Flow monitoring
Immersion sensor with integrated processor
FCS-G1/2A4P-AP8X-H1141/L080
Flow sensor for liquid media
Calorimetric principle
Adjustment via potentiometer
LED band
Sensor length 80 mm
3-wire DC, 2126 VDC
NO contact, PNP output
Plug-in device, M12 x 1
Wiring diagram
FCS-G1/2A4P-AP8X-H1141/L080
6870364
Mounting conditions
Water Operating Range
Oil Operating Range
Stand-by time
Switch-on time
Switch-off time
Temperature jump, response time
Temperature gradient
Medium temperature
insertion style sensor
1150cm/s
3300 cm/s
typ. 8 s (215 s)
typ. 2 s (115 s)
typ. 2 s (115 s)
max. 12 s
250 K/min
- 2080 C
Operating voltage
Current consumption
Output function
Rated operational current
Voltage drop at Ie
Short-circuit protection
Reverse polarity protection
2126VDC
60 mA
PNP, NO contact
0.4 A
1.5 V
yes
yes
Housing material
Sensor material
Max. tightening torque housing nut
Connection
Pressure resistance
Process connection
plastic, PBT
stainless steel, AISI 316Ti
100 Nm
male, M12 x 1
100 bar
G
Switching state
Flow state display
Indication: Drop below setpoint
Indication: Setpoint reached
Indication: Setpoint exceeded
LED display
LED chain green / yellow / red
LED chain, red (1x), green (5x)
LED red
LED yellow
4 x LEDs green
red = 4 mA
1 x green > 4 mA
2 x green > 8 mA
3 x green > 12 mA
4 x green > 16 mA
5 x green = 20 mA
Functional principle
Our insertion - flow sensors operate on the
principle of thermodynamics. The measuring probe is heated by several C as against
the flow medium. When fluid moves along the
probe, the heat generated in the probe is dissipated. The resulting temperature is measured and compared to the medium temperature. The flow status of every medium can be
derived from the evaluated temperature difference. Thus TURCK's wear-free flow sensors
reliably monitor the flow of gaseous and liquid
media.
Edition 2015-02-13T20:28:44+01:00
Type code
Ident no.
1/1
Hans Turck GmbH & Co.KG D-45472 Mlheim an der Ruhr Witzlebenstrae 7 Tel. 0208 4952-0 Fax 0208 4952-264 more@turck.com www.turck.com