Technical Data
Oil Immersed Power Distribution Transformer Sizes for the 11/0.4 kV
Losses Fuse (or CB) Size Amp. Efficiency
Rated Impedance
Power PF = 1 PF = 0.8
No load On load %
kVA H.V. Side L.V. Side Full Half Full
W W load load load
Half load
50 190 1100 4 6.3 80 97.48 98.17 96.87 97.72
63 225 1300 4 10 100 97.63 98.28 97.06 97.86
100 320 1750 4 10 160 97.97 98.50 97.47 98.14
160 460 2350 4 16 250 98.27 98.70 97.85 98.38
200 550 2800 4 25 315 98.35 98.76 97.94 98.46
250 650 3250 4 25 400 98.46 98.84 98.08 98.55
315 780 3850 4 40 500 98.55 98.90 98.19 98.63
400 930 4600 4 40 630 98.63 98.97 98.30 98.71
500 1100 5500 4 63 800 98.69 99.01 98.37 98.77
630 1300 6500 4 63 1000 98.77 99.07 98.47 98.85
800 1500 9000 6 63 1250 98.70 99.07 98.38 98.84
1000 1700 10500 6 80 1600 98.79 99.14 98.49 98.93
1250 2200 14000 6 100 2000 98.72 99.09 98.40 98.87
1600 2600 17000 6 125 2500 98.78 99.15 98.47 98.94
2000 3200 22000 6 160 3150 98.75 99.13 98.44 98.92