You are on page 1of 1

PNEUMATIC CONTROL

FAN POWERED TERMINAL UNIT • PARALLEL FLOW


VARIABLE VOLUME • PRESSURE INDEPENDENT
MODEL: 35NE 1P3

DIAMOND NORMALLY OPEN ELECTRIC LINE


FLOW DAMPER HEAT VOLTAGE
SENSOR COIL N H
STAGE 3 P. E.
AIRFLOW MCP-8030 (OPTIONAL) SWITCH
HI LO
ACTUATOR
(8 – 10 PSI) STAGE 2 P. E.
(OPTIONAL) SWITCH

NORMALLY
P. E. TOGGLE
BALANCING STAGE 1 SWITCH
CLOSED
TEES P. E. SWITCH(ES) DISCONNECT
SWITCH
(OPTIONAL)

RESET START POINT


FACTORY SET SPEED
@ 8 PSI CONTROLLER

T
B H L
SETTING
NC

MUST BE
NO
N. O. M
KREUTER
DAMPER

NORMALLY
G RESET SPAN P. E.
CLOSED
CSC-3011 FACTORY SET SWITCH
P. E. SWITCH
RESET CONTROLLER @ 5 PSI
M
MAIN AIR MB
20 PSI CAPACITOR
FAN
FACTORY WIRING/ PIPING DIRECT ACTING MOTOR
2-PIPE THERMOSTAT
FIELD PIPING (OPTIONAL OR BY OTHERS)

CONTROL SEQUENCE 1P3 • VAV COOLING WITH ELECTRIC


HEAT • DA/NO • 3000 CONTROLLER
Sequence of Operation: Options:
On a rise in space temperature, the thermostat regulates the controller to Two Pipe Thermostat (Vertical Mount.
increase primary airflow. Includes backing plate for 2" x 4" electrical box).
When the space temperature is warm, the primary air damper is controlling at q CTC-1621-103 °F scale plate
q CTC-1621-113 °C scale plate
the maximum airflow setting.
As the space temperature decreases, the damper modulates back towards
the minimum airflow setting. If room temperature continues to drop, the fan is
energized and warm air is induced from the ceiling plenum. Minimum primary
100
airflow is maintained and staged electric heat is energized.
TOTAL AIRFLOW MAX.
Primary airflow is held constant in accordance with thermostat demand. Any 80
CLG.
changes in volume due to static pressure fluctuations are sensed and
AIR

INDUCED PLENUM AIR


AIRFLOW INCREASE

Y
AR

compensated for, resulting in pressure independent control. 60 STAGE


IM
PR

3 STAGE
40
2 STAGE
MIN. 1
20

0
0 3 8 13 15
THERMOSTAT OUTPUT PRESSURE, PSI
SPACE TEMPERATURE INCREASE

SCHEDULE TYPE:
PROJECT:
ENGINEER: DATE B SERIES SUPERSEDES DRAWING NO.
CONTRACTOR: 4 - 22 - 13 3500 NEW 35NECD-1P3
Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.