Hamad General Hospital Room Data Sheet
External Design Condition:
Summer: 46ºC Db / 32ºC Wb Design temperature for fresh air cooling load calculation
50ºC Db / 30ºC Wb Design temperature for heat gains calculation
Winter: 11.2°C Db / 50% RH
Space Temperature Internal Cooling Load Fresh Air Rate Min. Total SA Extract Air
ASHRAE 170 & 62.1 Infiltration Rate ASHRAE 170 & 62.1 100% Recirculation Pressure Relationship
Area Description Internal Occupancy Remarks
Miscellaneous (170 to be superior to (Summer) (170 to be superior exhausted to anywhere within? with Adjacent Areas
Summer Winter Lighting
W/m² 62.1) to 62.1) atmosphere
W/m² People Density (sensible / latent)
BEDROOM (SINGLE / DOUBLE) 22°C 50% RH 22°C 50% RH 8 15 2 PERSONS PER BED 75W / 55W 2 ACH 0.25 ACH 4 ACH YES POSITIVE
CHANGING ROOM (W/O TOILET) 22°C 50% RH 22°C 50% RH 10 5 1 PERSON 75W / 55W 5.1 L/s PER PERSON 0.25 ACH YES BALANCE
CIRCULATION / CORRIDOR 22°C 50% RH 22°C 50% RH 11 - - - - 0.25 ACH 2 ACH YES BALANCE
CLEAN UTILITY 22°C 50% RH 22°C 50% RH 10 - - - - 0.25 ACH 2 ACH YES POSITIVE
DIRTY UTILITY / SOILED LINEN - - 10 - - - - 0.25 ACH 10 ACH NO NEGATIVE
ELECTRICAL ROOM 22°C 50% RH 22°C 50% RH 16 50 - - 0.3 L/s PER m² 0.25 ACH YES BALANCE
EN SUITES 22°C 50% RH 22°C 50% RH 10 - - - - 0.25 ACH 10 ACH NO NEGATIVE
EQUIPMENT / MEDICAL STORES 22°C 50% RH 22°C 50% RH 10 - - - 0.6 L/s PER m² 0.25 ACH 4 ACH YES POSITIVE
GENERAL TOILETS 22°C 50% RH 22°C 50% RH 10 0.25 ACH 10 ACH NO NEGATIVE
HOSTESS PANTRY / KITCHEN 22°C 50% RH 22°C 50% RH 13 120 4 m² / PERSON 75W / 55W 2 ACH 0.25 ACH 10 ACH YES NEGATIVE
0.25 ACH
NEGATIVE / POSITIVE
ISOLATION ROOM (AII / PE) 22°C 50% RH 22°C 50% RH 8 15 1 75W / 55W 2 ACH NEGATIVE 0 12 ACH 12 ACH NO WITH HEPA FILTRATION
(+/- 5 Pa)
ACH POSITIVE
JANITOR ROOM - - 10 - - - - 0.25 ACH 10 ACH NO NEGATIVE
LIFT LOBBY 22°C 50% RH 22°C 50% RH 12 - 3.33 m² / PERSON 75W / 55W 2.7 L/s PER PERSON 0.25 ACH YES BALANCE
LINEN ROOM 22°C 50% RH 22°C 50% RH 10 - - - 2 ACH 0.25 ACH 4 ACH YES POSITIVE
MECHANICAL ROOM 22°C 50% RH 22°C 50% RH 16 50 - - 0.3 L/s PER m² 0.25 ACH YES BALANCE
NURSE STATION 22°C 50% RH 22°C 50% RH 11 15 5 PERSONS 75W / 55W 2 ACH 0.25 ACH 6 ACH YES BALANCE
2.5 L/s PER PERSON
OFFICES 22°C 50% RH 22°C 50% RH 11 15 PER ARCH LAYOUT 0.3 L/s PER m²
0.25 ACH YES BALANCE
PANTRY 22°C 50% RH 22°C 50% RH 13 120 4 m² / PERSON 2 ACH 0.25 ACH 10 ACH NO NEGATIVE
PREPARATION ROOM 22°C 50% RH 22°C 50% RH 8 16 2 PERSONS 75W / 55W 2 ACH 0.25 ACH 6 ACH YES POSITIVE
PROCEDURE ROOM 22°C 50% RH 22°C 50% RH 24 15 3 PERSONS 75W / 55W 2 ACH 0.25 ACH 6 ACH YES BALANCE
RECEPTION 22°C 50% RH 22°C 50% RH 12 15 3.33 m² / PERSON 75W / 55W 5.5 L/s PER PERSON 0.25 ACH YES BALANCE
Based on ICT
SERVER / IT ROOM 22°C 50% RH 22°C 50% RH 16 - - 0.3 L/s PER m² 0.25 ACH YES BALANCE
report
STAFF ROOM / LOCKER ROOM 22°C 50% RH 22°C 50% RH 15 20 4 m² / PERSON 75W / 55W 5.1 L/s PER PERSON 0.25 ACH YES BALANCE
STORE ROOM 22°C 50% RH 22°C 50% RH 10 - - - 0.6 L/s PER m² 0.25 ACH 4 ACH YES POSITIVE
IDF6A = 8.26 kW
TELECOM / IDF ROOM 22°C 50% RH 22°C 50% RH 16 - - 0.3 L/s PER m² 0.25 ACH YES BALANCE
IDF6B = 6.43 kW
TREATMENT ROOM 22°C 50% RH 22°C 50% RH 16 15 2 PERSONS - 2 ACH 0.25 ACH 6 ACH YES BALANCE
WAITING AREA 22°C 50% RH 22°C 50% RH 12 15 3.33 m² / PERSON 75W / 55W 5.5 L/s PER PERSON 0.25 ACH YES BALANCE
L02 TO L05 NEW
ROOMS
22°C, No Humidity 22°C, No Humidity
SURGICAL UNIT 24 15 4 PERSONS 75W / 55W 4 ACH 0.25 ACH 20 ACH YES POSITIVE Ventilation is from ASHRAE 170. Other data are copied from Procedure room (exept nos. occupancy)
Control Control
22°C, No Humidity 22°C, No Humidity
PLASTER ROOM 24 15 3 PERSONS 75W / 55W 2 ACH 0.25 ACH 6 ACH YES BALANCE Same as Procedure room
Control Control
22°C, No Humidity 22°C, No Humidity
TELEVISION ROOM 12 15 3.33 m² / PERSON 75W / 55W 5.5 L/s PER PERSON 0.25 ACH YES BALANCE Same as Waiting Area.
Control Control
22°C, No Humidity 22°C, No Humidity
EEG ROOM 24 15 3 PERSONS 75W / 55W 2 ACH 0.25 ACH 6 ACH YES NEGATIVE Ventilation is from ASHRAE 170 (Laboratory, general). Other data are copied from Procedure room
Control Control
22°C, No Humidity 22°C, No Humidity
EMG ROOM 24 15 3 PERSONS 75W / 55W 2 ACH 0.25 ACH 6 ACH YES NEGATIVE Ventilation is from ASHRAE 170 (Laboratory, general). Other data are copied from Procedure room
Control Control
22°C, No Humidity 22°C, No Humidity
BREAST FEEDING 16 15 2 PERSONS - 2 ACH 0.25 ACH 6 ACH YES BALANCE Same as Treatment Room
Control Control
22°C, No Humidity 22°C, No Humidity
LOUNGE 12 15 3.33 m² / PERSON 75W / 55W 5.5 L/s PER PERSON 0.25 ACH YES BALANCE Same as Reception
Control Control
22°C, No Humidity 22°C, No Humidity
EXAMINATION ROOM 24 15 3 PERSONS 75W / 55W 2 ACH 0.25 ACH 6 ACH YES BALANCE Ventilation is from ASHRAE 170 (Laboratory, general). Other data are copied from Procedure room
Control Control
22°C, No Humidity 22°C, No Humidity
PRAYER ROOM 18 5 0.833 m² / PERSON 75W / 55W 2.8 lps / person 0.25 ACH YES BALANCE ASHRAE 62.1
Control Control
TUB ROOM (we assume this is for giving 22°C, No Humidity 22°C, No Humidity
birth???) Control Control
24 15 3 PERSONS 75W / 55W 4 ACH 0.25 ACH 10 ACH YES POSITIVE Ventilation is from ASHRAE 170 (Delivery Room). Other data are copied from Procedure room
ENDOSCOPY DEPARTMENT
0.6 kW
22°C, No Humidity 22°C, No Humidity (endoscope) + 15 Assumed as Gastrointestinal Endoscopy where biopsy can be done; Using recirculating
G.I. Endoscopy Lab 24 4 PERSONS 75W / 55W 2 ACH - 6 ACH NO BALANCE
Control Control W/sq.m for other units within the room is not recommended.
equipment
Accessories Store - - 10 - - 2 ACH - - 2 ACH NO POSITIVE Using recirculating units within the room is not recommended.
Endoscopy Unit HG-2-0202 (Assumed 22°C, No Humidity 22°C, No Humidity
12 15 3.33 m² / PERSON 75W / 55W 5.5 L/s PER PERSON - NO BALANCE Using recirculating units within the room is not recommended.
as Waiting Room) Control Control
22°C, No Humidity 22°C, No Humidity
Recovery Area
Control Control
9 15 8 PERSONS 75W / 55W 2 ACH - 6 ACH NO BALANCE Using recirculating units within the room is not recommended.
Endoscopy Cleaning Area - - - - - - 2 ACH - 10 ACH YES NO NEGATIVE Using recirculating units within the room is not recommended. Will connect to Central TEF.
0.6 kW
22°C, No Humidity 22°C, No Humidity (endoscope) + 15 Assumed as Gen. Endoscopy where biopsy and minor procedure/surgery can be done.
Procedure Room 24 4 PERSONS 75W / 55W 3 ACH - 15 ACH NO POSITIVE
Control Control W/sq.m for other Using recirculating units within the room is not recommended.
equipment
0.6 kW
22°C, No Humidity 22°C, No Humidity (endoscope) + 15 Assumed as Gen. Endoscopy where biopsy and minor procedure/surgery can be done.
Endoscopy HG-2-0217 24 4 PERSONS 75W / 55W 3 ACH - 15 ACH NO POSITIVE
Control Control W/sq.m for other Using recirculating units within the room is not recommended.
equipment
0.6 kW
Procedure Room with Cystoscopic 22°C, No Humidity 22°C, No Humidity (endoscope) + 15
24 4 PERSONS 75W / 55W 4 ACH - 20 ACH NO POSITIVE Recirculating units within the room is not recommended.
Surgery Control Control W/sq.m for other
equipment
0.6 kW
22°C, No Humidity 22°C, No Humidity (endoscope) + 15 Exhaust will be connected to Negative Isolation room IEF. Using recirculating units within the
Procedure Room with Bronchoscopy 24 3 PERSONS 75W / 55W 2 ACH - 12 ACH YES NO NEGATIVE
Control Control W/sq.m for other room is not recommended.
equipment