ENERGIVO CONTROL SYSTEMS

Check list - Wiring

ECS w/o no : 180


Customer : GE T&D
Job. Ref : TURKMEN RING 5TH LOT
Panel Ref :
Panel si.no :
Date : 6/29/2023

Sl.no. Description Yes No

1 Wire size & colour as per panel construction note

2 In.bunching of wires at micom relay

3 Termination tightness check

4 Ferrule Readability of wires

5 Proper Bunching of wires at all relays & components (Aesthetic)

6 BBX wire bunching at both ends

7 Ensure the BBX wire bunching with identification tag provided

8 Wire pull test

9 Ensure the BCU Card Negative link check (if BCU applicable )

10 Ensure the CT & MICOM link check as per schedule

Verify the shielded cable crimping & connection (if shielded cable
11
applicable )

12 RED Tube ferrule using TRIP Circuit

13 Spiral/Nylon mesh used for swing wiring & Ac wiring

14 Ensure wires are not routed in Customer Cable trough

15 CAD checking

16 CAD report completion

Formate No: ECS/QC/W/2020


rev 1 Checked :
ENERGIVO CONTROL SYSTEMS

Check list - Wiring Harness


PO NO Panel Ref :
INVOICE NO Inspected Date :
GRN NUMBER Inspected qty :
SUPPLIER NAME Accepted qty
Job. Ref Rejected qty
Sl.no. Description Yes No
1 Wire size & colour as per panel construction note & wiring schedule

2 wire cutting as per schedule


Striping Length (Ring & fork &flat-6mm ,Tubler lugs-10 +_5 mm )
3

4 Ferrule inserting as per approved drawing


5 Lug crimping as per schedule mentioned .
6 Readability of Ferrules as per drawing
7 wire bunching
Inspected sample wire bunch si.no reference
Pul test Standard
Sl.No Sq.mm kg
1 1.5 13.6
2 2.5 22
3 4 31.75
4 6 36
Striping length standard
Sl.No LUG TYPE STRIPING LENGTH
1 RING 6MM
2 FORK 6MM
3 FLAT 6MM
4 TUBLER 10 +_5MM

IEC-60352-2
Formate No: ECS/QMF/QA/WH
REV NO 1 Checked :