0% found this document useful (0 votes)
2K views81 pages

DVM S2 Catalogue LKA

Uploaded by

Ishan Ranganath
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
2K views81 pages

DVM S2 Catalogue LKA

Uploaded by

Ishan Ranganath
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Samsung India Electronics Pvt. Ltd.

Sri Lanka Branch Office,


Access Towers - 21st Floor, No.278/4, Union Place,
Colombo 02, Sri Lanka.
Tel: +94 11 4426300, Fax: +94 11 4426325.
We are proud to say that Samsung is recognised as one of the
world’s leading intuitive product design companies, and one

We create new possibilities


of the world’s top electronics producer. Samsung system air
conditioners have been designed with the same passion for
innovation and quality that has helped make Samsung one of
Interbrand’s 2018 Best Global Brands.

As such, Samsung system air conditioners are held in high


esteem around the world and have been selected for a
multitude of applications, including shopping centres, airports,
stadiums and hotels. And in constant pursuit of excellence,
we continue to invest heavily in research and development,
performance testing and quality control to deliver superior air
conditioning systems.

Helsinki (Finland)
Oslo (Norway)
Kista (Sweden)

Copenhagen (Denmark) Stockholm (Sweden)


Moscow (Russia)

309,630 7
Warsaw (Poland)
Chertsey (UK)
Amsterdam (Netherland)
Kiev (Ukraine) Ulaanbaatar (Mongolia)
Lyon (France) Praha (Czech)
Budapest (Hungary)
Employees Design Centers
Kishinev (Moldova) Almaty (Kazakhstan)
Milan (Italy)
Madrid (Spain) Istanbul (Turkey) Beijing (China)

Teheran (Iran) Tianjin (China) New York (USA)


Porto Salvo (Portugal) Athens (Greece)
Tunis(Tunisia) Baghdad (Iraq) Suwon (Korea)
Algiers (Algeria) Beirut (Lebanon) Santa Fe Springs (USA)

74 37
Kabul (Afghanistan) Gwangju (Korea)
Rabat (Morocco) Amman (Jordan)
Petah Tikva (Israel) Lahore (Pakistan) Roanoke (USA)
Suzhou (China)
Noida (India)
Cairo (Egypt) Kuwait City (Kuwait)
New Delhi (India)
Countries Production Sites
Doha (Qatar)/Manama (Bahrain)
Hong Kong
Dubai (UAE) Dhaka (Bangladesh)

Muscat (Oman) Kolkata (India)


Hanoi (Vietnam) Mexico City (Mexico) Santo Domingo (Dominica)
Jeddah (Saudi Arabia)
San Juan (Puerto Rico)
Mumbai (India) Guatemala City (Guatemala)
Dakar (Senegal) Manila (Philippines)
Bangkok (Thailand)
Taguig (Philippines)

216 15
Chennai (India) Pattaya (Thailand)
Abuja (Nigeria) Barranquilla (Colombia)
Hochiminh (Vietnam)
Lagos (Nigeria) Panama City (Panama)
Colombo (Sri Lanka)
Accra (Ghana) Kuala Lumpur (Malaysia) Bogota (Colombia)
Singapore (Singapore) Global Bases
Quito (Ecuador)
Manaus (Brazil)

Nairobi (Kenya)
Jakarta (Indonesia)

Lima (Peru)

Training Centers Training Centers 37 52


Production Facilities Production Facilities Sao Paulo (Brazil)
RandD Centers
Brisbane (Australia)
Johannesburg (South Africa)

Sydney (Australia)
Santiago (Chile)
Perth (Australia)
Buenos Aires (Argentina)

1 2
“comfort”
Free™
• 1 way, 4 way and High Wall

Samsung is synonymous with pushing back However, all of this advanced technology doesn’t
boundaries, and we are revolutionizing the world of make them hard to use. In fact, it is the complete
air care. Our award-winning air conditioning systems opposite. You can control your air conditioner
are recognized worldwide for their stunning designs, really easily, even when you’re on the go. As well as
offering standard remote controls with a bright color
display and intuitive interface, you can also control 360 Cassette
Using groundbreaking technology, we have the air conditioner anytime and anywhere using an • Innovative Circular Design
developed an extensive range of innovative App on your smartphone.
• Omni-directional Outlet
climate systems. So, we can provide the best
• Bladeless Design
As a result, Samsung has received a host of
with a Booster Fan
home or for a business. prestigious industry awards. The 360 Cassette was

Our Free™ technology spreads fresh air 2016 and the International Design Excellence Awards
uniformly without unpleasant cold drafts. To ensure (IDEA) 2016. In addition, Samsung’s Digital Inverter
maximum comfort throughout an entire room, 8-Pole was recognized for its product excellence in
the bladeless 360 Cassette features booster fan the 40th Mostra Convegno Expocomfort’s “Beyond
technology and a cutting-edge circular design. And Class A” initiative. And our Wallmount climate
system received the “Eco-design and Sustainable
cools you quickly without wasting energy. You can Technologies” CES award in 2015.
even stay wonderfully warm when it’s freezing
outside, as our Flash Injection technology maintains
a reliable performance even at temperatures as
low as -25°C.
• 34HP Large Capacity in a Single Unit
• Larger Heat Exchanger Area#

We understand
exceptional performance
“business”.

• Compact Size
So we provide
• Up to 14HP Large Capacity the
to exquisitely meet
• Flexible Installation with 4-way Piping

every need.

• Modular Design with a Small


Footprint
• Flash Injection Technology
• Expandable to up to 320ton

#
Based on Samsung's measurements, comparing 33.6kW models of a DVM S2 and a conventional outdoor unit.
3 4
Continuous innovation
Samsung has been manufacturing air conditioners and challenging the status quo of
the industry for over 40 years.
Thanks to cutting-edge innovations in design and technology, we will continue to aspire
to be a leader in the cooling and heating industry in the years to come.

1985 2015
Introduced World’s First
Began Inverter
360 Cassette
RAC / FAC / PAC
30HP DVM
Production

2012
1974 Launched Wi-Fi Control RAC 2022
Began WAC Production
2000 (Jungfrau) 2018
First Launched DVM Water Extended Free™ Large capacity up to 34HP (Single ODU unit.)
With Cassette Range

2007
1975 Launched World’s
Largest Capacity DVM+4
2017 2020
Began RAC Production (22HP, Max 88HP) Launched Free™ Free™ technology

2013
1992 Launched Triangle Design
RAC (A3050)
Began SAC Production

Image simulated for representational purposes only. Image simulated for representational purposes only.

5 6
I Technologies that go greener

Optimal
Discharge
Superheat Active AI
Active AI
Control AI Pressure Control
Technologies

Flash injection Multi-serration Optimised


Fan refrigerant Active AI Defrost
path

Active AI
Enlarged Refrigerant Analysis
Triple
heat
exchanger

In line with Samsung’s unwavering commitment Digital


inverter
to being an eco-responsible organisation, the motor

Ultra
DVM S2’s radical new design incorporates a range Advanced Flash PHE type
sub-cooler
of technologies that minimise its impact on the Injection Compressor™
(90cc capacity)
environment. As well as transferring heat much Dual
magnet Slimmer
rotor liquid pipe
also intelligently optimises its cooling performance
to reduce any waste. In addition, its improved
sub-cooling rate and Advanced Flash Injection

required, making it much more environmentally

Artificial Less
performance
minimises controls reduces replaces
waste of more AI environmental fossil
energy risks fuel

The DVM S2 has been redesigned to cut the cost The DVM S2 optimises its cooling performance The DVM S2 saves money and helps protect the The DVM S2 introduces a new era of eco-friendly
automatically, based on a learning and optimising
enlarged Heat Exchanger has a much greater transfer algorithm about the installation conditions and usage system. It is equipped with a high-performance
area to exchange heat faster. An optimised refrigerant patterns. Active AI Pressure Control intelligently adjusts sub-cooler that improves the sub-cooling rate of Wrap and Optimal Discharge Superheat (DSH)
the refrigerant condensing pressure and evaporating refrigerant. Its slimmer liquid pipe also means it Control. The improved strength of its Flash Injection,
the transfer of heat. An aerodynamic Multi-serration pressure, so it cools faster and reduces energy usage. requires 25% less refrigerant compared to a normal which delivers superior heating in frozen conditions,
Active AI Defrost ensures it defrosts more precisely, so pipe, on average. So it reduces the costs of installation means that the capacity is now much larger (90cc).
electricity as it minimises air turbulence. And a 7th So it is powerful enough to replace conventional
generation insulated gate bipolar transistor (IGBT), And Active AI Refrigerant Analysis proactively monitors in designing the entire system. In addition, by using less heating methods that use fossil fuel. And its highly
which switches current and frequency to suit the and helps maintain the optimum level of refrigerant. refrigerant, it is much more environmentally friendly.
system, reduces the loss of conducted electricity.

Image simulated, for representational purposes only. Image simulated for representational purposes only.

7 8
I Overview

Rebuilt on
all-new innovations.

and reliability.

Comfort

Enlarged 90cc chamber Advanced Active AI


Dual Kammtail
heat with triple
motor bracket
exchanger ™
Control

Upgraded Multi-

Ultra
path

High- Active AI
Galvanized iron Quiet
DSH control operation
IGBT Control

plenum
Convenience
True innovation is a rare thing – so the multiple reliability, as it can operate effectively in diverse Wider High elevation
Active AI Kammtail
motor bracket
Slimmer Emergency
new technologies in the Samsung DVM S2 environmental conditions, including the most operating with long
piping
liquid pipe operation
outdoor air conditioning unit make it truly extreme temperatures. It also includes a host of Rotational
Enlarged heat
unique. It has been totally redesigned to deliver new and intelligent management features that Active On-Device
Inverter
Center point operation
exchanger

outstandingly consistent comfort in a wide make its installation and maintenance much drive 10Hz control Check™ weight

range of locations, as well exceptional energy simpler and more cost-effective. Quite simply it
Up to 110Pa Active AI
Compact
efficiency. Its flexibility is equally matched by its redefines the art of comfort. cover with
handle

Image simulated, for representational purposes only.

9 10
I Key features
II Cost sav II Cost sav

01-01 01-02 01-03 01-04 01-05 01-06 01-07 01-08 01-09 01-10

The air flow speed inside the outdoor unit varies depending
on how far it is from the top fan – the closer the faster and
02-01 the farther the slower – which normally results in the uneven
02-02 02-03 02-04 02-05 02-06 02-07 02-08 02-09 02-10

exchange of heat from top to bottom. The Samsung DVM


DVM S2
S2 has an optimised refrigerant path* that ensures that the 3a
Seasonal Other brand 03-01 flow of the refrigerant matches the air
03-02 03-03 03-04 03-05 03-06 03-07 03-08 03-09 03-10

flow speed, which optimises the


7.5 transference of heat. So, it performs
7.2
more effectively and efficiently 2 3b
6.91 6.9 6.9 6.9 6.94 04-01 04-02 04-03 04-04 04-05 04-06 04-07 04-08 04-09 04-10

6.84
6.7
6.5 by balancing the exchange of 4a
6.32 6.26
5.91 5.93 6.0 5.92 energy.
05-01 05-02 05-03 05-04 05-05 05-06 05-07 05-08 05-09 05-10

1 4b
22.4kW 28.0kW 33.6kW 40.0kW 45.0kW 50.4kW 56.0kW Average 06-01 06-02 06-03 06-04 06-05 06-06 06-07 06-08 06-09 06-10

07-01 07-02 07-03 07-04 07-05 07-06 07-07 07-08 07-09 07-10

Transfers more energy


08-01 08-02 08-03 08-04 08-05 08-06 08-07 08-08 08-09 08-10

with an enlarged contact area 09-01 09-02 09-03 09-04 09-05 09-06 09-07 09-08 09-09 09-10

10-01 10-02 10-03 10-04 10-05 10-06 10-07 10-08 10-09 10-10

01-01 01-02 01-03 01-04 01-05 01-06 01-07 01-08 01-09 01-10

The Samsung DVM S2 has an enlarged heat exchanger


that is capable of transferring much more heat at once.
Its heat transfer area is up to 36.2% larger# to quickly
02-01 02-02 02-03 02-04 02-05 02-06 02-07 02-08 02-09 02-10

exchange heat. As a result, it consumes less energy to


achieve the same cooling and heating performance.

4
03-01 03-02 03-03 03-04 03-05 03-06 03-07 03-08 03-09 03-10

1 5
04-01 04-02 04-03 04-04 04-05 04-06 04-07 04-08 04-09 04-10

Heat
Rate of improvement in
05-01 05-02

05-03
transfer
area
05-04 05-05

05-06 05-07 05-08 05-09 05-10 **
Top 22% 3

The refrigerant flow rate is


2 6
06-01 06-02 06-03 06-04 06-05 06-06 06-07 06-08 06-09 06-10
adjusted by increasing the mass
flow rate in order to increase the
Conventional

amount of heat exchanged in the 19%

07-01 07-02 07-03 07-04 07-05 07-06 07-07 07-08 07-09 07-10
upper part.
15%

08-01 08-02 08-03


Heat
08-04
transfer
08-05 08-06 08-07 08-08 08-09 08-10
m² m²
area Bottom 8%

09-01 09-02 09-03 09-04 09-05 09-06 09-07 09-08 09-09 09-10

Conventional

10-01 10-02 10-03 10-04 10-05 10-06 10-07 10-08 10-09 10-10

* The shape of the refrigerant path differs by model.


** Based on an internal module evaluation. Results may vary depending on the individual test or usage conditions.
#Based on Samsung's measurements, comparing 33.6kW models of a DVM S2 and a conventional outdoor unit.
Image simulated for representational purposes only. Image simulated, for representational purposes only.

11 12
I Key features I Key features
II II

Circulates more refrigerant while using less energy

-01 01-02 01-03 01-04 01-05 01-06 01-07 01-08 01-09 01-10 01-01 01-02 01-03 01-04 01-05 01-06 01-07 01-08 01-09 01-10

The DVM S2 has a brand-new, aerodynamic Multi-serration The Samsung 90cc inverter scroll compressor used in the
fan* that creates more air flow while consuming less Samsung DVM S2 has the world’s largest capacity and
-01 02-02 energy. Its multi-serration wing tip design, inspired by
02-03 02-04 02-05 02-06 02-07 02-08 02-09 02-10 02-01 02-02 02-03 02-04 circulates up to 17% more refrigerant*. Its new triple profile
02-05 02-06 02-07 02-08 02-09 02-10

an eagle owl’s wing, minimises the turbulence of the air scroll combines arc, involute and quadratic curves and also
vortex, which reduces the air resistance and ensures more has a thicker profile towards the middle to reinforce the
-01 03-02 stable fan movement.
03-03 03-04 03-05 03-06 03-07 03-08 03-09 03-10 03-01 03-02 03-03 03-04
strength of the center part. So, it creates a larger chamber
03-05 03-06 03-07 03-08 03-09 03-10

and rotates reliably at high speed. By delivering a higher


level of performance at a lower frequency, it consumes less
-01 04-02 04-03 04-04 04-05 04-06 04-07 04-08 04-09 04-10 04-01 04-02 04-03 04-04
electricity and improves overall energy efficiency, especially
04-05 04-06 04-07 04-08 04-09 04-10

in a high frequency domain.


Large Small
-01 05-02 05-03 05-04 05-05 05-06 05-07 05-08 05-09 05-10 05-01 05-02 05-03 05-04 05-05 05-06 05-07 05-08 05-09 05-10

Serration Arc Arc


-01 06-02 06-03 06-04 06-05 06-06 06-07 06-08 06-09 06-10 06-01 06-02 06-03 06-04 06-05 06-06 06-07 06-08 06-09 06-10

Involute
Involute

-01 07-02 07-03 07-04 07-05 07-06 07-07 07-08 07-09 07-10 Large vortex 07-01 07-02 07-03 07-04 07-05 07-06 07-07 07-08 07-09 07-10

Minimal vortex Quadratic


Quadratic
curve
curve

-01 08-02 08-03 08-04 08-05 08-06 08-07 08-08 08-09 08-10 08-01 08-02 08-03 08-04 08-05 08-06 08-07 08-08 08-09 08-10

* Only available in certain models that have one fan. The shape of the fan may vary by model and region.
-01 09-02 09-03 09-04 09-05 09-06 09-07 09-08 09-09 09-10 09-01 09-02 09-03 09-04 09-05 09-06 09-07 09-08 09-09 09-10

10-01 10-02 10-03 10-04


* Samsung circulates 14,400cc/sec refrigerant (= 90cc (displacement volume) x 160rps (revolutions per second)), while Company A circulates 12,480cc/sec (= 96cc x 130rps), Company B
circulates 14,080cc/sec (= 88cc x 160rps) and Company C circulates 12,320cc/sec (=88cc x 140rps).
-01 10-02 10-03 10-04 10-05 10-06 10-07 10-08 10-09 10-10 10-05 10-06 10-07 10-08 10-09 10-10

Reduces the loss of conducted electricity

-02 01-03 01-04 01-05 01-06 01-07 01-08 01-09 01-10

An IGBT has a key role in inverter systems. It switches direct current (DC) to alternating current (AC) and maintains
Reduced losses at partial loads Arc Arc
a frequency (Hz) that is suited to the system. So, the efficiency of an IGBT affects the efficiency of the whole air
Involute
Involute
-02 02-03 conditioning system. The Samsung DVM S2 uses the 7th generation of IGBT, which reduces the loss of conducted
02-04 02-05 02-06 02-07 02-08 02-09 02-10 9 release valves
electricity by 20%*, while being 36% smaller in size. As a result, the Inverter Controller's energy efficiency is improved by 01-01 01-02 01-03 01-04 01-05 01-06 01-07 01-08 01-09 01-10

up to 3.6%*, depending on the operating frequency (Hz). Compressors always draw in the maximum amount of
refrigerant to generate the 100% pressure needed
Quadratic to operate
Quadratic
curve
curve
at full load, as their chamber size is not variable. And, to
-02 03-03 03-04 03-05 03-06 03-07 03-08 03-09 03-10

02-01 02-02 02-03 02-04 02-05 02-06 02-07 02-08 02-09 02-10

compress more refrigerant, more electricity is required. So,


Comparison of energy loss on IGBT it's crucial to release any excessive refrigerant pressure in
(W)
-02 04-03 04-04 04-05 04-06 04-07 04-08 04-09 04-10

order to save energy when there's only a small load that


Loss amount

03-01 03-02 03-03 03-04 03-05 03-06 03-07 03-08 03-09 03-10

700
doesn't need a high discharge pressure. The new Samsung
-02 05-03 05-04 05-05 05-06 05-07 05-08 05-09 05-10
600 Conventional 90cc scroll compressor has 9 release valves, so it accurately
New 04-01 04-02 04-03 04-04 04-05 and immediately releases refrigerant to prevent the over-
04-06 04-07 04-08 04-09 04-10

500 Conventional
compressing that wastes electricity.
400
-02 06-03 06-04 06-05 06-06 06-07 06-08 06-09 06-10

05-01 05-02 05-03 05-04 05-05 05-06 05-07 05-08 05-09 05-10
300

Pressure

Pressure

Pressure
-02 07-03 07-04 07-05 07-06 07-07 07-08 07-09 07-10 0 50 100 150 (Hz) Full load operation
Operating frequency06-01 06-02 06-03 06-04 06-05 06-06 06-07
Discharge pressure
06-08 06-09
Over-compressing
06-10

(Pressure loss)

-02 08-03 08-04 08-05 08-06 08-07 08-08 08-09 08-10 Partial load operation
07-01 07-02 07-03 07-04 07-05 07-06
Discharge pressure
07-07 07-08 07-09 07-10

Suction pressure
-02 09-03 09-04 09-05 09-06 09-07 09-08 09-09 09-10

08-01 08-02 08-03 08-04 08-05 08-06 08-07 08-08 08-09 08-10

Volume Volume Volume


* Based on internal testing of the DVM S2 33.6kW model compared to a conventional outdoor unit, combined with 6 GD2 5.6kW indoor units. Results may vary depending on the individual test or No release valve 4 release valves 9 release valves
-02 10-03 usage conditions.
10-04 10-05 10-06 10-07 10-08 10-09 10-10

09-01 09-02 09-03 09-04 09-05 09-06 09-07 09-08 09-09 09-10

Image simulated, for representational purposes only.

13 10-01 10-02 10-03 10-04 10-05 10-06 10-07 10-08 10-09 10-10
14
I Key features I Key features
II

Automatically optimises to save energy

05 01-06 01-07 01-08 01-09 01-10

Elevation (m)
110
The optimal refrigerant condensing pressure is 100
crucial to ensure a stable cooling and heating Active AI pressure control
90
05 02-06 performance. A much higher pressure is to be
02-07 02-08 02-09 02-10 80

maintained of the piping length is long or if there 70


60
is a large difference in elevation. More than 50
05 03-06 90% of outdoor units are installed in a situation
03-07 03-08 03-09 03-10
40
where the elevation is 30m or lower and the pipe 30
length is 100m or shorter** (Figure 1). Using active 20
05 04-06 AI pressure control*, the DVM S2 recognises both
04-07 04-08 04-09 04-10
10 Length (m)
0
the piping length and the difference in elevation -10
20 40 60 80 100 120 140 160 180 200

and learns the usage pattern and external -20


05 05-06
temperature in real-time. It then automatically
05-07 05-08 05-09 05-10
-30
adjusts the refrigerant condensing pressure -40

accordingly, by up to 32% (Figure 2). As a result, it


05 06-06 06-07 06-08 06-09
reduces the energy
06-10

consumption
by 15%*** when
Pressure (P)

the condensing
15
05 07-06 07-07 07-08 07-09 07-10

12.5kWh % pressure is reduced


Normal High
pressure
Saving
by 12% Condensation
05 08-06 08-07 08-08 08-09
(Figure 3).
08-10

10.7kWh Active AI
pressure Expansion Compression

Ensures reliable inverter control


control
05 09-06 09-07 09-08 09-09 09-10

Low 01-01 01-02 01-03 01-04 01-05 01-06 01-07 01-08 01-09 01-10

pressure
Evaporation
Active AI
05 10-06 10-07 10-08 10-09 10-10
pressure Energy
control saving 02-01 02-02 02-03 02-04 02-05 02-06 02-07 02-08 02-09 02-10

Normal
pressure control Normal
The inverter circuit of VRF systems generates a lot of
heat, which affects the entire system performance. The
Energy use
to compress
Enthalpy (h) Samsung DVM S2 has a Dual heat sink that uses both air and
03-01 03-02 03-03 03-04 03-05 03-06 03-07 03-08 03-09 03-10

refrigerant. Its unique Insert diecasting heat sink design


minimises the thermal loss between the pipe and heat sink
by increasing their contact area by 33%. By radiating heat
04-01 04-02 04-03 04-04 04-05 04-06 04-07 04-08 04-09 04-10

from the inverter circuit more effectively, it helps extend


the maximum operating temperature from 48°C to 53°C,
and delivers a reliable performance regardless of the
05-01 05-02 05-03 05-04 05-05 05-06 05-07 05-08 05-09 05-10

external conditions.
Simply limits power consumption 06-01 06-02 06-03 06-04 06-05 06-06 06-07 06-08 06-09 06-10

06 01-07 01-08 01-09 01-10

To help businesses manage their power


07-01 07-02 07-03 07-04 07-05 07-06 07-07 07-08 07-09 07-10
Electric current

Usual energy usage


at peak hours
consumption
06 02-07 and related costs better, the DVM S2 offers power-
02-08 02-09 02-10 Limited energy usage
demand control for peak hours and seasons. This
08-01 08-02 08-03 08-04 08-05 08-06 08-07 08-08 08-09 08-10

Peak demand control


is especially useful when the electricity supply
06 03-07 is insufficient or when businesses want to block
03-08 03-09 03-10
09-01 09-02 09-03 09-04 09-05 09-06 09-07 09-08 09-09 09-10

excessive and wasteful energy usage. st


3

06 04-07 04-08 04-09 04-10 06 12 18 24 Hour


10-01 10-02 10-03 10-04 10-05 10-06 10-07 10-08 10-09 10-10

06 05-07 05-08 05-09 05-10

* Optionally available depending on the installation conditions. For detailed information, please refer to the installation manual.
06 06-07 ** Based on internal analysis.
06-08 06-09 06-10

*** Based on internal testing with an AM080AXVGGH/EU outdoor unit connected to AM083NN4DBH1 and AM145NN4DBH1 indoor units with 25m of piping, using the cooling operation in
Auto mode for 4 hours, with an external temperature of 30°C and a set temperature of 22°C. Results may vary depending on the actual installation and usage conditions, such as the piping
06 07-07
length, elevation and external temperature.
07-08 07-09 07-10

06 08-07 08-08 08-09 08-10

15 16
I Key features I Key features
II II

Less damage from physical shocks and swaying Lasting performance with enhanced resistance to corrosion
Corrosion-resistance is a crucial factor in outdoor units, as they need to withstand a range of climate conditions.
The Samsung DVM S2 features improved anti-corrosion capabilities on the heat exchanger and chassis to ensure
maximum durability in harsh environments.

02 01-03 01-04 01-05 01-06 01-07 01-08 01-09 01-10


01-01 01-02 01-03 01-04 01-05 01-06 01-07 01-08 01-09 01-10

Robust frame ™
ultra
02 02-03 02-04 02-05 02-06 02-07 02-08 02-09 02-10
02-01 02-02 02-03 02-04 02-05 02-06 02-07 02-08 02-09 02-10

The Samsung DVM S2 outdoor unit’s Durafin™ Ultra


has an anti-corrosive layer of epoxy acrylic and
02 03-03 03-04 03-05 03-06 03-07 03-08 03-09 03-10
03-01 03-02 03-03 03-04 03-05 03-06 a hydrophilic layer of acrylic resin that disperses
03-07 03-08 03-09 03-10

water and reinforces its corrosion-resistance. Its


superb quality was proven using the Salt Spray Test
02 04-03 04-04 04-05 04-06 04-07 04-08 04-09 04-10
04-01 04-02 04-03 04-04 04-05 04-06 (SST) over a period of 2,280 hours* with no leakage of
04-07 04-08 04-09 04-10

refrigerant**.
02 05-03 05-04 05-05 05-06
Conventional
05-07 05-08 05-09 05-10
05-01 05-02 05-03 05-04 05-05 05-06 05-07 05-08 05-09 05-10

130%
More
02 06-03 06-04 06-05 06-06 06-07 06-08 06-09 06-10
06-01 06-02 06-03 06-04 06-05 06-06 06-07 06-08 06-09 06-10

Epoxy acrylic

Raw aluminum material


02 07-03 07-04 07-05 07-06 07-07 07-08 07-09 07-10
07-01 07-02 07-03 07-04 07-05 07-06 07-07 07-08 07-09 07-10

03 01-04 01-05 01-06 01-07 01-08 01-09 01-10

02 08-03 08-04 08-05 08-06 08-07 08-08 08-09 08-10


08-01 08-02 08-03 08-04 08-05 08-06 08-07 08-08 08-09 08-10

03 02-04 02-05 02-06 02-07 02-08 02-09 02-10


01-01 01-02 01-03 01-04 01-05 01-06 01-07 01-08 01-09 01-10

02 09-03 09-04 09-05 09-06 09-07 09-08 09-09 09-10


09-01 09-02 09-03 09-04 09-05 09-06 09-07 09-08 09-09 09-10

03 03-04 03-05 03-06 03-07 03-08 03-09 03-10


02-01 02-02 02-03 02-04 02-05 02-06 02-07 02-08 02-09 02-10

02 10-03 10-04 10-05 10-06 10-07 10-08 10-09 10-10


10-01 10-02 10-03 10-04 10-05 10-06 The Samsung DVM S2 uses galvanized iron steel plate
10-07 10-08 10-09 10-10

as its external material, with a PE powder coating of


Conventional
up to 100µm thickness. This powerful combination is
03 04-04 04-05 04-06 04-07 04-08 04-09 04-10
03-01 03-02 03-03 03-04 03-05 03-06 03-07 03-08 03-09 03-10

proven to improve corrosion-resistance by 43%, based


% on the Complex Cycle Test (CCT)***. So, it protects the
More cabinet from rusting and ensures it can endure harsh
03 05-04 05-05 05-06 05-07 05-08 05-09 05-10
04-01 04-02 04-03 04-04 04-05 04-06 04-07 04-08 04-09 04-10

conditions.
03 06-04 06-05 06-06 06-07 06-08 06-09 06-10
05-01 05-02 05-03 05-04 05-05 05-06 05-07 05-08 05-09 05-10

04 01-05 01-06 01-07 01-08 01-09 01-10

03 07-04 07-05 07-06 07-07 07-08 07-09 07-10


06-01 06-02 06-03 06-04 06-05 06-06 06-07 06-08 06-09 06-10

04 02-05 02-06 02-07 02-08 02-09 02-10

03 08-04 08-05 08-06 08-07 08-08 08-09 08-10


07-01 07-02 07-03 07-04 07-05 07-06 07-07 07-08 07-09 07-10

04 03-05 03-06 03-07 03-08 03-09 03-10

03 09-04 09-05 09-06 09-07 09-08 09-09 09-10


08-01 08-02 08-03 08-04 08-05 08-06 08-07 08-08 08-09 08-10

04 04-05 04-06 04-07 04-08 04-09 04-10

03 10-04 10-05 10-06 10-07 10-08 10-09 10-10


09-01 09-02 09-03 09-04 09-05 09-06 09-07 09-08 09-09 09-10

04 05-05 05-06 05-07 05-08 05-09 05-10

Conventional
10-01 10-02 10-03 10-04 10-05 10-06 10-07 10-08 10-09 10-10

Leg
Leg base
base Leg
Leg base
base
04 06-05 06-06 06-07 06-08 06-09 06-10

9%
Leg side
Leg side More Leg
Leg side
side ** Based on testing by a third party lab, applying the actual pressure of refrigerant for 1 minute, after a Salt Spray Test (SST) of over 2,280 hours.
* Based on a test in accordance with ICC ES AC156 : 2010 (SDS=2.5g, z/h=1), conducted by
*** Based on internal testing using corrosion chambers, Q-FOG and CCT-1100. The Complex Cycle Test (CCT) includes cycles of spray (for 2 hours at 35°C), dry (for 4 hours at 60°C with 30%
SGS Korea Co., Ltd. Result report No.: SGS-R20-1599-KR00.
04 07-05 07-06 07-07 07-08
Center
Centerof07-09
of Leg-bolt
Leg-bolt
07-10
Center
Centerofof Leg-bolt
Leg-bolt Relative Humidity) and damp (for 2 hours at 50°C with 95% Relative Humidity) conditions. As a result, the Galvanized Iron Steel Plate (GI) formed red rust after 240 hours, which is 43%
gravity
gravity gravity
gravity ** Based on internal testing using Siemens NX nastran 1867 simulation. slower than general Electro-Galvanized Steel Plate (EGI) which forms red rust after 168 hours.
*** Patent No.: P2020-0099857
04 08-05 08-06 08-07 08-08 08-09 08-10
Image simulated, for representational purposes only.
Image simulated, for representational purposes only.

17 18
04 09-05 09-06 09-07 09-08 09-09 09-10
I Key features I Key features
II Comfort II Comfort
01-01 01-02 01-03 01-04 01-05 01-06 01-07 01-08 01-09 01-10

02-01
Keeps on working well in freezing temperatures
02-02 02-03 02-04 02-05 02-06 02-07 02-08 02-09 02-10

03-01 03-02 03-03 03-04 03-05 03-06 03-07 03-08 03-09 03-10

Stay comfortably warm when it’s freezing outside. The


performance of a general heat pump worsens in low
04-01 temperatures as the refrigerant pressure decreases. The
04-02 04-03 04-04 04-05 04-06 04-07 04-08 04-09 04-10

Samsung DVM S2 outdoor unit’s flash injection technology


increases the flow of refrigerant, so the compressor
05-01
continues working reliably. It also performs well at even lower
05-02 05-03 05-04 05-05 05-06 05-07 05-08 05-09 05-10

temperatures, providing non-stop comfort in the coldest


conditions.
06-01 06-02 06-03 06-04 06-05 06-06 06-07 06-08 06-09 06-10

(%)

Capacity
07-01
100
07-02 07-03 07-04 07-05 07-06 07-07 07-08 07-09 07-10

Flash injection
90
Vapor injection
08-01 08-02
80 08-03 08-04 08-05 08-06 08-07 08-08 08-09 08-10

70
09-01 09-02 09-03 09-04 09-05 09-06 09-07 09-08 09-09 09-10

60
-25 -20 -15 -10 (°C)
Outdoor dry bulb temperature
10-01 10-02 10-03 10-04 10-05 10-06 10-07 10-08 10-09 10-10

Better heating performance with advanced


01-01 01-02 01-03 01-04 01-05 01-06 01-07 01-08 01-09 01-10

flash injection technology


02-01 02-02 02-03 02-04 02-05 02-06 02-07 02-08 02-09 02-10
01-01 01-02

Optimally controls the degree of discharge superheat


01-03 01-04 01-05 01-06 01-07 01-08 01-09 01-10


02-01 02-02
to improve both performance and efficiency
02-03 02-04 02-05 02-06 02-07 02-08 02-09 02-10

03-01 03-02 03-03 03-04 03-05 03-06 03-07 03-08 03-09 03-10

The compressor is the engine that makes a major contribution to the overall
performance of an air conditioning system. Samsung has been developing core
technologies to reinforce the power of its global-leading compressor. The result
03-01 03-02 03-03 03-04 03-05 03-06 03-07 03-08 03-09 03-10

04-01 04-02 04-03 04-04 04-05 04-06 04-07 04-08 04-09 04-10
The heating load and external
is the Samsung Advanced Flash Injection Compressor™, which includes a host of (°C)

Degree of DSH
temperature are the two most
brand-new innovations created by Samsung and provides the world’s largest
influential factors on an outdoor
capacity*. By combining flash injection technology with a strengthened triple
04-01 04-02 04-03 04-04 04-05 04-06 04-07 04-08 04-09 04-10

05-01 05-02 05-03 05-04 05-05 05-06 05-07 05-08 05-09 05-10
unit’s heating performance. So, 40
profile wrap and optimal discharge superheat (DSH) control technology, the +15% Performance +14% Performance +11% Performance
the Samsung DVM S2 automatically +5% +3.5% +3%
Samsung DVM S2 delivers a new level of comfort by maintaining pleasantly cool or
adjusts the degree of discharge 30
warm conditions in every corner of a building all year round.
05-01 05-02 05-03 05-04 05-05 05-06 05-07 05-08 05-09 05-10

superheat to reflect any changes


06-01 06-02 06-03 06-04 06-05 06-06 06-07 06-08 06-09 06-10

in them and heat more efficiently 20


06-01 06-02
and effectively. This new method
06-03 06-04 06-05 06-06 06-07 06-08 06-09 06-10

of control improves the heating


07-01 07-02 07-03 07-04 07-05 07-06 07-07 07-08 07-09 07-10

10
performance by up to 15% and Optimal DSH control
Flash
injection
07-01 07-02
increases operational efficiency by
07-03 07-04 07-05 07-06 07-07 07-08 07-09 07-10

0
5% at -15°C*.
08-01 08-02 08-03 08-04 08-05 08-06 08-07 08-08 08-09 08-10

-30 -20 -10 0 10 (°C)

08-01 08-02 08-03 08-04 08-05 08-06 08-07 08-08 08-09 08-10
Outdoor temperature
09-01 09-02 09-03 09-04 09-05 09-06
Advanced
09-07 09-08 09-09 09-10

flash injection
technology Optimal DSH
control 09-01 09-02 09-03 09-04 09-05 09-06 09-07 09-08 09-09 09-10

10-01 10-02 10-03 10-04 10-05 10-06 10-07 10-08 10-09 10-10
Conventional Flash + Vapour injection Vapour injection

scroll 10-01 10-02 10-03 10-04 10-05 10-06 10-07 10-08 10-09 10-10

DVM S2 Flash + Vapour injection

* Based on internal testing. Results may vary depending


on environmental factors and individual use.

Image simulated, for representational purposes only.

19 20
I Key features I Key features
Arc

II Comfort Involute II Comfort


Super durability and speed
01-01 01-02 01-03 01-04 01-05 01-06 01-07 01-08 01-09 01-10 01-01 01-02 01-03 01-04 01-05 01-06 01-07 01-08 01-09 01-10

create an unrivaled capacity Heats for longer with less defrosting


Quadratic
curve
02-01 02-02 02-03 02-04 02-05 02-06 02-07 02-08 02-09 02-10 02-01 02-02 02-03 02-04 02-05 02-06 02-07 02-08 02-09 02-10

Arc
03-01 03-02 03-03 03-04 03-05 03-06 03-07 03-08 03-09 03-10 03-01 03-02 03-03 03-04 03-05 03-06 03-07 03-08 03-09 03-10

In order to compress flash type refrigerant and increase the The heating operation generally causes ice to build up
total amount of compression, the compressorInvolute needs to have on outdoor units, which may interfere with the heat
04-01 04-02 04-03 much better durability and rotary power. The DVM S2 has a
04-04 04-05 04-06 04-07 04-08 04-09 04-10 04-01 04-02 04-03 04-04 exchange process. To remove any ice, air conditioning
04-05 04-06 04-07 04-08 04-09 04-10

triple profile scroll that combines arc, involute and quadratic systems normally pause the heating and run a defrost
Quadratic
curves to create a much larger chamber, curveand the strength of operation, so the indoor environment feels less
05-01 05-02 05-03 the centre part is significantly reinforced with a thicker profile
05-04 05-05 05-06 05-07 05-08 05-09 05-10 05-01 05-02 05-03 05-04
comfortable. Samsung’s Active AI defrost technology
05-05 05-06 05-07 05-08 05-09 05-10

towards the middle. analyses various operating data, including the system’s
air resistance, operating frequency and cycle, so it
06-01 06-02 06-03 06-04 06-05 06-06 06-07 06-08 06-09 06-10 06-01 06-02 06-03 06-04
defrosts more precisely. As a result, it reduces wasted
06-05 06-06 06-07 06-08 06-09 06-10

Arc
energy and increases the continuous heating time by
Involute up to 40%*.
07-01 07-02 07-03 07-04 07-05 07-06 07-07 07-08 07-09 07-10 07-01 07-02 07-03 07-04 07-05 07-06 07-07 07-08 07-09 07-10

Quadratic
curve
08-01 08-02 08-03 08-04 08-05 08-06 08-07 08-08 08-09 08-10 08-01 08-02 08-03 08-04 08-05 08-06 08-07 08-08 08-09 08-10

Conventional Triple profile scroll


09-01 09-02 09-03 09-04 09-05 09-06 09-07 09-08 09-09 09-10

Arc
09-01 09-02 09-03 09-04 09-05 09-06 09-07 09-08 09-09 09-10

And, its new motor also has a 11.4% enlarged


Involute rotor with many
10-01 10-02 10-03 more magnets, which increases the rotary power by 10.8%*.
10-04 10-05 10-06 10-07 10-08 10-09 10-10 10-01 10-02 10-03 10-04 10-05 10-06 10-07 10-08 10-09 10-10

Operating
Quadratic
curve

Dual
Dual
magnet
magnet Temperature

Air

Conventional

01-01 01-02 01-03 01-04 01-05 01-06 01-07 01-08 01-09 01-10

As a result, it has an incredible 90cc compression chamber and


operates at a superfast 160rps (revolutions per second), which
combine to create the world’s largest capacity**. So, it provides 02-01 02-02 02-03 02-04 02-05 02-06 02-07 02-08 02-09 02-10

the exceptional reliability needed to keep rooms warm in


severely cold weather. Step 0 Step 1
03-01 03-02 03-03 03-04 03-05 03-06 03-07 03-08 03-09 03-10
Normal heating operation Non-stop heating operation
The DVM S2 HR module's Rotational defrost Rotational defrost Step 1
operation ensures a continuous heating
04-01 04-02 04-03 04-04 04-05 performance for reliable warmth and
04-06 04-07 04-08 04-09 04-10

comfort.
* Based on internal testing, compared to a Samsung's conventional motor.
** Samsung circulates 14,400cc/sec refrigerant (= 90cc (displacement volume) x 160rps (revolutions per second)), while Company A circulates 12,480cc/sec (= 96cc x 130rps), Company B circulates After initially running all of a building’s outdoor Heating Heating Heating Heating Defrosting Heating
14,080cc/sec (= 88cc x 160rps) and Company C circulates 12,320cc/sec (=88cc x 140rps).
05-01 05-02 05-03 05-04 05-05 05-06 05-07 05-08 05-09 05-10

units in heating mode, it automatically


switches each unit over to defrosting mode Step 3 Step 2
06-01 06-02 06-03 06-04 06-05 in strict rotation. Because the heating mode
06-06 06-07 06-08 06-09 06-10 Non-stop heating operation Non-stop heating operation
runs for a longer period of time, users can Rotational defrost step 3 Rotational defrost step 2

enjoy a more pleasant, warm environment.


07-01 07-02 07-03 07-04 07-05 07-06 07-07 07-08 07-09 07-10

Heating Heating Defrosting Defrosting Heating Heating


Samsung Advanced Flash Injection Compressor™ 08-01 08-02 08-03 08-04 08-05 08-06 08-07 08-08 08-09 08-10

of the DVM S2 has been certified with a reliability


mark (R-Mark), organised by the Korea reliability
certification center, Korean reliability society. 09-01 09-02 09-03 09-04 09-05 09-06 09-07 09-08 09-09 09-10

* Based on internal testing. Heating time at -10°C over a period of 6 hours: Samsung DVM S2 (AM240AXVAGH/EU) = 180 minutes vs. conventional outdoor unit = 110 minutes. Results may
vary depending on environmental factors and individual use.
10-01 10-02 10-03 10-04 10-05
** Available only on the DVM S2 HR (Heat Recovery) models.
10-06 10-07 10-08 10-09 10-10

Image simulated, for representational purposes only.

21 22
I Key features I Key features
II Comfort II Comfort
01-01 01-02 01-03 01-04 01-05 01-06

Optimal cooling by learning usage


01-07 01-08 01-09 01-10

patterns Reduces fan noise by


minimising the air vortex
02-01 02-02 02-03 02-04 02-05 02-06 02-07 02-08 02-09 02-10

Active AI pressure control


03-01 03-02 03-03 03-04 03-05 03-06 03-07 03-08 03-09 03-10

By learning usage patterns from recent cooling operations and the


surrounding conditions, the DVM S2 proactively creates the optimal
01-01 01-02 01-03 01-04 01-05 01-06 01-07 01-08 01-09 01-10

Eagle owls fly silently at night. Inspired by their wings, a


cooling environment to suit users’ general requirements.
new multi-serration fan* has two types of serration on
04-01 04-02 04-03 04-04 04-05 04-06 04-07 04-08 04-09 04-10

For example: (1) If a user frequently lowers the room temperature


02-01 02-02
its wing tip. It has a large serration on the inner part
02-03 02-04 02-05 02-06 02-07 02-08 02-09 02-10

when turning on the air conditioner, the Active AI Pressure Control and a small serration on the outer part, which are
designed to suit the different wind speeds around
05-01 05-02 05-03 05-04 05-05 05-06 05-07 05-08 05-09 05-10

recognises this pattern. So, when the air conditioner is turned on


again, it automatically lowers the pressure of the inflow refrigerant by
03-01 03-02
them. This combination minimises the air vortex
03-03 03-04 03-05 03-06 03-07 03-08 03-09 03-10

up to 33% and cools up to 20% faster*. (2) However, if there's no need around the wing tip and significantly reduces the
noise generated by the movement of the fan.
06-01 06-02 06-03 06-04 06-05 06-06 06-07 06-08 06-09 06-10

for fast cooling, it saves energy by adjusting the refrigerant pressure


to be higher than normal.
04-01 04-02 04-03 04-04 04-05 04-06 04-07 04-08 04-09 04-10

07-01 07-02 07-03 07-04 07-05 07-06 07-07 07-08 07-09 07-10

05-01 05-02 05-03


Conventional fan
05-04 05-05 05-06 05-07 05-08 05-09 05-10

08-01 08-02 08-03 08-04 08-05 08-06 08-07 08-08 08-09 08-10

06-01 06-02 06-03 06-04 06-05 06-06 06-07 06-08 06-09 06-10

Pressure (P)
09-01 09-02 09-03 09-04 09-05 09-06 09-07 09-08 09-09 09-10
Condensation
High
pressure 07-01 07-02 07-03 07-04 07-05 07-06 07-07 07-08 07-09 07-10

Active AI
10-01 10-02 10-03 10-04 10-05 10-06 10-07 10-08 10-09 10-10
pressure Expansion Compression
control
08-01 08-02 08-03 08-04 08-05 08-06 08-07 08-08 08-09 08-10
(2)
Low
Normal pressure
Evaporation
(1) (2) Energy saving
09-01 09-02 09-03 09-04 09-05 09-06 09-07 09-08 09-09 09-10
(1) Time saving

Enthalpy (h)

10-01 10-02 10-03 10-04 10-05 10-06 10-07 10-08 10-09 10-10

Comparison of vorticity based on the design of the edge**.

33
Room temperature (°C)

Normal
32
Active AI Pressure Control * Only available on models of 33.6kW or less. The shape of the fan may vary by model
31
and region.
30
** Based on internal testing and simulation using a CAE software, Simcenter STAR-
29
CCM+ (v.13.06).
28
27
01-01 01-02 01-03 01-04 01-05 01-06 01-07 01-08 01-09 01-10
26
25
0 5 10 15 20 25 30 35
02-01
40 45
02-02
50
02-03
55
Elapsed time
60
02-04 02-05 02-06 02-07 02-08
Works quietly and efficiently at night
02-09 02-10

(mins.)

Quiet operation
03-01 03-02 03-03 03-04 03-05 03-06 03-07 03-08 03-09 03-10

Normal cooling 50 mins.


A noise control system lowers the level of noise
Fast cooling with
to below 50dB(A)*, which is as quiet as a normal
Temperature
Active AI Pressure Control 40 mins.
04-01
20% faster
04-02 04-03 04-04 04-05 04-06 04-07 04-08 conversation. It has a timer and can be set to
04-09 04-10
change
operate for up to 12 hours. hour

05-01 05-02 05-03 05-04 05-05 05-06 05-07 05-08 05-09 05-10 12 18 00 06 12

Quiet operation
Mode and
06-01 06-02 06-03 06-04 06-05 06-06 06-07 06-08 06-09 06-10
noise level 50dB(A)

07-01 07-02 07-03 07-04 07-05 07-06 07-07 07-08 07-09 07-10

* Based on internal testing of the cooling operation, with the temperature set at 22°C and using Auto mode for 4 hours, at a room temperature of 33°C and an external temperature of * Based on internal testing. Results may vary depending on environmental factors and individual use.
08-01 08-02 08-03 08-04 08-05 08-06 08-07 08-08 08-09 08-10

35°C. The tested model was an AM080AXVGGH/EU connected to AM083NN4DBH1 and AM145NN4DBH1 indoor units with 25m of piping. The elapsed times were measured when the room
temperature reached 25°C. Image simulated, for representational purposes only.

09-01 09-02 09-03 09-04 09-05 09-06 09-07 09-08 09-09 09-10

23 24

10-01 10-02 10-03 10-04 10-05 10-06 10-07 10-08 10-09 10-10
I Key features I Key features
II Comfort II

Optimises the air flow - less friction, less noise


Along with a multi-serration fan, the Samsung DVM S2 has various new technologies that optimise the air flow
inside the unit. So, the air moves smoothly and quickly with less of a vortex or turbulence that creates noise*.
to meet your every need
The location of an air conditioning system can have a significant impact on its performance. So, the
01-01 01-02 01-03 01-04 01-05 01-06 01-07 01-08 01-09 01-10

DVM S2 outdoor unit is designed to give you maximum flexibility, as it will operate effectively in a wide
range of locations and climates.
02-01 02-02 02-03 02-04 02-05 02-06 02-07 02-08 02-09 02-10

Its compact design ensures that you can select the optimum installation location, including inside
03-01 03-02 03-03 03-04 03-05 03-06 03-07 03-08 03-09 03-10

The edgeless,
curved design of the a building. In fact, its long piping, optimised refrigerant distribution and high external static pressure
04-01 04-02 04-03 04-04 04-05 04-06 04-07 04-08 04-09
discharge plenum
04-10

make it the ideal choice for use in high-rise buildings.


enables the fan to pull
air steadily from inside
05-01 05-02 05-03 05-04 05-05 05-06 05-07 05-08 05-09
and gently diffuse
05-10

Even the harshest weather conditions are no problem. It can cool in heat of up to 53ºC and provide
it outside without
warmth in freezing cold conditions of -25ºC, while also optimising its performance to minimise energy
01-01 01-02 01-03 01-04 01-05 01-06 01-07 01-08 01-09 01-10

creating a vortex*. Conventional


use and deliver a consistently comfortable environment.
06-01 06-02 06-03 06-04 06-05 06-06 06-07 06-08 06-09 06-10

02-01 02-02 02-03 02-04 02-05 02-06 02-07 02-08 02-09 02-10

07-01 07-02 07-03 07-04 07-05 07-06 07-07 07-08 07-09 07-10

01-01 01-02 01-03 01-04 01-05 01-06 01-07 01-08 01-09 01-10

Top-class performance in
03-01 03-02 03-03 03-04 03-05 03-06 03-07 03-08 03-09 03-10

extreme conditions
08-01 08-02 08-03 08-04 08-05 08-06 08-07 08-08 08-09 08-10

02-01 02-02 02-03 02-04 02-05 02-06 02-07 02-08 02-09 02-10

Instead of a traditional 04-01 04-02 04-03 04-04 04-05 04-06 04-07 04-08 04-09 04-10

squared bracket, it
has a streamlined
09-01 09-02 09-03 09-04 09-05 09-06 09-07 09-08 09-09 09-10

03-01 03-02 03-03 03-04 03-05 03-06 03-07 03-08 03-09 03-10

Kammtail bracket that 05-01 05-02 05-03 05-04 05-05 05-06 05-07 05-08 05-09 05-10

minimises noise. No matter how extreme the temperature,


10-01 10-02 10-03 10-04 10-05 10-06

04-01
10-07

04-02
10-08

04-03
10-09

04-04
10-10

04-05 04-06 04-07 04-08 04-09 04-10


the high-performance DVM S2 can handle the
conditions. Operating across a wide temperature
06-01 06-02 06-03 06-04 06-05 06-06 06-07 06-08 06-09 06-10

spectrum, it can cool in heat of up to 53°C and


Conventional provide warmth in freezing cold conditions of
05-01 05-02 05-03 05-04 05-05 05-06 05-07 05-08 05-09 05-10

-25°C to ensure a constant and comfortable


07-01 07-02 07-03 07-04 07-05 07-06 07-07 07-08 07-09 07-10

environment.
06-01 06-02 06-03 06-04 06-05 06-06 06-07 06-08 06-09 06-10

08-01 08-02 08-03 08-04 08-05 08-06 08-07 08-08 08-09 08-10

When it’s installed on the rooftop of a building, the


actual temperature around the outdoor units may
As the heat transfer
01-01 01-02 01-03 01-04 01-05 01-06 01-07 01-08 01-09 01-10
07-01 07-02 07-03 07-04 07-05 07-06 07-07 07-08 07-09 07-10

become much higher due to the effects of direct


area has been
09-01 09-02 09-03 09-04 09-05 09-06 09-07 09-08 09-09 09-10

sunlight, the radiant heat of the rooftop and the


increased**, the wind
08-01 08-02 08-03 08-04
02-01 02-02

speed and friction


08-05 08-06
02-03

08-07
02-04

08-08
02-05

08-09
02-06

08-10
02-07 02-08 02-09 02-10
discharged air of other outdoor units. So, delivery
have been reduced of a stable performance in hot environments, is
10-01 10-02 10-03 10-04 10-05 10-06 10-07 10-08 10-09 10-10

accordingly, while still vital.


03-01 03-02 03-03 03-04 03-05 03-06 03-07 03-08 03-09 03-10

09-01 09-02 09-03 09-04 delivering the same


09-05 09-06 09-07 09-08 09-09 09-10

level of performance*.
Conventional
04-01 04-02 04-03 04-04 04-05 04-06 04-07 04-08 04-09 04-10

10-01 10-02 10-03 10-04 10-05 10-06 10-07 10-08 10-09 10-10

05-01 05-02 05-03 05-04 05-05 05-06 05-07 05-08 05-09 05-10

06-01 06-02 06-03 06-04 06-05 06-06 06-07 06-08 06-09 06-10

07-01 07-02 07-03 07-04 07-05 07-06 07-07 07-08 07-09 07-10

* Based on internal testing and simulation using a fluid dynamics software, Ansys CFX.
08-01 08-02 08-03 08-04 08-05 08-06 08-07 08-08 08-09 08-10

Results may vary depending on the actual usage conditions.


** 36.2% increase in a 28kW model and 23.7% increase in a 56kW model.
09-01 09-02 09-03 09-04 09-05 09-06 09-07 09-08 09-09 09-10

Image simulated, for representational purposes only. Image simulated, for representational purposes only.

25 26
10-01 10-02 10-03 10-04 10-05 10-06 10-07 10-08 10-09 10-10
01 01-02 01-03 01-04 01-05 01-06 01-07 01-08 01-09 01-10

I Key features 01-01 01-02 01-03 01-04 01-05 01-06 01-07 I Key features
01-08 01-09 01-10

01 02-02 02-03 02-04 02-05 02-06 02-07 02-08 02-09 02-10

II 02-01 02-02 02-03 02-04


II 02-05 02-06 02-07 02-08 02-09 02-10

01 03-02 03-03 03-04 03-05 03-06 03-07 03-08 03-09 03-10

01 04-02
Smaller footprint, saving valuable space and costs
04-03 04-04 04-05 04-06 04-07 04-08 04-09 04-10
03-01 03-02 03-03 03-04

Install in the optimum location,


03-05 03-06 03-07 03-08 03-09 03-10

04-01 04-02 04-03 04-04


regardless of distance and height
04-05 04-06 04-07 04-08 04-09 04-10

01 05-02 05-03 05-04 05-05 05-06 05-07 05-08 05-09 05-10

The Samsung DVM S2 has a small footprint, so it creates


up to 33% more space*, which can be used for other 05-01 05-02 05-03 05-04 05-05 05-06 05-07 05-08 05-09 05-10

01 06-02 purposes, without compromising on performance. As it is


06-03 06-04 06-05 06-06 06-07 06-08 06-09 06-10
01-01 01-02 01-03 01-04 01-05 01-06
Enjoy more choices when selecting the optimum installation
01-07 01-08 01-09 01-10

possible to install outdoor units inside buildings, especially location. The DVM S2’s long piping length provides the flexibility
high-rise buildings, its compact size means that you can 06-01 06-02 06-03 06-04 for the outdoor unit to be installed almost anywhere, regardless
06-05 06-06 06-07 06-08 06-09 06-10

01 07-02
maximise the area that is available to sell or lease, which
07-03 07-04 07-05 07-06 07-07 07-08 07-09 07-10
02-01 02-02 02-03 02-04 02-05 02-06
of its height or distance from the building. It has a maximum
02-07 02-08 02-09 02-10

directly increases revenue. length that is equivalent to 220 metres (721 feet) between the
07-01 07-02 07-03 07-04 outdoor and indoor units. It can also work efficiently and reliably
07-05 07-06 07-07 07-08 07-09 07-10
Max. length Max. height*
01 08-02 08-03 08-04 08-05 08-06 08-07 08-08 08-09 08-10
03-01 03-02 03-03 03-04 03-05 03-06
at an elevation of up to 110 metres (360 feet)*, which is the
03-07 03-08 03-09 03-10

220m Outdoor
to indoor 110m
32 Story Building**
Other company A Other company B Samsung DVM S2
1,695mm equivalent of 32 stories**.
08-01 08-02 08-03 08-04 08-05 08-06 08-07 08-08 08-09 08-10

04-01 04-02 04-03 04-04 04-05 04-06 04-07 04-08 04-09 04-10
01 09-02 09-03 09-04 09-05 09-06 09-07 09-08 09-09 09-10

09-01 09-02 09-03 09-04 09-05 09-06 09-07 09-08 09-09 09-10

05-01 05-02 05-03 05-04 05-05 05-06 05-07 05-08 05-09 05-10
Max. Height*
The DVM S2 compensates for the long piping distance between 50m
01 10-02 10-03 10-04 10-05 10-06 10-07 10-08 10-09 10-10
Indoor
to indoor
40kW 40kW 40kW
10-01 10-02 10-03 10-04
the outdoor and indoor units by providing balanced refrigerant
10-05 10-06 10-07 10-08 10-09 10-10

06-01 06-02 06-03 06-04 06-05 06-06 distribution. All the individual indoor units deliver capacity
06-07 06-08 06-09 06-10

connection control and automatic refrigerant balancing to


ensure a consistent performance in each unit.
0.95m² 0.94m² 0.71m² 0.23~0.24m²
07-01 07-02 07-03 07-04 07-05 07-06 07-07 07-08 07-09 07-10

Freed up
765mm
930mm
08-01 08-02 08-03 08-04 08-05 08-06 08-07 08-08 08-09 08-10

* Based on the AM140AXVAGH/EU, compared to the same capacity models of other


* When the piping height is over 50m, a PDM (Pressure Drop Modulation) Kit may be required depending on the conditions at the installation location.
01-01 01-02 01-03 01-04 01-05 01-06 01-07 01-08 01-09 01-10

companies.
** Based on the assumption that the height of a story is 3.5m. May vary depending on the location of indoor units.
01-01 01-02 01-03 01-04 01-05 01-06 01-07 01-08 01-09 01-10

09-01 09-02 09-03 09-04 09-05 09-06 09-07 09-08 09-09 09-10

02-01 02-02 02-03 02-04 02-05 02-06 02-07 02-08 02-09 02-10

02-01 02-02 02-03 02-04 02-05 02-06 02-07 02-08 02-09 02-10

Ideal for continuous cooling even in


10-01 10-02 10-03 10-04 10-05 10-06 10-07 10-08 10-09 10-10

03-01 03-02 03-03 03-04 03-05 03-06 03-07 03-08 03-09 03-10

cold weather
03-01 03-02 03-03 03-04 03-05

More flexibility to install between


03-06 03-07 03-08 03-09 03-10

floors in a high-rise building


04-01 04-02 04-03 04-04 04-05 04-06 04-07 04-08 04-09 04-10

04-01 04-02 04-03 04-04 04-05 04-06 04-07 04-08 04-09 04-10

The need for air conditioning tends to rise not only in summer
05-01 05-02 05-03 05-04 05-05 05-06 05-07 05-08 05-09 05-10

but also in spring and autumn. In particular, in rooms that require 05-01 05-02 05-03 05-04 05-05 05-06 05-07 05-08 05-09 05-10

a constant temperature, like a server room, air conditioners are High-rise buildings are usually designed to have outdoor units
installed to ensure a stable cooling operation.
06-01 06-02 06-03 06-04 06-05 06-06 06-07 06-08 06-09 06-10

installed inside them using ductwork, because the height


06-01 06-02 06-03 06-04 06-05 difference to the rooftop is too big. The DVM S2 has up to 110Pa
06-06 06-07 06-08 06-09 06-10

In cool weather, air conditioners can quickly reach the desired external static pressure*, which ensures that it can discharge air
temperature, but then repeatedly turn themselves off and on
07-01 07-02 07-03 07-04 07-05 07-06 07-07 07-08 07-09 07-10

effectively through a much longer


to maintain the temperature. Not only does this consume much 07-01 07-02 07-03 07-04 07-05 07-06 07-07 07-08 duct. So, it gives you an even greater
07-09 07-10

more electricity than continuous cooling, it also reduces the choice when selecting an installation
lifespan of the products and causes discomfort for any occupants
08-01 08-02 08-03 08-04 08-05 08-06 08-07 08-08 08-09 08-10

location inside the building.


due to the fluctuation in temperature. 08-01 08-02 08-03 08-04 08-05 08-06 08-07 08-08 08-09 08-10

The Active Frequency Drive of


09-01 09-02 09-03 09-04 09-05 09-06 09-07 09-08 09-09 09-10

the Samsung DVM S2 enables


Hz
Frequency

09-01 09-02 09-03 09-04 09-05 09-06 09-07 09-08 09-09 09-10

the compressor to operate at


110Pa
14 Conventional

the lowest revolution of 10Hz,


10-01 10-02 10-03 10-04 10-05 10-06 10-07 10-08 10-09 10-10

10 DVM S2
which prevents the operation 10-01 10-02 10-03 10-04 10-05 10-06 10-07 10-08 10-09 10-10

from frequently turning on and


off, so it maintains the indoor
0
Elapsed time
temperature more precisely to
ensure continuous comfort.
* May vary by model and depending on the actual condition
of the ductwork and installation location. For more
* Only available on the DVM S2 HR (Heat recovery) models.
** Optional. professionals.

Image simulated, for representational purposes only. Image simulated, for representational purposes only.

27 28
01-01 01-02 01-03 01-04 01-05 01-06 01-07 01-08 01-09 01-10

I Key features I Key features


02-01 02-02 02-03 02-04 02-05 02-06 02-07 02-08 02-09 02-10

03-01 03-02 03-03 03-04 03-05 03-06 03-07 03-08 03-09 03-10

II Convenience II Convenience
04-01 04-02 04-03 04-04 04-05 04-06 04-07 04-08 04-09 04-10

Greater design flexibility and lower costs


05-01 05-02 05-03 05-04 05-05 05-06 05-07 05-08 05-09 05-10

06-01 06-02 06-03 06-04 06-05 06-06 06-07 06-08 06-09 06-10

The Samsung DVM S2 is equipped with a high-performance sub-cooler to


improve the sub-cooling rate of refrigerant. It requires 28% less refrigerant
on average** as it uses a slimmer liquid pipe*. So, it provides added flexibility
07-01 07-02 07-03 07-04 07-05 07-06 07-07 07-08 07-09 07-10
Outdoor
in designing the entire system, while saving costs on the installation and unit
maintenance of refrigerant and piping materials.
08-01 08-02 08-03 08-04 08-05 08-06 08-07 08-08 08-09 08-10

09-01 09-02 09-03


supplement
09-04 09-05 09-06 09-07 09-08 09-09 09-10

Normal Slimmer Normal Slimmer Average

10-01 10-02
N/A 10-03 10-04
N/A 10-05
- 10-06
- 10-07 10-08 10-09 10-10

4 01-05 01-06 01-07 01-08 01-09 01-10 36% branch


Normal pipe Slimmer pipe of indoor

4 02-05 02-06 02-07 02-08 02-09 02-10

350

4 03-05 03-06 03-07 03-08 03-09 03-10


01-01 01-02 01-03 01-04 01-05 01-06 01-07 01-08 01-09 01-10

* Optional. A slimmer pipe can be used for the main liquid pipe, between an outdoor unit and the first branch of indoor units. The diameter of the slimmer pipe will vary depending on the
diameter of the pipe that is normally used, which is defined in the table above. Not available on the 22.4kW and 28kW models. It may not be available in certain installation conditions, and is
4 04-05

Maintains the optimal amount of refrigerant


04-06 04-07 04-08 04-09 04-10
02-01 02-02 02-03 02-04 02-05 02-06 02-07 02-08 02-09 02-10

** When a slimmer pipe, instead of a normal pipe, is used for the main liquid pipe on the same capacity of air conditioning system, the amount of refrigerant to be charged can be reduced by

4 05-05
to ensure the best performance
05-06 05-07 05-08 05-09 05-10
03-01
28% on average.
03-02 03-03 03-04 03-05 03-06 03-07 03-08 03-09 03-10

Active AI
4 06-05 06-06 06-07 06-08 06-09 06-10

Shortage of refrigerant hinders the outdoor unit’s cooling and heating performance as well as its energy efficiency.
04-01 04-02 04-03 04-04 04-05 04-06 04-07 04-08 04-09 04-10

And, if refrigerant leaks out, due to any error in installation, operation or maintenance, it also impacts global warming
4 07-05 and may even cause the system to stop working. Using Deep Learning technology*, the Active AI refrigerant analysis
07-06 07-07 07-08 07-09 07-10 Less parts. Less effort and cost for servicing.
of the DVM S2 collects and analyses various operational data in real time, and proactively alerts you with an error
05-01 05-02 05-03 05-04 05-05 05-06 05-07 05-08 05-09 05-10

message if the amount of refrigerant is too low. So, an installer or a service engineer can maintain the optimal level of
4 08-05 refrigerant.
08-06 08-07 08-08 08-09 08-10
06-01 06-02 06-03 06-04 06-05 06-06 06-07 06-08 06-09 06-10

The Samsung DVM S2 consists of optimised modular components,


which have fewer parts. In particular, based on its Quality- -23%
4 09-05 09-06 09-07 09-08 09-09 09-10
07-01 based modular design (QMD), the DVM S2 is built with high-quality
07-02 07-03 07-04 07-05 07-06 07-07 07-08 07-09 07-10

modules that have been preselected and preconfigured. So, it


delivers both superior performance and reliability, while also
significantly reducing the number of parts that need servicing.
4 10-05 10-06 10-07 10-08 10-09 10-10

Sensing Hidden layer 1 Hidden layer 2 Decision 08-01 08-02 08-03 08-04 08-05 08-06 08-07 08-08 08-09 08-10

09-01 09-02 09-03 09-04 09-05 09-06 09-07 09-08 09-09 09-10

Previous DVM S2 Previous DVM S2


Quantity of modules Quantity of materials
No. of combinations No. of service components
10-01 10-02 10-03 10-04 10-05 10-06 10-07 10-08 10-09 10-10

This modular design simplifies the entire process of


maintenance and service, as less time and effort is
required to check and fix any issues. And, from the
viewpoint of warehousing, it also saves space as
Correction there is no need to store a lot of parts.

29 30
01 01-02 01-03 01-04 01-05 01-06 01-07 01-08 01-09 01-10
01-01 01-02 01-03 01-04 01-05 01-06 01-07 01-08 01-09 01-10

01 02-02 02-03 02-04 02-05 02-06 02-07 02-08 02-09 02-10

I Key features I Key features


02-01 02-02 02-03 02-04 02-05 02-06 02-07 02-08 02-09 02-10

01 03-02 03-03 03-04 03-05 03-06 03-07 03-08 03-09 03-10


03-01 03-02 03-03 03-04 03-05 03-06 03-07 03-08 03-09 03-10

II Convenience II Convenience
01-0

01 04-02 04-03 04-04 04-05 04-06 04-07 04-08 04-09 04-10


04-01 04-02 04-03 04-04 04-05 04-06 04-07 04-08 04-09 04-10

02-0

01 05-02
Simply and quickly check errors without extra tools
05-03 05-04 05-05 05-06 05-07 05-08 05-09 05-10
05-01 05-02 05-03 05-04 05-05 05-06 05-07
Quick access and ease of service.
05-08 05-09 05-10

03-0


01 06-02 06-03 06-04 06-05 06-06 06-07 06-08 06-09 06-10
06-01 06-02 06-03 06-04 06-05 06-06 06-07 06-08 06-09 06-10

The DVM S2 has an Inverter PBA (Printed Board Assembly) with a one-touch button to simply check errors on the device. The front cover of conventional outdoor units consists of 04-0

Without having to remove the entire front cover, it’s easy to access this button through a small opening in the display multiple pieces, which means it can require a lot of work
01 07-02 window. So, it reduces the service time and effort as it eliminates the need for extra tools and simplifies the service
07-03 07-04 07-05 07-06 07-07 07-08 07-09 07-10
to open them fully. The Samsung DVM S2’s front cover is a
1
07-01 07-02 07-03 07-04 07-05 07-06 07-07 07-08 07-09 07-10

process. single piece, so it’s simple to open and access every part 05-0

inside the outdoor unit, which reduces the time and effort
01 08-02 08-03 08-04 08-05 08-06 08-07 08-08 08-09 08-10
08-01 08-02 08-03 08-04 08-05 08-06 08-07 for servicing.
08-08 08-09 08-10

06-0

3
OK
01 09-02 09-03 09-04 09-05 09-06 09-07 09-08 09-09 09-10
09-01 09-02 09-03 09-04 09-05 09-06 09-07 09-08 09-09 09-10

07-0

01 10-02 10-03 10-04 10-05 10-06 10-07 10-08 10-09 10-10


10-01 10-02 10-03 10-04 10-05 10-06 10-07 10-08
1 10-09 10-10
1
08-0

3
09-0

Need to check

10-0

Conventional
1 piece with a handle
01-01 01-02 01-03 01-04 01-05 01-06 01-07 01-08 01-09 01-10

Conventional process

1 3 U V W
02-01 02-02 02-03 5 02-04 U V W02-05 02-06 02-07 02-08 02-09 02-10

02 01-03 01-04 01-05 01-06 01-07 01-08 01-09 01-10


Inverter Phase Inverter Phase
Checker Checker
x6 x10
Image simulated, for representational purposes only.
U V W U V W

03-01 03-02 03-03 03-04 03-05 03-06 03-07 03-08 03-09 03-10

02 02-03 02-04 02-05 02-06 02-07 02-08 02-09 02-10


Connect them to an

02 03-03 03-04 03-05 03-06 03-07 03-08 03-09 03-10


New process
04-01

04-02 04-03 04-04 04-05 04-06 04-07 04-08

Keeps you comfortable, even


04-09 04-10

05-01 05-02 05-03 05-04 05-05 05-06 05-07 05-08


if there’s a malfunction
05-09 05-10

02 04-03 04-04 04-05 04-06 04-07 04-08 04-09 04-10

02 05-03
Remotely monitor and solve issues
05-04 05-05 05-06 05-07 05-08 05-09 05-10
06-01 06-02 06-03 06-04 06-05 06-06 06-07 06-08 06-09 06-10

When the air conditioning system consists of multiple


Conventional

Samsung DVM S2 outdoor units, its refrigerant regulating


control technology ensures that you can continue Yes Yes
07-01 07-02 07-03 07-04 07-05 07-06 07-07 07-08 07-09 07-10

02 06-03 06-04 06-05 06-06 06-07 06-08 06-09 06-10


working using only one compressor in an emergency.
01-01
With the S-converter, you can access the system using a PC or
01-02 01-03 01-04 01-05 01-06 01-07 01-08 01-09 01-10

So, if every unit except one is not working or getting


laptop* whenever and wherever you like. Its self-diagnosis function 08-01 08-02 08-03 08-04 08-05 08-06 08-07 08-08 serviced and any compressor on the remaining one is
08-09 08-10

02 07-03 automatically monitors its performance and displays an error code if


07-04 07-05 07-06 07-07 07-08 07-09 07-10
working properly, it will keep cooling or heating for up to Yes Yes
02-01
it detects anything abnormal. So, you can then check and address the
02-02 02-03 02-04 02-05 02-06 02-07 02-08 02-09 02-10

8 hours. It ensures that you can maintain a comfortable


issue promptly. 09-01 09-02 09-03 09-04 09-05 09-06 09-07 09-08 indoor environment until the whole system is functioning
09-09 09-10

02 08-03 08-04 08-05 08-06 08-07 08-08 08-09 08-10


properly again. Not
03-01 03-02 03-03 03-04 03-05 03-06

* Windows operating system. A smartphone or tablet PC can also be used in certain regions.
03-07 03-08 03-09 03-10

available
Yes
10-01 10-02 10-03 10-04 10-05 10-06 10-07 10-08 10-09 10-10

02 09-03 09-04 09-05 09-06 09-07 09-08 09-09 09-10

04-01 04-02 04-03 04-04 04-05 04-06 04-07 04-08 04-09 04-10 Conventional
Not
Available available
Yes

Simply restore data for repair and recovery


Available
when one or more
02 10-03 10-04 10-05 10-06 10-07 10-08 10-09 10-10
when
05-01 05-02 05-03 05-04 05-05 05-06 05-07 05-08 05-09 05-10
compressors
on

Not
available
Yes
06-01 06-02 06-03
30
mins.
06-04 06-05 06-06 06-07 06-08 06-09 06-10

If a malfunction occurs, the DVM S2 automatically backs up the last 30 minutes of operational ON ON ON ON
data to make the repair and recovery process easier.
Not
07-01 07-02 07-03 07-04 07-05 07-06 07-07 07-08 07-09 07-10

available
Yes

08-01
Image simulated, for representational purposes only.
08-02 08-03 08-04 08-05 08-06 08-07 08-08 08-09 08-10

31 32
09-01 09-02 09-03 09-04 09-05 09-06 09-07 09-08 09-09 09-10
I Key features Best of VRF and chiller
II Convenience
05 01-06 01-07 01-08 01-09 01-10

Conveniently and safely handle with less effort


05 02-06 02-07 02-08 02-09 02-10

A modular design provides a wide choice of Its modular design and compact size reduces time, cost,
configurations. You can simply and flexibly combine and effort to transport, and install it on site. With a small
The Samsung DVM S2 has various convenient features that help installers and service providers to lift and
05 03-06 03-07 03-08 03-09 03-10

modules and expand capacity from 12 to 320 tonne footprint, it's easy to fit and combine multiple units even
move, and disassemble and assemble it with added safety and less effort. in various ways to optimise energy, or save space, or when there's limited space.
05 04-06 04-07 04-08 04-09 04-10 attain a balance of both.

05 05-06 05-07 05-08 05-09 05-10

05 06-06 06-07 06-08 06-09 06-10

VRF outdoor units usually weigh a lot and can


sometimes be over 300kg. It is obviously very
05 07-06 difficult and dangerous to handle such heavy
07-07 07-08 07-09 07-10

machines, so the Samsung DVM S2 has a removable


indicator to show its centre of weight. It makes
05 08-06 it much safer to lift and move with a crane or a
08-07 08-08 08-09 08-10

forklift as it helps to prevent the unit from becoming


unbalanced and tilting or toppling over.
05 09-06 09-07 09-08 09-09 09-10

05 10-06 10-07 10-08 10-09 10-10

Its advanced technology delivers a consistently higher To maximise operational convenience and the value of
performance and reduces energy wastage. It has a your existing units, an integrated control system lets you
highly efficient BLDC inverter compressor with flash centrally manage both outdoor and indoor units, such as
injection technology and evaporative condenser. the DVM chiller, VRF, and air side equipment.

A Night Silent Mode means it operates at 3 different levels


and works silently at night. It adjusts the speed of the
compressors and fans, so they supply the required cooling,
and a better sound performance.

It can be used for office, retail, hotels, hospitals, educational


institutions, and industrial processes.

Its compatibility, large capacity, and high space


efficiency make it perfect for replacing chillers as it cuts
down maintenance costs and frees up valuable space,
while expanding overall capacity.

-Based on internal lab test

Image simulated, for representational purposes only.

33 34
Simultaneous cooling and heating Increased energy savings

Samsung DVM S Water Air Conditioner System delivers


optimal comfort, efficiency, and performance with
for ultimate comfort Single outdoor units can operate all indoor units in both benefits such as:
The DVM S HR (Heat Recovery) model delivers continuous cooling and heating mode. They can also simultaneously
Save on energy consumption
heating performance using innovative rotational defrost for operate in cooling and heating mode when necessary, DVM S Water is a high-capacity outdoor cooling and and costs with a dual inverter system and high-
reliable warmth and comfort. In addition, it supports more providing more operational freedom. heating system, ideal for large buildings. Unique to performance compressors.
agile operation through simultaneous cooling and heating. other DVM S models, the DVM S Water air conditioning
system uses water as its heat source, which connects Ease of installation minimises
to a cooling tower and boiler. Using a highly efficient effort with a lightweight design, extended piping length,
(Rotational defrost step 3)
compressor and heat exchanger, DVM S Water provides and elevation support.
DVM S can operate continuously in heating mode with effective and reliable performance despite changes
rotational defrost operation. Because the heating mode in the surrounding environment. Its long piping and Monitor system performance
runs for a longer period of time, users can enjoy a more lightweight design also make it easy and economical to effectively with convenient web-based data access and
pleasant environment. Heating Heating Heating Heating Heating
install almost anywhere. management from anywhere.

(Rotational defrost step 1) (Rotational defrost step 2)


Support comfortable living and
working environments based on the combined strengths
of various technologies.

Heating Defrosting Heating Defrosting Heating Heating

The Mode Change Unit (MCU) has an internal on/off


valve that enables fine-tuned control via an electronic
expansion valve (EEV) and sub-cooler. Improved
performance and reduced noise create a pleasant
temperature-controlled environment.

Heating operation for indoor


environments where heating
load occurs due to the out-
door environment.

Cooling operation for


indoor environments
where cooling load occurs
all-year-round due to
devices and lighting that
generate heat.

Sites
Hotel Office Hospital

35 36
Increased energy savings

DVM S Water features advanced PHE technology, which DVM S Water provides extended piping length of up
Samsung DVM S Water features several smart improves heat exchange between refrigerant and water, The simplified yet powerful design of the DVM S to 170m and installation height of up to 50m, offering
technologies that combine to deliver world-class energy thus improving the efficiency, lowering foot print and Water unit eases the installation process. Non-polar businesses more installation options. The piping distance
efficiency for today’s economical and budget-conscious benefiting the environment. communication between indoor and outdoor units is far between outdoor and indoor units, so individual
businesses. With these technologies, DVM S Water boasts promotes easier, safer wiring work. indoor units perform capacity connection control and
up to 8 percent* higher EER than conventional models. Plus, automatic refrigerant equalisation for more balanced
its coefficient of performance (COP) also surpasses the performance between units.
competition with an average 11 percent higher rate.
Water
At 30 HP, the large-unit capacity of DVM S Water
facilitates economical installation with a smaller
footprint and lighter weight—an ideal solution for large
buildings.
The third-generation innovative system, DDI, adopts a dual
inverter compressor system. Both inverter compressors
operate simultaneously, providing compressor longevity
and balanced oil distribution for quick cooling and heating
to save energy and the environment. Plus, the upgraded
flash injection system increases refrigerant flow by up to
20 percent compared to conventional products.
Water

With the DVM S Water air conditioning system's optional


Mode Control Unit (MCU), users can independently switch
mode of each indoor unit. This means users can set
different temperatures for various spaces at the same
Eco-friendly DVM S Water uses geothermal energy as a
time, heating some rooms or areas of the building, while
renewable heat source instead of a cooling tower and
cooling others.
boiler, effectively supporting businesses’ environmental - Based on RandD Analysis
and cost reduction initiatives.

The DVM S Water air conditioning system's louver-less


installation ensures that the outside of the building
remains neat and tidy. Because the system cools with
water, it eliminates the need to install an unsightly louver
to allow air to circulate and to remove excess heat.
- Based on Internal Analysis Its streamlined operation supports easy installation
inside a building, without impacting the integrity of its
architectural design.

- Use elevator for moving

*Based on Samsung Internal Lab Analysis.

37 38
Convenient management

The Samsung DVM S Eco System Air Conditioner delivers


optimal comfort, efficiency, and performance with
DVM S Water’s built-in water flow controller helps regulate features such as:
DVM S Water features a smart management system for the amount of water used to cool and heat the outdoor The VRF-based Samsung DVM S Eco System Air
ultimate convenience. The advanced system facilitates unit. It determines the optimum flow of water based Conditioner combines world-class energy efficiency Save on energy
round-the-clock system monitoring, along with self- on the internal temperature of the space, economising and economy to deliver outstanding performance in a consumption and operational costs with high-
regulating water flow control to ensure peak operation at both the circulation pump’s energy usage and costs. And space-saving design. Supporting up to sixteen indoor performance compressor technology.
all times. because it’s a standard option, businesses can eliminate units, DVM S Eco is a perfectly optimised cooling system
the expense of purchasing a separate water flow control for residences and small buildings. Its lightweight, Enjoy a more peaceful home or
kit. small-scale build enables easy, low-cost installation, work environment with quiet operation, thanks to a
while its uniquely quiet design ensures soothing comfort streamlined fan design.
A smart Auto Commissioning Management (ACM) function and maximum efficiency. Plus, the DVM S Eco line offers a
continually monitors operational performance and wide range of capacities to suit every need. Ease of installation minimises
proactively signals any abnormal operation, so users can effort with a small footprint, and comes in a variety of
quickly address potential problems. And if a malfunction size options.
occurs, the last 30 minutes of operational data are stored
for automatic backup. This lowers the maintenance cost
of periodic inspections and ensures that the system
is always operating. DVM S Water also features an
application with built-in signal contacts to support BACnet,
and LonWorks - two popular building management
systems (BMS).

reliable performance
Samsung DVM S Water is dedicated to supporting
comfortable living and working environments based
on the combined strengths of various technologies.
Featuring central HVAC technology, DVM S Water delivers
stable performance, unaffected by the surrounding
environment. And VRF technology optimises comfort with
individual zone control with on/off temperature setting,
custom air flow rates, and scheduling.

Because of its low noise level, DVM S Water won't disturb


business or residential environments. Its water-cooled
Plate Heat Exchanger eliminates the noise caused by
an outdoor unit fan. In addition, the hermetically sealed
compressor reduces any other noise produced.

39 40
DVM S Eco has one of the world’s largest capacity and most compact side-discharge outdoor unit, which also offers a Its advanced technology radically improves performance and reduces energy wastage. It includes an
high level of energy efficiency. It's ideal for homes or businesses that need plenty of coverage, but have limited space. innovative Digital Inverter Compressor, an optimised heat exchanger with corrugated fins, and highly efficient
fans.

DVM S Eco provides more coverage, while taking up less space. It has the largest capacity in its class of 14HP, enabling
you to create a small footprint VRF solution. So it's ideal for installation in places with limited space.

Corrugated Fin Inverter Scroll Compressor

Featuring advanced refrigerant control technology, DVM S Eco provides the flexibility to be installed almost
DVM S Eco's flash injection provides improved heating anywhere, regardless of its location or distance from
performance at -25°C. It continues to perform even at the building. It has a piping length of up to 160m and can
lower temperatures, providing reliable comfort even reach up to a height of 50m.
when it's freezing.

DVM S Eco is the most compact air conditioner in its class, making it very easy and economical to install and operate
without compromising on performance. It also leaves plenty of space that can be used for other purposes.

Conventional Outdoor Unit Samsung DVM S ECO

41 42
I Engineering

• Outdoor unit machine room temperature simulation

• Indoor unit room temperature simulation

• Air flow distribution simulation

• Specialised simulation of theatre, residential, airport and


machinery room noise.

Always optimising
°C °C

Temperature

Temperature
50 30

The installation location and surrounding conditions 48


27

your air conditioning systems


significantly impact the performance of an air 46

conditioning system. In particular, these days the 44


24
structure of buildings has become more complex
42
and often includes a machine room to hide
21
outdoor units, so they are not visible on the outside. 40

As a result, it is much more important to determine 38


18
in advance if the preferred location will have 36
any impact on the performance of the system.
34 15
Samsung supports CFD simulation and analysis
Discharge air of outdoor units Indoor temperature
to assess the performance of the Samsung
air conditioning system before deciding on its
installation location, and also provides a guidance
report if it is necessary to change it.

dB(A)

Sound pressure level


70

To ensure a more comfortable indoor environment, 65

noise mitigation is now an important factor. So, 60

it’s essential to anticipate possible noises during 55


the building planning stage – before they really
50
happen. Samsung provides noise effect evaluation,
based on the location of indoor and outdoor 45

units, by modeling the actual building design and 40

data about the air conditioning system. After the 35


evaluation, Samsung will suggest the best choice
30
of installation location, and also provide a guidance
Initial planning Optimal planning
report if necessary. after improvement

How to request

In general buildings, the HVAC (Heating, Ventilating


and Air Conditioning) products usually consume
around 30% of the total energy used in the building.
Samsung helps conduct energy simulations to
analyse the economical efficiency of the installed
HVAC systems by evaluating the operation cost of
each product category. This enables developers
and consultants to propose the optimal HVAC
solution to their clients.

43 44
Top Discharge Side Discharge
Heat Pump

8HP | 10HP | 12HP 8HP | 10HP | 12HP 8HP | 10HP | 12HP


4HP | 5HP 6HP 6HP | 8HP | 10HP
12HP | 20HP | 30HP

14HP | 16HP | 18HP | 20HP 14HP | 16HP | 18HP | 20HP 14HP | 16HP | 18HP
8HP 8HP
22HP | 24HP | 26HP | 28HP 22HP | 24HP | 26HP | 28HP | 30HP 20HP | 22HP

12HP | 16HP | 20HP

30HP | 32HP | 34HP 32HP | 34HP 24HP | 26HP 10HP | 12HP | 14HP 10HP | 12HP | 14HP
28HP | 30HP

Product images shown are for representational purpose only, actual product may vary. Product images shown are for representational purpose only, actual product may vary.

45 46
Specification
DVM S ECO Cooling only
• Small footprint and volume

• Flexible piping design

• Low noise level

• Reliable operation

4 ~ 5HP 6 ~ 14HP

Model AM040TXMNKC/EA AM050TXMNKC/EA AM060TXMNKC/EA AM080TXMNNC/EA AM100TXMDNC/EA AM120TXMDNC/EA AM140TXMDNC/EA


Capacity Cooling [kW] 12.10kW 14.00kW 15.50kW 22.40kW 29.00kW 33.60kW 40.00kW
Cooling [Btu/h] 41,300Btu/h 47,800Btu/h 52,900Btu/h 76,400Btu/h 99,000Btu/h 114,600Btu/h 136,500Btu/h
Current Input Cooling 17.50A 19.50A 23.1A 11.70A 11.7A 13.74A 16.48A
Energy Efficiency EER (Cooling) [W/W] 3.36 3.50 3.33 3.25 3.97 3.83 3.78
Performance (nominal) 4.00HP 5.00HP 6.00HP 8.00HP 10.00HP 12.00HP 14.00HP
Power MCA 24.00A 24.00A 30.00A 18.40 (MCA)A 21.5A 23.50 (Max.)A 32.00 (Max.)A
MFA 32.00A 32.00A 40.00A 25.00A 30A 30.00A 40.00A
Power Input Cooling 1) 3.60kW 4.00kW 4.65kW 6.90kW 7.30kW 8.77kW 10.59kW
Compressor Type Inverter Rotary x 1 Inverter Rotary x 1 Twin BLDC Rotary x 1 . Rotary x 1 SSC Scroll x 1 SSC Scroll x 1 SSC Scroll x 1
Output(kW) (4.11)kW (4.11)kW -kW -kW (5.18)kW 6.39kW 6.76kW
Model Name UG5T450FUEJXS2 x 1 UG5T450FUEJXS2 x 1 UG5TK5450FJX x 1 UG5T520FUBJXS1 x 1 DS-GB052FAVB x 1 DS-GB066FAVB x 1 DS-GB070FAVA x 1
Oil Type PVE PVE PVE PVE PVE PVE PVE
Oil (Initial Charge) [cc] 1700cc 1700cc -cc 1700cc 1100cc 1100cc 1100cc
Fan Type Propeller / BLDC Propeller / BLDC Propeller / BLDC Propeller Propeller Propeller Propeller
Motor (Output) [W] 125.0W 125.0W 139.0W 139.0W 244.0W 244.0W 244.0W
Number of Unit (EA) 1EA 1EA 1EA 2EA 2EA 2EA 2EA
Air Flow Rate [㎥/min] 64CMM 64CMM 75CMM 135CMM 190CMM 201CMM 201CMM
Piping Connections Liquid Pipe (Φ, mm) 9.52mm 9.52mm 9.52mm 9.52mm 9.52mm 12.70mm 12.70mm
Liquid Pipe (Φ, inch) 3/8" 3/8" 3/8" 3/8" 3/8" 1/2" 1/2"
Gas Pipe (Φ, mm) 15.88mm 15.88mm 19.05mm 19.05mm 22.22mm 28.58mm 28.58mm
Gas Pipe (Φ, inch) 5/8" 5/8" 3/4" 3/4" 7/8" 1 1/8" 1 1/8"
Installation Max. Length [m] 70m 70m 50m 100m 160m 160m 160m
Installation Max. Height [m] 50.0m 30.0m 30m 30.0m 50.0m 50.0m 50.0m
Transmission Cable 0.75 0.75 0.75 ~ 1.5 0.75 0.75 0.75 0.75
Refrigerant Type R410A R410A R410A R410A R410A R410A R410A
Factory Charging (kg) 2.00kg 2.00kg 2.50kg 3.70kg 3.70kg 4.30kg 4.80kg
Sound Sound Pressure 52.0dBA 55.0dBA 55dBA 59.0dBA 58.0dBA 61.0dBA 62.0dBA
Operating Temp. Range Cooling (℃) -5.0 ~ 52.0℃ -5.0 ~ 52.0℃ -5.0 ~ 48.0℃ -5.0 ~ 48.0℃ -5.0 ~ 48.0℃ -5.0 ~ 48.0℃ -5.0 ~ 48.0℃
External Dimension (Outdoor Unit) Net Weight (kg) 76.0kg 83.5kg 84kg 115.0kg 143.0kg 153.0kg 160.0kg
Shipping Weight (kg) 79.0kg 89.0kg 89.5kg 125.0kg 156.0kg 166.0kg 173.0kg
Net Dimensions (WxHxD) (mm) 940 x 998 x 330mm 940 x 998 x 330mm 940 x 998 x 330mm 940 x 1,420 x 330mm 940 x 1,630 x 460mm 940 x 1,630 x 460mm 940 x 1,630 x 460mm
Shipping Dimensions (WxHxD) (mm) 995 x 1,136 x 426mm 995 x 1,136 x 426mm 995 x 1,096 x 426mm 995 x 1,578 x 426mm 1,020 x 1,820 x 575mm 1,020 x 1,820 x 575mm 1,020 x 1,820 x 575mm
Power Supply (Outdoor Unit) [Φ, #, V, Hz] 1, 2, 220-240, 50/60 1, 2, 220-240, 50/60 1, 2, 220-240, 50/60 3,4,380-415,50/60Hz 3, 4, 380-415, 50/60 3, 4, 380-415, 50/60 3, 4, 380-415, 50/60

Note:

1) 1) Nominal cooling capacities are based on indoor temperature : 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m
2) Nominal heating capacities are based on indoor temperature : 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m
3) Sound pressure was acquired in a dead room. Thus, actual noise level may be different depending on the installation conditions.

47 48
Specification
DVM ECO Heat pump

• Small footprint and volume

• Flexible piping design

• Low noise level

• Reliable operation

4 ~ 5HP 6 ~ 14HP

Attribute/Model code AM060TXMDEH/TL AM080MXMDGH/TL AM100KXMDGH/TL AM120KXMDGH/TL AM140KXMDGH/TL


1, 2, 220-240, 50 3,4,380-415,50 3,4,380-415,50 3,4,380-415,50 3,4,380-415,50
System Mode Heat pump Heat pump Heat pump Heat pump Heat pump
Performance (nominal) 6 8 10 12 14
15.5 22.4 28 33.5 40
52,900 76,400 95,500 114,300 136,500
Capacity
18 22.4 31.5 37.5 45.0
61,400 76,600 1,07,500 128,000 153,500
4.31 6.9 7 8.38 10.00
Power input (Nominal)
4.39 5.8 6.17 7.50 9.57
21 11.7 11.51 13.74 16.48
Current input (Nominal)
20.2 9.5 10.38 12.23 15.55
EER (Nominal cooling) 3.6 3.25 4 4 4
COP (Nominal heating) 4.1 3.86 5.1 5 4.7
Compressor Type Twin BLDC rotary Twin BLDC rotary Scroll inverter Scroll inverter Scroll inverter
9.52 9.52 9.52 12.7 12.7
19.05 19.05 22.22 28.58 28.58
Piping connections
150 m 100 160 160 160
50 m 30 50 50 50
Field wiring Transmission cable 0.75 ~ 1.5 0.75 ~ 1.5 0.75 ~ 1.5 0.75 ~ 1.5 0.75 ~ 1.5
Type R410A R410A R410A R410 R410
Refrigerant
Factory charging (kg) 3.3 3.7 3.7 4.3 4.8
Sound Sound pressure (dBA) 55 59 58 59 62
Net weight(kg) 101 115 145 155 162
Shipping weight (kg) 110 125 158 168 175
Net dimensions (WxHxD) (mm) 940 x 1,210 x 330 940 x 1,420 x 330 940x1630x460 940x1630x460 940x1630x460
External dimension (Outdoor unit)
Net dimensions (WxHxD) (cm) 94 x 121 x 33 94 x 142 x 33 94 x 163 x 46 94 x 163 x 46 94 x 163 x 46
Shipping dimensions (WxHxD) (mm) 995 x 1,388 x 426 995 x 1,578 x 426 1020x1820x575 1020x1820x575 1020x1820x575
Shipping dimensions (WxHxD) (cm) 99.5 x 138.8 x 42.6 99.5 x 157.8 x 42.6 102 x 182 x 57.5 102 x 182 x 57.5 102 x 182 x 57.5
-5.0 ~ 48.0 -5.0 ~ 48.0 -5.0 ~ 48.0 -5.0 ~ 48.0 -5.0 ~ 48.0
Operating temp. range
-20.0 ~ 24.0 -20.0 ~ 24.0

Note:

1) Nominal cooling capacities are based on indoor temperature : 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m
2) Nominal heating capacities are based on indoor temperature : 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m
3) Sound pressure was acquired in a dead room. Thus, actual noise level may be different depending on the installation conditions.

49 50
Specification
DVM S2 Heat pump

• Less refrigerent

• High Performance

Attribute/Model code

3,4,380~415,50/60 3,4,380~415,50/60 3,4,380~415,50/60 3,4,380~415,50/60 3,4,380~415,50/60 3,4,380~415,50/60 3,4,380~415,50/60 3,4,380~415,50/60 3,4,380~415,50/60

Heat pump Heat pump Heat pump Heat pump Heat pump Heat pump Heat pump Heat pump Heat pump
System Mode
8 10 12 16 18 20 22 24

22.4 28.0 33.6 40.0 45.0 50.4 56.0 61.6 67.2

Cooling 1) [BTU 76384.0 95480.0 114576.0 136400.0 153450.0 171864.0 190960.0 210056.0 229152.0
Capacity
25.2 31.5 37.8 45.0 50.4 56.7 63.0 69.3 75.6

Heating 1) [BTU 85932.0 107415.0 128898.0 153450.0 171864.0 193347.0 214830.0 236313.0 257796.0

4.84 6.29 8.77 10.68 11.5 13.94 12.18 16.2 16.8


Power input (nominal)
4.8 6.3 8.9 11.08 11.58 13.5 13.55 15.06 16.61

Cooling 1) [A 7.6 9.9 13.8 16.8 18 21.7 19.6 26.2 26.4


Current input (nominal)
Heating 1) [A 7.5 9.9 14.1 16.9 18.2 21.2 21.3 23.7 26.1

EER (nominal cooling) 4.63 4.45 3.83 3.75 3.91 3.62 4.60 3.80 4.00

COP (nominal heating) 5.25 5.00 4.25 4.06 4.35 4.20 4.65 4.60 4.55

Compressor Type Inverter scroll Inverter scroll Inverter scroll Inverter scroll Inverter scroll Inverter scroll Inverter scroll Inverter scroll Inverter scroll

Fan 80 80 110 80 110 110 110 110 80

9.52 9.52 12.7 12.7 12.7 15.88 15.88 15.88 15.88

Gas pipe [ 19.05 22.22 28.58 28.58 28.58 28.58 28.58 28.58 34.92
Piping connections
220 220 220 220 220 220 220 220 220

110 110 110 110 110 110 110 110 110


Field wiring 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75
Type R410A R410A R410A R410A R410A R410A R410A R410A R410A
Refrigerant
5.5 5.5 6.2 7 8 8 10.5 10.5 14
Sound 56 57 61 63 61 61 61 64 65

171 183 187.2 199.9 234 234 259.1 292.1 317

185 197 201.2 213.9 251 251 276.1 309.1 334

External dimensions Net dimensions (WXHXD 930 x 1,695 x 765 930 x 1,695 x 765 930 x 1,695 x 765 930 x 1,695 x 765 1,295 x 1,695 x 765 1,295 x 1,695 x 765 1,295 x 1,695 x 765 1,295 x 1,695 x 765 1,295 x 1,695 x 765
(outdoor unit) Net dimensions (WXHXD 93 x 169.5 x 76.5 93 x 169.5 x 76.5 93 x 169.5 x 76.5 93 x 169.5 x 76.5 129.5 x 169.5 x 76.5 129.5 x 169.5 x 76.5 129.5 x 169.5 x 76.5 129.5 x 169.5 x 76.5 129.5 x 169.5 x 76.5

Shipping dimensions (WXHXD 998 x 1,887 x 829 998 x 1,887 x 829 998 x 1,887 x 829 998 x 1,887 x 829 1,363 x 1,887 x 829 1,363 x 1,887 x 829 1,363 x 1,887 x 829 1,363 x 1,887 x 829 1,363 x 1,887 x 829

Shipping dimensions (WXHXD 99.8 x 188.7 x 82.9 99.8 x 188.7 x 82.9 99.8 x 188.7 x 82.9 99.8 x 188.7 x 82.9 136.3 x 188.7 x 82.9 136.3 x 188.7 x 82.9 136.3 x 188.7 x 82.9 136.3 x 188.7 x 82.9 136.3 x 188.7 x 82.9

-5 ~ 53 -5 ~ 53 -5 ~ 53 -5 ~ 53 -5 ~ 53 -5 ~ 53 -5 ~ 53 -5 ~ 53 -5 ~ 53
Operating temp. range
-25 ~ 24 -25 ~ 24 -25 ~ 24 -25 ~ 24 -25 ~ 24 -25 ~ 24 -25 ~ 24 -25 ~ 24 -25 ~ 24

2) Sound pressure level is obtained in an anechoic room.


1) Performances are based on the following test conditions.

51 52
Specification
DVM S2 Heat pump

• Less refrigerent

• High Performance

Attribute/Model code

3,4,380~415,50/60 3,4,380~415,50/60 3,4,380~415,50/60 3,4,380~415,50/60 3,4,380~415,50/60

Heat pump Heat pump Heat pump Heat pump Heat pump
System Mode
26 28 30 32 34

72.8 78.6 84.0 89.6 95.2

Cooling 1) [BTU 248248.0 268026.0 286440.0 305536.0 324632.0


Capacity
78.4 78.4 94.5 95.2 95.2

Heating 1) [BTU 267344.0 267344.0 322245.0 324632.0 324632.0

Power input 18.86 23.93 22.7 27.57 31.73


(nominal) 17.19 17.61 20.54 21.15 21.63

30 38 35.5 43.4 49.9


Current input (nominal)
27 27.7 32.3 33.3 34

EER (nominal cooling) 3.86 3.28 3.70 3.25 3.00

COP (nominal heating) 4.56 4.45 4.60 4.50 4.40

Compressor Type Inverter scroll Inverter scroll Inverter scroll Inverter scroll Inverter scroll

Fan 80 80 80 80 80

19.05 19.05 19.05 19.05 19.05

Gas pipe [ 34.92 34.92 34.92 34.92 34.92


Piping connections
220 220 220 220 220

110 110 110 110 110

Field wiring 0.75 0.75 0.75 0.75 0.75

Type R410A R410A R410A R410A R410A


Refrigerant
14 14 15.5 15.5 15.5

Sound Sound pressure [DB 65 65 65 65 66

317 317 390 390 390

334 334 416.2 416.2 416.2

External dimensions Net dimensions (WXHXD 1,295 x 1,695 x 765 1,295 x 1,695 x 765 1,860 x 1,695 x 765 1,860 x 1,695 x 765 1,860 x 1,695 x 765
(outdoor unit) Net dimensions (WXHXD 129.5 x 169.5 x 76.5 129.5 x 169.5 x 76.5 186 x 169.5 x 76.5 186 x 169.5 x 76.5 186 x 169.5 x 76.5

Shipping dimensions (WXHXD 1,363 x 1,887 x 829 1,363 x 1,887 x 829 1,928 x 1,887 x 829 1,928 x 1,887 x 829 1,928 x 1,887 x 829

Shipping dimensions (WXHXD 136.3 x 188.7 x 82.9 136.3 x 188.7 x 82.9 192.8 x 188.7 x 82.9 192.8 x 188.7 x 82.9 192.8 x 188.7 x 82.9

-5 ~ 53 -5 ~ 53 -5 ~ 53 -5 ~ 53 -5 ~ 53
Operating temp. range
-25 ~ 24 -25 ~ 24 -25 ~ 24 -25 ~ 24 -25 ~ 24

2) Sound pressure level is obtained in an anechoic room.


1) Performances are based on the following test conditions.

53 54
Combination table Heat pump

System model Capacity of single unit HP


Capacity (HP)
Code No of modules 8HP 10HP 12HP 14HP 16HP 18HP 20HP 22HP 24HP 26HP 28HP 30HP 32HP 34HP
8HP AM080 1 1
10HP AM100 1 1
12HP AM120 1 1
14HP AM140 1 1
16HP AM160 1 1
18HP AM180 1 1
20HP AM200 1 1
22HP AM220 1 1
24HP AM240 1 1
26HP AM260 1 1
28HP AM280 1 1
30HP AM300 1 1
32HP AM320 1 1
34HP AM340 1 1
36HP AM360 2 1 1
38HP AM380 2 1 1
40HP AM400 2 1 1
42HP AM420 2 1 1
44HP AM440 2 2
46HP AM460 2 1 1
48HP AM480 2 1 1
50HP AM500 2 1 1
52HP AM520 2 2
54HP AM540 2 1 1
56HP AM560 2 1 1
58HP AM580 2 1 1
60HP AM600 2 1 1
62HP AM620 2 1 1
64HP AM640 2 2
66HP AM660 2 1 1
68HP AM680 2 2
70HP AM700 3 1 2
72HP AM720 3 1 1 1
74HP AM740 3 2 1
76HP AM760 3 1 2
78HP AM780 3 3
80HP AM800 3 2 1
82HP AM820 3 1 2
84HP AM840 3 3
86HP AM860 3 2 1
88HP AM880 3 1 1 1
90HP AM900 3 1 2
92HP AM920 3 1 1 1
94HP AM940 3 1 2
96HP AM960 3 1 2
98HP AM980 3 2 1

55 56
Specification
DVM S2 Cooling only

• Less refrigerent

• High Performance

Model AM080AXVANC/EA AM100AXVANC/EA AM120AXVANC/EA AM140AXVANC/EA AM160AXVANC/EA AM180AXVANC/EA AM200AXVANC/EA


Power Supply (Outdoor Unit) [Φ, #, V, Hz] 3,4,380~415,50/60 3,4,380~415,50/60 3,4,380~415,50/60 3,4,380~415,50/60 3,4,380~415,50/60 3,4,380~415,50/60 3,4,380~415,50/60
Capacity (Rated) Cooling [kW] 22.4kW 28kW 33.6kW 40kW 45kW 50.4kW 56kW
Current Input (Rated) Cooling 7.6A 9.9A 13.8A 16.8A 18A 21.7A 19.6A
Energy Efficiency EER (Cooling) [W/W] 4.63 4.45 3.83 3.75 3.91 3.62 4.60
Heat Exchanger Type Fin & Tube Fin & Tube Fin & Tube Fin & Tube Fin & Tube Fin & Tube Fin & Tube
Material (Fin) Al Al Al Al Al Al Al
Material (Tube) Cu Cu Cu Cu Cu Cu Cu
Fin Treatment Anti-corrosion Anti-corrosion Anti-corrosion Anti-corrosion Anti-corrosion Anti-corrosion Anti-corrosion
Performance (nominal) 8HP 10HP 12HP 14HP 16HP 18HP 20HP
Power MCA 19A 23A 26A 29A 34A 39.2A 43A
MFA 25A 32A 32A 32A 40A 50A 50A
Power Input (Rated) Cooling 4.84kW 6.29kW 8.77kW 10.68kW 11.5kW 13.94kW 12.18kW
Compressor Type Inverter Scroll x 1 Inverter Scroll x 1 Inverter Scroll x 1 Inverter Scroll x 1 Inverter Scroll x 1 Inverter Scroll x 1 Inverter Scroll x 1
Output(kW) 4.39 x 1kW 6.67 x 1kW 6.67 x 1kW 6.67 x 1kW 8.93 x 1kW 8.93 x 1kW 8.93 x 1kW
Model Name DS2GR7046FV* x 1 DS4GR7066FV* x 1 DS4GR7066FV* x 1 DS4GR7066FV* x 1 DS4GM7090FV* x 1 DS4GM7090FV* x 1 DS4GM7090FV* x 1
Oil Type PVE PVE PVE PVE PVE PVE PVE
Oil (Initial Charge) [cc] 900 x 1cc 1,100 x 1cc 1,100 x 1cc 1,100 x 1cc 1,400 x 1cc 1,400 x 1cc 1,400 x 1cc
Fan Motor (Output) [W] 630W 630W 630W 630W 620W 620W 620W
Air Flow Rate [㎥/min] 174CMM 188CMM 205CMM 201CMM 293CMM 313CMM 342CMM
Air Flow Rate [l/s] 2906L/S 3138L/S 3425L/S 3346L/S 4880L/S 5217L/S 5699L/S
External Static Pressure [mmAq] 11mmAq 11mmAq 8mmAq 8mmAq 11mmAq 11mmAq 11mmAq
External Static Pressure [Pa] 110Pa 110Pa 80Pa 80Pa 110Pa 110Pa 110Pa
Piping Connections Liquid Pipe Type Braze Connection Braze Connection Braze Connection Braze Connection Braze Connection Braze Connection Braze Connection
Liquid Pipe (Φ, mm) 9.52mm 9.52mm 12.7mm 12.7mm 12.7mm 15.88mm 15.88mm
Liquid Pipe (Φ, inch) 3/8" 3/8" 1/2" 1/2" 1/2" 5/8" 5/8"
Gas Pipe Type Braze Connection Braze Connection Braze Connection Braze Connection Braze Connection Braze Connection Braze Connection
Gas Pipe (Φ, mm) 19.05mm 22.22mm 28.58mm 28.58mm 28.58mm 28.58mm 28.58mm
Gas Pipe (Φ, inch) 3/4" 7/8" 1 1/8" 1 1/8" 1 1/8" 1 1/8" 1 1/8"
Installation Max. Length [m] 220m 220m 220m 220m 220m 220m 220m
Installation Max. Height [m] 50(110)/40(110)m 50(110)/40(110)m 50(110)/40(110)m 50(110)/40(110)m 50(110)/40(110)m 50(110)/40(110)m 50(110)/40(110)m
Refrigerant Type R410A R410A R410A R410A R410A R410A R410A
Factory Charging (kg) 5.50kg 5.50kg 6.20kg 7.00kg 8.00kg 8.00kg 10.50kg
Sound Sound Pressure 55dBA 56dBA 60dBA 63dBA 59dBA 59dBA 61dBA
Sound Power Level 75dBA 78dBA 81dBA 85dBA 81dBA 81dBA 84dBA
External Dimension (Outdoor Unit) Net Weight (kg) 173.0kg 183.0kg 186.0kg 202.0kg 237.0kg 237.0kg 264.0kg
Shipping Weight (kg) 187.0kg 197.0kg 200.0kg 216.0kg 254.0kg 254.0kg 281.0kg
Net Dimensions (WxHxD) (mm) 930 x 1,695 x 765mm 930 x 1,695 x 765mm 930 x 1,695 x 765mm 930 x 1,695 x 765mm 1,295 x 1,695 x 765mm 1,295 x 1,695 x 765mm 1,295 x 1,695 x 765mm
Shipping Dimensions (WxHxD) (mm) 998 x 1,887 x 829mm 998 x 1,887 x 829mm 998 x 1,887 x 829mm 998 x 1,887 x 829mm 1,363 x 1,887 x 829mm 1,363 x 1,887 x 829mm 1,363 x 1,887 x 829mm

2) Sound pressure level is obtained in an anechoic room.


1) Performances are based on the following test conditions.

57 58
Specification
DVM S2 Cooling only

• Less refrigerent

• High Performance

Model AM220AXVANC/EA AM240AXVANC/EA AM260AXVANC/EA AM280AXVANC/EA AM300AXVANC/EA AM320AXVANC/EA AM340AXVANC/EA


Power Supply (Outdoor Unit) [Φ, #, V, Hz] 3,4,380~415,50/60 3,4,380~415,50/60 3,4,380~415,50/60 3,4,380~415,50/60 3,4,380~415,50/60 3,4,380~415,50/60 3,4,380~415,50/60
Capacity (Rated) Cooling [kW] 61.6kW 67.2kW 72.8kW 78.6kW 84kW 89.6kW 95.2kW
Current Input (Rated) Cooling 26.2A 26.4A 30A 38A 42.1A 43.4A 49.9A
Energy Efficiency EER (Cooling) [W/W] 3.80 4.00 3.86 3.28 3.13 3.25 3.00
Heat Exchanger Type Fin & Tube Fin & Tube Fin & Tube Fin & Tube Fin & Tube Fin & Tube Fin & Tube
Material (Fin) Al Al Al Al Al Al Al
Material (Tube) Cu Cu Cu Cu Cu Cu Cu
Fin Treatment Anti-corrosion Anti-corrosion Anti-corrosion Anti-corrosion Anti-corrosion Anti-corrosion Anti-corrosion
Performance (nominal) 22HP 24HP 26HP 28HP 30HP 32HP 34HP
Power MCA 44.6A 55A 60A 61A 68.6A 68.6A 73A
MFA 50A 63A 75A 75A 75A 75A 80A
Power Input (Rated) Cooling 16.2kW 16.8kW 18.86kW 23.93kW 26.84kW 27.57kW 31.73kW
Compressor Type Inverter Scroll x 2 Inverter Scroll x 2 Inverter Scroll x 2 Inverter Scroll x 2 Inverter Scroll x 2 Inverter Scroll x 2 Inverter Scroll x 2
Output(kW) 6.67 x 2kW 6.67 x 2kW 6.67 x 2kW 6.67 x 2kW 8.93 x 2kW 8.93 x 2kW 8.93 x 2kW
Model Name DS4GR7066FV* x 2 DS4GR7066FV* x 2 DS4GR7066FV* x 2 DS4GR7066FV* x 2 DS4GM7090FV* x 2 DS4GM7090FV* x 2 DS4GM7090FV* x 2
Oil Type PVE PVE PVE PVE PVE PVE PVE
Oil (Initial Charge) [cc] 1,100 x 2cc 1,100 x 2cc 1,100 x 2cc 1,100 x 2cc 1,400 x 2cc 1,400 x 2cc 1,400 x 2cc
Fan Motor (Output) [W] 620W 620W 620W 620W 620W 630W 630W
Air Flow Rate [㎥/min] 330CMM 344CMM 353CMM 353CMM 353CMM 412CMM 412CMM
Air Flow Rate [l/s] 5504L/S 5741L/S 5882L/S 5882L/S 5882L/S 6860L/S 6860L/S
External Static Pressure [mmAq] 11mmAq 8mmAq 8mmAq 8mmAq 8mmAq 8mmAq 8mmAq
External Static Pressure [Pa] 110Pa 80Pa 80Pa 80Pa 80Pa 80Pa 80Pa
Piping Connections Liquid Pipe Type Braze Connection Braze Connection Braze Connection Braze Connection Braze Connection Braze Connection Braze Connection
Liquid Pipe (Φ, mm) 15.88mm 15.88mm 19.05mm 19.05mm 19.05mm 19.05mm 19.05mm
Liquid Pipe (Φ, inch) 5/8" 5/8" 3/4" 3/4" 3/4" 3/4" 3/4"
Gas Pipe Type Braze Connection Braze Connection Braze Connection Braze Connection Braze Connection Braze Connection Braze Connection
Gas Pipe (Φ, mm) 28.58mm 34.92mm 34.92mm 34.92mm 34.92mm 34.92mm 34.92mm
Gas Pipe (Φ, inch) 1 1/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8"
Installation Max. Length [m] 220m 220m 220m 220m 220m 220m 220m
Installation Max. Height [m] 50(110)/40(110)m 50(110)/40(110)m 50(110)/40(110)m 50(110)/40(110)m 50(110)/40(110)m 50(110)/40(110)m 50(110)/40(110)m
Refrigerant Type R410A R410A R410A R410A R410A R410A R410A
Factory Charging (kg) 10.50kg 11.00kg 11.00kg 11.00kg 11.00kg 12.50kg 12.50kg
Sound Sound Pressure 64dBA 65dBA 65dBA 65dBA 65dBA 65dBA 66dBA
Sound Power Level 86dBA 87dBA 87dBA 87dBA 87dBA 87dBA 88dBA
External Dimension (Outdoor Unit) Net Weight (kg) 298.0kg 310.0kg 310.0kg 310.0kg 322.0kg 375.0kg 375.0kg
Shipping Weight (kg) 315.0kg 327.0kg 327.0kg 327.0kg 339.0kg 401.0kg 401.0kg
Net Dimensions (WxHxD) (mm) 1,295 x 1,695 x 765mm 1,295 x 1,695 x 765mm 1,295 x 1,695 x 765mm 1,295 x 1,695 x 765mm 1,295 x 1,695 x 765mm 1,860 x 1,695 x 765mm 1,860 x 1,695 x 765mm
Shipping Dimensions (WxHxD) (mm) 1,363 x 1,887 x 829mm 1,363 x 1,887 x 829mm 1,363 x 1,887 x 829mm 1,363 x 1,887 x 829mm 1,363 x 1,887 x 829mm 1,928 x 1,887 x 829mm 1,928 x 1,887 x 829mm

2) Sound pressure level is obtained in an anechoic room.


1) Performances are based on the following test conditions.

59 60
Combination table Cooling only

System model Capacity of single unit HP


Capacity (HP)
Code No. of modules 8HP 10HP 12HP 14HP 16HP 18HP 20HP 22HP 24HP 26HP 28HP 30HP 32HP 34HP
8HP AM080 1 1
10HP AM100 1 1
12HP AM120 1 1
14HP AM140 1 1
16HP AM160 1 1
18HP AM180 1 1
20HP AM200 1 1
22HP AM220 1 1
24HP AM240 1 1
26HP AM260 1 1
28HP AM280 1 1
30HP AM300 1 1
32HP AM320 1 1
34HP AM340 1 1
36HP AM360 2 1 1
38HP AM380 2 1 1
40HP AM400 2 2
42HP AM420 2 1 1
44HP AM440 2 2
46HP AM460 2 1 1
48HP AM480 2 1 1
50HP AM500 2 1 1
52HP AM520 2 1 1
54HP AM540 2 1 1
56HP AM560 2 1 1
58HP AM580 2 1 1
60HP AM600 2 2
62HP AM620 2 1 1
64HP AM640 2 2
66HP AM660 2 1 1
68HP AM680 2 2
70HP AM700 3 2 1
72HP AM720 3 1 1 1
74HP AM740 3 2 1
76HP AM760 3 1 1 1
78HP AM780 3 1 1 1
80HP AM800 3 1 1 1
82HP AM820 3 1 2
84HP AM840 3 1 2
86HP AM860 3 1 2
88HP AM880 3 1 2
90HP AM900 3 3
92HP AM920 3 2 1
94HP AM940 3 2 1
96HP AM960 3 1 1 1
98HP AM980 3 1 2

61 62
Specification
DVM heat recovery

• DSI (Dual Smart Inverter) system

• Smart management

• Flexible installation

• Comfortable and reliable operation

Attribute/Model code

3,4,380-415,50
System Mode Heat recovery
8 10 12 14 16 18 20 22 24 26 28 30
Capacity 22.4 28 33.6 40 45 50.4 56 61.6 67.2 72.8 78.6 84
76,400 95,500 114,600 136,500 153,500 172,000 191,100 210,200 229,300 248,400 268,200 286,600
25.2 31.5 37.8 45 50.4 56.7 63 69.3 75.6 81.9 88.2 94.5
86,000 107,500 129,000 153,500 170,600 193,500 215,000 236,500 258,000 279,500 301,000 322,500
Power input (Nominal) 5.0 6.8 8.4 8.9 11.0 12.88 15.19 17.35 18.61 20.92 24.49 22.7
5.1 6.7 8.7 9.5 11.5 11.9 13.9 16.7 13.2 15.17 15.53 20.59
Current input (Nominal) 8 10.9 13.5 14.3 17.6 20.7 24.4 27.8 29.8 33.6 39.3 36.4

8.2 10.7 14 15.2 18.4 19.1 22.3 26.8 21.2 24.3 24.9 33
EER (Nominal cooling) 4.48 4.12 4 4.49 4.09 3.91 3.69 3.55 3.6 3.5 3.2 3.7
COP (Nominal heating) 4.94 4.7 4.34 4.74 4.38 4.76 4.53 4.15 5.1 4.8 4.7 4.6
Compressor Type Scroll inverter
Fan External static pressure (Min / Std / Max) 78.45 Pa -

Piping connections 9.52 9.52 12.70 12.70 12.70 15.88 15.88 15.88 15.88 19.05 19.05 19.05
19.05 22.22 28.58 28.58 28.58 28.58 28.58 28.58 34.92 34.92 34.92 34.92
200(220) 200(220) 200(220) 200(220) 200(220) 200(220) 200(220) 200(220) 200(220) 200(220) 200(220) 200(220)
110.0(40.0) 110.0(40.0) 110.0(40.0) 110.0(40.0) 110.0(40.0) 110.0(40.0) 110.0(40.0) 110.0(40.0) 50(110)/40(110) 50(110)/40(110) 50(110)/40(110) 50(110)/40(110)
Field wiring Transmission cable 0.75 ~ 1.5 0.75 ~ 1.5 0.75 ~ 1.5 0.75 ~ 1.5 0.75 ~ 1.5 0.75 ~ 1.5 0.75 ~ 1.5 0.75 ~ 1.5 - - - -
Refrigerant Type R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A
Factory charging (kg) 5.50 5.20 5.50 7.70 7.40 8.70 8.40 8.40 14.00 14.00 14.00 14.00
Sound Sound pressure (dBA) 57 58 62 61 63 64 65 67 69 69 69 69
External dimension (Outdoor unit) Net weight (kg) 189.5 189.5 189.5 239.0 282.0 304.0 304.0 304.0 350.0 358.0 358.0 358.0
Shipping weight (kg) 205.5 205.5 205.5 258.0 301.0 323.0 323.0 323.0 372.0 380.0 380.0 380.0
Net dimensions (WxHxD) (mm) 880 x 1695 x 765 880 x 1695 x 765 880 x 1695 x 765 1295 x 1695 x 765 1295 x 1695 x 765 1295 x 1695 x 765 1295 x 1695 x 765 1295 x 1695 x 765 1295x1795x765 1295x1795x765 1295x1795x765 1295x1795x765
Net dimensions (WxHxD) (cm) 880 x 169.5 x 76.5 880 x 169.5 x 76.5 880 x 169.5 x 76.5 129.5 x 169.5 x 76.5 129.5 x 169.5 x 76.5 129.5 x 169.5 x 76.5 129.5 x 169.5 x 76.5 129.5 x 169.5 x 76.5 129.5 x 179.5 x 76.5 129.5 x 179.5 x 76.5 129.5 x 179.5 x 76.5 129.5 x 179.5 x 76.5
Shipping dimensions (WxHxD) (mm) 948 x 1887 x 832 948 x 1887 x 832 948 x 1887 x 832 1363 x 1887 x 832 1363 x 1887 x 832 1363 x 1887 x 832 1363 x 1887 x 832 1363 x 1887 x 832 1363x1987x832 1363x1987x832 1363x1987x832 1363x1987x832
Shipping dimensions (WxHxD) (cm) 94.8 x 188.7 x 83.2 94.8 x 188.7 x 83.2 94.8 x 188.7 x 83.2 136.3 x 188.7 x 83.2 136.3 x 188.7 x 83.2 136.3 x 188.7 x 83.2 136.3 x 188.7 x 83.2 136.3 x 188.7 x 83.2 136.3 x 188.7 x 83.2 136.3 x 188.7 x 83.2 136.3x198.7x83.2 136.3x198.7x83.2
Operating temp. range -15 ~ 48 -15 ~ 48 -15 ~ 48 -15 ~ 48 -15 ~ 48 -15 ~ 48 -15 ~ 48 -15 ~ 48 -5 ~ 48 -5 ~ 48 -5 ~ 48 -5 ~ 48
-25 ~ 24 -25 ~ 24 -25 ~ 24 -25 ~ 24 -25 ~ 24 -25 ~ 24 -25 ~ 24 -25 ~ 24 -25 ~ 24 -25 ~ 24 -25 ~ 24 -25 ~ 24

Note:

1) Nominal cooling capacities are based on indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m
2) Sound pressure was acquired in a dead room. Thus, actual noise level may be different depending on the installation conditions.

63 64
Specification Specification
DVM chiller DVM water

• Smaller footprint • Reliable operation

• Wide operating range • Small footprint

• Integrated control • Minimum noise level

• Provides Cold / Hot Water • Heat Recovery System (3 pipe)

Type Without pump Without pump Without pump With pump With pump With pump Model name AM080FXWANR/EU AM100FXWANR/EU AM120FXWANR/EU AM200FXWANR/EU AM300KXWANR/EU
Model name AG042KSVANH/EU AG056KSVANH/EU AG070KSVANH/EU AG042KSVGNH/EU AG056KSVGNH/EU AG070KSVGNH/EU
Φ, V,
Power supply Φ, V, Hz 3,380-415,50 3,380-415,50 3,380-415,50 3,380-415,50 3,380-415,50 3,380-415,50 Power supply 3,380-415,50 3,380-415,50 3,380-415,50 3,380-415,50 3,380-415,50
Hz
Mode - Heat pump Heat pump Heat pump Heat pump Heat pump Heat pump
Mode - Heat pump Heat pump Heat pump Heat pump Heat pump
Hp Hp 15 20 25 15 20 25
Ton Usrt 12 16 18.5 12 16 18.5 HP HP 8.00 10.00 12.00 20 30
Performance
Capacity Cooling kW 42.0 56.0 65.0 42.0 56.0 65 kW 22.40 28.00 33.60 56.00 84
(Nominal) Heating kW 42.0 56.0 69.5 42.0 56.0 69.5 Cooling
Power input Cooling 12.35 18.67 26.00 13.59 20.14 28.26 Performance Capacity Btu/h 76,400 95,500 114,600 191,100 286,600
kW (Nominal) kW 25.20 31.50 37.80 63.00 94.5
(Nominal) Heating 11.83 17.50 24.39 12.77 18.48 25.84
Current input Cooling 19.6 29.6 41.2 24.2 34.2 45.8
Heating
Power A Btu/h 86,000 107,500 129,000 215,000 322,400
(Nominal) Heating 18.8 27.8 38.7 23.4 32.4 43.3
Mca A 32.0 46.0 58.0 39 53 65 Power input Cooling 3.84 5.05 6.46 10.77 16.80
Current kW
Mfa A 40.0 60.0 75.0 50 60 75 (Nominal) Heating 4.12 5.25 6.51 10.86 16.88
Nominal cooling W/W 3.40 3.00 2.50 3.09 2.78 2.30 Cooling 6.20 8.10 10.30 17.30 26.4
Current input
Nominal heating W/W 3.55 3.20 2.85 3.29 3.03 2.69 Power
Cop (Nominal) Heating A 6.60 8.40 10.40 17.40 26.5
Eseer (Pump input is included
W/W 5.7 5.4 5 4.75 4.5 4.10 MCA 16.30 20.00 25.00 39.80 48
Based On En 14511)
Compressor Type - Inverter scroll Inverter scroll Inverter scroll Inverter scroll Inverter scroll Inverter scroll MFA A 20.00 20.00 30.00 40.00 63
Type - Brazing plate Brazing plate Brazing plate Brazing plate Brazing plate Brazing plate
Cooling kW 5.83 5.54 5.2 5.3 5.0
Water flow rate (Cooling/Heating) Lpm 120 / 120 160 / 160 186 / 200 120 / 120 160 / 160 186 / 200 COP
Pressure drop (Set. Norminal) Kpa 60 100 120 60 100 120 Heating kW 6.12 6.0 5.81 5.8 5.6
Water side heat
Max operationg pressure Mpa 1.0 1.0 1.0 1 1 1 Compressor Type - SSC Scroll x 1 SSC Scroll x 1 SSC Scroll x 1 SSC Scroll x 2 Inverter Scroll
exchanger
Connection type - Flange Flange Flange Flange Flange Flange
Type - PHE(Stainless Steel PHE(Stainless Steel PHE(Stainless Steel PHE(Stainless Steel PHE(Plate Heat
Pipe connection (Inlet/Outlet) Φ, Mm 40 40 50 40 40 50 Plate) Plate) Plate) Plate) Exchanger)
Q’ty Ea 2 2 2 2 2 2
Type - - - - End-Suction End-Suction End-Suction Condenser Lost head kPa 22 30 43 54 50
Input X N Kw - - - 1.68 1.68 1.68 Water flow rate LPM 80.0 96.0 114.0 190.0 285
Output X N W - - - 1.45 1.45 1.45 Max. pressure Mpa 1.96 1.96 1.96 1.96 1.96
Pump Lpm - - - 120 / 120 160 / 160 186 / 200
Normial water flow rate Liquid pipe Φ, mm 9.52 9.52 12.70 15.88 19.05
L/S - - - 2.0 / 2.0 2.7 / 2.7 3.1 / 3.3
External static Maq - - - 22.4 / 22.4 15.3 / 15.3 10.2 / 10.2 Gas pipe Φ, mm 19.05 22.22 28.58 28.58 34.92
Max.
Pressure(Set) Kpa - - - 220 / 220 150 / 150 131 / 100 Piping Discharge gas pipe Φ, mm 15.88 19.05 19.05 28.58 28.58
Refrigerant Type - R410A R410A R410A R410A R410A R410A connections
Cooling 60 62 63 60 62 63 Installation Max. Length m 170(190) 170 170 170 170(190)
Sound pressure limitation
Sound Heating dB(A) 57 59 64 57 59 64 Max. Height m 50.0(40.0) 50.0 50.0 50.0 50.0
Sound power 80 83 85 80 84 88 mm2
Field Power source wire 2.5 2.5 4 4 .75
Net weight Kg 446 446 465 472 472 493
External Shipping weight Kg 468 468 487 494 494 515
wiring Transmission cable mm2 0.75 ~ 1.25 0.75 ~ 1.25 0.75 ~ 1.25 0.75 ~ 1.25
dimension Net dimensions (Wxhxd) Mm (1,795 x 1,695 x 765) (1,795 x 1,695 x 765) (1,795 x 1,695 x 765) (1,795 x 1,695 x 765) (1,795 x 1,695 x 765) (1,795 x 1,695 x 765) Refrigerant Type - R410A R410A R410A R410A R410A
Shipping dimensions (Wxhxd) Mm (1,900 x 1,887 x 919) (1,900 x 1,887 x 919) (1,900 x 1,887 x 919) (1,900 x 1,887 x 919) (1,900 x 1,887 x 919) (1,900 x 1,887 x 919)
Cooling ℃ 5 ~ 25 5 ~ 25 5 ~ 25 5 ~ 25 5 ~ 25 5 ~ 25 Sound pressure 48.0 48.0 50.0 51.0 56
Operating Sound dB(A)
water temp. Cooling (If using brine) ℃ -10~25 -10~25 -10~25 -10~25 -10~25 -10~25 Sound power 70.0 70.0 70.0 73.0
range Heating ℃ 25 ~ 55 25 ~ 55 25 ~ 55 25 ~ 55 25 ~ 55 25 ~ 55 Net weight kg 160.0 160.0 160.0 240.0 282
Operating Water flow rate Lpm 60 ~ 240 80 ~ 320 93 ~ 400 60 ~ 240 80 ~ 320 93 ~ 400
water flow Minimum water storage in the
Shipping weight kg 167.0 167.0 167.0 250.0 292
L 294 392 490 294 392 490 External
range system dimension Net dimensions (WxHxD) mm (770 x 1,000 x 545) (770 x 1,000 x 545) (770 x 1,000 x 545) (1,100 x 1,000 x 545) (1,100 x 1,000 x 545)
Operating Cooling ℃ -15 ~ 48 -15 ~ 48 -15 ~ 48 -15 ~ 48 -15 ~ 48 -15 ~ 48 Shipping dimensions
amb. temp. mm (840 x 1,200 x 620) (840 x 1,200 x 620) (840 x 1,200 x 620) (1,170 x 1,200 x 620) (1,170 x 1,200 x 620)
Heating ℃ -25 ~ 43 -25 ~ 43 -25 ~ 43 -25 ~ 43 -25 ~ 43 -25 ~ 43 (WxHxD)
range
Operating Cooling ℃ 10 ~ 45 10 ~ 45 10 ~ 45 10 ~ 45 10 ~ 45
temp. range Heating ℃ 10 ~ 45 10 ~ 45 10 ~ 45 10 ~ 45 10 ~ 45

Note:
1) Nominal cooling capacities are based on;
Note:
2) Nominal heating capacities are based on;

3) Sound power level is an absolute value that a sound source generates.


-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
4) Sound level was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions.
-- Sound values are obtained in an anechoic room.
-- Sound values of multi comvination are theoretical values based on sound results of individual installed units.
4) Nominal heating capacityes are based on Eurovent test conditions:

65 66
Powerful and gentle cooling

Hi-Wall
Cassette 360 4Way 1Way
Slim Duct WindFree™
WindFree™ WindFree™

Product images shown are for representational purpose only, actual product may vary.

67 68
Samsun

360 Cassette
Circular design

Combining an elegantly modern look with a powerful performance and effortless control, the Samsung 360

DVM S Indoor Units


Cassette indoor unit can provide exceptional comfort and style in many locations.

The 360 Cassette has an innovative circular design that

perfectly everywhere. Its minimalist and elegant styling can


help to create a sophisticated and distinctive look in many
different sites. And its circular
shape stands out beautifully
when it’s installed in
an exposed ceiling,
which is the most
trendy of modern
architectural
designs.

mode mode

Using the 360 Cassette is a real pleasure as you can intuitively


control its performance and see where the air is going.
The Circular LED Display on the air conditioner also shows

horizontally. So with just one glance you


can quickly tell where the air is going.
And, its Wireless Remote Controller*
features a Jog shuttle (wheel
controller) and a dedicated button
that provide an easy and fun way
to adjust the strength of the air

*Optional.

69 70
70
360 Cassette 360 Cassette
Bladeless discharge Bladeless discharge

A bladeless design softly disperses cool air across the An innovative booster fan enables cool air to be expelled
room, making you comfortably cool without feeling a cold at much lower angles. It creates a low pressure area
draft**. With no blades to block the airflow, it also expels up around the outlet, so that cool air comes out parallel to
to 25 percent more air* and spreads it farther. the ceiling and disperses across a wider area.

Booster Fan
Within a 5m radius, no cold draft between 0~1.5m in height (with 14.0 kW).

*Samsung testing compared to a general 4Way cassette type air conditioner.

**Within a 9.3m radius the temperature difference is less than 0.6oC.

Its innovative circular design can match a multitude Intuitively control its performance and see where the air
of interior designs, so it perfectly fits in anywhere. Its is going. The Wireless Remote Controller's* Jog shuttle and
minimalist modern styling creates a sophisticated look button offer a fun way to adjust the airflow and a circular
and its circular shape stands out beautifully. LED display shows its direction.

*Optional.

30
mins.

71 72
Samsung Air Conditioner
Free™
360 Cassette WindFree™ 4Way
Bladeless discharge

Wind Free™
Wind Free™

Wind Free™

*Based on internal standard testing conditions in individual results may vary. Image simulated for representational purposes only.
Wind Free™ Wind Free™
73 74
74
Free™ Free™

III Hygiene - Even more comfort with even cleaner air


Staying cool is one thing, but to be really comfortable you also need to be breathing clean air.

An air conditioner and an air

Purification System (Optional)*


The Samsung WindFree™ 4Way Cassette not ony has a general
panel but can also include an optional Purifying Panel that keeps

Charger

Collector
PM1.0 Filter

PM1.0 PM2.5 Fine particles PM10 Coarse particles


Virus Powder Red blood cells 5
Bacteria Printer toner Car emissions
Pollen 6
Cigarette smoke Atmospheric
Hair 5
House dust Human hair
Cobweb width 2 3 Sand 62
Fog
Glass wool

Pre-Filter

Korea Air Cleaning Association


Wind Free™

Keep using for longer with


h a simple wash
Washable Filters
W r
The semi-permanent PM1.0 Filterr and Pre-Filterr are washable and reusable. It means you can continue enjoying clean, fresh air,
r while

STEP 01 Wash STEP 02 Rinse and Air Dry

Pre-Filter PM1.0 Filter


Remove any y dust or debris

using a va
acuum
Vacuum clean
ner Mild
detergent

Soft brush
30
mins.

75 76
Samsung Air Conditioner
Free™ Free™
WindFree™ 4Way

IImage simulated for representational purposes only. IImage simulated for representational purposes only.
77 78
Free™ Free™
Robust operation Low maintenance

Free™ Cooling keeps the temperature even inside the room. Samsung 4Way Cassette S features a remote controller
that enables users to manipulate the angles of the
fan blades for more efficient cooling. With the remote
-32.0
controller, users can individually set the opening angles
-31.0 of the four blades at the same angle or different
angles within a 32° - 65° range to create just the right
-30.0 atmosphere.
-29.0

-28.0

-27.0

-26.0

-25.0

-24.0 2M The Samsung 4Way Cassette S indoor unit is now lighter

-23.0 4M in weight at 17kg. It is one of the lightest indoor units in


the industry, about 40 percent lighter than conventional
products.
-22.0

-32.0 4Way Cassette S Conventional

-31.0 Free™
-30.0

-29.0
- Test model: WindFree™ 4Way 14.0 kW
-28.0 - Temperature: OD 35°C DB / 24°C WB, ID 27°C DB / 19°C WB

-27.0

-26.0

-25.0 - Based on 10kW

-24.0
zero 2M Free™
The 4Way outlet can cool every corner of the room. The
new and practical design of the blades minimise blind
-23.0 4M Under the same condition, Free™ Cooling Mode spots at the corners of the panel, and can cover nearly a
can save energy use by 55% compared to conventional full 360° around the indoor unit.
-22.0 cooling.

Free™
Normal Cooling Free™ Cooling
The check valve on the drain pump prevents drained
The Free™ Air Conditioner pushes air out through 15,700 water from flowing backwards into the drain pan. This
micro holes in the panel, producing a dispersed and gentle minimises the drain pan’s water level, eliminating the
flow of air, actually defined as “still air”*. The key here is all of worry and hassle of water stagnation or overflowing
those holes create a still, cooled air flow that infiltrates the drain water dripping.
room steadily. Save
55%
not detect wind. They define that condition as “Still Air”.

The Samsung 4Way Cassette S is uniquely designed for Integrating the most advanced technologies, Samsung
easy management. Featuring an advanced check valve, 4Way Cassette S delivers easy, efficient comfort with
and detachable panel and airflow blades, this unit offers specialised blade control, adjustable operation and
quick, simple setup and maintenance for the ultimate powerful airflow. An optional Loniser extends the unit’s
convenience, comfort, and performance. efficiency with air sanitation technology for a healthier
atmosphere.
#
Temperature difference based on internal research.

79 80
Free™ Free™
Tasteful design, compact and lightweight build Tasteful design, compact and lightweight build

The 4Way Cassette S (600 x 600) indoor air conditioning Free™


system provides high-performance heating and cooling
with features such as: Samsung's 4Way Cassette S (600 x 600) Air Conditioner
Samsung’s advanced 4Way Cassette S (600 x 600) can be installed on a single standard ceiling tile (600W
builds on the aesthetic appeal and performance of the Creates a Stylish design, effective x 600D) which helps minimise the installation time and
standard 4Way Cassette S with an enhanced design. polished ambiance with a compact design and attractive Smart Inverter compressor effort.
The 4Way Cassette S (600 x 600) comes in a variety of panel patterns. and a plethora of innovative
patterns to complement any interior. The stylish cassette features make Samsung
unit visually harmonises with the indoor space, while the Optimise comfort and save 4Way Cassette (600x600)
efficient cooling and heating performance makes it a energy with optional motion detection. great for residential and light The Samsung 4Way Cassette S (600 x 600) indoor unit
dependable and practical air conditioning solution. commercial applications weighs only 11kg. It is the lightest indoor unit in the industry,
Easy installation with limited about 35 percent lighter than our conventional products.
and maintenance, and maximises airflow with an efficient roof space.
design and robust performance.

4Way Casseette S (Interior) Conventional

Customisable airflow
Samsung 4Way Cassette
enables users to - Based on 3.5kW
manipulate the angles of
the fan blades for more
efficient cooling through a The 4Way outlet can cool every corner of the room. The
remote controller. new and practical design of the blades minimise blind
spots at the corners of the panel, and can cover nearly a
full 360° around the indoor unit.

Check valve on the drain pump prevents drained water


from flowing backward into the drain pan. This minimises
the drain pan’s water level, eliminating the worry and
hassle of water stagnation or overflowing drain water
dripping into the interior.

Main Unit Dimensions (W x D mm) Main Unit Weight (kg)


575 x 575 11.5

81 82
Free™ Free™
Enhanced comfort control Enhanced comfort control

The optional Motion Detection Sensor (MDS) for 4Way Cassette S (600 x 600) creates the ideal environment with added You can get optimum fan speed for high ceilings through the remote control, without having to adjust the DIP switch
comfort control and energy savings by providing just the right amount of airflow when needed. on the PCB. The fan speed adjustment function evenly distributes cool air throughout spaces with ceilings of up
to 3.6m. And the high ceiling mode delivers even more powerful airflow coverage throughout the interior space,
Smart on/off function expanding the airflow coverage area for height up to 4.6m.
Energy-saving MDS detects when individuals are absent from the area and automatically stops the air conditioning
operation. It also automatically sets operation patterns to create the perfect atmosphere and maximise energy efficiency.
4Way Cassette Conventional

3.6m
4.6m

The innovative MDS prevents the indoor unit from distributing airflow directly to individuals to reduced discomfort. It also Users can sanitise indoor air with the optional Loniser* for a cleaner work or living atmosphere. The easy-to-install
reduces the difference of thermal sensation in the body by detecting the temperature around the floor. Loniser generates active hydrogen and oxygen ions to eliminate airborne contaminants, completely eradicate
airborne bacteria and allergens, and even neutralise OH (hydroxyl) radicals.

Samsung 4Way Cassette S features a remote controller that enables users to manipulate the angles of the fan blades
for more efficient cooling. With the remote controller, users can individually set the opening angles of the four blades
at the same angle or different angles within a 32° - 65° range to create just the right atmosphere.
*Loniser device generates active hydrogen and oxygen ions which eliminate biological contaminants and active
oxygen (OH- radical) in the air by turning them into harmless H 2O.

83 84
Free™ Cassette

The Samsung 1Way Cassette air conditioner delivers a unique level of comfort by cooling optimally,
without the unpleasant feeling of cold air on your skin, while minimizing noise and energy use.

Free™
Save money every day by optimizing power usage with
Free™ the 1Way Cassette’s highly energy-efficient Free™
Stay feeling comfortable cool cooling. When operating in Free™ mode, the outdoor
with Free™ Cooling. It cools unit consumes only minimal power – using up to 55%
effectively without the unpleasant less electricity compared to the normal mode**. But it
sensation of cold wind being blown still provides sufficient cool air to maintain the desired
directly onto your skin. Cool air is temperature. So you can stay comfortably cool without
gently dispersed across the room worrying about your electricity bills.
through 10,000 micro air holes, which
creates a “Still Air” environment** with
a very low air speed of 0.15ms. There
are no drafts to disturb you and you
don’t feel too hot or too cold. So if Normal Cooling Up to 55% Saving
your children kick off the blanket at
night you don’t have to worry about

n
kW
them feeling cold in the room.

WindFreeTM Cooling

Time Elap
*Available only on the WindFree™ models.
**ASHRAE (American Society of Heating, Refrigerating,

of air is below 0.15m/s, so people cannot feel any cold drafts.

Library Sleep
Interruption
WindFree™
4Way
Room T

1kW model
Experience an intelligent way of creating
the ideal room conditions. The 1Way If a room is in the Comfort Zone If a room moves out of
Quiet operation
Barely
Cassette continually monitors both the Comfort Zone
The Samsung 1Way Cassette air conditioner drastically
Room Temp emp
32
the temperature and relative humidity elative humidityl
Wh ng WindFree™
reduces the amount of noise created by the air being
Room T 30 4Way
and analyzes the room conditions. It Suburb at night 600x600
dispersed. At its lowest level it only generates 24dB(A) of
then automatically switches between Comfort Zone 5kW model
sound*, which is almost as quiet as a whisper. It means
operating modes to keep everyone feeling
you won’t be disturbed by unpleasant noise when you’re
really comfortable without the need for
going to sleep – or doing anything else. So it’s ideal 26
any manual control. Time
Sound Sleep
Beginning Co ort Zone Co ort Zone for places where you sleep, relax, concentrate or are Tickiing
Fast Cooling WindFreeTM Cooling Normal Cooling
sensitive to noise, such as the bedroom, study or baby’s Normal mode
WindFree™ mode
room. Bedroom

Noise level of WindFree™ 4Way*

*Available only on the WindFree™ models. *Based on internal testing of a 3.6kW model when set to WindFree™ mode. Results may vary depending on environmental factors and individual use.

85 86
Free™ Cassette

The Samsung 1Way Cassette air conditioner is designed to cool a large area - quickly and efficiently. Its big It can be difficult to find space for an air conditioner, especially without impacting the interior. The
blade sends air over a much longer and wider area, while Auto Swing distributes air in every direction. Samsung 1Way Cassette has a slim and elegant design that will fit seamlessly into many locations.

The 1Way Cassette’s extremely slim design has a height of only 135mm and
can fit into a small ceiling space of just 155mm. So it provides a suitable
and effective solution for cooling and heating a wide range of locations
where space is limited. In addition, its elegant and compact design means
it blends discretely into interiors of all types and styles.

corner

8m
Create a comfortable environment with an even
temperature in every corner of a room. Conventional
1-way systems are normally installed in the ceiling and
it’s difficult to manually adjust the wind direction from
left to right. The 1Way Cassette's Auto Swing function*
automatically expels cool air in every direction. As well as
the auto up-down swing function it also has an auto left-
right swing function, so air is evenly distributed across the
room.

87 88
Free™ Free™

89 90
Cassette

Comfort
Even though it has a compact design, the Samsung 2Way Cassette is still very powerful. And its 2-way air flow
spreads air evenly over a greater distance, so it is ideal for cooling or heating long and narrow spaces.

Make good use of valuable space with the compact 2Way Cassette. It is ideal for cooling or heating long and narrow
areas, such as rectangular offices or hallways and corridors in hotels, schools and hospitals. Its 2-way air flow
distributes air evenly over a long distance without any temperature deviation.

The 2Way Cassette features an innovative Twin Cross Flow Fan


and an optimized air flow path, which enable air to be blown
out over a long distance. Its Auto Surround Swing system then
automatically distributes the air in every direction, ensuring
that it is evenly distributed across the whole room. So you can
enjoy a comfortable environment with an even temperature
in every corner.

91 92
Cassette

Overview Smart pressure control


The 2Way Cassette unit dimensions allow for easy Samsung Ducted type air conditioning units are a smart Samsung Ducted Type units feature a smart pressure
The modestly sized Samsung 2Way Cassette supports installation into standard ceiling grids (600W x 600D) for solution for low-maintenance, consistent cooling and control system. This system adjusts the fan speed
quick, simple setup for the ultimate convenience, comfort a tailored fit that blends unnoticeably into the interior heating performance in any environment. Their compact, based on the external static pressure (ESP), delivering
and performance. framework. slim frame blends seamlessly into ceilings, enhancing consistent cooling and heating power, regardless of the
the beauty of the interior space and offering users more surrounding environment.
flexible installation options.
Convenient installation
The 2Way Cassette indoor unit is now up to 45 percent The optional lift-up drain pump lifts condensed
smaller than conventional models, making it even easier Offering a comprehensive lineup, Samsung Ducted water up to 750mm, compared to a limit of 700mm
to incorporate into the building design. type air conditioning units offer just the right solution for on conventional models, for flexible and convenient
1030mm every need: installation.

This solution features 3way service, automatic air

650mm
volume, light weight and high EER.
After 1,000 hours of operation, the filter clean indicator

600mm
This solution is a low static pressure model, will notify you that the filter should be cleaned. The filter
which is optimised for places such as hotels and can be easily removed from the bottom, left, or right of
600mm residences. the unit (1,000 hours is the default set time, which can be
adjusted to 2,000 hours on the internal PCB.)
This model is specifically
designed to enhance interior design for large spaces
such as offices, stores, or residences.
With 750mm of discharge head, users can install the drain
themselves, saving them time and money. This model is optimised for large
spaces or places.
Conventional 2Way Cassette

The slim and compact size reduces the setup space


needed for easy installation and management.

2Way Cassette Conventional

Samsung's 2Way Cassette System Air Conditioner uses an


advanced drain hose, which is recognised in Europe for its
easy installation and leak prevention.

Included Panel Weight 5.6kW

93 94
Ultra-light, adaptable design Silent, strong performance

pressure control
Slim Duct S adopts an ultra-compact, slim size with its
thin width, which is 200mm narrower than conventional The external static pressure control makes it easy
products. This slender build enables flexible installation to customise the ductwork to ensure efficiency and
and maintenance in various environments. silent operation.

The efficient Slim Duct S is the lightest duct air conditioning


unit on the market. At a weight that’s 15 percent lighter
than conventional units, Slim Duct S offers the best in
convenient installation and maintenance.

Conventional
The new Samsung Slim Duct visually blends into the
ceiling while providing powerful cool and warm airflow. Concealed behind the ceiling, Samsung MSP Duct
It’s also easy to install and maintain in any interior provides powerful yet silent operation with external
regardless of the surrounding environment with its static pressure control. Its exceptional static pressure
compact size and weight—the lightest in the industry. enables a broad coverage area and provides stable,
efficient performance in larger spaces.

Flexible setup New MSP Duct offers greater static pressure than most
The air inlet can be set up either on the bottom or rear of slim ducts. This higher pressure level enables users to
the unit, giving users greater flexibility in installation. design more inlets and outlets with longer ductwork to
provide even more airflow
to larger areas.
Rear Side Air Inlet Bottom Side Air Inlet

The MSP Duct unit features quickly accessible parts


Slim Duct features a flexible design that enables users to
so users can maintain the unit with ease. And its
easily access its parts to maintain the unit.
compact size and narrow width of 900mm enable
flexible installation and management for added user
convenience.

The new drain pump in the Slim Duct unit can be


installed from the side by simply removing the right
side panel. Users no longer need to disassemble the
top cover to install, check or repair the drain pump for
maximum convenience.*

*Inbuilt drain pump option also available.

95 96
Free™ Premium plus

Comfort
The Samsung Free™ air conditioner keeps you comfortably cool with Free™ Cooling that is intelligently
optimised to suit your needs. And it can quickly cool large spaces from corner to corner.

Cool rooms quickly from corner to corner, so you’re


always comfortable whenever you want and wherever
you are. Digital Inverter Boost technology dramatically
Free™ shortens the time it takes for the compressor to reach
Stay feeling comfortable cool with Free™ Cooling. It maximum power when it starts operating, so it cools the
cools gently and quietly without the unpleasant feeling air 43% faster*. Its advanced design also has a 15% larger
of cold wind on your skin, as it disperses air fan, 18% wider inlet and a 31% wider blade. So cool air is
through 23,000 micro air holes. It creates a “Still dispersed farther and wider into every corner of a room,
Air” environment* with a very low air speed reaching up to 15 meters**.
and much less noise**. Its advanced air flow
structure also means it cools a wider and larger
area more evenly. And it consumes 58% less
energy than normal cooling mode*** so you can
stay comfortably cool without worrying about
electricity bills.

23,000
Micro Air Holes

* Tested on the AR12TXCAAWKEU model compared with the Samsung conventional model
AQ12EASER.
** Tested on the AR24TXFCAWKNEU model.

Create a comfortable environment with an even temperature in every corner of a room. The Free™ air
conditioner features a 4-way Swing function
Free™ that lets you remotely control the air direction,
so it goes towards a specific location, or
Even when the ambient humidity is high, you can keep the room air automatically expels air in every direction. As
comfortably dry with the Free™ Dry mode. When you select this well as the auto up-down swing function it
mode on your remote controller, its Humidity Sensor monitors the also has an auto left-right swing function, so
room humidity and effectively dehumidifies it without creating any air is evenly distributed across the room.
noise or a chilly wind. So you will feel comfortable, but won't notice
that it's working.

97 98
DVM Hydro

Performance
The Samsung DVM Hydro unit provides a single solution for cooling, heating and hot water that is both extremely The Samsung DVM Hydro unit is designed to be at the heart of your home or business. It is easy to install and
efficient and easy to manage. connect to a range of other devices, and can also be independently or centrally controlled.

installation
The DVM Hydro system is compatible with all DVM S Outdoor units and can be added to create a single,
integrated solution for cooling, heating and hot water that’s simple to manage. So it ensures much greater for external control
efficiency to suit a variety of demands – generating substantial energy and cost savings all year round with its
high-efficiency Heat Pump technology. The DVM Hydro is very quick and easy to
install and use for many different purposes.
It includes a range of connections for various
external input and output devices, such as Tank
Sensors, Booster Heaters, 2- and 3-way Valves,
and Room Thermostats.

Air Heating
Air Cooling

The DVM Hydro can be independently or centrally operated along with a variety of Samsung DVM systems. For
Water Tank Outdoor Unit
standalone use on individual sites it has its own control system or, using the Samsung DVM S Controller, it can be
integrated with various DVM systems eg. for water and air, and managed centrally.

Hot Water
Water Heating

The DVM Hydro is available in a choice of two types to


suit your hot water needs. The DVM Hydro HE provides
water at a mid temperature of 50°C, while the DVM
Hydro HT’s advanced, double compression technology
generates much hotter water at 80°C. So, whatever
your demands, there’s the perfect solution to satisfy
the requirements of various sites.

DVM Hydro HE DVM Hydro HT

99 100
Robust, high-pressure control Slim yet functional design

With the capacity to handle high external static pressure Samsung’s Ceiling Type indoor unit has two way
up to 25 mmAq, the powerful Samsung HSP Duct provides installation options for the ceiling and floor, enabling
an expansive coverage area with outstanding cooling more efficient use of available space. Users can enjoy
and heating performance. HSP Duct is an ideal fit for crisp, powerful air throughout their entire space from the
spaces with high ceilings and can be flexibly installed to compact unit in the ceiling or floor.
suit various environments.

The Samsung Ceiling Type air conditioner boasts a slim,


compact design—half the size of conventional products—
with cooling power comparable to larger units.

Products that are difficult to install are often challenging


to use as well. Considering users' product experience from
start to finish, Samsung separated the Duct S (AC6000)
into two parts, coil and fan, for easier installation and
management. When users experience difficulty handling
the product due to space limitations or weight, they Size Weight
can install the parts separately and then put them back
together as one unit.
Depending on the available space and the purpose of the
air conditioner, the indoor unit can be installed behind the
ceiling or on the floor.

Silent operation
The external static pressure control makes it easy
Under Ceiling
to customise the ductwork to ensure efficiency and
silent operation.

Samsung

Samsung
- Based on internal research 7.1kW Model

Samsung believes that products should improve users'


Comfortable airflow control
quality of life, not to impose more limitations. By making a
small change to the product, users now can install the Duct The purpose of air conditioners is to provide a pleasant
S (AC6000) right next to the roof's edge, freeing up rooftop indoor environment for users. To better serve this
space for other purposes. purpose, Samsung 4Way Cassette S provides a Comfort
Airflow Control function that prevents cold drafts. When Floor Standing
the room temperature reaches 23°C during cooling
mode, the indoor unit reduces the amount of discharged
air. By doing so, people in the room avoid the discomfort
of direct contact with cold airflow.

101 102
Powerful cooling Superior energy savings

The Samsung ERV and ERV Plus air conditioner systems


deliver optimal efficiency, quality and performance with
features such as:
Indoor air quality is gaining more attention as more
people are getting affected from airborne contaminants. Lower energy consumption
Indoor air contamination is often the cause behind and costs with a direct expansion (DX) coil and
building-related syndromes, such as asthma, headaches advanced heat exchange.
and dizziness.
Enjoy fresher air, quieter
The Samsung ERV (Energy Recovery Ventilation) system operation and humidity control for a more pleasant
air conditioner provides fresh, healthy air from outside environment.
while minimising energy loss for maximum efficiency.
Its intelligent structure incorporates features specifically Easy installation offers more efficient
designed for flawless ventilation and efficient operation. airflow with a slim, compact design.

Samsung ERV and ERV Plus deliver exceptional cooling


and heating all year round by employing the following
heat recovery method:

A two way ventilation design with air inlets and outlets


on both sides of the units provide superior ventilation
efficiency.

The remaining surface of the heat exchange area


transfers heat energy while preventing the discharged
contaminants from re-entering.

The system recovers up to 70 percent of the energy


needed to cool or heat the environment. The efficient
heat recovery maintains the indoor temperature and
humidity during the winter, and prevents outdoor heat
and moisture from entering indoors during the summer.

103 104
Superior energy savings Optimized design

ERV and ERV Plus automatically changes operation mode, The new diamond type heat exchanger features an

DVM S Indoor Units


depending on the temperature difference between the Samsung ERV and ERV Plus offers a smart, efficient optimised airflow design. This element is compact in
indoor and outdoor environment, to conserve energy. design that enables users to deliver fresher air wherever size, but offers higher efficiency than conventional
needed with more installation options. rectangular and hexagonal type heat exchangers.

Flexible setup
Extreme Climates (Winter and Summer) Mild Climates (Spring and Fall)

The ERV system can be installed vertically or horizontally.


This installation flexibility saves time on maintenance
when installing more than one unit. Users can reduce the
number of service holes by installing ERV with the control
Users can maintain a perfect indoor humidity level with an box facing a single service hole (applicable to ERV only).
optional humidifier element. The Samsung humidifier kit
delivers high-efficiency moisture balancing with its large
humidification area. Plus, the ERV self-cleaning function,
which sprays water from the top of the device when the
system starts, prevents offensive odors caused by dust,
and other particle accumulation.
Samsung ERV systems, coupled with an air conditioner,
provide world-class energy-saving solutions to
intelligently reduce air conditioner operating hours.
Decreased air conditioner operation lessens the cooling
and heating load while maintaining optimal performance.

Samsung’s advanced technology promotes a slim,


compact product. By applying a highly efficient heat
exchanger element, Samsung has been able to reduce
the ERV system’s height to 270mm. Compared to
traditional units with rectangular-type heat exchangers,
Samsung ERV units use space more efficiently with their
slim, diamond-shaped design.

ERV provides fresh in-room airflow by detecting CO2 with


the optional CO2 sensor. Users can also attach a humidity Space for
stat (procured locally), which detects the moisture of the
room and automatically adjusts its humidity level.
service
Peaceful performance
Samsung ERV units feature Quiet Mode for more discreet
With Samsung ERV and ERV Plus systems, users can enjoy operation compared to ordinary ventilators. AN 100
high-performance comfort throughout their environment 1,000 CMH
with crisp air quality and low noise levels.

ERV PLUS is equipped with a direct expansion coil to


pre-condition the outdoor air that enters the indoor
environment. Outdoor air passes through the DX coil to
produce fresh air without any temperature loss. AN050

500 CMH

105 106
WindFree™ WindFree™ WindFree™
1Way Cassette 4Way Cassette Mini 4Way 2Way Premium Plus
360 Cassette Cassette MSP Duct HSP Duct Slim Duct Floor Standing Ceiling DVM Hydro
Also available Also available
Cassette WindFree™
Also available Also available
Products in non-WindFree™ in non-WindFree™
in non-WindFree™ in non WindFree™

Capacity

TR kW

0.6 2.2

0.7 2.6

0.8 2.8

0.83 3.0

1.0 3.6

1.2 4.2

1.3 4.5

1.6 5.6

1.7 6.0
2.0 7.1

2.3 8.2

2.6 9.0

2.8 10.0

3.2 11.2

3.6 12.8

4.0 14.0
4.6 16.0

4.8 17.0

5.0 18.0

6.4 22.4

8.0 28.0

16.0

25.0
31.5
50.4

Available in chilled water FCU (Fan Coil Unit) Available in DX Coil

107 108
360 Cassette
Specification • Perfect even cooling
Indoor units • Cold-draft free

• Bladeless discharge

• Stylish design

DVM S Indoor Units


Model AM045KN4DEH/EU AM056KN4DEH/EU AM071KN4DEH/EU AM090KN4DEH/EU AM112KN4DEH/EU AM128KN4DEH/EU AM140KN4DEH/EU
Power Supply (Indoor Unit) [Φ, #, V, Hz] 1,2,220-240,50 1,2,220-240,50 1,2,220-240,50 1,2,220-240,50 1,2,220-240,50 1,2,220-240,50 1,2,220-240,50
System Mode HP/HR HP/HR HP/HR HP/HR HP/HR HP/HR HP/HR
Capacity Cooling [kW] 4.5kW 5.6kW 7.1kW 9.0kW 11.2kW 12.8kW 14.0kW
Cooling [Btu/h] 15400Btu/h 19100Btu/h 24200Btu/h 30700Btu/h 38200Btu/h 43700Btu/h 47800Btu/h
Heating [kW] 5.0kW 6.3kW 8.0kW 10.0kW 12.5kW 13.8kW 16.0kW
Heating [Btu/h] 15400Btu/h 21500Btu/h 27300Btu/h 34100Btu/h 42700Btu/h 47100Btu/h 54600Btu/h
Current Input Cooling 0.18A 0.21A 0.25A 0.42A 0.41A 0.62A 0.75A
Heating 0.18A 0.21A 0.25A 0.42A 0.41A 0.62A 0.75A
Power Input Cooling [kW] 0.026kW 0.030kW 0.034kW 0.055kW 0.053kW 0.077kW 0.091kW
Heating [kW] 0.026kW 0.030kW 0.034kW 0.055kW 0.053kW 0.077kW 0.091kW
Fan Type Turbo Fan Turbo Fan Turbo Fan Turbo Fan Turbo Fan Turbo Fan Turbo Fan
Motor (Output) [W] 65 x 1W 65 x 1W 65 x 1W 65 x 1W 97 x 1W 97 x 1W 97 x 1W
Air Flow Rate (High / Mid / Low) [m3/h] 870/810/750㎥/h 960/870/810㎥/h 1080/960/840㎥/h 1320/1110/960㎥/h 1530/1260/1050㎥/h 1770/1440/1140㎥/h 1890/1590/1260㎥/h
Air Flow Rate (High / Mid / Low) [l/s] 241.67/225.00/208.33 266.67/241.67/225.00 300.00/266.67/233.33 366.67/308.33/266.67 425.00/350.00/291.67 491.67/400.00/316.67 525.00/441.67/350.00
Piping Connections Liquid Pipe (Φ, mm) 6.35mm 6.35mm 9.52mm 9.52mm 9.52mm 9.52mm 9.52mm
Liquid Pipe (Φ, inch) 1/4 1/4 3/8 3/8 3/8 3/8 3/8
Gas Pipe (Φ, mm) 12.7mm 12.7mm 15.88mm 15.88mm 15.88mm 15.88mm 15.88mm
Gas Pipe (Φ, inch) 1/2 1/2 5/8 5/8 5/8 5/8 5/8
Drain Pipe (Φ,mm) VP25(OD32/ID25)mm VP25(OD32/ID25)mm VP25(OD32/ID25)mm VP25(OD32/ID25)mm VP25(OD32/ID25)mm VP25(OD32/ID25)mm VP25(OD32/ID25)mm
Field Wiring Power Source Wire 1.5 ~ 2.5 1.5 ~ 2.5 1.5 ~ 2.5 1.5 ~ 2.5 1.5 ~ 2.5 1.5 ~ 2.5 1.5 ~ 2.5
Transmission Cable 0.75 ~ 1.50 0.75 ~ 1.50 0.75 ~ 1.50 0.75 ~ 1.50 0.75 ~ 1.50 0.75 ~ 1.50 0.75 ~ 1.50
Refrigerant Type R410A(Contains fluorinated R410A(Contains fluorinated R410A(Contains fluorinated R410A(Contains fluorinated R410A(Contains fluorinated R410A(Contains fluorinated R410A(Contains fluorinated
greenhouse gas, GWP=2,088) greenhouse gas, GWP=2,088) greenhouse gas, GWP=2,088) greenhouse gas, GWP=2,088) greenhouse gas, GWP=2,088) greenhouse gas, GWP=2,088) greenhouse gas, GWP=2,088)
Control Method EEV INCLUDED EEV INCLUDED EEV INCLUDED EEV INCLUDED EEV INCLUDED EEV INCLUDED EEV INCLUDED
Sound Sound Pressure Level (High / Mid / Low) [dB(A)] 33/31/29dBA 34/32/29dBA 36/33/30dBA 40/36/32dBA 40/36/32dBA 42/38/33dBA 44/40/35dBA
Sound Power Level 50.0dBA 51.0dBA 53.0dBA 57.0dBA 58.0dBA 60.0dBA 61.0dBA
External Dimension (Indoor Unit) Net Weight (kg) 21.0kg 21.0kg 21.0kg 21.0kg 24.0kg 24.0kg 24.0kg
Shipping Weight (kg) 25.9kg 25.9kg 25.9kg 25.9kg 29.4kg 29.4kg 29.4kg
Net Dimensions (WxHxD) (mm) 947 x 281 x 947mm 947 x 281 x 947mm 947 x 281 x 947mm 947 x 281 x 947mm 947 x 365 x 947mm 947 x 365 x 947mm 947 x 365 x 947mm
Shipping Dimensions (WxHxD) (mm) 990 x 330 x 990mm 990 x 330 x 990mm 990 x 330 x 990mm 990 x 330 x 990mm 990 x 414 x 990mm 990 x 414 x 990mm 990 x 414 x 990mm
Panel Model Name PC4NUDMAN PC4NUDMAN PC4NUDMAN PC4NUDMAN PC4NUDMAN PC4NUDMAN PC4NUDMAN
Net Weight (kg) 3.6kg 3.6kg 3.6kg 3.6kg 3.6kg 3.6kg 3.6kg
Shipping Weight (kg) 6.0kg 6.0kg 6.0kg 6.0kg 6.0kg 6.0kg 6.0kg
Net Dimensions (WxHxD) (mm) 1000 x 66 x 1000mm 1000 x 66 x 1000mm 1000 x 66 x 1000mm 1000 x 66 x 1000mm 1000 x 66 x 1000mm 1000 x 66 x 1000mm 1000 x 66 x 1000mm
Shipping Dimensions (WxHxD) (mm) 1093 x 85 x 1083mm 1093 x 85 x 1083mm 1093 x 85 x 1083mm 1093 x 85 x 1083mm 1093 x 85 x 1083mm 1093 x 85 x 1083mm 1093 x 85 x 1083mm
Additional Accessories Drain Pump Built In Built In Built In Built In Built In Built In Built In
Drain Pump Max. Lifting Height/Displacement 750/24t 750/24 750/24 750/24 750/24 750/24 750/24

1) Mode: HP, Heat Pump


2) Nominal cooling capacities are based on indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m
3) Nominal heating capacities are based on indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m
4) Sound pressure was acquired in a dead room. Thus, actual noise level may be different depending on the installation conditions.

Optional accessories

Individual Panel
Controllers Options

(Auto Elevation)

109 110
Specification
Indoor units • Loniser (Optional)

• Surround flow

• Individual blade control

• Fan speed adjustment for high ceiling

Model AM 04 5 NN4 DEH /EU AM07 1N N 4DEH/ EU AM090N N 4DEH/ EU AM112N N 4DEH/ EU AM128N N 4DEH/ EU AM1 40 NN4DE H/E U
Power Supply (Indoor Unit) [Φ, #, V, Hz] 1 ,2,220-240,50 1,2,220 -240 ,50 1,2,220 -240 ,50 1,2,220 -240 ,50 1,2,220 -240 ,50 1,2,220- 240,50
Capacity Cooling [kW] 4.5 kW 7. 1kW 9.0 kW 11.2kW 12. 8 kW 14.0kW
Cooling [Btu/h] 1 5,400Bt u/ h 24,20 0 Btu/h 30 ,70 0 Btu/h 38 ,2 0 0 Btu/h 43,70 0 Btu/h 47,800B tu /h
Heating [kW] 5 .0kW 8 . 0 kW 10 . 0 kW 12. 5kW 13. 8 kW 16.0kW
Heating [Btu/h] 1 7,1 00Bt u/ h 27,30 0 Btu/h 34,10 0 Btu/h 42 ,70 0 Btu/h 47,10 0 Btu/h 54 ,600B tu /h
Current Input Cooling 0.22A 0 .31A 0 .43A 0 .55A 0 .51A 0.62A
Heating 0.22A 0 .31A 0 .43A 0 .55A 0 .51A 0.62A
Cooling [kW] 0.03 2kW 0 .0 45kW 0 .0 62kW 0 .0 78 kW 0 .0 73kW 0.089kW
Heating [kW] 0.03 2kW 0 .0 45kW 0 .0 62kW 0 .0 78 kW 0 .0 73kW 0.089kW
Air Flow Rate (High / Mid / Low) [㎥/min]
Air Flow Rate (High / Mid / Low) [m3/h] 870/ 81 0/ 750㎥ / h 10 2 0 /930 /8 70 ㎥ /h 1170 /10 8 0 /990 ㎥ /h 1560 /1440 /1320 ㎥ /h 168 0 /1560 /138 0 ㎥ /h 1800/1 680/1560㎥ /h
Air Flow Rate (High / Mid / Low) [l/s] 242/ 225 / 208 28 3/258 /2 42 325/30 0 /2 75 433/40 0 /367 467/433/38 3 500/467/433
Piping Connections Liquid Pipe (Φ, mm) 6 .3 5 mm 9.52mm 9.52mm 9.52mm 9.52mm 9.52mm
Liquid Pipe (Φ, inch) 1 / 4" 3/8 " 3/8 " 3/8 " 3/8 " 3/8"
Gas Pipe (Φ, mm) 1 2.70m m 15. 8 8 mm 15. 8 8 mm 15. 8 8 mm 15. 8 8 mm 15.88mm
Gas Pipe (Φ, inch) 1 / 2" 5/8 " 5/8 " 5/8 " 5/8 " 5/8"
Drain Pipe (Φ,mm) VP 25 ( O D 3 2,I D 25 ) m m V P2 5 (OD 32,ID 2 5)mm V P2 5 (OD 32,ID 2 5)mm V P2 5 (OD 32,ID 2 5)mm V P2 5 (OD 32,ID 2 5)mm VP25 (OD 32,ID 25)mm
Field Wiring Power Source Wire 1 .5 ~ 2.5 1.5 ~ 2 .5 1.5 ~ 2 .5 1.5 ~ 2 .5 1.5 ~ 2 .5 1.5 ~ 2.5
Transmission Cable 0.75 ~ 1 .50 0 .75 ~ 1. 50 0 .75 ~ 1. 50 0 .75 ~ 1. 50 0 .75 ~ 1. 50 0.75 ~ 1 .50
Refrigerant Type R41 0A ( Co n t a in s fluo rin a t ed R410 A(C ontai ns fl uori nated R 410 A(C ontai ns fl uori nated R 410 A(C ontai ns fl u ori nated R 410 A(C ontai ns fl uori nated R4 10A(Contains flu orinate d
g reen h o us e g a s , GW P = 2,088) g ree nhouse gas, G WP=2 ,0 8 8 ) greenhouse gas, G WP=2 ,0 8 8 ) greenhouse gas, G WP=2 ,0 8 8 ) greenhouse gas, G WP=2,0 8 8 ) gre e nhou se gas, GWP=2,088)
Control Method EEV I NCLUD ED E E V INC L UDE D E E V INC L UDE D E E V INC L UDE D E E V INC L UDE D EEV IN CLU DED
Sound Sound Pressure Level (High / Mid / Low) [dB(A)] 3 3 / 3 2/ 3 0dBA 35/34/33dBA 39/36/33dBA 40 /38 /35dBA 42 /40 /35dBA 44/4 1/35d B A
Sound Power Level 49 .0dBA 54.0 dBA 57.0 dBA 57.0 dBA 58 .0 dBA 60 .0d B A
External Dimension (Indoor Unit) Net Weight (kg) 1 5 .0kg 15. 0 kg 15. 0 kg 16.5kg 18 .5kg 18.5kg
Shipping Weight (kg) 1 8.5 kg 18 . 5kg 18 .5kg 20 . 0 kg 22 .5kg 22.5kg
Net Dimensions (WxHxD) (mm) 840 x 204 x 840m m 8 40 x 20 4 x 8 40 mm 8 40 x 20 4 x 8 40 mm 8 40 x 246 x 8 40 mm 8 40 x 28 8 x 8 40 mm 840 x 288 x 840mm
Panel Shipping Dimensions (WxHxD) (mm) 89 8 x 275 x 89 8m m 8 98 x 2 75 x 8 98 mm 8 98 x 2 75 x 8 98 mm 8 98 x 316 x 8 98 mm 8 98 x 357 x 8 98 mm 898 x 357 x 898mm
Model Name P C4NUF M A N PC 4NUFMAN PC 4NUFMAN PC 4NUFMAN PC 4NUFMAN PC4N U FMAN
Net Weight (kg) 6 .3 kg 6.3kg 6.3kg 6.3kg 6.3kg 6.3kg
Shipping Weight (kg) 8.7kg 8 . 7kg 8 . 7kg 8 . 7kg 8 . 7kg 8.7kg
Net Dimensions (WxHxD) (mm) 9 5 0 x 6 4 x 9 5 0m m 950 x 64 x 950 mm 950 x 64 x 950 mm 950 x 64 x 950 mm 950 x 64 x 950 mm 950 x 64 x 950mm
Shipping Dimensions (WxHxD) (mm) 1 ,01 0 x 1 1 7 x 1 ,000m m 1,0 10 x 117 x 1,0 0 0 mm 1,0 10 x 117 x 1,0 0 0 mm 1,0 10 x 117 x 1,0 0 0 mm 1,0 10 x 117 x 1,0 0 0 mm 1,010 x 117 x 1,000mm

1) Mode: HP, Heat Pump


2) Nominal cooling capacities are based on indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m
3) Nominal heating capacities are based on indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m
4) Sound pressure was acquired in a dead room. Thus, actual noise level may be different depending on the installation conditions.

Optional accessories

Individual Panel
Controtllers Options

PC4NUSKAN
(WindFree™) (Classic) (Black)

111 112
Specification
Indoor units • Compact and light unit

• Loniser (Optional)

• Motion Detect Sensor (Optional)

• No overflowing drain water

Model AM 015 NNNDEH/EU AM022N N N DEH/ EU AM028N N N DEH/ EU AM036N N N DEH/ EU AM045N N N DEH/ EU AM0 56NNNDE H/E U
Power Supply (Indoor Unit) [Φ, #, V, Hz] 1 ,2,220-240,5 0 1,2,220 -240 ,50 1,2,220 -240 ,50 1,2,220 -240 ,50 1,2,220 -240 ,50 1,2,220- 240,50
Capacity Cooling [kW] 1 .5kW 2. 2kW 2. 8 kW 3.6kW 4. 5kW 5.6kW
Cooling [Btu/h] 5,1 00Bt u/ h 7,50 0 Btu/h 9,60 0 Btu/h 12,30 0 Btu/h 15,40 0 Btu/h 19,1 00B tu /h
Heating [kW] 1 .7kW 2. 5kW 3.2 kW 4. 0 kW 5. 0 kW 6.3kW
Heating [Btu/h] 5 ,800Bt u/ h 8 ,50 0 Btu/h 10 ,90 0 Btu/h 13,60 0 Btu/h 17,10 0 Btu/h 21,500B tu /h
Current Input Cooling 0.1 7A 0 .17A 0 .17A 0 .19A 0 .2 2A 0.27A
Heating 0.1 7A 0 .17A 0 .17A 0 .19A 0 .2 2A 0.27A
Power Input Cooling [kW] 0.01 8kW 0 .0 18 kW 0 .0 18 kW 0 .0 20 kW 0 .0 23kW 0.028kW
Heating [kW] 0.01 8kW 0 .0 18 kW 0 .0 18 kW 0 .0 20 kW 0 .0 23kW 0.028kW
Fan Type T urbo F a n Turbo Fan Turbo Fan Turbo Fan Turbo Fan Tu rb o Fan
Motor (Output) [W] 65 x 1W 65 x 1W 65 x 1W 65 x 1W 65 x 1W 65 x 1W
Air Flow Rate (High / Mid / Low) [m3/h] 5 1 0/ 43 2/ 3 9 0㎥/ h 540 /462/390 ㎥/h 60 0 /510 /450 ㎥ /h 630 /540 /450 ㎥/h 690 /612 /540 ㎥/h 780/660/570㎥ /h
Air Flow Rate (High / Mid / Low) [l/s] 1 42/ 1 20/ 1 08 150 /128 /10 8 167/142 /125 175/150 /125 192/170 /150 217/183/158
Piping Connections Liquid Pipe (Φ, mm) 6 .3 5 mm 6.35mm 6.35mm 6.35mm 6.35mm 6.35mm
Liquid Pipe (Φ, inch) 1 / 4" 1/4" 1/4" 1/4" 1/4" 1/4"
Gas Pipe (Φ, mm) 1 2.70m m 12. 70 mm 12. 70 mm 12. 70 mm 12. 70 mm 12.70mm
Gas Pipe (Φ, inch) 1 / 2" 1/2 " 1/2 " 1/2 " 1/2 " 1/2"
Drain Pipe (Φ,mm) VP 25 ( O D 3 2,I D 25 ) m m VP2 5 (OD 32,ID 2 5)mm V P2 5 (OD 32,ID 2 5)mm V P2 5 (OD 32,ID 2 5)mm V P2 5 (OD 32,ID 2 5)mm VP25 (OD 32,ID 25)mm
Field Wiring Power Source Wire 1 .5 ~ 2.5 1.5 ~ 2 .5 1.5 ~ 2 .5 1.5 ~ 2 .5 1.5 ~ 2 .5 1.5 ~ 2.5
Transmission Cable 0.75 ~ 1 .5 0 0 .75 ~ 1. 50 0 .75 ~ 1. 50 0 .75 ~ 1. 50 0 .75 ~ 1. 50 0.75 ~ 1 .50
Refrigerant Type R41 0A ( Co n t a in s fluo rin a t ed R410 A(C ontai ns fl uori nated R 410 A(C ontai ns fl uori nated R 410 A(C ontai ns fl uori nated R 410 A(C ontai ns fl uori nated R4 10A(Contains flu orinate d
g reen h o us e g a s , GW P = 2,088) g reenhouse gas, G WP=2,0 8 8 ) greenhouse gas, G WP=2 ,0 8 8 ) greenhouse gas, G WP=2 ,0 8 8 ) greenhouse gas, G WP=2 ,0 8 8 ) gre e nhou se gas, GWP=2,088)
Control Method EEV I NCLUD ED E E V INC L UDE D E E V INC L UDE D E E V INC L UDE D E E V INC L UDE D EEV IN CLU DED
Sound Sound Pressure Level (High / Mid / Low) [dB(A)] 3 0/ 28/ 23 dBA 32/29/2 5dBA 33/30 /2 6dBA 34/30 /26dBA 36/34/32dBA 39/36/33d B A
Sound Power Level 46 .0dBA 47.0 dBA 50 .0 dBA 51. 0 dBA 53. 0 dBA 56.0d B A
External Dimension (Indoor Unit) Net Weight (kg) 1 1 .7kg 12. 0 kg 12. 0 kg 12. 0 kg 12. 0 kg 12.0kg
Shipping Weight (kg) 1 3 .7kg 14.0 kg 14.0 kg 14.0 kg 14.0 kg 14.0 kg
Net Dimensions (WxHxD) (mm) 5 75 x 250 x 575m m 575 x 250 x 575mm 575 x 250 x 575mm 575 x 250 x 575mm 575 x 250 x 575mm 575 x 250 x 575mm
Shipping Dimensions (WxHxD) (mm) 6 23 x 29 8 x 6 53 m m 623 x 298 x 653mm 623 x 298 x 653mm 623 x 298 x 653mm 623 x 298 x 653mm 623 x 298 x 653mm
Panel Model Name P C4SUF M A N PC 4SUFMAN PC 4SUFMAN PC 4SUFMAN PC 4SUFMAN PC4SU FMAN
Net Weight (kg) 2.7kg 2. 7kg 2. 7kg 2. 7kg 2. 7kg 2.7kg
Shipping Weight (kg) 3 .9 kg 3.9kg 3.9kg 3.9kg 3.9kg 3.9kg
Net Dimensions (WxHxD) (mm) 6 20 x 57 x 6 20m m 620 x 57 x 620 mm 620 x 57 x 620 mm 620 x 57 x 620 mm 620 x 57 x 620 mm 620 x 57 x 620mm
Shipping Dimensions (WxHxD) (mm) 6 70 x 1 20 x 6 55m m 670 x 12 0 x 655mm 670 x 12 0 x 655mm 670 x 12 0 x 655mm 670 x 12 0 x 655mm 670 x 120 x 655mm
Note:

1) Mode: HP, Heat Pump


2) Nominal cooling capacities are based on indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m
3) Nominal heating capacities are based on indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m
4) Sound pressure was acquired in a dead room. Thus, actual noise level may be different depending on the installation conditions.
Optional accessories

Individual Panel
Controllers Options

(WindFree™) (Classic)

113 114
Specification Specification
Indoor units Indoor units
• Slim and compact design • Standard formula for easy installation
• Quiet operation • Twin cross flow fan
• No overflowing drain water • Small size, big performance
• Stylish design • Ultra light weight

Model AM022NN1DKH/EU AM028NN1DKH/EU AM036NN1DKH/EU AM071NN1DEH/EU Model AM056CN2DKH/EA AM071CN2DKH/EA


Power Supply (Indoor Unit) [Φ, #, V, Hz] 1,2,220-240,50/60 1,2,220-240,50/60 1,2,220-240,50/60 1,2,220-240,50 Power Supply (Indoor Unit) [Φ, #, V, Hz] 1,2,220-240,50/60 1,2,220-240,50/60
Capacity Cooling [kW] 2.20kW 2.80kW 3.60kW 7.1kW System Mode HP/HR HP/HR
Cooling [Btu/h] 7,500Btu/h 9,600Btu/h 12,300Btu/h 24,200Btu/h Capacity Cooling [kW] 5.60kW 7.10kW
Heating [kW] 2.50kW 3.20kW 4.00kW 8.0kW Heating [kW] 6.30kW 8.00kW
Heating [Btu/h] 8,500Btu/h 10,900Btu/h 13,600Btu/h 27,300Btu/h Current Input Cooling 0.32A 0.34A
Current Input Cooling 0.16A 0.17A 0.20A 0.40A Heating 0.32A 0.38A
Heating 0.16A 0.17A 0.20A 0.40A Power Input Cooling [W] 40W 43W
Cooling [kW] 0.029kW 0.032kW 0.040kW 0.080kW Heating [W] 40W 49W
Heating [kW] 0.029kW 0.032kW 0.040kW 0.080kW Fan Type Crossflow Fan / BLDC Crossflow Fan / BLDC
Fan Type Crossflow Fan Crossflow Fan Crossflow Fan Crossflow Fan Motor (Output) [W] 27W 27W
Motor (Output) [W] 27 X 1W 27 X 1W 27 X 1W 54 x 1W Number of Unit (EA) 2EA 2EA
Number of Unit (EA) 1EA 1EA 1EA Air Flow Rate (High / Mid / Low) [㎥/min] 15.7/14.1/12.8CMM 16.0/14.49/12.8CMM
Air Flow Rate (High / Mid / Low) [m3/h] 360/300/240㎥/h 420/360/300㎥/h 480/420/360㎥/h 1020/930/840㎥/h Air Flow Rate (High / Mid / Low) [l/s] 261.67/235/213.33L/S 266.67/241.5/213.33L/S
Air Flow Rate (High / Mid / Low) [l/s] 100.00/83.33/66.67L/S 116.67/100.00/83.33L/S 133.33/116.67/100.00L/S 283.33/258.33/233.33 Piping Connections Liquid Pipe (Φ, mm) 6.35mm 9.52mm
Piping Connections Liquid Pipe (Φ, mm) 6.35mm 6.35mm 6.35mm 9.52mm Liquid Pipe (Φ, inch) 1/4" 3/8"
Liquid Pipe (Φ, inch) 1/4" 1/4" 1/4" 3/8" Gas Pipe (Φ, mm) 12.7mm 15.88mm
Gas Pipe (Φ, mm) 12.7mm 12.7mm 12.7mm 15.88mm Gas Pipe (Φ, inch) 1/2" 5/8"
Gas Pipe (Φ, inch) 1/2" 1/2" 1/2" 5/8" Drain Pipe (Φ,mm) VP25 (OD 32,ID 25)mm VP25 (OD 32,ID 25)mm
Drain Pipe (Φ,mm) VP20 (OD 25,ID 20)mm VP20 (OD 25,ID 20)mm VP20 (OD 25,ID 20)mm VP20 (OD 25,ID 20)mm Field Wiring Power Source Wire 1.5 ~ 2.5 1.5 ~ 2.5
Field Wiring Power Source Wire 1.5 ~ 2.5 1.5 ~ 2.5 1.5 ~ 2.5 1.5 ~ 2.5 Transmission Cable 0.75 ~ 1.50 0.75 ~ 1.50
Transmission Cable 0.75 ~ 1.50 0.75 ~ 1.50 0.75 ~ 1.50 0.75 ~ 1.50 Refrigerant Type R410A R410A
Refrigerant Type R410A(Contains fluorinated R410A(Contains fluorinated R410A(Contains fluorinated R410A(Contains fluorinated Control Method EEV INCLUDED EEV INCLUDED
greenhouse gas, GWP=2,088) greenhouse gas, GWP=2,088) greenhouse gas, GWP=2,088) greenhouse gas, GWP=2,088) Sound Sound Pressure Level (High / Mid / Low) [dB(A)] 37.5/36/34dBA 40/38/35dBA
Control Method EEV INCLUDED EEV INCLUDED EEV INCLUDED EEV INCLUDED External Dimension Net Weight (kg) 18.5kg 19.5kg
Sound Sound Pressure Level 29 / 26 / 24dBA 32 / 28 / 24dBA 37 / 33 / 30dBA 42 / 39 / 36dBA (Indoor Unit) Shipping Weight (kg) 21.5kg 22.5kg
(High / Mid / Low) [dB(A)] Net Dimensions (WxHxD) (mm) 890 x 230 x 575mm 890 x 230 x 575mm
Sound Power Level 47dBA 50dBA 55dBA 60.0dBA Shipping Dimensions (WxHxD) (mm) 1077 x 299 x 642mm 1077 x 299 x 642mm
External Dimension Net Weight (kg) 10.0kg 10.0kg 10.0kg 13.5kg Panel Model Name PC2NWSMEN PC2NWSMEN
(Indoor Unit) Shipping Weight (kg) 13.4kg 13.4kg 13.4kg 17.3kg Net Weight (kg) 4.0kg 4.0kg
Net Dimensions (WxHxD) (mm) 970 x 135 x 410mm 970 x 135 x 410mm 970 x 135 x 410mm 1200 x 138 x 450mm Shipping Weight (kg) 8.5kg 8.5kg
Shipping Dimensions (WxHxD) (mm) 1173 x 231 x 487mm 1173 x 231 x 487mm 1173 x 231 x 487mm 1435 x 224 x 525mm Net Dimensions (WxHxD) (mm) 1030 x 25 x 650mm 1030 x 25 x 650mm
Panel Model Name PC1NWFMAN PC1NWFMAN PC1NWFMAN PC1BWFMAN Shipping Dimensions (WxHxD) (mm) 1103 x 151 x 727mm 1103 x 151 x 727mm
Net Weight (kg) 4.3kg 4.3kg 4.3kg 5.0kg Additional Drain Pump Built-in Built-in
Shipping Weight (kg) 6.3kg 6.3kg 6.3kg 7.0kg Accessories Drain Pump Max. Lifting Height/Displacement 750/24 750/24
Net Dimensions (WxHxD) (mm) 1198 x 35 x 500mm 1198 x 35 x 500mm 1198 x 35 x 500mm 1410 x 35 x 500mm WiFi Kit Yes Yes
Shipping Dimensions (WxHxD) (mm) 1262 x 124 x 568mm 1262 x 124 x 568mm 1262 x 124 x 568mm 1473 x 124 x 568mm App Connectivity SmartThings App Support Yes Yes

Note: Note:

1) Mode: HP, Heat Pump 1) Mode: HP, Heat Pump


2) Nominal cooling capacities are based on indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m 2) Nominal cooling capacities are based on indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m
3) Nominal heating capacities are based on indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m 3) Nominal heating capacities are based on indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m
4) Sound pressure was acquired in a dead room. Thus, actual noise level may be different depending on the installation conditions. 4) Sound pressure was acquired in a dead room. Thus, actual noise level may be different depending on the installation conditions.

Optional accessories Optional accessories

Individual Panel Individual Panel


Controllers Options Controllers Options

for Small chassis for Big chassis (Classic) (Z-Slide) (Fluidic)

115 116
Specification
Indoor units • Flexible installation

• Easier drain pump installation

• Slim design

• Easy to maintain

Model AM 02 2 K NL DEH/EU AM028KN LDEH/ EU AM036 KN LDEH/ EU AM056MN LDEH/ EU AM0 71 MNLDE H/E U
Features Type SLI M H O M E D UCT SLIM HOME DUC T SLIM HOME DUC T Home Duct 1 Home Du ct 2
Power Supply (Indoor Unit) [Φ, #, V, Hz] 1 ,2,220~ 240,50 1,2,22 0 ~240 ,50 1,2,22 0 ~240 ,50 1,22 0 ~240 ,50 1,220~240,50
Capacity Cooling [kW] 2.2kW 2. 8 kW 3. 6kW 5. 6kW 7.1kW
Cooling [Btu/h] 7,5 00Bt u/ h 9,60 0 Btu/h 12,30 0 Btu/h 19,1 0 0 Btu/h 24,200B tu /h
Heating [kW] 2.5 kW 3. 2kW 4. 0 kW 6.3kW 8.0kW
Heating [Btu/h] 8,500Bt u/ h 10 ,90 0 Btu/h 13,60 0 Btu/h 21,50 0 Btu/h 27,300B tu /h
Current Input Cooling 0.25A 0 . 28 A 0 . 33A 0 . 62A 0.69A
Heating 0.25A 0 . 30 A 0 . 35A 0 . 58 A 0.65A
Power Input Cooling [kW] 0.03 0kW 0 . 0 34kW 0 . 0 40 kW 0 . 0 73kW 0.082kW
Heating [kW] 0.03 0kW 0 . 0 36kW 0 . 0 42kW 0 . 0 68 kW 0.077kW
Fan Type Siro cc o F a n Si rocco Fan Si rocco Fan Si rocco Fan Sirocco Fan
Motor (Output) [W] 69W 69W 69W 8 4W 84 W
Air Flow Rate (High / Mid / Low) [m3/h] 3 6 0/ 29 4/ 228㎥/ h 423/30 9/258 ㎥/h 492/390 /294㎥/h 930 /750 /570 ㎥ /h 1080/870/660㎥ /h
Air Flow Rate (High / Mid / Low) [l/s] 1 00.00/ 81 .6 7/ 6 3 .3 3 90 .8 3/74.17/63. 33 90 .8 3/74.17/63. 33 258 .33/20 8 . 33/1 58 . 33 300.00/241.67/183.33
External Static Pressure (Min / Std / Max) [mmAq] 1 ( 0~ 3 ) m m A q 1(0 ~3)mmAq 1(0 ~3)mmAq 0 /2/4mmAq 0/2/4mmAq
External Static Pressure (Min / Std / Max) [Pa] 0.00 / 9 .81 / 29 .42P a 0 . 0 0 / 9. 8 1 / 2 9.42Pa 0 . 0 0 / 9. 8 1 / 2 9. 42Pa 0 /19.6/39.2Pa 0/19.6/39.2Pa
Piping Connections Liquid Pipe (Φ, mm) 6 .3 5mm 6. 35mm 6.35mm 6.35mm 9.52mm
Liquid Pipe (Φ, inch) 1/4 1/4 1/4 1/4" 3/8"
Gas Pipe (Φ, mm) 1 2.70m m 12.70 mm 12.70 mm 12.7mm 15.88mm
Gas Pipe (Φ, inch) 1/2 1/2 1/2 1/2" 5/8"
Drain Pipe (Φ,mm) VP 25 ( O D 3 2,I D 25) mm V P25 (OD 32 ,ID 25)mm V P25 (OD 32 ,ID 25)mm V P25 (OD 32 ,ID 25)mm VP25 (OD 32,ID 25)mm
Field Wiring Power Source Wire 1 .5 ~ 2.5 1. 5 ~ 2. 5 1. 5 ~ 2. 5 1. 5 ~ 2. 5 1.5 ~ 2.5
Transmission Cable 0.75 ~ 1 .5 0 . 75 ~ 1 .5 0 . 75 ~ 1 .5 0 . 75 ~ 1 .50 0.75 ~ 1 .50
Refrigerant Type R41 0A ( Co n t a in s fluo rin ated R 410 A(C ontai ns fl uori nated R 410 A(C ontai ns fl uori nated R 410 A(C ontai ns fl uori nated R 4 10A(Contains flu orinate d
g reen h o us e g a s , GW P = 2,0 8 8 ) greenhouse gas, G WP=2,0 8 8 ) greenhouse gas, G WP=2,0 8 8 ) greenhouse gas, G WP=2,0 8 8 ) gree nhou se gas, GWP=2,088)
Control Method EEV I NCLUD ED E E V INC LUDE D E E V INC LUDE D E E V INC LUDE D EEV IN CLU DED
Sound Sound Pressure Level (High / Mid / Low) [dB(A)] 26 / 23 / 1 9 dBA 28 /2 4/19dBA 31 /26/20 dBA 34/30 /26dBA 34 /30/27d B A
Sound Power Level 42.0dBA 44.0 dBA 46.0 dBA 49.0 dBA 49.0d B A
External Dimension (Indoor Unit) Net Weight (kg) 1 5.3 kg 15. 3kg 15.7kg 18 . 9kg 22.3kg
Shipping Weight (kg) 1 8.2kg 18 .2 kg 18 . 6kg 21.8 kg 25.3kg
Net Dimensions (WxHxD) (mm) 700* 1 9 9 * 440m m 70 0 *199*440 mm 70 0 *199*440 mm 90 0 ×199×440 mm 1100x199x440mm
Shipping Dimensions (WxHxD) (mm) 9 49 * 280* 5 44mm 949*28 0 *544mm 949*28 0 *544mm 1151 x2 8 0 x544mm 1351x280x54 4mm
Additional Accessories Drain Pump Buil t -in Bui lt-i n Bui lt-i n Bui lt-i n B u ilt- in
Drain Pump Max. Lifting Height/Displacement 750 mm / ( 24 Lit er/ h) 750 mm / (24 Li ter/h) 750 mm / (2 4 Li ter/h) 750 / (24 Li ter/h) 750 / (24 Lite r/h)
Air Filter Y Y Y Y Y

Note:

1) Mode: HP, Heat Pump


2) Nominal cooling capacities are based on indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m
3) Nominal heating capacities are based on indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m
4) Sound pressure was acquired in a dead room. Thus, actual noise level may be different depending on the installation conditions.

Optional accessories

Individual
Controllers

117 118
Specification
Indoor units
• Narrow width

• Strong and large coverage area

• Silent operation with the static pressure control

• Easy to maintain

Model AM028ANMPKH/EU AM036ANMPKH/EU AM045ANMPKH/EU AM056ANMPKH/EU AM071ANMPKH/EU AM090ANMPKH/EU AM112ANMPKH/EU AM128ANMPKH/EU AM140ANMPKH/EU AM160KNMDEH1EU
Power Supply (Indoor Unit) [Φ, #, V, Hz] 1,2,220~240,50/60 1,2,220~240V,50/60 1,2,220~240V,50/60 1,2,220~240V,50/60 1,2,220~240V,50/60 1,2,220~240V,50/60 1,2,220~240V,50/60 1,2,220~240V,50/60 1,2,220~240V,50/60 1,2,220-240,50
Features Type Global Duct Global Duct Global Duct Global Duct Global Duct Global Duct Global Duct Global Duct Global Duct MSP DUCT
System Mode HP / HR HP / HR HP / HR HP / HR HP / HR HP / HR HP / HR HP / HR HP / HR HP/HR
Capacity Cooling [kW] 2.8kW 3.6kW 4.5kW 5.6kW 7.1kW 9.0kW 11.2kW 12.8kW 14.0kW 16.00kW
Cooling [Btu/h] 12,300Btu/h 15,400Btu/h 19,100Btu/h 24,200Btu/h 30,700Btu/h 38,200Btu/h 43,700Btu/h 47,800Btu/h 54,600Btu/h
Heating [kW] 3.2kW 4.0kW 5.0kW 6.3kW 8.0kW 10.0kW 12.5kW 13.8kW 16.0kW 18.00kW
Heating [Btu/h] 13,600Btu/h 17,100Btu/h 21,500Btu/h 27,300Btu/h 34,100Btu/h 42,700Btu/h 47,100Btu/h 54,600Btu/h 61,400Btu/h
Current Input Cooling 0.40A 0.4A 0.5A 0.6A 1.0A 1.2A 1.2A 1.4A 1.7A 2.24A
Heating 0.40A 0.4A 0.5A 0.6A 1.0A 1.2A 1.2A 1.4A 1.7A 2.24A
Power Input Cooling [W] 42.0W 45.0W 55.0W 70.0W 110.0W 135.0W 130.0W 160.0W 210.0W 485.00W
Heating [W] 42.0W 45.0W 55.0W 70.0W 110.0W 135.0W 130.0W 160.0W 210.0W 485.00W
Fan Type Sirocco Fan Sirocco Fan Sirocco Fan Sirocco Fan Sirocco Fan Sirocco Fan Sirocco Fan Sirocco Fan Sirocco Fan Sirocco Fan
Motor (Output) [W] 153W 153W 153W 153W 153W 153W 244W 244W 244W 370 x 1W
Number of Unit (EA) 1EA 1EA 1EA 1EA 1EA 1EA 1EA 1EA 1EA
Air Flow Rate (High / Mid / Low) [㎥/min] 10.5/9/7CMM 12/9.5/7.5CMM 14/11/8CMM 16/13.5/9.0CMM 21/18/13CMM 27/22/16CMM 30/25/18CMM 36/30/23CMM 40/34/24CMM 43.00/38.00/30.50CMM
External Static Pressure (Min / Std / Max) [mmAq] 0/2.5/15mmAq 0/2.5/15mmAq 0/3/15mmAq 0/3/15mmAq 0/3/15mmAq 0/4/15mmAq 0/5.2/15mmAq 0/5.2/15mmAq 0/5.2/15mmAq 4.00/8.00/14.00mmAq
External Static Pressure (Min / Std / Max) [Pa] 0.00/24.52/147.10Pa 0.00/29.42/147.10Pa 0.00/29.42/147.10Pa 0.00/29.42/147.10Pa 0.00/39.23/147.10Pa 0.00/50.99/147.10Pa 0.00/50.99/147.10Pa 0.00/50.99/147.10Pa 39.23/78.45/137.29Pa
Piping Connections Liquid Pipe (Φ, mm) 6.35mm 6.35mm 6.35mm 6.35mm 9.52mm 9.52mm 9.52mm 9.52mm 9.52mm 9.52mm
Liquid Pipe (Φ, inch) 1/4" 1/4" 1/4" 1/4" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8"
Gas Pipe (Φ, mm) 12.7mm 12.7mm 12.7mm 12.7mm 15.88mm 15.88mm 15.88mm 15.88mm 15.88mm 15.88mm
Gas Pipe (Φ, inch) 1/2" 1/2" 1/2" 1/2" 5/8" 5/8" 5/8" 5/8" 5/8" 5/8"
Drain Pipe (Φ,mm) VP25 (OD 25,ID 20)mm VP25 (OD 25,ID 20)mm VP25 (OD 25,ID 20)mm VP25 (OD 25,ID 20)mm VP25 (OD 25,ID 20)mm VP25 (OD 25,ID 20)mm VP25 (OD 25,ID 20)mm VP25 (OD 25,ID 20)mm VP25 (OD 25,ID 20)mm VP25 (OD 32,ID 25)mm
Field Wiring Power Source Wire 1.5 ~ 2.5 1.5 ~ 2.5 1.5 ~ 2.5 1.5 ~ 2.5 1.5 ~ 2.5 1.5 ~ 2.5 1.5 ~ 2.5 1.5 ~ 2.5 1.5 ~ 2.5 1.5 ~ 2.5
Transmission Cable 0.75 ~ 1.5 0.75 ~ 1.5 0.75 ~ 1.5 0.75 ~ 1.5 0.75 ~ 1.5 0.75 ~ 1.5 0.75 ~ 1.5 0.75 ~ 1.5 0.75 ~ 1.5 0.75 ~ 1.50
Refrigerant Type R410A(Contains fluorinated R410A R410A R410A R410A R410A R410A R410A R410A R410A(Fluorinated
greenhouse gas, GWP=2,088) greenhouse gas, GWP=2,088)
Control Method EEV INCLUDED EEV INCLUDED EEV INCLUDED EEV INCLUDED EEV INCLUDED EEV INCLUDED EEV INCLUDED EEV INCLUDED EEV INCLUDED EEV INCLUDED
Sound Pressure Level (High / Mid / Low) [dB(A)] 28/26/24dBA 30/27/24dBA 31/28/25dBA 32/29/25dBA 36/32/27dBA 37/33/29dBA 36/33/30dBA 37/34/31dBA 39/36/33dBA
Sound Power Level 51dBA 53dBA 54dBA 57dBA 60dBA 61dBA 61dBA 62dBA 64dBA 69.0dBA
External Dimension (Indoor Unit) Net Weight (kg) 27.9kg 27.9kg 27.9kg 27.9kg 27.9kg 35.4kg 39.9kg 39.9kg 39.9kg 50.5kg
Shipping Weight (kg) 32.0kg 32.0kg 32.0kg 32.0kg 32.0kg 40.5kg 46.4kg 46.4kg 46.4kg 59kg
Net Dimensions (WxHxD) (mm) 850x250x700mm 850 x 250 x 700mm 850 x 250 x 700mm 850 x 250 x 700mm 850 x 250 x 700mm 1200 x 250 x 700mm 1300 x 300 x 700mm 1300 x 300 x 700mm 1300 x 300 x 700mm 1200 x 360 x 650mm
Shipping Dimensions (WxHxD) (mm) 1064x320x784mm 1064 x 320 x 784mm 1064 x 320 x 784mm 1064 x 320 x 784mm 1064 x 320 x 784mm 1429 x 320 x 779mm 1529 x 370 x 779mm 1529 x 370 x 779mm 1529 x 370 x 779mm 1480 x 420 x 790mm
Additional Accessories Drain Pump Built-in Built In Built In Built In Built In Built In Built In Built In Built In Drain Pump Included

Note:

1) Mode: HP, Heat Pump


2) Nominal cooling capacities are based on indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m
3) Nominal heating capacities are based on indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m
4) Sound pressure was acquired in a dead room. Thus, actual noise level may be different depending on the installation conditions.

Optional accessories

Individual
Controllers

119 120
Specification
Indoor units • High external static pressure • 2Way installation
• Strong and large coverage area • Compact but powerful
• Silent operation with the static • Stay-clean panel
pressure control
• Sophisticated control
• Easy to maintain

Model AM160KNMDEH1EU AM224JNHFKH/EU AM280FNHDEH/EU Model AM056FNCDEH/EU AM071FNCDEH/EU AM112JNCDKH/EU AM140JNCDKH/EU


Power Supply (Indoor Unit) [Φ, #, V, Hz] 1,2,220-240,50 1,2,220-240,50 1,2,220-240,50 Features Type CEILING CEILING Big Ceiling Big Ceiling
Capacity Cooling [kW] 16.00kW 22.4kW 28.0kW Model Name Indoor Unit AM056FNCDEH/EU AM071FNCDEH/EU AM112JNCDKH/EU AM140JNCDKH/EU
Cooling [Btu/h] 54,600Btu/h 76,400Btu/h 95,500Btu/h Power Supply (Indoor Unit) [Φ, #, V, Hz] 1,2,220-240,50 1,2,220-240,50 1,2,220-240,50/60 1,2,220-240,50/60
Heating [kW] 18.00kW 25.0kW 31.5kW Capacity Cooling [kW] 5.6kW 7.1kW 11.2kW 14.0kW
Heating [Btu/h] 61,400Btu/h 85,300Btu/h 107,500Btu/h Cooling [Btu/h] 19,100Btu/h 24,200Btu/h 38,200Btu/h 47,800Btu/h
Current Input Cooling 2.24A 5.90A Heating [kW] 6.3kW 8.0kW 12.5kW 16.0kW
Heating 2.24A 5.90A Heating [Btu/h] 21,500Btu/h 27,300Btu/h 42,700Btu/h 54,600Btu/h
Power Input Cooling [W] 485.00W 0.530kW 0.790kW Current Input Cooling 0.33A 0.35A 0.94A 1.45A
Heating [W] 485.00W 0.530kW 0.790kW Heating 0.28A 0.29A 0.83A 1.45A
Fan Type Sirocco Fan Sirocco Fan Sirocco Fan Power Input Cooling [kW] 0.072kW 0.080kW 0.092kW 0.160kW
Motor (Output) [W] 370 x 1W 630 x 1WW 400 x 1W Heating [kW] 0.072kW 0.077kW 0.080kW 0.160kW
Air Flow Rate (High / Mid / Low) [㎥/min] 43.00/38.00/30.50CMM 4320/3660/3000㎥/h 4320/3900/3480㎥/h Fan Type Sirocco Fan Sirocco Fan Sirocco Fan Sirocco Fan
Air Flow Rate (High / Mid / Low) [l/s] 716.67/633.33/508.33 1200.24/1016.87/833.5 1,200.00/1,083.33/966.67 Motor (Output) [W] 60 x 1W 120 x 1W 260W 355W
External Static Pressure (Min / Std / Max) [mmAq] 4.00/8.00/14.00mmAq 5.0/7.34/20mmAq 5.00/15.00/28.00mmAq Air Flow Rate (High / Mid / Low) [m3/h] 840/780/720㎥/h 1080/990/900㎥/h 1758/1434/1110㎥/h 2184/1848/1560㎥/h
External Static Pressure (Min / Std / Max) [Pa] 39.23/78.45/137.29Pa 50/72/200Pa 49.03/147.10/274.59Pa Air Flow Rate (High / Mid / Low) [l/s] 233.33/216.67/200.00 300.00/275.00/250.00 488.33/398.33/308.33 606.66/513.33/433.33
Piping Connections Liquid Pipe (Φ, mm) 9.52mm 3/8"mm 9.52mm Piping Connections Liquid Pipe (Φ, mm) 6.35mm 9.52mm 9.52mm 9.52mm
Liquid Pipe (Φ, inch) 3/8" 19.05mm 3/8" Liquid Pipe (Φ, inch) 1/4" 3/8" 3/8" 3/8"
Gas Pipe (Φ, mm) 15.88mm 3/4"mm 22.22mm Gas Pipe (Φ, mm) 12.70mm 15.88mm 15.88mm 15.88mm
Gas Pipe (Φ, inch) 5/8" VP25 (OD25,ID 20)mm 7/8" Gas Pipe (Φ, inch) 1/2" 5/8" 5/8" 5/8"
Drain Pipe (Φ,mm) VP25 (OD 32,ID 25)mm 1.5 ~ 2.5mm VP25 (OD 32,ID 25)mm Drain Pipe (Φ,mm) ID 18 HOSEmm ID 18 HOSEmm VP25 (OD25,ID 20)mm VP25 (OD25,ID 20)mm
Field Wiring Power Source Wire 1.5 ~ 2.5 0.75 ~ 1.5 1.5 ~ 2.5 Field Wiring Power Source Wire 1.5 ~ 2.5 1.5 ~ 2.5 1.5 ~ 2.5 1.5 ~ 2.5
Transmission Cable 0.75 ~ 1.50 R410A(Fluorinated green gas) 0.75 ~ 1.50 Transmission Cable 0.75 ~ 1.50 0.75 ~ 1.50 0.75 ~ 1.50 0.75 ~ 1.50
Refrigerant Type R410A(Fluorinated R410A(Contains fluorinated R410A(Contains fluorinated Refrigerant Type R410A(Contains fluorinated R410A(Contains fluorinated R410A(Contains fluorinated R410A(Contains fluorinated
greenhouse gas, GWP=2,088) greenhouse gas, GWP=2,088) greenhouse gas, GWP=2,088) greenhouse gas, GWP=2,088) greenhouse gas, GWP=2,088) greenhouse gas, GWP=2,088) greenhouse gas, GWP=2,088)
Control Method EEV INCLUDED EEV INCLUDED EEV INCLUDED Control Method EEV NOT INCLUDED EEV NOT INCLUDED EEV INCLUDED EEV INCLUDED
Sound Sound Pressure 43.0/40.0/36.0dBA 44/40/36dBA 48/46/43dBA Sound Sound Pressure Level (High / Mid / Low) [dB(A)] 40/37/34dBA 44/42/40dBA 45/41/37dBA 46/43/38dBA
Sound Power Level 69.0dBA 81.0dBA 79.0dBA Sound Power Level 60 .0dBA 63 .0dBA 61.0dBA 63.0dBA
External Dimension (Indoor Unit) Net Weight (kg) 50.5kg 82.5kg 89.0kg External Dimension Net Weight (kg) 21.0kg 21.0kg 33.5kg 42.5kg
Shipping Weight (kg) 59kg 92.0kg 99.0kg (Indoor Unit) Shipping Weight (kg) 25.5kg 25.5kg 39.5kg 48.5kg
Net Dimensions (WxHxD) (mm) 1200 x 360 x 650mm 1350x 910 x 450mm 1240 x 470 x 1040mm Net Dimensions (WxHxD) (mm) 1000 x 650 x 200mm 1000 x 650 x 200mm 1350*235*675mm 1650*235*675mm
Shipping Dimensions (WxHxD) (mm) 1480 x 420 x 790mm 1612 x 984 x 519mm 1507 x 558 x 1155mm Shipping Dimensions (WxHxD) (mm) 1080 x 730 x 300mm 1080 x 730 x 300mm 1439*758*321mm 1739*758*321mm
Additional Accessories Drain Pump Drain Pump Included MDP-G075SP, MDP-G075SQ MDP-N047SNC1D

Note: Note:

1) Mode: HP, Heat Pump 1) Mode: HP, Heat Pump


2) Nominal cooling capacities are based on indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m 2) Nominal cooling capacities are based on indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m
3) Nominal heating capacities are based on indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m 3) Nominal heating capacities are based on indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m
4) Sound pressure was acquired in a dead room. Thus, actual noise level may be different depending on the installation conditions. 4) Sound pressure was acquired in a dead room. Thus, actual noise level may be different depending on the installation conditions.

Optional accessories Optional accessories

Individual Individual EEV


Controllers Controllers KIT

121 122
Specification
Indoor units

• Clean-cut front panel

• Silver accent line

• Bottom opening front panel

• Improved dust-filtration

Model AM015KNQDEH/EU AM022KNQDEH/EU AM028KNQDEH/EU AM045KNQDEH/EU AM071KNQDEH/EU AM036KNQDEH/EU AM056TNVDKH/EU


Capacity Cooling [kW] 1.5kW 2.2kW 2.8kW 4.5kW 6.8kW 3.6kW 5.6kW
Heating [kW] 1.7kW 2.5kW 3.2kW 5.0kW 7.0kW 4.0kW 6.3kW
Power Supply (Indoor Unit) [Φ, #, V, Hz] 1,2,220-240,50 1,2,220-240,50 1,2,220-240,50 1,2,220-240,50 1,2,220-240,50 1,2,220-240,50 1, 220~240V, 50/60Hz
Current Input Cooling 0.20A 0.20A 0.22A 0.27A 0.28A 0.23A 0.35A
Heating 0.20A 0.20A 0.22A 0.27A 0.28A 0.23A 0.35A
Power Input Cooling [kW] 0.032kW 0.032kW 0.038kW 0.047kW 0.051kW 0.042kW 0.052kW
Heating [kW] 0.034kW 0.035kW 0.039kW 0.047kW 0.053kW 0.042kW 0.052kW
Fan Type Crossflow Fan Crossflow Fan Crossflow Fan Crossflow Fan Crossflow Fan Crossflow Fan Crossflow Fan
Air Flow Rate (High / Mid / Low) [m3/h] 372/342/300㎥/h 396/342/300㎥/h 420/372/300㎥/h 834/744/660㎥/h 942/846/720㎥/h 510/450/360㎥/h 261.7/230.0/200.0
Piping Connections Liquid Pipe (Φ, mm) 6.35mm 6.35mm 6.35mm 6.35mm 9.52mm 6.35mm 6.35mm
Liquid Pipe (Φ, inch) 1/4″ 1/4″ 1/4″ 1/4″ 3/8″ 1/4″ 1/4"
Gas Pipe (Φ, mm) 12.7mm 12.7mm 12.7mm 12.7mm 15.88mm 12.7mm 12.7mm
Gas Pipe (Φ, inch) 1/2″ 1/2″ 1/2″ 1/2″ 5/8″ 1/2″ 1/2"
Drain Pipe (Φ,mm) ID 18 HOSEmm ID 18 HOSEmm ID 18 HOSEmm ID 18 HOSEmm ID 18 HOSEmm ID 18 HOSEmm ID 18 HOSEmm
Field Wiring Power Source Wire 1.5 ~ 2.5 1.5 ~ 2.5 1.5 ~ 2.5 1.5 ~ 2.5 1.5 ~ 2.5 1.5 ~ 2.5 1.5 ~ 2.5
Transmission Cable 0.75 ~ 1.50 0.75 ~ 1.50 0.75 ~ 1.50 0.75 ~ 1.50 0.75 ~ 1.50 0.75 ~ 1.50 0.75 ~ 1.5
Refrigerant Type R410A(Contains fluorinated R410A(Contains fluorinated R410A(Contains fluorinated R410A(Contains fluorinated R410A(Contains fluorinated R410A(Contains fluorinated R410A
greenhouse gas, GWP=2,088) greenhouse gas, GWP=2,088) greenhouse gas, GWP=2,088) greenhouse gas, GWP=2,088) greenhouse gas, GWP=2,088) greenhouse gas, GWP=2,088)
Sound Sound Pressure Level (High / Mid / Low) [dB(A)] 30/28/25dBA 31/28/25dBA 31/29/26dBA 38/35/33dBA 40/38/35dBA 36/33/29dBA 40/37/34/29(Wind free)dBA
Sound Power Level 47.0dBA 48.0dBA 48.0dBA 53.0dBA 55.0dBA 51.0dBA 58dBA
External Dimension (Indoor Unit) Net Weight (kg) 8.5kg 8.5kg 9.0kg 12.5kg 12.5kg 9.0kg 12.0kg
Shipping Weight (kg) 10.2kg 10.2kg 10.6kg 14.5kg 14.5kg 10.6kg 14.0kg
Net Dimensions (WxHxD) (mm) 820 x 285 x 227mm 820 x 285 x 227mm 820 x 285 x 227mm 1065 x 298 x 243mm 1065 x 298 x 243mm 820 x 285 x 227mm 1055x299x215mm
Shipping Dimensions (WxHxD) (mm) 880 x 280 x 363mm 880 x 280 x 363mm 880 x 280 x 363mm 1128 x 299 x 378mm 1128 x 299 x 378mm 880 x 280 x 363mm 1115x290x375mm

Note:

1) Mode: HP, Heat Pump


2) Nominal cooling capacities are based on indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m
3) Nominal heating capacities are based on indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m
4) Sound pressure was acquired in a dead room. *WindFree™ Models Thus, actual noise level may be different depending on the installation conditions.
5) Cordless controllers comes in indoor unit box.

Optional accessories

Individual
Controllers

123 124
Specification
Indoor units

• Integrated solution

• Water temperature choice

• Easy and simple connection

• Integrated control

Attribute/Model code AM160FNBFEB/EU AM160FNBDEH/EU AM250FNBFEB/EU AM320FNBDEH/EU AM500FNBDEH/EU


Model Name Indoor unit
1, 2, 220-240, 50
Capacity NA 14 NA 28 44.8
NA 47,800 NA 95,600 152,900
16 16 25 31.5 50.4
54,600 54,600 85,300 107,500 172,000
Power input (Nominal) - 0.01 - 0.01 0.01
3.1 0.01 5 0.01 0.01
Current input (Nominal) Cooling 1) - 0.05 A - 0.05 A 0.05 A
Heating 2) 14.3 A 0.05 A 23.1 A 0.05 A 0.05 A
Energy grade of space heater (55 ºC / 35 ºC) A+ / A+ NA / A++ A+ / A+ NA / A+ NA / A+
Energy grade of package of space heater A+ A++ A+ A+ A+
Condenser Type PHE PHE PHE PHE PHE
PT 1 (25A)"" PT 1 (25A)" PT 1 (25A)"" PT 1 (25A)" PT 1-1/4 (32A)"
23 48 36 92 150
1.38 2.88 2.16 5.52 9
Piping connections 9.52 9.52 9.52 9.52 12.7
15.88 15.88 15.88 22.2 28.58
Field wiring Power source wire 4 2.5 4 2.5 2.5
Transmission cable 0.75 ~ 1.5 0.75 ~ 1.5 0.75 ~ 1.5 0.75 ~ 1.5 0.75 ~ 1.5
Refrigerant Type R410A R410A R410A R410A R410A
Control method EEV EEV EEV EEV EEV
Factory charging (kg) 2.15 NA 2.15 NA NA
Factory charging (tCO2e) 3.07 tCO2e NA 3.07 tCO2e NA NA
Sound 42 27 42 28 31
External dimension (Indoor unit) Net weight (kg) 104 29 104 33 40
Shipping weight (kg) 107 31 107 35 42
Net dimensions (WxHxD) (mm) 518 x 1,210 x 330 518 x 627 x 330 518 x 1,210 x 330 518 x 627 x 330 518 x 627 x 330
Net dimensions (WxHxD) (cm) 51.8 x 121 x 33 51.8 x 62.7 x 33 51.8 x 121 x 33 51.8 x 62.7 x 33 51.8 x 62.7 x 33
Shipping dimensions (WxHxD) (mm) 652 x 1,289 x 426 652 x 700 x 426 652 x 1,289 x 426 652 x 700 x 426 652 x 700 x 426
Shipping dimensions (WxHxD) (cm) 65.2 x 128.9 x 42.6 65.2 x 70 x 42.6 65.2 x 128.9 x 42.6 65.2 x 70 x 42.6 65.2 x 70 x 42.6
Operating temp. range NA -5.0 ~ 48.0 NA -5.0 ~ 48.0 -5.0 ~ 48.0
-20 ~ 35 -20 ~ 35 -20 ~ 35 -20 ~ 35 -20 ~ 35

Note:

1) Nominal cooling capacities are based on:


- Water temperature: 23°C inlet, 18°C outlet
- Indoor temperature: 27°C DB, 19°C WB
- Outdoor temperature: 35°C DB, 24°C WB
2) Nominal heating capacities are based on:
- Water temperature: 30°C inlet, 35°C outlet
- Indoor temperature: 20°C DB
- Outdoor temperature: 7°C DB, 6°C WB
3) Sound pressure was acquired in an anechoic room. Thus, actual noise level may be different depending on the installation conditions.

125 126
Specification Specification
Indoor units Indoor units

• Powerful and clean cooling • Slim design • Direct expansion (DX) coil

• 4Way auto-swing • New diamond type element

• Full touch panel control

• Auto shutter Attribute/Model code AM050FNKDEH/EU AM100FNKDEH/EU


1,2,220-240,50
System Mode HP/HR HP/HR
Capacity 5.1 10.5
17,400 Btu/h 35,800 Btu/h
6.5 13.2
22,200 45,000
Power input (Nominal) 0.22 0.51
Attribute/Model code AM140RNPDKH/EU AM280RNPDKH/EU 0.22 0.51
1,2,220-240,50/60 1,2,220-240,50/60 Current input (Nominal) 1.7 3.7
Capacity 14 28 1.7 3.7
47,800 95,500 138.83/138.83/100.00 277.83/277.83/191.67

16 31.5
8.70/10.20/16.32 7.60/9.20/15.30
85.32/100.03/160.04 74.53/90.22/150.04
54,600 107,500
500/500/360 1000/1000/690
Poer input (Nominal) 0.19 0.995
Piping connections 6.35 6.35
0.19 0.995
12.7 12.7
Current input (Nominal) Cooling 1) Amp 0.9 4.73 VP25 (OD 32,ID 25) VP25 (OD 32,ID 25)
Heating 2) Amp 0.9 4.73 Field wiring Power source wire 1.5 ~ 2.5 1.5 ~ 2.5
Fan 1236/1077/971 2471/2118/1765 Transmission cable 0.75 ~ 1.50 0.75 ~ 1.50
NA NA Refrigerant Type R410A R410A

Piping connections 9.52 9.52


Control method EEV INCLUDED EEV INCLUDED
Sound 36/32/28 dBA 36/33/31 dBA
15.88 22.22
Sound power 67 67
ID 18 HOSE ID 18 HOSE
External dimension (Indoor Net weight (kg) 61 90
Field wiring Power source wire 2.5 2.5 unit) Shipping weight (kg) 75.2 107.5
Transmission cable VCTF 0.75 ~ 1.5 VCTF 0.75 ~ 1.5 Net dimensions (WxHxD) (mm) 1553 x 270 x 1000 1763 x 340 x 1135
Refrigerant Type R410A R410A Net dimensions (WxHxD) (cm) 155.3 x 27 x 100 176.3 x 34 x 113.5
Control method EEV INCLUDED EEV INCLUDED Shipping dimensions (WxHxD) (mm) 1847 x 349 x 1300 2027 x 428 x 1424
Sound 70 74 Shipping dimensions (WxHxD) (cm) 184.7 x 34.9 x 130 202.7 x 42.8 x 142.4

External dimension (Indoor unit) Net weight (kg) 48 115


Shipping weight (kg) 55 130 Attribute/Model code AN050JSKLKN/EU AN100JSKLKN/EU
Net dimensions (WxHxD) (mm) 610 x 1850 x 400 1100 x 1800 x 485 1,2,220-240,50/60
Net dimensions (WxHxD) (cm) 61 x 185 x 40 110 x 180 x 48.5 Temperature exchange rate Cooling 70.00% 70.00%
Shipping dimensions (WxHxD) (mm) 705 x 1963 x 493 1177 x 1950 x 563 Heating 74.00% 74.00%
Enthalpy exchange rate Heating 50.00% 50.00%
Shipping dimensions (WxHxD) (cm) 70.5 x 196.3 x 49.3 117.7 x 195 x 56.3
Cooling 70.00% 70.00%
Available
Power input (Nominal) [kW 175 450
1.1 2.9
Fan 500 / 500 / 360 1000 / 1000 / 690
85 / 100 / 165 75 / 90 / 155
External dimension (Indoor Net weight (kg) 42.5 67
unit) Net dimensions (WxHxD) (mm) 1012 x 270 x 1000 mm 1220 x 340 x 1135 mm
Note:
Note:
1) Mode: HP, Heat Pump
1) Nominal cooling capacities are based on indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m
2) Nominal cooling capacities are based on indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m
2) Nominal heating capacities are based on indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m
3) Nominal heating capacities are based on indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m
3) Humidifying capacity is based on indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m
4) Sound pressure was acquired in a dead room. Thus, actual noise level may be different depending on the installation conditions.
4) Sound pressure

Optional accessories Optional accessories

Individual Individual
Controllers Controllers

127 128
CAC is a smart choice for saving both money and
[Link] economical outdoor unit employs advanced
technologies to minimise waste and improve efficiency.
By adopting the smart inverter technology, CAC not only
offers silent operation, but also provides outstanding
cooling and heating performance that is faster than 360 Cassette
conventional products.
Cold draft free
Perfect, even cooling
Circular to perfectly fit in everywhere
Fast cooling

Free™
Slim and compact design
Refined elegance and comfort to enhance any décor
Visually appealing panel
Light indoor unit

Individual blade control


Optimal airflow for high ceilings
Aesthetic panel and display

129 130
Specification
CAC

Model AC 100T N4 P K C /EA AC140T N 4PKC/ EA AC035T N 1DKC/ EA AC052T N 1DKC/ EA AC0 71 T N1 DKC/E A
Features Type 1 0kW -1 Φ -3 6 0 CST 14kW-1Φ-360 C ST 3. 5kW-1Φ-1Way 5. 2kW-1Φ-1Way 7.1kW- 1Φ- 1Way
Capacity Cooling [kW] 3 .0 / 1 0.0 / 1 2.0kW 3. 5 / 13. 4 / 15. 5kW 1. 0 / 3.5 / 4.1kW 1. 5 / 5. 0 / 6.0 kW 1.8 / 6.1 / 7.8kW
Power Supply (Indoor Unit) [Φ, #, V, Hz] 1 ,2,220-240,5 0 1,2,22 0 -240 ,50 1,2,22 0 -240 ,50 1,2,22 0 -240 ,50 1,2,220- 240,50
Current Input Cooling 3 .0/ 1 4.8/ 20.4A 3. 7/20 .4/28 .0 A 1. 6/5. 4/7.5A 1. 7/7. 1/9.5A 2.3/9.3/16.0A
Energy Efficiency EER (Cooling) [W/W] 3 .20 3. 0 3 3. 35 3. 40 3.10
Power MCA 26 .0A 34.0 A 11.5A 21.5A 21.5A
MFA 3 0.0 A 40 .0 A 12.7A 25.0 A 25.0A
Power Input Cooling 1) N/ A N/A 0 . 24/1 .0 45/1. 5kW 0 . 3/1. 47/2. 1kW 0.4/1.97/3.6kW
Compressor Type Twin BLD C Ro t a ry Tw i n BLDC R otary BL DC R otary Tw i n BLDC R otary Twin B LDC Rotary
Output(kW) 2.82kW 4. 19kW 0 . 8 3kW 1. 42 kW 2.32kW
Model Name UG8T 3 00F UBJ U UG 5TK 1450 FJX UG 9AJ30 90 FE R UG 9TK 3150 FE 4 U G8T265FXAEW
Oil Type POE POE POE POE POE
Oil (Initial Charge) [cc] 1 200c c 170 0 cc 32 0 cc 50 0 cc 700cc
Fan Type Turbo F a n Turbo Fan C rossfl ow Fan C rossfl ow Fan Crossflow Fan
Motor (Output) [W] 9 7W 97W 27W 65W 65W
Air Flow Rate (High / Mid / Low) [㎥/min] 3 1 .2/ 25 .5/ 1 9 .8CM M 33.3/2 7. 0 /2 1. 7C MM 9.0 /8 . 2/7.2C MM 14.0 /1 3. 0 /12. 0 C MM 15.0/14.0/12.5CMM
Piping Connections Liquid Pipe (Φ, mm) 9 .5 2m m 9. 52 mm 6. 35mm 6. 35mm 6.35mm
Liquid Pipe (Φ, inch) 3 / 8" 3/8 " 1/4" 1/4" 1/4"
Gas Pipe (Φ, mm) 1 5.88m m 15. 8 8 mm 9.52mm 12.7mm 15.88mm
Gas Pipe (Φ, inch) 5 / 8" 5/8 " 3/8 " 1/2" 5/8"
Installation Max. Length [m] 5 0m 75m 20 m 30 m 50m
Installation Max. Height [m] 3 0m 30 m 15m 20 m 30m
Refrigerant Type R41 0A R 410 A R 410 A R 410 A R4 10A
Control Method EEV EEV EEV EEV EEV
Factory Charging (kg) 3 .00kg 3. 40 kg 1. 0 5kg 1. 30 kg 2.00kg
Sound Sound Pressure Level (High / Mid / Low) [dB(A)] 44/ 3 9 / 3 3 dBA 45/42/38 dBA 38 /35/32dBA 41/38 /35dBA 46/4 2/38d B A
External Dimension (Indoor Unit) Net Weight (kg) 25.5kg 25.5kg 9.2kg 13.4kg 13.4kg
Shipping Weight (kg) 3 0.3 kg 30 .3kg 12.0 kg 16.5kg 16.5kg
Net Dimensions (WxHxD) (mm) 9 47 x 3 6 5 x 9 47mm 947 x 365 x 947mm 970 x 135 x 410 mm 120 0 x 138 x 450 mm 1200 x 138 x 450mm
Shipping Dimensions (WxHxD) (mm) 9 9 0 x 41 4 x 9 9 0mm 990 x 41 4 x 990 mm 1173 x 231 x 48 7mm 1435 x 224 x 52 5mm 1435 x 224 x 525mm
External Dimension (Outdoor Unit) Net Weight (kg) 71 .0kg 8 6.5kg 30 .0 kg 40 .5kg 52.5kg
Shipping Weight (kg) 76 .0kg 96.5kg 32 .5kg 43.5kg 56.5kg
Net Dimensions (WxHxD) (mm) 9 40 x 9 9 8 x 3 3 0m m 940 x 12 10 x 330 mm 790 x 548 x 2 8 5mm 8 8 0 x 638 x 310 mm 880 x 798 x 310mm
Shipping Dimensions (WxHxD) (mm) 9 9 5 x 1 09 6 x 426 m m 995 x 138 8 x 426mm 913 x 62 2 x 371 mm 10 23 x 730 x 413mm 1023 x 881 x 41 3mm
Drain Drain Pipe (Φ,mm) VP 25 ( O D 3 2,I D 25 ) mm V P25 (OD 32 ,ID 25)mm V P25 (OD 32 ,ID 25)mm V P25 (OD 32 ,ID 25)mm VP25 (OD 32,ID 25)mm
Power Supply (Outdoor Unit) [Φ, #, V, Hz] 1 ,2,220-240,50 1,2,22 0 -240 ,50 1,2,22 0 -240 ,50 1,2,22 0 -240 ,50 1,2,220- 240,50
Fan (Outdoor Unit) Air Flow Rate (Cooling) [m³/min] 76 CM M 110 C MM 30 C MM 43C M M 76CMM
Sound (Outdoor Unit) Sound Pressure (Cooling / Heating) [dB(A)] 5 3 dBA 54dBA 48 dBA 50 dBA 50d B A

Optional accessories Optional accessories

Panel Panel
Options Options

for Small chassis for Big chassis (Classic) (Z-Slide) (Fluidic)


(Auto Elevation)

131 132
Specification
CAC

Model AC 05 2 T N4 DK C /EA AC07 1T N 4DKC/ EA AC100T N 4DKC/ EA AC120TN 4DKC/ EA AC1 40 TN4DKC/E A
Features Type 5 .2kW -1 Φ -4W a y 7. 1kW-1Φ-4Way 10 kW-1 Φ-4Way 12kW-1Φ-4Way 14kW- 1Φ- 4Way
Power Supply (Indoor Unit) [Φ, #, V, Hz] 1 ,2,220-240,50 1,2,22 0 -240 ,50 1,2,22 0 -240 ,50 1,2,22 0 -240 ,50 1,2,220- 240,50
Capacity Cooling [kW] 1 .0 / 5 .0 / 6 .0kW 2. 2 / 7. 1 / 8 .5kW 3. 0 / 10 .0 / 12 .0 kW 3. 5 / 12.1 / 14. 0 kW 3.5 / 13.4 / 15.5kW
Current Input Cooling 1 .5 / 6 .7/ 9 .5A 2. 0 /10 .1 /16.0 A 3. 0 /14. 8 /20 .4A 3. 7/16.7/23.0 A 3.7/20.4/28.0A
Energy Efficiency EER (Cooling) [W/W] 3 .5 5 3. 25 3. 20 3. 30 3.03
Power MCA 21 .5A 21.5A 26.0 A 34.0 A 34 .0A
MFA 25.0A 25.0 A 30 .0 A 40 .0 A 40.0A
Power Input Output(kW) 1 .42kW 2. 32 kW 2. 8 2kW 4. 19kW 4.19kW
Model Name UG9 T K3 1 50F E4 UG 8 T265FXAE W UG 8 T30 0 FUBJU UG 5TK 1450 FJX U G5TK1450FJX
Oil Type POE POE POE POE POE
Oil (Initial Charge) [cc] 500c c 70 0 cc 120 0 cc 170 0 cc 1700cc
Fan Type Turbo F a n Turbo Fan Turbo Turbo Tu rb o
Motor (Output) [W] 6 5W 65W 97W 97W 97W
Air Flow Rate (High / Mid / Low) [㎥/min] 1 6 .9 /1 5 .9 / 1 4.9 CM M 20 .8 /1 7. 8 /14. 8 C MM 30 .3/2 4.3/19. 4C MM 31 .5/25. 5/20 . 5C MM 31 .5/26.7/21.8CMM
Piping Connections Liquid Pipe (Φ, mm) 6 .3 5m m 6.35mm 9.52 mm 9.52 mm 9.52mm
Liquid Pipe (Φ, inch) 1 / 4" 1/4" 3/8 " 3/8 " 3/8"
Gas Pipe (Φ, mm) 1 2.7m m 15. 8 8 mm 15. 8 8 mm 15. 8 8 mm 15.88mm
Gas Pipe (Φ, inch) 1 / 2" 5/8 " 5/8 " 5/8 " 5/8"
Installation Max. Length [m] 3 0m 50 m 50 m 75m 75m
Installation Max. Height [m] 20m 30 m 30 m 30 m 30m
Transmission Cable 0.75↑ 0 . 75↑ 0 . 75↑ 0.75↑
Refrigerant Type R41 0A R 410 A R 410 A R 410 A R4 10A
Factory Charging (kg) 1 .3 0kg 2. 0 0 kg 3. 0 0 kg 3. 40 kg 3.40kg
Sound Sound Pressure Level (High / Mid / Low) [dB(A)] 3 5/ 3 3 / 3 1 dBA 40 /36/32 dBA 43/38 /33dBA 44/40 /35dBA 44/4 1/37d B A
External Dimension (Indoor Unit) Net Weight (kg) 1 4.5kg 14.5kg 20 .0 kg 20 .0 kg 20.0kg
Shipping Weight (kg) 1 7.5kg 17.5kg 23.5kg 23.5kg 23.5kg
Net Dimensions (WxHxD) (mm) 840 x 204 x 840m m 8 40 x 20 4 x 8 40 mm 8 40 x 28 8 x 8 40 mm 8 40 x 28 8 x 8 40 mm 84 0 x 288 x 840mm
Shipping Dimensions (WxHxD) (mm) 89 8 x 275 x 89 8m m 8 98 x 275 x 8 98 mm 8 98 x 357 x 8 98 mm 8 98 x 357 x 8 98 mm 898 x 357 x 898mm
Operating Temp. Range Cooling (℃) -1 5 ~ 50℃ -1 5 ~ 50 ℃ -1 5 ~ 50 ℃ -1 5 ~ 50 ℃ - 1 5 ~ 50℃
External Dimension (Outdoor Unit) Net Weight (kg) 40.5kg 52 .5kg 71 .0 kg 8 6.5kg 86.5kg
Shipping Weight (kg) 43 .5kg 56.5kg 76. 0 kg 96.5kg 96.5kg
Net Dimensions (WxHxD) (mm) 880 x 6 3 8 x 3 1 0m m 8 8 0 x 798 x 310 mm 940 x 998 x 330 mm 940 x 12 10 x 330 mm 940 x 1210 x 330mm
Shipping Dimensions (WxHxD) (mm) 1 023 x 73 0 x 41 3 m m 10 23 x 8 8 1 x 41 3mm 995 x 10 96 x 42 6mm 995 x 138 8 x 426mm 995 x 1388 x 426mm
Drain Drain Pipe (Φ,mm) VP 25 ( O D 3 2,I D 25) mm V P25 (OD 32,ID 25)mm V P25 (OD 32 ,ID 25)mm V P25 (OD 32 ,ID 25)mm VP25 (OD 32,ID 25)mm
Power Supply (Outdoor Unit) [Φ, #, V, Hz] 1 ,2,220-240,5 0 1,2,22 0 -240 ,50 1,2,22 0 -240 ,50 1,2,22 0 -240 ,50 1,2,220- 240,50
Fan (Outdoor Unit) Air Flow Rate (Cooling) [m³/min] 43 CM M 76C MM 76C MM 110 C MM 110CMM
Sound (Outdoor Unit) Sound Pressure (Cooling / Heating) [dB(A)] 50dBA 50 dBA 53dBA 53dBA 54 d B A

Optional accessories

Individual Panel
Controtllers Options

PC4NUSKAN
(WindFree™) (Classic) (Black)

133 134
Products designed for easy, holistic control

Overview On/Off controller


Samsung Control System offers convenient, centralised Samsung Control System offers various control options for The On/Off controller controls the system air conditioners
control of individual indoor units or entire groups of indoor units. Users can control multiple units individually or The comprehensive suite of Samsung Control Systems individually or in groups.
multiple units. Using a variety of controls, users can simultaneously in groups to optimise convenience. include the following software, devices, controllers and
centrally manage and control multiple functions for the modules.
units.

This integrated software connects to the Ethernet


Samsung’s Integrated Management System provides to control the system air conditioners through Data
the easiest way to manage a large number of air Management Servers (DMS) from a single computer.
conditioning units at once. This integrated system helps
users control, monitor, manage and maintain every little
detail of their air conditioning needs.

Supporting convenient and optimised management,


Samsung’s Integrated Management System is an ideal
solution for managing large and middle-sized buildings
with many indoor and outdoor units.

Samsung Building Management System (BMS)


makes it possible to control and monitor the air The touch centralised controller is the optimised
conditioning network using the remote control management solution for the mid-sized site.
and monitoring function. Optimum control
keeps the air conditioning system efficient,
saves energy, reduces maintenance costs and
extends the lifespan of the units.

Samsung System Air Conditioning


DMS 2.5 is an explorer-based management device that
products include a full spectrum of
stores and manages all the data relevant to the system
offerings so users can find the most
air conditioner.
convenient, efficient air conditioning
system to suit their needs.

These individual remote controllers are used to


conveniently control single indoor units.

Remote Control

Internet

135 136
Integrated, complete control Integrated, complete control

Users can control and monitor up to 4,096 indoor units, S-NET 3 offers error and event history management, as
including ERV, ERV PLUS, and AHU. Wireless and wired well as report generation and printing, so users can readily
S-NET 3 manages a group of buildings through data remote control restrictions provide greater oversight of identify and resolve issues. The indoor unit also supports
management servers (DMS 2) that individually manage operations. A temperature limit setting, operation mode operation history management.
each building. This Ethernet-based management system lock and multiple/full indoor unit selection extend the
supports flexible, complete control of a wide variety of range of control. Plus, an icon-based indoor unit display
applications, providing users: mode enables easy, more intuitive usability.
Fully integrated PC management software

Up to 16 DMS 2.5 connections through the Ethernet

Centralised management of up to 4,096 indoor units

Schedule and zone control

Error and operation history management

Power distribution management and analysis

With S-NET 3, users can customise the management


structure regardless of the installation structure. They can
also create and edit control zones and manage the tree
Users can ensure optimal power usage with a data structure for the control zones.
query for power distribution and operation times.
Administrators can then generate and print power
distribution reports for a complete survey of operations.
For more specific output, S-NET 3 includes time section
settings for different electricity rates and a group setting
for the power distribution summary.

S-NET 3 enables users to monitor outdoor / indoor unit


cycle data. (The monitoring function is supported only on
specific outdoor unit models.)

S-NET 3 provides easy-to-read graphical schedule


settings, enabling administrators to schedule operation
weekly or daily or exclude dates with the exception date
setting.

137 138
Smarter functionality for maximum control Smarter functionality for maximum control

DMS 2.5 eliminates the need to open each outdoor unit to DMS 2.5 enables administrators to specify the scope of DMS 2.5 simplifies the task of monitoring system
monitor operation. Detailed refrigerant flow check in the unit control and monitoring by each user. operations with its vibrant, intuitive graphical display.
control room and reduced service lead time help keep the Icon-based,
The improved Samsung DMS (Data Management Server) units up and running. color-coded unit control makes it easy to recognise
2.5 is now smarter. It can manage a variety of different indoor unit status, while a handy, stylish controller makes
air conditioning units, and the newly upgraded functions management even more convenient.
can automatically manage the air conditioning system
for users. Key features include:

Built-in web server for PC-independent


management and remote access control
Color indication and icons make it easy
Each user can only to recognize indoor unit status

Multiple upper-level control access control and monitor the


(S-NET 3, Web-client) units which are allowed User-friendly icon-based unit control

to access.

Central management of up to 256 indoor units


including ERV, ERV PLUS, AHU, DVM CHILLER and FCU Kit

User editable control logic Convenient and


stylish controller
Users can control and monitor up to 256 indoor units,
Accessible level management including ERV, ERV PLUS, AHU, DVM CHILLER and FCU Kit, via the DMS 2.5 offers useful function for accommodations.
Internet. Control functions include on/off operation mode, Using this function, the manager can keep the room
Dynamic security management fan speed and temperature settings. temperature when guest goes out for a while.
And manager can pre-cool or pre-heat the room
Operation and error history management
temperature before guest enters the room.
Weekly / daily schedule control Critical data is safely stored on the DMS 2.5 SD memory
card, including:
Indoor/outdoor unit name
Power distribution data
Operation history
DMS power on/off history
System configuration
24oC 26oC
DMS 2.5 features operation history for indoor units, which Occupied Outing
records data for up to 6 months. The operation history
stores the following parameters:

Indoor unit address and name

On/Off time (year, month, day, hour, minute) General users, managers and administrators can be
registered separately by ID and password. Administrators Data backup
Operation mode (cool, heat, auto, fan dry, stop) (utility managers) have the authority to set access levels
for DMS 2.5 functions on users.
Set/Room temperature
Admin Manager User
Functions
Access All Changeable

Control/ O O O
Monitoring
Zone O O X
Management
Power distribution function
Storage Period - Up to 6 Schedule O O O
Current time management even during power months
failure (for 24 hours) Power O O X
Distribution
Data storage in non-volatile memory and SD
memory Emergency stop function with simple System O X X
contract interface

139 140
Extended, zone management

DMS 2.5 provides easy remote control and monitoring through DMS 2.5 records indoor unit operation and error DMS 2.5 enables power distribution to a maximum of
the Internet. Users can receive an email notification to a occurrence history. Recorded history makes it 256 indoor units and provides a data query for watt-
private Internet account in the event of a malfunction. convenient to analyse air conditioner operation and hour, usage time and usage ratio. One year of power
perform unit maintenance. distribution data is saved in storage; these files are saved
in Microsoft® Excel format. DMS 2.5 also provides current
actual power consumption monitoring.

1. Operation On/Off execution time


2. Daily accumulated operation on time
3. Schedule operation execution time

Malfunction
E-mail
1. Error occurred unit name
2. Error details
3. Error occurrence/clear time
4. Error state (solved / unsolved)
Remote Service

General users, managers and administrators can be


registered separately by ID and password. Administrators
(utility managers) have the authority to set access levels for
DMS 2.5 functions by user.

Building Control System Operation Restriction


Users can edit control logic with arithmetic, conditional operators and parameters. Energy can be efficiently used and
reduced for various operation conditions.

The watt-hour meter interface module can be


exclusively used for DMS 2.5 power distribution, displaying
power consumption for each watt-hour meter. It
connects with up to eight watt-hour meters and features
a pulse interface for each meter.
Fire Control System Error Status Indicator

DMS 2.5, the Control and Monitoring Zone edition offers


smart and centralised zone management. Wireless
and wired remote control restrictions provide greater
Logic Outdoor temp < Room temp Room temp < Outdoor temp Outdoor temp < 10 Outdoor temp > 25 oversight of operations. A temperature limit setting and
operation mode restriction extend the range of control.
Control Turn On (Cool air Intake UP) Turn On Air Conditioner Heating mode Cooling mode

EHP / ERV / AHU Arithmetic Equation EHP / ERV / AHU


Parameters AND Function Parameters change
OR
Temperature, Power, Mode...... <, >, =, =>, =<, Average Setting temp, Power, Mode, Fan speed......
A Zone
Example: Energy saving function, operation adjustment depending on outdoor temperature.

141 142
Compatibility interface modules Comprehensive and solid

This touch screen controller can be directly connected to the system air conditioner through the centralised
controller or interface modules, allowing for the control of up to 128 indoor units.

• Operation mode selection (Cooling, Heating or Auto)


MIM-N01 is the communication interface module
• Mixed operation mode protection
between the outdoor units and the upper level
controller, which has a different communication
type. Users connect one interface module to one
outdoor unit. For individual control, MIM-N01 supports • Flexible compatibility options (
a maximum of 48 indoor units; for group control, it DMS 2.5, centralised controller, interface module)
supports a maximum of 16 groups. • Central management of up to 128 indoor units including ERV,
ERV PLUS and AHU
• Detailed cycling information monitoring
• Schedule function (Weekly, Daily)
• USB keyboard support
MIM-N10 is the communication interface module
• Error display
between ERV and controller. For individual control,
• 17.78cm (7") wide LCD display
MIM-N10 supports maximum 16ERVs, for group control,
• Temperature limit setting
it supports a maximum of 16 groups.
• Touch screen
• Zone control
• Child lock setting
• Operation mode lock
• External contact control

• Centralised control + function + schedule


• 17.78cm (7") wide display
• Screen touch control
• Easy zone setting and control
• Multi-language

• Simple schedule setting User Interface


• Maximum of 16 group controls (Maximum of 128 Indoor units) • Easy to check each device status using colour and icon • Easy to execute and stop the schedule
• Unified/Individual indoor unit control (On/Off) • Turning over pages with flicking or simple touch
• Wireless/Wired remote control restriction (No scroll bar)
• Cooling/Heating mode control • Big sized indication for using easily
• Simple operation control interlocking with external
• Indoor unit error display contact (2 Digital input)
• MCM-A202D is compatible with MCM-A202A and MCM-A202B • Provides 3 types of operation pattern
• Temperature setting limitation
• Indoor unit operation on/off status output
(1 Digital output)
• Maximum 12 zone management
• Simply controls zone with one button
• Unique zone description icon makes it easy to recognise
each zone

• Maximum 10 operation schedule settings


• Possible to make various operation schedules
• Weekly, daily, exception day setting

143 144
Simple, convenient operation

Wireless remote controller • Exception date setting

The individual control system has a variety of wired and wireless controllers that enable you to easily control your air • Individual blade control
conditioners. Users can choose the one that best suits their air conditioning environment. This wireless remote controller provides several control (supported to specific indoor unit models)
functions, such as on/off, operation mode, fan speed,
airflow and temperature setting. With a wide display and • MWR-WW00N (for DVM Hydro)
soft touch buttons, users can easily and comfortably
manage system air conditioners with additional control
capabilities such as:

• Free™ mode using AR-EH03I

• Filter replacement alarm reset • It offers simple on/off control and improves system
monitoring with features such as operation and error
• Simple schedule control indication and a filter replacement sign.

• Individual blade control


(supports specific indoor unit models)

• Multi-channel wireless remote control • This simplified wired remote controller provides several
(maximum of four channels) control capabilities, such as on/off, operation mode, fan
speed, airflow, temperature setting and filter
replacement
alarm reset. Users can exercise individual and group
control for a maximum of 16 indoor units. An error
• The wireless remote controller’s jog shuttle and button display
offer a fun way to adjust the airflow. improves issue resolution, while mode selection
protection
MWR-SH10N
• Fast and intuitive navigation guards the settings from tampering.

• Easy use with consistent function array


AR-KH03I
• Improved legibility (150% better than traditional
controller) • The ERV wired remote controller features synchronised
operation with indoor units, enabling individual and
• Dedicated comfort cooling button group control of a maximum of 16 ERVs. Additional
control
functions include on/off control, operation mode
(bypass,
heat exchange), fan speed and simple schedule control.
Plus, an error display improves issue resolution.
• The MWR-WE13N wired, unified controller supports
models • AC, ERV, ERV Plus, AHU and FCU Kit. It features
broad control
MWR-SH00N functions, including on/off operation, mode fan speed,
• This external room sensor can sense the exact user
airflow, temperature setting and Sleep and Silent mode.
environment temperature. It has a wire length of 12 m.
Users can enhance system oversight with features such
as
child lock, automatic stop mode, different permission
levels and wireless remote control restriction. On a
clear,
MWR-WE13N bright LCD-backlit screen, users can also monitor issues
with the error display and apply summer-time
AR-EH03I operation,
supported by a built-in room temperature sensor.
Operators can easily and comfortably manage system
air conditioners with additional control capabilities such
as:

• Individual and group control (maximum to 16 indoor


units)

• Filter replacement alarm reset

• Weekly schedule setting (A/C, CRV, A/C+ERV)

145 146
BACnet gateway

Samsung Building Management System (BMS) provides various control functions for integrated management of varied
BACnet Gateway is an interface for connection to BACnet
system equipment and air conditioners. As a result, BMS facilitates an efficient and economical operating environment.
management system, providing users with a more
convenient way to manage their air conditioning system. It
can control a maximum of 256 indoor units.

Control Monitoring
• On/Off control • Filter alarm reset • On/Off control • Thermo On/Off
• Operation mode • User control restriction • Operation mode • Power distribution
• Temperature setting • Operation mode lock • Set/Room temperature • Operation mode lock
• Fan speed/Direction • Set temperature limit • Fan speed/Direction • Set temperature limit
• ERV operation mode • Emergency stop • ERV operation mode • In/Out contact state
• ERV fan speed • Output contact control • ERV fan speed • Emergency stop
• Filter alarm • Error code
• User control restriction

Connection

LonWorks gateway

BACnet gateway

147 148
LonWorks gateway Mobile solution for System AC

LonWorks gateway is an interface for Lon-Connection to


LonWorks management system, providing users with a
more convenient way to manage their air conditioning
system. It can control a maximum of 128 indoor units.

Control Monitoring

• On/Off control • Filter alarm reset • On/Off control • Thermo On/Off


• Operation mode • User control restriction • Operation mode • Power distribution
• Temperature setting • Operation mode lock • Set/Room temperature • Operation mode lock
• Fan speed/Direction • Set temperature limit • Fan speed/Direction • Set temperature limit
• ERV operation mode • Emergency stop • ERV operation mode • In/Out contact state
• ERV fan speed • Output contact control • ERV fan speed • Emergency stop
• Filter alarm • Error code
• User control restriction

Connection

^Requires a working Wi-Fi connection and compatible mobile handset. Image simulated for representational purposes only.

149 150
An external contact interface module provides direct
indoor unit control via an external contact signal, as
Samsung Guestroom Management System saves users well as window-synchronised indoor unit control. The
the energy and money wasted on cooling an unoccupied emergency control function features simple contact Samsung AHU Kit allows DVM S outdoor units to connect to
room. The air conditioner is activated when the Key-Tag input. Plus the module generates indoor unit operation/ air handling units (AHUs), which results in energy savings
is in place and turns off when the Key-Tag is removed. error state output through relay contacts. and improved performance and efficiency.

Variable capacity

2.5/5/7.5/10 HP Kit

Simple BMS application


MXD-K025AN
0-10 V
MXD-K050AN
Discharge air temperature control
MXD-K075AN
Setting range: Cooling 8º- 18º
Heating: 30º- 43º MXD-K100AN

Even if some of the indoor units are switched off, MTFC


detects it and supplies DC power to the indoor unit.

Also, the indoor unit stays standby mode closing EEV and
blocking control signal until being switched on.

As a result, the other indoor units will be working well.

151 152
Samsung DVM Pro 2.0 is an advanced design automation program that helps
you design your air conditioning system more easily and precisely. You can
simply select the most suitable equipment from the entire range of Samsung
air conditioner products and design the system with its user-friendly interface,
which significantly improves usability. And, it helps to ensure that the system’
design complies with Samsung’s engineering guidelines. The ability to export
reports, pipe and wire diagrams, additional refrigerant values and other
information make Samsung DVM Pro 2.0 a powerful tool for you as an engineer, DVM E-solution is used to perform energy load and
designer or installer. usage simulation based on different equipment
selection and operating conditions, by taking
into consideration the initial and operating costs.
Simulation reports available in various file formats
make supporting technical data easily accessible.

Go to the Samsung DVM Pro website*. Using a temporary password, sign in to Download the DVM Pro 2 installation file,
Simply complete the registration the website. If you want, you can then view the user manuals, and start the
process and a confirmation email with change the password. design of your project.
access details will be sent to you.

All design processes, including product selection, piping wiring and system checks, are
seamlessly integrated to provide a streamlined user experience, so you can respond to client
requests rapidly. And, it includes an intuitive interface and range of convenient features to
simplify and speed –up the whole design process.

Reports
Selection
Simply find and quickly Supports various report The wiring and controls of the A visualized structure,
select any Samsung air formats to suit any of indoor and outdoor units can based on floors and rooms,
conditioners with product your needs. You can also be designed on one screen. lets you intuitively view the
thumbnails and “favorites” selectively print by item, With fewer steps, designs can installation location and Engineers can search products with detailed Designers can find capacity chart instantly
functions. such as a floor or system. be completed quickly. working load. specification at their desktops. at their desktops.

A dedicated CAD program, developed by Samsung, lets you design system without the need Automatic report
for any expensive commercial CAD programs. It is also optimized with specialized features to
design air conditioning systems. A comprehensive
report that includes
specifications, SEER, SCOP
Reports and energy simulation
Let’s you design the system
results can be generated
Refrigerant piping and As well as a basic report,
drainpipes can be drawn it provides integrated in modules, which can be automatically.
It is compatible with
automatically, using the drawing data, including the easily duplicated without commercial CAD programs,
correct material and size equipment, power supply, wasting time and effort on including AutoCAD, for
to suit the installation and communication wiring repetitive tasks. So you can added convenience.
guidelines perfectly. diagrams. quickly complete a whole Exported design and
system. drawing data can be easily
handled and modified
separately.
Engineers can optimise their design to achieve
the best energy efficiency by carrying out energy
simulation of DVM S with annual temperature data.
The DVM S’ SEER / SCOP at various temperatures and
the weight factors can be simulated too.

153 154
Safeguard your air-conditioner from corrosive environment Accessories

Model
Image DVM S, single Application
(New communication protocol)

MDP-E075SEE3D Slim Duct (2.0 ~ 14.0 kW)

MDP-M075SGU1D M.S.P Duct (9.0/11.2 kW)


M.S.P Duct (12.8/14.0 kW)
MDP-M075SGU2D
H.S.P Duct (14.0/16.0 kW)
MDP-M075SGU3v D M.S.P Duct (5.6/7.1 kW)
Drain pump MDP-N047SNC0D O.A.P Duct (14.0 kW)

H.S.P Duct (22.4/28.0 kW)


MDP-N047SNC1D
Fresh Air Intake Duct (22.4/28.0 kW)

MDP-G075SP Duct S (External type)

MDP-G075SQ Duct S (Internal type)

MXD-A38K2A 8~12 HP
PDM kits MXD-A12K2A 14~16 HP
(High elevation kits)
MXD-A58K2A 18~22 HP

MXD-K025AN 7.0 ~ 8.75 kW AHU

MXD-K050AN 14.0 ~ 17.5 kW AHU

MXD-K075AN 21.0 ~ 26.25 kW AHU

AHU kits MXD-K100AN 28.0 ~ 35.0 kW AHU

MXD-A64K100E AHU EEV Kit (10HP)

MCM-D201N Control Kit (PBA, 10HP~40HP)

PC4NUDMAN NASA, Square

PC4NBDMAN NASA, Square - Black

PC4NUNMAN NASA, Circle (Exposed installation)


360 Cassette
AC panel
PC4NBNMAN NASA, Circle (Exposed installation) - Black

PC6EUCMAN (Purification)

PC6EUXMAN (Auto elevation)

PC4SUFMAN 4Way Cassette S - (600x600) - WindFree™

4Way Cassette
PC4NUSKAN
front panel

PC4NBSKAN 4Way Cassette S - Black

PC4NUFMAN 4Way Cassette S - WindFree™

4Way Cassette
PC4SUSMBN 4Way Cassette S (600x600) - Black
(600 x 600) front panel

PC4SUSMFN 4Way Cassette S (600x600) -Classic

PC1NWSMAN/PC1BWSMAN
Slim 1Way Cassette (5.6~7.1kW)
Slim 1Way Cassette (2.2~3.6kW)
PC1NUSMAN/PC1BWSEAN
1Way Cassette (Classic) (5.6~7.1kW)

1Way Cassette front panel PC1NWCMAN (Purification) Small chassis

PC1BWCMAN (Purification) Big chassis

Slim 1Way Cassette Z-Sliding (2.2~3.6kW)


PC1NUPMAN/PC1BWPEAN
Slim 1Way Cassette Z-Sliding (5.6~7.1kW)

155 156
Note
Accessories

Image Model Description Application

2Way Cassette front panel PC2NUSMEN - 2Way Cassette

Motion detect sensor MCR-SMA MCR-SMA 4Way Cassette S (600x600)

MXJ-YA1509N/M 15.0kW and below

MXJ-YA2512N/M Over 15.0 ~ 40.6kW and below

MXJ-YA2812N/M Over 40.6 ~ 46.4 kW and below

Y - Joint MXJ-YA2815N/M Over 46.4 ~ 69.6 kW and below DVM S/DVM S2

MXJ-YA3419N/M Over 69.6 ~ 98.6 kW and below

MXJ-YA4119N/M Over 98.6 ~ 139.2 kW and below

MXJ-YA4422M Over 139.2 kW

MXJ-YA1500M 23.2 kW and below

MXJ-YA2500M Over 23.2 ~ 69.6 kW and below


DVM S HR
for HR module
MXJ-YA3100M Over 69.6 ~ 139.2 kW and below

MXJ-YA3800M Over 139.2 kW

MXJ-TA3819M
Below 48 HP
Outdoor Joint MXJ-TA3419M
DVM S/DVM S2
(Outdoor connection) MXJ-TA4422M
Over 48 HP
MXJ-TA4122M

Outdoor Joint MXJ-TA3100M Below 48 HP


(High pressure gas) DVM S HR
for HR module MXJ-TA3800M Over 48 HP

MXJ-2D2509K 2-indoor unit connection

MXJ-3D2509K 3-indoor unit connection CAC Inverter (4way, 4way 600 x 600)

MXJ-4D2509K 4-indoor unit connection

MXJ-HA3819N Over 69.7 kW

MXJ-HA3115M Below 69.6 kW DVM S/DVM S2

MXJ-HA2512N Below 46.4 kW

Up to 48 units (1 port, 8 units) - Below 16 kW: Port 1EA -


MCU-S6NEK2N
Max capacity: 61.6 KW

Up to 32 units (1 port, 8 units) - Below 16 kW: Port 1EA -


MCU-S4NEK3N
Max capacity: 61.6 KW
MCU kits DVM S HR/DVM S2
Up to 16 units (1 port, 8 units) - Below 16 kW: Port 1EA -
MCU-S2NEK2N
Max capacity: 32 KW

Up to 8 units - Below 16 kW: Port 1EA -


MCU-S1NEK1N
Max capacity: 16 KW

Anti-Corrosion spray MOK-220SA R-Pro

157 158
Note Note

159 160

You might also like