Using more
and better materials, they run cooler and are bet-
ter suited to handle the extra heat generated due
to harmonics or inrush currents at start-up after a
voltage dip.

3.7. Dedicated circuit


ABOUT THE AUTHOR
Loads that are sensitive to harmonic pollution
should be served by dedicated circuits. Heavy loads
should also have their own circuits, in order not to
affect other loads during start-up.
ENGR.ARSENIO A. ABELLANA is a Senior
3.8. Multiple cables for harmonic loads Member of IIEE.He was the IIEE Region VII
Apart from the additional heat generated by Regional Governor early 2007.
neutral currents, the effective cross-section of the
cable is reduced because of skin effect. Using larger He obtained his BSEE and BSME degrees from
diameter cables is hardly a solution, since the the Cebu Institute of Technology;and his MScEE
current will continue to be displaced towards the from UP Diliman.He completed a graduate course
periphery of the conductor. Hence, in Advanced Power Systems from the Penn-
one should use multiple cables, appropriately sylvania State University,USA.He placed 5th in
disposed to maintain balance. the Asst.EE board examination and 4th in the Pro-
fessional EE board .He is the 2001 CIT Outstand-
3.9. Active Harmonic filters ing Alumnus in the field of Research.
A best practice solution but expensive. However,
they are extremely flexible and adaptable He has over 30 years experience in the academe
and especially useful when dealing with a and in industry occupying senior engineering man-
changing harmonic culture. agement positions.

3.10.TN-S rewiring Currently he is a freelance energy management/


TN-C systems, with the so-called PEN-conductor, conservation consultant.
have become the exception, where, in some
countries,they used to be the rule. In the email address:nonet_aaa@yahoo,com
standards committees, the PEN-conductor is now
considered as a special case. For IT-intensive
buildings, TN-C is no longer allowed. From an EMC
viewpoint, TN-S systems are superior. References:

Conclusion
With the rising cost of energy,it is imperative to
minimize losses attributable to poor power quality. 1.Schneider Electric: Module on Power
At present, most energy-intensive sites suffer to a Management
certain degree from poor power quality,while most
sites have already adopted some solutions. This is 2.European Copper Institute:Power Quality
typically the purchase of a UPS, back-up generator, Self-Assesment Guide,May 2002
adoption of true-RMS measurement and comple-
mented with some of the other solutions, such as
TVSS, TN-S rewiring, active harmonic filters, etc.It
is unlikely that a single solution will be effective.
Careful design of a solutions mix, tailored to the
PQ problems experienced, and based on a detailed
understanding of the causes of the PQ problems,
is needed.

congratulations to the winners of


Research Design Contest

1st Place Technological University of the Philippines—Manila


2nd Place Polytechnic University of the Philippines—Manila
3rd Place Pamantasan Lungsod ng Manila

---from the The Electrical Engineer Staff

THE ELECTRICAL ENGINEER FIRST QUARTER 2009 37

You might also like