You are on page 1of 121

Engineering Encyclopedia

Saudi Aramco DeskTop Standards

Drafting Instrument Loop Diagrams

Note: The source of the technical material in this volume is the Professional Engineering Development Program (PEDP) of Engineering Services. Warning: The material contained in this document was developed for Saudi Aramco and is intended for the exclusive use of Saudi Aramcos employees. Any material contained in this document which is not already in the public domain may not be copied, reproduced, sold, given, or disclosed to third parties, or otherwise used in whole, or in part, without the written permission of the Vice President, Engineering Services, Saudi Aramco.

Chapter : Drafting File Reference: AGE10803

For additional information on this subject, contact N. H. Alahaimer on 874-0876

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

CONTENTS Information Instrument Loop Diagram Ild Symbols And Abbreviations Interpreting Ilds Interpret An Ild For A Pneumatic Instrument Control Loop Interpret An Ild For An Electronic Instrument Control Loop Tracing Current Flow In Control Loops Computer Relays Computer Relay Symbols Instrument Systems Foxboro Spec 200 The Honeywell Vutronik Control Loop The Honeywell Vutronik Alarm Card Examples Of Honeywell Cards Honeywell Resistance To Current Converter Card Work Aids Glossary

PAGES

1 1 29 37 44 57 59 59 67 67 83 96 100 102 104 119

Saudi Aramco DeskTop Standards

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

Instrument Loop Diagram Every process control loop has an instrument loop diagram (ILD) drawn for it. ILDs give more information about control loops than any other drawing. Although they are of interest mainly to instrumentation engineers and tech-nicians they are one of the most common drawings seen in Saudi Aramco.
ILD Symbols And Abbreviations

Handout No. 1 (Drawing No. 990-J-36492 Sheets 1 and 2) shows common ILD symbols and abbreviations. Some of them will be described in detail in this module.
Orifice Plate. Figure 1 shows the symbol for a flow element orifice plate. Figure 2 shows an

orifice plate.

L LINE NUMBER

FLOW ELEMENT ORIFICE PLATE


MARK NO. BORE

CORRECT SIZE NUMBER MUST MATCH BORE SHOWN ON ILD

1.550

ORIFICE PLATE

OW FL

CORRECT DIRECTION NUMBER ON PLATE MUST FACE UPSTREAM FIGURE I. FLOW ELEMENT, ORIFICE PLATE

Saudi Aramco DeskTop Standards

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

ILD Symbols and Abbreviations(Cont'd) Orifice Plate(Cont'd). An orifice plate is placed into a pipeline to cause a pressure differential

between its upstream and downstream flow. H and L stand for High and Low. They indicate the high and low pressure sides of the plate. The difference in pressure is used to indicate flow rate. Pressure differential varies as the square of the flow rate. Therefore, the square root of the pressure differential reading is needed in order to obtain the linear value of the flow rate. Process variable measuring devices, such as orifice plates, are sometimes called elements. The mark number, seen in Figure 1, is the identification, or tag, number given to the flow element. Bore is the size of the hole, in inches, in the orifice plate. The line number is the identification number of the pipeline.
Control Valve. Figure 3 shows the symbol for a control valve. The letter S above the small

triangle means there is an air supply to open or close the valve. The abbreviation INST means that an instrument air signal is supplied to the valve positioner. The positioner is shown by the square block. The output air signal is shown going to the top of the valve. Therefore, the valve operates by air pushing down onto the diaphragm. The mark number for this valve would be PCV, TCV, LCV, or FCV (for pressure, temperature, level or flow control valve) followed by the loop number. Size rating is the size, in inches, of the valve inlet and outlet bore. A. F. ACTION, sometimes shown only as ACTION, says what the valve will do if there is an Air Failure (AF). The word OPEN or CLOSE will be shown after A.F. ACTION.

S INST.

OUTPUT

LINE NUMBER
MARK NO. SIZE RATING A. F. ACTION

DIAPHRAGM OPERATED GLOBE VALVE WITH POSITIONER

FIGURE 3.

CONTROL VALVE

Saudi Aramco DeskTop Standards

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

ILD Symbols and Abbreviations(Cont'd) Electrical Switches. Figures 4 and 5 show electrical switches. In Figure 4, NO means Normally

Open. NC means Normally Closed. The letter C on its own means Common. By operating the Hand Switch, C can be connected either to NO or to NC. Mark No. is the identification of the switch. In Figure 5, SET AT is the value of the process variable at which the switch will automatically trip open or close. The value will be shown in psi, F, or %, depending on the type of switch used (that is, the type of process variable that is being controlled). The symbol % is often used in level control. Level may be given not as a dimension but as a percentage of the vessel capacity. For example the set point may be 75% to show that the vessel should be kept at 75% full.

NO OR NC HAND SWITCH C
MARK NO.

FIGURE 4

LINE OF EQUIPMENT MARK NO.

SWITCH ( SINGLE )
MARK NO. SET AT

FIGURE 5. LEVEL SWITCH ( SINGLE )

Saudi Aramco DeskTop Standards

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

ILD Symbols and Abbreviations(Cont'd) Lamps And Lights. Figure 6 shows the symbols used for lamps and lights.

LAMP

MARK NO.

RED

RUNNING LIGHTS GREEN


MARK NO.

FIGURE 6

When a light is not identified by a color, the light will usually be white. The mark number will give the number of the instrument loop to which the light is connected.

ILD Line Symbols. Figure 7 shows ILD line symbols. Lines may be broken to avoid drawing

over equipment or information. The line may then be continued on the other side of the equipment or information.

PROCESS LINES INSTRUMENT AIR LINES INSTRUMENT ELECTRIC LINES INSTRUMENT CAPILLARY TUBES LINE BREAK LINE CONTINUES

FIGURE 7. ILD LINE SYMBOLS

Saudi Aramco DeskTop Standards

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

ILD Symbols and Abbreviations(Cont'd) Air Supply. Figure 8 shows more ILD abbreviations. Those on the left indicate air supply.

Those on the right are as stated.

D/P + _ S AIR SUPPLY A/S AO / AFS AC / AFO H EITHER SYMBOL MAY BE USED. L GND

DIFFERENTIAL PRESSURE POSITIVE TERMINAL NEGATIVE TERMINAL AIR OPEN / AIR FAILURE CLOSE AIR CLOSE / AIR FAILURE OPEN HIGH PRESSURE LOW PRESSURE GROUND

FIGURE 8.

ILD ABBREVIATIONS

Electrical Signal Lines. Figure 9 shows ILD Electrical Signal Lines.

RED WHITE BLACK GREY

WIRE COLORS

SHIELDED CABLE THIS SYMBOL INDICATES A SHIELD

FIGURE 9. ILD ELECTRICAL SIGNAL LINES

The wires are color coded to show which wires must be connected to terminal posts. Instrument cables that carry low voltage signals are shielded to prevent outside electrical energy from interfering with the signals.

Saudi Aramco DeskTop Standards

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

ILD Symbols and Abbreviations(Cont'd) Box and Cable numbering. Figure 10 shows box and cable numbering. The Junction Box (JB)

or Terminal Box (TB) number is located at the top of the box symbol shown in Figure 10. Connections, called terminal posts, inside the block are numbered.

JB OR TB NUMBER

TERMINAL NUMBERS SHOWN HERE TERMINAL BOX WITH TERMINALS

CONDUIT OR CABLE NUMBER

CONDUIT OR CABLE NUMBER SHOWN HERE

FIGURE 10.

BOX AND CABLE NUMBERING

The conduit or cable number will be written in the block near the electrical line symbol. Cables are always identified in pairs, or groups of pairs, of wire.

Saudi Aramco DeskTop Standards

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

ILD Symbols and Abbreviations(Cont'd) Local Indicators. Figure 11 shows the symbols for Local Indicators. Range means the range of

the indicator scale. The letters B and E in the Foxboro local indicator symbol give the polarity of the input signal (+ve or -ve). (Foxboro is the name of one of the manufacturers of instruments used by Saudi Aramco. Another manufacturer is named Honeywell.)

LOCAL INDICATOR

MARK NO. RANGE

E _

FOXBORO LOCAL INDICATOR CONNECTIONS

FIGURE 11.

LOCAL INDICATORS

Saudi Aramco DeskTop Standards

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

ILD Symbols and Abbreviations(Cont'd) Temperature Sensing Elements.

Figure 12 shows the symbols for Temperature Sensing

Elements. The Range is usually from zero to the maximum process temperature the Resistance Temperature Element (RTE) will measure in its loop, for example, 0 to 250F. Type on the thermocouple symbol identifies the metals in the thermocouple, for example, IRON/CON would mean iron and constantan.

EQUIPMENT NUMBER

RESISTANCE TEMPERATURE ELEMENT


MARK NO. RANGE

EQUIPMENT OR LINE NUMBER

THERMOCOUPLE TEMPERATURE ELEMENT


MARK NO. TYPE

FIGURE 12.

TEMPERATURE SENSING ELEMENTS

Transducer. Figure 13 shows the symbol used for a transducer. The figure shows that the transducer is changing an electrical input signal to a pneumatic output signal. Other symbols may show the transducer changing a pneumatic input to an electrical output.

+ _
TRANSDUCER

MARK NO.

FIGURE 13.

TRANSDUCER

Saudi Aramco DeskTop Standards

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

ILD Symbols and Abbreviations(Cont'd)

Figure 14 shows the ILD symbols for Level Transmitters. All four symbols are very similar and all show the vessel in which the level is being controlled. Note the symbol for an accumulator, which is shown with the dry leg transmitters. The accumulator is used to remove liquid from the dry leg.
Level Transmitters.

DRY LEG VESSEL NO. L H N


MARK NO. RANGE SUPPRESSION ELEVATION

OUT

S LEVEL TRANSMITTER WITH AIR SUPPLY CONNECTION ( D / P CELL ) WET LEG VESSEL NO. H L

+ _

RED GREY

MARK NO. RANGE SUPPRESSION ELEVATION

LEVEL TRANSMITTER ( D / P CELL ) DRY LEG VESSEL NO. L H

+ _

RED GREY

MARK NO. RANGE SUPPRESSION ELEVATION

WET LEG VESSEL NO. H L


MARK NO. RANGE SUPPRESSION ELEVATION

OUT

S LEVEL TRANSMITTER WITH AIR SUPPLY CONNECTION ( D / P CELL )

FIGURE 14. LEVEL TRANSMITTERS WITH D / P CELLS

Saudi Aramco DeskTop Standards

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

All four transmitter types use differential pressure to measure level. Types 1 and 3 are the same except that 1 is pneumatic and 3 is electronic. Both use dry legs. Types 2 and 4 are the same except that 2 is electrical and 4 is pneumatic. Both use wet legs. Pressure measurement is sometimes expressed as the height of a column of water. This is because a column of water one foot high produces a known pressure of 0.433 psi. Alternatively, a column of water 27.7 inches high produces a pressure of 1.0 psi. We can use this information to convert liquid pressure measurements into liquid level measurements. DP transmitters can be fitted with a biasing spring kit. The spring can be used to adjust or balance out certain differential pressure readings in order to give us the actual readings we require. When the bias acts to oppose pressure on the high side, it is called suppression. When it acts to assist pressure on the high side, it is called elevation. An example is shown below.

100 '' WC

15 psig

SEAL LEG

HIGH SIDE

LOW SIDE

P1
BIAS

P2

3 psig

0 '' WC

HL P1 P2

The pressure of liquid in the seal (or wet) leg is not needed for determining the liquid level in the tank. Therefore, bias can be applied to balance out this pressure. Because bias in this case is assisting pressure on the high side, we have elevation.

Saudi Aramco DeskTop Standards

10

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

ILD Symbols and Abbreviations(Cont'd) Level Transmitters (Cont'd). Figure 15 shows how a differential pressure transmitter is used to

measure level in a vessel open to the atmosphere. Atmospheric pressure acts on the top of the water and also on the low pressure side of the DP cell. Therefore, the difference in pressure between the high and low sides of the cell is equal only to the pressure exerted by the water level. Example: If the DP cell senses a pressure differential of 10 psi it means that the level of water is 10 x 27.7 inches.

OPEN TANK LEVEL MEASUREMENT

AIR PRESSURE

HEIGHT

WATER

LOW PRESSURE SIDE VENTED TO ATMOSPHERE

H L

FIGURE 15.

LEVEL MEASUREMENT USING A DP CELL

Saudi Aramco DeskTop Standards

11

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

ILD Symbols and Abbreviations(Cont'd) Level Transmitters (Cont'd). Figure 16 shows how a DP transmitter measures level in a closed

vessel.

200 ''

TANK PRESSURE

200 '' DRY LEG

100 ''

WATER

H L

DP CELL

FIGURE 16.

LEVEL MEASUREMENT USING DP CELL

In order to obtain a differential pressure that depends only on the liquid level, the pressure of the tank atmosphere must be cancelled out. This is done by connecting the low side of the DP cell to the top of the tank. This connection is called a dry leg.

Saudi Aramco DeskTop Standards

12

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

ILD Symbols and Abbreviations(Cont'd) Level Transmitters (Cont'd). Figure 17 shows why wet legs are sometimes used.

AIR

200 ''

200 '' WET LEG

100 ''

WATER

H L

DP CELL

FIGURE 17.

LEVEL MEASUREMENT USING DP CELL

The atmosphere in a tank may carry vapor from the liquid. If a dry leg DP cell is being used, some of the vapor will condense in the leg. After a time, liquid at varying levels could collect in the leg. This would cause differential pressure readings that do not represent only the height of liquid in the vessel.

Saudi Aramco DeskTop Standards

13

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

ILD Symbols and Abbreviations(Cont'd)

To overcome this problem the wet legs are made to a known height, then filled with liquid. Because the liquid level in the leg is constant, the pressure it exerts on the low side of the DP cell is constant. This pressure can be taken into account when reading differential pressure. Figure 17 shows that it is possible for the low side pressure to be greater than the high side pressure. DP cells are always connected with their high side to the vessel.
Temperature Transmitters. Figure 18 shows the symbols for Temperature Transmitters. Range

gives the temperature range of the transmitter, for example 0 to 250F.

EQUIPMENT OR LINE NUMBER

RED

+ _
GREY TEMPERATURE TRANSMITTER. THERMOCOUPLE WITH INTEGRAL ELECTRONIC mV / mA CONVERTER

MARK NO. RANGE

EQUIPMENT OR LINE NUMBER

RED

+ _
GREY TEMPERATURE TRANSMITTER. RESISTANCE TEMPERATURE DETECTOR WITH RTD / mA CONVERTER

MARK NO. RANGE

FIGURE 18.

TEMPERATURE TRANSMITTERS

Saudi Aramco DeskTop Standards

14

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

ILD Symbols and Abbreviations(Cont'd) Pressure and Flow Transmitters. Figure 19 shows two kinds of transmitters, one for pressure and

one for flow. The difference is in the connection to the process. Pressure measurement requires only one connection. Flow measurement requires two connections; one for the high pressure side of the orifice plate, and one for the low side.

EQUIPMENT OR LINE NUMBER

+ _

RED GREY

PRESSURE TRANSMITTER

MARK NO. RANGE

OUT IN
MARK NO. RANGE

FLOW TRANSMITTER WITH AIR SUPPLY CONNECTION

FIGURE 19

Note that the flow transmitter has two input lines (on the left). This is because the flow transmitter is using differential pressure. Range will show the calibrated range of each transmitter. Examples would be: 0 - 100 psi (for pressure transmitter) 0 - 100" W.C. (inches water column) - [for flow transmitter]

Saudi Aramco DeskTop Standards

15

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

ILD Symbols and Abbreviations(Cont'd) Controller. Figure 20 shows the ILD symbol for a controller.

IN OUT S CONTROLLER
MARK NO. SET POINT P. BAND RESET DERIVATIVE ACTION

FIGURE 20. ILD CONTROLLER SYMBOL

The meaning of the terms shown on the controller are explained below. Mark No. identifies the process variable or loop number which is being controlled. Set Point is the process variable value to which the controller has been set. It is the value needed for efficient and safe operation. The set point setting can be altered by the operator when necessary. P Band means proportional band. This is a setting which determines the amount the variable measurement must change from the set point for the control valve to move through 100% of its travel. For example, suppose the total travel of a control valve is 6" (that is from fully closed to fully open is a travel of 6"). If a total deviation of the process variable from set point is also 6" (that is 3" below set point to 3" above set point) then the P Band is 100% (because a 6" movement of the variable causes a 6" movement of the valve). Note that the controller has a constant pressure air supply. The output of this supply depends on the input being received from the transmitter (which signal depends on the process variable measurement).

Saudi Aramco DeskTop Standards

16

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

ILD Symbols and Abbreviations(Cont'd) Level Control. Figure 21 shows a level control system. The valve is fully closed when the

level is 3" above its set point. It is fully open when the level is 3" below its set point. Therefore, the level must travel through its full range in order to move the valve through 100% of its travel (6"). Therefore, P (Proportional) Band is 100%.

1.5 FEET

1.5 FOOT

6 '' VALVE MOVEMENT

200 % 100 % 50 % PB PB PB

6 '' FLOAT MOVEMENT

VALVE A

SPAN SET POINT ZERO

3 '' 3 ''

VALVE B

FIGURE 21. LEVEL CONTROL SYSTEM

Saudi Aramco DeskTop Standards

17

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

ILD Symbols and Abbreviations(Cont'd)

Figure 22 shows the arrangement for a P Band of 50%. A total deviation from the set point of 3" causes a 6" movement of the control valve. The P Band is, therefore, 50%.
Level Control (Cont'd).

2 FEET

1 FOOT

6 '' VALVE MOVEMENT

200 % 100 % 50 % PB PB PB

3 '' FLOAT MOVEMENT

VALVE A

1.5 '' SET POINT 1.5 ''

VALVE B

FIGURE 22

Saudi Aramco DeskTop Standards

18

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

ILD Symbols and Abbreviations(Cont'd) Level Control (Cont'd). Figure 23 shows the arrangement for a P Band of 200%. A total set

point deviation of 12" causes a 6" movement of the control valve.

1 FOOT

2 FEET

6 '' VALVE MOVEMENT

200 % 100 % 50 % PB PB PB

12 '' FLOAT MOVEMENT

VALVE A SPAN 6 '' SET POINT 6 '' SPAN

VALVE B

FIGURE 23.

PIVOT TO THE LEFT

Saudi Aramco DeskTop Standards

19

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

ILD Symbols and Abbreviations(Cont'd) Level Control (Cont'd). Reset may have a time value next to it. Reset is used with proportional

control to return a variable back to its set point. (Reset is also sometimes called Gain.) For example, Figure 24 shows a stable process. The level is at set point and 50 gpm is entering and leaving the tank.

WATER IN

50 GPM MAXIMUM LEVEL SET POINT MINIMUM LEVEL WATER OUT

50 GPM

FIGURE 24. STABLE PROCESS

Saudi Aramco DeskTop Standards

20

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

ILD Symbols and Abbreviations(Cont'd) Level Control (Cont'd). If for some reason the flow leaving the tank increases to 60 gpm the

level will fall. The float will then cause the control valve to open and input flow will increase. However, the valve cannot adjust until after the level has deviated from set point. Hence, a new stable condition may exist which is not at set point, as shown in Figure 25. The difference between the new level and the set point is called offset.

WATER IN

60 GPM OFFSET SET POINT

WATER OUT

60 GPM

FIGURE 25. STABLE BUT OFFSET

Saudi Aramco DeskTop Standards

21

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

ILD Symbols and Abbreviations(Cont'd) Level Control (Cont'd). Reset is used to help the proportional control to bring the variable back

to set point. It does this by sending an extra signal to the control valve. The signal adjusts the control valve until set point is reached. Then the reset signal stops. The reset mechanism is part of the controller. It has a scale on which different times can be set, for example from 0.1 to 50 minutes. A setting of 0.5 means that the control valve will be adjusted every 0.5 minutes until set point is reached. Derivative also may have a time value next to it. It is usually used only in Temperature Control Loops. Derivative is sometimes called Rate Action or Integral. Derivative is necessary because proportional plus reset control may take a long time to correct temperature deviations from set point. Derivative action is concerned with how fast a temperature is changing from set point. If temperature is deviating only slowly from set point, the controller will make only small adjustments to the control valve. Derivative action senses the speed of the change immediately the change begins (unlike reset, which responds after the change has occurred and caused offset). If the rate of change is high, derivative immediately causes a large adjustment to be made to the control valve to bring the temperature under control. Derivative action stops when the temperature stops changing. The derivation mechanism is also a part of the controller. It uses the same kind of time scale as the reset unit. Action will have Direct or Reverse next to it. Direct means that if the input signal to an instrument is increased, the output signal from the instrument will also increase. Reverse means that if the input signal increases, the output signal decreases.

Saudi Aramco DeskTop Standards

22

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

ILD Symbols and Abbreviations(Cont'd) Indicating Controller. Figure 26 shows the symbols used for an indicating controller. They are

the same as for a basic controller except that a scale range for the variable will be given. Scales may be linear or square root. Linear scales are used for those process variables which change in direct proportion to changes in instrument output signals, e.g. level, temperature, pressure. Flow measurements, however, are taken from differential pressure readings at an orifice plate. Differential pressure changes in proportion to the square of the flow rate. Therefore, the square root of the differential pressure must be found (or extracted) from a differential pressure signal in order to find the flow rate. This is why some scales are square root.

IN OUT S
MARK NO. SET POINT P. BAND RESET DERIVATIVE ACTION SCALE RANGE

INDICATING CONTROLLER

IN OUT SET S

( IND. CONTROL ) ( MANUAL CONTROL UNIT )


MARK NO. SET POINT P. BAND RESET DERIVATIVE ACTION SCALE RANGE

INDICATING CONTROLLER WITH MANUAL CONTROL UNIT

FIGURE 26. INDICATING CONTROLLERS

Saudi Aramco DeskTop Standards

23

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

ILD Symbols and Abbreviations(Cont'd) Panel-Mounted Indicator. Figure 27 shows the symbol for a panel-mounted indicator. Range

gives the range for the indicator scale.

IN INDICATOR ( 1 TO 3 POINTERS )
MARK NO. RANGE

FIGURE 27. PANEL MOUNTED INDICATOR

Strip Chart Recorder. Figure 28 shows the symbol for a strip chart recorder. Mark numbers and Range are given for each pen.

If more than one instrument loop is being recorded, additional input line symbols are added for each loop. Notes may be given to explain more about the symbols. GND, L1 and L2 mean Ground, Line 1 and Line 2, respectively.

IN GND L1 L2
MARK RANGE MARK RANGE MARK RANGE
1 ST. PEN 1 ST. PEN 2 Dn. PEN 2 Dn. PEN 3 Dr. PEN 3 Dr. PEN

RECORDER ( 1 TO 3 PENS )

FIGURE 28

Saudi Aramco DeskTop Standards

24

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

ILD Symbols and Abbreviations(Cont'd) Two-Purpose Instrument Devices. Figure 29 shows the ILD symbols for two components of a

loop combined into one. The top output signal goes to a level transmitter or controller. The bottom output signal goes to a final control element, such as a control valve.

VESSEL NO. S

IN

OUT OUT LEVEL TRANSMITTER / CONTROLLER WITH AIR SUPPLY CONNECTION ( DISPLACER )

TRANSMITTER
MARK NO. RANGE

CONTROLLER AND
MARK NO. SET POINT P BAND RESET

FIGURE 29. TWO - PURPOSE INTRUMENT DEVICES

Saudi Aramco DeskTop Standards

25

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

ILD Symbols and Abbreviations(Cont'd) Level Transmitter/Controller. Figure 30 shows the symbols used to denote a transmitter or a

controller. In each case, the appropriate information blocks would be filled in and the other blocks left blank.

EQUIPMENT OR LINE NUMBER

OUT IN S

PRESSURE TRANSMITTER OR CONTROLLER WITH AIR SUPPLY CONNECTION

TRANSMITTER
MARK NO. RANGE

OR

MARK NO. RANGE SET POINT P BAND RESET DERIVATIVE ACTION

EQUIPMENT OR LINE NUMBER

OUT IN S

TEMPERATURE TRANSMITTER OR CONTROLLER WITH AIR SUPPLY CONNECTION

TRANSMITTER
MARK NO. RANGE

OR

MARK NO. RANGE SET POINT P BAND RESET DERIVATIVE ACTION

FIGURE 30. LEVEL TRANSMITTER / CONTROLLER

Saudi Aramco DeskTop Standards

26

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

ILD Symbols and Abbreviations(Cont'd) Three-Way Solenoid Valve. Figure 31 gives the symbol for a three-way solenoid valve. This

symbol is usually connected to the symbol for the final control element. Most solenoid valves are not very large. They are commonly used to shut off instrument air supply to control valves.

P E

SOLENOID OPERATED THREE - WAY VALVE ENERGIZED P-A DEENERGIZED A - E

MARK NO.

FIGURE 31.

Saudi Aramco DeskTop Standards

27

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

ILD Symbols and Abbreviations(Cont'd) Three-Way Valve Operation. Figure 32 shows the normal operation of a three-way valve. When

the coil is energized, air flows to the control valve actuator without interruption. When the solenoid coil is de-energized (which is what happens when the Emergency Shut Down (ESD) button is pressed) the three-way valve closes. This blocks the flow of air to the control valve. At the same time, the 3-way valve allows the air which is operating the control valve to vent to the atmosphere. This causes the control valve to close.

AIR SUPPLY

TO ACTUATOR

AIR SUPPLY

FROM ACTUATOR

P E ENERGIZED
P - PRESSURE

A E DEENERGIZED

A - ACTUATOR

E - EXHAUST

FIGURE 32

Saudi Aramco DeskTop Standards

28

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

INTERPRETING ILDS Handout No. 2 (Drawing 461-J-NA-942815) is a simplified ILD. The Title Block, shown in Figure 33 below, identifies the loop that is on the drawing.

It is Flow Control Loop 101 (FC-101). The block says that FC-101 is part of a crude oil pipeline at Berri-3 Plant, Ras Tanura, The Plant Number is 461. The index letter, J, is the standard index letter for Instrument Loop Diagrams. The Reference Drawing Block gives the drawing numbers of P&IDs and Instrument Installation Schedules on which FC-101 can be found. Reference is also made to the drawing numbers of Rack Power Distribution (Rack Pwr Dist.) and ILD PC-301.

Saudi Aramco DeskTop Standards

29

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

INTERPRETING ILDS (Cont'd) Handout No. 2 shows that the ILD is divided into four parts: FIELD, FIELD JUNCTION BOX, CONTROL ROOM PANEL REAR and CONTROL ROOM PANEL FRONT. (Large junction boxes are sometimes called Marshalling Boxes.) When reading an ILD, it is usual to start at the sensing element. In Handout No. 2, this is an orifice plate, as shown in Figure 34. Note: The Figures given inside the circles are for this module reference only. They do not appear on an actual ILD.

FIELD
8 E-9007 7

4 MARK NO. FT - 101 RANGE 0-100''WC 2 H L 10'' - P - 145 - 1A1 3 1 MARK NO. BORE FE - 101 6''

ILD SENSOR AND TRANSMITTER FIGURE 34

Saudi Aramco DeskTop Standards

JOB ORDER NO.

61845

INDEX

PLANT NO.

461

DRAWING NO.

NA - 942815

SHT

REV. NO.

4-20 m ADC 9

30

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

INTERPRETING ILDS (Cont'd)

At

1 2 3 4 5 6 7 8 9

The mark number (which is the same as a tag or identification number) of the flow element is 101 (that is, FE-101). The BORE of the flow element is 6" (that is, the hole through the orifice plate is 6" diameter). H and L show on which side of the orifice plate high and low pressures are sensed. The pipeline is 10" pipe and the pipeline number is 10"-P-145-1A1. The Mark Number for the Flow Transmitter is 101 (that is, FT-101). The pressure measuring range of the transmitter is 0-100" water column (WC). Auxiliary process lines take high and low pressure to the flow transmitter. This is an electrically operated flow transmitter, as shown by the electric signal lines . The electrical signal lines are shielded all the way from the transmitter to the next loop component. E-3007 is the identification number of the electrical signal line cable. Electronic loops use standard instrument signals of either 4 to 20 mA or 10 to 50 mA, direct current. The drawing shows that 4-20 mA DC is being used.

Saudi Aramco DeskTop Standards

31

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

INTERPRETING ILDS (Cont'd) Figure 35 shows the JUNCTION BOX and CONTROL ROOM PANEL REAR instrument signal wire line connections.

(1)

Shows JUNCTION BOX-200 (J.B. 200). The left side cables come from the flow transmitter and enter Terminals 1 and 2. Terminal 3 is used to ground the shielding on the signal line. C-8101 identifies the signal line cable coming from JB 200. J. B. 320 is located behind the control room panel, that is, panel rear. CC-517 identifies the wire cable from JB 320 that goes to Flow Recorder (FR-101) on the Control Room front panel. The wire line symbol shows a connection between Terminals 12 and 13. This is done in order to complete a circuit.

(2) (3) (4) (5)

Saudi Aramco DeskTop Standards

32

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

INTERPRETING ILDS (Cont'd) Figure 36 gives information about control panel instruments.

Saudi Aramco DeskTop Standards

33

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

INTERPRETING ILDS (Cont'd) (1) (2) (3) These are the incoming signals from JB 320. This is the ILD symbol for a three-pen recorder. Mark No. 1st Pen is for flow recorder FR-101. 0-10 identifies the part of the strip chart which is recording the flow in loop 101. The square root sign () shows that a square root scale is being used. The 2nd Pen is recording the pressure in control loop PC-301. The range 0-100 refers to the part of the strip chart that is recording pressure. The note symbol, 2 , refers to the reference drawing in the Legend block. These are incoming signals from JB 320 to flow indicating controller, FIC-101. This is the basic ILD symbol for an indicating controller. These are the outgoing symbols from FIC-101. CC-518 identifies the cable between the FIC-101 and JB 320.

(4)

(5) (6) (7) (8)

Saudi Aramco DeskTop Standards

34

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

INTERPRETING ILDS (Cont'd) Figure 37 below shows again the wiring terminations In the junction box and rear panels. (Reference should be made to the ILD as a whole.)

(1)

The outgoing signals from FIC-101 go to the same JB 320 as do the incoming signals to FIC-101. Different terminals in JB 320 are used for the incoming and outgoing signal wires. C-8101 is the same cable that has the incoming signal lines. This is JB 200. It has the signal lines from the flow transmitter, FT-101. It also has the outgoing signals wired to terminals 5 and 6. E-1115 identifies the signal cable wires from JB 200 to the field instruments.

(2) (3) (4)

Saudi Aramco DeskTop Standards

35

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

INTERPRETING ILDS (Cont'd) Figure 38 below shows the field-mounted instruments which complete the control loop.

MARK NO.

FTd - 101

1 3 2
S

4
S

10''- P - 145 - 1A1

MARK NO. SIZE RATING A. F. ACTION

FCV - 101 10'' GLOBE CLOSE

FIGURE 38.

ILD TRANSDUCER AND CONTROL VALVE

(1) (2) (3) (4) (5) (6)

These are the signal lines from JB 200. This is the symbol for a transducer. Mark No. identifies it as Ftd-101. The transducer changes the incoming electrical signal to an outgoing pneumatic signal. This is the basic ILD symbol for a control valve. The information block shows that the control valve is Flow Control Valve FCV-101. It is a 10" globe valve. A.F. Action Close means it will close if there is an air failure. This is the pipeline number. It is 10" pipe, line number S-145.

Saudi Aramco DeskTop Standards

36

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

INTERPRET AN ILD FOR A PNEUMATIC INSTRUMENT CONTROL LOOP Figure 39 shows a simplified section of a P&ID. Control Loop number 113 is controlling the level of tempered water in the surge drum 139-D-211.

Saudi Aramco DeskTop Standards

37

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

INTERPRET AN ILD FOR A PNEUMATIC INSTRUMENT CONTROL LOOP (Cont'd) The level in the drum is sensed by the level transmitter, LT-113. The transmitter sends pneumatic signals to a level indicating controller, LIC-113, and to two level switches LS113A and LS-113B. In turn, LIC-113 sends pneumatic signals to a level control valve, LCV-113. If the level in the drum goes low, the signals cause the control valve to open. This allows more make-up water to flow into the drum. If the level goes high, the signals cause the valve to close. This reduces the make-up water flow rate. The level switches are connected to high and low alarms (XA-3-32 and XA-3-33). The switches are set to operate if the drum level goes dangerously high or dangerously low. They are operated by the pneumatic signals coming from the level transmitter. The 3 refers to the row number on the control panel. The 32 and 33 respectively refer to the column numbers. They give the locations on the control panel where the alarms can be found. Figure 40 shows how the level control loop would look on an ILD. The ILD is shown in sections in Figure 41 through 44

Saudi Aramco DeskTop Standards

38

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

INTERPRET AN ILD FOR A PNEUMATIC INSTRUMENT CONTROL LOOP (Cont'd)

Saudi Aramco DeskTop Standards

39

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

INTERPRET AN ILD FOR A PNEUMATIC INSTRUMENT CONTROL LOOP (Cont'd) Figure 41 is the ILD symbol for the level indicating controller LIC-113. The range is from 0100. Because it is a level controller, the scale range is a percentage. Levels are usually indicated as a percentage of the vessel capacity. 0 to 100, therefore, is the range from completely empty to completely full. Note the triangle and letter S to indicate air supply.

Saudi Aramco DeskTop Standards

40

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

INTERPRET AN ILD FOR A PNEUMATIC INSTRUMENT CONTROL LOOP (Cont'd) Figure 42 is the symbol for a level transmitter. The symbol P/P means that the differential, pressure (P) sensed by the transmitter is sent to the loop controller as a pressure (P). It will be sent as a pneumatic pressure signal of 3 to 15 psi.

The figure shows that the transmitter senses the differential pressure at equipment number 139-D-211. This is the surge drum shown on the P & ID.

Saudi Aramco DeskTop Standards

41

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

INTERPRET AN ILD FOR A PNEUMATIC INSTRUMENT CONTROL LOOP (Cont'd) Figure 43 shows the level control valve. 3"-SC-160-IAIA identifies the make-up water pipeline. This is the line the level control loop uses to control the level in the surge drum.

Saudi Aramco DeskTop Standards

42

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

INTERPRET AN ILD FOR A PNEUMATIC INSTRUMENT CONTROL LOOP (Cont'd) Figure 44 shows the level switches in the control loop. LS-113A is the high level alarm switch. It is set to open when it receives a 12-psi signal from the level transmitter. LS-113B is the low-level alarm switch. It will open when it receives a 6-psi signal from the level transmitter.

Figure 40 shows that the switches are connected to alarms XA-3-32 and XA-3-33 on the front panel of the control room. The alarms can be seen on windows 3-32 and 3-33

Saudi Aramco DeskTop Standards

43

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

INTERPRET AN ILD FOR AN ELECTRONIC INSTRUMENT CONTROL LOOP Handout No. 3 (Drawing Number J-415-NB-582636) shows an electronic instrument control loop. Electronic loops are more complicated than pneumatic loops. There are two reasons for this: Loop components are both field mounted and located in the control room. Also, the instruments may be great distances away from each other. They must be connected together by electric wires. The wires may pass through one or more junction boxes. The electric wiring connections between instruments must be done in such a way that complete electric circuits are formed.

Saudi Aramco DeskTop Standards

44

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

INTERPRET AN ILD FOR AN ELECTRONIC INSTRUMENT CONTROL LOOP (Cont'd) The top of Handout No. 3 shows a pressure control loop, shown again below in Figure 45. The symbol for a control valve can be seen. It has Tag No. PCV-51. It is connected to pipeline 4"-5-304-6A1 and has a 20-psig air supply.

Fig 45

Saudi Aramco DeskTop Standards

45

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

INTERPRET AN ILD FOR AN ELECTRONIC INSTRUMENT CONTROL LOOP (Cont'd) Figure 46 shows the symbol for the transducer. You can tell it is a transducer because it has two electrical connections, an air supply and a pneumatic output line. The two electric wires are part of the control loop electric circuit. The current through the transducers varies with changes in process variable values. Air at a constant pressure of 20 psig is supplied to the transducer. The output value of the air pressure varies with changes in the transducer current. Hence, electric signals are converted to pneumatic signals.

The symbol for a transducer is sometimes drawn as a square, but Foxboro, the company which makes the instrument, draw it as a circle. The letters E and B identify the terminal connections inside the transducer junction box. Note again that the transducer needs a 20-psig air supply. The symbols shown in Figure 47 are for locally-mounted air regulators.

Saudi Aramco DeskTop Standards

46

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

INTERPRET AN ILD FOR AN ELECTRONIC INSTRUMENT CONTROL LOOP (Cont'd)

Saudi Aramco DeskTop Standards

47

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

INTERPRET AN ILD FOR AN ELECTRONIC INSTRUMENT CONTROL LOOP (Cont'd) Figure 48 shows the symbols for the field-mounted pressure indicator (PI-51) and the fieldmounted pressure transmitter (PT-51). The transmitter is shown to be connected to a pipeline identified as 4"-S-305-3A1. The circular symbol marked 'IND' shows that the transmitter has an indicator mounted on it.

Saudi Aramco DeskTop Standards

48

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

INTERPRET AN ILD FOR AN ELECTRONIC INSTRUMENT CONTROL LOOP (Cont'd) Figure 49 shows the field junction box. All the instruments of Loop P-51 are wired into this box. The box is identified as ETB3. The number that follows the ETB3 symbol is the terminal number for the wire inside the terminal box. The symbol marked 503 is a shield for the cable coming out of the junction box. It shields the cable from outside electrical interference.

Saudi Aramco DeskTop Standards

49

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

INTERPRET AN ILD FOR AN ELECTRICAL INSTRUMENT CONTROL LOOP (Cont'd) Figure 50 shows that the wiring goes from the junction box, through a marshalling box, and to a panel interconnection junction box in the control room. A marshalling box (MB) is simply a big junction box. It is usually located just inside the control room building. It is a collection point for field wiring that comes into the control room from many parts of the plant. From the marshalling box, the instrument loop wiring is organized and routed to various display areas and panels in the control room. The number of marshalling boxes in a plant depends on the size of the plant. Each box is numbered. Figure 50 shows that on this ILD the marshalling box is MB7. The number that follows each MB7 is the terminal number inside the box. There may be hundreds of wires in each box.

Saudi Aramco DeskTop Standards

50

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

INTERPRET AN ILD FOR AN ELECTRICAL INSTRUMENT CONTROL LOOP SET Figure 51 shows, at the left, numbered blocks between the marshalling block and the panel interconnection junction box. These are the individual wire numbers between the boxes.

The panel interconnection junction box is located behind the control room panel. It is usually close to the loop controller. A short cable connects the controller to the junction box. The cable carries a number of wires each insulated from the others. The wires are color coded.

Saudi Aramco DeskTop Standards

51

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

INTERPRET AN ILD FOR AN ELECTRONIC INSTRUMENT CONTROL LOOP (Cont'd) The panel interconnection junction box symbols are shown in Figure 52.

The colors identify wires inside the connecting cable. Each of the lines below the colors represents one wire inside the cable. The letter indicates the connection point on the cable plug. For example, the violet wire in the cable is connected to point F in the cable plug. You can also see from the figure that the violet wire is connected to the terminal strip at connection number 5. Figure 53 shows the cable plug. The letters BK at the top of the numbers column identify the terminal strip inside the panel interconnection junction block. The ILD shows the identification of other terminal strips, such as BH1, EA1 and so on.

Saudi Aramco DeskTop Standards

52

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

INTERPRET AN ILD FOR AN ELECTRONIC INSTRUMENT CONTROL LOOP (Cont'd) The (+) and (-) signs indicate the polarity of each numbered terminal that is being used.

Saudi Aramco DeskTop Standards

53

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

INTERPRET AN ILD FOR AN ELECTRONIC INSTRUMENT CONTROL LOOP (Cont'd) Figure 54 shows that there is a 100-ohm resistor connected across terminals 3 and 4 in the junction box. Resistors are needed whenever an input signal is too high for other instruments in the control loop.

Saudi Aramco DeskTop Standards

54

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

INTERPRET AN ILD FOR AN ELECTRONIC INSTRUMENT CONTROL LOOP (Cont'd) Figure 55 shows the symbol for the pressure controller. The controller needs a 118V 60Hz power supply. FOP No. F3-10 means that the instrument is located on the Face Of Panel F3, in position 10. On other ILDs the abbreviation BOP (Back of Panel) may sometimes be seen.

Saudi Aramco DeskTop Standards

55

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

INTERPRET AN ILD FOR AN ELECTRONIC INSTRUMENT CONTROL LOOP (Cont'd) Figure 56 shows the recorder and its connections.

Saudi Aramco DeskTop Standards

56

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

TRACING CURRENT FLOW IN CONTROL LOOPS The symbol at the bottom right-hand corner of Figure 56 is for a three-pen recorder. Pen number 2 records pressure values on PR-51. The recorder operates with a 118V, 60Hz supply. In order to record pressure values, the recorder must be connected to the pressure control loop. It must receive signals that indicate the pressure values. A study of the ILD, on Handout No. 3, shows that the power to operate the pressure transmitter, PT-51, is supplied by the pressure controller, PC-51. The controller also operates with a 118V, 60Hz supply. The ILD shows that a multi-wire cable connects the pressure controller output to terminal 1 on terminal strip BK. A wire connects terminal 1 to the positive side of the pressure transmitter, PT-51. The transmitter acts as a variable resistor. Its resistance depends on the value of the process variable. Therefore, the current flowing through the control loop changes as the transmitter resistance changes. And this change is a measure of the process variable. From the transmitter, the current flows through the pressure indicator, PI-51. From there it goes to terminal BK-3. From BK-3 the current flows through a 100- ohm resistor to BK-4. A wire connects BK-4 to BH-6. A wire from the multi-wire cable connects BH-6 to the plug. The ILD shows this connection to be letter H on the plug (a violet colored wire). The current goes to operate PR-51. In order for the current to flow, there must be a complete circuit. Therefore, the current that operates PR-51 must be returned to its source, PC-51. The ILD shows that this is done by connecting a wire from the multi-wire cable (a brown wire) to terminal 7 on terminal strip BH. This wire acts as a return wire. It takes the return current from PR-51 to BH-7. A wire connects BH-7 to terminal 2 on terminal strip BK. A wire from the multi-cable wire is connected to BK-2. The IDL shows this to be connection U on the plug (a grey color wire). The connection completes the circuit.

Saudi Aramco DeskTop Standards

57

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

INTERPRET AN ILD FOR A PNEUMATIC INSTRUMENT CONTROL LOOP (Cont'd) Figure 57 shows the symbol for a panel-mounted alarm. The numbers 1 - 10 identify the location of the alarm in the alarm display panel, i.e., Row 1, Column 10. Tracing the wires from the alarm shows that it is connected to the multi-wire cable plug at terminals 6 and 7 on terminal strip EO. Temperature switch TS-54 is connected by the multiwire cable (connections J and B) to these same terminals. Hence, the current passing through TS-54 can also pass through alarm XA-1-10. If the supply fails, the switch will trip and set off the alarm.

Saudi Aramco DeskTop Standards

58

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

Computer Relays
Computer Relay Symbols

Symbols are used to show Computer Relays on ILDs. Details of other information related to the relays may also be given. This section of the module covers the symbols and related information.
Manufacturer's Symbols. Saudi Aramco uses instrumentation supplied by two manufacturers,

Foxboro and Honeywell. Relays supplied by these companies are drawn differently on ILDs. An example is shown in Figure 58. The symbols are for adder/subtractor cards.

Saudi Aramco DeskTop Standards

59

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

Computer Relays (Cont'd)


Manufacturer's Symbols(Cont'd). Foxboro instruments use the words "adder" or "summer" on

their cards (from "sum" meaning 'add'). Foxboro summer card output terminals are always the number 2 terminals. adder/subtracter card output terminals are always the number 6 terminals. Honeywell

TP (terminal panel) followed by a mark number is used to identify terminals on Honeywell Computer Relays. Handout No. 4 (Drawing No. R84-A-NA-B44995 Sheet 1) is a P&ID for a deethanizer system. Handout No. 5 (Drawing No. R84-J-NB46327 Sheet 1 A) is the ILD for Flow Control Loop F-010 shown on the P&ID.

Saudi Aramco DeskTop Standards

60

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

Computer Relays (Cont'd)


Manufacturer's Symbols(Cont'd).

The ILD on Handout No. 5 shows that Honeywell relay

instruments are being used. The ILD shows that the following instruments are to be found in the field (that is, out in the plant area). Flow Transmitter, FT-010 NOTE: On this ILD the mark Flow Element, FE-010 numbers also include the Plant Flow Indicator, FI-010 number (R84). Flow Transducer, FTd-010 Flow Control Valve, FCV-010

It also shows that the following instruments are found on the front of Control Panel CP-R84101. Flow Recorder, FR-010 Flow Totalizer, FQI-010 Flow Indicating Controller, FIC-010

Note that the flow indicator, FI-010, has a (non-linear) square root scale. This is because the indicator is connected in series with the flow transmitter, FT-010, and the transmitter's differential pressure signals have not yet passed through the square root extractor. The auxiliary rack section shows that there are three Computer Relays being used. These are: FY-010A FY-010B FQ-010 a multiplier/divider card a square root extractor a flow integrator card.

Saudi Aramco DeskTop Standards

61

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

Computer Relays(Cont'd)
Computer Relay Symbols (Cont'd). Note that the function of the relays is shown at the top, as

shown in Figure 59.

The square root sign () indicates a square root extractor. The multiplication sign (X) indicates a multiplier/divider card which is performing multiplication. (If a division sign ( ) were above the relay, the card would be performing a division function.) The integral sign (_) indicates an integrator card.

Saudi Aramco DeskTop Standards

62

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

Computer Relays (Cont'd)


Computer Relay Symbols(Cont'd). Figure 60 shows where the other information about the relays

was obtained from the ILD.

Saudi Aramco DeskTop Standards

63

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

Computer Relays (Cont'd)


Computer Relay Symbols(Cont'd). A study of the ILD (Figure 60) shows the symbol

2
10-TT-016-12

The arrow enters the multiplier card at terminal number 8. 10-TT-016 tells us that a temperature transmitter, TT-016, is sending a signal to the multiplier card. The 12 tells us that a wire from terminal 12 on the transmitter is connected to terminal 8 on the multiplier. The number 2 in the box refers us to the Reference Drawings given on the right-hand side of the ILD. 2 refers to ILD NB-B46327, sheet 35. This kind of information is characteristic of ILDs. They show where an input signal comes from and, if necessary, will make reference to another ILD to show the destination of the signal. Block number 7, just above TPAI-1, shows that the output from terminal 3 goes to 10TY010B. The reference drawing section refers to ILD NB-B46327 sheet 29. Sheet 29 is shown in Handout No. 6. (Drawing No. R84-J-B46327 Sheet 29.) It shows that a TYPE E thermocouple is used to sense the temperature in line 16"-P-1002-3A1. It also shows that a 3", globe type temperature control valve is fitted into line 3"-SC-1001-3A1C. The symbols shown at the center of the auxiliary rack section of the ILD are for a computer system. They are shown in Figure 61.

Saudi Aramco DeskTop Standards

64

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

Computer Relays (Cont'd)

Saudi Aramco DeskTop Standards

65

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

Computer Relays (Cont'd)


Computer Relay Symbols(Cont'd)

Note that the symbol MV/I represents the temperature transmitter TT-10. MV/I means it is converting millivolts to current. Two input signals are shown entering the transmitter. One is from TE-010; the other is from TE-015. Block 3 says that TE-015 is found on Sheet 34. 17/C cable, in the Rack Section, means 17 conductor cable. It is a cable containing 17 conductor wires. The cables are connected to the control instruments. The ILD shows that lines 7 and 10 out of TPA-2-2 can be traced to the computing relays TY010A and TY-010B respectively. TY-010A is the signal selector. The symbol above the card (<) is the mathematical symbol for less than. In this case, the symbol means that the card is a low signal selector. If the symbol was >, which means greater than, the card would be operating as a high signal selector. TY-010B is the adder/subtractor card. The Greek letter, capital sigma (_) above the card means the sum of. It shows that the card is operating as an adder or subtractor, depending on how the card is set. If a plus sign (+) is over the card, it means that the card is only adding. The Greek capital letter delta () or a minus sign (-) is used to indicate a subtractor card. Note that the input signal to terminal 5 on the adder/subtractor card comes from TPA1-1-3. This shows again how ILDs are used to trace electric circuits from one drawing to another. Other connections are shown going to sockets and pins for the computer control of the temperature.

Saudi Aramco DeskTop Standards

66

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

Instrument Systems Saudi Aramco uses two control systems that are manufactured as complete units. The systems are shown on ILDs. One of the systems is the Foxboro Spec 200 and the other is the Honeywell Vutronic.
Foxboro Spec 200

'Spec' is an abbreviation for Simplified Package for Electronic Control. arrangement of the Spec 200 is shown in Figure 62.

The basic

PROCESS

TRANSMITTER

I
ALARMS 4 - 20 mA

4 - 20 mA 10 - 50 mA RTD THERMOCOUPLE mV VOLTAGE

INPUT BUFFER AND SIGNAL CONVERSION

CONTROL 0 - 10V FUNCTION 0 - 10V

OUTPUT BUFFER AND SIGNAL 10 - 50 mA CONVERSION

BASIC ARRANGEMENT OF A SPEC 200 LOOP FIGURE 62

Saudi Aramco DeskTop Standards

67

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

Instrument Systems(Cont'd) Foxboro Spec 200 (Cont'd) The system is a closed loop. The block symbol marked I/P (Figure 63) is used to show Spec 200 transducers. These transducers convert current energy (I) to pressure energy (P).

FIGURE 63

Input signals such as 4-20 mA, 10-50 mA, millivolts and ohms can be used by the system. These signals are converted to 0 - 10 Volts DC signals by input signal converters. The 0 - 10 V signals are used by rack and panel mounted instruments, such as controllers, indicators, recorders and alarms. Using small voltage signals makes the system safe to work on. All Spec 200 instruments are connected in parallel. This allows components to be removed from the loop without breaking up the system. It also means that the same voltage is applied to all components. Output signal converters are used to send 4-20 mA and 10-50 mA signals to field instruments. The Spec 200 system consists of two areas: the display area and the nest area, as shown in Figure 64. The display area contains the recorders and indicators, and provides all the information needed by operators. The nest area contains the circuit cards for the control, computing, input and output converters, alarm and conditioning units. Nest units are fitted into sections called racks.

Saudi Aramco DeskTop Standards

68

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

Instrument Systems(Cont'd) Foxboro Spec 200 (Cont'd)

Saudi Aramco DeskTop Standards

69

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

Instrument Systems(Cont'd) Foxboro Spec 200 (Cont'd) Figure 65 shows the operation of the Spec 200.

PROCESS

TRANSMITTER 5 VOLTS ALARMS 5 VOLTS 4 - 20 mA INTPUT BUFFER AND SIGNAL CONVERSION CONTROL 0 - 10V FUNCTION 0 - 10V 0 - 20 mA

OUTPUT BUFFER AND SIGNAL 0 - 50 mA CONVERSION

5 VOLTS

5 VOLTS

INPUT SIGNAL DISTRIBUTION

FIGURE 65

Saudi Aramco DeskTop Standards

70

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

Instrument Systems(Cont'd) Foxboro Spec 200 (Cont'd) Suppose the following: A process control loop is for pressure control; the set point is 15 psi; the transmitter has a range of 0-30 psi; the current range for the transmitter is 4-20 milliamps. From the above it follows that a set point of 15 psi is equal to 50% of the transmitter's range. This gives a signal of 12 mA (i.e. 50% of 4-20 mA range). As long as the process pressure remains steady at 15 psi, the transmitter sends a 12 mA signal. When the 12 mA signal reaches the input buffer and signal converter relay card in the nest unit, it is changed to a voltage signal. Spec 200 operates on 0-10 V. Since 12 mA is exactly half the transmitter range, the voltage signal would also be exactly half its range, that is, 5 V. Therefore, the relay card in the converter sends a 5 V signal to all other components in the control loop. For example, 5 volts will be sent to the recorder and this will be seen as 15 psi on the recorder graph. The transducer operates on a milliamp range. Therefore, the voltage signal must be converted back to an amperage signal before it enters the transducer. This is done by the card in the output buffer and signal converter in the nest unit. The Spec 200 cards are used for specific functions. Some of these functions are described below.

Saudi Aramco DeskTop Standards

71

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

Foxboro Spec 200 (Cont'd) The Function of the 2AI-I2V Current to Voltage Converter Card. The Foxboro current converter

card Model No. 2AI-I2V is a solid state component located in the nest assembly. 2AI-I2V stands for: 2 A I I 2 V A Spec 200 component Analog signals in and out Input instrument Current signals in This is an isolated card Voltage signals out

The 2AI-I2V card has only one function. It receives 4 to 20 mA signals from a field transmitter and changes them to 0 to 10-volt signals. These are the signals needed by the Spec 200 system. The voltage output is proportional to the current input. The card can operate with two inputs and two outputs for dual operation. This means that the card can receive and convert 4-20 mA signals from two transmitters. The input (current signals) sides of the card circuit are isolated electrically from the output sides (voltage signals). The two circuits are not connected by wires, but the input influences the output because it passes through a transformer. This induces a proportional voltage in the output side of the transformer coils. Isolated cards are used because they give more protection to the cards. For example, a short circuit in the transmitter circuit will not damage the card. If the figure 3 were shown in place of the 2, it would mean that the card was not isolated. The Function of the Controller Card 2AX+45. The Foxboro controller card, 2AX+45, has electronic circuits that receive the input signals and modify them according to the control settings. The card sends an electronic output signal to control a final control element, usually a control valve.

Saudi Aramco DeskTop Standards

72

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

Foxboro Spec 200 (Cont'd)

Alarm cards cause alarms to sound in the plant control room if operating conditions become abnormal.
The Function of 2AP+ALM-AR Alarm Card.

The Foxboro 2AP+ALM-AR is a dual alarm card. That means that it can monitor two different variables at the same time. 2AP+ALM-AR stands for: 2 A P ALM AR Spec 200 component Analog signals in and out Process component module Alarm Dual absolute alarm - relay output

The card can be set to send output signals to two different alarm lights. For example, the 2AP+ALM-AR alarm card could monitor pressure for a low condition and temperature for a high condition. The card can also be set to monitor both high and low conditions for the same process variable. It could do this using only one input signal. The alarm card is a solid state function card that slides into a module in the nest unit. The card has two single alarm circuits with a common power supply. Each alarm has one input, one set point, and one output. Alarm points are calibrated from zero to 100% of scale. The alarm card receives voltage signals from other function cards, such as a square root extractor, or a resistance-to-voltage temperature card. It has two relays built into it, one for each alarm circuit. When the alarm is off, the relays on the alarm card are energized. The relay contacts are normally open (NO) and this gives a no-alarm condition, as shown in Figure 66.

TERMINAL NUMBERS -4 NC COM NO +2 TERMINAL NUMBERS RELAY CONTACTS OPEN FIGURE 66 -2 LAMP OFF

POWER SUPPLY

Saudi Aramco DeskTop Standards

73

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

Foxboro Spec 200 (Cont'd) The Function of 2AP+ALM-AR Alarm Card (Cont'd. So long as the process variable that the alarm card is monitoring stays within its set-point range, the relay will stay energized.

Imagine that the alarm circuit is monitoring a pressure control loop. The alarm is set to come on if the pressure goes too high. At this condition, the voltage signal coming into the alarm card will be at the value for which the alarm card has been set. This will cause the relay to be deenergized. When this happens the NC contacts close, as shown in Figure 67, and the alarm light comes on.

TERMINAL NUMBERS -4 NC COM NO +2 TERMINAL NUMBERS RELAY CONTACTS CLOSED FIGURE 67 -2

POWER SUPPLY

+
LAMP ON

Saudi Aramco DeskTop Standards

74

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

Foxboro Spec 200 (Cont'd) The Function of the 2AO-V2I V/I Card The Foxboro voltage to current (V/I) card is a solid state

component located in the nest assembly. 2AO-V2I stands for: 2 A O V 2 I Spec 200 component Analog signals in and out Output instrument Voltage signals in This is an isolated card Current signals out

The 2AO-V2I card has only one function. It receives input voltage signals from the controller card and converts these 0 to 10 volts to a 4 to 20 mA output signal. This output signal is sent to a field mounted transducer. The current output is proportional to the voltage input.
The Function of the 2AI-P2VR/V Converter Card. The Foxboro 2AI-P2V resistance to voltage

converter card is a solid state component located in the nest assembly. It produces an output voltage signal that is proportional to the temperature of a resistance temperature detector (RTD). 2AI-P2V stands for: 2 A I P 2 V Spec 200 component Analog signals in and out Input Platinum resistance bulb An isolated card Voltage output

The converter card has two inputs and two outputs for dual operation with a common power supply.

Saudi Aramco DeskTop Standards

75

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

Foxboro Spec 200 (Cont'd)

A resistance temperature detector (RTD) is used to monitor the temperature of a process. The resistance measured by the RTD is sent into the converter card. The card changes the measured resistance from ohms into volts. The card is calibrated so that the low end of the temperature range corresponds to zero volts. The high end of the temperature range is calibrated to correspond to 10 volts.
The Function of the 2AI-P2VR/V Converter Card (Cont'd).

Output signals from the converter card can go to a loop controller, a temperature indicator, a temperature recorder, and to an alarm card. NOTE: Some cards may be identified as 2AI-N2V, where the N stands for nickel. RTDs operate on the principle that some metals increase their electrical resistance when heated. Other abbreviations often seen on Spec 200 cards are: I/P for input O/P for output DS for Distribution P/I means differential pressure (P) input, current (I) output.

Saudi Aramco DeskTop Standards

76

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

Foxboro Spec 200 (Cont'd) Nest Unit Card Symbols. Symbols used on Saudi Aramco ILDs for Nest Unit cards on the Spec

200 are as shown in Figure 68. Handout No. 7 (Drawing No. 490-J-674433) Shows an ILD with Spec 200 control.

28 29 30

+2 -2

+4 A: (PY - 101A) B: PY - 102A -4 C: D: ANALOG INPUT E: 4 - 5 - 3 F: 2AI - 13V

+1

A: (PY - 101A) B: PY - 102A -1 C: D: REC. DIST. E: 4 - 2 - / F: 2AX + DSI

NEST UNIT CARD SYMBOLS FIGURE 68

Note the word analog on some of the card symbols. This means that the card is operating with numbers that are represented by directly measurable quantities, such as voltage, amperage. That is, the numbers are analogous to physical quantities. Compare this with digital which means that operation is made with numbers and is represented by numbers. Note also the letters A, B, C, D, E and F. These will be given as a legend on ILDs for Spec 200. They identify each function of the card in the rack area. See Figure 69. A, B and C tell us the Tag Numbers of the respective loops. 'D' tells us the function of the card. For example in Figure 68 one card is an analog input card and the other is a recorder distribution card. 'E' tells us the location of the card. For example, 4-5-3 means that the card is in rack 4, nest 5 and is card 3. 'F' tells us how to identify the card in a nest unit. For example, 2AI-13V will be printed on the card near the bottom. LEGEND
A B C D E F : : : : : : TAG NO. LOOP A TAG NO. LOOP B TAG NO. LOOP C FUNCTION LOCATION REF. MODEL NO. FIGURE 69. LEGEND

Saudi Aramco DeskTop Standards

77

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

Interpreting Foxboro Spec 200 ILD's(Cont'd)

Handout No. 8 (Drawing No. 490-J-NB-67483) shows a Spec 200 loop ILD. It is for a level control loop L-360 at Ras Tanura Refinery. Figure 70 shows part of the ILD. The variable being measured is the level in vessel 4900 - 14. The ILD shows (inside the vessel) the high level alarm (HLA) is 3 feet and the low level alarm (LLA) is 1 foot 8 inches. The level transmitter (LT-360) senses the level in the vessel. The ILD shows that the transmitter output is a pneumatic signal. The signal will vary between 3 and 15 psi. The level measurement is indicated on a locally mounted indicator, LI-360. The same pneumatic signal that indicates the level value is sent to a transducer, LTd-360A, Model E11GM. The ILD shows that LTd - 360A converts the pressure signals to Milliamp signals (i.e., 3 - 15 psi pneumatic signals are converted to 4 - 20mA signals).

LINE NO. 4" - C - 46 - 3AI

FIELD JUNCTION BOX FIELD TAG MODEL RANGE LT - 360 2500T-2495 60 " ETB #6 23 24

MARSHALLING BOX MTC #2

RACK AREA

490D-14 HLA

FISHER LEVEL TRANSMITTER

P/I + -

RED GREY

368 369

8 -12+ 8 -12-

+1 A : LY - 358 -1 B : LY - 360A 0 C: +2 D : ANALOG INPUT -2 E : 8 - B6 0 F : 2AI - 13V

+3 -3 +4 -4

1' - 8"

3' - 0"

LLA

TAG 67 FR MODEL

LTd. - 360 A EIIGM

CAL.RANGE 3 - 15#

DATA LOGGING CONNECTOR 8

S 23
LOCATED NEAR LCV - 360 IND. TAG MODEL LI - 360
ASHCROFT 1279A

24
LDL - 360

CAL.RANGE 0 - 1000

FIGURE 70.

INPUT CIRCUIT

Saudi Aramco DeskTop Standards

78

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

Interpreting Foxboro Spec 200 ILD's(Cont'd)

Tracing the two output wires from LTd - 360A shows that they are connected to terminals +2 and -2 on card 2AI - I3V. This card has two inputs and two outputs. The card model number indicates that the card is not isolated electrically. The 4-20 mA input at terminals 2 is found as an output at terminals +4 and -4 of the card. Figure 71 shows that one pair of wires goes to a data logging connector (Level Data Logging (LDL-360). This is for a computer connection. The computer receives and records the level signal, but it does not control anything in the loop. Another pair of wires goes to terminals +1 and -1 on the alarm card 2AP - ALM - A. The terminals are jumped to terminals +3 and -3. This gives a single input to both alarm circuits (+3B is LS-360 (H); -3 is LS-360 (L) .) One alarm circuit responds to a high level. The other responds to a low level. As long as the process level remains between the high and low set points, no alarm will be given.

FIELD JUNCTION BOX


ETB #6 23 24

MARSHALLING BOX MTC #2

RACK AREA NO. 8

368 369

8 -12+ 8 -12-

+1 -1 0 +2 0

A : LY - 358 B : LY - 360A C: D : ANALOG INPUT F : 2AI - 13V

+3 -3 +4 -4

-2 E : 8 - B6

DATA LOGGING CONNECTOR 8 23 24 LDL - 360 +1 A : LS - 360 +2 C : -2 D : ALARM E : 8 - E9 -1 1 TO FY - 360A NB - 674434 F : 2AP - ALM - A (H) +3 -3 +4 -4 +5 -5

-1 B : LS - 360A ( L )

+1

FIGURE 71. 2AI - I3V OUTPUT

Saudi Aramco DeskTop Standards

79

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

Interpreting Foxboro Spec 200 ILD's(Cont'd)

Figure 72 shows the outputs. It can be seen on the symbols that terminal 9 refers to the high (H) alarm, and terminal 10 to the low (L) alarm.

+1 -1 +2 -2 +1 -1

A: 9: X A -2 -3 (H) +3 B: 10: X A -2 -4 (L) -3 +4 C: D: ALARM -4 +5 E: 8 - E9 -5 F: 2AP - ALM -A

TO FY-360 A NB - 674434

+1 A: 9: X A -2 -3 (H) -1 B: 10: X A -2 -4 (L) +2 C: -2 D: ALARM DIST. +3 -3 +4 -4 +5 -5 E: 8 - F10 F: 2AX + DSI

+7 -7 +8 -8 +9 -9 +10 -10 +11 -11 +12 -12

TO ALARM RACK 15

+6 -6

FIGURE 72.

ALARM CIRCUIT

Terminals +2 and -2 are for output 1. The wires from terminal 2 can be traced to the alarm distribution card 2AX +DSI, terminals +9 and -9. This is the high level signal input.

Saudi Aramco DeskTop Standards

80

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

Interpreting Foxboro Spec 200 ILD's(Cont'd)

Terminals +5 and -5 on 2AP - ALM - A are wired to terminals +10 and -10 on 2AX + DSI. These are the low-level input terminals. If there is a high or low alarm, the distribution card will send a signal to Alarm Rack 15, through a standard 2AK cable. The ILD shows that the annunciator XA - 2 - 3 illuminates for a high-level alarm. Annunciator XA - 2 - 4 lights up for a low-level alarm. Figure 73 shows the 2AP - ALM - A card. It shows that input terminals +3 and -3 have two additional pairs of wires connected to it.

+1 +2 -2

A : LS - 360 C: D : ALARM E : 8 - E9

(H)

+3 -3 +4 -4 +5 -5

-1 B : LS - 360A ( L )

F : 2AP - ALM - A TO FY - 360A NB - 674434 -1 +1

TAG MODEL LOCATION SET PIONT P. BAND RESET

LIC - 360 230SM P10 - 8

ACTION REVERSE

+1 +2

A : LY - 360 C: E : 8 - D5 F : 2AC + A4

+3 -3 +4 +5 -5

-1 B :

-2 D : ANALOG CNTRL. -4

FIGURE 73. CONTROL INPUT CIRCUIT

Saudi Aramco DeskTop Standards

81

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

Interpreting Foxboro Spec 200 ILD's(Cont'd)

One pair goes to a computing relay FY - 360A which can be seen on drawing NB - 674434. The other pair goes to terminals +1 and -1 on the top of controller card 2AC + A4. It is these two connections that provide the O - 10v signal for the controller. The output signals of the control card are +2 and -2 as shown in Figure 74. The O - 10 volt signal enters the voltage to current connector card 2AO - V2I + P + P at terminals +4 and -4. The 4 - 20mA output signals leave from terminals +2 and -2. After passing through the marshalling and field junction boxes, the mlliamp signals enter the transducer LTd - 360B. The transducer converts the current signals to 3 - 15 psi pneumatic signals to operate control valve LCV - 360.

+1 A : LC - 360 -1 B : +2 C : E : 8 - D5 F : 2AC +A4

+3 -3 +4 +5 -5

-2 D : ANALOG CNTRL. -4

67 FR OUT + RED GREY


ETB#6 25 26 370 371 8 -10+ 8 -10+1 0 +2 A : LY - 356C C: D : ANALOG INPUT F : 2AO - V3I + P + P +3 -3 +4 -4 +5 -5 -1 B : LY - 360C

LINE NO. 4 '' - C - 33 - 3AI


S 67 FRS
TAG MODEL LCV - 360 3" TAG MODEL LTd - 360B 69TA - I

-2 E : 8 - CI 0

CAL.RANGE AO / AFC

CAL.RANGE 3 - 15 PSI

FIGURE 74.

OUTPUT CIRCUIT

Saudi Aramco DeskTop Standards

82

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

The Honeywell Vutronik Control Loop

Honeywell manufacture a process control system called the Vutronik. It can be used to control a complete system in a plant. The system is made up of five categories, as shown in Figure 75.

ACCESSORY EQUIPMENT

FIELD EQUIPMENT

CONTRX SYSTEM

CONTROL AND NONCONTROL STATION

ELECTRONIC AUXILIARY UNIT

FIGURE 75.

VUTRONIK SYSTEM

Saudi Aramco DeskTop Standards

83

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

The Honeywell Vutronik Control Loop(Cont'd) Electronic Auxiliary Units. Electronic auxiliary components are used for performing monitoring

and computing functions. The components are printed circuit cards mounted in a single-card file. The cards provide such functions as: alarm switches square root extraction millivolt to current conversion (mV/I) resistance to current conversion (/)

Saudi Aramco uses single-card files (cases) to house auxiliary cards. The cases are mounted behind the control panel or in a rack. Figure 76 shows a file case. Input signals are transmitted to the card circuit through a flat flexible circuit and card-edge selector. Note that the case has a 16-point terminal block for connecting signal wiring. The card receives the input signal and then performs the function for which it was set (i.e. square root extraction, mV to I conversion, etc.). The output signals are transmitted back through the edge connector and flexible circuit to the terminal block. Wires transmit the signals to the control instruments in the field and control room.

Saudi Aramco DeskTop Standards

84

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

The Honeywell Vutronik Control Loop(Cont'd) Contrx System. Contrx is a plug-in system. It connects the Vutronik display panel instruments

to the field instruments. The connections are made through termination panels similar to the one shown in Figure 77.

Saudi Aramco DeskTop Standards

85

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

The Honeywell Vutronik Control Loop(Cont'd)

Signals from field instruments pass from the terminals through multiconductor cables to the control room instruments, as shown in Figure 78.
Contrx System (Cont'd).

Saudi Aramco DeskTop Standards

86

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

The Honeywell Vutronik Control Loop(Cont'd)

The Vutronik system includes accessories such as power supplies, Zenner barriers and standby control modules.
Accessory Equipment.

The power supplies provide the voltages for operating Vutronik devices. A Zenner barrier is a connection device that keeps loop current below an unsafe limit. It limits current surges and prevents sparking due to short circuits. Standby control modules can be plugged into a loop to allow a Vutronik controller to be removed without upsetting the process.

Field Equipment. Field equipment used on the Vutronik system include:

Flow measurement instruments Pressure measurement instruments Level measurement instruments Transducers Valve positioners Control valves.

Vultronik transmitters use a 4 to 20mA current loop. Other devices in the system use 1 to 5vdc. Therefore, the current signal being used by the transmitters must be converted to a voltage signal.

Saudi Aramco DeskTop Standards

87

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

The Honeywell Vutronik Control Loop(Cont'd) Changing Current Signals to Voltage Signals. Figure 79 shows a Vutronik terminal block (TPA).

Terminal number 4 is the signal common (that is, it is the terminal to which all signals return). You saw earlier that there are eight terminal blocks on a Vutronik termination panel (TPA). ALL number 4 terminals on a TPA are connected together internally. This produces a circuit that carries a common voltage signal through the TPA (that is, through all eight terminals.)

TRANSMITTER

250

10

11

12

13

14

+25V DC

PV

SC

+V

-V 1 - 5V LL OUT

RL

#1 AL AL COM

#2 AL

RSP

TPA TERMINAL BLOCK FIGURE 79

Saudi Aramco DeskTop Standards

88

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

The Honeywell Vutronik Control Loop(Cont'd) Changing Current Signals to Voltage Signals (Cont'd). Terminal number 1 on each terminal block

is connected to a 25v dc supply. The power supply is not shown on ILDs. Terminal number 2 is the process variable input to the controller. A jumper lead is connected across terminals 2 and 3. A 250-ohm resistor is connected across terminals 3 and 4. The resistor helps to reduce the 25 vdc to a 1 - 5 vdc potential across terminal 3 and the signal common. This arrangement is shown in Figure 80.

TRANSMITTER 4 - 20 mA

250

10

11

12

13

14

25 vdc FIGURE 80

Saudi Aramco DeskTop Standards

89

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

The Honeywell Vutronik Control Loop(Cont'd) Changing Current Signals to Voltage Signals (Cont'd). Figure 81 is a reminder of what is meant by signal common. It is the common point on a parallel circuit through which current is returned to its source.

CONVENTIONAL DRAWING OF CIRCUIT

UNCONVENTIONAL DRAWING OF CIRCUIT

R1

R2

R3

R1

R2

R3

SIGNAL COMMON FIGURE 81

SIGNAL COMMON

Saudi Aramco DeskTop Standards

90

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

The Honeywell Vutronik Control Loop(Cont'd)

Return connections from control instruments to the signal common at terminal 4 are NOT shown on ILDs.
Changing Current Signals to Voltage Signals (Cont'd).

Note the following from Figure 79: Current flows: from terminal 1 to the transmitter from the transmitter to terminal 2 from terminal 2 across the jumper lead to terminal 3 through the 250 ohm resistor to terminal 4, the signal common.

Remember that Vutronik transmitters operate with 4 - 20mA. If a 4-mA current signal is received from the transmitter, then Ohm's Law says that the voltage drop across the 250-ohm resistor is 1 volt, since V = IR = 0.004 x 250 = 1 V. If a 20-mA current signal is received from the transmitter, then from 0.020 x 250, there is a 5v drop across the 250-ohm resistor. 4 - 20 mA is the range of current flow through the transmitter. This is proportional to a 1-5 v signal at the signal common. Figure 82 shows a Vutronik system for level control loop 3010. The system is operating a level recorder, a level indicating controller and an alarm. Note the symbol [-||-] that is used to denote a switch card. As an example, we will trace the signal that operates the level recorder, LR - 3010. A 25 - vdc power supply producing 4 - 20 mA is connected to terminal 1 on TPAI-2. This supply is not shown on the ILDs. (Remember that other connections, such as the internal connections between all terminal 4 and the return connections from instruments to terminals 4 are also not shown on ILDs.) A wire connects terminal 1 on TPAI-2 to the positive side of the transmitter, LT-3010. The connection is made through CA-41 and FA-1 on the BACK AUXILIARY RACK, RK-D283001-1. From FA-1 the wire goes to TB-E-3007 in the junction box, terminal 1. The wire is shielded and is earthed at terminal 3.

Saudi Aramco DeskTop Standards

91

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

Tracing Signals

Saudi Aramco DeskTop Standards

92

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

The Honeywell Vutronik Control Loop(Cont'd)

From TB-E-3007 the current goes to the positive side of the transmitter. The transmitter acts like a variable resistor: the resistance depends on the process variable measurement it is receiving. Therefore, the current that passes through the transmitter depends on the process variable measurement.
Tracing Signals (Cont'd).

The current flows from the negative terminal of the transmitter, through TB-E-3007 terminal 2, FA terminal 2, CA terminal 42 and to TPAI-3 terminal 2. Terminal 2 on TPAI-3 is wired to terminal 2 on TPAI-2. This terminal is jumped to terminal 3. Terminal 3 is connected by a 250-ohm resistor to terminal 4. The voltage drop across the resistor will be between 1 and 5 volts, depending on the value of the current which the process variable has allowed to flow through the system. But, remember, terminals number 4 are connected together, internally, even though this is not shown on the ILD. Therefore, the voltage across terminals 2 and 4 in TPAI-2 and TPAI-3 is 1-5 v, as shown in Figure 83.

4 - 20 m A FROM TRANSMITTER TPA1- 3

1
+

4
_

5
VOLTMETER WILL INDICATE 1 TO 5 vdc INTERNAL CONNECTION

V
250

TPA1- 2

+ 25 vdc TO TRANSMITTER

FIGURE 83. ILD DETAIL

Saudi Aramco DeskTop Standards

93

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

Tracing Signals (Cont'd)

Suppose a connection is made between terminal 2 on TPAI-3 and the input of the recorder, and then from the output of the recorder to terminal 4 on TPAI-3. The voltage across the recorder terminals will be between 1 and 5 vdc, proportional to the value of the process variable. Hence the voltage operating the recorder will be in accordance with the value of the process variable. The connections between the terminal blocks and the instruments are made by wires or cables. These connections are not shown on ILDs. The same wires or cables connect the instruments to terminal 4, the signal common, in order to complete the circuit. The ILD shows that the output signals from the level indicating controller come from terminals 5 and 6 on TPAI-2. These are the standard terminals used on Honeywell TPAs for output signals. (Remember that the output signals of a controller are proportional to the input signals it receives from the transmitter. In this case the input signals will be between 1 - 5 V dc and the output signals will be between 4 - 20 mA DC.) The wire from terminal 5 goes to transducer LTd-3010. The current signal is converted to a pneumatic signal to open or close control valve LCV-3010. The negative terminal of the transducer is connected to terminal 6 of TAPAI-2. This terminal is connected to the negative terminal of the controller and so completes the circuit. The schematic in Figure 84 shows the circuits we have been discussing.

Saudi Aramco DeskTop Standards

94

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

The Honeywell Vutronik Control Loop(Cont'd) Tracing Signals (Cont'd)

LT - 30 10 + -

4 - 20 mA

SIGNAL COMMON

LR - 3010 + 25 vdc POWER SUPPLY 1 - 5vdc

250

SC

LIC - 3010 + -

LTd - 3010 + -

4 - 20 mA

LS-3010-1/ 2

LCV - 3010

FIGURE 84

Saudi Aramco DeskTop Standards

95

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

The Honeywell Vutronik Alarm Card

The Honeywell alarm card monitors a process variable and trips an alarm if the variable goes beyond preset limits. The alarm card may trip a circuit to start or stop a pump, open or close a valve, or trip a plant's ESD system. The Honeywell dual alarm card has two input circuits. Each input circuit needs a 1 to 5 vdc input signal. Figure 85 shows a simple illustration of how the alarm card operates as part of an alarm circuit.

ALARM CIRCUIT 1A INPUT 1 1 - 5 vdc ALARM CIRCUIT 1B

OUTPUT 1A

ALARM

OUTPUT 1B

ALARM

ALARM CIRCUIT 2A INPUT 2 1 - 5 vdc ALARM CIRCUIT 2B

OUTPUT 2A

ALARM

OUTPUT 2B

ALARM

FIGURE 85.

DUAL ALARM CIRCUIT

Saudi Aramco DeskTop Standards

96

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

The Honeywell Vutronik Alarm Card(Cont'd)

Each input has two outputs. Each output is a set of relay contacts. They act as the switch part of the alarm card. Figure 86 shows how a relay operates.

A relay is an electrically-operated switch. Figure 86 shows a relay that is normally open. A spring keeps the relay contacts apart. When current flows through the coil the soft iron core becomes a magnet. The magnetic force pulls the armature down and the contacts close. When the current stops flowing through the coil, the spring pulls the contacts apart. Now return again to the dual alarm system (Figure 85.) When the input voltage signal goes beyond a preset limit, the relays will operate. They will activate an alarm in the control room.

Saudi Aramco DeskTop Standards

97

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

The Honeywell Vutronik Alarm Card(Cont'd)

Figure 85 showed that the card provides two separate alarms for each input signal. Thus, for example, both a high and low alarm can be set for the input from a level transmitter. Handout No. 9 (Drawing No. U54-J-XB-B19079) shows an ILD for level control loop L-020. The alarm card is located on the auxiliary rack RX-454-1. The card is a level switch LS-020 A and B. The card receives two 1 to 5 vdc signals from terminals 2 and 7 on TPAI-7. They are connected to terminals 3 and 5 on the alarm card. The mark number of input 1 is LS-020A. Its alarm settings are 2.1 volts high/1.0 volt low. These are alarms 1A and 1B respectively. Input 2 has a mark number of L-020B. It uses only one alarm setting, which is 3.0 v high. This is alarm 2A. Tracing the connections from the alarms back to the switch card shows that the alarm output terminals for these three alarms are: Output for Alarm 1A Output for Alarm 1B Output for Alarm 2A Terminals 2 and 6 Terminals 7 and 8 Terminals 10 and 11

These connections are made through terminal strips TBC and TBA. Alarm 1A Alarm 1B Alarm 2A operates operates operates XA-1-37 XA-1-43 XA-1-30

Saudi Aramco DeskTop Standards

98

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

The Honeywell Vutronik Alarm Card(Cont'd)

Note that alarm circuits 1B is not a complete circuit on the ILD. This is because alarm 1B is also connected to TBA-78, which is seen to be shown on drawing number XB-B-19078 sheet B. (A study of this drawing shows that alarm 1B is part of the ESD system.) The ILDs will not always show the inputs and outputs on an alarm card. When they are not shown, you must refer to the vendor manual. This gives the inputs and outputs of all the alarms. Note the bracket around terminals 14, 15 and 16. This means that the terminals act as a single unit case only. A study of the ILD for loop 020 shows that when the level transmitter LT-020 senses a low level in U54-D-052 the light in window panel 1-43 on the control room panel will come on. When the level is high the light in window 1-37 will come on. (Note that terminals 82 and 83 on TBA are jumped together to form a complete circuit.)
Summary

Alarm cards can be used to monitor any process variable. The mA output from any transmitter is converted to 1 to 5 vdc and used to operate the cards. The cards can monitor two different variables at the same time. Both input signals are independent of each other. Each set of output contacts on the card can be set at high or low alarms.

Saudi Aramco DeskTop Standards

99

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

Examples of Honeywell Cards

Honeywell mV/I Converter Card. The Honeywell mV/I converter card is mounted in a single card file. The card has two separate converter circuits. It can be used in two different loops at the same time. Each output is 4-20 mA. Figure 87 shows an ILD for a temperature control loop. A thermocouple (Type J) measures temperature in the field. The thermocouple develops millivolt signals, the values of which depend on the temperature measurement. Wires carry the mV input signal to input number 1 on the mV/I converter card, TY-304. Note that the input terminals are on the card, not on the card file terminal strip. The ILD shows that the converter is in the auxiliary rack in the control room. The card converts the mV signal to a 4-20 mA signal. The output of TY-304 is shown to be at terminal 12. The 250-ohm resistor on TB 1 converts the mA output signal to 1-5 vdc. Remember that the power supply and some connections are not shown on ILDs. These include the internal connections that link all terminals number 4 together, and the wire or cable connections that take the 1-5 vdc signal to the control instruments. The 1-5 vdc signal goes to TR-304 (Recorder). The same voltage also exists across terminals 3 and 4 on TB 2. From these the voltage is sent to TI-304 (Indicator).

Saudi Aramco DeskTop Standards

100

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

Honeywell mV/I Converter Card (Cont'd)

Saudi Aramco DeskTop Standards

101

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

Honeywell Resistance to Current Converter Card

Figure 88 shows a temperature control loop in which a Resistance Temperature Detector (RTD) is used to measure temperature. The RTD is a variable resistor. Its resistance changes according to changes in temperature. TY-305 converts the resistance signal to a 4-20 mA signal. The 250 ohm resistor on TB 7 causes a voltage drop of 1-5 vdc. This voltage is used by TR-305 and TI-305.

Saudi Aramco DeskTop Standards

102

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

Honeywell Resistance to Current Converter Card (Cont'd)

Figure 89 show an ILD using square root extractor card, SQ-301. The operation of the circuit is similar to those already discussed.

Saudi Aramco DeskTop Standards

103

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

WORK AIDS ILDs use standard symbols to depict various control instruments. These symbols, taken from Saudi Aramco Standard Drawing numbers 990-J-AD-036491, 990-J-AB-36492 and 990-JAB-36493 are shown below:

Saudi Aramco DeskTop Standards

104

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

WORK AIDS (Cont'd)

01500H
H L LINE NUMBER

MARK NO.

FLOW ELEMENT : ' ANNUBAR ' TYPE

PD / T LINE NUMBER

01500E

MARK NO. SIZE

FLOW INSTRUMENT: PD : POSITIVE DISPLACEMENT METER. T : TURBINE METER

01500D
PD OR T OUT

TRANSMITTER WITH INTEGAL ORIFICE S

LINE NUMBER

INSTR.

01500C
LINE NUMBER

MARK NO. SIZE/RATING A.F. ACTION DWG. AB 036560 HOOK UP

PISTON OPERATED BALL VALVE POSITIONER, SWITCHING VALVES AND VOLUME TANK.

Saudi Aramco DeskTop Standards

105

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

WORK AIDS (Cont'd)

OUTPUT

001500

INSTR.

LINE NUMBER DIAPHRAGM OPERATED GLOBE VALVE WITH POSITIONER

MARK NO. SIZE /RATING A.F. ACTION


MOTOR JUNCTION BOX

01500A
DIAPHRAGM - OPERATED GLOBE VALVE WITH POSITIONER MARK NO. CONT. PSTN VALVE PSTN

LINE NUMBER

MARK NO. SIZE/RATING TYPE

NC OR NO C

MARK NO. CONT. POS VALVE POS

NC OR NO

MARK NO. CONT. POS VALVE POS

SAFETY SHUT OFF VALVE WITH TWO CYLINDERS AND TWO LIMIT SWITCHES LINE NUMBER MARK NO. SIZE
3

Saudi Aramco DeskTop Standards

106

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

WORK AIDS (Cont'd)

MARK NO. CONT. POS VALVE POS


C NO OR NC

C NO OR NC

SAFETY SHUT OFF VALVE WITH ONE CYLINDERS AND TWO LIMIT SWITCHES

LINE NUMBER

MARK NO. CONT. POS VALVE POS

MARK NO. SIZE

3 MARK NO. 5 1

HAND OPERATED SPRING RETURN 4 WAY PILOT VALVE

4 DIAPHRAGM OPERATED 4 WAY PILOT VALVE

3 MARK NO.

LINE OR EQUIPMENT MARK NO.

C NO OR NC

SWITCH ( SINGLE )

MARK NO. SET AT 4

Saudi Aramco DeskTop Standards

107

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

WORK AIDS (Cont'd)


LINE OR EQUIPMENT MARK NO.

C C NO OR NC NO OR NC

SWITCH ( DUAL )

MARK NO. SW1 SET AT SW2 SET AT JB OR TB NUMBER TERMINAL BOX WITH TERMINALS

RB NUMBER

RELAY BOX OR SHUTDOWN SYSTEM

CONDUIT OR CABLE NUMBER

CHECK VALVE

PNEUMATIC TERMINAL 5

Saudi Aramco DeskTop Standards

108

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

WORK AIDS (Cont'd)

Saudi Aramco DeskTop Standards

109

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

WORK AIDS (Cont'd)


COAX PROXIMITY VIBRATION PICK - UP ELEMENT EQUIPMENT MARK NO. MARK NO. RANGE
BLACK RED GREEN WHITE

SHIELD

A B C D

SEISMIC VIBRATION PICK - UP ELEMENT

EQUIPMENT MARK NO. MARK NO. RANGE MTG. POS.

SHIELD

MOTOR J. B.

MOTOR OPERATED VALVE

LINE NUMBER

MARK NO. SIZE

Saudi Aramco DeskTop Standards

110

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

WORK AIDS (Cont'd)

1 2 7 8 9 10 3 4 5 6

SPEED TRANSMITTER WITH INTEGRAL SPEED INDICATOR

MARK NO. RANGE INSTRUMENT PROCESS LINES INSTRUMENT AIR LINES INSTRUMENT ELECTRIC LINES INSTRUMENT CAPILLARY TUBES

SPARE

IN GND. L1 L2
MARK 1st PEN RANGE 1st PEN MARK 2nd PEN

RECORDER ( 1 TO 3 PENS )

DWG. NO.

RANGE 2nd PEN MARK 3rd PEN RANGE 3rd PEN

Saudi Aramco DeskTop Standards

111

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

WORK AIDS (Cont'd)

IN OUT

CONTROLLER

MARK NO. SET POINT P. BAND RESET DERIVATIVE ACTION

IN

INDICATOR ( 1 TO 3 POINTERS

MARK NO. RANGE

IN OUT

INDICATING CONTROLLER

MARK NO. SET POINT P. BAND RESET DERIVATIVE ACTION SCALERANGE

Saudi Aramco DeskTop Standards

112

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

WORK AIDS (Cont'd)

IN OUT SET S

( IND. CONTROL ) ( MANUAL CONTROL UNIT )


MARK NO. SET POINT P. BAND RESET DERIVATIVE ACTION SCALE RANGE

INDICATING CONTROLLER WITH MANUAL CONTROL UNIT

1 2 3 4 5 6 7 8 9 10

COLOR CODE '' '' '' '' '' '' '' '' '' '' '' '' '' '' '' '' '' '' 9 CORES TIED BACK TERMINAL STRIP WITH CORD SET THE TERMINAL STRIP COLOR CODE AND CORD SET SHALL BE IN ACCORDANCE WITH VENDOR DRAWINGS.

TYPICAL

100

IN OUT

INDICATING CONTROLLER

MARK NO. SET POINT P. BAND RESET DERIVATIVE ACTION SCALERANGE

10

Saudi Aramco DeskTop Standards

113

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

WORK AIDS (Cont'd)

CONTROLLER

DWG. NO.
MARK NO. SET POINT P. BAND RESET DERIVATIVE ACTION

INDICATOR ( 1 TO 3 POINTERS )

DWG. NO.
MARK NO. RANGE

ALARM UNIT

DWG. NO.
MARK NO. SET POINT

EMF / RTD TO CURRENT CONVERTER

DWG. NO.
MARK NO. RANGE IN RANGE OUT

11 Saudi Aramco DeskTop Standards 114

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

WORK AIDS (Cont'd)

GRND. DWG. NO.

L2 L1

10 9 8 7 6 5 4 3 2 1
MARK NO. PRE ALARM S. D. SET AT SCALE RANGE

11 12 13 14 15 16 17 18 19 20

VIBRATION MONITOR SEISMIC TYPE OR PROXIMITY TYPE

MULTIPOINT TEMPERATURE RECORDER

MARK NO. RANGE SCALE

DWG. NO.

L1 L2

GRND.

MULTIPOINT TEMPERATURE INDICATOR

MARK NO. RANGE SCALE

DWG. NO.

L1 L2

GRND. 12

Saudi Aramco DeskTop Standards

115

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

WORK AIDS (Cont'd)

MARK NO. SCALE RANGE NO NC H

TEMPERATURE MONITOR MASTER MODULE

MARK NO. SET AT ACTION NO NC H

TEMPERATURE SWITCH ANNUNCIATOR ALARM SINGLE SET POINT MODULE

HI. SET AT HI. HI. SET AT ACTION NO NC H

TEMPERATURE SWITCH ANNUNCIATOR ALARM DUAL SET POINT MODULE FOR FRONT OF PANEL MOUNTING.

MARK NO.

NO NC C NO NC C NO NC C NO NC C

HI. SET AT ACTION

TEMPERATURE SWITCH ANNUNCIATOR ALARM DUAL SET POINT FOR REMOTE RACK MOUNTING.

HI. SET AT ACTION

13

Saudi Aramco DeskTop Standards

116

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

WORK AIDS (Cont'd)


ANNUNCIATOR WINDOW TERMINAL ONE COMMON TERMINAL FOR ALL ANNUNCIATOR LIGHTS MARK NO. WINDOW

COMMON

ANNUNCIATOR WINDOW TERMINAL

MARK NO. WINDOW

PUSH BUTTONS

MARK NO.

MARK NO.

SPEED INDICATOR

MARK NO. RANGE

NO OR NC C MARK NO.

HAND SWITCH

14

Saudi Aramco DeskTop Standards

117

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

WORK AIDS (Cont'd)

LAMP

MARK NO.

RED

RUNNING LIGHTS

GREEN MARK NO.

DIODE

1 2

TELEPHONE JACK

MARK NO.
15

Saudi Aramco DeskTop Standards

118

Engineering Encyclopedia

Drafting Drafting Instrument Loop Diagrams

GLOSSARY Derivative (or Rate Action): Offset: Proportional band: The name given to the control procedure that is concerned with how quickly a process variable (usually temperature) is changing its value. The difference between the actual value of a process variable and its set point value. The ration, as a percentage, of the deviation of a process variable from set point divided by the amount of control valve stem movement the deviation causes. The name given to the control procedure which is designed to bring a process variable back to its set point.

Reset (or gain):

Saudi Aramco DeskTop Standards

119

You might also like