Se TRANE
Installation, Operation, and Maintenance
Series R® Air-Cooled
Helical Rotary Liquid Chillers
Mode = RTAC
AASAFETY WARNING
‘Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of
heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training.
Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury.
When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are
attached to the equipment.
August 2021 RTAC-SVX01R-EN TRANES}$ TRANE™
Introduction
Read this manual thoroughly before operating orservicing
this unit,
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as
required. Your personal safety and the proper operation of
‘this machine depend upon the strict observance of these
precautions.
The three types of advisories are defined as follows:
PENINTS cae pazonaty hazrcous
situation which, i not avoided, could
result in death o serious injury
rn Indicates a potentially hazardous
NUE situation which, if not avoided, could
fesult in minor of moderate injury. It
could also be used to alert against
unsafe practices.
PLS indicates. situationthat could resultin
equipment or property-damage only
Important Environmental Concerns
Scientific research has shown that certain man-made
chemicals can affect the earth's naturally occurring
stratospheric ozone layer when released to the
atmosphere. In particular, several of the identified
chemicals that may affect the ozone layer are refrigerants
that contain Chlorine, Fluorine and Carbon (CFCs) and
‘those containing Hydrogen, Chlorine, Fluorine and
Carbon (HCFCs). Not all refrigerants containing these
compounds have the same potential impact to the
environment, Trane advocates the responsible handling of
all refrigerants-including industry replacements for CFCs
and HCFCs such as saturated or unsaturated HFCs and
HCFCs.
Important Responsible Refrigerant
Practices
‘Trane believes that responsible refrigerant practices are
important to the environment, our customers, and the air
conditioning industry. All technicians who handle
refrigerants must be certified according to local rules. For
the USA, the Federal Clean Air Act (Section 608) sets forth
the requirements for handling, reclaiming, recovering and
recycling of certain refrigerants and the equipment that is.
Used in these service procedures. In addition, some states
for municipalities may have additional requirements that
must also be adhered to for responsible management of
refrigerants. Know the applicable laws and follow them.
©2021 Trane
Proper Field Wi
Required!
Failure to follow code could resu
injury. All field wiring MUST be performed by quali
personnel. Improperly installed and grounded field
‘wiring poses FIRE and ELECTROCUTION hazards. To
4vold these hazards, you MUST follow requirements for
and grounding as described in
NEC and your ocal/state/national electrical codes,
ing and Grounding
Personal Protective Equipment (PPE)
Required!
Failure to wear proper PPE for the job being undertal
‘could result in death or serious injury. Technicians, in
order to protect themselves from potential electrical,
mechanical, and chemical hazards, MUST fallow
precautions in this manual and on the tags, stickers,
and labels, as well as the instructions below:
+ Before installing/servicing this unit, technicians
MUST put on all PPE required for the work being
undertaken (Examples; cut resistant gloves/sl
uty! gloves, safety glasses, hard hat/bump cap,
protection, electrical PPE and are flash clothing).
ALWAYS refer to appropriate Safety Data Sheets
{SDS) and OSHA guidelines for proper PPE.
+ When working with or around hazardous chemicals,
ALWAYS refertothe appropriate SDS and OSHA/GHS
{Global Harmonized System of Classification and.
Labeling of Chemicals) guidelines for information on
allowable personal exposure levels, proper
respiratory protection and handling instructions.
+ Ifthore isa risk of energized electrical contact, arc, or
flash, technicians MUST put on all PPE in accordance
with OSHA, NFPA 70E, or other country-specific
requirements for arc flash protection, PRIOR to
servicing the unit. NEVER PERFORM ANY
‘SWITCHING, DISCONNECTING, OR VOLTAGE
TESTING WITHOUT PROPER ELECTRICAL PPE AND
ARC FLASH CLOTHING, ENSURE ELECTRICAL
(METERS AND EQUIPMENT ARE PROPERLY RATED
FOR INTENDED VOLTAGE.
RTAC-SVXOIR-ENFollow EHS Policies!
Failure to follow instructions below could result in
death of serious injury.
‘+ All Trane personne! must follow the company’s
Environmental, Health and Safety (EHS) policies
when performing work such as hot work, electrical,
fall protection, lockout/tagout, refrigerant handling,
etc. Where local regulations are more stringent than,
these policies, those regulations supersede these
policies.
‘+ Non-Trane personnel should always follow local
regulations.
Refrigerant under High Pressure!
Failure to follow instructions below could result in an
‘explosion which could result In death or serious injury
‘or equipment damage.
System contains refrigerant under high pressure.
Recover refrigerant to relieve pressure before opening
the system. See unit nameplate for refrigerant type. Do
not use non-approved refrigerants, refrigerant
Substitutes, or refrigerant additives.
Factory Warranty Information
Compliance with the following is required to preserve the
factory warranty:
All Unit Installations
Startup MUST be performed by Trane, or an authorized
agent of Trane, to VALIDATE this WARRANTY. Contractor
‘must provide a two-week startup notification to Trane (or
fan agent of Trane specifically authorized to perform
startup).
Copyright
This document and the information in itare the property of
Trane, and may not be used or reproduced in whole or in
part without written permission. Trane reserves the right
to revise this publication at any time, and to make changes
to its content without obligation to notify any person of
such revision or change.
Trademarks
All trademarks referenced in this document are the
trademarks of their respective owners.
RTAC-SVXOTR-EN
Introduction
Factory Training
Factory training is available through Trane University™ to
help you learn more aboutthe operation and maintenance
of your equipment. To learn about available training
opportunities contact Trane University™
Online: www-trane.comitraneuniversity
Phone: 855-803-3563
Email: traneuniversity@trane.com
Revision History
+ Minor error corrections.
+ Minor edits to document.Table of Contents
Model Number Description 6 Evaporator Water Piping . see AB
Outdoor Unit Nameplate 6 Entering Chilled Water Piping 46
Compressor Nameplate 6 Leaving Chilled Water Piping «2... ..48
Unit Model Number .........s.eeesere 7 Evaporator Drain 46
Compressor Model Number 8 Evaporator Flow Switch coe 86
Compressor Serial Number 8 Water Pressure Gauges .. coe 50
General Data 9 Water Pressure Relief Valves 50
Unit Description : 9 Freeze Avoidance ........ 151
Accessory/Option Information 9 Low Evaporator Refrigerant Cutout, Give!
Isolator Shipping Location 9 Recommendations ....... vn 82
Pre-installation 20 Procedure 2
Unit inspection .... 20 Specials 82
Inspection Checklist 20 pstallation Mechanical sa
Storage 20 System Configuration and interconnecting
Installation Responsibilities 20 Refrigerant Piping ....... ve 5
General 20 Line Sizing 58
Dimensions and Weights ......2.2.20200. 21 Liquid Line Sizing Steps 58
Dimensions 21 Suction Line Sizing Steps cee 58
Clearances 2 Suction Accurnulator Sizing 59
Weights .. : : 24 Piping Installation Procedures 60
Non-Seismically Rated Units .......... 24 Refrigerant Sensors ...... eee 80
Seismically Rated Unit Weights... 26 Refrigerant Pressure Relief Valve Venting .60
Remote Evaporator Unit Weights 27 Leak Test and Evacuation . ve 81
Installation - Mechanical ..........06+... 28 Refrigerant and Additional Oil Charge 62
Location Requirements ........20.0.0.+ 28 Refrigerant Charge Determination .... ..62
Noise Considerations 28 Oil Charge Determination 62
Foundation 28 Installation - Electrical ...... ee)
Clearances 28 General Recommendations vee 83
Rigging . 28 Installer-Supplied Components 63
Lifting Procedure . : 28 Power Supply Wiring 63
Isolation and Sound Emission .......... 31 Control Power Supply 6s
Mounting and Leveling an Heater Power Supply and Convenience
Unit Isolation 3 Outlet (Packaged Units Only)... ...+ 68
Elastomerie leoletore Interconneeting Wiring ... foe 65
(Optional for units without seismic rating) 31 Chilled Water Pump Control «65
Unit Isolation for Seismically Rated Units 32 Alarm and Status Relay Outputs
Isolator Selection and Mounting Locations: (Programmable Relays) 66
34 Relay Assignments Using TechView .....67
Drainage . 45 Low Voltage Wiring ...... sees 87
4 RTAC-SVXOIR-ENTable of Contents
Emergency Stop 87 Compressor Service View 83
External Auto/Stop « see Status View . eee 83
External Circuit Lockout - Circuit #1 and #2 Setpoint View 83
68 Diagnostics View ..... ee BA
Ice Building Option 68 Configuration View 84
External Chilled Water Setpoint oe Software View ....... cee 87
External Current Limit Setpoint Binding View a7
{ECLS) Option ..... coves 68 Replacing or Adding Devices ..........87
Chilled Water Reset (CWR) 69 Integrated Rapid Restart 89
Communications Interface Options 70 Pre-Start Checkout 90
Tracer’® Communications Interface Start-Up and Shutdown ..... cect
Option serene 70 Unit Start-Up +91
LonTalk® Interface Ler ¢) 70 ‘Temporary Shutdown and Restart 92
BACnet® Interface (BCI-C) ............ 70 Extended Shutdown Procedure .........92
Operating Principles nm Seasonal Unit Start-Up Procedure 93
Refrigeration Cycle n System Restart After Extended Shutdown 93
Refrigerant R-134a a Sequence of Operation ... wee 94
Compressor 71 Maintenance .. cee coe 98
Condenser and Subcooler weceeeee 72 Weekly ..... coe veces 88
Expansion Valve 72 Monthly 98
Evaporator R Annual ..... vee 98
Oil System 72 Refrigerant and Oil Charge Management .98
Controls Interface 73 Lubrication System ...... eee 9D
Overview . : 8 il Sump Level Check 99
Controls Interface 73 Condenser Maintenance . . wee OD
DynaView™ Display 73 Condenser Coil Cleaning 99
Key Functions 3B Travel Restraint 100
Display Screens . 74 Diagnostics 101
Modes Screen 7 Legend to Diagnostics Table 101
Chiller Sereen 73 Starter Diagnostics ...... wee 101
Compressor Screen 79 Main Processor Diagnostics eee 106
Refrigerant Screen . 73 Communication Diagnostics eee 114
Setpoint Sereen 50 Main Processor Boot Messages
Diagnostic Seren a1 and Diagnostics ......... ceeeeM19
Power-Up 81 Unit Wiring 120
Display Formats 81 Log and Check Sheet ...... vee 122
Units. 81
Languages a1
TechView . . eee 81
Unit View a3
RTAC-SVXOTR-EN 5S}$ TRANE™
Model Number Description
Nameplates
‘The RTAC outdoor unit nameplates are applied to the
exterior of the Control Panel. A compressor nameplate is
located on each compressor. When the unit arrives, if unit
is notcovered with atarp, compare all nameplate data with
ordering, submittal, and shipping information.
Outdoor Unit Nameplate
See igure 1,p. 6foratypicalunit nameplate. The outdoor
Unit nameplate provides the following information:
+ Unit model and size description
Unit serial number.
‘+ Identifies unit electrical requirements.
+ Lists correct operating charges of R-134a and
refrigerant oil (Trane 0100048}
Lists unit test pressures.
‘+ Identifies installation, operation and maintenance and
service data literature (Pueblo).
‘+ Lists drawing numbers for unit wiring diagrams
(Puebto.
Model Number Coding System
‘The model numbors for the unit and the compressor are
composed of numbers and letters that represent features
of the equipment. Shown in the following tables asample
of typical unit model number and the coding system for
each.
Each position, or group of positions, in the model number
is used to represent a feature. For example, in the first
table, position 08 of the unit model number, Unit Voltage,
contains thenumber “4”-A4inthis position meansthatthe
unit voltage is 460/60/3.
Unit Model Number. An example of a typical unit
model number (MIN) is:
RTAC 350A UAON NAFN NINX 1TEN NNON NO1N,
Model number digits are selected and assigned in
accordance with the definitions as listed in “Unit Model
Number,” p. 7
Compressor Nameplate
The compressor nameplate provides following
information:
+ Compressor model number, See “Compressor Model
Number,” p. &
+ Compressor serial number. See"Compressor Serial
Number,” p. 8
+ Compressor slectrical characteristics.
+ Utilization range.
‘+ Recommended refrigerant.
Om —
|
mas Ee ace fen
SS pro sees
| b= eC IL IL Oe LIL OL)
exe EE) @ ae)
a
a =
SC see Ce tc. es.
suger oe eee
ee ee
SSE SSSR EEE SES
RTAC-SVXOIR-ENModel Number Descriptions
Unit Model Number
Digits 1, 2 - Unit Model
RT = Rotary chiller
Digit 3 - Unit Type
A = Aircooled
Digit 4- Development Sequence
© = Development sequence
Digits 5, 6 and 7 - Nominal
Capacity
120 = 120 Nominal tons
130 Nominal tons
140 Nominal tons
155 Nominal tons
170 Nominal tons
185 Nominal tons
200 Nominal tone
225 Nominal tone
250 Nominal tone
275 Nominal tone
4300 Nominal tone
350 Nominal tone
4375 Nominal ton
400 Nominal tone
{450 Nominal tons
500 Nominal tons
8 - Unit Voltage (Volts/Hz/
)
2o0V60'3
230/603
‘e0/60/3
‘ao0/s0r3
‘aso/e0r2
575/603
it 9 - Manufactun
Location
U_ = Water chiller Business Unit,
Pueblo, COUSA,
10, 11 - Design Sequence
sm Factory Input
12- Unit Basie
Configuration
N= Standard effciency/performance
H = High eficiencyiperformance
A = Extra eficienyiperformance
Digit 13 - Agency Listing
No agency listing
ULtisting
Seismic rated - IBC and OSHPD
CCIUL listed and seiemic rated
14 - Pressure Vessel Code
A = ASME pressure vessel code
C= Canadian code
>
L
Australian code
Chinese code
RTAC-SVXOTR-EN
Digit 15 - Evaporator
Application
F = Standard (40-60°F} leaving temp
G = LowiLess than 49°F leaving
temp
R= Remote (40.60°F} leaving tomp
2 pass, 0.754. insulation
3 pass, 0.754. insulation
2pass, 125-in insulation
3 pass, 1254 insulation
it 17 - Con
pplication
Standard ambiant(25-115"F)
= High ambient (25-125°F)
Low ambient (0-115°F)
Wide ambient (0-125°F)
it 18 Condenser
Standard sluminum slit fing
Copper fins
CompleteCoat™ epoxy coated
fins
Digit 19 - Condenser Fan/Motor
Configuration
STD fans with TEAO motors
Low noize fans
it 20 - Compressor Motor
Starter Type
Acrosethesine
Wye-delta closed transition
it 21 - Incoming Power Line
Connection
‘Single point pawer connection
Dual peint power connection
D = Non-fused disconnect switchi
© = Circuit breakers}
Digit 23 - Unit Operator
Interface
D = DynaView operator interface
Digit 24 - Remote Operator
Interface
N= No remote interface
© = Tracer Comm 3 interface
3 = BACnet™ interface
LonTalk® compatible (Lcl-c)
interface
Digit 25 - Control Input
Accessories/Options
N= Noremote inputs
R © Ext evaporator leaving water
setpoint
Ext current limit setpoint
Ext leaving water and current
limit setpoint
it 26 - Control Output
\eeessoriesiOptions
No output ontions
Alarm relay outputs
lee making VO
= Alarm relay outputs and ice
making WO.
27 - Electrical Protection
ptions
‘No shor circuit rating
Default short circu rating
High amp short circuit rating
28 - Flow Switch
Factory installed flow switch
Factory installed flow switch,
onawvater fluids
29 - Control Panel
No convenience outlet
= 188 115V convenience outlet
(soz)
30 - Service Valves
"No suction service valves
With suction service valves
31 - Compressor Sound
Attenuation Option
0 = Nocompressor sound
= Factory installed compressor
sound attenuation
32 - Appearance Options
No appearance options
Architectural lwvered panels,
© = Halflouvers
Digit 33 - Installation
Accossories
N= Nojnstallation accessories
F = Flange kit for water connections
R= Neoprene in shear unit isolators
6
E
Neoprene isolators and flange kt
= Seismic elastomer solation
pads
= Seismic spring isolators
Digit 34 - Factory Testing
Options
0 = Standard functional test
© = Witness performance test
with report
Es Performance test with reportModel Number Descriptions
35 - Control, Label and
Literature
© = Spanish
E = English
F = Frenen
Digit 36 - Special Order
X = Standard unit configuration
F = Ship totinal fisher
= Unithas special order festure
Digit 37 - Safety Devices
N= Standard
Compressor Model
Number
Digits 1-3 — Compressor Family
CHH= Positive displacement,
refrigerant, helical rotary,
hermetic compressor
Digit 4— Compressor Type
P= GP
T = Gp2e
w= GP2s
Digit 5 - Economizer Port Detail
No Economizer Port \zera}
Economizer port = 65*,Vi=35
Economizer port = 140", Vi= 3.57
it 6 — Frame Size
K Frame
UFrame
Ma Frame
Nerame
it 7 — Compressor Capacity
GP2 Smaller capacity (minor)
GP? Larger capacity (major
GP2+ Smaller capacity (minor)
P24 Largor capacity (major)
P25 Smaller capacity
= GP25 Larger eapacty
igit & - Motor Veltag
200-60-3,
230-603
30-603,
575-603
400:50-3 (NB only)
'460-60-3 (NS only)
220503
Special voltage
400/460-50180-3 used for
duane zoo> g scaensg zEerng me
380-50-3,
Digit 9 - Internal Reliet
K = 450psid
Digits 10, 11 - Design Sequence
tt = Factory assigned
it 12 - Capacity Limit
Standard Capacity
Digits 13 to 15 - Motor kW
Rating
ose= K SoH
oes KI got
ost = Kz 50H
K2 sole
Ui sone
Li 60H
L2 50H:
Leone
MVM SoH
MMe Bons
Maza Son
Ma/Ma Gots
INUNGINS SoH
INUNGINS oH
N2INAING SoHE
N2INaING Gob
Compressor Serial
Number
5 1,2- Year
Last two digits of veer of
manufacture
Digits 3, 4- Week
WW= Week of build, from 00 to 52
Digit 5 - Day
Monday
Tuesday
= Wednesday
Thureday
Friday
ssturday
Sunday
s 6, 8 - Coded Time Stamp
Used to ensure uniqueness of
serial number
9 Assembly Line
Varies with facility
10 - Build Loca
Monterrey
w
g Vouaune
4
>org
RTAC-SVXOIR-EN}$ TRANE™
General Data
Unit Desct
n Informa’
Accessory/Opt n
‘The 140-500ton ModelRTACunits are helical-rotarytype, Check al the accessories and loose parts which are
air-cooled liquid chillers designed for installation shipped with the unit against the shipping list. Included i
outdoors. The compressor circuits are completely ‘these items will be water vessel drain plugs, rigging and
assembled, hermetic packages that are factory-piped, electrical diagrams, and service literature, which are
wired, leak-tested, dehydrated, and tested for proper placed inside the control panel andior starter panel for
control operation before shipment. shipment.
Chilled water inlet and outlet openings are covered for ippi
shipment. Each compressor has a separate compressor |solator Shipping Loe:
motor starter. The RTAC series features Trane’s exclusive If optional neoprene isolators (model number digit 33) are
Adaptive Control ™ logic, which monitors the control ordered with unit, they are shipped mounted on the unit.
variables that govern the operation of the chiller unit. See Figure 3 and Figur
Adaptive Control logie ean adjust capacity variables to
avel chiller shutdown when necessary, and Keep Figure 3 solator shipping locations,
producing chilled water. The units feature two 140 to 250 ton units
independent refrigerant circuits. Compressor unloaders
are solenoid actuated and oil pressure operated. Each
refrigerant circuit is provided with fier, sight glass,
slectronic expansion valve, and charging valves. The
shell-and-tube type evaporator is manufactured in
accordance with ASME standards or other international
codes. Each evaporator is fully insulated and is equipped
‘with water drain and vent connections, Packaged units
have heat tape protection to - 20°F (-28.9°C) as standard.
‘As an option, a convenience outlet can be supplied.
Note: Packaged units are factory charged with refrigerant
and oil
Figure 2. Typical RTAC packaged unit and components
[Neoprene lslator Shipping Location
Figure 4. Isolator shipping locations,
275 to 500 ton units
Neoprene lsolator Shipping Location
RTAC-SVXOTR-EN 8General Data
Table 1. 60 Hz standard efficiency — LP
Size 140455 170 185 200 225 250 275 300350 ~~400~—~450~—~500
Compressor serew
qanty # 2 2 2 2 2 2 2 3 3 3 4 @ 4
Nemepeore om) gS S8 ‘ts! You too ta “00 ‘San ‘S00 toowsee_soo-acenao-220
Evaporator Focded
Water storage (gal) 29 2932-22358 28 swt
2 pass arangement
Minton) (gpm) 195 195 204 204 219 19 239267312230 aR
Moxtlow(s) (gpm) 715 735 748 740 909 802 803 9791148 2544896582
Waterconnection (WS) 4 4 6 6 6 6 6 8 8 8 f8 @ 8
3 pass arangement
MMinflow(a) (Gem) 330 120 3268 136 146 146 M6178 oats aks
Max wa) (gpm) 477 47 499 499 S36 S36 S36 6837626098802
Waterconnedton (W?S-n) 35 35 4 4 4 4 4 6 6 6 8 8 8
Condenser Fin and ube
ayo # 94 4 4 4 4 4 4 8 8 8 8 8 28
coitnatn (ny SE MMRY HBRY 2EGY 23By 2527 2521807 ar6yrop aszyx08 216/216 252/216 252/252
Golthelgnt (ny 42424222 awk waka aw
(me) 1067 1067 1067 1067 1067 1067 1067 1067 106710671087 10671067
fom 4 3 3 3 3 3 8 8 3 3 3 3
Fins per foot (fof) 192 192192 192 192 192 192 192 192__—t92_——t92_—t92 192
Fan ‘rect crve propeller
Quantity # 4/8 5/4 5/5 6/5 ME 7187/7 t/a. san saa
Diameter (in) 30.0 30.0 30.0 30.0 30.0 30.0 300 30.0 300 30.0 30.0 30.0 300
[flow perfan (cfm) 9625 9394 9209 9209 9209 9210 9210 9209 9209 920892099102
Powerlmotor (ho) 15 15 25 18 15 15 15 415 15 45 25 15 18
Fan speed (rpm) 1240 1140 1140 1140 1140 1280 1240 1140 116011401140 11408140
Tio speed (Fu/min) 9954 9954 6954 6954 9954 9954 A956 9954 8954 8954 8954 9548854
General Unit HEC I34e
FRhigcts # 2 2 2 2 2 2 2 2 2 2 2 2 2
Seminlosd % 35 15 15 15 35 a5 45 15 18 15 1s 15 5
Refrigerant 365) 175/175) 225/ 215/ 2257 225/365 gasya0q 460/200 15/415 460/a1s 460/460
) 365 ies 175 210 218 15 225 200,
13) 13 LaF LOY 4.9/1.9) 1.9)
vag ¥3 UF Ys is Ys
oll erarse (oat) 4219 46/19 4619 46/08 46/86 46/88
Minamoient-std (F) 25 25-25-25 SBS BSH
Minambientow (F) 0 0 0 0 0 09 0 0 oO ° ° ° o
Notes
1 Bata containing information on two circus is shown 9s follows: ck 1 kt 2
2 Minimum stanuproperaing ambien bases on a5 mph wind seross te condenser
(2) Mum ane maxim flo ates py constant. water system runing at AAR condone wot rere Nr ade to the war
10 RTAC-SVXOIR-ENGeneral Data
Table2.
‘Size 40455 ~+4470~«4e5 ~—~200”~«225~—«250~—=275~~—~«300~=«SSO 400
‘Compressor Screw
Quantty 6 2 2 2 2 2 2 2 3 a 4 4
Nomieseore (tons) 70/70 85/70 85/85 100/85 100/100 120/100 20/120 “SO ak, Sea Oo od,
Evaporator Fooded
Waterstorage (a) 333338
2 pass arrangement
Min flow®) (gpm) 2082042829 a2 aaa
Moxftow(a) (gpm) 748—-748-—=«8O3_—=«8OH_—«S« OS 8S HOS. «12541254 tao S62
Woter connection (NPS-in) 6 6 6 6 6 6 6 8 8 8 8
3 pass arrangement
Minflow(a) (opm) 136138146 246512528
Maxflow(a) (opm) 499 499« 536536. 835.5556 836358390
Water connection (NPS-in) #8 4 4 4 6 6 8 8
‘Condenser Fin and tbe
Qyotcols #4 os 4 4 4 8 ® 8 8 e 8
Colttength (in) 186/280 246/180 216/216 252/216 252/252 144/144 I4s/i44 DIE/I44 252/244 216/216 252/252
Coitheiaht in) 42a www
Number ofrows #2 3 3 3 a 3 a 3 a 3 3
Fins perfoct (ff) 1929292 tz 202 gest
Fan Direc dive propeller
Quantty #55 SSG? tanng
Diameter (im) «30,303 BOD
Arflon/fan (etm) 9198 9198 9189 9200 920197839203. 6529605 9159 9201
Powerimotor (ho) 15 1S SS SS 5s 15 15
Fan speed (rem) 1140 460.1340 114034014040 a0 a4 tn40 1340
Tip speed (FUMin) 6954 6954 S954 8054 8954 S954 8954 954 NSA _—80S¢ 8054
General Unie Tress
fmrges #200 2k 222 kk
nnd Bos ob os
Retegent (yy apsins aisya0s zasjais za5/ais 225/225 25/235 2957298 415/200 ae0/200 415/815 460/460
Oll charge (gal) 33 1313 1313 1913 1919 191g 19g ALZM 2229/ 2-2U 23237
oe toa) 1983 Lana tana tena see sens sone BBM 2223 Bray 233
hinanbietstd (25S
Haamberciow (7) 00
= Bata conaining information on two cut is shown as follows: ck kt2
2 Minimum stanupfoperaing ambient beset on 83 mph wind sero the condenses
(2) Moir and masini rates appl to constant chilled wate system running at AHA condton, without reezeinhibRors added to the wate loop.
RTAC-SVXOTR-EN "General Data
Table 3. 60 Hz extra efficiency — LP
‘Size 140 4185.~«a70~«aS~=~C«ROO~S~«OS*~C«SS~SCGOO SCS
‘Compressor Screw
Quantity # 2 2 2 2 2 3 3 4 4
Nominal si (ene) 79/70 -—«88/70.«—«5/85-—«L00/@S © 00/100 70-70/85 as-asyas 770 S-BSY
‘eeone 0") 790 7 if " ” 1857070 95-88
Evaporator Flooded
Woter storage (os) 35 2 38 3 38 655 5 z 84
Min flow) (opm) -29«= 2082 a ae 304 226
Maxflow(s) (gem) 8037488380803 a258 Seams 862
n (NPS-in) 6 6 5 6 5 8 8 8 a
5 pass arrangement
Minflowis) (oom) 14613552208 228 256 288
Moxflow(a) (gpm) 536499535 53653686, 936939042
Water connection (NPS-in) 4 4 4 4 4 6 6 8 8
‘Condenser Fin and tube
Qty ofcols 4 4 4 8 8 8 6 8 ‘
Coll langth (In) 216/236 252/216 252/252 Leajaaa aaaji4s 2aK/I44 — DSD/IAA—UB/AIe 252/282
Col hetght (In) 4 2 42 2 2 42 a2 2 2
Number of rows 3 3 3 3 3 3 3 3 3
Fins per‘foot (ef) 192—ts2—92 392192 192 192 192 392
Fan Direct érve propaller
Quanity #616 716, 7786 8176 nae
Diameter (in) 30 30 30 30 30 30 20 20 30
Nirflomifan (cfm) 9199-9200» 9201.-== 97839039652 9605919990
Power/motor (hp) LS 1s 1s 15 1s 15 1s 5 1s
Fen speed (tpm) 140 aang aad nao
Tip speed (FUMin) 8954 69548954954 6954_—94 8548S 8S
‘General nit Heise
P Refrigckts 2 2 2 2 2 2 2 2 2
min ood % 1s 15 15 15 1s 15 1s 15 6
Refrigerant charge (Ib) 245/215 225/215 225/225 235/235 235/235 415/200 460/200 415/415 460/460
olcharge (Go) 13/3 19f3 19s 19H L9ns 2424922249 BABY
Minombientstd (F) «25S SS
Min ambiention (°F) ° Q ° a ° a ° °
(2) Minimum and maximum How rates apa to constant chiled water system runing at AHRE condtons, without freeze inhibitors seed athe wate
2 RTAC-SVXOIR-ENGeneral Data
Table 4. 60 Hz standard efficiency — SI
Size 140185 170185 200225 250275 300350400450 00
Compressor Sew
ctor) wean yore ssyro ssies "3s! Soy go ta0 “soo! "too “Sao” Yoousou iooae azo-120
Wiotr storage 4) 1513112722738 245 24s 2052006
pass arangement
winflow®) (Ws) 323213
Mx tonto) (Us) 5457477
osercomecion (MS-n) 4 4 6 6 6 6 6 8 8 8 8 8 8
inflow) (Ws) 8 8 9 9 9 9 9 ue a6 a7 a8
Moxtlwo) (Us) 30 3008
(Condenser Fin and tbe
caitenatn (mm) Syed Sood Sd od Saad Stee too ad Te Sed Shee Stee Ste
Fins perfoct (of) 192192 192192 192 192 192 192 192192 t82—ts2—_ tse
Fan Dect dive proselr
aunty #4 5M SIS GIS WS 718 717” 30/8 1I8_=SCMaYGSCnartatarta tat
Diameter (mm) 7260 726.0 7260 7260 7260 726.0 7260 7260 7260 7260 R60 760 7260
Airfow pefan (n/n) 16351 15959 15646 15644 15644 15646 15647 I56e4 15645 15682 15685 15646 15659
Fnseed (ps) 9 9 1 ww 1 w ww 3 1 19
General Unit Wea
Yerintad % 15 15 15 ts 15 ts ts i ts os 1 as
Retegerant gy 75/78 79/95 79/79 94/95 90/98 122 102 so6jo1 seeox 200/91 308/308 200/88 20/200
otcharge 5155587877777 777 BAIT BL SaIIi 989/99 99/99 93/99
Ninamientstd (6) 39 39 239 29 39 39 29 39 39 39 39 39-39
Min ambiension (%C) 378 478 278 478 478 478 478 478 478 478 a8 478-478
Bata conaining information on two cuts is shown as follows! ck 1 kt2
2 Minimum stanusfoperaing ambient beses on 5 mph wind eros te condenses
(2) Minirum and
RTAC-SVXOTR-ENGeneral Data
Table 5. 60 Hz high efficiency — SI
Size 340455 —470~—~4485—~'200~=325”~—=350~—=a75 300350400
Compressor Sarew
qumy # 92 2 2 2 2 2 2 3 3 « 4
Nominal sz (ons) 70/70 85/70 B5/8S 100/85 100/100 420/200 s20/s20 PES 300, 85-8 200-1007
Evaporster Food
Tas arrangement
Wintow®) 19a tte
Maxfiowo) (Ws) 4747 SST SE SLD
Vatercomecton (WE-n) 6 6 6 6 6 6 6 8 8 @ 68
3 Fas rangement
Minfowa) Ws) 8 8a
oxtow) (Ws) 3s
Wate-comedion (WSs) 4 4 4 4 4 4 @ 6 6 28 8
Condenser Fin and tbe
Qvocis # 6 ¢ 4 4 4 8 8 8 8 8 28
cailengen (mm “572/ S486/ $406) 6400/ 6400/ 2657/ 26577 SeR6/ 6400) SANG 400/
wen oe Sead Sane Glogs Ses Seay See Staal
Crithsight (om) 1067 10671067 1067 1067 10671067 1067 1067 1067 1067
hunberofrows # = 3338
Finsporfoot (pf) 192192 ——«9a—aoa_soe toes maa
Fan Diet ve proper
aunty Ff 95 Sweet akas
Diameter (mm) 762, 7274276266761
Avera (fv) 15628 15628 15628 1562915651 16619 15636 16307 1631715628 15831
Fowerimotor (WW) A212 dada LAP Daag
Fonspecd (os) 919191388
Tossed NS 455 SSS
General Unit 13H
dmfiguts # 2 2 2 2 2 2 2 2 2 2 2
Semnied % 5S SSS tsa
fig charge (i) 79/79 98/93 98/08 102/98. oa/s02 107/107 107/107 188/91 200/91. 188/188 209/209
oem «S/S «SSIS? 77 BITS eB 38/539
Minamintstd (6) 39 39 29 39 39 39 39 39 39 39 39
Minambiention (90) 378 178 178-178-478 178 ane 178-178 ane 178
"I Bata conaiing information on two crcl is show 95 flows: ck 1 ct 2
2 Minimum stancuproperaing ambian's bases on 5 mph wind seross te condenser
(2) Minimum ana maximum tow rates appWy to constant ciled water system cunning at AKRI cantons, without freeze inhbtrs added tothe water
“4
RTAC-SVXOIR-ENGeneral Data
Table 6, 60 Hz extra efficiency — SI
Size 10 455.~«470~=~«aS == ~«SOS~CaS «BOO «CSO
‘Compressor |
Quantity = 2 2 2 2 2 a a 4 4
Nominee (tons) © 70/70 «85/70 «58S aK/BS —ou/100 7a-70e5 Bs-8syes | TM EBS
Evaporator Floodea |
Water storage (353125512885 20 316
1 Pass arrangement
Minow) (Us) 14 13 “ 4 1" 2 2 Pa 2
Max flow(a) (Us) St a st st st 79 9 a9 99
Water connection (NPS-in) 6 6 5 5 6 8 @ a @
5 Pass arrangement
Minflows) (Us) 9 9 9 9 ° 1“ 1“ 16 18
Max flowia) (Us) 34 3 Es En 3 53 5 89 66
Water connection (NPS-in) 4 4 4 4 4 6 6 8 8
‘Condenser Fin and tube |
Qryorcols ‘ ‘ ‘ 8 8 8 8 6 ®
Colltength (mm) 486/548 5400/5486 6400/6400 3657/3657 4572/2743 5486/3657 6400/3657 5486/5488 6400/6400
Collhelgnt (mm) 106730671087 t067 106710671067 3067067
Number ef rows 3 3 3 3 3 3 3 3 3
Fins perfoot (fo) 192192192 19239292 192 192
Fan Direct ve propeller
Quentty #616 716 "7 916 se ays tyes ana
Diameter (mm) 762,—=-762—= 762762. 76R_—= 7626 762 762
AN porfan (mi/he) 15628 15629 1563116619 «15634 1630716317 1562815631
Powerimetor (kW) 112 ana aaa 12
Fen speed (ps) 19 19 19 19 8 8 19 19 19
Tio speed M/S 45 45 45 45 4s 45 45 45 45
‘General Unit WiC Iaee
ree cats 2 2 2 2 2 2 2 2 2
min toad % 15 15 15 6 15 15 15 15 15
Retrig charge (ka) 98/98 «102/98 102/102 107/107 107/107 s8e/91 209/91 ssB/I88 209/209
ol crarse (YS 75 "7 a v7 88/7 B87 888-8 BIBS
Min amolent-std (2¢) 3.9 59 3900-39398 39 39
Min ambienciow (°C) 1768 178 78 17S aT
Bate containing information on two drcuts is shown as flows: cht 1 t2
2, hinrmam sarcupfoperatng abe
Based ova 5 mph wind across the condenser,
(2) Minimum and maximum How rates appv to constantow chile water system running st AHRI condtons, without freeze hioters ade tthe water
Toop
RTAC-SVXOTR-ENGeneral Data
Table 7. 50 He standard efficiency — LP
Tine 1055470405900 -50—=a75 30035075 _—_—a00
Compressor Screw
achgtit! (ons) 70/70 95770 95/05 100185 100/100 7070/ SE-S/ 100. B5-85/ 100-190; 190-1007
Wterstorage oo) 292)
pas arangoment
Mexrtows) (gon) 715715748748 OB «679879 sted 29848
Motercomedion (Sin) 4 4 6 6 6 8 8 @ #8 8 8
wis fow(s) (pm) 530=«120,= «3363S aS 20 amas
Maxton(s) (gpm) 4774774505876 wma
condenser Fi ond ibe
aye # 4 © 4 «6 4 8 8 8 8 8 8
Mumborotrows #203
Qunty #44 5k SSSI aNVG SOND aaa
ronersermstor (Wp) 40 «18«8sd®st@ 88st tt
Fan speed (wm) 950950950950. ««950«950««50 «95095095
Tip specd (Wimin) 746i _746L__7464__746L_746L_—_—746L_T46L_—7a6h_—74GL_—4GL_—_ 7468
General Unie Tee
sages # 92 2 2 2 2 2 2 2 2 2 2
mining 9% 3S SSS SS Sas
Refng charge (ib) 265/165 199/351 175/78 220/383 248/305 306/298 as4242 15/200 a6s/AeS aNS/I6S S/AL5
Olehwe (oe 19/2 19nd tata Lena song MBM MARY 2993 2AY 2329) 2399)
At"Gata containing information an two circus is shown as follows: ct 1 kt 2
2 minrmum sarcupfoperating ambien based on a5 mph wind across te condenser
(2) Minimum and maximo flow rates apy
6
constant-ow chile wae sytem running a AKRLeondtion, wehout Freeze nnbtors added othe water
RTAC-SVXOIR-ENGeneral Data
Table 8. 50 Hz high efficiency — EF
prea i
size@sortz (Cons) 60/60 70/60 70/70 85/70 85/85 gs’ 199 100100 _100/100 85-85 85-85 100-100
connate (NPS-in) 4 4 6 6 6 6 6 8 8 8 8 8 8
conmeelink (NPS-in) 3.50 3.5 4 4 4 4 6 6 6 8 8 8
ccolliengtn (in) SRY MERA AN BRYA AUBY asayiaa 2eyais 252/236 252/252
wom w WY WR WY RY BY ay gy wy ay yg
Ly 13 Ly 19) Qd- ade 23-25 BhR 2325 2323)
Oil charge (oa)
v3 13 ia Ts 3 19 2ife zine “1s 2121 Fs23 2323
Minambenestd (°F) 25-2525 HS HHS
Hinembietow (fF) 9 9 9 9 0 9 0 o o 0 a ° °
‘Sata containing information on two cuts i shown a follows kt 1/2,
2 Minmmam starupfoperauing ambient based on a5 mph wind across Ue condense
(2) Minimum and maximum Now ate apply to constant-tow cited water system runing 3
RTAC-SVXOTR-EN 7General Data
Table 9. 50-He standard efficiency — SI
Size 14055 ~+4170”~«485~~—=«200~~«as0 +2275 ~«800 «380-375 400
‘Compressor Screw
Quantity 2 202 2 2 03 3 a4 4 4
scagsone (ors) 70/70 85/70 a5/05 tomas t00/100 "159! ag! soortoo esas “esas” 100-100
Evaporator Flooded
Water storage (ttt way aay ae 0520s aaa
2 pass arrangement
minnow) (Ys) 22S aaa aw
Moxtowia) (Us) 45457 Fw www
Water connection (NPS-in) 4 #6 6 6 8 8 8 8 8 8
3 pass arrangement
Minfowa) Ws) 8 8 aa aaa
Maxflow(a) (Ws) 3030 kaw 8D
Water connection (WS-in) 35 35 4 A 6 6 6 8 8 8
‘Condenser Fin and tbe
Qyotcols of 8 os 4 4 8 ® sos 8 8
3962/4572) 4572/ 5486/ 5405 3962/ 4572/5486) 4572; S486; ——5886/
Coit length (mm) agg “Ggez 452572 4B 2422743 bad 4572 ABT ‘SABE
col height (mm) 10871087 3067 10871067 10671087 106710671067 1087
Fine perfost (pf) 192 -382—«192—«192_—s2_—t9?_t9?se?t_t9R
Fan Direct drive propeller
Quontty #48 58S OSG 10/H 2/8 OND. BIO. ANID.
Diameter (mm) 762-762 762-—=«762_—=«762_—=«762_—=«HZ_—=«762_—=«782_—=«762_—=—782
Airflow per‘fan (r¥fhe) 13452 13120 12855 1285512855 13190 1285312856 12854 1285512855
Power permetar (kW) 0.74 740.7 .7h Oh... 78
Fan speed (fos) 158 158 1580 15.8 SB 1SB SBSH ISB ISS 58
Tp speed WS 38388
General Unit HECLiae
Wretrig kts 2 2 2 20 2 2 2 2 2 2 2
mined % 35 SASS
Refrg charge (Ks) 75/75 86/68 79/79 105/88 107/88 139/104 160/96 188/91 166/166 188/366 188/188
Olcharge () SIS SIS S/S S77 88/7 BIT BEB D.9/B-B 9.9/9.9
Minambient-std (C) 39 39 39 39 39 39 39 39 39 39-39
At" Gata containing information an two cuts is shown as follows: ct 1 okt 2
2 minrmum starcupfoperating ambien based on a5 mph wind across te condenser
{@)Minimum and maximum lw rates apply to constantow chile water syst runing at AHR contions, witht freeze inhibitors aed t the water
® RTAC-SVXOIR-ENGeneral Data
Table 10. 50 Hz high efficiency — S1
Se G20 130140185170 185 200250275 30038037800
Compressor saw
sizesone (ors) 60/60 70760 70/70 85/70 asres ‘35! Loy too 100300.” a5-89 85-83 100-300
Miterstoage (1) inh 127ay ase 45145 220424503066
Zpassarengement
hinfon®) (Us) «2 wow
Mewtowa) (Us) 450-450 «47-47 SLOSS 7B
cmt M5 4 6 6 6 6 6 8 8 8 8 kl
pss arengement
Hntow®) (Ws) 8 8 9 9 9 9 9 ow mw ow 7B
Mexftow) (Us) 300«30SL3k www
Water (NPS- 35 3.5 4 4 4 4 4 6 6 6 8 8 8
comein_“W)
Condenser Ta andthe
Collenatn (mm) 3263 “Sguz “anya Asya Sate Sad en00 2743 Ses? Seay Saas ase NOD,
Fins perfect (hf) 192192 192192192192 19219219292 tsetse
Fan Drea ave proper
curity # 4 54 5S 6S 66 718 77 10/6 1216 He a2 tania saya
Dameter (mm) 762 762 762 -762«-762«<7ED_«<7eR_ «TD MR 62_— THD TH_—=— 74
[eto perfan (one) 62484 68619 12839 12839 12839 s2eM0 2eM2 i2e¥e 13493 AIO 2B BEE
Tpspecd_wS 38 38 3838383838388
General Unit WiC
mined % 1S Sst
ffir charge (hg) 75/75 79/75 7879 seros soos 10 10 166/188 2097 a88y 2097 2aHy
olcrage 95 8S HS HS HS so ON ON OH BH 88 58
hin ambition (C) 178 176 178 -178 “178 “178 178 178 178-178 178 178-178
‘Sata containing information on two cuts i shown a follows ke 1/2,
2 Minimum starupfoperaing ambien based on a5 mph wind across Ue condense
(2) Minimum and maximum tow rates appv to constant-ow chile water system runing at AMR cecltions, wthout ere nbitors added the water
RTAC-SVXOTR-ENUnit Inspection
‘When unit is delivered, verify it is the correct unit and is
properly equipped.
It units covered with optional tarp, confirm unit was
ordered with a tarp. Inspect tarp for any visible damage.
I unit does not have optional tarp, compare information
on unit nameplate with ordering and submittal
information. Inspect all exterior components for visible
damage.
Report any apparent damage or material shortage to
carrier and make a “unit damage” notation on carrier's
dolivary receipt. Specify extant and type of damage found
‘and notify Trane Sales Office, Do not proceed with
installation of a damaged unit without sales office
approval.
Inspection Checklist
To protect against loss due to damage in transit, complete
this checklist upon receipt of unit.
‘+ Inspect the individual pieces of the shipment before
accepting the unit. Check for obvious damage to the
unit o packing material.
‘+ Inspect the unit for concealed damage as soon as
possible after delivery and before itis stored.
Concealed damage must be reported within 15 days.
+ Ifconcealed damage is discovered, stop unpacking the
shipment Do not remove damaged material from the
receiving location. Take photos of the damage, if
possible. The owner must provide reasonable
‘evidence that the damage did not occur after delivery.
+ Notify the carrier's terminal of the damage
immediately, by phone and by mail, Request an
immediate, joint inspection of the damage with the
cartier and the consign
Notify Trane sales representative and arrange for repait.
Do not repair unituntil damageis inspected by thecarrier's,
representative,
Storage
Extended storage of outdoor unit prior to installation
requires these precautionary measures:
‘Store the outdoor unit in a secure area
‘Atleast every three months (quarterly), check the
pressure in the refrigerant circuits to verify that the
refrigerant charge is intact. Ifit is not, contact a
qualified service organization and the appropriate
Trane sales office.
Close the discharge and liquid line isolation valves.
Installation Responsi
Generally, the contractor must do the following when
installing an RTAC unit,
es
20
‘+ Install unit on a fat foundation, level (within 1/4inch [6
mm] across the length and width of the unit), and
strong enough to support unit loading
‘+ Install unit por the instructions contained in the
Installation-Mechanical and Installation-Electrical
sections of this manual.
‘+ Install any optional sensors and make electrical
‘connections at the CH530,
‘+ Where specified, provide and install valves in water
piping upstream and downstream of evaporator water
connections to isolate evaporator for maintenance,
and to balancertrim system.
‘+ Furnish and install pressure gauges in inlot and outlet
Piping of the evaporator.
‘+ Furnish and instal a drain valve to the bottom of the
evaporator waterbox.
‘+ Supply and install a vent cock to the top of the
evaporator waterbox.
‘+ Furnish and install strainers ahead of all pumps and
automatic modulating valves, and at inlet of
evaporator,
‘© Provide and install field wiring,
‘+ Installheattape and insulate the chilled waterlines and
any other portions of the system, as required, to
prevent sweating under normal operating conditions
freezing during low ambient temperature
conditions.
‘+ Install evaporator drain plug. The plug ships in unit
control panel,
+ Start unit under supervision of a qualified service
technician,
General
Report any damage incurred during handling or
installation to the Trane sales office immediately.
RTAC-SVXOIR-ENS}$ TRANE™
Dimensions and Weights
Dimensions
See unit submittals for specific unit dimensions and water
connection locations.
Clearances
Provide enough space around the outdoor unitto allow the
installation and maintenance personnel unrestricted
Figure 5. Recommended unit clearance
Working clearance per National
Electric Code Article 110-26.
accessto all service points. Referto submittal drawings for
the unit dimensions. A minimum of 4 feet (1.2 m) is
recommended for compressor service. Provide sufficient
clearance for the opening of control panel doors. See
Figure §, p.21 through Figure 7, p. 22 for minimum
clearances. In all cases, local codes which require
additional clearances will ake precedence over these
recommendations.
A
aa earanos area
(215mm) See notes in
J
OD
~
following table.
ow
(239mm)
YDCHC
NC
| No obstructions recommended
Aree required fo unt operation,
airtow.
|
ae"
fraintnance, access panel and (1243) |
oa
Top View
Table 11, RTAC tube removal clearance
Clearance (A)
Full Tube
Base Lensth (ft) unite | Minimum | Removal Notes
to 24,30 (225 or 250T units) a a 2
ts 157 Non-contal panel end
30 exceot 225 oF 2507) 036
wm 129 3975
sows ia 6 157 | End of unit wih non-Dyraiow paral
RTAC-SVXOTR-EN
aDimensions and Weights
Figure 6. Recommended remote evaporator unit clearances — 15 to 30 foot bases
Working Clearance per National
Electric Code Arvele 110"26.
------—------4 a
I 48
I (1219)
OOO00O
OOOO0CO
No obstructions recommended. ,
| ‘rea required for unit operation, ‘3
| ‘maintenance, access panel, and
airflow.
L
(121mm)
7
|
i
|
Lf (
I
i
i
|
i
a
a
(610mm)
2
peconnendeal ee,
ay
gp -n--------
RTAC-SVXOIR-ENDimensions and Weights
Unobstructed flow of condenser air is essential to
‘maintain chiller capacity and operating efficiency. When
determining unit placement, give careful consideration to
assuring a sufficient flow of air across the condenser heat,
transfer surface. Two detrimental conditions are possible
and must be avoided if optimum performance is to be
achieved: warm air recirculation and coil starvation.
Warm air recirculation occurs when discharge air from the
condenser fansis recycled back to the condenser coilinlet.
Coil starvation occurs when free airflow to (or from) the
condenser is restricted
Both warm air recirculation and coil starvation cause
reduction in unit efficiency and capacity due to the
increased head pressures.
Dobris, trash, supplies etc. should not be allowed to
accumulate in the vicinity of the unit. Supply air movement
may draw debris into the condenser coll, locking spaces
between coll fins and causing coil starvation. Special
consideration should be given to low ambient units,
Condenser coils and fan discharge must be kept free of
snow or other obstructions to permit adequate airflow for
satisfactory unit operation,
In situations where equipment must be installed with less
clearance than recommended, such as frequently occurs
in retrofit and rooftop applications, restricted airflow is
common. The Main Processor will direct the unit to make
as much chilled water as possible given the actualinstalled
ns. Consult your Trane sales engineer for more
Note: If the outdoor unit configuration requires a
variance to the clearance dimensions, contact your
Trane Sales Office Representative. Also refer to
Trane Engineering Bulletins for application
information on RTAC chillers.
RTAC-SVXOTR-EN
2Dimensions and Weights
Weights
Non-Seismically Rated Units
Table 12, Weight — packaged units, 60 Hz, aluminum or CompleteCoat™ coils
i Seuaiiacemanias.
Table 13, Weight — packaged units, 60 He, copper cols
Seandard eleney igh Econey Tete Eidancy
"Operating woah includes retigrant and wat
2. Shing weg includes nizogen nolang charge
3 aieeghee 13%
24
RTAC-SVXOIR-ENDimensions and Weights
Table 14. Weight — packaged units, 50 Hz, aluminum or CompleteCoat™ colls
‘Standard Efficiency
High Efficiency
var shipping ‘Operating shipping operating
Table 16. Weight — packaged units, 50 Hz, copper coils
Sandra Eiioney High Eilon
com) | ts 5 ts ® ® is
3. Almonte 1-38
RTAC-SVXOTR-EN
26Dimensions and Weights
Seismically Rated Unit Weights
Table 16. Weight — seismically rated, packas
Jed units, 60 Hz, aluminum or CompleteCoat™ coils
Standard ecleney Wi Einar aa ciara
3, alwoghee 1-3
26
RTAC-SVXOIR-ENDimensions and Weights
Remote Evaporator Unit Weights
Table 17. Weights — condensing unit, 60 Hz
Bandara Efciency High Eficiency
ve shipping Operating shipping operating
cons) | ts a ts n ts ® ts
"ian 0 Cortecol™ as
1408359 ‘3792 ‘8624 ‘3912 8292 ‘3761 8624 3912
ass | 20 aye, waza | tsa ast 5
170 | soe are? aezs iz) 0st a8 sa
aso | ies sere tzizs—_ 00
Capper
seve 8 | sae
17397711200) sass
15s 76k 30252 THR
soos 7207363867438 : : :
2 Shopng went neudes houses heling cherse
Table 18. Weights — remote evaporator, 60 Hz
Flandord eiciney igh iiency
Nominal
Tonnage | Shipping Shipping Operating Operating | shipping Shipping Operating Operating
Weight (ib) Weight (kg) Weight (Ib) Weight (kg) | Weight (Ib) Weight (kg) Weight (Ib) Weight (ka)
140 2486 128 2730 1238 2528 ue? "805 ar
ass 2525 nus 2790 1266 2ss6 nse 2850 1293
170 2508 na? 2805 pr 2600 179 2920 1325
185, 2556 1159 2950 1293 207 1269 site 1413
200 2600 173 2820 1325 2846 291 3192 8
225 2707 1269 aia m3 - - -
250 2806 191 ai 48
2. Shipping weight Incudesnivogen hela charge.
3. altmegn 13%
RTAC-SVXOTR-EN 2Installation - Mechanical
Noise Considerations
Locate outdoor unit away from sound sensitive areas. If
required, install rubber vibration isolators in all water
piping and use flexible electrical conduit. Consult an
acoustical engineer for critical applications. Also refer to
‘Trane Engineering Bulletins for application information on
RTAC chills,
Foundation
Abase or foundation s not required if unit location is level
and strong enough to support unit's operating weight as
listed in "General Data,” p. 8, Table 1, p. 10 through
Table 10, p. 18. Provide rigid, non-warping mounting pads
or concrete foundation of sufficient strength and mass to
support unit operating weight (including piping, and full
operating charges of refrigerant, oll and water). Once in
place, outdoor unit must be level within 1/4 inch (6 mm}
over its length and width,
Trane Company is not responsible for equipment
problems resulting from an improperly designed or
constructed foundation.
Note: To allow for cleaning under the condensing coll, t
is recommended that an opening be left between
the unit base and the concrete pad.
Clearances
Provide enough space around the outdoor unitto allow the
installation and maintenance personnel unrestricted
accessto all service points. Referto submittal drawings for
the unit dimensions, A minimum of 4 feet (1.2 m) is,
recommended for compressor service. Provide sufficient
clearance for the opening of control panel doors. See
Figure 5,p, 21 through Figure 7, p. 22in "Dimensions and.
Weights," p. 21 forminimum clearances. In all cases, local
codes which require additional clearances will take
precedence over these recommendations.
28
Rigging
Lifting Procedure
Heavy Object!
Failure to follow instructions below could result in unit
[dropping which could result in death or serious injury,
and equipment or property-only damage.
Ensure that all the lifting equipment used is properly
rated for the weight of the unit being lifted, Each of the
[cables {chains or slings), hooks, and shackles used to
lift the unit must be capable of supporting the entire
‘weight of the unit, Lifting cables (chains or slings) may
not be of the same length. Adjust as necessary for even
unit lift
Improper Unit Lift!
Failure to properly lift unit in a LEVEL position could
result in unit dropping and possibly crushing operator/
‘technician which could result in death or serious injury,
and equipment or property-only damage.
‘Test lift unit approximately 24 inches (61 cm) to veri
proper center of gravity lift point. To avoid dropping of
unit, reposition lifting point if unit is not level.
Important: Do not fork lift unit.
See Table 19,p. 30 and Table 20, p. 31 for center of gravity
(CG) dimensions.
RTAC-SVXOIR-ENInstallation - Mechanical
Rigging
See Figure 8 through Figure 10, p. 29 for lifting point
references, and unit submittals lft point dimensions.
Figure 8. Lifting the unit (packaged and remote) — 15 to 21 foot bas
oO
Figure 9. Lifting the unit (packaged and remote) — 30 to 36 foot base
SIDE VIEW BACK VIEW
Figure 10. Lifting the unit (packaged and remote) — 39 to 45 foot base
& K ries
i
Side_View
RTAC-SVXOIR-EN 29Wd - Near side
W2 Far Side W3 - Near Side
Wa “Far Side
= a
ose
7 (625mm)
ae
SIDE VIEW “ END VIEW
Center of Gravity Table 18. Center of gravity (in), 60 Hz (continued)
Table 19. Center of gravity (in) 60 Hz (Unitsize| Packaged [Remote | Remote Evap
(ons) [XY zp x Y 2x Ye
(Unisize] Packaged [Remote —[Remoteevap) “rig [oy as as [ws as 7.25] 3830 as
(ions) [XY [KY 2x Y 2 is |o0 45 38 [os 4s 372s| 29 30 25
‘iors Calb> Standard Haney to |50 3s 32 [ee 45 372s| 39 30 25
Ww ST wa srs | tes soe ae 38 fics aa 39 | ss 30s
15 |e 4s ass | es as 3 30 25 | 200 [io 4538 [107 as 39 | 330 25
vo |os 43 ass | a5 as sos aie eis an
tos [ios a4 ass [1c 44 ss 30 25 | aso [ize a 30 [iz as ais | 53 30. 25
zoo |ioe 45 355 |107 43 sx 25, | ds fin 2 38 ne paren
bs fie as 83 [iat as eee
a50 [ioe 45 ass ii 4s ss 2 | 350 [ae se] |
ms |e 2 as|- 7 | a0 pas aa 38 |
geo iss oass|- 2 fe we jaa el... |...
a0 fas 4e 355 | = afar C= GR EET
aso [oe a ass] > 2 foe OS | ae as aS
soo jz a _ass[- | 5 toe as 38 [ice as 99 | 53 30 25
Hisar Colby tre tos as 38 [ioe as 39 [53 302s
Towa SS PBS aS S728] SOS TE EO
155106 45 35s |i0 4s 39 [5230025 aap ape ae be Tan ee aT S| SFOS
v7 106 45 355 |109 45 39 [52 30 25° | 50 [ize as 30 [ize as ars | 533025
tes ize as ass [iz 46 as) 53 3028) (ae tee
ao tm as sss|i1 as as|ss 30a | a lio a |. . |.
as ey ss ps jamin x f- 2 2 fe ee
ao i a ass) > 2 fs Se boo [20 4238
ms om aossls 5 2 fee yo jes |... fs.
boo boo 42.88 ato [saa 95 [
aoe aes] > | Copper Cols Evia ETC
a0 ra a3 | poo eee
Aorinan Cals ay ts jase ef... |. se
We SP ve fuss fo 2 ffl lt
tse we oass;- [te tes [im 3338
mous asf 2 ffl lt no |e ss |... [2 2 |
wes i ws asf 2 ffl lt 30 paar aa 38 |
zor as_sss| + | bs [a a2 38
So aos as geo joe a asf 2 fee
bs me 42358 See ee
Topper Cals - Standare EFcancy
30 RTAC-SVXOIR-ENInstallation - Mechanical
Table 20. Center of gravity (in), packaged units, 50 Hz
Unit Size | Standard Efficiency | High Efficiency
(tons) [| XYZ ¥
aa
130 - = | eas 85
ass | a8 44355 | 0544358
17 | a9 4535.5 | 106 45355
15) 10645555 aaa
aso | 182 41388 177,88
27s | 172 41555 20255
al
375 | 729° 4835.5 265 aa 85
‘Ceppar Calls
en
wo | 90 45 38 | 904538
ass | 90 4838 | 084g 38
[38s [0s as
200 | 18 458 | 125s
as | an 428 2008
goo | 97428 | 22038
350) 235 ae Sa
400 | 235 ae 38278
Isolation and Sound Emission
‘The most effective form of isolation is to locate the unit
away from any sound sensitive area, Structurally
Figure 12. RTAC elastomeric isolator
Hr
per
RTAC-SVXOTR-EN
transmitted sound can be reduced by elastomeric
Vibration eliminators. Spring isolators are not
recommended for nor-seismically rated applications,
Consult an acoustical engineer in critical sound
applications.
For maximum isolation effect, isolate water lines and
electrical conduit, Wall sleeves and rubberisolated piping
hangers can be used to reduce the sound transmitted
‘through water piping, To reduce the sound transmitted
‘through electrical conduit, use flexible electrical conduit.
State and local codes on sound emissions should always
be considered, Since the environment in which a sound
source is located affects sound pressure, unit placement
‘must be carefully evaluated, Sound powerlevelsfor Trane
air-cooled Series R® chillers are available on request.
Mounting and Leveling
For additional reduction of sound and vibration, install the
optional elastomeric isolators, seismic isolation pads or
seismic spring isolators. See “Unit Isolation,” p. 31 for
details,
Construct an isolated concrete pad for the unit or provide
concrete footings at the unit mounting points. Mount the
unit directly to the conerete pads or footings.
Level the unit using the base rail as a reference, The unit
must be level within 1/4-in (6 mm) over the entire length
and width. Use shims as necessary to level the unit
Unit Isolation
Elastomeric Isolators
(Optional for units without seismic rating)
See Figure 12 and Table 21 for description of elastomeric
isolators (model number digit 33 = R or G).
aInstallation - Mechanical
Table 21. RTAC elastomeric isolator details
Max Load Each Maximum
ext (bs) Color Deflection (in) A
62 2250 RED
oso 3.00
3 3000 ‘GREEN
a 4000 GRAY
‘See “Elastomericlsolator Mounting Units without Seismic
Rating,” p. 34 for isolator selection, placement and point
weights,
1. Secure the isolators to the mounting surface using the
‘mounting slots in the isolator base plate. Do not fully
tighten the isolator mounting bolts at this time.
Important: For proper operation, isolator must be
oriented as shown in Figure 12. Mounting
holes must be to the outside, and under the
unit,
2. Align the mounting holes in the base of the unit with
the threaded positioning pins on the top of the
isolators.
3, Lower the unit onto the isolators and secure the
isolator to the unit with a nut,
4. Level the unit carefully. Fully tighten the isolator
‘mounting bolts.
Unit Isolation for Seismically Rated Units
Seismic Elastomeric Isolation Pads
Elastomeric pads are provided with an isolation washer
‘and 3/4 inch free hole in the center of the plate. Isolation
pads are shipped inside the unit control panel. See
Table 22 for pad specifications.
‘Table 22. Seismically rated elastomeric isolation pad
Dimension (in)
Max toad | Length Width
2520 6 6
Modet
B36
Hetght
0.625
See Table 23 for quantity of isolation pads required and,
‘Seismic Isolator Mounting,” p. 41 or unit submittal for
isolator placement dimensional information.
‘Table 23. Seismic elastomeric isolation pad quantities
Unit Size (tons) | _std High Extra
120
130 .
140 5 8 8
155 8 8 10
170) @ 8 1
18s a 10 10
200 6 10 10
2
Bc > ew Lm Ww Type
oso | san | a6 | 038 | 275 | 625 | *S0*) 463] ors
Table 23. Seismic elastomeric isolation pad quantities
Efficiency
Unit Size (tons) | std High extra
225 10 10 z
250 10 10 2
300 2 2 2
350 2 2 4
275 z
“400 2 ro 5
500 1“ : :
Set isolation pads on mounting surface, ensuring that all
isolator centerlines match the submittal drawing
Place uniton pads, and secure as shown in Figure 1Susing
provided isolation washer and additional hardware
obtained locally.
Figure 13. Seismic isolation pad — installed'*!
ace ssn Unt ase Rt
ye
Ee ocad —
Netto sate
‘+ With the exception of the isolation washer, hardwareis,
not included.
* Recommended use of Grade & hardware
+ Units have a tapered base rail that requires 2 tapered
washer
‘+ Support structure may vary
‘= IFjob site has an beam or C-channel, a fender
washer and grade 8 washer should be installed
under the support structure,Replace Isolation Pads and Hardware
after Seismic Event!
If unit experiences a seismic event, isolation pads and
hardware must be replaced. Failure to replace isolation
pads and hardware would compromise the installation
{and could result in equipment damage during future
‘seismic events,
Seismic Spring Isolators
See “Seismic Isolator Mounting,” p. 41 for mounting
locations, isolator selection and point weights.
Seismically ratedisolators are optional foriBC and OSHPD.
seismically rated units
Isolators are identified by partnumber and color as shown
in Table 24, For dimensions, see Figure 14,
Table 24, RTAC seismically rated isolator
Rated Rated Spring
Load Deflection Rate
bs) (lbs/in) Color Code
Installation - Mechanical
Figure 14. MSSH seismically rated isolator
White/Ok Porple
White/Dk Green
(MSSH-IE-2575N 2575 1a Ere)
(MSSH-16-2990N 2990 1.31 2682
RTAC-SVXOTR-EN
Install the optional seismically rated isolators at each
‘mounting location specified in section “Seismic Isolator
Mounting,” p. 41, See Figure 15forcorrectorientation, and
Figure 16 for installation reference
Figure 15. Seismic isolator installation orientation
waa ay
|
3Installation - Mechanical
Figure 16. MSSH seismic isolator installation reference
p/p cusrowen
re pee
re
AS
i
é ¢
ce
1. Set isolators on mounting surface, ensuring that all
igolator centerlines match the submittal drawing. All
isolator base plates (B) must be installed on a level
surface. Shim orgroutas required, levelingallisolat(or
base plates at the same elevation
2. Anchor all isolators to the surface using thru holes (C)
for concrete or {0} for steel as require. Welding to stee!
is permitted providing the weld achiaves the requir
strength.
3. Remove clamp down nut (H} and washer (I). Isolators
are shipped with (2) removable spacer shims (E)
between the top plate and the housing,
Important:
These shims MUST be in place when the
‘equipment is positioned over the isolators.
4. With all shims (E) in place, place the equipment onto
the top plate (A) of the isolators,
4
5. Bolt equipment securely to the isolators using washer
(i) and nut (HY
Important: The following adjustment process can only
begin after the equipment or machine is at
its full operating weight
6. Back off each of the (2) or (4) limit stop locknuts (F} per
isolator 1/4 to 378 inch,
7. Adjust each isolator in sequence by turning adjusting
rnut{s} (G) one full clockwise turn at atime, Repeat this
procedure on allisolators, one ata time. check thellimit
stop locknuts (F) periodically to ensure that clearance
between the washer and rubber grommet is
maintained. Stop adjustment of an isolator only when
the top plate (A) has risen just above the shim (E).
Remove all spacer shims (E)
9. Fine adjust isolators to level equipment.
10. Adjust limit stop locknuts (F) per isolator to obtain 3/
Binch gap. the limit stop nuts must be kept at this 3/8
inch gap to ensure uniform bolt loading during uplift.
Isolator Selection and Mounting Locations
Elastomeric Isolator Mounting
Units without Seismic Rating
Figure 17. Mounting locations (without seismic rating)
RTAC-SVXOIR-ENTable 25. Mounting locations — 60 Hz units without
Table 26. Mounting locations — 50 Hz units without
seismic rating seismic rating
size Dimension (in) Size Dimension (in)
(tons) 8 c . E (tons) A 8 c > e
Standard Eficieney ‘Standard eiioney
140 3 33 B > a0 sas a6 3 3
155 46 3 3 : 1555134, 53 33 -
170 “ 3 3 : wo 5a3 48 33 33 -
tes ts ae % : ses 5.0848 76 76 -
= = = = = ‘Seandord Efiiency
ane 2 ° a a 350 1870S 0 0 7%
ae Se S a 27s 187078 90 90 7s
aie * 3 oe 30018707 90 300140
= a 2 ie 37818703908 oe
30 fe “ 3501870038303 oe
400187038308 578
450 er 27 High Efceney
500 mea moe = = -
High EFiiency 13051346, 33 33 -
wos 3 3 - uo 151348, 33 33 -
7051348 76 % : wo sas 48 76 76 -
200 15.139 6 6 64 200 151339 69 6 68
2s 155956 95 7 105 20155976 90 0 7s
250155956 9s 18 10s as ss 90 200140
251870 30 woo 340 30018707 SCC
300 7 nos 15 350 1870 © 139103 oy 8
350 187003903 128 a7 18700 Baa
4003870 27a? 27 27 400187078772?
Eira etiieney
155 29 6 6 6
3085 86 9s 8 10s
200 56 95 % 105
250 n 90 soo aa
275 97 mo 25s
350 18,70 12812727
RTAC-SVXOTR-EN
38Elastomeric Isolator Selection
‘Table 27. Elastomerie
olator selections, packaged units, 60 Hz
size Tocation
(tons) 2 2 3 4 5 6 7 @ 2 10
370 -Rec62 —Red62—«RaGG2_©—«RedG2_-—«RUGST «RGGI «Red? RAD . -
485 Ras62 —-Red62—«RaGG2_—«RedE2 «RUG ST_—«—ReGZ «Red? —=RA GD . -
200 _-Rac62_—_—Red62__—Rad 62 _—RedE2_—«REG ST —RaGG2Z_—RedGZ_—_—RA GD : -
225 Rad62 Red 62 Rad 62 RedG2 Red 62 _RadG2 Red G2 __ReaG2 Rede? Wea GE
250 -Rad62 —RedG2_—«RadG_—«RESG2Z_—«RECGZ_—«RAGGZ_ «Red? —«RACGD_-—«—RESGZ_—REE EZ
275 Grave GrayS4# Gray64Gay6# Gray 64 Gray Gay St © Gray64.Grayé4# Gray 64
300 Gray GrayS4 —Gray64Gray# Gray 6 © Gray Gay G# © Gray64Gray4 Gray 64
350 © Gray64 GrayS4# Gray64Gray6# Gray 64 Gray6¢ Gay 6# © Gray64Gray# Gray 64
400 Gray GrayS4# —Gray64 Gray 64 Gray 64 Gray 64 Gray 6# Gray 64. Gray 64 Gray 64
450 Gay Gray64 Gray64 Gray64Gray64 Gray 64 Gry64 Gray64 — Gray.64 Gray 64
500 Gray64__Gray64 _Gray64 Gray 64 Gray 64 Gray Gray6# _Gray64 Gray 6¢__Gray 64
High Efienay
370 -Rac62 —Red62—«RaG 62 ©—«RedG2_—«RAGST © ReCG2 «Red? RAD . -
15 Red62 —-Red62_—«RaGSD_©—«—REdEZ_—«RESZ «RAGED —«REdEZ_-—«RAGD_©—«—REEZD_—REGAT
200 © Rad62 ——Red62—«RaGG_©—«REdG2 «REGS? «RAGE _—RedG?_—«RACSD_~—RESE? —REE ST
225 -Rad62 ——Red62—«RaGGD_—REdG2Z_—«RECSZ «RAGED —RedGZ_—«RACHD_—«—RESGZ —REE ST
250 -Rad62 —-Red62—«RadG2_—«REdGZ «REG? —«RAGGZ «Red? —«RACSD_-—REAGZ —REEGI
275 Grave GryS4# Gray64Grayé# Gray 64 Gray Gays! Gray64Gryé4# Gray 64
High evcieney
300 Gray Gray64 Gray 64 GrayG4 Gray 64 Gray Gt Gay! Gray 64 Gray# Gray 64
350 Gray Gray 64 Gray64Gray6# Gray 64 Gray6¢Gray6# © Gray64 Gray 64 Gray 64
400 Gray64__Gray64__Gray64 __Gray64__Gray64 Gray 64 Gry64 _Gray64__Gray64 Gray 64
Extra Efficiency
200 _-Red62 Red 62 _—RAGSD_—RedG2_—REK? _—RAGEIZ_—RedE?_—=RACSD_~—ReE?_—REG ST
250 Grayei Gaysi Gray6i_Gayéi Gaye? Gray6t Gays! Gray6i_ Gaye! Gray 6@
275 Graves Grayst# Gray61 Gaye Gry6t © Grey6i Gayst Grays Gryet Gray sa
300 Grays Grays# —Gray6sGrayet © Gry64 Grays Gays? © Gray64 Grayes Gray 6a
350 Grays Grys4 Grays Gayét Gray 64 Gray Gays? Grays Grayé4 Gray 64
36 RTAC-SVXOIR-EN‘Table 28. Elastomeric isolator selections, packaged units, 50 Hz
‘Size Tocation
(tons) 3 2 3 4 5 6 7 8 9 10
‘andora Eficenay
a0 Rad62 Red 2 RadG2 Red G2 Reg G2 RadG] Red? fed 2
ASS -Rad62—RedS2—«ReG2_—RedG2_—«ReGZ —«RAUGD_©—REGGZ_—Red GZ
170 -ResG2—RedG2—«ReGGZ_—REdG2Z —«REGGZ —«REHGD_—REGG? —Re GP
185 Rev 62 Red62_—«REGGZ_—REdG2_—«REGGZ —«REHGD_—«—REGG2_—REU GZ.
200 _-Rev62__Rod62_—_—ReG6Z_—_—~RedG2_—_—REGHZ _—~RedGZ__—~REGZ_—REU GZ -
250 Gray 6 Gray64 Gray 6—
-
a eT ToD
200 4971552792538 a 1496714663894
22s 6611686692674) a6s4 ass asa]?
goo 21472392 120-«=2391 0872357089219 0142288
350 26472629535, 2517452249852 23802284 2300,
400 274s 2705277) 2mao 2797 ash 8222778 kas 2802
‘Auminum Cais - Extra Eflelency
17014971552 14783539 1445461817165 1389 1480
18516611686 2649642629654 8139S 17
200 6612686 = 6926746292658 s? sas 67
300 26472628535. 25174522438 2512200228230
350274 270527792728 2797 2788 28222778 28s 2802
(Copper Cals - Standard Efficiency
wo i658 —~«S~*SSSCT SCS? SCBSCT
200 20422210802 203822920068 2810, : :
38 RTAC-SVXOIR-ENTable 30. Point weights (Ibs), packaged units, 60 Hz, units not seismically rated (continued)
Teolator Location
size
(tons) wa. we ws ws we w7 we ws wi
300 255027872888 25e7 27842585 78225432798
35024672708. zest 28882765 «300329453263
40378398872, 3272 oy, 3207s 30822077
wo i658 ~«20”S~*~«SS*~«T SCG SSSCABSSSCT : :
3551956. 2029958 2022949201298 2008
370 19652040958 20359492098 299920 : -
225 20772252090 2135 tS 2s? 2866 21372185,
2502077225090 2135 tS? tt 256621972885,
27s ~~) ~«éSS*«éSS*«iO]SC*~«SS*«e~S~*«éSTSC*«SCS*«tMSCS*«
a0 282s 3097 2768 «3087690202608 287G 8282798,
Copper Gals - Extra Eceney
i0~*i965”~« ~*~ S]S~*«OS=SC«R]S~SC0~S~SC«NONSSC
ass 17egaa792 ag = 2796951280092 1801028
170168928 na6S 938s] 932 nes] nes3 928
2002077225090 2155 tosis? 216521372185,
250 ~«e10~*~«S SPS*S*~«RSHS*~«STOOSC*~«SS*«BTCSC*«ék ST SS*«SCS*«tIDSC*«OD
275 —282s3097 2766 © «3037602962608. 2876 «8262798,
a0 3377357281 3at 439-3078 tas ase Om 2M
RTAC-SVXOTR-EN
9Table 31. Point weights (Ibs), packaged units, 50 Hz
we Teolator Location
(tons) wa we ws wa ws we w7 ws wo wio
‘Numinum Cis - Slandara Fifer
m0 aaz as :
rss 346257, ae 2435 22g aL 389 1386, : -
170 t40z_—= 1503, taea nag) tastes a 1885, : :
185 16781793686 26991586685 5321586, : :
2001674 7422662736 seed t678 sao 3604 . :
275 2092353973 2266. «1870 «22017872062 16831986
au0 196 ude ze ©1998 296 2029266 = 20802334
"5095399529245 24212682349 3002501 22302300
3752437238541 20d 2518206782562 51126202568
4002748 27582667 2686 = 584 2s6e = 259251082822
‘Aluminum Cols - High EMiceney
12a aso sas a0 sera - -
1301402450383 2430 13610833379, . :
vo 1402, aso. 383 24301361329 1387, : -
155 1657686172627 158557511537, : :
1701597712629 ——t68e 1585 16855811596, : -
wes i468 5524551539 1aa@_tsa2 a7) i389 3472
0015211571 t503 ass a2 522 tas aaa 873
250 1926 «= 21870882685 183321001785 «= 206320002015
275 1907729732209 20222273293 2a 93d
300284727 22023912087 287mg 2819 onda
3503392 3035722470355] —as38 2695 25a 3537 3780
37527558738 2698 = 27252678 26056582574 2637
4002744 gas 27732292797 ase 2822277982802.
Copper Coils - Standard Eeiency
ieee aS aS a :
iss 4778s? aa? ame : -
7777372798 1765 127893. - -
1952082217103 20s? 2020 === 203820062090, : :
2002056 —~—~«~«SSSSCSC*GS~C~COSSSSCTSSSCS : -
250 207823322088 1658218238524 243170287
275-2638 «25335282805. 2358 26532215501 2079 2388
goo 246278 287727322495 278k 8578225432798
350 gis8 313730393018 29512598358 287378 2779
375-3575 3579212553083 29482982912 2589 2590
40035983498 3372 338032723207 —=—a0? anes 0822077
‘Coppar Coll - standard Eelency
1206s es asa a = =
1301658720678. a737, 169575777. - -
mo 1ss8 7206787876957 a7. : :
1552025 2000«= 20122035 200870332007, 2038 - -
1702025 210030342098 20202038 = am6 2090, - -
vas 18291954 iee2._1948 tase 1920 1859 195@ 1857 961
200° © 188119611880 1960 18871957 18851956 883983
250 7506 2767, 2882138 = 732125882278 = ust 2170247
275 aea8——a40 2529 2aos se 283326292720 2072
‘30028253097 —-3786 3037 2690-2962 9605 2ae S28 CTH
350 3000-2934 saa 3118-3281 aats a9 36236283582
3753576 3579243309376 1782793042086
400 444s a3 3816 3675878382658 3509 628
40 RTAC-SVXOIR-ENTable 32. Point weights (Ibs), condensing units, 60 Hz
Teolator Location
Size (tons) 2 3 4 5 6 7 8 2 10
‘Aluminum Cols - Standard EMicency
170 n150 «1183109513280 1065 968002 -
185 soe 3843925 tm azdt zd 156 62 -
200 s397 4378392279 HB 1206 3286
235 sl aoy~—CwaSSSC*SC«SSCGSSCDSC«OBSSC
‘ominum Cais -Righ Eiaeney
740 yiso tes —~—«aOSS—~«TGS~«SO~«NOGGSSC~«DSSC~«
455 rai a6t 27030290 230209 a4
170 rat asta a90 323009 aa
‘Copper Coll~ Standerd Efilency
340 ios Cias4SCaSBBSCHSSS SSeS C8 -
155 14061454 3881435366 date 3451392
470 s406 «4543881435368 ats 34S 302
250 36a 170236331690 161s 3668 159165711628
‘Copper Cols - High Efcency
140 ie ~=~WSaS~SC*SBSSCSSSCGSCad CSCO
185 154616571537 16495231638 150961495607
200 16221686 16081666 1587 1682 _—tS68~—s62i——is49 599
Seismic Isolator Mounting
Figure 18. Mounting locations — seismic spring isolators or seismic elastomeric pads
A 5 ope Fug
ae
5g
° ° ° ° ° ° ow
RTAC-SVXOTR-EN aTable 33. Mounting locations — 60Hzunits with seismic Table 34. ‘Mounting locations — 50 Hz units with seismic
rating rating
Size Dimension (in) size Dimension (in)
(tons) AB CDE OF OG tons) ABE
‘Slanaard eiioney ‘Standard Eiioney
Cas ase ts
20 1739 2s 7% DDH
2s 7 8 TS 30017 60.25 80.25 80.25 80.25 s025 -
300 1780.25 60.25 80.25 e025 e025 - | [a7 7 875 7S O75 875 87S -
35017-8025 80.25 80.25 80.25 80.25 350 17S 87S 7S BFS ATS
400 17 «7S «875 «BTS 87S BTS 40017 875 875 7S 87S ATS
45017495 85,85 8495 85,05 92.75 70 High Feeney
500 17 84,85 86.85 84.05 96.85 9275 78 mo 4%
igh Fficleney 0017433
2507 88S SS 20 7% 90S
27517 _-80.25 0.25 80.25 80.25 80.25 [300 a7 ars 87s 7S aS 7s
(soi? 7s ars 875 a7s 75 - | | 350 7 875 aS e75 O75 OS -
350 1787.5 87S 87.5 BS 87S 37517 AAS 88.85 86.05 8485 92.75 78
4001745 08.05 40S 86.05 92.75 78 40017 40S 86.85 8405 8405 9279 78
Batra Eiceney
wo 7H
ws 173868 ww
a RTAC-SVXOIR-ENSeismic Spring Isolator Selection
Table 35. Seismic spring isolator selections (MSSH-1E-200x)
‘Size Location
(ons) 228k tt
‘Standard Eaaney
ass 2000 2000 2000 ©2000 2000-2000 «2000 «2000 = -
470 2000 2000 2000 © 2000 2000 2000-2000 2000
185 2575N 25/5N 257SN 257SN 2575N 257SN 257SN 257SN
200 2S75N 2575N_2575N 257SN_2575N_2575N 2S75N_2575N ~~ ee
22s 2000 2000 2000 2000 2000-2000 2000 2000 2000-2000. ~SS S
250. 2575N 257SN 2575N 2575N 2575N 2575N 2575 2575N 2575N 2575N
275 2990N 2990" 2990N 2990N 2575N 2575N 2575N 2575N 2575N 2575N — - - oe
300 2590N 2990N 2990N 2990N 2575N 2575N 2575N 2575N 2000 2000 2000 2000 =
350 _2990N _2990N_2990N _2990N _2575N_2575N_2575N__2575N_2575N_2575N 20002000 ~~
High efcenay
485 2000 2000 2000 2000 ©2000 2000-2000 «2000 Ss
385 2000 2000 ©2000 2000 2000 2000-2000 © «2000/2000 2000
200 2000 2000 2000 20002000 2000 +2000 20002000 2000
225 2S75N2575N2575N 2573N —7576N—2575N 2000 — 2000 2000 2000
250. 2575N 257SN 2575N 257SN 2575N 2575N 2000 2000 2000 2000
275 2990N 2990N 2990N 2990N 2575N 2575N 2575 2575N 2000 2000 2000 2000 =
300. 2575N 2575N 2575N 2575N 2575N 2575N 2575 2575N 2575N 2575N 2575N 2575N ~~
350 _2950N_2990N 2590N _2950N__2990N 2980N _2590N _2890N 2950N _2950N_2590N 2990N-
485 2575N 257SN 2575N 2575N 257SN 257SN 2000 2000 2000 2000 -
"250 2990N 2090N 2990N 2990N —2575N2575N 257SN —2575N 2000 2000 2000 2000
275 2S7SN 257SN 257SN 257SN 2575N 257SN 257SN 2575N 2575N 2S7SN 2575N 2575N =
300 2990N 2990N 2990N 2990N 2990N 2990N 2990N 2990N 2990N 2990N 2990N 2990N
350 _2990N 2990N 2990N 2990N _2990N 2990N _2990N _2990N 2950N _2990N _2990N 2990N_2990N _2990N
RTAC-SVXOTR-EN 4Point Weights (Units with Seismic Rating)
Table 36. Point weights (Ibs), seismically rated units
Size Tsolator Location
(tons) Wi W2 WS WS WS WS? WS WWW W123 WA
vandard Efilancy
1534 1523 14521502 16291478
yao 17571022, -1720«1642_ 166318988
175g 162017281786 sae aan_as39 697
275-2360 «225022517140 «-7322«2011«1993« 188218851778
3002387 2287 2220«-2120«2008-«1909«1772«1673«1607 «1508 t4e2 132
3502357 2254 2224 2122-2058 1954 1871-1768 37A1_—:1638 16111507
40023222410 —2380 2368 ~—~2039~—~a327 ~—~197 2286 21S 205 —-aNIS BOBS
‘Aluminum Cote High Etiioney
a0 aa7i isms asada aS aS SSSCSCSCSCSCSCSCSS
3551667 173016431689 1580 1636 3528 1582
225 I70i—-ise6~—<3683 3628 —<16S2 «1796 ~«NeA? ats SSCS
250 1702 1886 ©3683-1828 365217963627 «377235921737
275 229321932183 2084 1976 3877 3780 3680 3642 1543 1504 3406
‘Auminurn Cols = Extra Eficiency
yao i736 — wit
erate
Proper flow switch indexing
F pressure drop, 2-pass evaporator, 120 to 250 tons.
100
+ son: 1408, 1558
1408, 1955,
1308
“sor: 1708, 1855,
Sov: 1708, 1858,
Pressure Drop (ft H,0)
100 200 300
400500 8001000
Flow Rate (GPM)
RTAC-SVXOTR-EN
47