You are on page 1of 13

ETAP

Project:

6.0.0

Location:

Page:

Date:

07-04-2012

Contract:

SN:

12345678

Engineer:

Revision:

Base

Config.:

Normal

Filename:

Study Case: LF
domafinal

Electrical Transient Analyzer Program


Load Flow Analysis
Loading Category (1):

Design

Generation Category (1):

Design

Load Diversity Factor:

None

Swing

V-Control

Load

Total

23

24

XFMR2

XFMR3

Reactor

Line/Cable

Impedance

Tie PD

Total

23

23

Number of Buses:

Number of Branches:

Method of Solution:

Newton-Raphson Method

Maximum No. of Iteration:

99

Precision of Solution:

0.0001000

System Frequency:

50 Hz

Unit System:

Metric

Project Filename:

domafinal

Output Filename:

C:\ETAP 600\domafinal\Untitled.lfr

ETAP

Project:

6.0.0

Location:

Page:

Date:

07-04-2012

Contract:

SN:

12345678

Engineer:

Revision:

Base

Config.:

Normal

Filename:

Study Case: LF
domafinal

Adjustments
Apply
Tolerance

Individual

Adjustments

/Global

Transformer Impedance:

Yes

Individual

Reactor Impedance:

Yes

Individual

Overload Heater Resistance:

No

Transmission Line Length:

No

Cable Length:

No

Apply

Individual

Adjustments

/Global

Transmission Line Resistance:

Yes

Individual

Cable Resistance:

Yes

Individual

Temperature Correction

Percent

Degree C

ETAP

Project:

6.0.0

Location:

Page:

Date:

07-04-2012

Contract:

SN:

12345678

Engineer:

Revision:

Base

Config.:

Normal

Filename:

Study Case: LF
domafinal

Bus Input Data


Load
Bus
ID

Constant kVA

Initial Voltage
kV

Sub-sys

% Mag.

Ang.

Bus1

20.000

Bus2

20.000

Bus3
Bus4

MW

100.0

0.0

100.0

0.0

0.020

0.015

20.000

100.0

0.0

0.427

0.281

20.000

100.0

0.0

0.215

0.083

Bus5

20.000

100.0

0.0

0.640

0.464

Bus6

20.000

100.0

0.0

0.520

0.390

Bus7

20.000

100.0

0.0

0.252

Bus8

20.000

100.0

0.0

Bus9

20.000

100.0

0.0

Bus10

20.000

100.0

Bus11

20.000

100.0

Bus12

20.000

100.0

0.0

Bus13

20.000

100.0

Bus14

20.000

100.0

Bus15

20.000

Bus16

20.000

Bus17

20.000

Bus18
Bus19

Constant Z

Mvar

MW

Constant I

Mvar

MW

0.000

-0.100

0.000

-0.300

0.156

0.000

-0.200

0.893

0.554

0.000

-0.200

0.264

0.097

0.0

0.277

0.234

0.000

-0.200

0.0

0.157

0.074

0.0

0.323

0.201

0.0

0.156

0.055

100.0

0.0

0.085

0.053

100.0

0.0

0.322

0.233

0.000

-0.200

100.0

0.0

0.085

0.053

20.000

100.0

0.0

0.618

0.415

0.000

-0.300

20.000

100.0

0.0

Bus20

20.000

100.0

0.0

0.370

0.229

Bus21

20.000

100.0

0.0

0.123

0.045

Bus22

20.000

100.0

0.0

0.277

0.086

Bus23

20.000

100.0

0.0

0.933

0.613

0.000

-0.300

Bus24

20.000

100.0

0.0

0.454

0.337

0.000

-0.300

7.411

4.668

0.000

-2.100

Total Number of Buses: 24

Generation Bus
ID
Bus1

kV
20.000

Voltage
Type

Swing

Sub-sys
1

Generation

% Mag.

Angle

100.0

0.0

MW

0.000

Mvar

0.000

Generic

Mvar

0.000

MW

0.000

Mvar Limits
% PF

Max

Min

0.000

Mvar

0.000

ETAP

Project:

6.0.0

Location:

Page:

Date:

07-04-2012

Contract:

SN:

12345678

Engineer:

Revision:

Base

Config.:

Normal

Filename:

Study Case: LF
domafinal

Line/Cable Input Data


Ohms or Siemens/1000 m per Conductor (Cable) or per Phase (Line)
Length

Line/Cable
ID

Library

Size

Adj. (m)

% Tol.

#/Phase

T (C)

Line1

3250.0

0.0

75

0.192970

0.144000

Line2

300.0

0.0

75

0.176034

0.236121

Line3

5.0

0.0

75

0.283300

0.380000

Line4

208.0

0.0

75

0.283300

0.120000

Line5

1000.0

0.0

75

0.283300

0.380000

Line6

500.0

0.0

75

0.283300

0.120000

Line7

600.0

0.0

75

0.283300

0.120000

Line8

450.0

0.0

75

0.459610

0.235560

Line9

400.0

0.0

75

0.680000

0.380000

Line10

1000.0

0.0

75

0.680000

0.380000

Line11

500.0

0.0

75

0.680000

0.380000

Line12

400.0

0.0

75

0.680000

0.380000

Line13

800.0

0.0

75

0.680000

0.380000

Line14

200.0

0.0

75

0.680000

0.380000

Line15

700.0

0.0

75

0.422532

0.236121

Line16

100.0

0.0

75

0.680000

0.380000

Line17

90.0

0.0

75

0.680000

0.380000

Line18

500.0

0.0

75

0.680000

0.380000

Line19

800.0

0.0

75

0.680000

0.380000

Line20

950.0

0.0

75

0.680000

0.380000

Line21

250.0

0.0

75

0.680000

0.380000

Line22

302.0

0.0

75

0.680000

0.380000

Line23

500.0

0.0

75

0.680000

0.380000

Line / Cable resistances are listed at the specified temperatures.

ETAP

Project:

6.0.0

Location:

Page:

Date:

07-04-2012

Contract:

SN:

12345678

Engineer:

Revision:

Base

Config.:

Normal

Filename:

Study Case: LF
domafinal

Branch Connections
CKT/Branch

Connected Bus ID

ID

Type

From Bus

% Impedance, Pos. Seq., 100 MVA Base


To Bus

Line1

Line

Bus1

Bus2

15.68

11.70

19.56

Line2

Line

Bus2

Bus3

1.32

1.77

2.21

Line3

Line

Bus3

Bus4

0.04

0.05

0.06

Line4

Line

Bus4

Bus5

1.47

0.62

1.60

Line5

Line

Bus5

Bus6

7.08

9.50

11.85

Line6

Line

Bus6

Bus7

3.54

1.50

3.85

Line7

Line

Bus7

Bus8

4.25

1.80

4.62

Line8

Line

Bus8

Bus9

5.17

2.65

5.81

Line9

Line

Bus9

Bus10

6.80

3.80

7.79

Line10

Line

Bus9

Bus11

17.00

9.50

19.47

Line11

Line

Bus11

Bus12

8.50

4.75

9.74

Line12

Line

Bus12

Bus13

6.80

3.80

7.79

Line13

Line

Bus14

Bus12

13.60

7.60

15.58

Line14

Line

Bus15

Bus14

3.40

1.90

3.89

Line15

Line

Bus16

Bus15

7.39

4.13

8.47

Line16

Line

Bus17

Bus16

1.70

0.95

1.95

Line17

Line

Bus18

Bus17

1.53

0.86

1.75

Line18

Line

Bus19

Bus18

8.50

4.75

9.74

Line19

Line

Bus19

Bus20

13.60

7.60

15.58

Line20

Line

Bus21

Bus20

16.15

9.03

18.50

Line21

Line

Bus22

Bus21

4.25

2.38

4.87

Line22

Line

Bus19

Bus23

5.13

2.87

5.88

Line23

Line

Bus23

Bus24

8.50

4.75

9.74

ETAP

Project:

6.0.0

Location:

Page:

Date:

07-04-2012

Contract:

SN:

12345678

Engineer:

Revision:

Base

Config.:

Normal

Filename:

Study Case: LF
domafinal

LOAD FLOW REPORT

Bus

Voltage

Generation

Load

Load Flow

XFMR

kV

% Mag.

* Bus1

20.000

100.000

0.0

7.704

2.955

Bus2

7.704

2.955

238.2

93.4

Bus2

20.000

98.447

-0.3

0.020

0.015

Bus1

-7.597

-2.875

238.2

93.5

Bus3

7.577

2.860

237.5

93.6

Bus2

-7.568

-2.848

237.5

93.6

ID

Ang.

MW

Mvar

MW

Mvar

ID

Bus3

20.000

98.294

-0.3

0.427

0.184

Bus4

20.000

98.291

-0.3

0.215

0.083

Bus5

20.000

98.170

-0.3

0.640

0.175

Bus6

20.000

97.486

-0.6

0.520

0.390

Bus7

20.000

97.248

-0.6

Bus8

20.000

96.972

-0.6

Bus9

20.000

96.685

-0.6

0.252

-0.033

0.893

0.366

0.264

0.097

MW

Mvar

Amp

% PF

Bus4

7.141

2.664

223.8

93.7

Bus3

-7.141

-2.663

223.8

93.7

Bus5

6.926

2.580

217.1

93.7

Bus4

-6.917

-2.577

217.1

93.7

Bus6

6.277

2.402

197.6

93.4

Bus5

-6.244

-2.357

197.6

93.6

Bus7

5.724

1.967

179.2

94.6

Bus6

-5.710

-1.962

179.2

94.6

Bus8

5.458

1.995

172.5

93.9

Bus7

-5.443

-1.988

172.5

93.9

Bus9

4.550

1.622

143.8

94.2

Bus8

-4.537

-1.616

143.8

94.2

Bus10

0.277

0.047

8.4

98.6

Bus11

3.996

1.472

127.2

93.8

Bus10

20.000

96.664

-0.6

0.277

0.047

Bus9

-0.277

-0.047

8.4

98.6

Bus11

20.000

95.838

-0.7

0.157

0.074

Bus9

-3.963

-1.453

127.2

93.9

Bus12

3.806

1.379

121.9

94.0

Bus11

-3.791

-1.371

121.9

94.0

Bus13

0.323

0.201

11.5

84.9

Bus12

20.000

95.432

-0.7

Bus14

3.468

1.170

110.7

94.8

Bus13

20.000

95.401

-0.7

0.323

0.201

Bus12

-0.323

-0.201

11.5

84.9

Bus14

20.000

94.845

-0.8

0.156

0.055

Bus12

-3.448

-1.158

110.7

94.8

Bus15

3.292

1.103

105.7

94.8

Bus14

-3.288

-1.101

105.7

94.8

Bus16

3.203

1.048

102.7

95.0

Bus15

-3.193

-1.043

102.7

95.1

Bus17

2.871

0.988

92.8

94.6

Bus16

-2.869

-0.987

92.8

94.6

Bus18

2.784

0.934

89.9

94.8

Bus17

-2.783

-0.933

89.9

94.8

Bus19

2.165

0.785

70.5

94.0

Bus18

-2.160

-0.782

70.5

94.0

Bus15

Bus16

Bus17

Bus18

Bus19

20.000

20.000

20.000

20.000

20.000

94.705

94.409

94.348

94.294

94.059

-0.8

-0.8

-0.9

-0.9

-0.9

0.085

0.322

0.085

0.618

0.053

0.055

0.053

0.148

% Tap

ETAP

Project:

6.0.0

Location:

Page:

Date:

07-04-2012

Contract:

SN:

12345678

Engineer:

Revision:

Base

Config.:

Normal

Filename:

Study Case: LF
domafinal

Bus
ID

Voltage
kV

% Mag.

Generation

Ang.

MW

Load

Mvar

MW

Load Flow
Mvar

Bus20

20.000

93.919

-0.9

0.370

0.229

Bus21

20.000

93.837

-0.9

0.123

0.045

ID

MW

XFMR
Mvar

Amp

% PF

Bus20

0.771

0.361

26.1

90.6

Bus23

1.388

0.421

44.5

95.7

Bus19

-0.770

-0.360

26.1

90.6

Bus21

0.400

0.131

12.9

95.0

Bus20

-0.400

-0.131

12.9

95.0

Bus22

0.277

0.086

8.9

95.5

Bus22

20.000

93.822

-0.9

0.277

0.086

Bus21

-0.277

-0.086

8.9

95.5

Bus23

20.000

93.971

-0.9

0.933

0.348

Bus19

-1.387

-0.421

44.5

95.7

Bus24

0.454

0.072

14.1

98.8

Bus23

-0.454

-0.072

14.1

98.8

Bus24

20.000

93.926

-0.9

* Indicates a voltage regulated bus ( voltage controlled or swing type machine connected to it)
# Indicates a bus with a load mismatch of more than 0.1 MVA

0.454

0.072

% Tap

ETAP

Project:

6.0.0

Location:

Page:

Date:

07-04-2012

Contract:

SN:

12345678

Engineer:

Revision:

Base

Config.:

Normal

Filename:

Study Case: LF
domafinal

Bus Loading Summary Report

Directly Connected Load


Constant kVA

Bus
ID

kV

Rated Amp

MW

Constant Z

Mvar

MW

Total Bus Load

Constant I

Mvar

MW

Generic

Mvar

MW

Mvar

MVA

% PF

Amp

Bus1

20.000

8.251

93.4

238.2

Bus2

20.000

0.020

0.015

8.123

93.5

238.2

Bus3

20.000

0.427

0.281

-0.097

8.121

93.2

238.5

Bus4

20.000

0.215

0.083

7.621

93.7

223.8

Bus5

20.000

0.640

0.464

-0.289

7.487

92.4

220.2

Bus6

20.000

0.520

0.390

6.674

93.6

197.6

Bus7

20.000

0.252

0.156

-0.189

6.102

93.6

181.1

Bus8

20.000

0.893

0.554

-0.188

5.862

92.9

174.5

Bus9

20.000

0.264

0.097

4.817

94.2

143.8

Bus10

20.000

0.277

0.234

-0.187

0.363

76.4

10.8

Bus11

20.000

0.157

0.074

4.221

93.9

127.2

Bus12

20.000

4.031

94.0

121.9

Bus13

20.000

0.323

0.201

0.380

84.9

11.5

Bus14

20.000

0.156

0.055

3.638

94.8

110.7

Bus15

20.000

0.085

0.053

3.467

94.8

105.7

Bus16

20.000

0.322

0.233

-0.178

3.419

93.4

104.5

Bus17

20.000

0.085

0.053

3.034

94.6

92.8

Bus18

20.000

0.618

0.415

-0.267

3.031

91.8

92.8

Bus19

20.000

2.297

94.0

70.5

Bus20

20.000

0.370

0.229

0.850

90.6

26.1

Bus21

20.000

0.123

0.045

0.421

95.0

12.9

Bus22

20.000

0.277

0.086

0.290

95.5

8.9

Bus23

20.000

0.933

0.613

-0.265

1.547

89.7

47.5

Bus24

20.000

0.454

0.337

-0.265

0.565

80.3

17.4

* Indicates operating load of a bus exceeds the bus critical limit ( 100.0% of the Continuous Ampere rating).
# Indicates operating load of a bus exceeds the bus marginal limit ( 95.0% of the Continuous Ampere rating).

Percent
Loading

ETAP

Project:

6.0.0

Location:

Page:

Date:

07-04-2012

Contract:

SN:

12345678

Engineer:

Revision:

Base

Config.:

Normal

Filename:

Study Case: LF
domafinal

Branch Loading Summary Report

Transformer
CKT / Branch
ID

Cable & Reactor


Type

Ampacity
(Amp)

* Indicates a branch with operating load exceeding the branch capability.

Loading
Amp

Capability
(MVA)

Loading (input)
MVA

Loading (output)
MVA

ETAP

Project:

6.0.0

Location:

Page:

10

Date:

07-04-2012

Contract:

SN:

12345678

Engineer:

Revision:

Base

Config.:

Normal

Filename:

Study Case: LF
domafinal

Branch Losses Summary Report

CKT / Branch
ID

From-To Bus Flow


MW

Mvar

To-From Bus Flow


MW

Mvar

Losses
kW

% Bus Voltage
kvar

Vd
% Drop
in Vmag

From

To

Line1

7.704

2.955

-7.597

-2.875

106.7

79.6

100.0

98.4

1.55

Line2

7.577

2.860

-7.568

-2.848

8.9

12.0

98.4

98.3

0.15

Line3

7.141

2.664

-7.141

-2.663

0.2

0.3

98.3

98.3

0.00

Line4

6.926

2.580

-6.917

-2.577

8.3

3.5

98.3

98.2

0.12

Line5

6.277

2.402

-6.244

-2.357

33.2

44.5

98.2

97.5

0.68

Line6

5.724

1.967

-5.710

-1.962

13.7

5.8

97.5

97.2

0.24

Line7

5.458

1.995

-5.443

-1.988

15.2

6.4

97.2

97.0

0.28

Line8

4.550

1.622

-4.537

-1.616

12.8

6.6

97.0

96.7

0.29

Line9

0.277

0.047

-0.277

-0.047

0.1

0.0

96.7

96.7

0.02

Line10

3.996

1.472

-3.963

-1.453

33.0

18.4

96.7

95.8

0.85

Line11

3.806

1.379

-3.791

-1.371

15.2

8.5

95.8

95.4

0.41

Line12

0.323

0.201

-0.323

-0.201

0.1

0.1

95.4

95.4

0.03

Line13

3.468

1.170

-3.448

-1.158

20.0

11.2

95.4

94.8

0.59

Line14

3.292

1.103

-3.288

-1.101

4.6

2.5

94.8

94.7

0.14

Line15

3.203

1.048

-3.193

-1.043

9.4

5.2

94.7

94.4

0.30

Line16

2.871

0.988

-2.869

-0.987

1.8

1.0

94.4

94.3

0.06

Line17

2.784

0.934

-2.783

-0.933

1.5

0.8

94.3

94.3

0.05

Line18

2.165

0.785

-2.160

-0.782

5.1

2.8

94.3

94.1

0.23

Line19

0.771

0.361

-0.770

-0.360

1.1

0.6

94.1

93.9

0.14

Line22

1.388

0.421

-1.387

-0.421

1.2

0.7

94.1

94.0

0.09

Line20

0.400

0.131

-0.400

-0.131

0.3

0.2

93.9

93.8

0.08

Line21

0.277

0.086

-0.277

-0.086

0.0

0.0

93.8

93.8

0.01

Line23

0.454

0.072

-0.454

-0.072

0.2

0.1

94.0

93.9

0.04

292.5

211.0

ETAP

Project:

6.0.0

Location:

Page:

11

Date:

07-04-2012

Contract:

SN:

12345678

Engineer:

Revision:

Base

Config.:

Normal

Filename:

Study Case: LF
domafinal

Alert Summary Report


% Alert Settings
Marginal

Critical
Loading
Bus

100.0

95.0

Cable

100.0

95.0

Reactor

100.0

95.0

Line

100.0

95.0

Transformer

100.0

95.0

Panel

100.0

95.0

Protective Device

100.0

95.0

Generator

100.0

95.0

OverVoltage

105.0

102.0

UnderVoltage

95.0

98.0

OverExcited (Q Max.)

100.0

95.0

UnderExcited (Q Min.)

100.0

Bus Voltage

Generator Excitation

Critical Report
Device ID

Type

Condition

Rating/Limit

Unit

Operating

% Operating

Phase Type

Bus14

Bus

Under Voltage

20.000

kV

18.969

94.8

3-Phase

Bus15

Bus

Under Voltage

20.000

kV

18.941

94.7

3-Phase

Bus16

Bus

Under Voltage

20.000

kV

18.882

94.4

3-Phase

Bus17

Bus

Under Voltage

20.000

kV

18.870

94.3

3-Phase

Bus18

Bus

Under Voltage

20.000

kV

18.859

94.3

3-Phase

Bus19

Bus

Under Voltage

20.000

kV

18.812

94.1

3-Phase

Bus20

Bus

Under Voltage

20.000

kV

18.784

93.9

3-Phase

Bus21

Bus

Under Voltage

20.000

kV

18.767

93.8

3-Phase

Bus22

Bus

Under Voltage

20.000

kV

18.764

93.8

3-Phase

Bus23

Bus

Under Voltage

20.000

kV

18.794

94.0

3-Phase

Bus24

Bus

Under Voltage

20.000

kV

18.785

93.9

3-Phase

Marginal Report
Device ID
Bus10

Type
Bus

Condition
Under Voltage

Rating/Limit
20.000

Unit
kV

Operating
19.333

% Operating
96.7

Phase Type
3-Phase

ETAP

Project:

6.0.0

Location:

Page:

12

Date:

07-04-2012

Contract:

SN:

12345678

Engineer:

Revision:

Base

Config.:

Normal

Filename:

Study Case: LF
domafinal

Marginal Report
Device ID

Type

Condition

Rating/Limit

Unit

Operating

% Operating

Phase Type

Bus11

Bus

Under Voltage

20.000

kV

19.168

95.8

3-Phase

Bus12

Bus

Under Voltage

20.000

kV

19.086

95.4

3-Phase

Bus13

Bus

Under Voltage

20.000

kV

19.080

95.4

3-Phase

Bus6

Bus

Under Voltage

20.000

kV

19.497

97.5

3-Phase

Bus7

Bus

Under Voltage

20.000

kV

19.450

97.2

3-Phase

Bus8

Bus

Under Voltage

20.000

kV

19.394

97.0

3-Phase

Bus9

Bus

Under Voltage

20.000

kV

19.337

96.7

3-Phase

ETAP

Project:

6.0.0

Location:

Page:

13

Date:

07-04-2012

Contract:

SN:

12345678

Engineer:

Revision:

Base

Config.:

Normal

Filename:

Study Case: LF
domafinal

SUMMARY OF TOTAL GENERATION , LOADING & DEMAND

MW

Mvar

MVA

% PF

Source (Swing Buses):

7.704

2.955

8.251

Source (Non-Swing Buses):

0.000

0.000

0.000

Total Demand:

7.704

2.955

8.251

93.37 Lagging

Total Motor Load:

7.411

4.668

8.759

84.61 Lagging

Total Static Load:

0.000

-1.924

1.924

0.00 Lagging

Total Constant I Load:

0.000

0.000

0.000

Total Generic Load:

0.000

0.000

0.000

Apparent Losses:

0.293

0.211

System Mismatch:

0.000

0.000

Number of Iterations: 3

93.37 Lagging