APC Modbus Register Map Inrow SC

The document describes a Modbus register map for an InRow SC unit. It lists data points that can be accessed via Modbus registers, including status information, setpoints, sensor readings, and alarms. The register map includes the starting address, data type, units and valid values for each data point. Fault conditions are also enumerated for internal reference.

Uploaded by

Roque Padilla
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
769 views6 pages

APC Modbus Register Map Inrow SC

The document describes a Modbus register map for an InRow SC unit. It lists data points that can be accessed via Modbus registers, including status information, setpoints, sensor readings, and alarms. The register map includes the starting address, data type, units and valid values for each data point. Fault conditions are also enumerated for internal reference.

Uploaded by

Roque Padilla
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Modbus Register Map: InRow SC

990-3027B 02/2009
See the InRow SC Operation Manual for more information on Display Interface status and menu screens.

Absolute Starting Register Number, (Hexidecimal) Unit 0000

Absolute Starting Register Number, (Decimal) 0

Data Point

R/W

Length

Units

Valid Response

Corresponding Display Interface Message

OVERALL_STATUS

Enum

0 = No Alarm

2 = Informational 4 = Warning 8 = Critical

0001 0003 0005 0006 0007 0008 0009 000B 0020 0035 003F 0049 004D 0051 0057 0058 005A 005C 005E 0060 0062

1 3 5 6 7 8 9 11 32 53 63 73 77 81 87 88 90 92 94 96 98

COOL_SETPOINT SUPPLY_AIR_SETPOINT CONFIGURATION_TYPE FAN_SPEED_PREFERENCE UNIT_CONTROL CAPACITY_CTRL COOL_DEADBAND UNIT_NAME UNIT_LOCATION MODEL_NUM SERIAL_NUM FIRMWARE_REV HARDWARE_REV DATE_OF_MANUFACTURE OPERATE_MODE UNIT_COOL_OUTPUT UNIT_COOL_DEMAND RACK_INLET_TEMP SUPPLY_TEMP RETURN_TEMP COND_OUTLET_TEMP

R/W R/W R/W R/W R/W R/W R/W R/W R/W R R R R R R R R R R R R

2 2 1 1 1 1 2 21 21 10 10 4 4 6 1 2 2 2 2 2 2

Long Long Enum Enum Enum Enum Long ASCII ASCII ASCII ASCII ASCII ASCII ASCII Enum Long Long Long Long Long Long

(Tenths Deg) F (Tenths Deg) F 0 = RACS 0 = Low 0 = Standby 0 = Discrete (Disc) (Tenths Deg) F N/A N/A N/A N/A N/A N/A mm/dd/yyyy 0 = Standby (Tenths) kW (Tenths) kW (Tenth Deg) F (Tenths Deg) F (Tenths Deg) F (Tenths Deg) F

1 = Spot 1 = Med-Low 1 = On 1 = Proportional (Prop)

2 = In row 2 = Med

3 = MedHigh

4 = High

None - (Fault Summary - In the event of multiple faults, the highest priority fault is enumerated.) Cool Setpoint Supply Air Type Fan Speed On/Standby Capacity Ctrl Deadband Name Location Model S/N Number F/N H/N Made Op Mode Cool Output Cool Demand Rack Inlet Supply Air Return Air Cond Outlet
1

1 = On

2 = Idle

InRow SC Modbus Map

Absolute Starting Register Number, (Hexidecimal) 0064 0066 0068 006A 006C 006E 0070 0072 0074 0076 0078 007A 007C 007E 0080 0082 0084 0086 0088 008A 008C 008E 0090 0091 0093 0095 0097 0099 009B 009C 009D 009E 009F
2

Absolute Starting Register Number, (Decimal) 100 102 104 106 108 110 112 114 116 118 120 122 124 126 128 130 132 134 136 138 140 142 144 145 147 149 151 153 155 156 157 158 159

Data Point

R/W

Length

Units

Valid Response

Corresponding Display Interface Message Cond Inlet Air Flow Evap Fan Spd Suction Temp Superheat Cond Fan Spd Filter DP Removed in Firmware Rev. 3.5.3 Suction Discharge Air Filter Evaporator Evaporator Evaporator Compressor Condenser Condenser Condenser Lt Fan PS Rt Fan PS Condensate Pump Air Filter Interval Alarm Rack Inlet Supply Air Return Air Altitude Start-up delay Idle on Leak Input Norm Input State Output Norm Output State

COND_INLET_TEMP UNIT_AIR_FLOW EVAPORATOR_FAM_SPEED SUCTION_TEMP SUPERHEAT CONDENSER_FAN_SPEED FILTER_DP CONTAINMENT_DP SUCTION_PRESSURE DISCHARGE_PRESSURE AIR_FILTER_RUNHOUR EVAPORATOR_FAN_1_RUNHOUR EVAPORATOR_FAN_2_RUNHOUR EVAPORATOR_FAN_3_RUNHOUR COMPRESSOR_RUNHOUR CONDENSER_FAN_1_RUNHOUR CONDENSER_FAN_2_RUNHOUR CONDENSER_FAN_3_RUNHOUR FAN_LEFT_PWRSP_RUNHOUR FAN_RIGHT_PWRSP_RUNHOUR CONDS_PUMP_RUNHOUR AIR_FILTER_SERV_INT AIR_FILTER_SERV_INT_ALARM RACK_TEMP_HIGH_THRESH SPLY_AIR_TEMP_HIGH_THRESH RTN_AIR_TEMP_HIGH_THRESH ALTITUDE STARTUP_DELAY IDLE_ON_LEAK INPUT_NORMAL INPUT_STATE OUTPUT_NORMAL OUTPUT_STATE

R R R R R R R R R R R R R R R R R R R R R R/W R/W R/W R/W R/W R/W R/W R/W R/W R R/W R

2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 1 2 2 2 2 2 1 1 1 1 1

Long Long Long Long Long Long Long Long Long Long Long Long Long Long Long Long Long Long Long Long Long Long Enum Long Long Long Long Long Enum Enum Enum Enum Enum

(Tenths Deg) F CFM (Tenths) % (Tenths Deg) F (Tenths Deg) F (Tenths) % (Hundredths) in W.C. (Hundredths) in W.C. Psi Psi Hours Hours Hours Hours Hours Hours Hours Hours Hours Hours Hours Weeks 0 = Enable (Tenths Deg) F (Tenths Deg) F (Tenths Deg) F Feet Seconds 0 = Yes 0 = Open 0 = Open 0 = Open 0 = Open

1 = Disable

1 = No 1 = Closed 1 = Closed 1 = Closed 1 = Closed

InRow SC Modbus Map

Absolute Starting Register Number, (Hexidecimal) 00A0 00A1 00A2 Group 00C8 00CA 00CC 00CE 00CF 00D0 00D1 00D2 00D4 00D6 00D8 00DA 00DC 00DE 00E0 00E2 00E4

Absolute Starting Register Number, (Decimal) 160 161 162 200 202 204 206 207 208 209 210 212 214 216 218 220 222 224 226 228

Data Point

R/W

Length

Units

Valid Response

Corresponding Display Interface Message Outpt Src Compressor None Num Units Cool, Cool Setpt Supply Air Type Fan Speed Capacity Control Fan Cntrl Deadband Altitude Max Rack Min Rack Max Return Min Return Cool Demand Cool Output Air Flow None

OUTPUT_SOURCE COMPRESSOR_STATE UNIT_RESERVED_REGISTERS NUMBER_OF_COOLING_UNITS GROUP_COOL_SETPOINT GROUP_SUPPLY_AIR_SETPOINT GROUP_CONFIGURATION_TYPE GROUP_FAN_SPEED_PREFERENCE GROUP_CAPACITY_CONTROL GROUP_FAN_SPEED_CONTROL GROUP_COOL_DEADBAND GROUP_ALTITUDE GROUP_RACK_INLET_MAX_TEMP GROUP_RACK_INLET_MIN_TEMP GROUP_RETURN_AIR_MAX_TEMP GROUP_RETURN_AIR_MIN_TEMP GROUP_COOLING_DEMAND GROUP_COOLING_ACTUAL GROUP_AIRFLOW_DEMAND GROUP_RESERVED_REGISTERS

R/W R R R/W R/W R/W R/W R/W R/W R/W R/W R/W R R R R R R R R

1 1 38 2 2 2 1 1 1 1 2 2 2 2 2 2 2 2 2 28

Enum Enum Reserved Long Long Long Enum Enum Enum Enum Long Long Long Long Long Long Long Long Long NA

0 = Any Alarm 0 = Off

1 = Only Critical Alarms 1 = On

(Tenths Deg) F (Tenths Deg) F 0 = RACS 0 = Low 0 = Discrete (Disc) 0 = Automatic (Tenths Deg) F Feet (Tenths Deg) F (Tenths Deg) F (Tenths Deg) F (Tenths Deg) F (Tenths) kW (Tenths) kW CFM Reserved

1 = Spot 1 = Med- low 1 = Proportional (Prop) 1 = Manual

2 = In-Row 2 = Med

3 = MedHigh

4 = High

InRow SC Modbus Map

See the InRow SC Operation Manual for more information on Alarm messages.

Absolute Starting Register Number, (Hexidecimal) Faults 0100 0101 0102 0103 0104 0105 0106 0107 0108 0109 010A 010B 010C 010D 010E 010F 0110 0111 0112 0113 0114 0115 0116 0117
4

Absolute Starting Register Number, (Decimal)

Data Point

R/W

Length

Units

Valid Response

Corresponding Display Interface Alarm Message and Severity Level

256 257 258 259 260 261 262 263 264 265 266 267 268 269 270 271 272 273 274 275 276 277 278 279

INTERNAL_COMM_FAULT ALINK_ISOLATION_RELAY_FAULT EXTERNAL_COMMUNICATION_FAULT COOL_FAIL HIGH_RACK_TEMP AIR_FILTER_CLOGGED RTN_AIR_SENSOR_FAULT CONDENSOR_INLET_AIR_SENSOR_FAULT SPLY_AIR_SENSOR_FAULT CONDENSOR_OUTLET_AIR_SENSOR_FAULT RACK_TEMP_SENSOR_FAULT HIGH_DISCHARGE_PRESSURE LOW_SUCTION_PRESSURE EVAPORATOR_FAN_1_FAULT EVAPORATOR_FAN_2_FAULT EVAPORATOR_FAN_3_FAULT WATER_DETECTED CONDS_PUMP_FAULT COND_PAN_FAN FAN_PWRSP_LEFT_FAULT FAN_PWRSP_RIGHT_FAULT AIR_FILTER_RUNHOUR_VIOLATION CONDENSER_FAN_1_FAULT CONDENSER_FAN_2_FAULT

R R R R R R R R R R R R R R R R R R R R R R R R

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Enum Enum Enum Enum Enum Enum Enum Enum Enum Enum Enum Enum Enum Enum Enum Enum Enum Enum Enum Enum Enum Enum Enum Enum

0 = Clear 0 = Clear 0 = Clear 0 = Clear 0 = Clear 0 = Clear 0 = Clear 0 = Clear 0 = Clear 0 = Clear 0 = Clear 0 = Clear 0 = Clear 0 = Clear 0 = Clear 0 = Clear 0 = Clear 0 = Clear 0 = Clear 0 = Clear 0 = Clear 0 = Clear 0 = Clear 0 = Clear

1 = Alarm 1 = Alarm 1 = Alarm 1 = Alarm 1 = Alarm 1 = Alarm 1 = Alarm 1 = Alarm 1 = Alarm 1 = Alarm 1 = Alarm 1 = Alarm 1 = Alarm 1 = Alarm 1 = Alarm 1 = Alarm 1 = Alarm 1 = Alarm 1 = Alarm 1 = Alarm 1 = Alarm 1 = Alarm 1 = Alarm 1 = Alarm

Internal Communication Fault - Critical A-Link Isolation Relay Fault - Critical External Communication Fault - Critical Cooling Failure - Critical Rack Inlet High Temperature Violation - Critical Air Filter Clogged - Warning Return Air Sensor Fault - Critical Condenser Inlet Air Sensor Fault - Warning Supply Air Sensor Fault - Critical Condenser Outlet Air Sensor Fault - Warning Rack Inlet Temperature Sensor Fault - Critical High Discharge Pressure Alarm - Critical Low Suction Pressure Alarm - Warning Evaporator Fan #n Fault - Warning Evaporator Fan #n Fault - Warning Evaporator Fan #n Fault - Warning Water Detection Fault - Warning Condensate Pump Fault - Warning Condensate Pan Full Fault - Critical Fan Power Supply Left Fault - Warning Fan Power Supply Right Fault - Warning Air Filter Run Hours Violation - Warning Condenser Fan #n Fault - Warning Condenser Fan #n Fault - Warning

InRow SC Modbus Map

Absolute Starting Register Number, (Hexidecimal) 0118 0119 011A 011B 011C 011D 011E 011F 0120 0121 0122 0123 0124 0125 0126

Absolute Starting Register Number, (Decimal) 280 281 282 283 284 285 286 287 288 289 290 291 292 293 294

Data Point

R/W

Length

Units

Valid Response

Corresponding Display Interface Alarm Message and Severity Level

CONDENSER_FAN_3_FAULT SUPPLY_HIGH_TEMP_FAULT RETURN_HIGH_TEMP_FAULT FILTER_DP_SENSOR_FAULT CONTAINMENT_DP_SENSOR FAULT SUCTION_TEMP_SENSOR_FAULT SUCTION_PRESSURE_SENSOR_FAULT DISCH_PRESS_SENSOR_FAULT CONTAINMENT_DP_HIGH_FAULT INPUT_CONTACT_FAULT HIGH_DISCHARGE_PRESSURE_FAULT LOW_SUCTION_PRESSURE_FAULT START_LOW_SUCTION_PRESSURE START_LINE_PRESSURE_IMBALANCE GROUP_COMM_FAULT

R R R R R R R R R R R R R R R

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Enum Enum Enum Enum Enum Enum Enum Enum Enum Enum Enum Enum Enum Enum Enum

0 = Clear 0 = Clear 0 = Clear 0 = Clear 0 = Clear 0 = Clear 0 = Clear 0 = Clear 0 = Clear 0 = Clear 0 = Clear 0 = Clear 0 = Clear 0 = Clear 0 = Clear

1 = Alarm 1 = Alarm 1 = Alarm 1 = Alarm 1 = Alarm 1 = Alarm 1 = Alarm 1 = Alarm 1 = Alarm 1 = Alarm 1 = Alarm 1 = Alarm 1 = Alarm 1 = Alarm 1 = Alarm

Condenser Fan #n Fault - Warning Supply Air High Temperature Violation - Warning Return Air High Temperature Violation - Warning Filter Sensor Fault - Warning Removed in Firmware Rev. 3.5.3 Suction Temperature Sensor Fault - Warning Suction Pressure Sensor Fault - Warning Discharge Pressure Sensor Fault - Warning Removed in Firmware Rev. 3.5.3 Input Contact Fault - Warning Persistant High Discharge Pressure Alarm - Critical Persistant Low Suction Pressure Alarm - Critical Cannot Start Due to Low Suction Pressure - Critical Startup Line Pressure Imbalance Alarm - Critical Group Communication Fault - Critical

InRow SC Modbus Map

Absolute Starting Register Number, (Hexidecimal) Logging Registerss FFEE FFF0 FFF2 FFF4 FFF6 FFF8 FFFA FFFC FFFE End of Data

Absolute Starting Register Number, (Decimal)

Data Point

R/W

Length

Units

Valid Response

Modbus Link Definition

65518 65520 65522 65524 65526 65528 65530 65532 65534

APC RX CRC ERRORS APC RX PACKET COUNTER APC TX PACKET COUNTER APC SER FRAME ERRORS APC SER OVERRUN ERRORS APC SER PARITY ERRORS APC SER RX15 ERRORS APC SER RX35 ERRORS APC SER BAUD RATE

R R R R R R R R R

2 2 2 2 2 2 2 2 1

Long Long Long Long Long Long Long Long Integer

RX CRC Errors RX Packet Counter TX Packet Counter Ser Frame Errors Ser Overrun Errors Ser Parity Errors Ser RX15 Errors Ser RX35 Errors Ser Baud Rate

The number of accumulated CRC errors of received packets The total number of packets received The total number of packets transmitted The number of accumulated frame errors of received packets The number of accumulated overrun errors of received packets The number of accumulated parity errors of received packets Number of times the intercharacter delay hss exceeded 1.5 character times Number of times the intercharacter delay has exceeded 3.5 character times See Baud Rate in the InRow SC Operation manual

Note 1: ASCII strings include Null terminator. Note 2: To prevent Building Management Service and automated script difficulties, accesses to data points on unsupported units will return a value of 0 instead of an error. Note 3: Accesses to items before data is available will result in an invalid address error.

InRow SC Modbus Map