Battery Discharge Test
Site name B R Power Gen Site ID 2 Tested by Mirsarsai
Inspect Date 19-Oct-22 Indoor/Outdoor Indoor Bat. Capacity 100Ah
Start Time 18.00 End Time 18.20
Time Power on Power off 0:30 1:00 1:30 2:00 2:30 3:00 3:30 4:00
Clock Time 20.05 20.10 20.40 21.10 21.20
Current(A) 20.1 22.5 21.00 22.8 21.20
Battery group
52.8 49.8 47.1 46.4 45.8
voltage(V)
Cell 1 13.2 12.0 11.7 11.5 11.4
Cell 2 13.2 11.9 11.8 11.6 11.4
Cell 3 13.2 11.9 11.8 11.6 11.5
Cell 4 13.2 11.9 11.8 11.6 11.4
Cell 5
Cell 6
Cell 7
Cell 8
Remarks
Existing only four batteries