0 ratings0% found this document useful (0 votes) 66 views90 pagesAppendix D Examples (Steel Embedments)
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content,
claim it here.
Available Formats
Download as PDF or read online on Scribd
N
GSTRERIScmrOMKRY
18
Example Al—Single stud, tension only, no edge effects
Design an embedment using a stud welded to an embedded plate.
Given:
Conerete edges
ce =12in.
ho =48in.
Concrete material
f= 4,000 psi
‘Stud material (A108)
f= 51 ksi
fe = 65ksi
Plate
3x 3.x 3/8 in. thick
Fy = 36 ksi
Loads
No = Skips
Where N, is the applied factored external load using
load factors from Appendix C of the code.
‘Assumptions:
Concrete is cracked
+ @ factors are based on Condition B in 0.4.5 of the code,
(no supplementary reinforcement)
th.
CODE
SECTION
DESIGN PROCEDURE
CALCULATION
STEP 1: Determine required steel area and diameter of the stud
44
45,
46. D414
47, D512
Equate the external factored load to the internal
design strength and solve for the required steel
@N, 2 No
Equation
=aCODE
SECTION | DESIGN PROCEDURE CALCULATION
7 ‘area of the stud Ny = N= Wha oy
2
3. 0.36.1 | Assume embedment will be designed as ductile
4 D5 | inaccordance with D.36.1 (in Step 2). N= 8 =@ Mata
5. D5.1_| Therefore: @ = 0.80 for tension. B01. Aye 65 kips
8 Aree = 0-154in. required
7 Calculate nominal steel strength of selected
8 stud,
8
10. Etfective
1 Anchor diameter area, Aue Use one 1/2 in. diameter stud
12 in
13. Ag = 0.198 in? > 0.154 in?
14 3B 0.110
15, 12 0.196 controls,
16. 05.12 Ny = MAtu (03)
0 Calculate the nominal steel strength, Ns 4.070.196" 65
18 = 12.74 kips
19,
20. 05.12
21 Check that the material tensile and yield 9751=96.9ksi
22. steengihs meet requirements of D.5.1.2, = 128,000 psi ok
23. (See also Endnote 1)
24. STEP 2: Determine required embedment length for the stud to prevent concrete
25, breakout failure in tension
26.
27. D5.2_ | Calculate the required embedment depth forthe
28. 0.3.6.1 | stud to prevent concrete breakout failure, The
29, depth will be selected so thatthe stud will be
30. governed by the strength of the ductile steel
31 lament. This wil produce a ductile embedment | From Step 1
32. and justify the use of the @-factor for stee! used
33. previously N,= 12.74 kips
34
35, The requirements for @ ductile design are given
36. inD36.1. To prevent concrete breakout for | 0.85 * Nerron = Ns
37 tension load, requires that: Neeeg = NyO.85
38. O.85'Ney2 Ny 12.7410.85
39 14.99 kips
40.
41 7
42. 5.2.1 | Concrete breakout strength for a single stud: |Ny = ZEW, V My ID (04)
43 he
4
45 For a single stud away from edge: Ay = 9h? (08)
48, AilPva
47. Modification factors for,
48. 0.5.25 | Edge effects ¥, Ys (0-19)
49. 0.526 | Concrete cracking Ws vs
50. D.5.2.7 | Spliting control factor Yay applies to post’ | Wanye = NIA for studs (0527)
51 installed anchors only
52
53, 0.5.2.2 | k= 24 for castinheaded stud Ny (0-7)
10SECTION | DESIGN PROCEDURE CALCULATION
t Assume hy < Tt Ta fan
3
a
5
8 Neng = 14.99 kips "
i Determine required embedment length 14.99 0° 1.0° 1.0 * 1.52 hy
8. aoa Hessen a
9
i Use 172 in, x 43/4 in, long stud
"1
12 Total length of a stud L, before weld, is equal to 75-312 + 375
13 the embecment iength plus the head thickness burn off (0.125 in)
14, plus allowance for burn off. Standard length = 4.69 In. > 4.60 in. OK
15 and head dimensions are given by the
18. manufacturer, Typical values are given in Table
7 6, Appendix A :
HA baie 1.52" 4.69"
19. Calculate Nea using hetsowses 18.44 kips
20,
21. STEP 3: Check pullout strength of stud
22.
23, 0.5.3 _| Caloulate the pullout strength ofthe stud in
24, 0.3.6.1 | tension in accordance with 0.5.3. Design
28. tembedment as ductile in accordance with
26 D361
27.
28. 0.5.3.1 | Concrete is ecacked per problem statement. (0-44)
29,
30.
31. 0.5.34 | Calculate pullout strength of anchor. (0-415)
32
33.
34,
35. 0.5.3.5 | W, = 1.0 for cracked concrete.
36 0
37. Calculate the bearing area. From manufacturer
38. data, stud head diameter is 1.0 in. for @ 1/2 in. 7 (1.08- 0.84
39. diameter stud (see also Table 6 in Appendix A). 59 in?
40
41 032° 0.59
42. }8.88 kips
43. 0.3.6.1 | Design embedment as duct, in accordance
44 with 3.6.1 O.85Nyy = 0.85" 18.88
45. 0.85 Ngo 2 Ny = 16.05 kips > N, = 12.74 kips
46.
47. Therefore ductile ok
48,
49, Use 1/2 in, diameter x 4-3/4 in. long
50 stud
51
52
"ene
CODE
SECTION | DESIGN PROCEDURE CALCULATION
1. STEP 4: Check concrete side-face blowout
2,
3. D.S4_ | Because this stud is far away from an edge, NIA
4 side-face blowout Ney will not be a factor, and
5, will nt be checked in this example.
6
z.
8, STEPS: Summary
3.
10. Given | Applied load Ny =8 Kips:
ri
12, Step 1 | Design steal tensile strength @N,= 0.8" 12.74 = 10.19 kips
13, D4A5.a
14. Step2 | Design concrete breakout strength Neg = 0.75" 15.44 = 11.58 kips
18. D.45.c
46. Step 3. | Design concrete pullout strength Non 20.75" 18.88 = 14.16 kips
17. 045.c
18. Step4 | Design concrete side face-blowout strength | @Na»= N/A
19. Da.Sc
20. 0.4.1.2 | Design strength of stud in tension Ny = min (pNs, New, GNee)
21, min (10.19, 11.58, 14.16)
22. =10.19kips > Nv=8kips OK
23,
24. 0.3.6.1 | Ductiity min (0,85Nep, O.85Neo) Ne
25. min (0.85 * 15.44, 0.85 * 18.88)
26.
27. 2131221274 Kips Ok
28.
28.
30. STEP 6: Check plate thickness
31
32. AISC | Because the load is applied directly over the | Stud welding of 1/2 in. diameter studs is,
33. stud, the only requirement on plate thickness is _| acceptable on 3/8 in. thick plate per
34 that it satisfies the minimum thickness required | 0.6.2.3.
35. for stud welding,
36.
37. Stud material s A108, material properties per AWS D117, 2002, Table 7.7, Type & stud, yield stvenath
38. =51 ksi, tensile strength = 85 ksi. It has elongation of 20% and reduction in area of 50%, meets the
39, definition of a ductile stee! element given in D.1, and meets the tensile strength requirements of 0.5.1.2
40,_and 0.6.1.2: fu 1.9f, (65 < 1,9°51.0 = 96.9 ksi
i. Inthe above example, the effective embedment length hy is taken to the face of the concrete. TF ihe
22. plate was larger than the projected surface area, then the embedment length would exclude the
43, thickness of the embedded plate.
12SSSISGRBNIScovonsens
heise ane ee
RENN:
RBERBS:
Example A2—Single stud, shear only
Design an embedment using a stud welded to an embedded plate.
Given:
Concrete
‘Stud material (A108)
Plate
Loads
Where Vis the applied factored external load
using load factors from Appendix C of the cade.
‘Assumptions
Edge
c= 10in
& 1Bin
ho =48in.
f= 4000 psi
f = Stkel
f= OS ksi
‘Assume 3 x3 x 3/8 in, thick
Fy 236 ksi
VW = Skips
Concrete is cracked
(p-factors are based on Condition B in 0.4.5 of the code
{no supplementary reinforcement)
CODE
section [DESIGNPROCEDURE | CALCULATION
48,_ STEP 1: Determine required steel area of the stud
45
47. 0.4.1. | Equate the external factored load to the internal Equetion No
48 design svength and solve forthe required steel | @V, = Vy i
49. 0.6.1.2 | area af the stud Va) =Ve= OA (0-18)
50
51. 0.36.1 | Assume embadment willbe designed as duct | Arens =Vul@nta)
52___| inaccordance with D 3.6.1 (n Step 2)
13CODE
E 0
SECTION | DESIGN PROCEDURE CALCULATION :
7, DS | Therefore: @ = 0.75 for shear loads 075
2
3. p61 | Design required area of stud using the stes! | Arrog = 810.75",1*65)
4 strength provision. = 0.123 in? required
5
8 Etective Use one 1/2 in, diameter stud
7 Anchor di Are, Av
8. erty Aye =0.196 in? > 0.123 in? OK
8 (0-18)
70. ae 3.110
" 42 0.196 contro's
72
13. 06.12 9751 = 96.9ksi
14 Calculate nominal shear capacity of the selected ok
15 stud
16
7 Material properties are given. See Endnote 1.
18 Check that D.6.1.2[s met. (See also Table 6,
19, ____| Appendix A for edaltional stud properties).
20. STEP 2: Determine required edge distance to prevent concrete breakout failure in
21. shear
21.
2 Ensure that the embedment design is controled
2 by the strenath ofthe embedment steal. The
24 requirement for ductile design is given in
25. 0.3.6.1. For shear load this requires that
26
27. D364 0.85Vey2 Acca O.85V a 2 Aula
28 min Veg = Aasa/0.85
2, 0195 "65 10.85
30 1499 Kips
at
32. | A
38. D.6.2:1 | Calculate concrete breakout strength Vis in| Vis = Vet (0-20)
34 shear fr a single stu. Av
3 Ao = (0-22)
38, Calculate projected area for a single stud ‘
37. See figure above for ilustration of Avo AiKo
38 Because edges are far enough away, A, and
80, Aare equal.
40
For castin headed studs, orheaded bolts, that | y, — gqva,ye* fay (Fe!*
41, D623 Vy, =80ld)? {a {Rel bb 0-24)
2 Settee atackaer kanege | TMU EE O29
a | minimum thickness equa! to the greater of 318
44 in. or half of the anchor diameter, the basic 1s 8dy Definition in D.0
e onerete breakout strength Vy is determined | assume / = 25 in
46 reac: {ildg)= 2.515 =5.0
47
48
‘s See definition in 0.0 for limits on / 3*5:02*05** 40003* 6"?
50. 494c)'9 Ib
54 = 0.496 6,’ Kips _
14CODE :
SECTION DESIGN PROCEDURE CALCULATION
1
2
3 | Modification factors for shear for:
4. D626 | Edge effects yo
§ 2827 | Cracked concrete wr
c Concrete is cracked per problem statement. No | Vervos= 14.99 kips ts
8 additional supplementary steel is provided. 07 1.0* 1.0 * 0.494 ¢;'
9. = 494" cy'* kips:
10
"1
12. C1y0q = 9.73 in. (required)
i ‘< 10.0 in, (provided) OK
Calculate Voy using = 10 in. provided
ie aa ceca ‘Strength controlled by steel
1
17. Vay = 0.494 * 10'8 = 15.62
8 > 12.74 kips
19,
20. STEP 3: Determine the required embedment length for the stud to prevent concrete
21. _pryout failure
2
23, D.6.3 | Determine the required effective embecment | V, = 12.74 kips (o-8)
24 length to prevent pryout See Step 1
25, (Note: Same value as for tension N,)
26. 0.36.1 | Ductlty requirements of 0.3.6.1 shall be
21 satisfied
28,
29, 0.85 Veg? Ve 0.85" Vep2 Ve= 12.74
30 2.74/0.85,
31 4.98 kips
32,
33. 0.63 | Design required embedment depth, from the (0-28)
34 concrete pryout strength requirement. Assume
36. he? 2.5 in. Therefore, Keg = 2.0.
36 4,9972.0
37 No is the required concrete breakout strength 50 kips - required
38 intension, Calculate the required embedment
39 depth ofthe anchor to prevent breakout. The
40 approach is identical to that for tension used in
44 Example 1. fi |
42, 052 Ny = Ae eN, 0-4)
43, Aus
44. AWAno = 1.0
45.
46 Because this isa single stud away from edges,
a7 modification factors are all 1
4B
49. 0.5.22 | Basie concrote breakout strength fora single o
50. anchor in tension: ef ny = Aeon 7
51 24 for cast-in headed studs 2a OOO?
52 Assume ha < 1110,
15CODE
SECTION
DESIGN PROCEDURE
CALCULATION
‘See Appendix A, Table 6, for stud head
dimensions. Note that 0.312 in. is head
thickness and 0.125 in. is bur off.
Caleulate Veg using hey = 3.08 in.
= 1.52hy) kips.
}7.50 = 1.0 1.071.0*(1.52)h)?
aing =2.90in. required
Use 4/2 in. x 3-1/2 in, long stud
hes provided:
hes
=3.50-0.312-0.125
= 3.06 in, > 2.90 OK
eaNes
2.0" 1.52" 3.05"*
= 16.27 > 12.74 kips
oK
STEP 4
Check pullout strength of stud to check head of the stud
053
Ds34
Ds35
36.1
Checking of stud head is required to develop
the concrete breakout strength Nes used to
‘check conerete pryout.
Procedure is the same as that used in Example
the anchor in tension in accordance with 0.5.3.
| Concrete is cracked per problem statement.
Therefore, ¥, = 1.0. Bearing areais based on
manufacturer data, (See Table 6 in Appendix
Ay
Design embedment as ductile, in accordance
with D.3.6.1:
0.85 Noa 2 Ny
NN, for this problem is calculated in the pryout
section shown in Step 3.
Al. Calculate the nominal pullout strength Nj, of
Non = "AN
(0-14)
No = Ante
(0-15)
B74" Aug
32.Bng Rip
1732" 0,589
= 18.8 kips
O.85Nyq= 0.85°18.8
= 16 kips > N,
‘Therefore ductile
Use 1/2 in. diameter x 3 1/2 in. long
‘stud
Specified 1/2 in. diameter anchor
head dimension OK
32.
STEP 5: Summary of design strength
16| CODE
SECTION DESIGN PROCEDURE CALCULATIO!
7
2, Given | Applied load Vy =8kips
3
4 Step | Design stee! shear strength OV, =0.75*12.74= 9.58 hips
5 DASA 0K |
8. Siep2 | Design concrete breakout strength |
7 DASc Ve = 0.78" 15.62" 11.72 kips
8. Siep3_| Design concrete pryout strength 0K
9. DASc
10 Veg = 0.75" 16.27 = 12.20 ips
11, D.4.1.2 | Design strength of stud in shear
12
13 Vp = min (GV, Ven, Ve)
| 14 in (9.56, 11.72, 12.20)
} 45, 0.3.6.1 | Ductity 56 > 6 kips.
16. oK
17.
18 mmin (0.85V ep, 0.85Vep}2 Vz
oe min (0.85 * 15.62, 0.85 * 18.8)
21 = 13.28> 12.74 kip
22, OK
23.
2A
25. STEP 6; Check plate thickness
26. T
27. AISC_| Select plate thickness equal to or greaterthan | max (38 n,,0.5/26.25 in)
28. 0.6.23 | 3/Bin. orhalfthe anchor diameter 318 in
23
30 Tests have also shown that plate rupture is | min > 0.5/2.7 = .19in. < 3/8.
31 prevented when dit < 2.7,
32 38 in. thick plate is OK
33
534, "Stud material & AIOG, material properties per AWS DI.I, 2002, Table 7.1, Type B stud, yield sirongth = 31 ksi
35, tensile strength = 65 ksi. I has elongation of 20% and rection in area of 50%, meets definition ofa dette
36, steel element given in D-, and meas the tensile strength requirements of D.1.2 and D.6.1.2: fa $ 1.9 (63
37,19 *51 =969 < 125 ksi).
38.” Goble, G. G., 1968, "Shear Sirngih of Thin Fangs Compost Seatons, "AISC Engineering Jowmal, Ape. _|
7Example A3—Single stud, combined tension and shear
Design an embedment using a stud welded to an embedded plate,
gre?
ASTESNAS0e1HOM a ONA=
18
Giver:
Edge
c= 12in
c= 20in
ho =48in
Conerete
f= 4000 psi
‘Stud material (A108)
5 =STksi
he =65ksi
Plate
3x3x 9/8in. thick
F, = 36ksi
Loads
Ne =8kips
Ve =Bkips
‘Where N, and V, are the applied factored external loads
using load factors from Appendix C of the code.
Assumptions:
+ Concrete is cracked
‘* g-factors are based on Condition B in D.4.5 of the code
(no supplementary reinforcement)
SEgnOu p28 Crnsou ovCODE
SECTION DESIGN PROCEDURE CALCULATION
1, STEP 1: Determine required steel area of the stud
2
3. 0.4.1.1 | Equate the extemal factored load to the
4 internal design strength and solve for the Equation
5 required steel area of the stud
6 No.
7. D5. | Use the tension provisions of 0.5.1 to
8. D5:.2 | determine the required steel area for
9 tension load gh, 2N, (on
10, Ne’ NS = Ante (03)
"1 ‘Aves required stee! area for tension load
12
13, D.3.6.1 | Assume embedment wil be designed as | Ae: =No! (Qnty)
14, ductile in accordance with 0.36.1 {in Step 2) = (8/0.80" 1.0" 65)
3504.5 _ | Therefore, ~~ 0.80 for tension and 0.75 for
16.0.5.1.2/0.6 | shear. Steel material is ductile (See Endnote | Ay, = 0.154in.7
7.42 ».
18
19
20 Use the shear provisions of D.6.1 10
21, 0.6.1 _ | determine the required steel area for shear
Wns 02)
= Pa Va =Ve = MBsovha (o-r7)
23. yor fequited steel area for shear
24 -
25, {Add the area of steel required fortension to |e 2 Sel@hl) | 55)
26, the area of steel required for shear. eo aee
21,
28. Total required area
29, v.73 | Amen (Arent Asay 12
x This sssumes interaction betvoen tension | sees
a and shear, which will be checked in Step 8 on?
33
4 efocive
Es Anchordiameter __area, Asin
7 2 0186
ee 58 0307 controls
39,
‘o Caldas nominates! sverath Ne Use one 58. diameter stud
42. Ase = 0.307 in.? > 0.231 in?
43. oK
48
45, een Ne= NAc:
7 Calculate nominal stee strength Vs = Male soy «65
a7
48
49
50
51 = 19,96 kips
52
53
19CODE
SECTION
DESIGN PROCEDURE
CALCULATION
STEP 2: Determine required embedment length of the stud to prevent concrete
Ds2
D521
17. 036.4
24. D521
30. 0525
31. D526
32. D527
34. D522
3
4.
5._ breakout failure in tension
6.
ia
8
Calculate the required embedment depth for
the stud to prevent concrete breakout failure.
‘The depth will be selected so that the stud will
be governed by the strength of the ductile
steel element. This will produce a ductile
‘embedment and justify the use of the @-factor
used above. The steel capacity is based on
the selected stud diameter.
‘The requirements for a ductile design are
given in 0.3.6.1. For tension toad, this
requires that
O.85°Nas = Ns
Calculate concrete breakout strength for a
single anchor
Fora single stud away from edge:
Modification factors for:
Edge effects W,
Concrete cracking Ys
Weg.n applies to post installed anchors only
k= 24 for cast-in-place stud.
Assume hay < 11 in.
Required embedment length hjog
In this example, the total length of the stud L
is equal to the embedment length plus the
head thickness plus allowance for weld burn
off. Head dimensions are given by the
manufacturer. Typical values are given in
Table 6 in Appendix 1
Calculate Ney using hetronted
From Step 1
Nz = 19.96 kips
(D3)
0.85" Nowa?
Nessea = NeO.85
= 19,960.85
= 23.48 kips
A
Fa %yqfy (4)
Ave
Ne = fs pny I (0-7)
= 24 TOO?
= 1.52413 kips
28.48 = 1.0" 1.0" 1.0° 1.529
hasea = 6.20 i required
Use 5/8 in. x 6-3/4 in. long stud
78-312 - 187 +.375 in,
= 6,63in.> 6.20in
Prove
OK
G)2 12> 15 *hy=15"663=994 in
edge distance has no effect.
20CODE
SECTION
DESIGN PROCEDURE
CALCULATION
Nes = 1.52" 6.63" = 25.95 kips.
8. STEP3: Check pullout strength of stud
¢ ‘Slud head is required to develop the concrete
10. breakout strength No
1
42. 05,3. | Procedure is similar to that used in Example | Nox = Np
% ‘At Calculate the nominal pullout strength Nex (0-14)
1a of he st in tenslon in accordance with
15. 0.5.3.4 053. Ne
8
i Conerete is cracked per problem statement.
Therefore, ¥z= 1.0. Bearing area is based
jo. 535 | Srnutooue dei, (append Ac abe)
21. Aog= 0.92 in? Table 6
22 = 1.0" 32" 0.92
23. 29.44 kips
a Design embedment as ductile in
25, p36. accordance with 0.3.6.1:
26.
27. 0.85 Nyn® Ne
28
i, for this problem is ce in Stey O.85Nmn = 0.85 * 29.44
2, efor this problem is calculated in Step 1 ScepaMeeN cia iis
Bt Thortoe deta
3 sin. dieters 64 org oud
35. OK
36. STEP 4: Check concrete side-face blowout
a7
38 0.5.4 | Because this stud is relatively far away from ;
39, ROS. | anedge, skdeface blowout wil nat be 9 60¢ fad h (046)
40. factor, According tothe commentary, side- =12in
41, face blowout is not a concem if c > 0.4he. Aigg = 0.92 in? Table 6
2 i= 4000 psi
43. In this example:
4 hy 6.83 in Ne =160" 1270.92» 4000"
45. O.4he = 0.4 * 6.63 = 2.6 in, = 116.5 kips
46. 5 12 in. > 2.6 in.
47 Because ¢> 04h, side-face blowout
48, aleualon isnot required. The calculation | 0.85 N= 99.0 kips > N= 12.98 kips OK
49 wl be done to llustate the method. See also
50. Table in Appendix A 5i8 in. diameter x 6-34 in. long stud
51 ok
21‘CODE
SECTION
DESIGN PROCEDURE
CALCULATION
1, STEP 5: Determine required edge distance to prevent concrete breakout failure in shear
36.1
10.
12
13. 06.21
14,
16.
17.
8
13
20.
21. D623
22
23,
24,
25,
26
27
28,
29,
30.
3
32. D626
33. D827
36.
36.
37.
38,
38,
40.
41. Stop 1
42,
43,
44,
45,
46,
Ensure that the embedment design is,
Controlled by the strength of the embedment
steel, The requirement for ductile design is
given in D.3.6.1. For shear load this requires
that:
O.85Ven 2 Aaah
Calculate concrate breakout strength Vey in
shear for a single stud.
Calculate projected area for a single stud.
‘See figure above for illustration of Avg
Because edges are far enough away, A, and
Aare equal
For cast-in headed studs or headed bolts that
are welded to steel attachments having a
‘minimum thickness equal to the greater of 3/8
in, or half of the anchor diameter, the basic
concrete breakout strength Vj is determined
using 0.6.2.3,
‘See definition in D.0 for limits on C.
‘Modification factors for shear for:
Exige effects, we
Cracked concrete,
Concrete is cracked per problem statement.
No additional supplementary stee! is supplied.
Steel strength in shear Vs
Calculate Vey using ¢) = 12 in. provided
0.85Vey = Asta
Vener = Aki. 85
0.307 * 65 0.85
(0-20)
(022)
H=B da)" Vdelhes pay
Udy =6.63/0.625 = 10.61 >8.0
Use Ud = 8.0 Do
Vp = 8" 8°? + 0.625% * 400085 * o;'*
o' Ibs
1.606 c"* kips
23.48 = 1,0* 1.0* 1,0" 0.606 criea!®
Cig = TAB in. < 12.010 ok
Strength controlled by stee!
V.= 19.96 kips
= 0.606 ¢,'
606 (12)"5
5.19 kips
Ve
22CODE
SECTION | DESIGN PROCEDURE CALCULATION
1. STEP 6: Check concrete pryout failure
2
3 063 Pryout strength of the stud is checked using
4 D.6.3. For an anchor or stud designed for
5. tension, this will not govern. The calculations
6 are for ilustration of the method.
i
8. 0.3.6.1 _ | Duetlity requirements of 0.3.6.1 shall be
8 satisfied
40. 0.85 Vep2 Vs
11
2
13, (0-28)
14, Kop
15 Nes = 25.95 kips
16 06.3 | Nis calculated in Step 2
47. Vey =2° 25.95
18. 51.9 kips >> 23.5 kips, oK
19.
20. 5/8 in, diameter x 6-2/4 in. long stud
21 is OK
22
23. STEP 7: Summary
24
25. D412 | TENSION
26.
27. Applied load Ny = 8kips
28.
29. Step1 | Steel strength @N,= 0.80" 19.96 = 15.97 kips
30. D452
31. Step2 | Concrete breakout strength Ney = 0.75 * 25.95 = 19.46 kips
32, D456
33. Step3 | Concrete pullout strength 787 29.44 = 22.08 kips
34. D4Sc
35. Step4 | Concrete side face-blowout strength ‘gNap = 0.75 * 116.5 = 87.40 kips
36. 0.4.5.0
37, 0.4.1.2 | Design strength of stud, tension min (Ns, Nes Nex, PNax )
38. min (15.97, 19.45, 22.08, 87.40)
39. = 15.97 kips = Ny= Skins | OK
40. SHEAR
41
42. Applied load Vy = 6 hips:
43.
44. Step1 | Stee! strength @V,= 0.75" 19.96 = 14.97 kips
45. DAS
46. Step2 | Concrete breakout strength @Ven = 0.75 * 25.19 = 18.89 kips
47. DABS
48. Step 3 | Concrete pryout strength Ve #075" 51.9 = 38.9 kips
49. D45c
50. 0.4.1.2 | Design strength of stud, shear QVq = min (PVs Vey PV)
51 min (14.97, 18.89, 38.9)
52 = 14,97 kips>V,=6kips_ __OK
23CODE 7 eaeea ql
SECTION DESIGN PROCEDURE CALCULATION
i
2. 03.6.1 Ductility, min (0.85Nc, 0.85Non, 0.85 Neb) 2 Ns
3 tensian min (0.85 "25.05, 0185 18.88, 0.85"
4 1165)
5. min (22.06, 16.05, 99.03)
8 72.06 > = 19.80 Kips 0K
7 Shear
a min (0.85Ve, 0.85Vcq) > Ve
8 mmin(0.85°28.19, 0.85°51.9)
40. min (21.41, 44.12)
" 221.81>V,= 19.96 kips ox
iz
13,__ STEP 8 Check interaction of tension and shear forees
14.
15.
ul sttength in tension shall not be permit >
17, DIA ss es
18. NaN, > 0.2 NUON, 3.0/15.97
19 Fullsttengt in shear shal not be permed = 050202
20. D7.2
21 Ne Me 950040090 (0-3)
4 a,
23. D73 0.90<1.2 OK
24,
25.
26.
27.
28,__ STEP 9: Caleulate minimum plate thickness
78,
30. 0.6.23 | select pate tickness equal to or greater than | t imax (38 in, 0.572=25 in)
31 3/8 in. or haf the anchor diameter Sein
32
33 Tests have also shown that pate rupture is | tag > 0572.7 = 0.19. < 38,
34 prevented when dete 2.7
38. 2/8 In. thik plate is OK
36.
37, * Stud material is A108, material properties per AWS DI-I, 2000, Table 7.1, Type B stud, yield swengih = 51 ksi,
38. tensile strength = 65 ksi. It has clongation of 20% and reduction in area of 50%, meets the definition of a ductile
39, steel element given in D.1, and meets the tensile strength requirements of D.5..2 and D.6.1.2: fa S 1.9f, (655 1.9
40. * 51.0 96.9 ks).
41, * Goble, G. G., 1968, “Shear Suengih of Thin Flange Composite Sections,” AISC Engineering Journal, Apr
24Example A4 - Single bolt, combined tension and shear
Design an embedment using a high-strength bolt, F1554 Gr. 105 (AB105").
Given:
Where N, and V. are the applied factored external loads using load factors from Appendix C of the code.
‘Assumptions:
Concrete is cracked
‘© g-faciors are based on Condition 8 in D.4.§ of the code
(no supplementary reinforcement)
CODE zi : ‘
SECTION DESIGN PROCEDURE CALCULATION
32, STEP 1: Determine required steel area of the bolt
3
34 Equate the external factored load to the Equation
35 intemal design strength and solve for the ‘No.
36. D414 required steel area of the bolt.
37
38. 0.5.12 | Use the tension provisions of D..1 to (0-1)
39, determine the required steel area for tension (03)
40. load.
41 m1 = Fequired steel rea for tension load
42
43. 0.3.6.1 Assume embedment will be designed es Aces = 400.8" 1 * 125) = 0.40 in?
44. 0.45.2 _| duetiein accordance with 0.36.1 (in Stop 2).
45, Therefore, 9 = 0.80 for tension and 0.75 for
48. shear.
47 ‘Assume bolts far away from an edge
43 (02)
48. 0.6.1 | Use the shear provisions of D.6.1 to (0-18)
50. D.45.a | determine the required steel area for shear
51. D612 | load 011.0 "0.8 * 0.75 125)
52 Avev= fequired steel area for shear lozd 36 in?
53
25CODE
SECTION _ | DESIGN PROCEDURE CALCULATION
7 ‘Rad the area of steal required for tension to
2 the area of steel required for shear.
3
4. 073 Total required area, Aw = (Aros + Asay VIZ (0.40 + 0.36/1.2 = 0.64 in?
5.
6 ‘This assumes interaction between tension
a ‘and shear, which will be checked in Step 8.
8
9 Effective
10, ‘Anchordiemeter___area, Arein® | Use one 1-1/8 in. diameter headed
1 1.0 0.606 bolt
12 1.125 0.763, controls
13, OK
14,
15. Calculate nominal stee! strength N.in tension.
16. Aces
7. 0.98 * 125
18. 5.0 kips
19. Calculate nominal steel strength V, in shear.
20.
21 0.6 Acta
22. "0.6" 0.76" 125
23. 7.0 kips
24.
25, STEP 2: Determine required embedment length for the bolt to prevent concrete
26. breakout failure in tension
27.
28. D5.2 | Calculate the required embedment depth for | From Step 1
23, the bolt to prevent concrete breakout failure.
30. ‘The depth will be selected so that the anchor | N, = 95.0 kips
31 will be governed by the strength of the ductile
32 steel elamont. This will produce a ductile
33. embedment and justify the use of the @-factor
34. used above. The steel capacity is based on
35. the selected anchor diameter. Use N, to
36. determine required ha,
37.
38, D.3.6.1 | The requirements for a ductile design are
29, given in 0.3.6.1. For tension load, this
40. requires that
41
42. 0.85 * Nay 2 Ny (0.85 * Nax® Ne
43,
44 Nessee = NyO.85
45, 95.01.85,
46. = 111.8 kips
47,
43, Away :
49. 0.5.2.1 | Caleulate concrete breakout strength fora | No =a Bary Cl
50. single bolt oe
51
52
53. For e single bolt away from edge: Alu = 1.0
26Srcrion | DESIGN PROCEDURE CALCULATION
7
2 Modification factors for
3. 0528 | Edgeetfects Y 210
4 0526 | Concrete cracking Ys on =10
5. D527 | Wow applies to postinstalled anchors only | Wis. = NIA for bolts
6
7. Basic concrote breakout strength: Ne = nus (07)
8 k= 24 for castin-place anchors see
9 24 f(HO00)H?
10 = 1g2htt
i" = 1.52/13 kips.
72
13 Determine the required effective embedment Aes 0-4)
14 depth heiea cae of
18. 1s
16 Determine bolt leneth L TB = 1,071.0" 1.07 152K,
7. Pang = 17-57in.
38
19 L__ = 1757 + 0.75 (thickness. of
20 head)
a = 1832.
22.
2. Use 18.5 in.
28
25. Use 4-118 in. diameter, F1554 Gr105
26, bolt embedded 18.5 in. into the
27, concrete.
28
20, hatpontes 85-75
30. Calculate Ne using hay provided 47.75 in, > 17.57 in.
31 Note: For 11 in, shay 25 in, the besic oK
32 conerete breakout strength Ny can
33 alternatively be calculated using £q.(D-8) | Ne = 1.527 17.75"S = 113.7 kips
34 that yields largor loads. This was neglected
35, in this exempee.
36,
37, STEP 3: Check pullout strength of bolt
38,
39. 0.5.3 | Procedure is the same as that used in
40. Example Ai. Calculate the pullout strength of | Ny = WaNy
41 the bolt in tension in accordance with D..3 (0-14)
42
48 Calculate pullout strength
44
45.
48.
47, 5.3.5 | Concrete is cracked per problem statement.
48, = 1.0
49.
50. ASTM F 1554 recommends a heavy hex
51 head and washer.
52
53 Appendix A, Table 4(0), Aus = 1.85 in
arCODE
Section _ | DESIGN PROCEDURE CALCULATION
7
2 For this combination of steel strength and | Nye = 1.0" 32 * 1.85 = 59.2 kips
3. Conerate strength, the anchor head alone is -< Ns, 95 kips
4. rot sufficient to develop the required bearing
5 strength
6.
7. Find required net bearing area,
8 Design embedment as ductile in accordance
8. with D.3.6.4
10. 0.3.6.1 85Ng Ns
n
12 = 95 kips (Nftom Step 1)
13. Nonsoq = 9510.85
14 Find the total area of bearing surface. 11.8 kips
16.
6 1118 =32Ayg
7 See Appendix A, Table 4 foranchorhead — | Augig = 111.8/32 = 2.49 in?
8. areas.
18. As 89 in? anchor area
20. Aastney = 349+ 0.99
21 Design a washer to meet the required bearing = 4.48 in?
22 area, From Table 5 we can see that the SAE
23 washers will not work, and U.S. standard | For 1-1/8 in. bol, hex head area is:
24 washers seem too thin. A 85 in?
25. Try a square plate. Bn 48 -2.85 = 1.63 in’
26.
27 Use a square plate 2-1/4 in, each side.
28.
29. Ayaner = 2.28
30. 5.06 in.?> 4.48 in?
FI oK
32. Caloulate Nyx using Aa, provided Arasrodtes 05 -0.99
33. = 407 in? > 3.49 in?
34. D.3.6.1. | Check ductility, 0.85Ny,2 Ny OK
35. Now 1.0 * 32° 407
36. 130.24 kips
37. According to D.5.2.8, when adding a washer
38. atthe head of an anchor, itis permitted to | O.85N,. = 0.857 130.24
39. calculate the projected area of the failure 110.7 kips > Ns, 95 kips
40. surface by projecting the failure surface
4 ‘outward 1.Shy from the effective perimeter of | Use 1-1/8 in, diameter AB 105 bol,
a2 the washer. Therefore, the conerete breakout | embedded 18.5 in., with 2 square
43 strength can be revised. washor 2-114 in. sides and 3/8 in. thick.
44
45.
46. STEP 4: Check concrete side-face blowout
47.
48. D.5.4 | Because this anchor is far away form an
49, edge, side-face blowout will not be a factor,
50. ‘and wil not be checked in this example.
SI
28CODE
section _ | DESIGN PROCEDURE CALCULATION
J. STEPS: Determine required edge distance to prevent concrete breakout failure in
2.__shear
3
4 0.6.1.2 | Compute nominal steel strength in shear 0.6
5 (0° 0.6 "0.78" 125
6. 257 kips
7
8. D.36.1 | Ensure that the embedment design is
8. controlled by the strength of the embedment
10 steel, The requirement for ductile design is
4 given in D.3.6.1. For shear load, this requires
12 that:
13 0.85Ver 2 Acs 0.85Ve 2 Ve
14, Vesa = V0.85
18,
16.
17,
18. 0.6.2.1 | Catculate concrete breakout strength Vein (0-20)
18. shear for a single anchor.
20.
a1 Calculate projected area for a single anchor. (0-22)
2. See figures for llustration of Aa. Because
23. ‘edges are far enough aviay, Ay and Ay are
26 equal
25. y= 1ltdy)" 8 23
FA Thebasiccorceta beskoutsvongtn vais |= MMI Aa Ifel* (O20
27. determined using D.6.2.2.
28. Ud = 17,75/01.125 = 15.78> 8.0
er See definition in D.0 for limits on €. Use Udo = 8.0 Do
at Ve, = 778°? 1,128°%+ 40008 +
32 Mes
33 =7H0'5,
4 = O71 6)" kips
35.
36. 1.6.2.6 | Moditication factors for shear for:
37. D627 | Edge effects, We ve = 10
38. Gracked conerete, yr v= 10
39, Gonerete is cracked per problem statement ‘e
a No additional supplementary steel is supplied. | 67.06 = 1.07 1.07 1.0° 0.711 Cyeq!
42. Coq = 20.72 in. < 26 in ox |
43
44. Strength controlled by steel
45.
os Calculate Vey using ¢) = 24 in. provided Veo= 0.711 c)'*
47. : 0.711 (24)"*
48, = 83.60 kips
49.
50.
51
52
52,
29CODE
SECTION _ | DESIGN PROCEDURE CALCULATION
1. STEP 6: Check concrete pryout failure
2.
3 D3 For a bolt designed for tension, as in Step 2, (0-28)
4 concrete pryout failure will nat govern, and
5 hence, this step is not required.
6 Vep is calculated for illustration. Na = 113.7 kips
7 Nays calculated in Step 2.
8 Vey = 2113.7
9 = 227.4 kips >> 95 kips
10.
di. STEP 7: Summary
72
13. D412 | TENSION
14,
15, Applied load Ny = 40 kips
16.
17. Step | Steel strength @N, = 0.80 * 95.0 = 76.0 kips
18 D452
Step 2/0.4.5.¢ | Concrete breakout strength Ney = 0,75 * 113.7 = 85.3 kips
20.
Step 2/0.4.5.¢ | Concrete pullout strength GNyq 20.75 * 130.24 = 97.88 ips.
22.
Step 41D.4.5.¢ | Concrete side face-blowout strength NIA
23,
24. Design strength of stud, tension GNq = min (Ne Ne
2. min (76.0, 85.
28. =76.0kips>Ny=40kips OK
27. 041.2 | SHEAR
28.
23. Applied load Wy = 20kips:
30.
Step 0.4.5.2 | Steel strength OV, = 0.75 "87.0 = 42.75 kips
32.
Step 2/D.4.5.c | Concrete breakout strength Vey = 0.75 * 83.60 = 62.70 kips
34,
Step 9/D.4.5.c | Concrete pryout strength Vey =0.75* 227.4 = 170.55 kips
36,
37 Design strength of stud, shear Va = min (@Vs. Gen Ves),
28 ‘min (42.75, 62.70, 170.55)
35, i OK
40. 0.3.6.1 | Ductiity
41. iin (0.85Ney, 0.85Nyp, 0.85 Nzs) > Ny
42 Tension min (0.85 * 113.7, 0.85 * 130.24, N/A)
43, ‘min (96.65, 110.70)
44 =96.65>N,=95.0kips OK
45,
46. min (0.85Vey, 0.85V5) > Vs
47. Shear min (0.85 * 83.60, 0.85 * 227.4)
48. min (71.06, 193.29)
49, ok
50.
30CODE a
SECTION _ | DESIGN PROCEDURE CALCULATION
1, STEP 8: Check interaction of tension and shear forces
2
3 D7 Wg, > 0.2 VuQVe = 2042.75
4 D7. Fl strength in tension shall not be permitted =0.47>0.2
5. (030)
8
7 Nl GNa > 0.2
8. 0.7.2 _| Fullstrongthin shear shall not be permited
8 NJ@N, = 40/76.0
10 053>0.2
11
2
13
4 Mey Me 1.2
1s nN, WY, (0-30)
16
"7
18
19. 0.53+0.47= 1.00 1.2
20 oK
a
22. STEP 9: Calculate minimum plate thickness
23.
28. AISC | Select plate thickness using the appropriate
25, steel code. This step Is not included inthis
26. example,
27
28, 1 ASTM F 1554.00 specilication, Grade 105, Class 1A, bolt matenal willbe used. Bolt identification s
29, (ABIO5) witha tensile strength in the range of 125 to 1S0 ksi, and minimum yield strength of 105 ksi for 1/4 10
30, 3 in. diameters. Reductions in area requirements vary. For anchor diameters < 2 in., elongation in 2 in is 13%,
31. and reduction in area is 45% and meets the definition of a ductile steel element given in D.1. Also, max fy [4
32. f. According to D.6.1.2, fy, shall be-< 1.9 f oF 125,000 psi, See also Table | for other materials
31RBNIScoraaaoNn
15
Example B1(a)—Four-stud embedded plate, tension only, wide spacing
Design an embedment wih four welded studs and an embedded plate for a 3.x 3 x 3/16 in. A501 structural tube
‘atlachment where anchors are spaced her apart.
Given:
‘Conerete edges
c=) = c= 18in. A
ho =18in,
Concrete material
f= 4,000 psi
Stud material (A29/A108)'
f= St ksi
fa = 65 ksi
Plate
Fy = 26 ksi
Load
Ny = 28 kips
Where N, is the applied factored external load using
load factors from Appendix C of the code. The wide spacing
indicates that each of the four anchors develops.
full tensile capacity.
Assumptions:
Concrete is cracked
+ g-factors are based on Condition B in D.4.5 of the code
(no supplementary reinforcement)
+ Ductile embedment design in accordance with D.3.6.1,
CODE
section |PESIGN PROCEDURE CALCULATION
35. STEP 1: Determine the required stud diameter
36. ‘Equation
37. No.
38-D.4.1.1 | Equate intemal design strength (gNs) tothe, Ne? Nu (1)
39. external factored load (Nu)
40. In a ductile design, the internal strength (Na) is | Na=Ne= AAs
41 controlled by the steel strength of the stud (Ns)
42
43 “The required steel strength ofthe stud (Nyseq) iS | 0.80* Nejeq = 28
44. 0.45 | multiplied by 9 = 0.80 fortension because the | New = 26/0.8
45. | embedment and the steel stu is ductile and the = 35.0 kips |
46. load factors are based on Appendix C of the code.
47. Naweq = Ase fa (0-3)
48. Solve for the required steel area fora single stud | 35.0 = 4" Ajeng 65
49. D5. | crm) Arouse = 35.0/(4 65)
50. 0.13 in? required
31 Effective |
52. ‘Anchor diameter areaA.in? | Use 1/2.in, diameter studs
53. | Ag = 0.196> 0.13 in? OK
32CODE
SECTION | DESIGN PROCEDURE CALCULATION
7 38 0.170
2 42 0.196 controls
3
4, DSA 03)
5 Determine the nominal tensile strength Nz
8 of 4-1/2 in, diameter studs.
Z
8. STEP 2: Determine the minimum embedment length and spacing for the studs to prevent
9, concrete breakout failure in tension.
10
at
2 Ensure steel strength controls:
13. 0.3.6.1. | To prevent concrete breakout failure in tension the | @ * Nesaea Ns
14, required design concrete breakout tensile strength
15 (@ Nea) has to be greater than or equal to the
| 16. Nominal tensile strength of the embedment steel] N, = 51.0 kips Step 1
1, (Nd.
18
19
20. 0.3.6.1 | The design concrete breakout strength shall be | 0.85 * Negron Ne
a taken as 0.85 times the nominal strength. Nesiea 251.85
22. lo = 60.0 kips
23.
24. DS2 | Nagis the nominal concrete breakout strength in| Nu YEN, (D5)
25. tension of a group of anchors. Avo
26.
27. 05.2.1 | Avis not calculated because itis assumed that | Ay = 4" Ayo
28. spacing is not limited, Therefore, only the ratio | AWAv = 4
29. AA is needed,
30.
3
32, 0.5.2.4 | Modification factors ate all 1.0 for: vy =10
33. 0.5.25 | Eccentricity effects we = 10
34 Edge offocts W.
36. Grin = 15 in. per problem statement.
36. Edge effecis factor, will be 1.0 a long as Ce
37. 4.57 hy OF het S Col 1.5.
38. Therefore, the embedmenthyneedsto be less |
39. than 15/1.5 = 10 in. to ensure no reduction due to
40. edge distance.
41
42, 05.26 | Concrete cracking Ys, Concrete is cracked per |W, = 1.0
43. problem statement,
44, 0.5.2.7 | Wanis not used for cast-in-place anchors, Yoon = NIA for studs
45
46. 0.5.2.2 | Neis the basic concrete breakout strength in fn
” tension ofa single anchor ineracked concrete. |y, = AVJc Hy in
48
48. Assume the embedmentwilbe ess than *1in. |], = 24¢6,000)8*%tha)*
50. and use Eq, (0-7). For cast-in-place anchors use 2S ke
St k= 24 eos
52.
53._D.5.2__ | Negis the nominal concrete breakout steenath in
33CODE
SECTION DESIGN PROCEDURE CALCULATION
1 tension of 6 group of anchors. | A
2. | | Neg = SE PSN, (0-5)
3. | | ‘wo
4 =4°4,0° 1.0.1.0" 1.52 * ha)'®
5. Calculate the minimum required effective = 6.08" (ha)
8 embedment depth har by setting Ney equal 10
7. Negae: 6.08" (hei)'® = 60.0 kips
8 Perea 48in.
8 Determine the total length L ofthe stud:
“The total required length L ofthe stud is equal io
the required effective embedment depth hy plus | Leg = hy + head thickness + burn off
SESSSSSSSRSSCSSSBUSSS BRS SBRLRRVSPRBSssaaRassS
Ds2.1
ps2
D521
ps24
ps21
the head thickness, plus allowance for bum off,
{minus the plate thickness, which is conservatively
ignored in this problem’). Typical values for head
thickness, and bur off are provided in Table 6 of
Appendix A
Determine the spacing s:
Assume no limits on spacing. Space anchors at 3
times hs.
Determine the actual concrete breakout failure
(Nag) using the actual embedment and spacing,
Nesp is the nominal concrete breakout strength in
tension of a group of anchors.
Determine Ay
Determine Avo
“The ratio of AyAyo is limited to 4
The embedment is less than 11 in, Therefore,
Eq, (D-7) is used to calculate the basic concrete
breakout strength. Also, because the embedment
is less than 10 in., v2 is 1.0 as assumed
previously.
= 4.6 + 0.312 40.125
=5.04 in,
Use 4-1/2 In, diameter x 5-1/4 in. long
studs.
aprons * 5.25-0:312 -0.125 (Burn
ct)
81in
‘Spacing required between anchors is
3° 481= 14.43 in
Use spacing s = 15 in.
Nag = AUN, 5)
Avo
Au = Ghats)
(3 *4.81+ 15)
366.1 in.”
thy? 6)
“ery
08.2 in.
AvlAyo = 866.1/208.2
16>40
Use 4.0
Ne 52 (he) (07
52° (4.81)'*
6.03 ips
+4.0° 4.0" 1,0" 1.0" 16.03
64.1 kips
Nag
34CODE
suction | DESIGN PROCEDURE CALCULATION
7. O85" Noy = 0.85" 6412
2 54.5 > 51.0(N,) kips OK
3
4.
5
8. "Inthe above example, the effective embedment length hy is teken fo the face of the concrete. Ifthe
7._ plate was lerger than the projected surface area, then the embedment length would exclude the thickness
8. ofthe embedded plate.
9.
10, STEP 3: Check pullout strength of stud
Th
12 Determine Noa
13, 0.5.3.1 | Nyy isthe nominal pullout strength in tension of a | Ny, = YaNy (0-14)
4 single anchor.
15.
16. 5.3.1. | Npis the pullout strength in tension ofa single | Ny = Ae (0-18)
7 aichorin cracked concrete.
18 0.5.38 | Concrete is eracked per problem statement #10
19.
20. 05.34 | Caleuate the bosring area. The anchorhead — | Ayg = x*(1.00°-0.sc?y4
21 diameters 1.0 in. fora 1/2in, diameter stud =0.59in?
22 (Table 6, Appendix A),
3. N, =05ar8"4
24, = 18.9 kos
25
26. Nw = Np (0-14)
27 1.0" 189
28 = 189 kips/bolt
20, = 75.6 kips (4 bolts)
30
31. 0.3.6.1 | Check duetity 0.85" Nyy = 0.85*75.6
2 085 “Nyy 2Ne 64,3 > 51.0 kips (N,) OK
34, STEP 4: Check concrete side-tace blowout
35, 5.4.1 | Check concrete side-face blowout
36 =04 "481
a Ife> 0.4 hy, side-face blowout will not be a factor
© = 15in.>1.92in oK
38
39. STEP 5: Summary
40.
41. Given | Applied toad = 28 kips
42,
Stop 1/0.4.5.a | Design steel tensile strength ON, = 0.8°51.0= 40.8 kips
44,
Step 210.4.5.¢ | Design concrete breakout strength @Naqg = 0.75" 64.1 = 48.1 kips
46.
Step 31D.4.5.¢ | Design concrete pullout strength Nox = 0.75" 75.6 = 58.7 kips
48,
Step 40.4.5. | Design concrete side face-blowout strength Ne = NA
Ea
35CODE
|_ section |PESIGN PROCEDURE CALCULATION
7
2. D.4.1.2 | Design strength of stud in tension ON,
3, q
4. = 40.8 kips > N,=28 kips OK
5.
6 0.36.1 | Ductlty: ‘min (0.85Naxy, 0.85Nga) = No
7. min (0.85 * 64.1, 0.85" 75.8)
8 ‘min (54.5, 64.3)
8. 54.5 >N,= 51.0 kips oK
10.
Il. STEP 6: Cheek plate thickness
72.
13. AISC | Select plate thickness using the appropriate steel
14, code. This stop is not included in this example. A
45. sample calculation for a base plate design is
16. provided in Example B1(b).
7.
48
19. "Shad material is ADO/ATOR, material propertics
per AWS Di.1, 2006, Table 7.1, Type B std, yield strength = 51
20. ksi, fensile strength = 65 ksi. Ithas elongation of 20% and reduction in area of 50%, meets the definition of a
21, ductile steel element given in D.1, and meets the tensile strength requirements of D.5.1.2 and D.6.1.2 fy $1.94, (65,
1.9 51.0= 96.9 ksi)
36Example B1(b)—Four-stud embedded plate, tension only, close spacing
Design an embedment with four welded studs and a rigid embedded plate for a3 x 3.x 3/16 in. ASOT structural
tube attachment
Given:
‘Concrete edges
in = 15 it
hr = Bi
Base plate
BxBin,
Spacing
s=6in,
Concrete mi
=
Stud materi
fy
fe
Plate
F, = 36k
Load
I.
in
in,
iaterial
‘4000 psi
ial (A108)
81 ksi
65 ksi
Nv= 28 kips
where Nu is the
applied factored external load using
load factors from Appendix C of the code.
Assumptions:
+ Concrete is cracked
+ factors are based on Condition B in D.4.5 of the code
(n0 supplementary reinforcement)
© Ductile
‘embedment design is in accordance with 0.3.6.1
CODE 7
SECTION | DESIGN PROCEDURE CALCULATION
STEP 1: Determine the required stud diameter.
a7. Equation
48 No.
49. 0.4.1.1 | Equate internal design strength @N, to the external | @Ny 2 Ny (0-1)
50. factored load Nu
37CODE : : ,
section | DESIGN PROCEDURE CALCULATION
i Ina ductile design, the nlernal strangih Ny
2 controlled by the steel strength of the stud N, | Np =Ny = MAeta
3
4
5
6
7. D45 | The required steel suength of the stud Nszoyis | 0.80" Naeg 2 28
8 multiplied by @ = 0.80 for tension because the
8. embedment and the steel stud is ductile and the | Nyyeg = 28/0.8
10. load factors are based on Appendix C of the code = 35.0 kips
M1.
42, 0.5.1 | Solve forthe required stool area Aare fora single | Nyieg = PAs (0-3)
13. stu 35.0) = 4 Arie’ 65
14 Areva = 35.0104 65)
2 =0.13in? required
16.
17 Effective Use 1/2.n, diameter studs
18. Anchor diameter area, Axe in?
19. [ys aAT0 196 > 0.13 in.” OK
20 we 0.198 controls
24 |
22. D5.1__| Determine the nominal tensile strength Ny ast (03) |
23. of 4-12in. diameter studs. “0.196 65,
24, 1.0 kips
25
26, STEP 2: Determine the minimum embedment length of the studs to prevent
27._conerete breakout failure in tension
cy
23 Ensure steel strength controls:
30. 0.36.1 | To prevent concrete breakout failure in tension, | @ * Negros» Ne
3 the required design concrete breakout tensile
32, strength @Nesseq as to be greater than the
3 nominal tensile strength ofthe embedment steel | N= $1.0 kips Step 1
34 Ne
35,
36. 0.361 0.85 * Nesp Ne
a7. “The design concrate breakout strength shall be | Neywa> 31785,
38, taken as 0.85 times the nominal strength. Neen > 60.0 kips
39,
40. 052 4
4 Nag the nominal concrete breakout strength in EHH Ns (05)
42. tension of @ group of anchors. Ayo
43,
4,
45. 05.24
46. 0.525 | Modification factors are all 1.0 for W190
47, Eccentricity effects Y= 10
48, Edge effects Y,
49, nin = 18 in, por problem statement.
50, Edge effects facior will be 1.0 25 long a5 Cain
51 1.8 he OT hy S Cpal 5.
52 Therefore, the embedment hy needs to be less
53, than 15/1,5 = 10 in, to ensure no reduction due to
38CODE
SECTION DESIGN PROCEDURE CALCULATION
i edge distance
2 0826 W=1.0
3 Concrete cracking Ws, Concrete is cracked per
4. problem statement.
5 D527 Yeo = NIA for studs
6 ‘egw is not used for cast-in-place anchors
7
& 0522 (0-7)
9. Ny is the basic concrete breakout strength in
40. tension of a single anchor in cracked concrete
u
72, ‘Assume the embedment willbe less than 11 in,
3 and use Eq. (D-7), For castin-place anchors, use A
14 k= 24 beat lie (05)
15, D521 wo
16. Nag is the nominal concrete breakout strength in| Nag = (AWAyo)* 1.0" 1.0 1.0" 1.52*
7. tension of a group of anchors. het
18, = (AwAva) * 1.52 * he®
| 19.
| 20.
24 Use trial and error; increase heruntil Negi
22 equal to or greater than the required Nese
B
24 First eration: Try he = 8 in.
25. 05.24 (3 * hy) +s]?
26. Aw is the projected area of the failure surface for r
27. the group of anchors. See Figure RD.5.1 in
28. Commentary for guidance in calculating Ay
29. Spacing $i 6 in. per problem statement
30. 0521 5)
31 ‘Aygis the projected area ofthe failure surface of @
32 single anchor remote from edges.
33
34. D524 900/576
35 Ratio of ereas.
38
37. D522
38 Basic concrete breakout strength
39.
40.
41
42, 0.5.2.1 | Nominal group concrete breakout stienath, Ney (05)
43.
44
45. Because New of 53.6 kips is less than required, | Nay = 1.56*34.4
46. 60.0 kips, we need to increase the effective Nesp = 53.6 kips <60kips (No good)
47 ‘embedment depth he, and try again.
48
49,
50. Second Iteration: Try he = 9 in.
51
52. 05.2.1 | Determine Ay
53
54 (05)
39CODE | DESIGN PROCEDURE CALCULATION
SECTION
D521 | Determine Aw 5° 9
| = 729 in?
AglAwo = 10897729 =
Ny = 1.52" hy!
7
2
3,
4
5. D.5.2.1 | Determine the ratio of Ay/Aye
6
7.
8 52° 9°
5. D522 _ | Basic concrete breakout strength 0 kips
70,
" Neg =1.49°41.0
2 Neg =613kips 2600 Ks OK
13. 052 _ | Nominal group concrete breakout strength Nag
\14 hy =9in. 80K
‘S
6 Because the conerete breakout strength Nu of
7 61.3 kis is greater than the required value of 60
8 kips, the embedment depth har of in, wil
3 produce a ductle design
20 Liegess™ hy + head thickness + bum off
zi
22. D5.2 Determine the total length of the stud L. L =9.0+0.312+ 0.125
23. ‘The total requied length ofthe stud Lis equal to =o4in
24. the required effective embedment depth h'., plus
25. the heed bickness, pls some addifonal feng
28. account for burn off (minus the plate thickness,
27 which s Consorvatively ignored in his problem)
28 “Typical values for head thickness and burn off ae
2 provided in Table 6, Appendix A.
20.
31 Determine the conerete breakout strength Nain
: sion ofthe anchor group usin the final
ae nee hg = L-head thickness - burn off
7 50312-0125
35. Determine actual her 06 in.
38
7 s=6in
38
38 Spacing is 6 in as per statement problem, |
40 peena . f (3.07 hy) +sP
4 (8.0 9:08) + oF
22. 0521 | Determine &y
3
4 (os)
7s
46. 0.5.21 | Determine Ano
2
3
48
50. D521 | Determine the rato-of Avy
51
82
| 53.
540.52 _ | Determine basic concrete breakout stenath. The _| -
40CODE
SECTION | DESIGN PROCEDURE | CALCULATION -
7 ‘ombedment bless than Ti in. Therefore,
2 Eq, (D-7)is used to calculate the basic concrete
3 breakout strength. Also, because the embedment
4. is less than 10 in., vzis 1.0.95 assumed above.
5.
6.
7.
8 | Nominal te breakout strength N Nog = 1497415
. jominal group concrete breakout strength Neoy Tyee
4
i 0.85 * Ney = 0.85" 61.7
13, heck ductility eet
14, 0.85 * New > Ns oe esc e pe,
5
16 _
17. STEP 3: Check pullout strength of stud
18.
19,
20. Determine Nex
21, D.5.3.1 | Nps is the nominal pullout strength intension of a | Nyx = ¥eNy om
22. single anchor.
23.
24, 1.5.3.1 | Npis the pullout strength in tension ofa single | Np = AagBt (015)
25. anchor in cracked concrete.
26.
27. 0.5.3.5. | Concrete Is cracked per problem statement. We 0
28.
29. 05.3.4 | Caleuiate the bearing area. The anchor head Pog =" (1,007 -0.50"V4
30. Giameter's 1.0 in, fora 1/2'n, diameter stud 59 in?
31 ‘(Table 6, Appendix A)
32, N, 59°8*4
33 = 18.9 kips
34
35. DAS Ni (O14)
36. r
37. 8.9 kips/bot
38. 5.6 kis (4 bolts)
39.
40. ‘Check ductility 0.85 * Nyy = 0.85" 75.6
41 (0.85 * Nox > Ny = 64,3 > 51.0 kips oK
42.
43. .
44, STEP 4: Check conerete side-face blowout
45.
46. © 204hy
® ‘Check concrete side-face blowout Saiane
. side-fece blowout wil factor | _ 2 38in.
29. Ife 204 hq, side-face blowout will not bea factor | 238i
50.
51
4CODE
SECTION DESIGN PROCEDURE CALCULATION
1. STEP 5: Summary.
z T
Sven | Applied toad Nu= 28kips
:
Stop 10.45. | Design see tensile strength ess 08°51 =408kis —— contols
6
Step 210.4.5.c
8,
Step 30.4.5.
10.
Step 4
12.
B
14. D412
45.
16.
17.
18. 03.6.1
19.
20.
21
22,
Design conerete breakout strength
Design concrete pullout strength
Design concrete side face-blowout strength
Design strength of stud in tension
Duetity:
@Neag= 0.75 * 61.7 = 46.3 kips
Np 0.75 * 75.6 = 56.7 kips
(gNao= NIA
= 40.80 kips > N, = 28 kips
0K
min (0.85Naxg, 0.85Nox) > Ne
min (0.85 ° 61.7, 0.85" 75.6} > 51.0
min (52.4, 64.3)
2.4 > Nz = 81.0 kips
23. STEP
: Calculate the required plate thickness
| The plate is 8 x 8 in. as per problem statement.
‘The plate must transmit to the studs all loads used
in the design of the attachment
‘Appendix C load factors are conservative
compared with AISC
Evaluate sections a-a and b-b to determine
‘minimum load capacity
Yield of the plate material is 35 ksi
‘The plate shall be designed in accordance with the
AISC-LRFD code. The design flexural strength is
based on the limit state of yielding and is equal to
‘@oM, where, per Chapter F of AISC:
Ye =0.90
M, =M,=F,Z<1.5M,
| Evaluate pate at Section e-a
|At face of tube (aa)
[Tension in two bolts*
[Tages = 28/2 = 14.0 kins.
42CODE
secTION | DESIGN PROCEDURE CALCULATION
| la = 15+ aR2=
Moment in plate at section a-a: [Mans = Tapans®
Use the midsurface of the tube as point of fixity. = 14°16 = 224 in-kips
Nominal capacity of plate. The effective width is |M, =Z*F,
‘assumed to be equal tothe width of the A" bag
attachment plus 2t on either side. Use the plastic 34+2°05+2°05
section modulus 2. in.
Fy = 36 ksi
Assume plate thickness is 1/2 in
| Piastic moment: IM=2"F,
4? g* B+ 36
5.08
Nominal moment capacity Ms looMa = ZF y
Osrase
4050
Required thickness on Section 2-2 tensa = VEBATAOE = 0.74 in
Evaluate Section b-b:
Foree in one bolt
Applied moment:
S125 + tuagl2
25 in,
*2.25
SB in-k
‘The distance wis the distance from the comer
‘anchor to the midsurface of the tube.
43CODE
SECTION DESIGN PROCEDURE CALCULATION
i :
2
3
;
6, IZ = V4 day t?
;
8 ‘The effective width at Section b-b is assumed to [bp = 4*(3/4) in.
@
14, wt 3.0° "38
15. at
te
17, {pol o.g'27t
18. 24.30
8 lan = 7887953 =081 in. contol
7 bst« mi
2 lst inx8in, x78 in nbd pat
25.
26. “Stud material is AZOIAT0B, material properties per AWS D1.1, 2006, Table 7.1, Type B stud, yield
27. strength = 57 ksi, tensile strength = 65 ksi. It has elongation of 20% and reduction in area of 50%, meets
28. the definition of a ductile steel element given in D.1, and meets the tensile strength requirements of
28. D5.4.2and D.6.1.2: fy-$ 1.8%, (65 5 1.9 * 51.0 = 96.9 ksi)
33. iin the above example, the effective embedment length ha is taken to the face of the concrete. ifthe
34._ plate was larger than the projected surface area, then the embedment length would exclude the thickness
35. of the embedded plate.
Je." A note about prying: In this problem, ris assumed that prying does not occur, and the fores in individual
37. anchors under the applied tension force is not increased by the prying effect. Prying may exist depending
38. on the thickness of the plate, the location of the anchor, and the stiffness of the anchor. Itis assumed that
39, there is no prying in this example.BRBNAS Corson +
Example B1(c)—Four-bolt surface-mounted plate, tension only, close spacing,
close to a corner
Design an embedment with four post-installed undercut anchors and a surface-mounted plate for a3 x 3 x 3/16 in. ASOI
structural mabe attachment.
Given:
Concrete edges
= 0) = 02 12in,
Base plate
8x Bin.
‘Anchor spacing
s=6in,
Concrete material
f= 4000 psi
Anchor material (F1854 Gr 36)'
a 36 ksi
fa 58 ksi
Anchor type
‘Threaded, undercut §
Prat 1s 4
Fy = 36 ksi fs
Losd
N= 28 Kips
where N, is the applied factored external load using
load factors from Appendix C of the code.
‘Assumptions:
+ Concrete is cracked
+ g-factors are based on Condition B in D.4.5 of the code
(no supplementary reinforcement)
+ Ductile embedment design is in accordance with 0.3.6.1. —
teed
SECTONAS
CODE NY
SEOHON | DESIGN PROCEDURE CALCULATION
48._ STEP 1: Determine the required anchor diameter
7 Equation
50
51,_D.4.1.1_| Equete internal design strength @Ntothe | oN, 2 o-)
45CODE
SECTION DESIGN PROCEDURE CALCULATION
7 ‘external factored load Ny.
2 ina ductile design, the internal strength Nos
13. controlled by the sieol stength ofthe siud N,. | Ny =Ny = nA
4
5 ‘The requited stee! strength of the stud Na,
6 0.45 | multilied by @ = 0.80 fortension because the | 0.80" Naey = 28
7. ‘embedment and the steel stud is ductile and the | News = 28/0.8
8 load factors are based on Appendix C of the 35.0 kips
8 code
10.
41. D.5.1__ | Solve for the required steel area for a single Nereg = MAserocfu (0-3)
12. Stud Agereq 35.0 £47 Avena” 58
13. Aseseq = 35.014 * 58)
14, Effective: 0.15 in? required
15, Anchor diameter, area, Ace
16. | i 0.142 Use 6/8 in. diameter anchors
17. 5/8 0.226 Bae = 0.226 > 0.15 in.* OK
18,
19. 1.5.12 | Determine the nominal tensile strength N, of | Ne = nAvty (03)
2 4-518 in. diameter boits. 410.226" 58
21 = 52.4 kips
2 Note: is assumed that prying will not occur.
ee ‘See Footnote iii in Exemple B1(b).
4
25. STEP 2: Determine the minimum embedment of the anchors to prevent concrete
26. breakout failure in tension
WT. Ensure steel strengih contol:
28, D.3.6.1. | inaccordance with D.3.6.1, the design of the | 0.85Neag 2 Ne
29, tembedment will be contolied by the strength of
30. the embedment steel, Following D361, this [Nay > Ny0.85
31 {goal is met when the nominal stgol strength of | Nag 2 52.4/0.85
32. the anchor Ns is set equal to 0.85 times the Nesgreg =61.7 kips:
33. rominal strength ofthe concrete controlled
34 sirengths (Nap Np, ete). Note that 0.85 isnot a
35, @-facior.
36.
37, 052 _ | Nagis the nominal concrete breakout strength Ay
38. in tension of a group of anchors. Ne YP vNy (05)
38, Ivo
40. 052.1 | Avis the projected area ofthe failure surface for
41 the group of anchors. See Figure RD.5.1 in| Ay=[(1.5*ha) +34} "[(15*ha)+84¢]
42, ‘Commentary and the figure at the beginning of | Ay= (1.5 herr 18)°
43. this problem for guidance in calculating Ay
4a
45, Spacing ss 6 in. por problem statement
46 Edge distance c is 12 in. per problem
47 statement, Because itis not known ithe edge
48, distance affects Ay, (that i, needs to be
4 checked that ena = 1.Shg). We will assume it
50 does, and caleulate Wy and Ay for each
51 iteration
52
53__D5.2.1 | Avgls the projected area of the fallure surface (08)
46; :
CODE | DESIGN PROCEDURE | CALCULATION
SECTION
7 ‘ofa single anchor remote from edges.
2
3 Modification factors:
| 4 0.5.24 | Eccentricity effects #,, Assume no load w, =10
5 ‘eccentricity.
6 D525 | Edge effects ¥, We = [0.7 + 0.3 * (Co/(1.5* hei] (O-11)
7. D526 | Concrete cracking Ws, Concrete is cracked per | = 7.0
8 problem statement.
9. 05.27 | Vayu depends on tests. ean = 1.ShelCae. nO | Yoon = 1.0
86 | tests are done then, ce =2.5 "ha. if
reinforcement is included to control spiting or if
analysis indicates cracking at service loads,
then Way is taken as 1.0. In this problem, we
will assume adequate reinforcing exists 10
preclude splitting. Therefore, use Wepyi= 1.0.
19. 0.5.22 | Neis the basic concrete breakout strength in
D.5.25. | Determine edge effect factor Y, Y
7 + 03" Lenufl1.5* hel} (D-11)
7 +037 [120.5°9)) |
7+0.26
37
1.5.2.2 | Basic concrete breakout strength Ny = 1.52{he)!*
1.529)"
= 41.0 kips
20. tension of a single anchor in cracked concrete. (O7)
2 Assume the embedment will be less than 11 in.,
22. and use Eq, (D-7). Use k = 24 for this undercut
23. post.installed anchor, For post-installed = 24" 4000" Sha! ®
24, anchors, k values may be increased up to 24 = 1.52he*
25. provided that product-specific testing is done in
26. accordance to D.3.3.
27.
28. Use iteration on her until Nesp is equal to or
29, greater than Neegq-
30.
31 First iteration First iteration
32, Try her = in, - same embedment used in he = 90.
3. Example B1(b).
34.
38. Determine Ay for the comer location. Note that | Ay = (1.5 ha + 18)%
36. | the embedment dimensions are symmetric and (1.5"9+ 18)
37. that itis located near 3 corner. Ay =992.3in#
38.
39, 0.5.2.1 | Determine Axo thy? (0-6)
| 40. <9
4a 29 in?
42.
7 D.5.2.1 | Determine the ratio of Aw/Ane. AalAo = 992.41729 = 1.36
4,
45.
46,
47.
48,
49.
50.
51
52,
53.
54.
47CODE
section | DESIGN PROCEDURE CALCULATION
7
2. 0.5.2 | Nominal group concrete breakout strength Nery (05)
3.
4 Because Nesjis less than Naga the effective | Nog = 1.36°1.0°0.97"1.071.0°41.0
5 ‘embedment depth needs to be increased, Nig =54.1 kips <61.7 kips (No good)
}7 Second iteration ‘Second iteration
8 Try har = 16 in, he =16in.
8
10. D.5.2.1 | Determine Ay, for the comer location, Ay = (1S e+ 18)?
u G5 "6 +18)
12 Ay = 1764 in?
13, |
14. D821 | Determine Ave Ao 297 he 05)
18, erie?
16. = 2304 in?
17. 1.5.2.1 | Determine the ratio of Av/Ave
18 Ado = 176412304 = 0.77
19.
20. 0.5.2.6 | Determine edge effect factor #2 Vz £07403" fenil(1.5* he) (0-11)
21 0.7+0.3" [12i(1.5* 18)]
22, = 0.85
23.
28 Yeon 21
2.
26. 0.5.2.2 | Basic concrete breakout strength, Ny = 1.52the)"S
27. 52(16)'*
28.
29,
30. D521 | Nominal group concrete breakout strength Ney | Nay = (05)
31 | Ivo
32, |
3 Neyo # 0.76 * 1.0" 0.85 1.0° 1.07973
3%. Newg = 62.9 kips = 61.7 ki
7 0 ps ips
7 Ok for ductility
39 Use 5i8 in. diameter anchor, with 16 in.
40. embedment depth.
4
42 Check strength @ Neg = 0.75" 62.9
43. = 47.2 > 28 kips OK
44,
45. STEP 3: Check pullout strength of anchor
4.
47 Ensure steel fallure:
48, 0.3.6.1 | To prevent concrete breakout failure in tension | 0.85Npa 2 Ne
49. the design concrete breakout tensile strength,
50. {OANea, Has to be greator than or equal tothe | 0.85 Nay = Ny
5 ‘nominal tensile strength of the embedment
52, 0.3.6.1. | stee!N.. To satisfy the ductility requirements of | No. = Nv0.85
53. 1.3.6.7, the design pullout strength shall be [Ne = 13.10.85 _
48CODE
| SECTION DESIGN PROCEDURE CALCULATION
7 Taken a5 0.85 limes the nominal strength.
2 Nowa 15.4 kips for single anchor
3 Determine Nyx
4. [Noa fs the nominal pullout strength in tension of
5. a'single anchor.
6 DS31
7. For post-installed expansion and undercut
B ‘anchors, the values of Np shall be based on the
8 D532 | 5% fractile of tests performed and evaluated
10. according to D.3.3. tis not permissible to |
" calculate the pullout strength in tension for such |
12, anchors. Therefore, testing for this specific
13 anchor needs to show a result greater than
14. Nonrog OF the testing needs to show that pullout
15, does not occur at all
16, |
7.
Bo _
49. STEP 4: Check concrete side-face blowout
20.
21. D.54.1_ | Check concrete side-face blowout, > 0.4hy
22 0.4 “16 = 64 in.
23,
24 c=12>64 OK.
25, 7
26. STEPS: Summary
2
28. Given | Applied load Ny = 28 kips
29.
Step!/D.4.5.a | Design steel tensile strength ON, =0.87524= 41.9 kips
31
Stop2/D.4.8.¢ | Design concrete breakout strength @Nexg = 0.75" 62.9 = 47.1 kips
33. |
Step 3D.4.8.¢ | Design conerete pullout strength(testing) @Noq = Check with manufacturer
35.
36. Step4 | Design concrete side face-blowout strength | @Nw» = N/A
37
38, D.4.1.2 | Design strength of stud in tension GN, = min (gN., @Neos)
39, in (41.9, 47.1)
40. H.9kips>N, =28kips OK.
an.
42, 0.3.6.1 | Ductiity O.B5Negs 2 Ne
43, 0.85 “62.92 52.4 kips
44, 535 >524 kips OK.
45,
46. Plate design: same as Example B1(b)
47.
48
‘49, Anchor material s ASTM F1554 Gr 36, [thas elongation of 23% and reduction im area of 2 in. and mevis the
'50._defintion of a ductile steel clement given in D.1 (f= 58 ksi< L.9f, = 1.9 * 36= 64 ksi, z
49Example B2(a)-Four-stud embedded plate, combined shear and uniaxial moment
Design an embedment using welded studs and an embedded piate for a 3 x 3 x 1/4 in, A501 structural tube
attachment.
Giver:
Concrete edges
Concrete material
e ‘4000 psi
Stud material A108: 7
4 51 ksi
Qs 6 ksi ir
Plate:
Fo = 36ksi
Loads:
My 70 in-kips 2
Ve 12.4 kips.
‘where M,, and V, are the applied factored extemal loads
as defined in Appendix C of the code.
Note that the loads in this example have been selected to
provide an example in which the anchors in tension must
also camry shear,
‘Assumptions
‘© Concrete is cracked
‘+ p-faclors are based on Condition B in D.4.5
of the code
(no supplementary reinforcement)
ANCHORS.
IN TENSION
50CODE
SECTION
DESIGN PROCEDURE.
CALCULATION
1.
STEP 1: Di
jetermine required steel area of the studs
43
49.
AIsc
‘Chapter F
DAL
DS.12
Das
BASE PLATE
Determine the plate size and thickness and anchor
bolt size for moment
‘Assume a 1/2 in. thick, 7x 7 in. plate
Stud spacing, $= 5 in. is given.
Assume the center of compression force resultant
is at a distance d,~ 2¢ away from the outer edge
of the supported member, the structural tube.
‘The center of the tension force is at the center of
the anchors in tension.
Derertine the lever arm d betveen the eenter
‘of compression and tension forces.
‘Calculate the tension in the anchors.
Design the plate using the AISC LRFD Code.*
Use the plastic moment M, to define the nominal
strength ofthe plate in bending, and use p= 0.9 in
accordance with the AISC Code. Assume thatthe
| full width of the base plate is effective.
‘Strength of steel plate is greater than the applied
ultimate moment, but elose tothe limit
Use 5/8 in, plate,
ANCHORS
‘Tension:
Determine the required stud area A. for tension.
Assume ductile design and use the corresponding
factor in accordance with D4.5. @= 0.8 for tension
load
From Appendix A, Table 2:
Effective area
Anchor (gross area for stud) in?
diameter,
in,
38 O10
2 0.196
SIS 0307
51
It dt de
0+30+10=50
d= 14.0" 1.0= 140in-k
b= FZ
9F,2
14 (7) 0.5)= 0.44 in?
eMy= 0.9(36)(0.48)
= 14.3 > Myi=14 kein, OK
Use plate, 7 x7 x 5/8 in. thick plate
ly = ON
OPA‘CODE
SECTION
DESIGN PROCEDURE
CALCULATION
47, 061
Shear:
Shear forces in anchors:
From the figure on the right the forces in each
anchor group and force due to friction can be
calculated
From above, C and T are already calculated
Determine friction force Vis
Shear strength
‘Because this is an embedded base plate, shear
strength may be calculated using either direct
shear or shear friction; however, only the direct
shear option will be shown herein.”
Using the steel! area Aye determined from
‘tension above, calculate the available shear
strength of the anchors.
Shear strength using direct shear
and friction from compression
‘A. Assume all four anchors resist shear
{Concrete breakout strength needs to be
checked; see Step 3)
Strength of front and back anchors, Vay and Vao!
Total strength of front and back anchors:
Strength-reduction factor:
Design strength of anchors at Line 1, V33 and
Line 2, Vy: (Note: strenath is based on fy, not
STE OOB* 2" 65)
Reese = 0.135 in?
Use 4-1/2 in. diameter studs.
Bs + Aseioor = 0.196 in? OK
a
=14.0kips
4C=
4°14 = 5.6 kips
Bao = Bors Beet
Aer ® Rua
1Aaa= 2 * 0.196 = 0.392 in?
Ver =Viz= Asef
+ 0,196 * 65 = 25.5 kips
V, =2725.5=51.0kips
(0-18)
52‘CODE ;
SECTION DESIGN PROCEDURE i CALCULATION
1 a) @ 20
2 ‘Total design steel strength of four anchors
3 Ves = PVqg= 0.75" 25.5= 19.1 kips
4
5.
6 ‘Additional shear strength is provided from QV, =2° 19.4
7 friction on the compression side of the
8. D45c | plate. @ is taken as 0.75 from Condition B, = 38.2 kips
9
10. Vy =04C=0.4* 14> 5.8 kips
it
12 Vr =0.75°5.6 = 42kips
13, 6.14 | Design shear strength of the connection,
14 four anchors plus frictional resistance:
15,
18 Note: tis prudent to ignore the shear strength
17. provided by frictional resistance, especially fora | QV; + Vn = 38.2+4.2
18 new design. Itis included herein, however, 0 =424kios > 12.4 kips OK
19. illustrate the procedure as the code permits it It
20. is best utlized to avoid rework if shear demand
21 increases later due to a reanalysis or retrofit
22,
23
24,
2B B. Assume all shear taken by back two anchors
26, (Cine 2 in figure). Frition will not be included
21
28. Design strength of anchors @V,2 at Line 2:
29 Vea = 19.1 Kips
30,
31
32. Vaz > Vu = 12.4 kips: OK
33
34.) STEP 2: Determine required embedment length for the studs to prevent concrete breakout failure
35, in tension
36
37
38. D541 Calculate the stee! strength of anchors in Asai
39. | tension, Only anchors on Lino 2 resist tension, (0°196)(05)
40, = 25.5 ips
4
42
43. 0.5.22 | Caleulate the required concrete breakout Ny = 0.85Nag,
44. D.3.6.1 _| strength of anchors in tension to ensure that
45 embedment is ductile, Nereg = 25:510,85 = 29.9 kips
46.
47. Conerete breakout strength fora group of Ay
48 anchors: Nag SEF # YF yr (D5)
49 vo
50, Try 55518 in. long Nelson stud
51
|52. 0.5.2.1 | Calculate Aye, Note that because the failure
53 surface extends to the top ofthe concrete, the
5a. thickness of the plate is added to the anchor a
53CODE ;
SECTION DESIGN eRe ener CALCULATION
i Teng
2
3 he = 5.625 + tase -burn off (See Table 6) | Ano = She” (D-6)
4 5.625 + 6625 -0.125
§, = 6.125 in, = 9° (6.125)*
é
i Calculate Ay There are no edge effects, = 337.6 in?
a | because 1.5" 6.125=92in.
27 |
B Concrete breakout strength for group 52(6.125)"
9,
30, eee
» 23.0 kins
32 521 :
i Nag= SEM Money
34 Embedment is ductile in tonsion Appaaaitas
35. Strength contolled by steel. This satisfies the
26. shear retin requlement from Stop 1 1a (1oyt.oy.oz3.0
on 29.9 Kips 2 Nesgsen™ 29.9 kips OK
i Use 4-1/2 in, diameter x 5-5/8 in. long
oo ‘anchors at 5 in. spacing
41
22
ra e a
44. STEP 3 : Check pullout strength of anchor
45.
46. 053 | Calculate the pullout strength of the anchor in
a7 tension in accordance with D523. Design| Nyy = WN
48, 0.5.24 | embedment as ductile in accordance wih (O14
49 036.1
50. Ne = AngBle
51 (0.45)
52 = B74 Bay
52, 0.5.2.5 | Concreteis cracked per problem statement £32 Ag
54
54CODE
SECTION
DESIGN PROCEDURE
CALCULATION
Calculate the bearing area. From
manufacturer data, anchor head diameter is
1.0in, for a 1/2 in. diameter stud (See Table
6 in Appendix A).
Pullout strength to maintain ductile design in
accordance with D.3.6.1
Ws
Ay =nt (1.0? 0.584
59 in?
No =1732°0.59
= 18.9 kips:
0.85 N=
25" 18.9
= 16.1 kips each anchor
= @D22kpstertwoancas
1/2.in, diameter studs are OK for pullout
Cheek concrete side-face blowout
Check anchors closest to the edge for side-face
blowout,
61> O.4hes
1Bin, > 0.4" 6.125 = 2.45 in
| Side-ace blowout Ns need not be
checked.
55STEP 5: Check concrete breakout failure in shear
‘To determine the critical concrete breakout strength, three modes of failure would be considered. They are shown
‘below. The frst mode places the failure cone at the front anchors, and a strength check is made against 1/2 of the
applied shear V,, The second mode considers the filure cone initiating atthe back anchors, and a strength check is
‘made against the total shear V,. The final mode is a conservative check, which assumes that all of the shear is acting at
the front anchors. This check might be considered if significantly oversized holes are used as in a column base plate
Per the note on Fig. RD.6.2.1(b) of the Commentary, the only check that is required for this problem is Mode 2,
1,
12,
13,
14
36.
16,
17.
18
19.
20.
21
22
23.
24.
25.
27.
28.
2
30
31
33,
34.
36.
37.
38,
a
42
43
45,
46.
47
48,
43.
50.
51
52
26.
32.
35.
because the studs are welded to the anchor plate.
Mode
230,
Mode 2
(Only che
required —
wolded st
SECTION A-A
®
Mode 3
SECTION A-A
53.
t
cr OVeigt = gVey Vu
25.1 kps18.1 Kips" 82 kps™
©) 0.8BVeag2
Zin. 2e5epe
Vea Vo
285kips 82 kips*
* from page 3
~ shwarto be sisted © 12.4-4.2= 82kips, pages
56SELSRESSASSBLRAS ARIS BRU BREN SS SaaRassS
9
D625
D626
D627
D623
D361
bas
p21
| Determine concrete breakout strength using
Mode 2.
For a plate with welded studs Mode 2 can be
used to calculate the concrete breakout
strength, Therefore c\=18 + 5 = 23 in. The
failure cone passes through the bottom of the
slab, 50 the A, equation uses the full slab
thickness (h = 18 in, < 23 in.)
Modification factors:
Eccentricity on Anchor group ‘Ps
Second edge effect Ye
Assumed cracked
Note: by definition, £ is limited to Bd,= 4 in
Nominal concrete breakout strength:
‘Check ductility, two anchors on Line 2:
Check for strengti
‘Strength-reduetion factor:
Design group concrete breakout strength:
(D2)
A, = (3c*s)(h)
= (3 * 23+ §)(18)=1332 in?
Ae 4.5 014.5 * 23722981 in?
22)
AlBvo 0.56
0 No eccentricity
0 c> 1.5;
0
£) ere
fe) oss eos61209*
= 59.8 kips
Veoge = 0.86°1.0°7.0°1.0°59.8
= 33.5 kips
0.85Vesge = 0.85 * 33.5
Mode.
ductile
e | =075
Ven = 0.75 * 33.5
OK for strength
(o-
(0-26)
(0-24)
= 2B.5 > Vg= 25.5 kips
28.1 > Vy= 8.2 kips
2
STEP 6
“Check group pryout
D63
Concrete pryout of the anchors in shear must be
checked
Two anchors :
Vero Kep * Nevo
Key =2 forhy> 2.5 in.
| Nesot 29.9 kips
(029)
87Veg? 2* 29.9 = 59.8 kips
0.85 * Vesg = 0.85 * 59.8 = 50.8 > 25.5 kips
Ductile
7. STEP 7: Summary
=
9 Sit 5
10 Diameter d= 1/2 in 2
ML Length L= 5-58 in 2
12. Effective depth hy = 6.13 in. ee
5 Base plate thickness, €= 5/8 in 8
ia ‘Anchors are ductile 8
15. TENSION j
16. a
n Applied oad
18. Step |
pase [Seeee oe a
2 ase | meme imsom ens ee ee eae
3 pase |Cumnmuentennet tga ee ike
Bose | Omens sown seat @Noy 90.75" 2" 18.9 = 28.4 Kips
2 sa) Besitn stent fst nsion €1> O.thy so this isnot applicable
28 :
{Ny = min (ON, Noy, Nan)
x SHEAR: Mode 2 (frictional resistance counted) Oe a eT
32. Applied load, 12.4 — 4.2 = 8.2 kips, page 6, i lis 2 Nesta RS Oe
33. Sup
34 Steel strength Se
Step 1/D.4.5.a eeeaeeante
36 ase | otis conte eV, £075°255 = 19:1 Kips
2 pase |Cmmroasecah g¥og2 0.75 *98.5 © 25.1 tps
4 gag | Dsltastentsud dew (9Vagg" 0.75" 59.8 = 44.9 Kips
2 Vn = in (OV, Ven @Yean)
43. min (19.1, 25.1, 44.9)
: =19.1kips>Vj=82kips OK
46. STEP 8: Check for tension-shear interaction
a7
48
49. 0.7.3 | Anchors subject to combined shear and tension (030)
50, forces must meet the tension-shear interaction
51 requirements of 0.7
52
53. Mode 2;
54.
589
Design strength in shear:
Vy > 0.2" design shear strength interaction | @V,
check is required
9.1 Kips step 3
2719.4
(0.2)9Ve5
8 <8.2kips
14/20.4 + 8.2119.1 = 0.69 + 0.43
112<1.2
oK
If the frictional resistance was ignored, then
the aforementioned interaction equation
becomes 14/20.4 + 12.4/19.1 = 0.69 + 0.65
= 134> 1.2
and the anchors have to be redesigned.
Mode 3 assumption:
An alternate assumption is that all of the shear
Is taken by only the anchors on the
compression side. With this assumption, there
‘sno interaction check because the anchors in
tension are not in shear and the anchors in
shear are not in tension, This approach,
however, requires that Mode 3 failure for the
‘concrete shear breakout strength (Step 5) be
checked. Mode 3 will have lower concrete
breakout strength, and is more likely to lead to a
nonductile design.
* Shud material is AIOE, material properties per AWS DI1, 2000, Table 7.1, Type B stad, yield strengih = 51,000 psi,
tensile strength = 65,000 psi, It has elongation of 20% and reduction in area of 50%, meets the definition of @ ductile
steel element given in D.1, and meets the tensile strongth requirements of D.5.1.2 and D.6.1.2: fy 1.9f, (65.5 1.9
51 = 96.9 ksi. ie
Notes on steel designs ‘The plate will be designed using the AISC-LRFD code (American Insitute of Stes!
Construction, 1999, “Load Resistance Factor Design for Structural Steel Buildings,” AISC, Chicago, I). In
applying ito this example, some conservative simplifying assumptions will be made:
18) Loads: This example assumes thatthe loads are the same as used in the previous editions of the ACI and therefore
‘we used the Appendix C g-factors, The AISC Code uses the ASCE 7 (Ref. xx) load factors, and the strength
reduction factors are determined accordingly. The loads used in this example are therefore conservative, and wil be
‘used with the LRFD design
b) Strength-reduction factors: The strength-reduction factors will be those ofthe AISC-LRFD Code (@ —0.9 for
bending)
) Strength design: The nominal strength of a section in bending in the LRFD Code is based on a plastic section
modulus Z and yield strength F, of the steel material (M,= My= ZF). This approach will be followed inthis
example _
D.4.3 of the code requires the resistance to combined tensile and shear loads to be considered i design. In his
problem, the tensile load on some ofthe anchors comes fiom the moment, The moment is assumed to be a result of
the shear acting some distance from the face ofthe base plate. The anchorage, therefore, has no net externally
applied tension force. Tlie tension results in an equal and selfequilibrating compression force. The code is not clear
if the tension shear interaction equation isto be applied on an anchor-by-anchor basis or on the entire base plate
‘Also, because Appendix D permits shear to be resisted by direct shear through individual anchors or by sheat
friction, either approach could be used; however, only the direct shear procedure is shawn in this example problem.
59WOVEMAAN—
44
42
Example B2(b)-Four-anchor surface-mounted plate, combined shear and uniaxial moment
Design an embedment using cast-n-place anchors and a flexible surface-mounted plate for a 3 x 3 x 1/4 in.
‘A501 structural tube attachment
Given:
Concrete edges
Concrete material }
fe ‘4000 psi {
Rod material F1554 Gr.105!
= 105 ksi
fe 120 ksi
Plate
Fo = 36 ksi
Loads
My 70 in-kips
Ve 12.4 kips
‘Where M,, and V, are the applied factored external loads
using load factors as defined in Appendix C of the cose.
‘See introduction for commentary on the distribution of
stresses to the anchors for this problem,
Assumptions:
* Concrete is cracked
‘+ g-factors are based on Condition B in D.4.5 of the code
(no supplementary reinforcement)
Mu
“>
SECTION A-A
60
1.5hel_1.Shet
PLAN
ANCHORS
IN TENSIONCODE
SECTION
DESIGN PROCEDURE
CALCULATION
concrete due to the compressive reactio
1. STEP 1: Determine required steel area of the rod
2
3 | try 7x7 in. plate with 5 x 5 in. rod spacing.
: |
5 Calculate the tension force in the anchors and |
6 compression reaction force in the concrete
7 from the applied forces.
8
2 Kosh
10, Assume, conservatively, that the center of
1 compression force resultant is at the outer (oles fe
12 ‘edge of the supported member, the structural
13, tube. (Alternately, ican be assumed that the
14 center of the compression force is at a
15, distance of 2 from the outer edge of the tube
16, as used in Example B2(a). This, however,
147) requires the designer to estimate plate
18 thickness and later verify that the thickness is)
19. no less than that assumed). The center of the
20, tensile foree is at the center of the anchors in
21 tension,
22. Determine the required rod area Az. for
23, tension. Assume ductile design and use the
24. ‘corresponding (factor in accordance with | Ne
2. 0512 | DAs.
28. 045
27. Try 1/2 in. diameter rods. Gross cross-
28. sectional area is 0,196 in* Tensile stress
29, ‘area is 0.142 in (see Table 2, Appendix A) | Nu Ne
30. Asa
31 Anchor Effective area Ase, ® 80
32, diameter, in a anchors,
33, fu = 120ksi
34, 38 0078
35, 12 0.142 Aroueg = Ne‘@nh
36. 58 0.228 17.5i(0.80 *2* 120)
37 = 0,091 in?
38
39. Use 1/2 in. diameter rods
40.
a | Acaigee = 0.142> 0.091 In?
42. | OK
43,
44,
45, 2
46.
47. D.6.1.2 | Because this is a surface-mounted plate, only
48, direct shear D.6.1.2 is applicable.
49.
50. 0.6.1.4 | The nominal shear strength is the sum of the | Shear resistance
51 shear strength provided by the anchors and Vet Vs
52, the friction force between the base plate and 20.60 Asef * 0.400
61CODE 4)
SECTION DESIGN PROCEDURE CALCULATION
7 Taken a5 04G, Assume threads in shear
2 plane.
3
4 Shear strength of four anchors SOMA
5. 674°0.142" 120
8 0.9 Kips
7.
8 ‘Strength-reduetion factor 9=075
9
10. Design strength of four anchors | ov. = 0.75*40.9= 30.68 hips
"1
42. 0.6.1.4 | Adkdtional shear strength provided by fiction | Vy =0.40C = 0.40T
13 between the base plate and concrete 0.40 (17.5),
14 = 7 kos
15, (See note in Step 1 of Example B2{a) about
16. the prudency of considering the shear
"7 strength from fictional resistance)
18
19. D.Sc | Strength-reduction factor
20
21 Design strength provided by fiction 5.25 kips
22
B Design shear strength ofthe connection Vs + @ Vo = 30.68 + 5.25 = 35.99 kips
24 {four anchors and fictional resistance) > 124 kips
25 OK
26
21
28, get
29. STEP2: Design base plate"
30
31
32
33
34
35, AISC LRFD | Nominal flexural strength of base plate, per
36. Chapter F | AISC LRFD Code, is, My Mp=FyZ. The
37 tension in the anchors based on the applied
38 ‘moment, and is not based on the fll tensile
39 | capacity of the anchor
40, |
4 |
a2
43. D @
44, Men = Td
45 = (17.5)(1.0)
46. = 175 in-kips
47, AISCLRFD
48. Chapter F
49 “The wp factor for flexure py is 0.90 OM= OFZ
50. QF {br M4) =0.9 (36)(7)64
51 6.7
52
53. Required plate thickness per AISC: 56.7" _=17.5
62CODE
SECTION
DESIGN PROCEDURE
CALCULATION
t = 055i,
Use 7" X7" X 5/8" plate
breakout failure
Dst
13, 0361
po
31 Ds24
32, DS.2.5
33, 05.26
34. 0527
37. 05.22
Calculate design tension on anchors
assuming two studs resist tensile loads.
7
2
3
4 =
5S. STEP 3: Determine required embedment length for the studs to prevent concrete
6.
7
8
9.
Galculate the concrete breakout strength of
anchors in tension so that embedment is,
ductile,
Concrete breakout strength for a group of
anchors
Try 1/2 in. diameter headed rod with 8-1/2 in
effective length hy,
Modification factors are all 1.0 for
Eccentricity effects
Edge effects V2
Concrete cracking Ys
Without spiiting reinforcement eax.
Basic concrete breakout strength Na of a
single anchor in tension in cracked concrete,
k = 24 for cast-in anchors
Concrete breakout strength for group.
N, = MA sed
(03)
=2"0.142* 120
= 34.1 kips
Ne =0.85Ney
Neon rat 34,100.85 = 42.6 Kips,
4,
Neva? Sees (05)
Ao = they? co)
=9° 85
= 850 in?
Au =(274.8*85 +5(2"1.5°85)
=778 in?
Ayn = 7781650
= 1.20
(0-8)
= 24 (4000)"*(h)">
= 1918(hy)"* Ibs
= 152° 8.5"* kips
= 37.6 kips
63CODE
SECTION
DESIGN PROCEDURE
CALCULATION
Nesp Ay YPN,
Ane aa
Neg = 1.207 1.0" 1.07 1.0" 37.6
= 45.1 > 42.6 kips
OK
‘Therefore, embedment is ductile
Strength controlled by steel
Use 4 -1/2 in, diameter anchors with 8-
1/2 in, embedment depth at 5 in. spacing
Check pullout strength of anchor
bss
DS35
Caleulate the pullout strength of the anchor in
tension in accordance with D.8.3. Desig
embedment as ductile in accordance with
B61
Conerete is cracked per problem statement.
= 10
Calculate the bearing area. Assume heavy
hex head for the rod. Appendix A, for 1/2 in
diameter rod, F = 7/8 in,, C = 1.0 in
(3F*/2)tang0°
(3 0.875%/2\(0.577) = 0.663 in?
0.5" /4= 0.196 in?
Arent
reo
Aes
Pullout capacity for two anchors
Determine required bearing area
Try a hardened washer, with diameter D.
(Table 5 SAE hardened washer)
Ae = Atest = Mae
0.663 - 0.198,
=0.47 in? -see also Table 4(c)
Ny =1792"0.47
15.0 kips each anchor
O.85Njn= 0.85" 2" 15.0
=25.5 O4hy 084.
21. 054 | face blowout Bin, > 0.4(6.128) = 2.45 in.
22, Side-face blowout Nay need not be
2. checked
Poa af
25. STEP 6: Check concrete shear breakout
65CODE. ,_| DESIGN PROCEDURE CALCULATION
SECTION
1. _ To determine the ertical concrete breakout strength, three modes of failure should be considered.
2. They are shown below. The first mode places the failure cone at the front anchors, and a strength check
3, is made against 1/2 of the applied shear V,.. The second mode considers the failure cone initiating at
4. the back anchors, and a strength check fs made against the total shear V,,. The final mode is &
5. conservative check, which assumes that all of the shear is acting at the front anchors. This check might
6. be considered if significantly oversized holes are used as in a column base plate.
7,
8.
9.
10.
1
ee
oa ee
tiie aw
SEGTIONAA
* Shest to be resisted = 12.45.25 = 7.15 kips
Each row resists, 0.5° 7.15 =3.6 kips
Concrete Steel Anpiied
breakout strength Toad
©, 0.850Vinge Ver @Ve2 Vur_Vu
asecheseae: hescreesahscck:
2 49 205 154 38 38
Mode 2
[eee :
| 4 Caan DUCTILE -OK fer strength, see pages 7& 8
‘SECTIONAA
: * see note above
an Const Stoo! pes
ee bral evength read
| wet © 0.85Vaags Ver OVe2 Mua
in, kK KKK
1B 224 205 154 720
43, Mode 3
DUCTILE - OK for Strength
SEGTIONAA
49. 0.62 | Mode 1:
50. Because the plate is not rigidly connected to
51 the anchor, check the anchors nearest to the
52 edge using 1/2 the applied shear.
66CODE
SECTION
DESIGN PROCEDURE
CALCULATION
poo
32
33. 062
36.
36.
37
38.
36,
| 40.
41
42
43
44. D625
45,
46. D626
47.
48, D627
49,
50.
51
52
53,
54,
Therefore, o=18.
Note that the depth of A, is limited by h.
Eccentricity on anchor group W's
‘Second edge effect Ys
Second edge effect 7 assumed cracked
| Note: by definition, ¢ is limited to Bd,= 4 in,
Duetlty check
From Step 1 V,= 40.912 = 20.5 kips
(two anchors)
strength
Mode 2:
Nox, check against failure at the back
anchors under the full shear.
Therefore, = 23. Note that the depth of A,
is limited by h
Eccentricity on anchor group Ys
Second edge effect Ye
Second edge effect ¥; assumed cracked
Noto: by definition, ¢ is limited to 8d = 4 in.
A, = (Beyts)(h)
= (3° 18 +5)(18)
An 45 c2= 4.5°18? = 1458 in? (0-22)
= 1062 in?
Alyy 1062/1458=0.73
Ws= 1.0 No eccentricity
We= 1.0 c2> 1.5c;
{D-26)
ws1.0
n=(2) Velie 02
n)
(ci) S03 00008"'*
V, =36.2kips
Figg =0.73(1.0)(1.0}(1.0)(36.2)
Veog = 26.4 Kips
0.88 Ving=0.85(26.4)
224 > V, =20.5 kips
Ductile, OK
@ Vy = 0.75 * 20.5 = 15.40 kips
(0-21)
Aupyyy,
A
Ser+s)(h)
(3* 23 + 5)(18) = 1332 in?
Ag= 4S c;2= 45°29 = 2381 In? (0-22)
AL A= 0.58
52 1.0 No eccentrciy
67CODE
SECTION DESIGN PROCEDURE : CALCULATION
T T
2 | Wee 1.0 c> 1.51
3 (0-28)
4
5. = 1.0
8
7 on
: a) ENR (08)
10. .
1
12
13, ae
14 v,=14) Josvaoo3)
15 's (4) '.5-+/4000(23)'
16.
7 i
| 18. Ductility check Vy =82.3 kips
18.
20, From Step 1, V, = 40.9/2 = 20.5 kips 4g =0.56(1.0X1.090.03(523)
21 {two anchors)
22. Veog = 29.2 Kips.
23 lees = 23.2 Kips
24 Strength 9 Vang? 0.75 * 29.2 = 21.9 kips
26, Note to reader: See Problem B2(a) for | 0,85Va=0.85(29.2)
27 discussion of the assumptions regarding 324.9 > V,= 20.5 Kips
28. the distribution of shear stresses in the
7 steel anchors in a Mode 2 failure. Ductile, OK
3 Mode 3 assumption: | = 0.75 * 20.5 = 15.40 kips
32 An alternate assumption is that all ofthe
33 shear is taken by only the anchors on the
34 compression side. With this assumption,
35, there is no interaction check because the
36. anchors in tension are not in shear and the
37, ‘anchors in shear are notin tension. This
38. approach, however, requires that Made 3
39. failure for the concrete shear breakout
40. strength (Stop 3) be checked. Mode 3 will
41 have lower conerete breakout strength and is
2 more ikely to lead to a nonductil design,
43 although inthis particular example, itis
44 duet.
45
46, 2
47._ STEP 7: Check group pryout
48.
49. 0.6.3 | Concrete pryoutof the anchors in shear must | Vers = (0-29)
50, be chacked: Mode 1 is checked herein, Mode
51 2 can be similarly checked kop #2 forhy> 28in.
52
53. (Note: The code states that Nex is taken from | New = 45.1 Kips
68CODE
SECTION
DESIGN PROCEDURE
CALCULATION
Eq. (D5))
ve
= 2745.1 = 90.2 kips
78*90.2
7.7 kips > 12.4 kips
OK
__ STEP 8: Summary
22. Step 1
23.
Step 3/0.4.5.a
25.
Step 30.4.5.¢
27
Stop 410.4.5.6
29.
Step 5/0.4.5.¢
31
32. 04.1.2
33,
34,
35,
36.
37. D442
38.
39,
40,
a
Step 1045.0
43.
Step 60.4.5
45.
Step 710.4.5.6
46.
47.
48,
49,
50,
51
52.
53,
Rod diameter dy= 1/2 in.
Plate thickness t = 5/8 in
Effective length h = 8-1/2 in,
TENSION
Applied load
Stee! strength
Conerete breakout strength
Conerete pullout stength
Conerete side-face blowout strength
Design strength of stud, tension
SHEAR - Mode 2
(frictional resistance considered)
Applied load
Steel strength, wo anchors
Concrete breakout strength
Conerete pryout strength
Design strength of stud, shear
6g
fase
Ny =17.5 kips (trom applied moment)
@N, = 0.80" 34.1 = 27.3 ips
Neg 0.75 * 45.1 = 33.8 Kips
Np) =0.75 * 58.9 41.9 Kips
12 O.4hy- $0 this is Not Applicable
Oa = min(ONs. ON: ON)
= min(27.3, 338, 41.9)
= 27.3 kips > Ny= 17.5 kips
0K
Vy 2124-5252 72kips
Ve =0.75" 205) = 15.40 kips
(eq = 0.75 "29.2 = 21.9 kips
WVogq =0.75* 90.25 67.7 kips
Wn = min (PV, WVeay WV)
= min (15.4, 21.8, 67.7)
= 15.4 kips > V,=7.2 KipsCODE
SECTION | DESIGN PROCEDURE CALCULATION
OK
Check for tension-shear interaction
‘Tension-shear interaction, Mode 2 17.5127.3+7.215.4=1.11<1.2 OK
"ASTM F 1554-00 specification, Grade 105, Class TA, rod material will be used. Rod identification is (AB105)
witha tensile strength inthe range of 125 to 150 ksi, and minimum yield strength of 105 ksi for 4 to 3 in.
diameters. Reduetions in area requirements vary. For anchor diameters in, elongation in 2 i. is 15%,
reduction in atea is 45%, and meets the definition ofa ductile steel clement given in D.1, Also, max fy 1.4 fy
‘According to D.6.1.2, fy shall be $ 1.9 fy or 125, 000 psi. See also Table 1 for other material,
* Notes on steel design: The plate will be designed using the AISC-LRFD code (American Institute of Steel
Construction, 1999, “Load and Resistance Factor Design for Sicuctual Stee] Buildings,” AISE, Chicago, It. In
applying ito this example, some conservative simplifying assumptions will be made:
Loads: This example assumes that the load combinations are the same as used in the previous editions of the ACL
‘and therefore we used the Appendix C factors. The AISC-LRFD code uses the ASCE 7 load factors, and the
strength-reduction factors are determined accordingly. The loads used in this example are therefore conservative,
‘and will be used with the LRFD design
Strength-reduetion factors: The strength-reduction factors will be those of the AISC-LRFD code (p~0.9 for
bending).
Strength design: ‘The nominal strength ofa section in bending in the LRFD code is based on a plastic section
modulus Z and yield strength F, of the steel material (M,= My ZF,). This approach will be used inthis
example.
AISC recommends oversizing holes for base plates. The fortheoming ATSC Design Guide will contain the
following table for recommended rod hole size. In cases like this, iis possible to have the anchors closest to the
530. edge make contact withthe base plate before the back anchors contact. The resulting breakout cone shown in
31. Mode 3 would need to be evaluated,
70CODE
SECTION
DESIGN PROCEDURE, CALCULATION
Maximum Permitted Nominal
‘Anchor Rod Hole Dimensions"®,
Anchor Rod Lu
Diameter, d, Shear Holes | Normat Holes
in (diameter) | (diameter)
42 58 146
518 1316 436
314 1816 1516
718 1116. 196
1 114 11346
144 19116 246
1412 11346 25N6
1314 216 234
22 yt5/16 yh 114
° The upper tolerance on tabulated nominal dimensions shall
not exceed 1/164,
"The slight conical hole that naturally resuls from punching
‘operations with properly matched punches and dies is
acceptabie
71@eryOMReNa
Example B3—Four-threaded anchors and surface-mounted plate, combined axial, moment and
shear load
Design a group of four threaded headed anchors to resist seismic loads given below. The supported member is
a W10x15 stub column. Design parameters are provided as follows.
Given:
Concrete edges
y= Bin,
> 24 in
h = 16in.
Base plete
12x 12in,
Bolt spacing
$= Bin,
Concrete material
‘4000 psi (concrete)
‘2000 psi (grout)
Bolt material (F1554 Gr. 36 anchor rods)
5 36 ksi
f= BBksi
Plate
Fy = 36ksi
7 kips
18 in, (height of stub column above
surface of concrete)
My, Wyxe = 126.0 iIn-kips
No 3.0 kips
‘Where M., Nu and V, are the required factored
external loads using load factors from Chapter 9 of
the code.
‘Assumptions:
* Concrete is cracked
+ @-factors are based on Condition 8 in D.4.4
of the code (no supplementary
reinforcement)
Ductile embedment design is in
accordance with D.3.6.1
72RON
she
s
1h
oz
isha 4.Shat
PLAN
Puy
SECTION A-A
SECTION A.A,
CODE
SECTION
DESIGN PROCEDURE
CALCULATION
5,_ STEP 1: Design for moment and tension
‘The plate size is 12 x 12 in., and the spacing s
Of the anchors is 8 x 8 in.
‘Assume plate thickness tis 1 in.
‘The frst step is to calculate the tension force in
the anchors and compression reaction force in
the concrete from the applied forces.
‘The base plate is just large enough in area to
accommodate the column profile, that is, small
73DESIGN PROCEDURE CALCULATION
‘base pate (per AISC). For the shear toward the
‘edge of the slab, the resultant tension from the
moment is taken by the two left-hand side (Line
2) bolts, and the compression is taken in
bearing on the effective bearing area. The
bearing area is taken to the edge of the plate.
‘The effective bearing area is taken as a
distance t around the compression flange. This
is an approximation. The error introduced into
the calculation is negligible.
The exact location of the compression resultant
is dificult to determine. For design, take the
resultant to act at the outside edge of the
compression flange. This approximate analysis,
is deemed adequate.
Determine the moment arm a.
Determine the tension in the bolts and
Compression in the concrete,
Me
a
Check the effective bearing area based on |, _ 126 in-kips
the location of the resultant compression 'n om
assumed previously. The bearing capacity
is as given in the noted code section. An. | Nx = 144/08
assumption has been made in this example
40, 10.17.1_ | that the grout under the plate, though Cy =Na
41. 8325 | unconfined, does not control because itis at | c < 29(0.859:)4,
'm $ 26(0-85%. rwang
42 least 9000 psi in compressive strength. °
43. Check the conerete instead. The gfactors | Anon =(6r* 21K, +1+4,)
i are as given in Chapter 9. ois 0.65 for Areonag = (3.96 + 20.27 +1+1)
| bearing. Due to confinement, use the 2
oy | maximum allowed factor, 2. Fave = 13.53 4
ot Cry $ 2{0.65Y0.85.4 4S! Aesang
50. Cn $2(0.05X0.85,r4 13.53 in*
ay Cu $59.8hi05
53. kivs < S9.8hios OK
74CODE
DESIGN PROCEDURE
N
| SECTION CALCULATIO!
2 Nw = Nm +f (intwobotts)
3
4 Ny = 14kips + 308
5 2
6 Ng = 15.Skips
7.
8
9.
+0 © = 6,-NYf (onbearing area)
un “The effect ofthe tension force in shifting the ‘Shine
12 location of the compression resultantis deemed | C = 14kips ~
3 negligible, and hence, itis conservative to
4 algebraically add the bol force distribution from | C = 12.5kips
15 moment to that from tension. N, i the tension in | Wi, < 6M,
16, the column, and Ng, isthe tension in the two 2 .
7 seas Mo = OAs fy (0-3)
18
18 Likewise, the compression on the bearing rea
20 can be reduced directly by the tension force
a even though the forces are centered at different
2 locations. «9 is 0.75 for tension sirength in steel
23
be oad fame = "fag
25, Determine the required bolt are2 Avaracs for fe
26. tension. F1554 Gr. 36is @ duct steel Ame = 56 r5(0)58
27. clement. The plactors areas giveninO.aa. |” gee
28 Note that Avge isthe effective tensile area | “wore =
29. 0.8.1.2 | required, and'n's the number of bots resisting
30. the tension force. Note that the bolts resist Use % in. diameter threaded rods.
a shear as well, hence the margin in area of bolt
32 provided (Ase). See Step 2 for consideration of 44a (nominal acca)
3%. sheer. ae
34 yg = 03340" (effetve area)
35. Net tensile area of threaded bots canbe found | gi,— bay fy (03)
x in Table 2 of Appendix | pace ostossila}se
38. ON,= 29.06hips (two bolts)
39,
Hy ON, > Ny
4 29.06 kips > 15.5kips
42
oe OK
44, STEP 2: Design for shear
45. Concrete breakout modes (options) that willbe used in design.
78DESIGN PROCEDURE,
CALCULATION
‘SEGHONAA
'b) Shear resisted by two anchors closest to edge
SHEAR FORCE TOWARD EDGE
Shear resisted by two anchors farthest
from edge
76CODE
SECTION
DESIGN PROCEDURE
CALCULATION
SECTION,
c) Shear resisted by two anchors closest to edge
Le ‘SECTONAA
1) Shear resisted by two anchors farthest from edge.
‘SHEAR FORCE AWAY FROM EDGE
‘This Is a base plate on grout therefore Section
D.6.1 is applicable. Note that surface mounted
plates with grout often come with oversized bolt
holes." Therefore, in this example it will be
assumed that only two anchors are engaged in
resisting shear.
‘There are two options for analysis. The frst is
to assume the bolts in tension also camry shear
and compute the avaliable shear strength from
steel based on that assumption. Alternatively,
assume that only the bolts in the compression
take the shear and compute the shear strength
based on that assumption. Both will be
checked in the solution presented.
‘Compute the ste! shear capacity
7CODE
computation and minimizes the effective width
Section _ | DESIGN PROCEDURE CALCULATION
7.D.6.1.2 | In Options (a) and (@), the bals in tension also
2.06.13 | resist shear. This is critical case for steel
3.06.14 __| strength of anchor. Options (a) and (c)
4 : vse,
5. | Note that the 0.8 factor for grout (0.6.1.3) : e
6 epplies to Ea. (0-19) 9, = 410.8, + 8(040,)
5 4Y, = 6(0.8)0.67 A, f + 6(0.4C-) (0-19)
apas “The g-factoris 0.65 for steel in shear and 0.7"
8 for the friction between the base plate and the |
40. ‘concrete $(0.8)0.604,, £, = 0.65(0.8}0.6(2)(0.334)58 |
4
#08)0.50 4, f,=1209hips
12 Section D.6.1.4 states thatthe friction (0.4C)
13. Banwosn te bace ate and to concrete (nis | #04Cr)=070(04(28)-=3 50bps
14 case, grout) shall be permitted to be used to
18. resist shear, Therefore, combine the provisions | V, <#(0.8)0.67 Af, + #(0.4C,) (D-19)
% of D.6.1.4 with Eg, (D-18) to obtain the shear | 7'<12.09+3.50
i strength
8, Check fortension-shear interaction based on | 7515394
18 steel strength only forthe bolts loaded in both | OK
xm tension and shear. See Step 9.
7
| 22. -
23. STEP 3: Design for base plate
24 The plate thickness was assumed at the
25. beginning of the example problem to be 1 in.
26. To check tho required plate thickness, there are
27. two possible failure modes:
28.
29. 1. Yielding ofthe plate in the tension region
30, ‘around the two tension bolts.
a 2. Yielding ofthe plate in the compression esa area
32, region, rr
33,
3s Pryout ofthe bolls in the tension region is wi, = 85. <72hios per bot
38 ‘ignored 2
37 Fellure Mode 1 alr
38. Tension yielding ofthe plate around the bolts in
39. tension
40.
“1 Plate bending approximation |
42 ‘Assume that the plate is fixed along the web
48. and the flange of the wide flange shape in
44. tansion and thatthe plate acts as a cantilever
45. between the bolts and the web and flange of the
. wide flange. Also assume the effective width b
7 of plate for stress computation is 21 each side of
48. the point of maximum stress. Therefore, b=4t, | % =
2 where tis the thickness of piate. This
0. approximation is conservative because it xe
51 mmaximizgs the moment arm for moment a
78CODE
SECTION
DESIGN PROCEDURE
CALCULATION
of the plate resisting this moment. Ttlso
ignores the clamping effect at the bolt location
Failure Mode 2°:
‘The compression is acting in the effective
bearing area. The bearing area is taken as
fixed along the column web and compression
flange. The maximum cantilever distance of the
area Icaded in bearing relative to the fixed axis
Is the maximum of tor d.. The bearing area
atuin)
M, = Nalx) = 7.8(0.73i0)
M, = 87k-in
M, = Nyly) = 7.8(3.88i)
M, = 30.1k-in
(57 +30."
w= fut
M, = 30.8k-in
$M, = 09F,Z = 09F, 20
gu, = o9(esssi $l = s24k—in
eM, 2 My
324K -in
OK
Use 1 in. thick plate
306k —in
C = 128kips
t= max(t.d,) esF aw
(2a
°Vou@e)353
0.24 in. <1.0%.
ae
OK
79CODE 1
SECTION DESIGN PROCEDURE CALCULATION
1 can be taken to be under @ uniform pressure
2. ‘equivalent to C/Ageaang
3. ‘This means thatthe eesumed plate thickness is
4 adequate both for tension and compression on
5 the plate
6.
7
8. STEP 4: Determine required embedment length for the bolts to prevent concrete
breakout failure
8. |
10. | The required embedment length for the anchors | jV, = 0.334" 2* 58 =38.7kips
n willbe determined using the concrete breakout
12 strength of he anchors in tension. Section |. 18.5kips
13. D.5.2 applies. Steel strengths remain as. we
14 previously calculated, 2
a5: N, < 0.85 Nag (for stee!o control)
16.052 | The shearforce is seismic, and hence, has @ 38.7kips 4. «
17.0.3.6.1 | reversible direction. The critical tension eras teed
18 breakout cone is that closest to the edge. This a
19 is depicted in Options (c) and (d) in Step 2. If l eal
20. the steel strength is less than 85% of the fe
21 nominal concrete tension breakout strength, 2 opm e
22 then the connection will be ductile for tension £ al
23 toad; otherwise, itis nonductle. Notations are T fae
24 consistent with Section RD 5.2.1 i] 8) | soe oF cone
2s
26
27.044 | Assume Condition 8 exists, Also assume that
28 the anchors use a standard A563 nut and a
29, F436 washer atthe end of the anchors to serve
30, as the enchor head.
31
32 Provide embedment hy (Fin sketch) = 12 in.
33 Bolt dimension
34,
35
38.
a7 L = 1B5in. (for double mut)
38,
39.
40
44 I
42
a3 (ease ta
44, Modification factors are as computed for: Iceaaeeyoiriare
45.05.24 | Eccentricity effects Wy hy = ¥2in
48.0525 | Edgeeffects ¥
47.0526 | Concrete cracking Ys Nag We Ws Yeon No (05)
48,D.5.2.7 Post-installed anchor effect Yon Not required
43 inthis case. |
50
51,0524
80CODE =
‘ALCULATION
SECTION _ | DESIGN PROCEDURE c
7 1 q
2 peti
: t
4 |
: | be}
8
7.
: FA cterson
a breakout cone
1
12,
3
14
15,
16, (o)
2
18 (5p ee )l15n, +5,+15%,)
hi. aa
| 20. .
a (1.5(12)+8)1.5(12)+8+15(12)
22. = 114417
a A if :
24 Ags OF, = O12 = 12960"
25. A= 1296h? Me a 05.5ni
ie Nay = 46.80Ki08 > ips
44 | Check strength
45. Ductile. OK.
46. 0.4.4 {91 0.70 for tension strength in concrete against
tension breakout Embedment is ductile for tension
Tension-shear interaction remains as computed | yy -0.7(46.80kjos) 2 #N,
in Step 8
. Wang =32.76hips > 29.08 Kjos
Use four rods 34 in. diameter x 18.5 in
Jong with her= 12
81CODE
Section — | DESIGN PROCEDURE CALCULATION
1. STEP 5: Check pullout strength of anchor
ae) N= WN, om
2.0. Calculate the pullout strength of the anchor in . :
3 tension in accordance with 5.3 Aoy 8 (0-48)
4
5 From Table 4b in Appendix A, a concrete
6 strength of 4400 ps is needed to avoid pullout
7 fof ahex head nut. To obtain a ductle design
8 ‘we must either use a heavy Hex nut or provide 1.0 cracked concrete
9 washer. Forthis example problom awasheris | 0.0. = min(s4681.125+21,)
10 provided OD. ~ min(1468.1.125+2(0.136)=1.4
un
12,0.5.2.8 | Width across the flat for an A563 hex nut is
130.5.34 | 1.125in, Use the outside diameter (OD) of the |
| 14.0835 | washer and the diameter of the anchor d to
15. compute the bearing area ofthe head :
16 Nye * Va dag 8
17 The OD of a F463 (USS dimensions) circular | y= !0(.)(4000)=352pr
8 washer is 1.468 in. for 8 2/4 in, bot. From Ne * Nye
18 5.2.8, check that the OD is less than diameter
20 for the nut plus two times thickness of washer 1 > As Uerdietereponey
2 ty 2(082)= 70s > 48 Shpe
2,036.1 | Pullout capacity to maintain ductle design in
23. accordance with D.3.6.1. Number of bolts in
24, tension is used inthe computation of pullout. | Pu. OK
25.
26. 418.0.70 fortension strength in concrete against | Van = 0 7(70.4)= 49.3kips
z. pullout 49.3kips > @N, = 28.08 kips
sai 3/4 in. diameter bolts are OK tor pullout
31. STEP 6: Check concrete side-face blowout
32,054 Check i side-face blowout neads to be 3 8i>04h, =0Alt2)= 487
33, investigated using the code limits given in OK. ‘|
7 investigated us Ignore side-face blowout
35. STEP 7: Check concrete shear breakout
36.062 Because the base plats & not dgidly alached to | V,~ 06nd, fy
37. the anchor bolts, two shear failure cones need | o6(2}(0.334)s8)
38. to be checked. Note that these two shear 7
39, breakout cones need tobe checked aven ital | x= 23-2kips (wobols)
40. the bolis resist sheer. This is done to prevent | ,, oe
41 the Zipper effect in which the concrete Yeeros 27.3kips_(ovobots)
42 supporting the two bolts closest to the edige fails
43. frst and causes the faye ofthe concrete
4a around the two bolts farther from the edge.
45,
46,
47 | two bots feilure cone: Option (a)
48, Note: For Option (a) where the shearis towards |
49 | the edge and tension bolts resist shear,
82