Hamad Hospital Room Conditions Data

This document provides room data and design parameters for Hamad General Hospital. It lists various room types and specifies the internal cooling loads, occupancy rates, fresh air requirements, exhaust air rates, and pressure relationships between rooms. Target summer and winter temperatures are listed for most room types. Internal lighting and miscellaneous loads are specified along with occupancy densities and sensible and latent heat gains per person. Fresh air rates are defined according to ASHRAE standards for many room types.

Uploaded by

John
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
266 views2 pages

Hamad Hospital Room Conditions Data

This document provides room data and design parameters for Hamad General Hospital. It lists various room types and specifies the internal cooling loads, occupancy rates, fresh air requirements, exhaust air rates, and pressure relationships between rooms. Target summer and winter temperatures are listed for most room types. Internal lighting and miscellaneous loads are specified along with occupancy densities and sensible and latent heat gains per person. Fresh air rates are defined according to ASHRAE standards for many room types.

Uploaded by

John
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Hamad General Hospital Room Data Sheet

External Design Condition:

Summer: 46ºC Db / 32ºC Wb Design temperature for fresh air cooling load calculation

50ºC Db / 30ºC Wb Design temperature for heat gains calculation

Winter: 11.2°C Db / 50% RH

Space Temperature Internal Cooling Load Fresh Air Rate Min. Total SA Extract Air
ASHRAE 170 & 62.1 Infiltration Rate ASHRAE 170 & 62.1 100% Recirculation Pressure Relationship
Area Description Internal Occupancy Remarks
Miscellaneous (170 to be superior to (Summer) (170 to be superior exhausted to anywhere within? with Adjacent Areas
Summer Winter Lighting
W/m² 62.1) to 62.1) atmosphere
W/m² People Density (sensible / latent)
BEDROOM (SINGLE / DOUBLE) 22°C 50% RH 22°C 50% RH 8 15 2 PERSONS PER BED 75W / 55W 2 ACH 0.25 ACH 4 ACH YES POSITIVE

CHANGING ROOM (W/O TOILET) 22°C 50% RH 22°C 50% RH 10 5 1 PERSON 75W / 55W 5.1 L/s PER PERSON 0.25 ACH YES BALANCE

CIRCULATION / CORRIDOR 22°C 50% RH 22°C 50% RH 11 - - - - 0.25 ACH 2 ACH YES BALANCE

CLEAN UTILITY 22°C 50% RH 22°C 50% RH 10 - - - - 0.25 ACH 2 ACH YES POSITIVE

DIRTY UTILITY / SOILED LINEN - - 10 - - - - 0.25 ACH 10 ACH NO NEGATIVE

ELECTRICAL ROOM 22°C 50% RH 22°C 50% RH 16 50 - - 0.3 L/s PER m² 0.25 ACH YES BALANCE

EN SUITES 22°C 50% RH 22°C 50% RH 10 - - - - 0.25 ACH 10 ACH NO NEGATIVE

EQUIPMENT / MEDICAL STORES 22°C 50% RH 22°C 50% RH 10 - - - 0.6 L/s PER m² 0.25 ACH 4 ACH YES POSITIVE

GENERAL TOILETS 22°C 50% RH 22°C 50% RH 10 0.25 ACH 10 ACH NO NEGATIVE

HOSTESS PANTRY / KITCHEN 22°C 50% RH 22°C 50% RH 13 120 4 m² / PERSON 75W / 55W 2 ACH 0.25 ACH 10 ACH YES NEGATIVE

0.25 ACH
NEGATIVE / POSITIVE
ISOLATION ROOM (AII / PE) 22°C 50% RH 22°C 50% RH 8 15 1 75W / 55W 2 ACH NEGATIVE 0 12 ACH 12 ACH NO WITH HEPA FILTRATION
(+/- 5 Pa)
ACH POSITIVE

JANITOR ROOM - - 10 - - - - 0.25 ACH 10 ACH NO NEGATIVE

LIFT LOBBY 22°C 50% RH 22°C 50% RH 12 - 3.33 m² / PERSON 75W / 55W 2.7 L/s PER PERSON 0.25 ACH YES BALANCE

LINEN ROOM 22°C 50% RH 22°C 50% RH 10 - - - 2 ACH 0.25 ACH 4 ACH YES POSITIVE

MECHANICAL ROOM 22°C 50% RH 22°C 50% RH 16 50 - - 0.3 L/s PER m² 0.25 ACH YES BALANCE

NURSE STATION 22°C 50% RH 22°C 50% RH 11 15 5 PERSONS 75W / 55W 2 ACH 0.25 ACH 6 ACH YES BALANCE
2.5 L/s PER PERSON
OFFICES 22°C 50% RH 22°C 50% RH 11 15 PER ARCH LAYOUT 0.3 L/s PER m²
0.25 ACH YES BALANCE

PANTRY 22°C 50% RH 22°C 50% RH 13 120 4 m² / PERSON 2 ACH 0.25 ACH 10 ACH NO NEGATIVE

PREPARATION ROOM 22°C 50% RH 22°C 50% RH 8 16 2 PERSONS 75W / 55W 2 ACH 0.25 ACH 6 ACH YES POSITIVE

PROCEDURE ROOM 22°C 50% RH 22°C 50% RH 24 15 3 PERSONS 75W / 55W 2 ACH 0.25 ACH 6 ACH YES BALANCE

RECEPTION 22°C 50% RH 22°C 50% RH 12 15 3.33 m² / PERSON 75W / 55W 5.5 L/s PER PERSON 0.25 ACH YES BALANCE
Based on ICT
SERVER / IT ROOM 22°C 50% RH 22°C 50% RH 16 - - 0.3 L/s PER m² 0.25 ACH YES BALANCE
report
STAFF ROOM / LOCKER ROOM 22°C 50% RH 22°C 50% RH 15 20 4 m² / PERSON 75W / 55W 5.1 L/s PER PERSON 0.25 ACH YES BALANCE

STORE ROOM 22°C 50% RH 22°C 50% RH 10 - - - 0.6 L/s PER m² 0.25 ACH 4 ACH YES POSITIVE

IDF6A = 8.26 kW
TELECOM / IDF ROOM 22°C 50% RH 22°C 50% RH 16 - - 0.3 L/s PER m² 0.25 ACH YES BALANCE
IDF6B = 6.43 kW

TREATMENT ROOM 22°C 50% RH 22°C 50% RH 16 15 2 PERSONS - 2 ACH 0.25 ACH 6 ACH YES BALANCE

WAITING AREA 22°C 50% RH 22°C 50% RH 12 15 3.33 m² / PERSON 75W / 55W 5.5 L/s PER PERSON 0.25 ACH YES BALANCE
L02 TO L05 NEW
ROOMS
22°C, No Humidity 22°C, No Humidity
SURGICAL UNIT 24 15 4 PERSONS 75W / 55W 4 ACH 0.25 ACH 20 ACH YES POSITIVE Ventilation is from ASHRAE 170. Other data are copied from Procedure room (exept nos. occupancy)
Control Control
22°C, No Humidity 22°C, No Humidity
PLASTER ROOM 24 15 3 PERSONS 75W / 55W 2 ACH 0.25 ACH 6 ACH YES BALANCE Same as Procedure room
Control Control
22°C, No Humidity 22°C, No Humidity
TELEVISION ROOM 12 15 3.33 m² / PERSON 75W / 55W 5.5 L/s PER PERSON 0.25 ACH YES BALANCE Same as Waiting Area.
Control Control
22°C, No Humidity 22°C, No Humidity
EEG ROOM 24 15 3 PERSONS 75W / 55W 2 ACH 0.25 ACH 6 ACH YES NEGATIVE Ventilation is from ASHRAE 170 (Laboratory, general). Other data are copied from Procedure room
Control Control
22°C, No Humidity 22°C, No Humidity
EMG ROOM 24 15 3 PERSONS 75W / 55W 2 ACH 0.25 ACH 6 ACH YES NEGATIVE Ventilation is from ASHRAE 170 (Laboratory, general). Other data are copied from Procedure room
Control Control
22°C, No Humidity 22°C, No Humidity
BREAST FEEDING 16 15 2 PERSONS - 2 ACH 0.25 ACH 6 ACH YES BALANCE Same as Treatment Room
Control Control
22°C, No Humidity 22°C, No Humidity
LOUNGE 12 15 3.33 m² / PERSON 75W / 55W 5.5 L/s PER PERSON 0.25 ACH YES BALANCE Same as Reception
Control Control
22°C, No Humidity 22°C, No Humidity
EXAMINATION ROOM 24 15 3 PERSONS 75W / 55W 2 ACH 0.25 ACH 6 ACH YES BALANCE Ventilation is from ASHRAE 170 (Laboratory, general). Other data are copied from Procedure room
Control Control
22°C, No Humidity 22°C, No Humidity
PRAYER ROOM 18 5 0.833 m² / PERSON 75W / 55W 2.8 lps / person 0.25 ACH YES BALANCE ASHRAE 62.1
Control Control
TUB ROOM (we assume this is for giving 22°C, No Humidity 22°C, No Humidity
birth???) Control Control
24 15 3 PERSONS 75W / 55W 4 ACH 0.25 ACH 10 ACH YES POSITIVE Ventilation is from ASHRAE 170 (Delivery Room). Other data are copied from Procedure room

ENDOSCOPY DEPARTMENT

0.6 kW
22°C, No Humidity 22°C, No Humidity (endoscope) + 15 Assumed as Gastrointestinal Endoscopy where biopsy can be done; Using recirculating
G.I. Endoscopy Lab 24 4 PERSONS 75W / 55W 2 ACH - 6 ACH NO BALANCE
Control Control W/sq.m for other units within the room is not recommended.
equipment
Accessories Store - - 10 - - 2 ACH - - 2 ACH NO POSITIVE Using recirculating units within the room is not recommended.
Endoscopy Unit HG-2-0202 (Assumed 22°C, No Humidity 22°C, No Humidity
12 15 3.33 m² / PERSON 75W / 55W 5.5 L/s PER PERSON - NO BALANCE Using recirculating units within the room is not recommended.
as Waiting Room) Control Control
22°C, No Humidity 22°C, No Humidity
Recovery Area
Control Control
9 15 8 PERSONS 75W / 55W 2 ACH - 6 ACH NO BALANCE Using recirculating units within the room is not recommended.

Endoscopy Cleaning Area - - - - - - 2 ACH - 10 ACH YES NO NEGATIVE Using recirculating units within the room is not recommended. Will connect to Central TEF.
0.6 kW
22°C, No Humidity 22°C, No Humidity (endoscope) + 15 Assumed as Gen. Endoscopy where biopsy and minor procedure/surgery can be done.
Procedure Room 24 4 PERSONS 75W / 55W 3 ACH - 15 ACH NO POSITIVE
Control Control W/sq.m for other Using recirculating units within the room is not recommended.
equipment

0.6 kW
22°C, No Humidity 22°C, No Humidity (endoscope) + 15 Assumed as Gen. Endoscopy where biopsy and minor procedure/surgery can be done.
Endoscopy HG-2-0217 24 4 PERSONS 75W / 55W 3 ACH - 15 ACH NO POSITIVE
Control Control W/sq.m for other Using recirculating units within the room is not recommended.
equipment

0.6 kW
Procedure Room with Cystoscopic 22°C, No Humidity 22°C, No Humidity (endoscope) + 15
24 4 PERSONS 75W / 55W 4 ACH - 20 ACH NO POSITIVE Recirculating units within the room is not recommended.
Surgery Control Control W/sq.m for other
equipment

0.6 kW
22°C, No Humidity 22°C, No Humidity (endoscope) + 15 Exhaust will be connected to Negative Isolation room IEF. Using recirculating units within the
Procedure Room with Bronchoscopy 24 3 PERSONS 75W / 55W 2 ACH - 12 ACH YES NO NEGATIVE
Control Control W/sq.m for other room is not recommended.
equipment