Transformer Bushings
with Porcelain Insulator
24-170 kV Type RTKF
Bushings
RIP
For more than 40 years we at Micafil have been Routine testing
successfully developing and implementing under
Each bushing is routine tested before leaving the
vacuum Resin Impregnated Paper technology for
factory. The tests, either according to IEC or IEEE
high voltage bushings. We are proud of our leading
Standard, include partial discharge, tanδ and capac-
position in this technology, practice proven, well
itance measurement, as well as power frequency
known and accepted worldwide. The base of more
voltage withstand test. The test tap is also tested.
than 50.000 RIP bushings in operation speaks for
itself. Here are main advantages of RIP technology:
Solid body
- dry, oil-free
- fire resistant
- environmental friendly
- pressure-free, explosion resistant
- high earthquake and vandalism withstand
- damaged bushings are highly suitable
for emergency service
- any position (vertical to horizontal)
during storage, handling and in operation
allowed
Application
Micafil Resin Impregnated Paper bushings of type
PORIP are designed for application on oil filled trans-
formers, covering the nominal voltage range from
24kV to 170 kV. They are used to connect transfor-
mer winding leads with overhead lines or air-insula-
ted bus ducts. The CT spaces of 0 and 300 mm are
available as a standard, other lengths on request.
The very short bushing’s lower part allows space
saving transformer design.
Design
Accessories
Test Tap
Each bushing is equipped with a standard test tap.
The test tap is connected to the outmost aluminium
layer and is automatically earthed, Fig. 9. Each test
tap is tested with 3kV, 50Hz, for 1 minute.
For a testing purpose the cap must be unscrewed
and female-female pin adapter used. Such an
adapter is available from Micafil.
Type RT K F IEC IEEE / ANSI C u rrent (A)
Ø max. 330
Ø max. 355 Ø max. 390
test
tap
Ø 130 Ø 170
sealing Ø 92
area Ø 230 Ø 270
6 holes
Ø 16 12 holes
8 holes Ø 16
Ø 16
Fig.
1
L
665
L16
120
L2 L4 L5 L6
0
L6 Fig.
Technical Data
405 230 95 5 RTKF 24-150/1000 T
1
1
965
780
420
140
300
0
and
500 325 95 5 RTKF 36-200/1000 T
1
1
1080 440
900 140
620 450 95
300
0
5 RTKF 52-250/1000 T
Dimensions
1 1200 440 300
1 1165 175 0
850 675 100 5 RTKF 72.5-350/1000 T
1 1465 475 300
2 1370 230 0
1000 840 100 5 RTKF 100-450/800 T
2 1670 530 300
2 1680 310 0
1230 1070 105 5 RTKF 123-550/800 T
2 1980 610 300
3 1910 360 0
1380 1220 105 6 RTKF 145-650/800 T
3 2210 660 300
4 2215 420 0
1625 1465 105 6 RTKF 170-750/800 T
4 2515 720 300
Ø max.250
max. 405
Fig.7
cable bolt
Ø 40 Ø 40
test
tap
Ø 170
Ø 270
sealing Ø 159
area Ø 75
Ø 65
Ø 134
Ø 109
12 holes
Ø 16 Fig.5 Fig.6
Electrical shield Electrical shield
for 24 - 123kV for 145 and 170kV
Fig.4
RTKF 170 -
Recommendation for Checking and
Bushings Installation Maintenance
Distance from bushing’s lower part to the earthed One of the main advantages of dry PORIP bushings
parts depends on the shape of surrounding parts, is that they are fully check/maintenance-free.
as well as on quality and condition of the transformer If there is any problem on the transformer or in the
oil. The recommended minimum distances (A) to be network, the condition of the bushing can be checked
used under standard conditions are shown in Fig. 8. by measuring tanδ and capacitance of the bushing’s
active part, using the test tap.
Fig. 8 Fig. 9
Test tap
A
Our concept - your benefit
R = RIP bushing
T = Transformer application
K = kurz (in German = short lower part)
F = Freiluft (in German = outdoor)
Micafil Ltd.
Badenerstrasse 780
CH – 8048 Zurich
Switzerland
Phone +41.1.435 63 33 All information in this document is subject to change
Fax +41.1.435 64 44 without notice and does not represent a commitment
E-mail info@micafil.ch on the part of Micafil Ltd.
or visit our homepage: www.micafil.ch